0% found this document useful (0 votes)
38 views52 pages

Ba01268ken 0113

Controlador electrónico

Uploaded by

s2gmf65js9
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
38 views52 pages

Ba01268ken 0113

Controlador electrónico

Uploaded by

s2gmf65js9
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 52

BA01268K/09/EN/01.

13 Products Solutions Services


71232744
Valid as of FW version
01.00.xx

Operating Instructions
RID16
Field indicator
with PROFIBUS® PA protocol
Brief overview
For quick and straightforward commissioning:

Safety instructions  ä6

Installation  ä9

Wiring  ä 12

Display and operating elements  ä 22

Information about configuration and operating programs from other


manufacturers.
Information about setting the HW write protection

Commissioning  ä 28

Endress+Hauser
RID16

Table of contents
1 Document information . . . . . . . . . . . . . . 4 10.2 Status messages . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
10.3 Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
1.1 Document function . . . . . . . . . . . . . . . . . . . . . . . . . . 4 10.4 Software history and overview of compatibility . 33
1.2 Document conventions . . . . . . . . . . . . . . . . . . . . . . . 4
11 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
2 Safety instructions . . . . . . . . . . . . . . . . . . 6
2.1 Requirements for the personnel . . . . . . . . . . . . . . . 6
12 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . 34
2.2 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.3 Occupational safety . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.4 Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 13 Technical data . . . . . . . . . . . . . . . . . . . . 35
2.5 Product safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
14 Appendix . . . . . . . . . . . . . . . . . . . . . . . . 41
3 Identification . . . . . . . . . . . . . . . . . . . . . . 8
14.1 DTM operating parameters . . . . . . . . . . . . . . . . . . 41
3.1 Device designation . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.2 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
3.3 Certificates and approvals . . . . . . . . . . . . . . . . . . . . 8

4 Installation . . . . . . . . . . . . . . . . . . . . . . . . 9
4.1 Incoming acceptance, transport, storage . . . . . . . . 9
4.2 Installation conditions . . . . . . . . . . . . . . . . . . . . . . . 9
4.3 Installation instructions . . . . . . . . . . . . . . . . . . . . 10
4.4 Post-installation check . . . . . . . . . . . . . . . . . . . . . 11

5 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.1 Connecting the cable to the field indicator . . . . 12
5.2 Connection to PROFIBUS® PA . . . . . . . . . . . . . . . 14
5.3 PROFIBUS® PA cable specifications . . . . . . . . . . 16
5.4 Degree of protection . . . . . . . . . . . . . . . . . . . . . . . 19
5.5 Post-connection check . . . . . . . . . . . . . . . . . . . . . 20

6 Operating the field indicator . . . . . . . . 21


6.1 Quick operation guide . . . . . . . . . . . . . . . . . . . . . 21
6.2 Display and operating elements . . . . . . . . . . . . . 22
6.3 PROFIBUS® technology . . . . . . . . . . . . . . . . . . . . 22
6.4 Configuration via interface & PC configuration
software "FieldCare Device Setup" . . . . . . . . . . . . 25
6.5 Hardware settings . . . . . . . . . . . . . . . . . . . . . . . . . 26

7 Commissioning . . . . . . . . . . . . . . . . . . . . 28
7.1 Post-installation check . . . . . . . . . . . . . . . . . . . . . 28
7.2 Switching on the field indicator . . . . . . . . . . . . . 28
7.3 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

8 Maintenance . . . . . . . . . . . . . . . . . . . . . . 29

9 Accessories . . . . . . . . . . . . . . . . . . . . . . . 29
9.1 Device-specific accessories . . . . . . . . . . . . . . . . . . 29
9.2 Communication-specific accessories . . . . . . . . . 29

10 Troubleshooting . . . . . . . . . . . . . . . . . . . 30
10.1 Troubleshooting instructions . . . . . . . . . . . . . . . . 30

Endress+Hauser 3
Document information RID16

1 Document information

1.1 Document function


These Operating Instructions contain all the information that is required in various phases
of the life cycle of the device: from product identification, incoming acceptance and storage,
to mounting, connection, operation and commissioning through to troubleshooting, main-
tenance and disposal.

1.2 Document conventions

1.2.1 Safety symbols

Symbol Meaning

DANGER!
This symbol alerts you to a dangerous situation. Failure to avoid this situation
A0011189-EN
will result in serious or fatal injury.

WARNING!
This symbol alerts you to a dangerous situation. Failure to avoid this situation
A0011190-EN
can result in serious or fatal injury.

CAUTION!
This symbol alerts you to a dangerous situation. Failure to avoid this situation
A0011191-EN
can result in minor or medium injury.

NOTE
This symbol contains information on procedures and other facts which do not
A0011192-EN
result in personal injury.

1.2.2 Electrical symbols

Symbol Meaning

Direct current
A0011197 A terminal to which DC voltage is applied or through which direct current flows.

Alternating current
A0011198 A terminal to which alternating voltage is applied or through which alternating current flows.

Direct current and alternating current


A0017381
• A terminal to which alternating voltage or DC voltage is applied.
• A terminal through which alternating current or direct current flows.

Ground connection
A0011200 A grounded terminal which, as far as the operator is concerned, is grounded via a grounding sys-
tem.

Protective ground connection


A0011199 A terminal which must be connected to ground prior to establishing any other connections.

Equipotential connection
A connection that has to be connected to the plant grounding system: This may be a potential
A0011201
equalization line or a star grounding system depending on national or company codes of practice.

ESD - electrostatic discharge


Protect the terminals from electrostatic discharge. Failure to observe this may result in destruction
of parts of the electronics.
A0012751

4 Endress+Hauser
RID16 Document information

1.2.3 Symbols for certain types of information

Symbol Meaning

Permitted
Indicates procedures, processes or actions that are permitted.
A0011182

Preferred
Indicates procedures, processes or actions that are preferred.
A0011183

Forbidden
Indicates procedures, processes or actions that are forbidden.
A0011184

Tip
Indicates additional information.
A0011193

Reference to documentation
Refers to the corresponding device documentation.
A0011194

Reference to page
Refers to the corresponding page number.
A0011195

Reference to graphic
Refers to the corresponding graphic number and page number.
A0011196

Series of steps
, , …
A0015662

 Result of a sequence of actions

Help in the event of a problem

A0013562

1.2.4 Symbols in graphics

Symbol Meaning

1, 2, 3, etc. Item numbers

Series of steps
, , …
A0015662

A, B, C, etc. Views

A-A, B-B, C-C, Sections


etc.

Flow direction
A0013441

Hazardous area
- A0011187
Indicates a hazardous area.

Safe area (non-hazardous area)


. Indicates the non-hazardous area.
A0011188

Endress+Hauser 5
Safety instructions RID16

2 Safety instructions

2.1 Requirements for the personnel


The personnel for installation, commissioning, diagnostics and maintenance must fulfill the
following requirements:
‣ Trained, qualified specialists must have a relevant qualification for this specific function
and task
‣ Are authorized by the plant owner/operator
‣ Are familiar with federal/national regulations
‣ Before beginning work, the specialist staff must have read and understood the instruc-
tions in the Operating Instructions and supplementary documentation as well as in the
certificates (depending on the application)
‣ Following instructions and basic conditions
The operating personnel must fulfill the following requirements:
‣ Being instructed and authorized according to the requirements of the task by the facility's
owner-operator
‣ Following the instructions in these Operating Instructions

2.2 Designated use


‣ The device is a field indicator designed for connection to a fieldbus.
‣ The device is designed for installation in the field.
‣ The manufacturer accepts no liability for damages resulting from incorrect use or use
other than that designated.
‣ Safe operation is only guaranteed if operators comply strictly with the Operating Instruc-
tions.
‣ Only operate the device in the designated temperature range.

2.3 Occupational safety


For work on and with the device:
‣ Wear the required personal protective equipment according to federal/national regula-
tions.

2.4 Operational safety


Risk of injury!
‣ Operate the device in proper technical condition and fail-safe condition only.
‣ The operator is responsible for interference-free operation of the device.
Conversions to the device
Unauthorized modifications to the device are not permitted and can lead to unforeseeable
dangers.
‣ If, despite this, modifications are required, consult with Endress+Hauser.
Repair
To ensure continued operational safety and reliability,
‣ Carry out repairs on the device only if they are expressly permitted.
‣ Observe federal/national regulations pertaining to repair of an electrical device.
‣ Use original spare parts and accessories from Endress+Hauser only.

6 Endress+Hauser
RID16 Safety instructions

Environmental requirements
If a plastic transmitter housing is permanently exposed to certain steam and air mixtures,
this can damage the housing.
‣ If you are unsure, please contact your Endress+Hauser Sales Center for clarification.
‣ If used in an approval-related area, observe the information on the nameplate.

Hazardous area
Measuring systems for use in hazardous areas are accompanied by separate "Ex documenta-
tion", which is an integral part of these Operating Instructions. Strict compliance with the
installation instructions and connection data as stated in this supplementary documentation
is mandatory!

2.5 Product safety


This measuring device is designed in accordance with good engineering practice to meet
state-of-the-art safety requirements, has been tested, and left the factory in a condition in
which it is safe to operate.
It meets general safety standards and legal requirements. It also complies with the EC direc-
tives listed in the device-specific EC Declaration of Conformity. Endress+Hauser confirms
this by affixing the CE mark to the device.

Endress+Hauser 7
Identification RID16

3 Identification

3.1 Device designation

3.1.1 Nameplate
The right device?
Compare the nameplate on the device with the following diagram:

A0021542

Fig. 1: Nameplate of the field indicator (example)


1 Order code, serial number and extended order code of the device
2 Power supply
3 Ambient temperature range
4 Firmware version
5 Degree of protection and type of approval
6 Approvals

3.2 Scope of delivery


The scope of delivery of the field indicator comprises:
• Field indicator
• Brief Operating Instructions as hard copy
• Operating Instructions on CD-ROM
• ATEX - safety instructions for using a device approved for hazardous areas, optional
• Optional accessories (e.g. pipe mounting bracket), see 'Accessories' section

3.3 Certificates and approvals

CE mark, Declaration of Conformity


The device is designed in accordance with good engineering practice to meet state-of-the-
art safety requirements, has been tested, and left the factory in a condition in which it is safe
to operate.
The device complies with the standards EN 61 010-1 "Protection Measures for Electrical
Equipment for Measurement, Control, Regulation and Laboratory Procedures" and with the
EMC requirements of IEC/EN 61326.
The device described in these Operating Instructions therefore complies with the statutory
requirements of the EU Directives. The manufacturer confirms that the device has been suc-
cessfully tested by applying the CE mark.
The field indicator has successfully passed the PROFIBUS PA physical layer test. As a "non-
active" bus user it does interfere with Profibus data transfer.
CSA General Purpose.

8 Endress+Hauser
RID16 Installation

4 Installation

4.1 Incoming acceptance, transport, storage


Compliance with the permitted environmental and storage conditions is mandatory. Precise
specifications are provided in the "Technical data" section .

4.1.1 Incoming acceptance


On receipt of the goods, check the following points:
• Is the packaging or the content damaged?
• Is the delivery complete? Compare the scope of delivery against the information on your
order form. See also the "Scope of delivery" section ( ä 8).

4.1.2 Transport and storage


Please note the following:
• Pack the device so that is protected against impact for storage and transport. The original
packaging provides optimum protection.
• The permitted storage temperature is -40 to +80 °C (-40 to +176 °F); it is possible to store
the device at borderline temperatures for a limited period (48 hours maximum).

4.2 Installation conditions


The indicator is designed for use in the field.
The orientation depends on the readability of the display.
Operating temperature range:
-40 to +80 °C (-40 to +176 °F)
NOTICE
Shorter display operating life at higher temperatures
‣ Where possible do not operate the device in the higher temperature range.
The display can react slowly at temperatures < -20 °C (-4 °F).
The readability of the display is no longer guaranteed at temperatures < -30 °C (-22 °F).

4.2.1 Dimensions

a0011152

Fig. 2: Dimensions of the field indicator; dimensions in mm (in)

4.2.2 Mounting location


Information about the conditions (such as the ambient temperature, degree of protection,
climate class etc.) that must be present at the installation point so that the device can be
mounted correctly, is provided in the "Technical data" section.

Endress+Hauser 9
Installation RID16

4.3 Installation instructions


The device can be mounted directly on the wall or the optional mounting bracket can be used
for wall and pipe mounting ( å 3).

4.3.1 Mounting directly on the wall


Proceed as follows to mount the device directly on the wall:
1. Drill 4 holes
2. Fit the device on the wall with 4 screws (5 mm (0.2 in)).

4.3.2 Pipe mounting


The mounting bracket is suitable for pipes with a diameter between 1" - 5". The mounting kit
consists of a mounting plate (item 1), 2 clamps (item 2) and 4 screws (item 3).
Proceed as follows to mount the device on a pipe:

A0011269

Fig. 3: Mounting the field indicator on a pipe with mounting kit, steps 1-2

A0011270

Fig. 4: Mounting the field indicator on a pipe with mounting kit, steps 3-4
Mounting kit, comprising:
1: Mounting plate
2: Mounting bracket
3: 4 screws

10 Endress+Hauser
RID16 Installation

4.4 Post-installation check


After installing the device, always run the following final checks:

Device condition and specifications Notes

Is the device damaged (visual inspection)? Visual inspection

Is the seal undamaged? Visual inspection

Is the device securely fastened to the wall or the -


mounting plate?

Is the front of the housing securely closed? -

Does the device correspond to the measuring point See 'Technical data' section,
specifications, e.g. ambient temperature range etc.?

Endress+Hauser 11
Wiring RID16

5 Wiring
! WARNING
Danger of explosion if unit is connected incorrectly in hazardous area
‣ When connecting Ex-approved devices please take special note of the instructions and
connection schematics in the Ex-specific supplement to these Operating Instructions. If
you have any questions, please do not hesitate to contact your E+H representative.
NOTICE
Electronics can be destroyed if unit is connected incorrectly
‣ Switch off power supply before installing or connecting the device. Failure to observe this
may result in destruction of parts of the electronics.
‣ The post connector is only used to connect the display. If other devices are connected, this
can result in the destruction of parts of the electronics.
Devices can be connected to the PROFIBUS® PA in two ways:
• Via a conventional cable gland  ä 15
• Via a fieldbus connector (optional, available as an accessory)  ä 15

5.1 Connecting the cable to the field indicator

5.1.1 Preparing to connect

Mounting the cable gland or fieldbus connector, plastic housing

A0021557

Fig. 5: Mounting the cable gland or fieldbus connector


A Mounting plate
B Cable gland
C Fieldbus connector

1. First of all using a suitable tool, such as a screwdriver, open one of the indentations pro-
vided on the bottom of the device. Open the indentation at room temperature, as oth-
erwise the housing could be damaged at very low temperatures.
2. Install the mounting plate for the cable gland and fieldbus connector. The mounting
plate is supplied with the field indicator, see the scope of delivery.
3. Insert the cable gland or the fieldbus connector into the mounting plate. A cable gland
is supplied with the field indicator, see the scope of delivery. The fieldbus connector is
available as an accessory.

Mounting the cable gland or fieldbus connector, aluminum housing


In the case of the aluminum housing, the cable gland or the fieldbus connector can be
screwed into the housing directly. A mounting plate is not required.

12 Endress+Hauser
RID16 Wiring

Procedure to wire the field indicator

A0011636

Fig. 6: Opening the housing of the field indicator


1 Internal ground terminal (only aluminum housing)

1. Open the cable gland and open the housing cover.


2. Guide the cable through the cable gland.
3. Connect the cable as shown in  å 8.
4. Mount the cable shield grounding clamps (only aluminum housing).

a0014935

Fig. 7: Mounting the cable shield grounding clamps (only aluminum housing)

5. Tighten the cable gland again and close the housing cover.
6. To avoid any mistakes when connecting the unit, follow the instructions in the "Post-
connection check" section.

Endress+Hauser 13
Wiring RID16

5.1.2 Quick wiring guide

Terminal assignment

A0021544

Fig. 8: Terminal assignment

ESD - electrostatic discharge


Protect the terminals from electrostatic discharge. Failure to observe this may result in
destruction or malfunction of parts of the electronics.

Terminal Terminal assignment

+ PROFIBUS® PA connection (+)

- PROFIBUS® PA connection (-)

5.2 Connection to PROFIBUS® PA


Devices can be connected to the PROFIBUS® PA in two ways:
• Via a conventional cable gland  ä 15
• Via a fieldbus connector (optional, available as an accessory)  ä 15
NOTICE
The device and fieldbus cable can be damaged by electrical voltage
‣ Switch off power supply before installing or connecting the device.
‣ It is recommended to ground the unit via one of the grounding screws.
‣ If the shield of the fieldbus cable is grounded at more than one point in systems that do
not have additional potential equalization, mains frequency equalizing currents can
occur that damage the cable or shield. In such cases the shielding of the fieldbus cable is
to be grounded on one side only, i.e. it must not be connected to the ground terminal of
the housing. The shield that is not connected should be insulated!
It is not advisable to loop the fieldbus via conventional cable glands. If you want to replace just one mea-
suring device at a later date, you will have to interrupt bus communication.

14 Endress+Hauser
RID16 Wiring

5.2.1 Cable gland or cable entry


Please also observe the general procedure on  ä 12.

A0012567

Fig. 9: Connection to the PROFIBUS® PA fieldbus cable


A Terminals - fieldbus communication and power supply
B Internal ground terminal
C External ground terminal
D Shielded fieldbus cable

‣ The terminals for the fieldbus connection (1+ and 2-) are not polarity sensitive.
‣ Conductor cross-section:
2
– Max. 2.5 mm (14 AWG)
‣ Always use a shielded cable for the connection.

5.2.2 Fieldbus connector

Optionally, a fieldbus connector can be installed in the field housing instead of a cable gland.
Fieldbus connectors can be ordered as an accessory from Endress+Hauser (see Section 8
"Accessories").
The PROFIBUS® PA connection technology allows measuring devices to be connected to the
fieldbus via standardized mechanical connections such as T-boxes, junction box modules etc.
This connection technology using pre-fabricated junction box modules and plug-in connec-
tors offers considerable advantages over conventional wiring systems:
• Field devices can be removed, replaced or added at any time during normal operation.
Communication is not interrupted.
• Installation and maintenance are considerably easier.
• Existing cable infrastructures can be used and extended immediately, e.g. when creating
new star distributor systems using 4-channel or 8-channel distribution modules.
Shielding the supply line/T-box
Always use cable glands with good EMC properties, where possible with wrapround cable
shielding (Iris spring). This requires minimum differences in potential, and possibly poten-
tial equalization.
• The shielding of the PA cable may not be interrupted.
• The shielding connection must always be kept as short as possible.
Ideally cable glands with Iris springs should be used to connect the shield. The Iris spring,
which is located inside the gland, connects the shield to the T-box housing. The shielding
braid is located under the Iris spring.

Endress+Hauser 15
Wiring RID16

When the armored thread is screwed tight, the Iris spring is pressed against the shield,
thereby establishing a conductive connection between the shield and the metal housing.
A junction box or a plug-in connection must be considered part of the shielding (Faraday
shield). This applies in particular to remote boxes if such boxes are connected to a PROFI-
BUS® PA device via a plug-in cable. In such cases, you must use a metal connector where the
cable shielding is connected to the connector housing (e.g. pre-terminated cables).

A0021545

Fig. 10: Connectors for connection to the PROFIBUS® PA fieldbus

Pin assignment / color codes


D 7/8" connector D M12 connector
A Fieldbus connector 1 Brown wire: PA+ (terminal 1) 1 Gray wire: shielding
B Field indicator 2 Green-yellow wire: grounding 2 Brown wire: PA+ (terminal 1)
C Connector on the housing (male) 3 Blue wire: PA- (terminal 2) 3 Blue wire: PA- (terminal 2)
4 Gray wire: shielding 4 Green-yellow wire: grounding
5 Positioning key 5 Positioning key

Technical data for connector:


• IP 67 degree of protection (NEMA 4x)
• Ambient temperature range: –40 to +105 °C (–40 to +221 °F)

5.3 PROFIBUS® PA cable specifications

5.3.1 Cable type


Twin-core cables are generally advisable for connecting the device to the fieldbus. Following
IEC 61158-2 (MBP), four cable types (A, B, C, D) can be used for FOUNDATION Fieldbus™,
only two of which (cable types A and B) are shielded.

• Cable types A or B are particularly preferable for new installations. Only these types have
cable shielding that guarantees adequate protection from electromagnetic interference
and thus the most reliable data transfer. In the case of cable type B, several fieldbuses
(same degree of protection) may be operated in one cable. No other circuits are permissible
in the same cable.
• Practical experience has shown that cable types C and D should not be used due to the lack
of shielding, since the freedom from interference frequently does not meet the require-
ments described in the standard.
The electrical data of the fieldbus cable have not been specified but determine important
characteristics of the design of the fieldbus, such as distances bridged, number of users, elec-
tromagnetic compatibility, etc.
Suitable fieldbus cables (type A) from various manufacturers for non-hazardous areas are
listed below:
• Siemens: 6XV1 830-5BH10

16 Endress+Hauser
RID16 Wiring

• Belden: 3076F
• Kerpen: CeL-PE/OSCR/PVC/FRLA FB-02YS(ST)YFL

5.3.2 Maximum overall cable length


The maximum network expansion depends on the type of protection and the cable specifi-
cations. The overall cable length combines the length of the main cable and the length of all
spurs (>1 m/3.28 ft). Please note the following:

• The maximum permissible overall cable length depends on the cable type used.
• If repeaters are used, the maximum cable length is doubled. A maximum of three repeaters
are permitted between the user and master.

Type A Type B

Cable structure Twisted pair of cores, shielded Individual or multiple pairs of


twisted cores, complete shield

Wire cross-section 0.8 mm2 (AWG 18) 0.32 mm2 (AWG 22)

Loop resistance (direct current) 44 /km 112 /km

Characteristic impedance at 100  ± 20% 100  ± 30%


31.25 kHz

Attenuation constant at 39 kHz 3 dB/km 5 dB/km

Capacitive asymmetry 2 nF/km 2 nF/km

Envelope delay distortion 1.7 ms/km *


(7.9 to 39 kHz)

Shield coverage 90% *

Max. cable length (incl. spurs >1 1900 m (6233 ft) 1200 m (3937 ft)
m)

* not specified

5.3.3 Maximum spur length

The line between the distribution box and field device is described as a spur.
In the case of non-Ex applications, the max. length of a spur depends on the number of spurs
(>1 m/3.28 ft):

Number of spurs 1 to 12 13 to 14 15 to 18 19 to 24 25 to 32

Max. length per spur 120 m (393 90 m (295 60 m (196 30 m (98 ft) 1 m (3.28
ft) ft) ft) ft)

5.3.4 Number of field devices

In systems that meet FISCO with Ex ia type of protection, the line length is limited to max.
1000 m (3280 ft). A maximum of 32 users per segment in non-Ex areas or a maximum of
10 users in an Ex-area (Ex ia IIC) is possible. The actual number of users must be determined
during the planning stage.

Endress+Hauser 17
Wiring RID16

5.3.5 Shielding and grounding

Optimum electromagnetic compatibility (EMC) of the fieldbus system can only be guaran-
teed if the system components and, in particular, the lines are shielded and the shield forms
as complete a cover as possible. A shield coverage of 90% is ideal.
• To ensure an optimum EMC protective effect, connect the shield as often as possible to the
reference ground.
• For reasons of explosion protection, you should refrain from grounding however.
To comply with both requirements, the fieldbus system allows three different types of
shielding:
• Shielding at both ends
• Shielding at one end on the feed side with capacitance termination at the field device
• Shielding at one end on the feed side
Experience shows that the best results with regard to EMC are achieved in most cases in
installations with shielding at one end. Appropriate measures with regard to input wiring
must be taken to allow unrestricted operation when EMC interference is present. These
measures have been taken into account for this device. Operation in the event of disturbance
variables as per NAMUR NE21 is possible with shielding at one end.
Where applicable, national installation regulations and guidelines must be observed during
the installation!
Where there are large differences in potential between the individual grounding points, only
one point of the shielding is connected directly with the reference ground. In systems with-

grounded on one side, for example at the fieldbus supply unit or at safety barriers,  å 11.
out potential equalization, therefore, cable shielding of fieldbus systems should only be

A0011645

Abb. 11: Shielding and grounding of the fieldbus cable shield at one end
1 Supply unit
2 Distribution box (T-box)
3 Bus terminator
4 Grounding point for fieldbus cable shield
5 Optional grounding of the field device, isolated from cable shielding.

NOTICE
Equalizing current can damage the bus cable or bus shield
‣ If the shielding of the cable is grounded at more than one point in systems without
potential matching, mains frequency equalizing currents can occur that damage the bus
cable or the bus shield or have a serious effect on signal transmission. In such cases the
shielding of the fieldbus cable is to be grounded on one side only, i.e. it must not be
connected to the ground terminal of the housing. The shield that is not connected should
be insulated!

5.3.6 Bus termination

The start and end of each fieldbus segment must always be terminated by a bus terminator.
With various junction boxes (non-Ex), the bus termination can be activated via a switch. If

18 Endress+Hauser
RID16 Wiring

this is not the case, a separate bus terminator must be installed. Please also note the follow-
ing:
• In the case of a branched bus segment, the measuring device furthest from the segment
coupler represents the end of the bus.
• If the fieldbus is extended with a repeater then the extension must also be terminated at
both ends.

5.3.7 Further information

General information and additional wiring instructions are provided in the manual "Guide-

04), which can also be found on the CD-ROM. (Also available at:  www.endress.de 
lines for planning and commissioning, PROFIBUS ® DP/PA, field communication" (BA034S/

Download).

5.4 Degree of protection


The devices fulfill the requirements for IP 67 degree of protection. Compliance with the fol-
lowing points is mandatory to ensure IP 67 protection is guaranteed after installation or
after service work:
• The housing seal must be clean and undamaged when it is inserted into the groove. The
seal should be cleaned, dried or replaced.
• The connecting cables must be of the specified outer diameter (e.g. M16 x 1.5, cable diam-
eter 5 to 10 mm).
• Replace all unused cable entries with dummy plugs.
• The cable entry seal may not be removed from the cable entry.
• The housing cover and cable entry/entries must be closed securely.
• Install the device in such a way that the cable entries point downwards.

Endress+Hauser 19
Wiring RID16

5.5 Post-connection check


After the electrical installation of the device, always run the following final checks:

Device condition and specifications Notes

Are cables or the device damaged (visual inspection)? -

Electrical connection Notes

Does the supply voltage match the specifications on the nameplate? 9 to 32 V DC

Do the cables used comply with the specifications? Fieldbus cable,  ä 16

Do the cables have adequate strain relief? -

Are the power supply and signal cables correctly connected?  ä 14

Are all the screw terminals well tightened and have the connections of the  ä 16
spring terminals been checked?

Are all the cable entries installed, tightened and sealed?


Cable run with "water trap"?

Are all housing covers installed and firmly tightened?

Electrical connection, fieldbus system Notes

Are all the connection components (T-box, junction boxes, connectors, etc.) -
correctly connected to one another?

Has each fieldbus segment been terminated by a bus terminator at both -


ends?

Has the max. length of the fieldbus cable, as defined in the fieldbus specifi-
cations, been observed?

Has the max. length of the spurs, as defined in the fieldbus specifications,  ä 16
been observed?

Is the fieldbus cable completely shielded (90%) and correctly grounded?

20 Endress+Hauser
RID16 Operating the field indicator

6 Operating the field indicator

6.1 Quick operation guide


Operators have two options for configuring and commissioning the device:
1. Configuration programs
Device-specific parameters are configured via the E+H Service interface (CDI). A special

for this purpose  ä 25


device driver (DTM) for an FDT operating program (e.g. DeviceCare, FieldCare) is available

2. Miniature switches (DIP switches) for local configuration


You can make the following settings for the PROFIBUS® PA interface using miniature
switches (DIP switches) on the rear of the display:
• Setting to specify whether operation is possible via DIP switches or remotely via the DTM
• Setting for the address of the bus users whose values are to be displayed
• Setting for an index (offset)
More information on the hardware settings via DIP switches  ä 26.

A0021500

Fig. 12: Hardware setting via DIP switches


1 ON switch position
2 OFF switch position
3 Write protection

Only 2 display values are displayed when operating via the DIP switches, even if several display values
have been configured via the configuration software.

6.1.1 Listener mode


The field indicator acts solely as a listener, i.e. it does not appear in the bus as an active user
with its own specific address and it also does not increase the traffic in the bus.
The field indicator analyzes the devices active on the bus. Via their addresses these devices
can be assigned to up to 8 channels if DTM operation is used, or up to 2 channels in the case
of operation with DIP switches.
Operation via the PROFIBUS protocol is not possible given the sole listener function of the indicator!

Endress+Hauser 21
Operating the field indicator RID16

6.2 Display and operating elements

6.2.1 Display

A0011309

Fig. 13: LC display of the field indicator


Item 1: Bar graph display in increments of 10% with indicators for underranging (item 1a) and overranging (item 1b)
Item 2: Measured value display, status indication "Bad measured value status"
Item 3: 14-segment display for units and messages
Item 4: 'Communication' symbol
Item 5: Parameters cannot be modified' symbol
Item 6: '%' unit
Item 7: 'Uncertain measured value status' symbol

The backlit LCD display contains a bargraph (0-100) and arrows to indicate measurements
above or below the measurement range. Analog process values, digital status and failure
codes are displayed in the 7-segment area. Here up to 8 values can be displayed with a alter-
nating time between 2 and 20 seconds. Plain text can be displayed in the 14-segment area
(text is limited to 16 characters and is scrolled if needed (marquee text)).
The indicator also displays the quality of the measured value. If the status of the displayed
value is 'good' (quality code equal to or above 0x80), no symbol is lit and the indicator
remains in the normal operational state. If the status of the displayed value is 'uncertain'
(quality code between 0x40 and below 0x80), the 'Uncertain measured value status' symbol
is lit. If the status is 'bad' (quality code below 0x40), within the 7-segment area the display
will show "BAD-" and the channel number where the bad value is published. The entered text
continues to be displayed in the 14-segment area and the bar graph is not shown.

6.3 PROFIBUS® technology


PROFIBUS is the open, digital communication system in factory and process automation that
is standardized for all applications. PROFIBUS communication is incorporated into the inter-
national standards EN 50170 and IEC 61158. It replaces analog 4 to 20 mA transmission
technology on a broad basis.
PROFIBUS has been around for over a decade and has systematically evolved to become the
global market leader. With different protocol versions, interfaces and profiles, the modular
PROFIBUS communication system can be applied universally and, with PROFIBUS versions
geared towards specific industries, covers the wide range of requirements of factory and pro-
cess automation in equal measure.
Configuration information is available in the manual "Guidelines for planning and commis-
sioning, PROFIBUS® DP/PA, field communication" (BA034S). This manual is available on the
CD-ROM supplied or can be downloaded at www.endress.com/download.

22 Endress+Hauser
RID16 Operating the field indicator

6.3.1 System architecture


The following figure shows an example of a PROFIBUS® network with the associated com-
ponents.

PLC
Visualization and monitoring
e. g. P View, FieldCare
and diagnostic software
PROFIBUS-DP

PROFIBUS-PA segment segment segment


IEC 61158-2 coupler coupler coupler
31.25 kbit/s FISCO

0 - 10 bar 0 - 10 bar

RID16 RID14
Up to 32 devices per segment
A0021436-EN

Fig. 14: System integration with PROFIBUS® PA

PROFIBUS PA is always used in connection with a higher-level PROFIBUS DP control system.


Given that PROFIBUS DP and PROFIBUS PA have different transmission media and baud
rates, the PROFIBUS® PA segment is integrated into the PROFIBUS DP system via a segment
coupler.
A segment coupler consists of a signal coupler and a bus power supply unit. One or more
transmission rates are supported on the PROFIBUS DP side, depending on the model. The
transmission rate for PROFIBUS PA is fixed at 31.25 kBit/s.
PROFIBUS PA has been specially designed to meet the needs of the process engineering sec-
tor. Three features set it apart from a PROFIBUS DP system:
• PROFIBUS PA supports operation in hazardous areas without any special requirements.
• The devices are powered via the bus cable (two-wire devices)
• The data are transmitted via a physical layer according to IEC 61158-2 (MBP), allowing
users freedom in selecting the topology. With PROFIBUS PA, a tree structure, a line or a
combination of both can be selected for the topology. The fieldbus cable can be looped
through individual field devices but it is more advisable to connect the devices via a T-junc-
tion with a short spur.
Field devices can be configured on the fly with PROFIBUS PA.
The number of connected fieldbus devices depends on different factors, such as use in a haz-
ardous area, spur length, cable types, current consumption of the field devices, etc.
The start and end of the bus segment must be terminated by a bus terminator.
No power should be supplied via the bus if configuring the PROFIBUS PA indicator with the DTM via the
CDI interface!

6.3.2 Bus access methods and data transmission


PROFIBUS PA uses the central master/slave principle as the bus access method. The PI (pro-
cess interface, e.g. PLC), a Class 1 master, is located on the PROFIBUS DP system. The field
devices are configured via a Class 2 PROFIBUS DP master, such as FieldCare. The field devices
on the PROFIBUS PA segment are the slaves.
Segment coupler
From the point of view of the PROFIBUS DP master, segment couplers are transparent and
are therefore not configured in the PLC, i.e. they only convert the signals and power the PRO-
FIBUS PA segment.

Endress+Hauser 23
Operating the field indicator RID16

They do not require any settings and they are not assigned an address.
Each field device on the PA segment is assigned a PROFIBUS DP address and acts like a DP
slave. Each slave is only assigned to one Class 1 master. The masters communicate directly
with the slaves:
• A Class 1 master, such as a PLC, retrieves the field device data with the cyclic service.
• A Class 2 master, such as FieldCare, sends and retrieves data from the field devices with
the acyclic service.
A link is recognized by the master and is a user of the PROFIBUS DP system. It is assigned a
DP address and is therefore no longer transparent for cyclic data exchange of the master
with the field devices. Instead it retains the device data in a data buffer which can be read
cyclically by a Class 1 master. Therefore a link must be configured.
On the PROFIBUS PA side the link behaves like a PA master. It retrieves the data cyclically
from the field devices and saves them in a data buffer. Each field device is assigned to a PA
address which may only occur once in the individual link. It can be present in another link
segment however.
For acyclic data exchange with a Class 2 master the link is virtually transparent.
Once the link address (DP address) and the device address (PA address) have been specified,
any field device can be addressed.
Since the field indicator is only a listener, it does not appear as an active user on the bus and does not
require its own bus address. Therefore the indicator can also not be addressed directly by the master. The
indicator listens to the cyclic data traffic on the bus and presents the corresponding values on the display.

6.3.3 Device ID, addressing


Users must be addressed correctly for communication on the bus to function correctly. Each
device on the PROFIBUS PA segment is given a unique bus address between 0 and 125.
Addressing depends on the type of DP/PA interface (segment coupler or link).
Since the indicator is only a listener and is not an active bus user, it does not require its own bus address.
The bus address of the device whose values are to be shown on the indicator must be configured on the
field indicator.

24 Endress+Hauser
RID16 Operating the field indicator

6.4 Configuration via interface & PC configuration soft-


ware "FieldCare Device Setup"
! WARNING
The device is not explosion-protected when the housing is open
‣ The device must be configured outside the hazardous area.
To configure the device via the FieldCare Device Setup software, connect the device to your
PC. For this you will require a special interface adapter, the Commubox FXA291 (see 'Acces-
sories' section).
The four-pin plug of the interface cable must be inserted into the corresponding socket in
the device. The USB plug must be inserted into a free USB port on the PC.
Establishing a connection
When the device is connected the device DTM is not loaded automatically in FieldCare, i.e.
the device must be added manually.
1. First of all add the communication DTM "CDI communication FXA291" to an empty proj-
ect.
2. In the settings for the Comm DTM, set the baud rate to 2400 baud and set the COM port
used.
3. Add the device DTM "RID14/16 / Vx.xx.xx" to the project via the "Add device...." function.
4. Continue the device configuration as described in these Operating Instructions for the
device. All the parameters listed in these Operating Instructions can also be found in the
FieldCare Device Setup. The DTM operating parameters can be found in the Appendix
( ä 41).

PC Configuration software
Configuration kit USB-Box

USB

.
A0021549-EN

Fig. 15: Configuration of the field indicator via the interface adapter

No power should be supplied via the bus if configuring the PROFIBUS® PA indicator with the DTM via the
CDI interface!
To ensure a connection to the device can be established, operation must be set to "Remote" at the DIP
switches. Furthermore write protection, which can be enabled and disabled via the DIP switches, must be
disabled so that the parameters of the field indicator can be modified via the DTM.
The DIP switches are described in the "Operation" section ( ä 21).

Endress+Hauser 25
Operating the field indicator RID16

6.5 Hardware settings


Hardware write protection can be enabled and disabled via DIP switches inside the field indi-
cator. When write protection is active, parameters cannot be modified. The current write
protection status is displayed in the "Locking status" parameter ( ä 44).
ESD - electrostatic discharge
Protect the terminals from electrostatic discharge. Failure to observe this may result in
destruction or malfunction of parts of the electronics.
To set the DIP switches, proceed as follows:
1. Open the housing cover.
2. Configure the DIP switches. Switch to ON = function enabled, switch to OFF = function
disabled.
3. Close the housing cover and secure it.

A0021499

Fig. 16: Hardware configuration of the field indicator

Assignment of the DIP switches


Data Address Set AI1 DIP
ON

OFF
1 2 4 8 16 32 64 Offset - AI2 Write pro- Remote
tection

6.5.1 Switching write protection on/off


Write protection is switched on and off via the "WRITE LOCK" DIP switch. When write pro-
tection is active ("WRITE LOCK" is "ON"), parameters cannot be modified. The current write
protection status is displayed in the "Locking status" parameter. When write protection is
active ("WRITE LOCK" is "ON"), a padlock symbol is lit on the display.

6.5.2 Choosing between operation via DIP switches and remote op-
eration
When the device is operated via the DIP switches only 2 values are displayed even if more display values
were configured previously in the configuration software.
The bargraph is not displayed when the device is operated via the DIP switches.

Via the "Remote/DIP" DIP switch users can specify whether configuration is possible onsite
via the DIP switches or remotely via the DTM and PC configuration software. If the switch is
set to "OFF" (remote), all the switches apart from "WRITE LOCK" are disabled. If the switch is
set to "ON", all the DIP switches work and operation via the DTM is not possible.

26 Endress+Hauser
RID16 Operating the field indicator

6.5.3 Setting the bus address


The DIP switches can be used to set the address of the Profibus PA measuring device whose
values are to be displayed on the field indicator.
The bus address is set as follows:
1. "AI1/AI2" DIP switch
This DIP switch is used to select whether the configured address refers to analog input
1 (switch set to "ON") or analog input 2 (switch set to "OFF").
2. "Address/Offset" DIP switch set to "ON"
If the switch is set to "ON", the bus address of the measuring device whose values are to
be displayed can be set using DIP switches 1 to 64.
Valid address range: 0 to 125
3. "Set" DIP switch set from "OFF" to "ON"
Switch which is used to accept the offset setting in the device.
The settings are only accepted if the "Set" switch is changed from "OFF" to "ON". If the "Set"
switch is set to "ON", device power-on does not have any effect, nor does a change in the
"Set" switch setting from "OFF" to "ON" if the write lock is enabled.
If all the DIP switches are set for the address, address 127 can be configured. This deletes the settings for
the channel. A channel that was previously configured can be disabled again in this way.
Address 126 is not valid for the necessary Data Exchange Telegram. The device displays a configuration
error with this address.

6.5.4 Configuring an offset


Using the DIP switch, it is possible to set the index (offset) of the first byte of the value to be
displayed in relation to the set bus address of the data source.
An index (offset) of between 0 and 127 can be set via the DIP switches.
The setting is made as follows:
1. "AI1/AI2" DIP switch
This DIP switch is used to select whether the configured index (offset) refers to analog
input 1 (switch set to "ON") or analog input 2 (switch set to "OFF").
2. "Address/Offset" DIP switch set to "OFF"
If the switch is in the "OFF" position, an index (offset) can be set for analog input 1 or
analog input 2.
3. "Set" DIP switch set from "OFF" to "ON"
Switch which is used to accept the index (offset) setting in the device.
The settings are only accepted if the "Set" switch is changed from "OFF" to "ON". If the "Set"
switch is set to "ON", device power-on does not have any effect, nor does a change in the
"Set" switch setting from "OFF" to "ON" if the write lock is enabled.

Endress+Hauser 27
Commissioning RID16

7 Commissioning

7.1 Post-installation check


Make sure that all post-connection checks have been carried out before putting your devices

• Checklist for "post-installation check"  ä 11


into operation:

• Checklist for “post-connection check”,  ä 20


The functional data of the PROFIBUS® PA interface according to IEC 61158-2 (MBP) must be observed.
A normal multimeter can be used to check that the bus voltage is between 9 and 32 V and that current
consumption is approx. 11 mA.

7.2 Switching on the field indicator


Once the final checks have been successfully completed, it is time to switch on the supply
voltage. The field indicator performs a number of internal test functions after power-up. As
this procedure progresses, the following sequence of messages appears on the display:

Step Display

1 All segments on

2 All segments off

3 Manufacturer name

4 Device name

5 Firmware version

6 Device revision

7a A published value

7b The current status message


If the switch-on procedure fails, the appropriate status message is displayed,
depending on the cause. A detailed list of the status messages, as well as the mea-
sures for troubleshooting, can be found in Section 9, ’Troubleshooting’.

Normal indicating mode commences as soon as the switch-on procedure is completed. Var-
ious measured values and/or status values appear on the display.

7.3 Commissioning
Note the following points:

described on  ä 19.
• The files required for commissioning and network configuration can be obtained as

• The field indicator acts solely as a listener. This means that the device listens on the bus
for values that should be displayed. The device does not have an address of its own and is
not an active bus user.
An address of a sensor connected to the PROFIBUS PA network can be selected for each of
the 8 channels of the indicator. The first published value of the selected address is listed in
the next step. The selected value is then displayed by the device. The first published value of
the selected address is listed in the next step. The selected value is then displayed by the
device.
If an address publishes more than one value, additional values can be selected manually. This
address generates a configuration error in the indicator once the bus has been reconfigured
or a published device has been removed. If only the displayed value of the device is no longer
available, the indicator switches automatically to the next value published to this address.

28 Endress+Hauser
RID16 Maintenance

8 Maintenance
The device does not require any special maintenance and servicing work.

9 Accessories
Various accessories are available for the device, and these can be ordered with the device or
at a later stage from Endress+Hauser. Detailed information on the order code in question is
available from your local Endress+Hauser Sales Center or on the product page of the
Endress+Hauser website: www.endress.com.

9.1 Device-specific accessories

Designation Description

Pipe mounting kit • Plastic housing


(for pipes 1-5") • Alu housing

Protective cover

A0021548

Fig. 17: Dimensions in mm (in)

9.2 Communication-specific accessories

Designation Description

Fieldbus connector

PROFIBUS® PA: • NPT ½"  M12


• M20  M12
• M20  7/8"

Interface cable Commubox FXA291 incl. FieldCare Device Setup + DTM Library

Endress+Hauser 29
Troubleshooting RID16

10 Troubleshooting

10.1 Troubleshooting instructions


In the event of a critical error, you might need to return the indicator to the manufacturer for repair.
Please follow the instructions for returning devices ( ä 34) before you send in the indicator.

Always start troubleshooting with the checklists below if faults occur after start up or during
operation. This takes you directly (via various queries) to the cause of the problem and the
appropriate remedial measures.

Checking the display

No display visible - no connec- 1. For fault elimination, see under "Faulty connection to the fieldbus system"
tion to the fieldbus system
2. Other possible causes of error:
– Defective electronics module » Test with spare module » Order spare
part
– Defective housing (internal electronics) » Test with spare
housing » Order spare part
3. Defective field indicator  Replace field indicator

No display visible - connection to 1. Check whether the display module is correctly connected to the electron-
the fieldbus system is estab- ics module,  ä 12.
lished, however
2. Defective display » Test with spare display » Order spare part
3. Defective electronics module » Test with spare module » Order spare part

Faulty connection to the fieldbus system

A connection cannot be established between the fieldbus system and the indicator.
Check the following points:

Fieldbus connection Check the data cable

Fieldbus connector (optional) Pin assignment / check wiring,  ä 15

Fieldbus voltage Check whether a minimum bus voltage of 9 V DC is present at the +/-
terminals. Permitted range: 9 to 32 V DC

Network structure Check the permitted fieldbus cable length and number of spurs,  ä 16

Basic current Is there a basic current of min. 11 mA?

Terminating resistors Has the PROFIBUS PA segment been terminated correctly?


Each bus segment must always be terminated with a bus terminator at both
ends (start and finish). Otherwise there may be interference in data transmis-
sion.

Current consumption Check the current consumption of the bus segment:


Permitted feed current The current consumption of the bus segment in question (= total of basic cur-
rents of all bus users) must not exceed the max. permissible feed current of
the bus power supply unit.

Error messages in the PROFIBUS® PA configuration system

 ä 30

Other errors (application errors without an error message)

Another error has occurred. Possible causes and remedial measures  ä 30

10.2 Status messages


The device displays warnings or alarms as status messages. If errors occur during commis-
sioning, these errors are displayed immediately. A distinction is made here between the fol-
lowing 4 status categories:

30 Endress+Hauser
RID16 Troubleshooting

Status category Description Error category

F Fault detected ('Failure') ALARM

C Device is in the service mode ('Check')


WARNING
S Specifications not observed ('Out of speci-
fication')

M Maintenance required ('Maintenance')

ALARM error category:


In the event of an error the display alternates between the error message (= letter F plus the
defined error number, e.g. "F283") and "BAD" and the channel number every second. The bar-
graph and the alarm signals are disabled in this case.
Other channels that are correctly configured continue to be shown alternately with the cor-
rect bargraph. As soon as the channel with the error is reached again, Fxxx) is shown alter-
nately with "BAD" and the channel number once more.
WARNING error category:
The display alternates between the displayed values and the error message (= appropriate
letter plus the defined error message, e.g. "C501").
If more than one value is displayed the display alternates between the values and the error
message as follows:
• e.g. channel 1, channel 2 and channel 3 are configured for value display
• Value of channel 1 => error message => value of channel 2 => error message => value of
channel 3 => error message => value of channel 1 => etc.
If no value is to be displayed and an error occurs, the display alternates between "- - - - -" and
the error message.
As long as the error message is active the alternating time is set to 2 seconds. Once the error has been
rectified the alternating time will return to its normal value which is entered in the
"DISP_ALTERNATING_TIME" parameter.

7-segment display 14-segment display Description Cause of error / remedy

C501 Device reset A reset has been performed.


This status is then only visible in
the last status message and just
before the reset, if applicable.

M561 CHAN Display overrun Value too large to be displayed


followed by channel with the number of decimal
info 1-8 places currently configured.
Measured value is displayed
with 5 dashes "-----".

F437 CHAN Configuration error An address has been selected


followed by channel that is currently not on the bus
info 1-8 or does not send a value to the
bus.

F283 Memory content Int. RAM, ext. RAM or EEPROM


error
• Perform reset
• Replace electronics

F261 Electronics board defective Replace electronics

Endress+Hauser 31
Troubleshooting RID16

10.3 Spare parts


When ordering spare parts, please specify the serial number of the device!

a0012119

Fig. 18: Spare parts of the FOUNDATION Fieldbus™ indicator

Item No. Description Order No.

1 Front aluminum, incl. film + glass RID16X-GB

2 Front, plastic incl. film RID16X-GA

3 Metal base (metric thread) RIA16X-GD

Metal base (NPT1/2 thread) RIA16X-GE

4 Plastic base RID16X-GC

5 Electronics cpl. (Ex + non Ex) RID16X-EB

6 Cable gland M16x1.5 PA RAL7035 51004048

7 Set of small parts: RIA16X-GG


Goretex filter, 2x hinged pins, shielding clamp (metal set = 5 brackets + screws
/ disks)

8 Spare parts set, cover parts + connecting parts RIA16X-GF


(contains cover plate for front, screw plate (plastic housing) + connecting
cable for mainboard -> display board)

9 LC display incl. display board RIA16X-DA

- Cable gland NPT 1/2 D4-8.5, IP68 51006845

- Adapter M16x1.5 NPT1/2 71085029

- Wall+pipe mounting kit (W08) 71089844

32 Endress+Hauser
RID16 Troubleshooting

10.4 Software history and overview of compatibility


Revision history
The version number on the nameplate and in the Operating Instructions indicates the device
release: XX.YY.ZZ (example 01.02.01).

XX Change to main version.


No longer compatible. The device and Operating Instructions change.

YY Change to functions and operation.


Compatible. The Operating Instructions change.

ZZ Fixes and internal changes.


No changes to the Operating Instructions.

Date Software version Software change Documentation

10/2013 1.00.zz Original software BA01268K/09/EN/01.13


71232742

Endress+Hauser 33
Return RID16

11 Return
The measuring device must be returned if repairs or a factory calibration are required, or if
the wrong measuring device has been ordered or delivered. According to legal regulations
Endress+Hauser, as an ISO-certified company, is required to follow certain procedures when
handling returned products that are in contact with the medium.
To ensure the safe, quick and professional return of your device,
visit the Endress+Hauser website (www.services.endress.com/return-material) for informa-
tion on the procedure to be followed and basic conditions.

12 Disposal
The device contains electronic components and must therefore be disposed of as electronic
waste. Comply with local disposal regulations.

34 Endress+Hauser
RID16 Technical data

13 Technical data

13.0.1 Communication and data processing


Breakdown information
• Status message as per the fieldbus specification.
Switch-on delay
•8s

PROFIBUS® PA
• PROFIBUS® PA in accordance with EN 50170 Volume 2, IEC 61158-2 (MBP)
• FDE (Fault Disconnection Electronic) = 0 mA
• Data transmission rate: supported baud rate = 31.25 kBit/s
• Signal coding = Manchester II
• Connection data in accordance with IEC 60079-11 FISCO, Entity

Protocol-specific data

PROFIBUS® PA

Basic data

Indicator for PROFIBUS PA, can be used in conjunction with PROFILE 2 and PROFILE 3 (3.0, 3.01 and 3.02)
devices

Device master files (GSD) How to acquire device master files (GSD) and device drivers:
• FieldCare/DTM: www.endress.com → Select country → Solutions →
Field Network Engineering → Fieldbus device integration → PROFIBUS
→ PROFIBUS® GSD files and certificates

Write protection Write protection enabled by hardware setting (DIP switch)

13.0.2 Power supply

Electrical connection

A0021528

Fig. 19: Terminal assignment of the field indicator


1 PROFIBUS® PA

Supply voltage
Voltage is supplied via the fieldbus.
U = 9 to 32 V DC, polarity-independent (max. voltage Ub = 35 V).

Endress+Hauser 35
Technical data RID16

Mains voltage filter


50/60 Hz

Current consumption
 11 mA

Cable entry
The following cable entries are available:
‣ Thread NPT1/2
‣ Thread M20
‣ Thread G1/2
‣ 2x gland NPT1/2 + 1x dummy plug
‣ 2x gland M20 + 1 x dummy plug

13.0.3 Installation

Installation instructions

Mounting location
Wall or pipe mounting (see 'Accessories')
Orientation
No restrictions, the orientation depends on the readability of the display.

13.0.4 Environment

Ambient temperature limits


-40 to +80 °C (-40 to 176 °F)
The display can react slowly at temperatures < -20 °C (-4 °F).
The readability of the display is no longer guaranteed at temperatures < -30 °C (-22 °F).

Storage temperature
-40 to +80 °C (-40 to 176 °F)

Altitude
Up to 4000 m (13100 ft.) above mean sea level in accordance with IEC 61010-1, CSA
1010.1-92

Climate class
According to IEC 60654-1, Class C

Humidity
• Condensation permitted as per IEC 60 068-2-33
• Max. rel. humidity: 95% as per IEC 60068-2-30

Degree of protection
IP67. NEMA 4X.

Shock and vibration resistance


10 to 2000 Hz for 5g as per IEC 60 068-2-6

36 Endress+Hauser
RID16 Technical data

Electromagnetic compatibility (EMC)


CE EMC conformity
The device complies with all the requirements of IEC 61326-1:2006 and NAMUR
NE21:2007.
This recommendation is a consistent determination as to whether the devices used in labo-
ratories and in distributed control systems are immune to interference, thus increasing their
functional safety.

ESD (electrostatic discharge) IEC 61000-4-2 6 kV cont., 8 kV air

Electromagnetic fields IEC 61000-4-3 0.08 to 4 GHz 10 V/m

Burst (fast transients) IEC 61000-4-4 1 kV

Surge IEC 61000-4-5 1 kV asym.

Conducted RF IEC 61000-4-6 0.01 to 80 MHz 10 V

Measuring category
Measuring category II as per IEC 61010-1. The measuring category is provided for measur-
ing on power circuits that are directly connected electrically with the low-voltage network.

Degree of contamination
Pollution degree 2 as per IEC 61010-1.

Endress+Hauser 37
Technical data RID16

13.0.5 Mechanical construction

Design, dimensions
Die-cast aluminum housing for general applications, or optional stainless steel housing

A0011162

Fig. 20: Dimensions of the field indicator; dimensions in mm (in)


1: Bore for mounting directly on the wall or on optional mounting plate with 4 screws 5 mm (0.2")

Weight
• Plastic housing: approx. 500 g (1.1 lb)
• Aluminum housing: approx. 1.7 kg (3.75 lb)

Material

Housing Nameplate

Fiber-glass reinforced plastic PBT-GF30 Laser inscription

Aluminum AlSi12 (optional) Laser-writable film, polyester

Terminals
Screw terminals for cables up to max. 2.5 mm2 (14 AWG) plus ferrule

38 Endress+Hauser
RID16 Technical data

13.0.6 Human interface

Display elements

a0011309

Fig. 21: LC display of the field indicator


Item 1: Bar graph display in increments of 10% with indicators for underranging (item 1a) and overranging (item 1b)
Item 2: Measured value display, digit height 26 mm (1.02"), status indication "Bad measured value status"
Item 3: 14-segment display for units and messages
Item 4: 'Communication' symbol
Item 5: 'Parameters cannot be modified' symbol
Item 6: '%' unit
Item 7: 'Uncertain measured value status' symbol

• Display range
-9999 to +99999

Configuration
PROFIBUS® PA
The parameters can either be configured remotely via the DTM and configuration software
or locally via DIP switches.

Endress+Hauser 39
Technical data RID16

13.0.7 Certificates and approvals

CE mark
The device meets the legal requirements of the EC directives. Endress+Hauser confirms that
the device has been successfully tested by applying the CE mark.

Ex-approval
Information about currently available Ex versions (ATEX, FM, CSA, etc.) can be supplied by
your E+H Sales Center on request. All explosion protection data are given in a separate doc-
umentation which is available upon request.

Other standards and guidelines


• IEC 60529:
Degrees of protection provided by enclosures (IP code)
• IEC 61010-1:
Safety requirements for electrical equipment for measurement, control and laboratory use
• IEC 61326 series:
Electromagnetic compatibility (EMC requirements)
• NAMUR:
International user association of automation technology in process industries
(www.namur.de)

CSA GP
CSA General Purpose

13.0.8 Documentation

‣ Overview brochure: System Components and Data Managers - Solutions for a Complete
Measuring Point: FA00016K/09
‣ ATEX Safety instructions:
– ATEX II2G Ex ia IIC: XA00099R/09

40 Endress+Hauser
RID16 Appendix

14 Appendix

14.1 DTM operating parameters

14.1.1 Operation menu

Display duration

Navigation  Operation ‣ Alternating time

Description Use this function to set the length of time the measured values are displayed if the
values alternate on the display. The display only alternates automatically between
values if more than one measured value is defined.
Info:
• The Value 1 display - Value 8 display parameters are used to specify which mea-
sured values are shown on the local display.
• The display format of the displayed measured values is specified using the Format
display parameter.

Visible offline Yes


Writable offline Yes

User entry Time in seconds [2-20]

Factory setting 5

"Display value X" submenu

Navigation  Operation ‣ Display value X

Description Settings to display the measured values received via PROFIBUS.

Source address

Navigation  Operation ‣ Display value X ‣ Source address

Description Allows users to select the bus address of the device whose values are to be displayed.

Visible offline Yes


Writable offline Yes

User entry Bus address [0-125]

Factory setting 0

Endress+Hauser 41
Appendix RID16

Offset source

Navigation  Operation ‣ Display value X ‣ Offset source

Description Indicates the index (offset) of the first byte of the value to be displayed from the pay-
load data received.

Visible offline Yes


Writable offline Yes

User entry Offset [0-244]

Factory setting 0

Description

Navigation  Operation ‣ Display value X ‣ Description

Description Possibility to enter a user-defined text with a maximum of 16 characters.


This text is shown below the value on the display.
If the text is longer than 5 characters, it is displayed as marquee text.

Visible offline Yes


Writable offline Yes

User entry Free text

Factory setting

Enable % symbol

Navigation  Operation ‣ Display value X ‣ Enable % symbol

Description Switches on the %-symbol of the display.

Visible offline Yes


Writable offline Yes

Options On, off

Factory setting Off

Bargraph 0%

Navigation  Operation ‣ Display value X ‣ Bargraph 0%

Description Enter the minimum value (0%) for the bargraph.


Only visible if data type = analog and bar graph on/off = on (Expert menu).

Visible offline Yes


Writable offline Yes

User entry Numerical value

Factory setting 0

42 Endress+Hauser
RID16 Appendix

Bargraph 100%

Navigation  Operation ‣ Display value X ‣ Bargraph 100%

Description Enter the maximum value (100%) for the bargraph.


Only visible if data type = analog and bar graph on/off = on (Expert menu).

Visible offline Yes


Writable offline Yes

User entry Numerical value

Factory setting 100

Decimal places

Navigation  Operation ‣ Display value X ‣ Decimal places

Description Use this function to select the number of decimal places for the display value.
This setting does not affect the accuracy of the device when measuring or calculat-
ing.
Only visible if data type = analog.

Visible offline Yes


Writable offline Yes

Options Automatic, xxxxx, xxxx.x, xxx.xx, xx.xxx, x.xxxx

Factory setting Automatic

14.1.2 Diagnostics menu

Current diagnostics

Navigation  Diagnostics ‣ Current diagnostics

Description The current diagnostic message appears on the display.


If two or more messages occur simultaneously, the message with the highest priority
is shown on the display. This parameter is the input parameter for the NE107 mod-
ule. The category and the channel are encoded in the value.

Visible offline No
Writable offline No

Options GOOD, Display overflow ch x, Preset, Electronic, Memory, Configuration ch x

Last diagnostics

Navigation  Diagnostics ‣ Last diagnostics

Description The last diagnostic message with the highest priority appears on the display.

Visible offline Yes


Writable offline No

Endress+Hauser 43
Appendix RID16

Actual diagnostics count

Navigation  Diagnostics ‣ Actual diagnostics count

Description Displays the number of diagnostic messages currently pending in the device.

Visible offline No
Writable offline No

Locking status

Navigation  Diagnostics ‣ Locking status

Description Displays the device locking status.


The DIP switch for hardware locking is provided on the display module.
Write access to the parameters is locked if write protection is enabled.

Visible offline No
Writable offline No

Only read access Not locked, Hardware locked

Factory setting Not locked

"Device information" submenu

Navigation  Diagnostics ‣ Device information

Description Displays general device information.

Device name

Navigation  Diagnostics ‣ Device information ‣ Device name

Description Displays the device name. Only read access.

Visible offline Yes


Writable offline No

Factory setting RID16

Device tag

Navigation  Diagnostics ‣ Device information ‣ Device tag

Description Text for the tag name

Visible offline Yes


Writable offline Yes

User entry Free text

Factory setting Serial number of the device

44 Endress+Hauser
RID16 Appendix

Serial number

Navigation  Diagnostics ‣ Device information ‣ Serial number

Description Serial number of the device, text, max. 11 characters

Visible offline Yes


Writable offline No

Order code

Navigation  Diagnostics ‣ Device information ‣ Order code

Description Displays the order code of the device. It can also be found on the nameplate. The
code is generated by reversibly transforming the extended order code which indi-
cates the attribute of all the device features in the product structure. In contrast to
the extended order code, the device features cannot be read directly from the order
code.
Uses of the order code
• To order an identical spare device.
• To identify the device quickly and easily, e.g. when contacting the manufacturer.

Visible offline Yes


Writable offline No

"Device reset" submenu

Navigation  Diagnostics ‣ Device information ‣ Device reset

Description Contains functions to reset the device.

Device reset

Navigation  Diagnostics ‣ Device information ‣ Device reset ‣ Device reset

Description Use this function to reset the device configuration - either entirely or in part - to a
defined state.

Visible offline No
Writable offline No

Options Not active, To factory defaults


INFO: If this parameter is set to "To factory defaults" the device reboots.

Factory setting Not active

Endress+Hauser 45
Appendix RID16

14.1.3 Expert menu


The Expert menu contains all the parameters in the Operation and Diagnostics menus as
well as the parameters listed below.

Enter access code

Navigation  Expert ‣ Enter access code

Description Disable the parameter write protection with the user-specific access code.

Visible offline Yes


Writable offline No

User entry 4-digit number

Factory setting 0

Access status tooling

Navigation  Expert ‣ Access status tooling

Description Displays access rights to the parameters

Visible offline Yes


Writable offline No

Options Operator, Service, Production

Factory setting Operator

"System" submenu

Navigation  Expert ‣ System

Description This submenu contains system settings.

Locking status

Navigation  Expert ‣ System ‣ Locking status

Description Displays the device locking status.


The DIP switch for hardware locking is provided on the display module.
Write access to the parameters is locked if write protection is enabled.

Visible offline No
Writable offline No

Only read access Not locked, Hardware locked

Factory setting Not locked

46 Endress+Hauser
RID16 Appendix

"Display" submenu

Navigation  Expert ‣ Display

Description This submenu contains display settings.

Display duration

See the Operation menu ( ä 41).

"Display value X" submenu

Navigation  Expert ‣ Display ‣ Display value X

Description Settings to display the measured values received via PROFIBUS.

This submenu contains the following parameters in addition to those described in the Operation ‣ Display value X
menu ( ä 41).

Data type

Navigation  Expert ‣ Display ‣ Display value X ‣ Data type

Description For selecting the data type (analog/digital) whose values are to be displayed.

Visible offline Yes


Writable offline Yes

Options Analog, Digital

Factory setting Analog

Data direction

Navigation  Expert ‣ Display ‣ Display value X ‣ Data direction

Description For selecting the direction of the data that are to be displayed. It is possible to dis-
play data that are sent from the device (slave) to the master or from the master to
the field device.

Visible offline Yes


Writable offline Yes

Options From device, To device

Factory setting From device

Endress+Hauser 47
Appendix RID16

Factor value

Navigation  Expert ‣ Display ‣ Display value X ‣ Factor value

Description Use this function to enter a factor by which the measured value should be multiplied.
Only visible if data type = analog

Visible offline Yes


Writable offline Yes

Options 1E-06, 1E-05, 1E-04, 1E-03, 1E-02, 1E-01, 1E-00, 1E+01, 1E+02, 1E+03, 1E+04,
1E+05, 1E+06

Factory setting 1E-00

Offset value

Navigation  Expert ‣ Display ‣ Display value X ‣ Offset value

Description Sets the offset for the measured value. The value indicated is added to the measured
value.
Only visible if data type = analog

Visible offline Yes


Writable offline Yes

User entry Numerical value [-99999 to 99999]

Factory setting 0

Digital representation

Navigation  Expert ‣ Display ‣ Display value X ‣ Digital representation

Description Select how the digital values are represented.


Only visible if data type = digital.

Visible offline Yes


Writable offline Yes

Options 1 = On; 0 = Off, 0 = On; 1 = Off, 1 = Open; 0 = Close, 0 = Open; 1 = Close, Display as
decimal value

Factory setting 1 = Open; 0 = Close

"Diagnostics" submenu

Navigation  Expert ‣ Diagnostics

Description Settings to display the measured values received via PROFIBUS.

This submenu contains the following parameters in addition to those described in the Diagnostics menu
( ä 43).

48 Endress+Hauser
RID16 Appendix

"Device information" submenu

Navigation  Expert ‣ Diagnostics ‣ Device information

Description Displays general device information.

Extended order code

Navigation  Expert ‣ Diagnostics ‣ Device information ‣ Extended order code

Description Displays the extended order code. The extended order code indicates the attribute of
all the features of the product structure for the device.

Visible offline Yes


Writable offline No

Device revision

Navigation  Expert ‣ Diagnostics ‣ Device information ‣ Device revision

Description Displays the device revision.

Visible offline Yes


Writable offline No

Hardware version

Navigation  Expert ‣ Diagnostics ‣ Device information‣ Hardware version

Description Displays the hardware version and is used to identify the device. Only read access.

Visible offline Yes


Writable offline No

Manufacturer name

Navigation  Expert ‣ Diagnostics ‣ Device information ‣ Manufacturer name

Description Displays the manufacturer name.

Visible offline Yes


Writable offline No

Factory setting Endress+Hauser

Endress+Hauser 49
Appendix RID16

50 Endress+Hauser
RID16

Index
B Data direction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Bus access methods and data transmission . . . . . . . . . . 23 Data type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Decimal places . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
C Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Cable gland . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Device name . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Cable specification Device reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Bus termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Device revision . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Cable type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Device tag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Further information . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Digital representation . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Maximum overall cable length. . . . . . . . . . . . . . . . . . 17 Display duration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Maximum spur length. . . . . . . . . . . . . . . . . . . . . . . . . 17 Enable % symbol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Number of field devices. . . . . . . . . . . . . . . . . . . . . . . . 17 Enter access code. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Shielding and grounding. . . . . . . . . . . . . . . . . . . . . . . 18 Extended order code . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Configuration programs . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Factor value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Configuring an offset . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Hardware version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Last diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
D Locking status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Device ID, addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Manufacturer name . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Offset source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
DIP switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Offset value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
DTM operating parameters . . . . . . . . . . . . . . . . . . . . . . . 41 Order code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Serial number. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
E Source address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Electrical symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Pipe mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Error category
Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Q
Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Quick wiring guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

F R
Fieldbus connector. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Release . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

I S
Incoming acceptance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Safety symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Setting the bus address. . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
M Status messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30–31
Menu Switching write protection on/off. . . . . . . . . . . . . . . . . . . 26
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Symbols
Expert . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 ~ for certain types of information . . . . . . . . . . . . . . . . . 5
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 ~ in graphics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Mounting Electrical symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Safety symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
T
N Technical data for field device connector. . . . . . . . . . . . . 16
Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Terminal assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Transport and storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
O
Operating parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 W
Operation via DIP switches and remote operation . . . . 26 Wall mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
P
Parameter
Access status tooling . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Actual diagnostics count . . . . . . . . . . . . . . . . . . . . . . . 44
Bargraph 0%. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Bargraph 100% . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Current diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

Endress+Hauser 51
www.addresses.endress.com

You might also like