800023-008 DIOM Manual, DLP HFC-227ea, LPCB
800023-008 DIOM Manual, DLP HFC-227ea, LPCB
800023-008 DIOM Manual, DLP HFC-227ea, LPCB
800023-008 07/20/2020
TABLE OF CONTENTS
SECTION NO. DESCRIPTION PAGE#
FOREWORD .....................................................................................................................................4
General 4
Warnings ...................................................................................................................................4
Safety Precautions ........................................................................................................................5
1 GENERAL INFORMATION ..............................................................................................................6
Introduction .....................................................................................................................6
HFC-227ea Clean Agent ........................................................................................................6
1.2.1 Cleanliness ................................................................................................................6
1.2.2 Thermal Decomposition Products .......................................................................................6
1.2.3 Agent Properties ..........................................................................................................6
2 SYSTEM DESCRIPTION ................................................................................................................7
General ..........................................................................................................................7
Component Descriptions ......................................................................................................7
2.2.1 Cylinder/Valve Assemblies ...............................................................................................8
2.2.2 Firetrace Detection Tubing ...............................................................................................8
2.2.3 Firetrace Tubing Cutter ...................................................................................................8
2.2.4 Filling Adapter .............................................................................................................8
2.2.5 Pressure Supervisory Switch ............................................................................................9
2.2.6 Pressure Operated Switch ................................................................................................9
2.2.7 EU Pressure Operated Switch ............................................................................................9
3 SYSTEM DESIGN AND LIMITATIONS ............................................................................................... 10
General ........................................................................................................................ 10
Specifications ................................................................................................................. 10
3.2.1 Storage and Operating Temperature Range .......................................................................... 10
3.2.2 System Operating Pressure ............................................................................................ 10
Design Procedure ............................................................................................................ 11
Minimum Design Concentrations ........................................................................................... 12
System Limitations ........................................................................................................... 12
3.5.1 Enclosure Size ........................................................................................................... 12
3.5.2 Ventilation and Unclosable Openings ................................................................................. 13
3.5.3 Fire Detection Tubing Limitations ..................................................................................... 13
4 INSTALLATION INSTRUCTIONS..................................................................................................... 15
Extinguisher Unit Installation ................................................................................................ 15
Component Installation ...................................................................................................... 15
4.2.1 Firetrace Detection Tubing ............................................................................................. 16
4.2.2 Slip-On Fittings .......................................................................................................... 16
4.2.3 End of Line Accessories ................................................................................................ 16
System Activation ............................................................................................................ 17
5 SERVICE AND MAINTENANCE INSTRUCTIONS ................................................................................... 18
General ........................................................................................................................ 18
Periodic Service and Maintenance Procedures ............................................................................ 18
5.2.1 Monthly Inspection ...................................................................................................... 18
5.2.2 Semi-Annual Inspection ................................................................................................ 18
5.2.3 Cylinder Maintenance ................................................................................................... 19
6 SYSTEM DEPRESSURIZATION AND CHARGING .................................................................................. 20
Depressurizing the Unit ...................................................................................................... 20
System Recharge ............................................................................................................. 20
WARRANTY ................................................................................................................................... 21
APPENDIX A................................................................................................................................... 23
System Parts List: DOT System ........................................................................................................ 24
System Parts List: CE System ......................................................................................................... 25
Detection Line Parts List ............................................................................................................... 26
APPENDIX B................................................................................................................................... 27
Tamper Proof Instruction ............................................................................................................... 28
2
800023-008 07/20/2020
Firetrace Detection Tubing Compatibility ............................................................................................. 29
APPENDIX C................................................................................................................................... 30
Safety Data Sheet: HFC-227ea ......................................................................................................... 31
Safety Data Sheet: Nitrogen ............................................................................................................ 42
3
800023-008 07/20/2020
FOREWORD
General
This manual is written for authorized fire protection professionals that install and maintain Firetrace Pre-Engineered Automatic Direct Clean
Agent Extinguisher Units with HFC-227ea Clean Agent.
Firetrace Pre-Engineered Automatic Direct Clean Agent Extinguisher Units with HFC-227ea are to be installed, inspected, tested, maintained,
and recharged by qualified trained personnel in accordance with the following:
• All instructions, limitations, etc. contained in this manual P/N 800023
• All information contained on the agent cylinder nameplate(s)
• Applicable parts of NFPA 2001, Standard on Clean Agent Fire Extinguishing Systems
• Local authority having jurisdiction
Warnings
Safety precautions are essential when any electrical or mechanical equipment is involved. These precautions should be followed when handling,
servicing, and recharging Firetrace Pre-Engineered Automatic Direct Clean Agent Extinguisher Units and equipment. If safety precautions are
overlooked or ignored, personal injury or property damage may occur.
WARNING
Pressurized (charged) cylinders are extremely hazardous and if not handled properly are capable of causing property damage,
bodily injury, or death. Always wear safety glasses and the correct PPE before unit installation, servicing, or other general
handling.
The following symbols are used throughout this manual. Always heed these precautions. They are essential to the safe use of the equipment
described in this manual.
DANGER:
This danger symbol identifies immediate hazards and provides specific instructions or procedures, which if not correctly
followed WILL result in severe personal injury or death.
WARNING:
This warning symbol identifies specific instructions or procedures, which if not correctly followed, COULD result in severe
personal injury or death.
CAUTION:
This caution symbol identifies specific instructions or procedures, which if not correctly followed, COULD result in minor personal
injury or equipment or property damage.
4
800023-008 07/20/2020
WARNING
Pressurized (charged) cylinders are extremely hazardous and if not handled properly are capable of causing property damage,
bodily injury, or death. Always wear safety glasses and the correct PPE before unit installation, servicing, or other general
handling.
Safety Precautions
The following safety precautions should always be followed:
1. Read and understand this manual and the other documents referenced herein.
2. Wear safety glasses when working with pressurized cylinders and charging equipment. It is recommended to wear leather gloves to
avoid any cryogenic burns.
3. Make sure that the ball valve (installed to the top of the cylinder valve) is closed (lever is in “OFF” position) and the detection tubing
has been removed from the cylinder valve before removing the cylinder from installation and before performing any charging, leak
tests, or salvage operations.
4. Follow all the safety procedures included on the cylinder nameplate and in this manual.
5. Never assume that a cylinder is empty. Treat all cylinders as if they are fully charged.
Local authorities having jurisdiction should be consulted as to the acceptability for particular hazards and requirements covering installation .
Any questions concerning the information contained in this manual should be addressed to:
www.firetrace.com
5
800023-008 07/20/2020
1 GENERAL INFORMATION
Introduction
The Firetrace Pre-Engineered Automatic Direct Clean Agent Extinguisher Units with HFC-227ea are designed to be used in a Local Application
manner providing the system is designed within the limitations outlined in the manual.
The pre-engineered concept minimizes the amount of engineering involved in system design. When the enclosure meets the specifications
outlined in this manual and the Firetrace detection tubing is installed within the limitations stated in this manual, no hydraulic calculations are
required to determine pressure drop, agent flow, or discharge time.
The hazard being protected by the Firetrace system can be any size, shape, or volume; provided that it is reasonably sealed and the hazard
being protected is within the limitations described in this manual. Each extinguisher unit, when installed, is a self-contained unit, meaning that it
is equipped with all the components necessary to detect and extinguish Class A, B, and C (Class E for Europe) fires.
Each installed Firetrace pre-engineered extinguisher unit is used in tandem with its own pneumatic Firetrace Detection Tubing (FDT).
Upon direct flame impingement of the FDT, the tubing will rupture forming a burst hole. This burst hole will act as a nozzle directly applying the
agent onto the flame source, extinguishing the fire and flooding the enclosure to prevent re-flash.
Since the units are listed as automatic units (e.g. no simultaneous manual or electric actuation means is provided), only one (1) extinguisher
unit can be used to protect one (1) hazard. These extinguisher units cannot be combined to protect a larger size hazard, since they are not
designed to provide for simultaneous actuation of two (2) or more units.
Local authorities having jurisdiction should be consulted as to the acceptability for particular hazards and requirements covering installation.
HFC-227ea is a chlorofluorocarbon depicted by the chemical formula CF3CHFCF3 (1,1,1,2,3,3,3-heptafluoropropane). HFC-227ea is a colorless
low odor gas, low in toxicity, electrically non-conductive, which leaves no residue, and is an extremely effective fire suppression agent.
HFC-227ea is included in NFPA 2001 and has been evaluated and approved for use in occupied areas as a Total Flooding agent when used as
specified under the U.S. Environmental Protection Agency (EPA) SNAP Program rules. Refer to the SNAP Program rules for more information.
1.2.1 Cleanliness
HFC-227ea is clean and leaves no residue, thereby minimizing post discharge clean-up, keeping expensive downtime to a minimum.
Most common materials, such as steel, aluminium, stainless steel, brass, plastics, rubber, and electronic components, are not affected by
exposure to HFC-227ea. The agent is also environmentally friendly, having an ozone depletion potential (ODP) of 0.00.
6
800023-008 07/20/2020
2 SYSTEM DESCRIPTION
General
The Firetrace Pre-Engineered Automatic Direct HFC-227ea Clean Agent Extinguisher Units are available in multiple sizes:
920301 / 898004 Charged with 3 lb / 1 kg of HFC-227ea
920601 / 898005 Charged with 6 lb / 2 kg of HFC-227ea
921201 / 898006 Charged with 12 lb / 5 kg of HFC-227ea
These units are designed for use in local applications only, where the hazard is normally unoccupied, and are rated for use in the following fire
classifications:
• Class A – Surface type fires
• Class B – Flammable liquid fires
• Class C (Class E for Europe) – Electrical equipment fires
HFC-227ea should not be used where the following materials may be present:
• Pyrotechnic chemicals containing their own oxygen supply
• Reactive metals such as lithium, sodium, potassium, magnesium, titanium, zirconium, uranium, and plutonium
• Metal hydrides
• Chemicals capable of undergoing auto thermal decomposition, such as certain organic peroxides and hydrazine
• Deep Seated or burrowing fires in ordinary combustibles where the clean agent cannot reach the point of combustion
The Firetrace Pre-Engineered Automatic Direct Clean Agent Extinguisher Units can be used, but are not limited, to protect the following:
• Electrical and electronic cabinets
• Telecommunication areas
• Data Processing areas and cabinets
• Laboratory fume /exhaust cabinets
• Pump enclosures
• UPS units
• Flammable Chemicals storage cabinets
• Generator Enclosures
• Transformer Cabinets
• Computer/Data Storage Cabinets
• CNC & VMC Machining centers
For hazards beyond the scope described above, it is recommended that the designer consult with Firetrace and the local authority having
jurisdiction as to the suitability on the use of these agents for particular hazards, for personnel exposure effects from the design concentration,
and for installation requirements.
Firetrace Pre-Engineered Automatic Direct Clean Agent Extinguisher Units consists of the following major components:
• Cylinder/Valve assembly
• Cylinder Mounting Bracket (Heavy duty bracket optional)
• Firetrace Detection Tubing (FDT) and fittings (No substitute)
• Pressure Supervisory Switch
• Pressure Operated Switch (Optional)
• EU Pressure Operated Switch (Optional)
Once installed, the Firetrace Pre-Engineered Automatic Direct Clean Agent Extinguisher Unit becomes a self-contained, self-actuating unit that
does not require an external power source.
The unit utilizes a UL recognized (per UL Standard 521) linear heat detector (see Certificate of Compliance 20140705-S35465) known as
Firetrace Detection Tubing. This tubing is pressurized with dry nitrogen, is temperature sensitive, and acts as a continuous linear thermal detector
that ruptures upon direct flame impingement or at temperatures above 383 °F [195 °C]. Once the Firetrace detection tubing is ruptured, it forms
a nozzle at the rupture point, allowing the HFC-227ea clean agent to flow through, distributing the agent through the nozzle and into the protected
area.
Upon system actuation, the pressure switch can be used to indicate system discharge, sound an alarm, shutdown ventilation, shut-off electrical
power, or provide additional electrical functions as may be required.
Component Descriptions
For a more comprehensive list of technical illustrations and part numbers, please see APPENDIX A.
7
800023-008 07/20/2020
2.2.1 Cylinder/Valve Assemblies
The HFC-227ea clean agent is stored in aluminum or steel cylinders and is super-pressurized with nitrogen. Each cylinder is equipped with a
nickel plated brass valve assembly.
Each valve assembly is equipped with a pressure gauge to monitor cylinder pressure, and a quarter turn ball valve that interfaces with the
Firetrace detection tubing (FDT). The valve assembly utilizes a straight siphon tube only for the unit to only be mounted in a vertical (upright)
position.
NOTE: The ball valve must be kept closed at all times when the unit is not in service.
The Firetrace detection tubing is heat sensitive and in a fire situation is designed to rupture at any point along its length upon direct flame
impingement or when the temperature reaches above 383 °F [195 °C]. The rupture of the tubing releases the nitrogen pressure causing the unit
to actuate. The portion of the tubing nearest the fire ruptures, resulting in a formation of a discharge nozzle that will perform a complete discharge
of the HFC-227ea clean agent. For additional information on tubing properties and material compatibility, please see Table 1 - Firetrace Detection
Tubing Properties and APPENDIX B.
8
800023-008 07/20/2020
2.2.5 Pressure Supervisory Switch
The pressure supervisory switch (P/N 400052) is used to monitor the pressure inside the unit cylinder. The pressure supervisory switch is factory
installed into the pressure switch port located on the valve assembly. If the unit loses pressure and reaches a pressure of 99 psig ± 9 psi
[6.8 ± 0.6 bar] or below, the switch contacts will activate, providing a signal to indicate that the unit has lost pressure.
The pressure supervisory switch is single pole, double throw (SPDT) and can be wired in either the normally open (NO) or normally closed (NC)
configurations, where the normal condition is at atmospheric pressure. When the unit is pressurized, the contacts switch over. The pressure
supervisory switch shall be installed in accordance with NFPA 70 and NFPA 72.
The pressure operated switch is single pole, double throw (SPDT) and can be wired in either the normally open (NO) or normally closed (NC)
configurations, where the normal condition is at atmospheric pressure. The pressure operated switch shall be installed in accordance with NFPA
70 and NFPA 72.
The EU pressure operated switch is single pole, double throw (SPDT) and can be wired in either the normally open (NO) or normally closed
(NC) configurations, where the normal condition is at atmospheric pressure. The EU pressure operated switch shall be installed in accordance
with NFPA 70 and NFPA 72.
Firetrace recommends that all units use a pressure switch coupled with a device to alert personnel in the event of discharge.
NOTE: Due to the nature of the Firetrace direct clean agent extinguishing unit, it provides for an extended discharge. Due to the extended
discharge, the pressure within the system slowly drops, which could provide a delay in the actuation of the pressure switch. The pressure
switch shall be installed as part of the detection line, at the end of the detection network.
EU Pressure Operated
Operating Pressure Supervisory Switch Pressure Operated Switch
Switch
Parameters P/N 400052 P/N 400004
P/N 400034
28 VDC – 15 AMP
36 VDC – 6 AMP
Electrical Rating NO: NC: 250 V – 5 AMP – 50 Hz
240 VAC – 3 AMP
120 VAC – 10 AMP 120 VAC – 25 AMP
240 VAC – 5 AMP 240 VAC – 25 AMP
-5 °F to 175 °F -20 °F to 150 °F 14 °F to 176 °F
Temperature Range
[-20.6 °C to 79.4 °C] [-28.9 °C to 65.6 °C] [-10 °C to 80 °C]
NOTE: Do not use the pressure supervisory switch as a handle when handling the extinguishing unit. Doing so can result in pressure leakage, damage to
the pressure switch, and/or system discharge.
9
800023-008 07/20/2020
3 SYSTEM DESIGN AND LIMITATIONS
General
The pre-engineered system concept minimizes the amount of engineering required when evaluating a design for a specific application.
Provided that the volume of the hazard, surface area coverage, agent quantity, and Firetrace Detection Tubing (FDT) is installed within the
limitations outlined in this manual, no calculations are required for pressure drop, flow rates, or discharge time.
NOTE: The basis for determining the agent quantity and concentration levels is derived from NFPA 2001, 2015 edition, and is deemed
to be compliant with the standard in this aspect.
Specifications
3.2.1 Storage and Operating Temperature Range
The Firetrace Pre-Engineered Automatic Direct HFC-227ea Clean Agent Extinguishing Units and equipment are designed to be stored and
operated at the ambient temperature range of -4 °F to 140 °F [-20 °C to 60 °C].
The Firetrace Pre-Engineered Automatic Direct HFC-227ea Clean Agent Extinguishing Units are designed for an operating temperature range
of -4 °F to 140 °F [-20 °C to 60 °C]. Table 3 - Cylinder Pressure-Temperature Relationship shows the cylinder gauge pressure-temperature
relationship based on a charging pressure of 150 psig at 70 °F [10.3 bar at 21.1 °C].
10
800023-008 07/20/2020
Table 3 - Cylinder Pressure-Temperature Relationship
Temperature Pressure
°F °C psig bar
-4 -20.0 88 6.1
0 -17.8 91 6.3
5 -15.0 94 6.5
10 -12.2 97 6.7
15 -9.4 101 7.0
20 -6.7 104 7.2
25 -3.9 108 7.4
30 -1.1 111 7.7
35 1.7 115 7.9
40 4.4 119 8.2
45 7.2 124 8.5
50 10.0 128 8.8
55 12.8 134 9.2
60 15.6 139 9.6
65 18.3 143 9.9
70 21.1 150 10.3
75 23.9 156 10.8
80 26.7 163 11.2
85 29.4 170 11.7
90 32.2 177 12.2
95 35.0 184 12.7
100 37.8 192 13.2
105 40.6 201 13.9
110 43.3 209 14.4
115 46.1 218 15.0
120 48.9 228 15.7
125 51.7 239 16.5
130 54.4 249 17.2
135 57.2 258 17.8
140 60.0 267 18.4
Design Procedure
The following procedures should be used to design a Firetrace Pre-Engineered Automatic Direct HFC-227ea Clean Agent Extinguisher Unit:
a. Conduct a survey and analysis of the hazard to be protected.
b. Determine the height, length, and width of the enclosure. Calculate the volume. (All of these parameters must be within the
dimensional limits specified in this Manual.)
c. Determine the anticipated minimum and maximum ambient temperatures expected within the enclosure to be protected. (These
must be within the recommend minimum and maximum service temperatures of the system.)
d. Determine the integrity of the enclosure and if any openings must be closed at the time of agent discharge.
e. Determine the cylinder size required based on the hazard volume limitations.
f. Based on the total quantity of agent being used at the maximum ambient temperature expected within the enclosure, evaluate
personnel safety exposure limits.
g. Determine the location of the system cylinder.
h. Determine the arrangement and placement of the Firetrace detection tubing.
i. Determine any auxiliary equipment requirements such as a pressure switch(es) to sound alarms, shut down ventilation, shut off
electrical power, etc.
11
800023-008 07/20/2020
Minimum Design Concentrations
The minimum design concentration to be used with Firetrace Pre-Engineered Automatic Direct HFC-227ea Clean Agent Extinguisher Units
include a minimum safety factor (SF), as specified in NFPA 2001, 2015 edition.
A minimum design concentration of 12.1% was established using the minimum design concentration for commercial grade heptane. Minimum
design concentrations will vary for different Class B fuels.
It is recommended that the designer consult with Firetrace, NFPA 2001, and the local authority having jurisdiction, as to the suitability on the
use of HFC-227ea for a particular hazard, for personnel exposure effects from the design concentrations, and for installation requirements.
System Limitations
LPCB approval applies for systems with:
• A single container heat detection tube installation run protecting a maximum single volume of 2 m³ *.
• Up to 4 heat detection tube runs connected to a single container where no single protected volume exceeds a 2 m³ * volume.
• A maximum heat detection tube length of 10 m from the container outlet to the end of any single detection tube run.
*The 2 m³ volume limitation applies only to 6 lb [2 kg] and 12 lb [5 kg] systems. For the 3 lb [1 kg] system, the volume is limited to 1 m³.
Concentration
Model Number Agent Amount
(%)
3 lb 35.31 ft³
920301 / 898004
[1 kg] [1 m³]
6 lb 70.63 ft³
920601 / 898005
[2 kg] [2 m³]
12 lb 70.63 ft³
921201 / 898006
[5 kg] [2 m³]
12
800023-008 07/20/2020
3.5.2 Ventilation and Unclosable Openings
Provisions must be made to provide means to close all openings in the hazard enclosure and shut off ventilation at the time of discharge, if
feasible. If openings are determined to be unclosable or ventilation is unable to be shut down, the volume of airflow for a reasonable amount of
time due to these impediments must be included in the overall volume calculations/survey.
In the event of a discharge, the hazard enclosure must have sufficient structural strength and integrity to contain the agent discharge. If the
pressure difference across the enclosure boundaries presents a threat to the hazard enclosure, venting shall be provided to prevent excessive
pressures.
To ensure that the entire height of an enclosure is protected, the tubing must be installed in layers. The maximum height between layers shall
not exceed 1.64 ft [0.5 m].
To ensure that the entire area of each layer is protected, the tubing must be installed in passes. The maximum distance between each pass
shall not exceed 10.22 in [25.96 cm].
The maximum distance from any wall to the tubing shall not exceed 5.11 in [12.98 cm]. The maximum bend radius shall not exceed 6 in [15.24
cm].
The tubing may be installed in runs to protect segmented areas within an enclosure. The maximum tube length from the container outlet to the
end of any single tube run shall not exceed 32.8 ft [10 m]. Up to 4 tube runs may be connected to a single cylinder, provided that the volume of
each segmented area does not exceed the maximum volume limitations.
The MAH is the maximum activation height of the tubing above the protected risk. The MAH for 4/6 mm tubing is 3.94 in [100 mm]. For better
response time in the event of a fire, the tubing should be placed at a height less than the MAH above the hazard.
13
800023-008 07/20/2020
3.5.3.1 Tubing Limitations Example
An example of a system configuration is shown below:
Run 1
Run 2
Run 3
The tubing is installed in three different runs in order to protect the segmented sections within the enclosure. The total length of Run 1 is 9.28 ft
[2.83 m]. The total length of Run 2 is 11.28 ft [3.44 m]. The total length of Run 3 is 13.28 ft [4.05 m]. Each tubing run is less than the maximum
tube run length of 32.8 ft [10 m].
The tubing is also installed in layers to protect the overall height of the enclosure. Each layer does not exceed the maximum height between
layers of 1.64 ft [0.5 m].
The tubing is fastened on the sides of the walls, ensuring the distance between the tubing to any wall does not exceed 5.11 in [12.98 cm].
14
800023-008 07/20/2020
4 INSTALLATION INSTRUCTIONS
Firetrace Pre-Engineered Automatic Direct HFC-227ea Clean Agent Extinguisher Units must be handled, installed, inspected, and serviced only
by qualified and trained personnel in accordance with the instructions contained in the appropriate manual, unit nameplate, and any other
regulations and codes that may apply.
The extinguisher unit and bracket must be mounted in the vertical plane and oriented so that the pressure gauge is facing out and away from
the mounting wall to facilitate visual inspection.
Mount the extinguisher unit where it will not be subjected to accidental damage or movement. Suitable protection must be installed where
necessary to prevent damage or movement.
1. Securely mount the cylinder bracket to structural support using 2 or more mounting holes.
2. Position the cylinder in the bracket with the pressure gauge facing out. Secure the cylinder in place using the bracket straps or
band clamps.
WARNING
During transportation, ensure that the ball valve, located on the top of the cylinder valve, is maintained in the “OFF” position.
Failure to follow these instructions will result in actuation and discharge of the cylinder contents.
WARNING
Do not use the pressure supervisory switch on the valve as a handle when during transportation of the unit. Doing so can result
in damage to the pressure switch, leakage to the unit, and/or unit discharge.
CAUTION
This unit is designed as an Automatic unit. No manual or electric means is provided for simultaneous actuation of
multiple units. Only one (1) unit can be used to protect one hazard. These extinguisher units cannot be combined
to protect a larger size hazard since they are not designed to provide for simultaneous actuation of two (2) or more
units.
Component Installation
All components should be installed to facilitate proper inspection, maintenance, testing, recharging, and any other required service as may be
necessary. Equipment must not be subjected to severe weather conditions, mechanical, chemical, or other damage which could render the
equipment inoperative. The equipment must be installed in accordance with instructions in this Manual.
15
800023-008 07/20/2020
4.2.1 Firetrace Detection Tubing
Location and spacing of the tubing is critical to the response time in the event of a fire. The tubing should be placed above the hazard areas
being protected. It is recommended that the tubing be placed in a manner such that it is situated horizontally above potential fire sources. It is
not recommended that the FDT is oriented vertically adjacent to a potential fire source. Tubing installation should always be inspected to ensure
the tubing is not kinked, crushed, or vulnerable to damage. Tubing shall not be installed on any galvanic surfaces.
1. Secure the detection tubing using Mounting Tabs at no more than 6 in [15.24 cm] intervals.
2. All FDT fittings at joints must be secured.
3. FDT must be secured within 6 in [15.24 cm] of all joints or fittings, to prevent leakage due to bends near joints.
4. Use the appropriate rubber/plastic grommets when the detection tubing is routed through sharp holes, in order to prevent damage to
the tubing.
5. When mounting to metal surfaces, rubber P-clips or a small piece of copper/rubber hosing is required to mount to the metal surface.
6. All FDT fittings and joints are to be inspected for leaks with a solution of liquid soap and water.
CAUTION
1. Do not kink, bend, or crush Firetrace tubing in order to prevent leakage which could result in accidental unit discharge.
2. Do not install tubing in a hazardous environment where the maximum ambient temperature exceeds 300 °F [148.9 °C].
End of Line Adapters are not designed to provide a lasting seal without the use of one of the following items:
Pressure Gauge:
The Pressure Gauge must be installed with its included O-ring. Thread the pressure gauge into the End of Line Adapter so that the gauge
indicates the tubing pressure.
16
800023-008 07/20/2020
System Activation
1. Ensure the detection tubing, fittings, and accessories are installed according the procedures specified in Section 4.2 of this manual.
2. Attach the filling adapter to the End of Line Adapter.
3. Using a regulated dry nitrogen supply, pressurize the detection tubing through the filling adapter. It is recommended to have a portable
dry nitrogen cylinder or Firetrace Nitrogen Fill Kit for on-site use.
4. Remove the filling adapter and thread the pressure gauge into the End of Line Adapter. Verify that the tubing is pressurized to the
correct pressure reading.
5. With the gauge still installed to the EOL, test for leakage:
1. Apply soapy water solution to the cylinder valve connection, end of line adapter connection, and the pressure gauge
connection. Observe for bubble leaks.
2. After 30 minutes check the pressure gauge reading. Any decrease in pressure is an indication of a leak.
3. In the event of a leak go back to Section 4.2 and verify the installation of all fittings and accessories.
6. If the pressure operated switch is to be installed, remove the pressure gauge and install the pressure switch according to the
procedures in Section4.2.3.
a. Check pressure switch connection for bubble leaks using soapy water solution.
b. Ensure the proper electrical connections are made to annunciate unit discharge, shut down ventilation, etc., as may be
required by the end user or the authority having jurisdiction. (All electrical connections are to be in accordance with
NFPA 70 National Electric Code and NFPA 72 National Fire Alarm and Signaling Code.)
NOTE: It shall not be possible for the user to isolate any power supply or alarm connections to the unit without also isolating the power supply to the
enclosure or placing the system into an alarm status.
7. Ensure the pressure supervisory switch electrical connections are properly installed to annunciate low pressure within the extinguisher
unit. (All electrical connections are to be in accordance with NFPA 70 National Electric Code and NFPA 72 National Fire Alarm and
Signaling Code.)
8. With the system fully installed and all components properly affixed within the hazard area, SLOWLY rotate the lever on the ball valve
counter clockwise to the “ON” position.
9. Remover the ball valve lever with a small Phillips head screw driver.
10. Install the Anti-Tamper device (P/N 201132) in accordance with APPENDIX B.
17
800023-008 07/20/2020
5 SERVICE AND MAINTENANCE INSTRUCTIONS
Firetrace Pre-Engineered Automatic Direct HFC-227ea Clean Agent Extinguisher Units must be handled, installed, inspected, and serviced only
by qualified and trained personnel in accordance with the instructions contained in the appropriate manual, unit nameplate, and any other
regulations and codes that may apply.
General
A regular program of systematic maintenance must be established for continuous, proper operation of all Firetrace Extinguisher Units and to
avoid violating the warranty. A periodic maintenance schedule must be followed and an inspection log maintained for ready reference. Each
unit is provided with a service record log. As a minimum, the log must record: (1) inspection interval, (2) inspection procedure performed, (3)
maintenance performed, if any, as a result of inspection, and (4) name of inspector performing task.
For any deficiencies that are found, appropriate corrective actions shall be taken immediately.
NOTE: Operational shut down during equipment maintenance is not required. It shall not be possible for the user to isolate any electrical power
supply or alarm connections to the system without also isolating power supply to the enclosure, or placing the system into an alarm status.
WARNING
Pressurized (charged) cylinders are extremely hazardous and if not handled properly are capable of causing bodily injury, death,
or property damage. Always wear safety glasses during unit installation, servicing, or other general handling.
18
800023-008 07/20/2020
WARNING
Firetrace cylinder/valve assemblies must be handled, installed, inspected and serviced only by qualified and trained personnel
in accordance with the instructions contained in this Manual, the cylinder nameplate and any other regulations and codes that
may apply.
ATTENTION
Any maintenance requiring depressurization, filling, or pressurization should only be performed at an Authorized Firetrace
Service Location. Service at any other location will void the Warranty. Please contact Firetrace directly for a list of Authorized
Firetrace Service Locations.
Follow visual inspection guidelines detailed in BS EN 1968:2002, BS EN 1802:2002, and NFPA 2001 (2015 Edition).
DOT-4B, 4BA, and 4BW cylinders used exclusively in HFC-227ea systems are required to follow DOT regulations. DOT regulations require
cylinders which have discharged to be retested and stamped prior to recharge, if more than 5 years have passed since the date of the last test.
Firetrace HFC-227ea systems equipped with DOT cylinders requiring retest must be hydrostatically tested in accordance with DOT CFR Title
49, Section 173.34(e). This periodic retest must be performed by an authorized tester having a current identification number issued by the
Associated Administrator for Hazardous Material Safety of DOT, and must include an internal and external examination in accordance with CGA
pamphlet C-6, C-6.1, C-6.2, or C-6.3, as applicable. The test procedures are described in CGA pamphlet C-1. Only the water jacket volumetric
expansion method or the direct expansion methods are acceptable because volumetric expansion of the container must be measured.
As an alternate option, HFC-227ea system equipped with DOT cylinders may be given a complete visual inspection, as detailed in section
173.34(e) (13), in lieu of hydrostatic testing. The visual inspection shall be made only by competent persons. A person who performs the visual
examination specified in 173.34(e) (13) is not required to have a retester identification number.
Firetrace HFC-227ea systems equipped with CE cylinders requiring retest must be hydrostatically tested in accordance with BS EN 1968:2002,
for steel cylinders, and BS EN 1802:2002, for aluminum cylinders. This periodic retest must be performed only by competent personnel, and
must include an internal and external examination in accordance with BS EN 1968:2002 and BS EN 1802:2002, as applicable. The test
procedures are described in the appendix of BS EN 1968:2002 and BS EN 1802:2002. Only the water jacket volumetric expansion method is
acceptable because volumetric expansion of the container must be measured.
For DOT cylinders requiring hydrostatic testing, testing can be performed by either of the following methods:
19
800023-008 07/20/2020
6 SYSTEM DEPRESSURIZATION AND CHARGING
Firetrace Pre-Engineered Automatic Direct HFC-227ea Clean Agent Extinguishing Units must be handled, installed, inspected, and serviced
only by qualified and trained personnel in accordance with the instructions contained in the appropriate manual, unit nameplate, and any other
regulations and codes that may apply.
WARNING
Pressurized (charged) cylinders are extremely hazardous and if not handled properly are capable of causing bodily injury,
property damage, or death. Always wear safety glasses during unit installation, servicing, or other general handling.
ATTENTION
Any maintenance requiring depressurization, filling, or pressurization should only be performed at an Authorized Firetrace
Service Location. Please contact Firetrace directly for a list of Authorized Firetrace Service Locations.
CAUTION
Opening the ball valve too far, or too fast, will bring HFC-227ea into the valve assembly.
System Recharge
Use the following steps to recharge an empty Firetrace Pre-Engineered Automatic Direct HFC-227ea Clean Agent Extinguisher Unit:
1. Weigh and record the empty weight of the cylinder and valve assembly.
2. Install the Firetrace Detection Tubing to the top of the valve assembly.
3. Connect the filling adapter to the end of line adapter.
4. Connect the HFC-227ea fill line to the fill adapter and record the weight shown on the scale.
5. Zero the scale.
6. Ensure the ball valve is open and open the HFC-227ea fill line.
7. Once the required weight is reached, close the HFC-227ea fill line.
8. Close the ball valve.
9. Open the valve vent to bleed the excess HFC-227ea from the fill line and disconnect the HFC-227ea fill line from the fill adapter.
10. Connect the dry nitrogen fill line to the fill adapter. Ensure it is regulated to 150 psig at 70 °F [10.3 bar at 21 °C] (pressure may
have to be adjusted for temperatures higher or lower than 70°F).
11. Open the ball valve and pressurize the cylinder with dry nitrogen.
12. Close the ball valve and shake the cylinder to allow the nitrogen to be absorbed by the HFC-227ea. (Some pressure loss will be
observed.)
13. Open the ball valve and pressurize back up to 150 psig at 70 °F, as will be indicated on the system pressure gauge.
14. Repeat steps 11 thru 13 until shaking of the system does not result in any pressure loss (i.e., no further nitrogen absorption) and
a pressure of 150 psig is reached.
15. Disconnect the dry nitrogen fill line.
16. Verify the system gross weight by checking it against what is printed on the label.
17. Leak test the unit by using a calibrated leak detector.
18. The unit is now ready to be transported to the installation site.
20
800023-008 07/20/2020
WARRANTY
Firetrace USA, LLC (hereafter referred to as Firetrace) provides the following Limited Warranty only to the original purchaser, who purchases
the Firetrace unit from an Authorized Firetrace Distributor. The Limited Warranty includes all Firetrace units and its component parts supplied
by Firetrace. Hereafter these products will be referred to as “Firetrace Products”. When the Firetrace Products are properly installed by an
authorized Firetrace distributor, in complete accordance with the written instructions contained in the instruction Manuals, or other data supplied
with Firetrace products, and when the Firetrace products have not subsequently been modified or altered, unless by express written instructions
from Firetrace, then the Firetrace products are warranted to be free of defects in materials and workmanship for a period of three (3) years from
the date of shipment from Firetrace, Scottsdale Arizona, as long as the following conditions are met:
(1) The original purchaser must maintain a semi-annual maintenance service agreement with an authorized Firetrace distributor,
commencing with the date the Firetrace product was accepted by the purchaser and placed into service. The service agreement shall
remain in effect for the duration of the warranty.
(2) The Firetrace Warranty Registration Card (P/N 800100) must be completed and returned to Firetrace within thirty (30) days of the
installation of the Firetrace unit.
Firetrace products that are not certified, as specified in the paragraphs 1 and 2 above, will carry a maximum limited warranty of one (1) year
from the date of shipment from Firetrace.
The original purchaser’s sole and exclusive remedy, unless varied by express written agreement with Firetrace, is as follows: Repair or
replacement, at Firetrace’s option, of any defective part which is returned to Firetrace within ninety (90) days of discovery of the defect.
Because of the deleterious effects of corrosion, heat, rust, dirt, debris and other factors of use and installation over which Firetrace has no
control, FIRETRACE MAKES NO OTHER WARRANTIES OF ANY KIND, WHETHER EXPRESSED OR IMPLIED, INCLUDING THE
WARRANTIES OF MERCHANTABILITY AND FITTNESS FOR A PARTICULAR PURPOSE, BEYOND THOSE EXPRESSLY PROVIDED
FOR IN THIS LIMITED WARRANTY. These warranties shall be void where defects occur due to improper maintenance, installation, service,
alterations and/or modifications subsequent to installation, not expressly authorized in writing by Firetrace or due to intentional or negligent acts
of the original purchaser or third parties.
Non-Assignability of Warranty
The limited warranty set forth herein may not be assigned, transferred or sold in any way and extends only to the original purchaser.
In no event shall Firetrace be liable for any consequential or incidental damages arising from the purchase and/or use of Firetrace products,
including but not limited to: damages resulting from loss of use of Firetrace products, the costs of replacing discharged suppression agent,
damages for lost profits or income, or damages for resulting harm to property other than the Firetrace products.
All Firetrace units must exclusively use Firetrace components, especially for connections made to the Firetrace tubing. Failure to exclusively
use Firetrace components will void this limited warranty and release Firetrace of any and all liability on the performance of the Firetrace
components and unit.
21
800023-008 07/20/2020
SOME FACTORS INFLUENCING ENGINEERING DESIGN AND PRODUCT APPLICATION OF FIRETRACE UNITS
The following are some of the factors that influence engineering design and application of Firetrace units. In many cases, these factors are
difficult to accurately estimate, and it is for these reasons that Firetrace makes no warranties other than those specifically stated in this Limited
Warranty.
1. The Firetrace unit has been designed to provide protection against fire, both existing and imminent, for a limited duration of time when: the
unit is fully operational; used in its normal, expected environment; the unit and its component parts are properly installed, maintained, and
operated in complete accordance with written instructions supplied with the unit.
2. The duration of the protection against fires dependent upon a sufficient concentration of agent being maintained in the protected hazard
area for a pre-determined period of time. This duration will be shortened by conditions or circumstances which may ventilate, cause the
agent concentration dilution within the protected hazard area thereby causing an insufficient concentration of agent as is needed to
extinguish or prevent the existence or re-ignition of combustion or fire. All hazard areas have different rate of ventilation, leakage, or agent
dilution that, in many cases, may be impossible to predict or determine. Air vents, air conditioning units, gaps and cracks in the enclosure,
windows, cable and pipe penetrations, etc., all may affect the agent concentration and the duration of the protection against fire. Also,
unforeseen changes in the configuration of a hazard area such as removal of a wall, an explosion or fire external to the protected space,
changes in the enclosures configuration, etc. can influence the duration of the fire protection. It is because of these many, and varied,
circumstances and conditions that Firetrace makes no warranty as to the duration of the protection against fire.
3. The effectiveness of an agent, such as HFC-227ea and/or CO2, as a fire extinguishant is directly related to the concentration of the agent
required to extinguish various substances. Not all substances require the same agent concentration to be extinguished. Therefore,
Firetrace can only assume that the customer has properly defined the hazard area(s) being protected.
4. The effectiveness of the Firetrace unit is dependent upon the timely discharge of the agent fire extinguishant in to the protected area. If
unforeseen circumstances such as an explosion, failure of the detection system to activate the Firetrace unit, failure to Manually activate
the unit, etc. occur, they can prevent the unit discharge from being accomplished in a timely manner, and the fire may become deep seated
or out of control and completely destroy the hazard area. Since Firetrace has no control over these circumstances, there are no warranties
as to the effectiveness of extinguishment of the fire other than those specifically stated in this Limited Warranty.
5. Even if the Firetrace unit is completely effective in suppressing a fire, failure to remove the ignition source of the fire could result in a re-
ignition of the fire. If possible, the source of the fire should immediately be eliminated to prevent re-ignition. Protection against re-ignition
only exists when a sufficient concentration of agent remains in the hazard area, as stated above.
Since the effectiveness of the Firetrace unit depends on when, under what circumstances, it is used, the judgment of operating personnel as to
when to activate a Firetrace unit, in an emergency, affects the protection provided by the unit. Because of the widely carrying conditions and
circumstances under which the Firetrace unit can be used, some conditions can cause its effectiveness to be unpredictable. Therefore,
evacuation of personnel from the protected areas must be accomplished without delay.
22
800023-008 07/20/2020
APPENDIX A
23
800023-008 07/20/2020
System Parts List: DOT System
MODELS:
920301 3 lb HFC-227ea DLP
920601 6 lb HFC-227ea DLP
921201 12 lb HFC-227ea DLP
24
800023-008 07/20/2020
System Parts List: CE System
MODELS:
898004 1 kg HFC-227ea DLP
898005 2 kg HFC-227ea DLP
898006 5 kg HFC-227ea DLP
5 810100 1 kg Cylinder 1 kg
5 810200 2 kg Cylinder 2 kg
5 810500 5 kg Cylinder 5 kg
9 810101 1 kg bracket 1 kg
9 810202 2 kg Bracket 2 kg
9 810505 5 kg Bracket 5 kg
25
800023-008 07/20/2020
Detection Line Parts List
26
800023-008 07/20/2020
APPENDIX B
27
800023-008 07/20/2020
Tamper Proof Instruction
28
800023-008 07/20/2020
Firetrace Detection Tubing Compatibility
Results of chemical testing of Firetrace Detection Tubing undertake by Oxford University.
*All chemicals were in contact with the tubing for five days (vapor and liquid)
29
800023-008 07/20/2020
APPENDIX C
30
800023-008 07/20/2020
Safety Data Sheet: HFC-227ea
FM-200™
Version 3.0
This SDS adheres to the standards and regulatory requirements of the United States and may not meet the regulatory
requirements in other countries.
™
Product name : FM-200
Tradename/Synonym : FE-227
2-Hydroperfluoropropane
Propane, 1,1,1,2,3,3,3-Heptafluoro- HFC-
227eaHP
2-Hydroheptafluoropropane
Heptafluoropropane
2-H-heptafluoropropane
1,1,1,2,3,3,3-Heptafluoropropane
R-227
R227
HFC-227ea
Restrictions on use : Do not use product for anything outside of the above specified uses
Manufacturer/Supplier : The Chemours Company FC, LLC
1007 Market Street
Wilmington, DE 19899
United States of America
1 / 11
31
800023-008 07/20/2020
Safety Data Sheet
FM-200™
Version 3.0
Label content
Pictogram :
Other hazards
Misuse or intentional inhalation abuse may lead to death without warning.
Vapours are heavier than air and can cause suffocation by reducing oxygen available for breathing.
Rapid evaporation of the liquid may cause frostbite.
2 / 11
32
800023-008 07/20/2020
Safety Data Sheet
FM-200™
Version 3.0
General advice : Never give anything by mouth to an unconscious person. When symptoms
persist or in all cases of doubt seek medical advice.
Inhalation : Remove from exposure, lie down. Move to fresh air. Keep patient warm and at
rest. Artificial respiration and/or oxygen may be necessary. Consult a physician.
Skin contact : In case of contact, immediately flush skin with plenty of water for at least 15
minutes. Take off all contaminated clothing immediately. Consult a physician.
Wash contaminated clothing before re-use. Treat for frostbite if necessary by
gently warming affected area.
Eye contact : In case of contact, immediately flush eyes with plenty of water for at least 15
minutes. Consult a physician if necessary.
3 / 11
33
800023-008 07/20/2020
Safety Data Sheet
FM-200™
Version 3.0
Safeguards (Personnel) : Evacuate personnel, thoroughly ventilate area, use self-contained breathing
apparatus. Keep upwind of leak - evacuate until gas has dispersed.
34
800023-008 07/20/2020
Safety Data Sheet
FM-200™
Version 3.0
Eye protection : Safety glasses with side-shields Additionally wear a face shield where the
possibility exists for face contact due to splashing, spraying or airborne
contact with this material.
Skin and body protection : Where there is potential for skin contact, have available and wear as
appropriate, impervious gloves, apron, pants, jacket, hood and boots.
35
800023-008 07/20/2020
Safety Data Sheet
FM-200™
Version 3.0
Exposure Guidelines
Exposure Limit Values
1,1,1,2,3,3,3-Heptafluoropropane
No applicable data available.
Odor : none
36
800023-008 07/20/2020
Safety Data Sheet
FM-200™
Version 3.0
37
800023-008 07/20/2020
Safety Data Sheet
FM-200™
Version 3.0
Hazardous decomposition : Hazardous decomposition products formed under fire conditions.: Hazardous
products thermal decomposition products may include:
Hydrogen halides, Carbon oxides, Fluorocarbons, Carbonyl halides
Inhalation : Dog
Cardiac sensitization
38
800023-008 07/20/2020
Safety Data Sheet
FM-200™
Version 3.0
1,1,1,2,3,3,3-Heptafluoropropane
Carcinogenicity : Not classifiable as a human carcinogen.
Animal testing did not show any carcinogenic effects.
Carcinogenicity
The carcinogenicity classifications for this product and/or its ingredients have been determined according
to HazCom 2012, Appendix A.6. The classifications may differ from those listed in the National Toxicology
Program (NTP) Report on Carcinogens (latest edition) or those found to be a potential carcinogen in the
International Agency for Research on Cancer (IARC) Monographs (latest edition).
None of the components present in this material at concentrations equal to or greater than 0.1% are listed
by IARC, NTP, or OSHA, as a carcinogen.
72 h ErC50 : Pseudokirchneriella subcapitata (green algae) > 114 mg/l OECD Test
Guideline 201
Information given is based on data obtained from similar substances.
39
800023-008 07/20/2020
Safety Data Sheet
FM-200™
Version 3.0
Guideline 201
Information given is based on data obtained from similar substances.
48 h EC50 : Daphnia magna (Water flea) > 200 mg/l OECD Test Guideline 202
Information given is based on data obtained from similar substances.
Class : 2.2
Labelling No. : 2.2
IMDG UN number : 3296
Proper shipping name : HEPTAFLUOROPROPANE
Class : 2.2
Labelling No. : 2.2
10 / 11
40
800023-008 07/20/2020
Safety Data Sheet
FM-200™
Version 3.0
SARA 313 Regulated : This material does not contain any chemical components with known CAS
Chemical(s) numbers that exceed the threshold (De Minimis) reporting levels established
by SARA Title III, Section 313.
California Prop. 65 : Chemicals known to the State of California to cause cancer, birth defects or
any other harm: none known
™
Chemours and the Chemours Logo are trademarks of The Chemours Company.
Before use read Chemours safety information. For further information contact the local Chemours office or nominated
distributors.
The information provided in this Safety Data Sheet is correct to the best of our knowledge, information and belief at the
date of its publication. The information given is designed only as a guidance for safe handling, use, processing, storage,
transportation, disposal and release and is not to be considered a warranty or quality specification. The information
relates only to the specific material designated and may not be valid for such material used in combination with any
other materials or in any process, unless specified in the text.
11 / 11
41
800023-008 07/20/2020
Safety Data Sheet: Nitrogen
42
800023-008 07/20/2020
43
800023-008 07/20/2020
44
800023-008 07/20/2020
45
800023-008 07/20/2020
46
800023-008 07/20/2020
47
800023-008 07/20/2020
48
800023-008 07/20/2020
49
800023-008 07/20/2020