CRUSHING TEST REPORT NF EN 12390-3

CONTRACTOR Zerock CTR N° 41 30A100_RFI N°: 050 EXT MIX DESIGN


Production line shed E1IF03-D9IF02-
PROJECT 1st Agri Hub PART OF STRUCTURE TRIAL MIX
F1IF03-G1IF03-G2IF01-D8IF02
POURING DATE 6/21/2023 ORIGIN OF CONCRETE Zerock Batching plant Loudima INFORMATION ✘

TEMPERATURE 27,8 / 32,2 °C SIZE OF SPECIMEN 16 x 32 cm NUMBER OF SPECIMEN 3

MIX DESIGN CODE 25-XC4-D25-S3-42.5N-SHR-S0/1


COMPOSITION OF CONCRETE CEMENT WATER SAND GRAVEL 1 GRAVEL 2 ADMIXTURE SLUMP TEST SPECIFIED

TYPE 42,5N - 0/1 5/12,5 16/25 ADMIX150 SLUMP TEST 0' 15 cm


THEORICAL (Kg/m3) 450 178.78 574 260 1018 4 SLUMP TEST 30'
PRATICAL - - - - - - SLUMP TEST 60'

COMPACTION Vibration CURING Water immersion

COMPRESSIVE
SPECIMEN AGE WEIGHT DENSITY LOAD
CRUSHING DATE STRENGHT FAILURE
REFERENCE
(J) (Kg) (T/m3) (KN) MPa AVERAGE
AH061 28 7/19/2023 16.14 2.51 499.41 24.84 Correct
AH062 28 7/19/2023 16.32 2.54 529.13 26.32 25.78 Correct
AH063 28 7/19/2023 16.24 2.53 526.58 26.19 Correct
Remarks :

Inspectors for : GEOLAB ENI CONGO ZEROCK


Name
Signature
Date
Roulé
Concassé

Correct
Incorrect
Pervibration