Key Plan: Support For Roof Ducts 2 Fcu/Crac Installation 3

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

NOTES:

1. CONDENSATE P TRAP SHALL BE AS PER MANUFACTURERS RECOMMENDATIONS.


2. PROVIDE CLOSED CELL INSULATIONS ON CONDENSATE DRAIN TO PREVENT CONDENSATIONS. SPRING TYPE
3. MAINTAIN AT LEAST 2% SLOPE PER FOOT FOR THE CONDENSATE DRAIN. VIBRATION ISOLATOR
4. ALL CONDENSATE DRAIN SHALL BE PROVIDED WITH A U-TRAP AND A FALL TO THE
SUMP PUMP / FLOOR TRAP/ FUNNEL DRAIN.
5. MAINTAIN REQUIRED CLEARANCE SPACE AS RECOMMENDED BY MANUFACTURER. RUBBER MOUNT
6. INSTALLATION OF FCU/CRAC SHALL BE AS PER MANUFACTURERS RECOMMENDATIONS.
7. SPRING ISOLATORS SHOULD PROVIDE 70%-80% ISOLATION EFFICIENCY. HANGING ROD
MINIMUM DEFLECTION AS PER ASHRAE APPLICATIONS HANDBOOK CHAPTER 48, TABLE 47.

GIS &
TRANSFORMER
GALVANIZED ANGLE IRON SIZES: BUILDING

40x40x5MM FOR DUCTS UP TO 1200mm


50x50x10mm FOR DUCTS LARGER THAN 1200mm
CANVASS CONNECTION AXIAL FAN CANVASS CONNECTION

ANTI VIBRATION MOUNTING


RECTANGULAR/ SQUARE DUCTS KEY PLAN
50mm WIDE 4mm THICK G.I. STRIP FOR
STRAPPING OF DUCT @2m C.C.
DUCTWORK DUCTWORK
ALUMINIUM SHEET CLADDING
INSULATION WITH VAPOUR BARRIER

RUBBER PAD 12mm THICK SUPPLY


SPRING ISOLATORS RETURN AIR
(REFER TO SPECS)
400

PANEL FILTER REMOVAL AS PER SITE


(GALVANIZED) IRON FRAME , CONDITION

400
WELDED AT ALL POINTS OF CONTACT . PANEL FILTER REMOVAL AS PER SITE
FLEXIBLE CONNECTION CONDITION

~
100x100x6mm FOOT PLATE
ROOF FINISHED LEVEL INSULATION
CONDENSATE (REFER TO
DRAINAGE STANDARD DETAIL
COOLING COIL

1 TYPICAL DETAIL OF ROOF MOUNTED AXIAL FAN


NTS
2 SUPPORT FOR ROOF DUCTS
NTS 3 FCU/CRAC INSTALLATION
NTS

NEOPRENE GASKET
ALL AROUND RIVET OR METAL SCREW
(TYPICAL)
WALL DETAILS REFER ARCH. LAYOUT

…" MASONRY ANCHOR SYNTHETIC BEARING


(TYPICAL)
OUTSIDE AIR DUCT SUPPLY AIR DUCT
WALL OPENING

EDGE SEAL (TYPICAL)

BACKDRAFT
AIRFLOW DAMPER ASSY

EXHAUST AIR LOUVER AIR DUCT


FIXED BLADE TYPE
VIBRATION
BACK-DRAFT DAMPER ISOLATION PADS
( INTEGRAL WITH UNIT)
400 MM HIGH
HOUSEKEEPING PAD
FROM ROOF/ SLAB FFL
EXHAUST FAN
UNIT STOPPER

5 TYPICAL DETAIL OF OAHU 6 BACK DRAFT MULTI BLADE DAMPER


This drawing and the design it covers are the property of the
TYPICAL WALL MOUNTED EXHAUST FAN NTS NTS Royal Commission for Jubail and Yanbu, Royal Commission
4 at Yanbu. These drawings are loaned on the borrower's
NTS express agreement that they will not be reproduced, copied,
loaned, exhibited or used except in the limited way, if any,
permitted by written consent of the Royal Commission.
CONTRACTORS SIGNATURE

0 5 10m
* FOR INSULATED AND NONE INSULATED DUCTS.
SCALE = 1 :100 METERS

20 GAUGE GALVANIZED SHEET NOTE : SHOP DRAWING


METAL DUCT SLEEVE 1. ALL INDOOR AND ACCU REFRIGERANT PIPING COMPONENTS INDOOR/ROOF OUTDOOR
TO BE HVAC VENDOR SUPPLIED. CONSTRUCTION INSULATED
FIRE RATED JOINT SEALANT CONTRACTOR TO ASSEMBLE IN FIELD. REFRIGERANT
2. RS AND RL TO BE IDENTIFIED ON SITE ALSO PIPES
DIRECTION OF FLOW ARROWS.
Liquid Line (RL)
FIRE DAMPER CHARGING
RL 00 06-Jun-24 MI ISSUED FOR CONSTRUCTION MA
VALVE
RG NO. DATE BY DESCRIPTION APPROVED BY
‍12mm ‍12mm DUCT SHUT-OFF
(FOR BOTH SIDE)

VALVE REVISIONS
H+200mm

FILTER DRIER
H

ROW SPLIT SOLENOID


DIRECT EXPANSION WALL SLEEVE
VALVE
COOLING COIL
M
PITCH

ACCESS DOOR SIZE AS PER


AHU
MECHANICAL SPECIFICATION ACCU
PITCH
PROJECT TITLE
JAZAN CITY FOR PRIMARY AND
DOWNSTREAM INDUSTRIES (JCPDI)
FALSE CEILING
TO DRAIN SEA WATER COOLING (SWC) SYSTEM - PHASE 1
COMPRESSIBLE FILLER MATERIAL EXPANSION VALVE SUCTION LINE MOUNTING DRAWING TITLE

ROCKWOOL, DENSITY 32KG/m


SIGHT GLASS LIQUID LINE PAD GIS AND TRANSFORMER BUILDING -
HVAC - INSTALLATION DETAILS - SHEET 03
DESIGNED BY: AK CONTRACTOR

DRAWN BY: MI

CHECKED BY: MA

PROJ. MGR.: IA
DUCT PENETRATION THROUGH INTERIOR WALLS, PARTITIONS (FIRE RATED) 8 TYPICAL REFRIGERATION PIPING SCHEMATIC DIAGRAM FOR SPLIT AHU(DX)
7 NTS QA/QC MGR:
NTS
A/E APPROVAL: WBS NO. DRAWING NO.

R.C. APPROVAL: CONT. NO. JCPDI I-2007 I-2007-HV-A1-0003-003


DATE: 06-Jun-24 SCALE NTS REV NO. 00