EE2024 Lecture12
EE2024 Lecture12
Lecture 12 Lecturer
Dr. (Mrs) R. M. M. Ruwanthika
[email protected]
The Magnetization Current in a Real Transformer
• When an ac power source is connected to a transformer as shown in
figure, a current flows in its primary circuit, even when the
secondary circuit is open circuited.
• This current is the current required to produce flux in a real
ferromagnetic core.
• It consists of two components:
1. The magnetization current 𝑖𝑀 , which is
the current required to produce the flux
in the transformer core
and if the initial flux in the core is zero, then the maximum flux during
the first half-cycle will just equal the maximum flux at steady state:
• The flux wave will reach its maximum value, 1/4 cycle or π/2 angle
later, reaching the maximum value of the voltage wave.
• As per the waves shown in the figure above, at the instant when the
voltage is zero, the corresponding steady state value of flux should be
the negative maximum (i.e. minimum value).
https://www.electrical4u.com/magnetizing-inrush-current-in-power-transformer/
• But it is not practically possible to have flux the instant you switch on the
supply to the transformer. This is because there will be no flux linked to the
core prior to switching on the supply.
• The steady state value of flux will not be reached instantly. Although it’s
very fast from our perspective – it takes a non-zero amount of time. The
speed of this process depends on how fast the circuit can take energy.
Solution
The five possible voltage ratings of this transformer are
+5.0% tap 13,860/480 V
+2.5% tap 13,530/480 V
Nominal rating 13,200/480 V
-2.5% tap 12,870/480 V
-5.0% tap 12,540/480 V
• The taps on a transformer permit the transformer to be adjusted in
the field to accommodate variations in local voltages.
• However, these taps normally cannot be changed while power is
being applied to the transformer. They must be set once and left
alone.
• But when single line to ground fault occurs on any phase of the system, as
shown in the figure,
• zero sequence component of the earth fault current flows in the earth and returns to
the electrical power system by way of earth star point of the earthing transformer.
• It gets divided equally in all the three phases.
• Hence, as shown in the figure, the currents in the two different halves of two
windings in the same limb of the core flow in opposite directions.
• And therefore the magnetic flux set up by these two currents will oppose and
neutralize each other.
• As there is no increase in flux due to fault current, there is no change of dφ/dt means
no choking effect occurs to impede the flow of fault current.
• So it can be concluded like that, the zigzag type earthing or grounding transformer
maintains the rated supply voltage at normal current as well as when a solid single
line to ground fault current flows through it.
https://www.electrical4u.com/what-is-earthing-transformer-or-grounding-transformer/
• The rated voltage of an earthing or grounding transformer is the line
to line voltage on which it is intended to be used.
• Current rating of this transformer is the maximum neutral current in
Amperes that the transformer is designed to carry in fault condition
for a specific time.
• Generally the time interval, for which transformer designed to carry
the maximum fault current through it safely, is taken as 30 second.