Ba01268ken 0113
Ba01268ken 0113
Operating Instructions
RID16
Field indicator
with PROFIBUS® PA protocol
Brief overview
For quick and straightforward commissioning:
Safety instructions ä6
Installation ä9
Wiring ä 12
Commissioning ä 28
Endress+Hauser
RID16
Table of contents
1 Document information . . . . . . . . . . . . . . 4 10.2 Status messages . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
10.3 Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
1.1 Document function . . . . . . . . . . . . . . . . . . . . . . . . . . 4 10.4 Software history and overview of compatibility . 33
1.2 Document conventions . . . . . . . . . . . . . . . . . . . . . . . 4
11 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
2 Safety instructions . . . . . . . . . . . . . . . . . . 6
2.1 Requirements for the personnel . . . . . . . . . . . . . . . 6
12 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . 34
2.2 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.3 Occupational safety . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.4 Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 13 Technical data . . . . . . . . . . . . . . . . . . . . 35
2.5 Product safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
14 Appendix . . . . . . . . . . . . . . . . . . . . . . . . 41
3 Identification . . . . . . . . . . . . . . . . . . . . . . 8
14.1 DTM operating parameters . . . . . . . . . . . . . . . . . . 41
3.1 Device designation . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.2 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
3.3 Certificates and approvals . . . . . . . . . . . . . . . . . . . . 8
4 Installation . . . . . . . . . . . . . . . . . . . . . . . . 9
4.1 Incoming acceptance, transport, storage . . . . . . . . 9
4.2 Installation conditions . . . . . . . . . . . . . . . . . . . . . . . 9
4.3 Installation instructions . . . . . . . . . . . . . . . . . . . . 10
4.4 Post-installation check . . . . . . . . . . . . . . . . . . . . . 11
5 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.1 Connecting the cable to the field indicator . . . . 12
5.2 Connection to PROFIBUS® PA . . . . . . . . . . . . . . . 14
5.3 PROFIBUS® PA cable specifications . . . . . . . . . . 16
5.4 Degree of protection . . . . . . . . . . . . . . . . . . . . . . . 19
5.5 Post-connection check . . . . . . . . . . . . . . . . . . . . . 20
7 Commissioning . . . . . . . . . . . . . . . . . . . . 28
7.1 Post-installation check . . . . . . . . . . . . . . . . . . . . . 28
7.2 Switching on the field indicator . . . . . . . . . . . . . 28
7.3 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
8 Maintenance . . . . . . . . . . . . . . . . . . . . . . 29
9 Accessories . . . . . . . . . . . . . . . . . . . . . . . 29
9.1 Device-specific accessories . . . . . . . . . . . . . . . . . . 29
9.2 Communication-specific accessories . . . . . . . . . 29
10 Troubleshooting . . . . . . . . . . . . . . . . . . . 30
10.1 Troubleshooting instructions . . . . . . . . . . . . . . . . 30
Endress+Hauser 3
Document information RID16
1 Document information
Symbol Meaning
DANGER!
This symbol alerts you to a dangerous situation. Failure to avoid this situation
A0011189-EN
will result in serious or fatal injury.
WARNING!
This symbol alerts you to a dangerous situation. Failure to avoid this situation
A0011190-EN
can result in serious or fatal injury.
CAUTION!
This symbol alerts you to a dangerous situation. Failure to avoid this situation
A0011191-EN
can result in minor or medium injury.
NOTE
This symbol contains information on procedures and other facts which do not
A0011192-EN
result in personal injury.
Symbol Meaning
Direct current
A0011197 A terminal to which DC voltage is applied or through which direct current flows.
Alternating current
A0011198 A terminal to which alternating voltage is applied or through which alternating current flows.
Ground connection
A0011200 A grounded terminal which, as far as the operator is concerned, is grounded via a grounding sys-
tem.
Equipotential connection
A connection that has to be connected to the plant grounding system: This may be a potential
A0011201
equalization line or a star grounding system depending on national or company codes of practice.
4 Endress+Hauser
RID16 Document information
Symbol Meaning
Permitted
Indicates procedures, processes or actions that are permitted.
A0011182
Preferred
Indicates procedures, processes or actions that are preferred.
A0011183
Forbidden
Indicates procedures, processes or actions that are forbidden.
A0011184
Tip
Indicates additional information.
A0011193
Reference to documentation
Refers to the corresponding device documentation.
A0011194
Reference to page
Refers to the corresponding page number.
A0011195
Reference to graphic
Refers to the corresponding graphic number and page number.
A0011196
Series of steps
, , …
A0015662
A0013562
Symbol Meaning
Series of steps
, , …
A0015662
A, B, C, etc. Views
Flow direction
A0013441
Hazardous area
- A0011187
Indicates a hazardous area.
Endress+Hauser 5
Safety instructions RID16
2 Safety instructions
6 Endress+Hauser
RID16 Safety instructions
Environmental requirements
If a plastic transmitter housing is permanently exposed to certain steam and air mixtures,
this can damage the housing.
‣ If you are unsure, please contact your Endress+Hauser Sales Center for clarification.
‣ If used in an approval-related area, observe the information on the nameplate.
Hazardous area
Measuring systems for use in hazardous areas are accompanied by separate "Ex documenta-
tion", which is an integral part of these Operating Instructions. Strict compliance with the
installation instructions and connection data as stated in this supplementary documentation
is mandatory!
Endress+Hauser 7
Identification RID16
3 Identification
3.1.1 Nameplate
The right device?
Compare the nameplate on the device with the following diagram:
A0021542
8 Endress+Hauser
RID16 Installation
4 Installation
4.2.1 Dimensions
a0011152
Endress+Hauser 9
Installation RID16
A0011269
Fig. 3: Mounting the field indicator on a pipe with mounting kit, steps 1-2
A0011270
Fig. 4: Mounting the field indicator on a pipe with mounting kit, steps 3-4
Mounting kit, comprising:
1: Mounting plate
2: Mounting bracket
3: 4 screws
10 Endress+Hauser
RID16 Installation
Does the device correspond to the measuring point See 'Technical data' section,
specifications, e.g. ambient temperature range etc.?
Endress+Hauser 11
Wiring RID16
5 Wiring
! WARNING
Danger of explosion if unit is connected incorrectly in hazardous area
‣ When connecting Ex-approved devices please take special note of the instructions and
connection schematics in the Ex-specific supplement to these Operating Instructions. If
you have any questions, please do not hesitate to contact your E+H representative.
NOTICE
Electronics can be destroyed if unit is connected incorrectly
‣ Switch off power supply before installing or connecting the device. Failure to observe this
may result in destruction of parts of the electronics.
‣ The post connector is only used to connect the display. If other devices are connected, this
can result in the destruction of parts of the electronics.
Devices can be connected to the PROFIBUS® PA in two ways:
• Via a conventional cable gland ä 15
• Via a fieldbus connector (optional, available as an accessory) ä 15
A0021557
1. First of all using a suitable tool, such as a screwdriver, open one of the indentations pro-
vided on the bottom of the device. Open the indentation at room temperature, as oth-
erwise the housing could be damaged at very low temperatures.
2. Install the mounting plate for the cable gland and fieldbus connector. The mounting
plate is supplied with the field indicator, see the scope of delivery.
3. Insert the cable gland or the fieldbus connector into the mounting plate. A cable gland
is supplied with the field indicator, see the scope of delivery. The fieldbus connector is
available as an accessory.
12 Endress+Hauser
RID16 Wiring
A0011636
a0014935
Fig. 7: Mounting the cable shield grounding clamps (only aluminum housing)
5. Tighten the cable gland again and close the housing cover.
6. To avoid any mistakes when connecting the unit, follow the instructions in the "Post-
connection check" section.
Endress+Hauser 13
Wiring RID16
Terminal assignment
A0021544
14 Endress+Hauser
RID16 Wiring
A0012567
‣ The terminals for the fieldbus connection (1+ and 2-) are not polarity sensitive.
‣ Conductor cross-section:
2
– Max. 2.5 mm (14 AWG)
‣ Always use a shielded cable for the connection.
Optionally, a fieldbus connector can be installed in the field housing instead of a cable gland.
Fieldbus connectors can be ordered as an accessory from Endress+Hauser (see Section 8
"Accessories").
The PROFIBUS® PA connection technology allows measuring devices to be connected to the
fieldbus via standardized mechanical connections such as T-boxes, junction box modules etc.
This connection technology using pre-fabricated junction box modules and plug-in connec-
tors offers considerable advantages over conventional wiring systems:
• Field devices can be removed, replaced or added at any time during normal operation.
Communication is not interrupted.
• Installation and maintenance are considerably easier.
• Existing cable infrastructures can be used and extended immediately, e.g. when creating
new star distributor systems using 4-channel or 8-channel distribution modules.
Shielding the supply line/T-box
Always use cable glands with good EMC properties, where possible with wrapround cable
shielding (Iris spring). This requires minimum differences in potential, and possibly poten-
tial equalization.
• The shielding of the PA cable may not be interrupted.
• The shielding connection must always be kept as short as possible.
Ideally cable glands with Iris springs should be used to connect the shield. The Iris spring,
which is located inside the gland, connects the shield to the T-box housing. The shielding
braid is located under the Iris spring.
Endress+Hauser 15
Wiring RID16
When the armored thread is screwed tight, the Iris spring is pressed against the shield,
thereby establishing a conductive connection between the shield and the metal housing.
A junction box or a plug-in connection must be considered part of the shielding (Faraday
shield). This applies in particular to remote boxes if such boxes are connected to a PROFI-
BUS® PA device via a plug-in cable. In such cases, you must use a metal connector where the
cable shielding is connected to the connector housing (e.g. pre-terminated cables).
A0021545
• Cable types A or B are particularly preferable for new installations. Only these types have
cable shielding that guarantees adequate protection from electromagnetic interference
and thus the most reliable data transfer. In the case of cable type B, several fieldbuses
(same degree of protection) may be operated in one cable. No other circuits are permissible
in the same cable.
• Practical experience has shown that cable types C and D should not be used due to the lack
of shielding, since the freedom from interference frequently does not meet the require-
ments described in the standard.
The electrical data of the fieldbus cable have not been specified but determine important
characteristics of the design of the fieldbus, such as distances bridged, number of users, elec-
tromagnetic compatibility, etc.
Suitable fieldbus cables (type A) from various manufacturers for non-hazardous areas are
listed below:
• Siemens: 6XV1 830-5BH10
16 Endress+Hauser
RID16 Wiring
• Belden: 3076F
• Kerpen: CeL-PE/OSCR/PVC/FRLA FB-02YS(ST)YFL
• The maximum permissible overall cable length depends on the cable type used.
• If repeaters are used, the maximum cable length is doubled. A maximum of three repeaters
are permitted between the user and master.
Type A Type B
Wire cross-section 0.8 mm2 (AWG 18) 0.32 mm2 (AWG 22)
Max. cable length (incl. spurs >1 1900 m (6233 ft) 1200 m (3937 ft)
m)
* not specified
The line between the distribution box and field device is described as a spur.
In the case of non-Ex applications, the max. length of a spur depends on the number of spurs
(>1 m/3.28 ft):
Number of spurs 1 to 12 13 to 14 15 to 18 19 to 24 25 to 32
Max. length per spur 120 m (393 90 m (295 60 m (196 30 m (98 ft) 1 m (3.28
ft) ft) ft) ft)
In systems that meet FISCO with Ex ia type of protection, the line length is limited to max.
1000 m (3280 ft). A maximum of 32 users per segment in non-Ex areas or a maximum of
10 users in an Ex-area (Ex ia IIC) is possible. The actual number of users must be determined
during the planning stage.
Endress+Hauser 17
Wiring RID16
Optimum electromagnetic compatibility (EMC) of the fieldbus system can only be guaran-
teed if the system components and, in particular, the lines are shielded and the shield forms
as complete a cover as possible. A shield coverage of 90% is ideal.
• To ensure an optimum EMC protective effect, connect the shield as often as possible to the
reference ground.
• For reasons of explosion protection, you should refrain from grounding however.
To comply with both requirements, the fieldbus system allows three different types of
shielding:
• Shielding at both ends
• Shielding at one end on the feed side with capacitance termination at the field device
• Shielding at one end on the feed side
Experience shows that the best results with regard to EMC are achieved in most cases in
installations with shielding at one end. Appropriate measures with regard to input wiring
must be taken to allow unrestricted operation when EMC interference is present. These
measures have been taken into account for this device. Operation in the event of disturbance
variables as per NAMUR NE21 is possible with shielding at one end.
Where applicable, national installation regulations and guidelines must be observed during
the installation!
Where there are large differences in potential between the individual grounding points, only
one point of the shielding is connected directly with the reference ground. In systems with-
grounded on one side, for example at the fieldbus supply unit or at safety barriers, å 11.
out potential equalization, therefore, cable shielding of fieldbus systems should only be
A0011645
Abb. 11: Shielding and grounding of the fieldbus cable shield at one end
1 Supply unit
2 Distribution box (T-box)
3 Bus terminator
4 Grounding point for fieldbus cable shield
5 Optional grounding of the field device, isolated from cable shielding.
NOTICE
Equalizing current can damage the bus cable or bus shield
‣ If the shielding of the cable is grounded at more than one point in systems without
potential matching, mains frequency equalizing currents can occur that damage the bus
cable or the bus shield or have a serious effect on signal transmission. In such cases the
shielding of the fieldbus cable is to be grounded on one side only, i.e. it must not be
connected to the ground terminal of the housing. The shield that is not connected should
be insulated!
The start and end of each fieldbus segment must always be terminated by a bus terminator.
With various junction boxes (non-Ex), the bus termination can be activated via a switch. If
18 Endress+Hauser
RID16 Wiring
this is not the case, a separate bus terminator must be installed. Please also note the follow-
ing:
• In the case of a branched bus segment, the measuring device furthest from the segment
coupler represents the end of the bus.
• If the fieldbus is extended with a repeater then the extension must also be terminated at
both ends.
General information and additional wiring instructions are provided in the manual "Guide-
04), which can also be found on the CD-ROM. (Also available at: www.endress.de
lines for planning and commissioning, PROFIBUS ® DP/PA, field communication" (BA034S/
Download).
Endress+Hauser 19
Wiring RID16
Are all the screw terminals well tightened and have the connections of the ä 16
spring terminals been checked?
Are all the connection components (T-box, junction boxes, connectors, etc.) -
correctly connected to one another?
Has the max. length of the fieldbus cable, as defined in the fieldbus specifi-
cations, been observed?
Has the max. length of the spurs, as defined in the fieldbus specifications, ä 16
been observed?
20 Endress+Hauser
RID16 Operating the field indicator
A0021500
Only 2 display values are displayed when operating via the DIP switches, even if several display values
have been configured via the configuration software.
Endress+Hauser 21
Operating the field indicator RID16
6.2.1 Display
A0011309
The backlit LCD display contains a bargraph (0-100) and arrows to indicate measurements
above or below the measurement range. Analog process values, digital status and failure
codes are displayed in the 7-segment area. Here up to 8 values can be displayed with a alter-
nating time between 2 and 20 seconds. Plain text can be displayed in the 14-segment area
(text is limited to 16 characters and is scrolled if needed (marquee text)).
The indicator also displays the quality of the measured value. If the status of the displayed
value is 'good' (quality code equal to or above 0x80), no symbol is lit and the indicator
remains in the normal operational state. If the status of the displayed value is 'uncertain'
(quality code between 0x40 and below 0x80), the 'Uncertain measured value status' symbol
is lit. If the status is 'bad' (quality code below 0x40), within the 7-segment area the display
will show "BAD-" and the channel number where the bad value is published. The entered text
continues to be displayed in the 14-segment area and the bar graph is not shown.
22 Endress+Hauser
RID16 Operating the field indicator
PLC
Visualization and monitoring
e. g. P View, FieldCare
and diagnostic software
PROFIBUS-DP
0 - 10 bar 0 - 10 bar
RID16 RID14
Up to 32 devices per segment
A0021436-EN
Endress+Hauser 23
Operating the field indicator RID16
They do not require any settings and they are not assigned an address.
Each field device on the PA segment is assigned a PROFIBUS DP address and acts like a DP
slave. Each slave is only assigned to one Class 1 master. The masters communicate directly
with the slaves:
• A Class 1 master, such as a PLC, retrieves the field device data with the cyclic service.
• A Class 2 master, such as FieldCare, sends and retrieves data from the field devices with
the acyclic service.
A link is recognized by the master and is a user of the PROFIBUS DP system. It is assigned a
DP address and is therefore no longer transparent for cyclic data exchange of the master
with the field devices. Instead it retains the device data in a data buffer which can be read
cyclically by a Class 1 master. Therefore a link must be configured.
On the PROFIBUS PA side the link behaves like a PA master. It retrieves the data cyclically
from the field devices and saves them in a data buffer. Each field device is assigned to a PA
address which may only occur once in the individual link. It can be present in another link
segment however.
For acyclic data exchange with a Class 2 master the link is virtually transparent.
Once the link address (DP address) and the device address (PA address) have been specified,
any field device can be addressed.
Since the field indicator is only a listener, it does not appear as an active user on the bus and does not
require its own bus address. Therefore the indicator can also not be addressed directly by the master. The
indicator listens to the cyclic data traffic on the bus and presents the corresponding values on the display.
24 Endress+Hauser
RID16 Operating the field indicator
PC Configuration software
Configuration kit USB-Box
USB
.
A0021549-EN
Fig. 15: Configuration of the field indicator via the interface adapter
No power should be supplied via the bus if configuring the PROFIBUS® PA indicator with the DTM via the
CDI interface!
To ensure a connection to the device can be established, operation must be set to "Remote" at the DIP
switches. Furthermore write protection, which can be enabled and disabled via the DIP switches, must be
disabled so that the parameters of the field indicator can be modified via the DTM.
The DIP switches are described in the "Operation" section ( ä 21).
Endress+Hauser 25
Operating the field indicator RID16
A0021499
OFF
1 2 4 8 16 32 64 Offset - AI2 Write pro- Remote
tection
6.5.2 Choosing between operation via DIP switches and remote op-
eration
When the device is operated via the DIP switches only 2 values are displayed even if more display values
were configured previously in the configuration software.
The bargraph is not displayed when the device is operated via the DIP switches.
Via the "Remote/DIP" DIP switch users can specify whether configuration is possible onsite
via the DIP switches or remotely via the DTM and PC configuration software. If the switch is
set to "OFF" (remote), all the switches apart from "WRITE LOCK" are disabled. If the switch is
set to "ON", all the DIP switches work and operation via the DTM is not possible.
26 Endress+Hauser
RID16 Operating the field indicator
Endress+Hauser 27
Commissioning RID16
7 Commissioning
Step Display
1 All segments on
3 Manufacturer name
4 Device name
5 Firmware version
6 Device revision
7a A published value
Normal indicating mode commences as soon as the switch-on procedure is completed. Var-
ious measured values and/or status values appear on the display.
7.3 Commissioning
Note the following points:
described on ä 19.
• The files required for commissioning and network configuration can be obtained as
• The field indicator acts solely as a listener. This means that the device listens on the bus
for values that should be displayed. The device does not have an address of its own and is
not an active bus user.
An address of a sensor connected to the PROFIBUS PA network can be selected for each of
the 8 channels of the indicator. The first published value of the selected address is listed in
the next step. The selected value is then displayed by the device. The first published value of
the selected address is listed in the next step. The selected value is then displayed by the
device.
If an address publishes more than one value, additional values can be selected manually. This
address generates a configuration error in the indicator once the bus has been reconfigured
or a published device has been removed. If only the displayed value of the device is no longer
available, the indicator switches automatically to the next value published to this address.
28 Endress+Hauser
RID16 Maintenance
8 Maintenance
The device does not require any special maintenance and servicing work.
9 Accessories
Various accessories are available for the device, and these can be ordered with the device or
at a later stage from Endress+Hauser. Detailed information on the order code in question is
available from your local Endress+Hauser Sales Center or on the product page of the
Endress+Hauser website: www.endress.com.
Designation Description
Protective cover
A0021548
Designation Description
Fieldbus connector
Interface cable Commubox FXA291 incl. FieldCare Device Setup + DTM Library
Endress+Hauser 29
Troubleshooting RID16
10 Troubleshooting
Always start troubleshooting with the checklists below if faults occur after start up or during
operation. This takes you directly (via various queries) to the cause of the problem and the
appropriate remedial measures.
No display visible - no connec- 1. For fault elimination, see under "Faulty connection to the fieldbus system"
tion to the fieldbus system
2. Other possible causes of error:
– Defective electronics module » Test with spare module » Order spare
part
– Defective housing (internal electronics) » Test with spare
housing » Order spare part
3. Defective field indicator Replace field indicator
No display visible - connection to 1. Check whether the display module is correctly connected to the electron-
the fieldbus system is estab- ics module, ä 12.
lished, however
2. Defective display » Test with spare display » Order spare part
3. Defective electronics module » Test with spare module » Order spare part
A connection cannot be established between the fieldbus system and the indicator.
Check the following points:
Fieldbus voltage Check whether a minimum bus voltage of 9 V DC is present at the +/-
terminals. Permitted range: 9 to 32 V DC
Network structure Check the permitted fieldbus cable length and number of spurs, ä 16
ä 30
30 Endress+Hauser
RID16 Troubleshooting
Endress+Hauser 31
Troubleshooting RID16
a0012119
32 Endress+Hauser
RID16 Troubleshooting
Endress+Hauser 33
Return RID16
11 Return
The measuring device must be returned if repairs or a factory calibration are required, or if
the wrong measuring device has been ordered or delivered. According to legal regulations
Endress+Hauser, as an ISO-certified company, is required to follow certain procedures when
handling returned products that are in contact with the medium.
To ensure the safe, quick and professional return of your device,
visit the Endress+Hauser website (www.services.endress.com/return-material) for informa-
tion on the procedure to be followed and basic conditions.
12 Disposal
The device contains electronic components and must therefore be disposed of as electronic
waste. Comply with local disposal regulations.
34 Endress+Hauser
RID16 Technical data
13 Technical data
PROFIBUS® PA
• PROFIBUS® PA in accordance with EN 50170 Volume 2, IEC 61158-2 (MBP)
• FDE (Fault Disconnection Electronic) = 0 mA
• Data transmission rate: supported baud rate = 31.25 kBit/s
• Signal coding = Manchester II
• Connection data in accordance with IEC 60079-11 FISCO, Entity
Protocol-specific data
PROFIBUS® PA
Basic data
Indicator for PROFIBUS PA, can be used in conjunction with PROFILE 2 and PROFILE 3 (3.0, 3.01 and 3.02)
devices
Device master files (GSD) How to acquire device master files (GSD) and device drivers:
• FieldCare/DTM: www.endress.com → Select country → Solutions →
Field Network Engineering → Fieldbus device integration → PROFIBUS
→ PROFIBUS® GSD files and certificates
Electrical connection
A0021528
Supply voltage
Voltage is supplied via the fieldbus.
U = 9 to 32 V DC, polarity-independent (max. voltage Ub = 35 V).
Endress+Hauser 35
Technical data RID16
Current consumption
11 mA
Cable entry
The following cable entries are available:
‣ Thread NPT1/2
‣ Thread M20
‣ Thread G1/2
‣ 2x gland NPT1/2 + 1x dummy plug
‣ 2x gland M20 + 1 x dummy plug
13.0.3 Installation
Installation instructions
Mounting location
Wall or pipe mounting (see 'Accessories')
Orientation
No restrictions, the orientation depends on the readability of the display.
13.0.4 Environment
Storage temperature
-40 to +80 °C (-40 to 176 °F)
Altitude
Up to 4000 m (13100 ft.) above mean sea level in accordance with IEC 61010-1, CSA
1010.1-92
Climate class
According to IEC 60654-1, Class C
Humidity
• Condensation permitted as per IEC 60 068-2-33
• Max. rel. humidity: 95% as per IEC 60068-2-30
Degree of protection
IP67. NEMA 4X.
36 Endress+Hauser
RID16 Technical data
Measuring category
Measuring category II as per IEC 61010-1. The measuring category is provided for measur-
ing on power circuits that are directly connected electrically with the low-voltage network.
Degree of contamination
Pollution degree 2 as per IEC 61010-1.
Endress+Hauser 37
Technical data RID16
Design, dimensions
Die-cast aluminum housing for general applications, or optional stainless steel housing
A0011162
Weight
• Plastic housing: approx. 500 g (1.1 lb)
• Aluminum housing: approx. 1.7 kg (3.75 lb)
Material
Housing Nameplate
Terminals
Screw terminals for cables up to max. 2.5 mm2 (14 AWG) plus ferrule
38 Endress+Hauser
RID16 Technical data
Display elements
a0011309
• Display range
-9999 to +99999
Configuration
PROFIBUS® PA
The parameters can either be configured remotely via the DTM and configuration software
or locally via DIP switches.
Endress+Hauser 39
Technical data RID16
CE mark
The device meets the legal requirements of the EC directives. Endress+Hauser confirms that
the device has been successfully tested by applying the CE mark.
Ex-approval
Information about currently available Ex versions (ATEX, FM, CSA, etc.) can be supplied by
your E+H Sales Center on request. All explosion protection data are given in a separate doc-
umentation which is available upon request.
CSA GP
CSA General Purpose
13.0.8 Documentation
‣ Overview brochure: System Components and Data Managers - Solutions for a Complete
Measuring Point: FA00016K/09
‣ ATEX Safety instructions:
– ATEX II2G Ex ia IIC: XA00099R/09
40 Endress+Hauser
RID16 Appendix
14 Appendix
Display duration
Description Use this function to set the length of time the measured values are displayed if the
values alternate on the display. The display only alternates automatically between
values if more than one measured value is defined.
Info:
• The Value 1 display - Value 8 display parameters are used to specify which mea-
sured values are shown on the local display.
• The display format of the displayed measured values is specified using the Format
display parameter.
Factory setting 5
Source address
Description Allows users to select the bus address of the device whose values are to be displayed.
Factory setting 0
Endress+Hauser 41
Appendix RID16
Offset source
Description Indicates the index (offset) of the first byte of the value to be displayed from the pay-
load data received.
Factory setting 0
Description
Factory setting
Enable % symbol
Bargraph 0%
Factory setting 0
42 Endress+Hauser
RID16 Appendix
Bargraph 100%
Decimal places
Description Use this function to select the number of decimal places for the display value.
This setting does not affect the accuracy of the device when measuring or calculat-
ing.
Only visible if data type = analog.
Current diagnostics
Visible offline No
Writable offline No
Last diagnostics
Description The last diagnostic message with the highest priority appears on the display.
Endress+Hauser 43
Appendix RID16
Description Displays the number of diagnostic messages currently pending in the device.
Visible offline No
Writable offline No
Locking status
Visible offline No
Writable offline No
Device name
Device tag
44 Endress+Hauser
RID16 Appendix
Serial number
Order code
Description Displays the order code of the device. It can also be found on the nameplate. The
code is generated by reversibly transforming the extended order code which indi-
cates the attribute of all the device features in the product structure. In contrast to
the extended order code, the device features cannot be read directly from the order
code.
Uses of the order code
• To order an identical spare device.
• To identify the device quickly and easily, e.g. when contacting the manufacturer.
Device reset
Description Use this function to reset the device configuration - either entirely or in part - to a
defined state.
Visible offline No
Writable offline No
Endress+Hauser 45
Appendix RID16
Description Disable the parameter write protection with the user-specific access code.
Factory setting 0
"System" submenu
Locking status
Visible offline No
Writable offline No
46 Endress+Hauser
RID16 Appendix
"Display" submenu
Display duration
This submenu contains the following parameters in addition to those described in the Operation ‣ Display value X
menu ( ä 41).
Data type
Description For selecting the data type (analog/digital) whose values are to be displayed.
Data direction
Description For selecting the direction of the data that are to be displayed. It is possible to dis-
play data that are sent from the device (slave) to the master or from the master to
the field device.
Endress+Hauser 47
Appendix RID16
Factor value
Description Use this function to enter a factor by which the measured value should be multiplied.
Only visible if data type = analog
Options 1E-06, 1E-05, 1E-04, 1E-03, 1E-02, 1E-01, 1E-00, 1E+01, 1E+02, 1E+03, 1E+04,
1E+05, 1E+06
Offset value
Description Sets the offset for the measured value. The value indicated is added to the measured
value.
Only visible if data type = analog
Factory setting 0
Digital representation
Options 1 = On; 0 = Off, 0 = On; 1 = Off, 1 = Open; 0 = Close, 0 = Open; 1 = Close, Display as
decimal value
"Diagnostics" submenu
This submenu contains the following parameters in addition to those described in the Diagnostics menu
( ä 43).
48 Endress+Hauser
RID16 Appendix
Description Displays the extended order code. The extended order code indicates the attribute of
all the features of the product structure for the device.
Device revision
Hardware version
Description Displays the hardware version and is used to identify the device. Only read access.
Manufacturer name
Endress+Hauser 49
Appendix RID16
50 Endress+Hauser
RID16
Index
B Data direction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Bus access methods and data transmission . . . . . . . . . . 23 Data type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Decimal places . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
C Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Cable gland . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Device name . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Cable specification Device reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Bus termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Device revision . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Cable type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Device tag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Further information . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Digital representation . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Maximum overall cable length. . . . . . . . . . . . . . . . . . 17 Display duration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Maximum spur length. . . . . . . . . . . . . . . . . . . . . . . . . 17 Enable % symbol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Number of field devices. . . . . . . . . . . . . . . . . . . . . . . . 17 Enter access code. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Shielding and grounding. . . . . . . . . . . . . . . . . . . . . . . 18 Extended order code . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Configuration programs . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Factor value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Configuring an offset . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Hardware version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Last diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
D Locking status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Device ID, addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Manufacturer name . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Offset source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
DIP switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Offset value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
DTM operating parameters . . . . . . . . . . . . . . . . . . . . . . . 41 Order code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Serial number. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
E Source address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Electrical symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Pipe mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Error category
Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Q
Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Quick wiring guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
F R
Fieldbus connector. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Release . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
I S
Incoming acceptance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Safety symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Setting the bus address. . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
M Status messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30–31
Menu Switching write protection on/off. . . . . . . . . . . . . . . . . . . 26
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Symbols
Expert . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 ~ for certain types of information . . . . . . . . . . . . . . . . . 5
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 ~ in graphics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Mounting Electrical symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Safety symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
T
N Technical data for field device connector. . . . . . . . . . . . . 16
Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Terminal assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Transport and storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
O
Operating parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 W
Operation via DIP switches and remote operation . . . . 26 Wall mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
P
Parameter
Access status tooling . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Actual diagnostics count . . . . . . . . . . . . . . . . . . . . . . . 44
Bargraph 0%. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Bargraph 100% . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Current diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Endress+Hauser 51
www.addresses.endress.com