Schneider - PowerLogic P1F - Manual
Schneider - PowerLogic P1F - Manual
Protection Relay
User Manual
www.se.com
Protection Relay
Legal Information
The Schneider Electric brand and any trademarks of Schneider Electric SE and its
subsidiaries referred to in this guide are the property of Schneider Electric SE or its
subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and
furnished for informational use only. No part of this guide may be reproduced or
transmitted in any form or by any means (electronic, mechanical, photocopying,
recording, or otherwise), for any purpose, without the prior written permission of
Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the
guide or its content, except for a non-exclusive and personal license to consult it on
an "as is" basis. Schneider Electric products and equipment should be installed,
operated, serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information
contained in this guide may be subject to change without notice.
2 P1F/EN M/1.2.1
Protection Relay
Table of Contents
Legal Information ...............................................................................................2
General information ...........................................................................................6
Safety information and password protection .....................................................7
Presentation ......................................................................................................8
Introduction .............................................................................................. 8
Identification........................................................................................... 13
Installation ...................................................................................................... 16
Safety Precautions ................................................................................ 16
Precautions ............................................................................................ 17
Equipment Receipt and Identification .................................................... 19
Mounting and Assembly ........................................................................ 20
Connectors ............................................................................................ 24
Connection Diagrams ............................................................................ 30
Connecting Current Transformers (CTs) ............................................... 33
Connecting a Core Balance CT ............................................................. 35
Connecting Binary Inputs and Outputs Relays ...................................... 37
Connecting the Communication Port ..................................................... 39
Dimensioning the CTs ........................................................................... 40
CSH120, CSH200 and CSH300 Core Balance CTs ............................. 43
Commissioning ............................................................................................... 47
Safety Precautions ................................................................................ 47
Principles ............................................................................................... 48
Testing and Metering Equipment Required ........................................... 50
Energization ........................................................................................... 52
Validation of the Complete Protection Chain ......................................... 53
Checking Settings .................................................................................. 54
Checking the CT Ratio .......................................................................... 55
Checking the Phase Current Input Connections ................................... 56
Checking the Earth Fault Current Input Connections ............................ 58
Phase Overcurrent Protection (ANSI 50/51) Test ................................. 60
Earth Fault Protection (ANSI 50N/51N) Test ......................................... 63
Thermal Overload Protection (ANSI 49) Test ........................................ 68
Checking the Logic Input Connections .................................................. 70
Operational Commissioning .................................................................. 71
PowerLogic P1F Test Sheet .................................................................. 72
Use ................................................................................................................. 78
Human Machine Interface ..................................................................... 78
Operation ............................................................................................... 80
Settings .................................................................................................. 84
Password Protection .............................................................................. 90
USB Communication Port ...................................................................... 91
3 P1F/EN M/1.2.1
RS485 Communication Port .................................................................. 93
First Steps with eSetup Easergy Pro ..................................................... 94
Menu Map .............................................................................................. 99
Communication with Power Operation ................................................ 109
Functions and Parameters ........................................................................... 111
Phase CT Ratio ................................................................................... 111
Earth CT Ratio or Core Balance CT Rating ........................................ 112
Network Frequency ............................................................................. 113
Phase Overcurrent (ANSI 50-51) ........................................................ 114
Earth Fault Protection (ANSI 50N-51N) .............................................. 120
Overcurrent Protection Tripping Curves .............................................. 129
Cold Load Pick-up ............................................................................... 139
Inrush blocking..................................................................................... 141
Thermal Overload Protection (ANSI 49) .............................................. 144
Circuit Breaker Control ........................................................................ 147
External Trip (Auxiliary timers) ............................................................ 150
Logic Discrimination (ANSI 68) ............................................................ 152
Operating Language ............................................................................ 154
Trip Circuit Supervision (TCS) ............................................................. 155
Date and Time ..................................................................................... 161
Password ............................................................................................. 162
Watchdog Relay .................................................................................. 166
Auto-Reclose (ANSI 79) ...................................................................... 167
Negative Sequence Overcurrent (ANSI 46) ........................................ 176
Broken Conductor (ANSI 46BC) .......................................................... 179
Switch-On-To-Fault.............................................................................. 181
Circuit Breaker Failure (ANSI 50BF) ................................................... 183
Communication Orders ........................................................................ 185
Circuit Breaker Monitoring ................................................................... 186
Circuit Breaker Status Monitoring ........................................................ 192
Circuit Breaker Supervision ................................................................. 193
Local / Remote Mode .......................................................................... 195
Setting Group Selection ....................................................................... 197
Commissioning Mode .......................................................................... 200
Real Time Clock Synchronization via Opto-Inputs .............................. 203
Resetting of Latched LEDs and Outputs ............................................. 204
Fault and Alarm Records ..................................................................... 206
Instantaneous Records ........................................................................ 208
Alarm Status ........................................................................................ 209
Event Records ..................................................................................... 210
Measurements and Related Settings .................................................. 212
Counters .............................................................................................. 213
4 P1F/EN M/1.2.1
Protection Relay
5 P1F/EN M/1.2.1
General information
Legal notice
Copyright
Disclaimer
No responsibility is assumed by Schneider Electric for any consequences arising out
of the use of this document. This document is not intended as an instruction manual
for untrained persons. This document gives instructions on device installation,
commissioning and operation. However, the manual cannot cover all conceivable
circumstances or include detailed information on all topics. In the event of questions
or specific issues, do not take any action without proper authorisation. Contact
Schneider Electric and request the necessary information.
Contact information
35 rue Joseph Monier
92500 Rueil-Malmaison
FRANCE
Phone: +33 (0) 1 41 29 70 00
Fax: +33 (0) 1 41 29 71 00
www.se.com
Purpose
This user manual is intended for people who are experts on electrical power
engineering, panel builder, commissioner, and experienced users, communication
specialists or general users of the PowerLogicTM P1 protection relays.
The complete manual is arranged as follows:
• Preliminary sections, with the details of the manual (how to use it, glossary) and
technical data.
• Functions of the protection relay.
Explanations, diagrams and settings of the protection, control, monitoring and
maintenance, measurement, recording and programmable logic functions are
detailed in these sections.
• Quick Start Guide, delivered in the relay package, summarises instructions for
installation.
• Communication Manual, for the understanding and the setup of the
communication protocols with PowerLogic P1 protection relays.
We welcome your comments about this document. You can reach us by contacting
Customer Care Centre Contact page:
http://www.se.com/CCC
6 P1F/EN M/1.2.1
Safety information and password protection
Important information
Read these instructions carefully and look at the equipment to become familiar with
the device before trying to install, operate, service or maintain it. The following
special messages may appear throughout this manual or on the equipment to warn
of potential hazards or to call attention to information that clarifies or simplifies a
procedure.
The addition of this symbol to a "Danger" or "Warning" safety
label indicates that an electrical hazard exists which will result
in death or serious injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to
potential personal injury hazards. Obey all safety messages
that follow this symbol to avoid possible injury or death.
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will
result in death or serious injury.
Failure to follow these instructions will result in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided, can
result in death or serious injury.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, can
result in minor or moderate injury, or equipment damage.
Failure to follow these instructions can result in injury or equipment
damage.
NOTICE
NOTICE is used to address practices not related to physical injury.
Failure to follow these instructions can result in equipment damage.
User qualification
Electrical equipment should be installed, operated, serviced, and maintained only by
trained and qualified personnel. No responsibility is assumed by Schneider Electric
for any consequences arising out of the use of this material. A qualified person is
one who has skills and knowledge related to the construction, installation, and
operation of electrical equipment and has received safety training to recognise and
avoid the hazards involved.
Use the password protection feature in order to protect untrained person interacting
with the PowerLogic P1 protection relay.
7 P1F/EN M/1.2.1
Protection Relay Presentation
Presentation
Introduction
The PowerLogic P1F Family
The PowerLogic P1F is a member of PowerLogic P1 product family. The
PowerLogic P1F family of protection relays is designed for the protection and
operation of MV/LV utility substations and electrical distribution networks in industrial
installations.
It comprises six models suitable for normal protection applications involving current
metering:
• PowerLogic P1F model L (3 + WD relay outputs, without communication port) for
phase overcurrent and earth fault protection
• PowerLogic P1F model L (3 + WD relay outputs, with communication port) for
phase overcurrent and earth fault protection
• PowerLogic P1F model N (5 + WD relay outputs, with communication port) for
phase overcurrent, earth fault protection and thermal overload protection
• PowerLogic P1F model B (4 binary inputs, 3 + WD relay outputs, with
communication port) for phase overcurrent, earth fault protection, thermal
overload protection, switch on to fault and external trip
• PowerLogic P1F model A (4 binary inputs, 7 + WD relay outputs, with
communication port) for phase overcurrent, earth fault protection, thermal
overload protection, switch on to fault, external trip and inrush block
• PowerLogic P1F model E (8 binary inputs, 5 + WD relay outputs, with
communication port) for phase overcurrent, earth fault protection, thermal
overload protection, switch on to fault, external trip, inrush block, negative
sequence overcurrent, broken conductor and autoreclose
• PowerLogic P1F model E+ (8 binary inputs, 5 + WD relay outputs, with
communication port) for phase overcurrent, directional and admittance earth fault
protection, thermal overload protection, switch on to fault, external trip, inrush
block, negative sequence overcurrent, broken conductor and autoreclose
8 P1F/EN M/1.2.1
Protection Relay Presentation
• Model L
Basic phase and earth fault current protection with fault recording and two setting
groups. With only 4 relay output contacts and circuit breaker control keys, this
model is the most economical option in the range. A good choice for retrofit of
older technology devices or for a low cost medium or low voltage substations.
This model is offered as non-communicating however it may be extended with a
rear RS485 port for remote communication (switchable IEC 60870-5- 103 or
Modbus).
• Model N
Communicating device with basic phase overcurrent and earth fault protection. It
provides thermal overload function, fault and events recording and two setting
groups. It comprises 6 relay outputs, a front USB and rear RS485 communication
port with switchable IEC 60870-5-103 or Modbus protocol. Circuit breaker control
can be effected via front panel keys and from SCADA. This model is cost-
optimized for essential protection functions that require serial communication.
Suited to industrial or commercial sites with medium voltage electric supply as
back-up protection or to low voltage substations.
• Model B
Standard protection relay with phase overcurrent, earth fault protection and
communication. It provides switch on to fault and blocking logic functions, event
and fault recording and two setting groups. It comprises 4 relay outputs and 4
binary inputs, a front USB and rear RS485 communication port. Circuit breaker
control is effected by front panel keys, remote communication port or via binary
input. It’s suited to industrial or commercial sites with medium voltage supply as
cost optimized protection solution for feeder, incomer or transformer. Thus, it is
one of the best choices for panel builders and OEMs as a standard, compact and
effective protection relay.
• Model A
9 P1F/EN M/1.2.1
Protection Relay Presentation
Advanced model with phase overcurrent and earth fault protection. Covering all
features of model B, it’s comprises additionally inrush blocking function and in-
built circuit breaker and trip circuit supervision. Moreover it can store 4 sec of
disturbance records. CB control can be realized via front panel keys, remotely
thru communication port or via binary input. This model offers a unique
functionality of powering HMI board via USB front port. It means that setting and
data downloading can be done without auxiliary voltage presence. Having 4
binary inputs and 8 relays outputs it can be applied to more advanced schemes
within utilities or industrial sites as feeder, incomer or transformer protection.
• Model E
More advanced model with phase overcurrent and earth fault protection.
Covering all features of model A it comprises 8 binary inputs and 6 output relays.
This relay can meet the requirements of more advanced applications in medium
and low voltage substation. Additionally, in-built negative sequence overcurrent
protection, broken conductor detection and 4 shot auto-reclose function makes
PowerLogic P1F suitable as a feeder protection of overhead lines. Thanks to
small size and high functionality, this relay is regarded as a good retrofit solution
for almost all overcurrent electromechanical devices including auto-reclose
relays. If back-up protection relay is needed, the PowerLogic P1F model E will
provide required functionality and will keep the budget healthy.
• Model E+
It’s a highest model in PowerLogic P1F range. Covering all features of model E it
comprises 8 binary inputs and 6 output relays. This relay can meet the
requirements of more advanced applications in medium and low voltage
substation. Additionally, in-built directional and/or admittance earth fault
protection makes PowerLogic P1F suitable as a feeder protection of overhead
lines. If back-up protection relay is needed, the PowerLogic P1F model E will
provide required functionality and will keep the budget healthy.
Selection Table
The selection table lists the functions performed by the various PowerLogic P1F
models in standard operation.
PowerLogic P1F model
ANSI code L L N B A E E+
(RS485)
Hardware
Phase current inputs 3 3 3 3 3 3 3
Residual current inputs 1 1 1 1 1 1 1
Neutral voltage inputs - - - - - - 1
Digital inputs - - - 4 4 8 8
Digital outputs 3+WD 3+WD 5+WD 3+WD 7+WD 5+WD 5+WD
USB front port with powering - - 1 1 1 1 1
RS485 rear port - 1 1 1 1 1 1
Protection functions
Phase overcurrent 50/51 3 3 3 3 3 3 3
Earth fault overcurrent 50N/51N 2 2 2 2 2 3 3
Negative sequence overcurrent 46 - - - - - 1 1
Broken conductor 46BC - - - - - 1 1
Thermal overload 49 - - 1 1 1 1 1
10 P1F/EN M/1.2.1
Protection Relay Presentation
11 P1F/EN M/1.2.1
Protection Relay Presentation
Power Supply L N B A E E+
Voltage
24 – 240 V ac
● ● - - - -
24 – 250 V dc
24 – 60 V ac
- - ● ● ● ●
24 – 60 V dc
90 – 240 V ac
- - ● ● ● ●
90 – 250 V dc
12 P1F/EN M/1.2.1
Protection Relay Presentation
Identification
Reference Code
The reference code for a PowerLogic P1F is an alphanumeric code that defines the
PowerLogic P1F main functions and hardware options. List of available model look
as follows:
Model L: 4 relay outputs, without binary inputs and communication
Cortec no. Ion Vx Catalogue no.
Vx = 24-240Vac and
P1F1L1N0N92N0NN11N Ion = 1A/5A ; (0.01-2)Ion REL15000
Vx = 24-250Vdc
Vx = 24-240Vac and
P1F1L1N3N92N0NN11N Ion = 1A/5A ; (0.05-12)Ion REL15001
Vx = 24-250Vdc
Model L: 4 relay outputs, without binary inputs, rear RS485 port included
Cortec no. Ion Vx Catalogue no.
Vx = 24-240Vac and
P1F1L1N0N92N1NN11N Ion = 1A/5A ; (0.01-2)Ion REL15002
Vx = 24-250Vdc
Vx = 24-240Vac and
P1F1L1N3N92N1NN11N Ion = 1A/5A ; (0.05-12)Ion REL15003
Vx = 24-250Vdc
Model N: 6 relay outputs, without binary inputs, rear RS485 and front USB port
Cortec no. Ion Vx Catalogue no.
Vx = 24-240Vac and
P1F1N1N0N92N1NN11N Ion = 1A/5A ; (0.01-2)Ion REL15004
Vx = 24-250Vdc
Vx = 24-240Vac and
P1F1N1N3N92N1NN11N Ion = 1A/5A ; (0.05-12)Ion REL15005
Vx = 24-250Vdc
Model B: 4 binary inputs; 4 relay outputs, rear RS485 and front USB port including
powering
Cortec no. Ion Vx Catalogue no.
P1F1B1N0N91N1NN11N Ion = 1A/5A ; (0.01-2)Ion Vx = 24-60Vac/Vdc REL15006
Vx = 90-240Vac and
P1F1B1N0N92N1NN11N Ion = 1A/5A ; (0.01-2)Ion REL15007
Vx = 90-250Vdc
Vx = 90-240Vac and
P1F1B1N3N92N1NN11N Ion = 1A/5A ; (0.05-12)Ion REL15009
Vx = 90-250Vdc
Model A: 4 binary inputs, 8 relay outputs, rear RS485, front USB with powering,
disturbance recorder
Cortec no. Ion Vx Catalogue no.
P1F1A1N0N91N1NN11N Ion = 1A/5A ; (0.01-2)Ion Vx = 24-60Vac/Vdc REL15010
Vx = 90-240Vac and
P1F1A1N0N92N1NN11N Ion = 1A/5A ; (0.01-2)Ion REL15011
Vx = 90-250Vdc
Vx = 90-240Vac and
P1F1A1N3N92N1NN11N Ion = 1A/5A ; (0.05-12)Ion REL15013
Vx = 90-250Vdc
13 P1F/EN M/1.2.1
Protection Relay Presentation
Model E: 8 binary inputs; 6 relay outputs, rear RS485, front USB with powering,
disturbance rec., auto reclose
Cortec no. Ion Vx Catalogue no.
P1F1E1N0N91N1NN11N Ion = 1A/5A ; (0.01-2)Ion Vx = 24-60Vac/Vdc REL15014
Vx = 90-240Vac and
P1F1E1N0N92N1NN11N Ion = 1A/5A ; (0.01-2)Ion REL15015
Vx = 90-250Vdc
Vx = 90-240Vac and
P1F1E1N3N92N1NN11N Ion = 1A/5A ; (0.05-12)Ion REL15017
Vx = 90-250Vdc
Model E+: 8 binary inputs; 6 relay, rear RS485, front USB with powering,
disturbance rec., auto reclose, directional earth fault protection
Cortec no. Ion Vx Catalogue no.
P1F1E110N91N1NN11N Ion = 1A/5A ; (0.01-2)Ion Vx = 24-60Vac/Vdc REL15020
Vx = 90-240Vac and
P1F1E110N92N1NN11N Ion = 1A/5A ; (0.01-2)Ion REL15021
Vx = 90-250Vdc
Vx = 90-240Vac and
P1F1E113N92N1NN11N Ion = 1A/5A ; (0.05-12)Ion REL15023
Vx = 90-250Vdc
Vx = 90-240Vac and
P1F1B1N3N92N1NN11E Ion = 1A/5A ; (0.05-12)Ion REL15009R
Vx = 90-250Vdc
Model A: 4 binary inputs, 8 relay outputs, rear RS485, front USB with powering,
disturbance recorder
Cortec no. Ion Vx Catalogue no.
Vx = 90-240Vac and
P1F1A1N0N92N1NN11E Ion = 1A/5A ; (0.01-2)Ion REL15011R
Vx = 90-250Vdc
Vx = 90-240Vac and
P1F1A1N3N92N1NN11E Ion = 1A/5A ; (0.05-12)Ion REL15013R
Vx = 90-250Vdc
Model E+: 8 binary inputs; 6 relay outputs, rear RS485, front USB with powering,
disturbance rec., auto reclose, directional earth fault protection
Cortec no. Ion Vx Catalogue no.
Vx = 90-240Vac and
P1F1E110N92N1NN11E Ion = 1A/5A ; (0.01-2)Ion REL15021R
Vx = 90-250Vdc
Vx = 90-240Vac and
P1F1E113N92N1NN11E Ion = 1A/5A ; (0.05-12)Ion REL15023R
Vx = 90-250Vdc
14 P1F/EN M/1.2.1
Protection Relay Presentation
Vx = 90-240Vac and
P1F1B1N0N92N1NN31N Ion = 1A/5A ; (0.01-2)Ion REL15007C
Vx = 90-250Vdc
Vx = 90-240Vac and
P1F1B1N3N92N1NN31N Ion = 1A/5A ; (0.05-12)Ion REL15009C
Vx = 90-250Vdc
Model E: 8 binary inputs; 6 relay outputs, rear RS485, front USB with powering,
disturbance rec., auto reclose
Cortec no. Ion Vx Catalogue no.
P1F1E1N0N91N1NN31N Ion = 1A/5A ; (0.01-2)Ion Vx = 24-60Vac/Vdc REL15014C
Vx = 90-240Vac and
P1F1E1N0N92N1NN31N Ion = 1A/5A ; (0.01-2)Ion REL15015C
Vx = 90-250Vdc
Vx = 90-240Vac and
P1F1E1N3N92N1NN31N Ion = 1A/5A ; (0.05-12)Ion REL15017C
Vx = 90-250Vdc
Adapter for PowerLogic P1 standard flush mounting case to allow mounting on the REL15039
wall
Front cover with sealing for PowerLogic P1 standard case helping to prevent from REL15040
unauthorised access
15 P1F/EN M/1.2.1
Installation Protection Relay
Installation
Safety Precautions
Before Starting
You are responsible for compliance with all the existing international and national
electrical codes concerning protective grounding of any device.
You should also read the safety precautions described below. These instructions
must be followed strictly when installing, servicing or repairing electrical equipment.
DANGER
HAZARD OF ELECTRIC SHOCK, ELECTRIC ARC, BURNS OR EXPLOSION
• Only qualified personnel should install this equipment. Such work should be
performed only after reading this entire set of instructions.
• NEVER work alone.
• Turn off all power supplying this equipment before working on or inside it.
• Always use a properly rated voltage sensing device to confirm that all power
is off.
• Before performing visual inspections, tests, or maintenance on this
equipment:
o Disconnect all sources of electric power.
o Assume that all circuits are live until they have been completely de-
energized, tested and tagged.
o Pay particular attention to the design of the power system. Consider all
sources of power, including the possibility of back-feeding.
• Beware of potential hazards, wear personal protective equipment, and
carefully inspect the work area for tools and objects that may have been left
inside the equipment.
• The successful operation of PowerLogic P1 depends upon proper installation,
setting, and operation.
• Setting the PowerLogic P1 relay requires relevant expertise in the field of
electrical network protection. Only competent people who have this expertise
are allowed to set this product.
CAUTION
HAZARD OF DAMAGE
• Before performing Dielectric (Hi-Pot) or Megger testing on any equipment in
which the relay is installed, disconnect all input and output wires to the relay.
High voltage testing may damage electronic components contained in the
relay.
• Do not open the device case. The PowerLogic P1 relay contains components
that are susceptible to electrostatic discharge. It is assembled in specially
equipped premises.
16 P1F/EN M/1.2.1
Protection Relay Installation
Precautions
Introduction
● Individually packaged
● Installed in a cubicle
The transport, handling and storage precautions for PowerLogic P1F relays vary
depending on which of these two methods is used.
● Transport
PowerLogic P1F relays can be shipped to any destination by all suitable means of
transport, without taking any additional precautions.
● Handling
PowerLogic P1F relays can be handled without any particular care and can
withstand being dropped from a height of 1 m (3.28 ft).
● Storage
An PowerLogic P1F relay can be stored in its original packaging in a location with
the following environmental characteristics:
● Temperature: -30...+70 °C (or -22...+158 °F).
● Humidity ≤ 90%.
● Storage is limited to a maximum of one month if the relative humidity is
higher than 93% and the temperature higher than +40 °C (or +104 °F).
If the relays are to be stored for an extended period, we recommend the following:
● Do not unpack the PowerLogic P1F prior to its intended period of use.
● Check the environment and the condition of the packaging annually.
Once the PowerLogic P1F relay has been unpacked, it should be energized as soon
as possible.
● Transport
PowerLogic P1F relays can be transported by all suitable means of transport in the
usual conditions for cubicles.
Storage conditions should be taken into consideration for a long period of transport.
● Handling
If the cubicle is dropped, check the PowerLogic P1F’s condition by visual inspection
and energizing.
● Storage
We recommend keeping the cubicle protective packaging for as long as possible.
PowerLogic P1F relays, like all electronic units, should not be stored in a damp
environment for more than a month. They should be energized as quickly as
possible. If this is not possible, the cubicle reheating system should be activated.
17 P1F/EN M/1.2.1
Installation Protection Relay
If the conditions of use are outside the normal zone, special arrangements should be
made before commissioning, such as air conditioning of the premises.
The effect of corrosion on PowerLogic P1F relays has been tested according to the
IEC 60068-2-60 standard under the following "4-gas" test conditions:
● 21 days' duration
You are responsible for compliance with all the existing international and national
electrical codes concerning protective grounding of any device.
You should also carefully read the safety precautions described below. These
instructions must be followed strictly when installing, servicing or repairing electrical
equipment.
18 P1F/EN M/1.2.1
Protection Relay Installation
The PowerLogic P1F unit is shipped in a cardboard box which helps to protect it
against any knocks received in transport.
On receipt, check that the packaging has not been damaged. If it has, note any
anomaly on the delivery slip and inform your supplier.
NOTICE
Our products leave our factory in closed, sealed original packaging. At delivery,
if the packaging is opened or the seal is broken, Schneider Electric must be
informed.
Failure to follow this instruction can result in compromised confidentiality
and authenticity of the information contained in the products.
Package Contents
Identification Label
The identification label on the top of the relays is used to identify the PowerLogic
P1F:
Figure 1. Identification label
1 Reference number
2 Device type
3 Power supply voltage
4 Nominal phase current CT input and measuring range
5 Nominal earth fault current CT input measuring range
6 Nominal neutral voltage input measuring range
7 Serial number
8 EAC Logo For REL150xxR Commercial References only
Make sure the delivered PowerLogic P1F relay corresponds to the product ordered.
In particular, check the power supply voltage if it is correct for your installation.
19 P1F/EN M/1.2.1
Installation Protection Relay
PowerLogic P1F relays weigh 0.8 kg (1.76 lb.) maximum and are flush-mounted in a
mounting plate 1.5 to 4 mm (0.06 to 0.16 in) thick or 4 to 6 mm (0.16 to 0.24 in)
depending on method of spring clips mounting direction.
They are designed to be mounted indoors (flush mounting). It is possible to use
extra case adapter to wall mounting to which the relay is mounted using fastening
element.
To help to ensure a waterproof seal, the surface of the panel must be smooth and
solid. The front panel is sealed from behind
Dimensions
Figure 2. Dimensions
mm
in
. .
Cut-out
Figure 3. Dimensions of cut out
20 P1F/EN M/1.2.1
Protection Relay Installation
CAUTION
HAZARD OF CUTS
Trim the edges of the cut-out plates to remove any jagged edges.
Failure to follow these instructions can result in injury or equipment
damage.
PowerLogic P1F relay is held in place by 2 catches on the sides, behind the front
panel.
21 P1F/EN M/1.2.1
Installation Protection Relay
Removing P1F
1 To remove the relay unlock
spring clips by press until click,
so that the spring clips could
be taken out (repeat the
operation on the other side),
and then the relay could be
withdrawn from the cut-out in
the mounting plate.
22 P1F/EN M/1.2.1
Protection Relay Installation
23 P1F/EN M/1.2.1
Installation Protection Relay
Connectors
Introduction
All the PowerLogic P1F connectors can be accessed on the rear panel.
24 P1F/EN M/1.2.1
Protection Relay Installation
Connector Wiring
25 P1F/EN M/1.2.1
Installation Protection Relay
Diagram
For model B, A, E, E+
+ +
For model L, N
+ +
26 P1F/EN M/1.2.1
Protection Relay Installation
Diagram
For model E,+ E+ +
For model A+ +
27 P1F/EN M/1.2.1
Installation Protection Relay
Diagram
For model E+
Ia Ib Ic I
For model B, E
Ia Ib Ic I
For model A
Ia Ib Ic I
For model N
Ia Ib Ic I
For model L
Ia Ib Ic I
28 P1F/EN M/1.2.1
Protection Relay Installation
29 P1F/EN M/1.2.1
Installation Protection Relay
Connection Diagrams
General Safety Precautions
DANGER
HAZARD OF ELECTRIC SHOCK, ELECTRIC ARC OR BURNS
• Only qualified personnel should install this equipment. Such work should
be performed only after reading this entire set of instructions and
checking the technical characteristics of the device.
• NEVER work alone.
• Turn off all power supplying this equipment before working on or inside it.
Consider all sources of power, including the possibility of backfeeding.
• Always use a properly rated voltage sensing device to confirm that all
power is off.
• Wear insulating gloves to avoid any contact with a conductor that has
accidentally been energized.
• Screw tight all terminals, even those not in use.
Failure to follow these instructions will result in death or serious injury.
Earthing
The earth terminal is not required for the PowerLogic P1F devices due to the plastic
casing.
30 P1F/EN M/1.2.1
Protection Relay Installation
Each model (L, N, B, A, E, E+) PowerLogic P1F relays measure the following
currents:
31 P1F/EN M/1.2.1
Installation Protection Relay
Variant
Typical connection 3 phase CTs, earth
fault CBCT and neutral voltage
32 P1F/EN M/1.2.1
Protection Relay Installation
To determine the CT size, refer to Dimensioning the CTs of this chapter, page 40.
Connection Example
IB
Io
Core Balance CT
Connection Precautions
33 P1F/EN M/1.2.1
Installation Protection Relay
DANGER
HAZARD OF ELECTRIC SHOCK, ELECTRIC ARC OR BURNS
• Never leave the current transformer secondary in open circuit. The high
voltage that would result from opening the circuit is dangerous for the
operator and for the equipment.
• Never undo the ring lugs on the cables of the CT secondaries when there is
current on the primary.
DANGER
HAZARD OF ELECTRIC SHOCK, ELECTRIC ARC OR BURNS
• Wear insulating gloves to avoid any contact with a conductor that has
accidentally been energized.
Failure to follow these instructions will result in death or serious injury.
Recommended Cable
The cross-section of the cable for connecting the CTs must be selected according to
the characteristics of the CT secondary and the length of the link so as to limit the
wiring energy consumption.
34 P1F/EN M/1.2.1
Protection Relay Installation
The specifically designed CSH120, CSH200, CSH300 core balance CTs are for
direct earth fault current measurement. They should be used with PowerLogic P1F
relays with sensitive earth fault protection.
They can be connected to earth fault current inputs (terminal numbers C11 - C12)
Connection Example
The diagram below shows the connection of a core balance CT to measure the
earth fault current:
Figure 10. Connecting core balance CT diagram
IB
Io
Core Balance CT
The core balance CT must only measure the sum of the 3 phase currents. The
current circulating in the medium voltage cable shielding must therefore be
excluded. To avoid the current circulating in the cable shielding being detected by
the core balance CT, its component must be canceled by making this current
circulate a second time through the core balance CT in the opposite direction.
This is achieved by connecting the shields coming out of the cable ends to earth via
a wire that passes through the core balance CT. This wire must not come into
contact with any part c connected to earth before it passes through the core balance
CT, otherwise use an insulated wire.
35 P1F/EN M/1.2.1
Installation Protection Relay
Figure 11. Correct and not correct connecting the shields of the cable
Connection Precautions
36 P1F/EN M/1.2.1
Protection Relay Installation
DANGER
HAZARDOUS VOLTAGE
Do not allow hazardous live voltages to coexist with voltages that could be
connected to accessible parts (SELV, PELV or PEB) on power supply and I/O
block terminals A, B and C. The logic inputs and output relays are isolated from
one another with simple isolation.
Failure to follow these instructions will result in death or serious injury.
CAUTION
RISK OF DAMAGE TO THE I/O
Do not supply the logic inputs and relay outputs from sources of power that could
come from different phases of a 3-phase supply.
CAUTION
LOSS OF PROTECTION OR RISK OF NUISANCE TRIPPING
If the PowerLogic P1F is no longer supplied with power or is in fail-safe position,
the protection functions are no longer active and all the PowerLogic P1F output
relays are de-energized. Check that this operating mode and the watchdog relay
wiring are compatible with your installation.
Failure to follow these instructions can result in injury or equipment
damage.
37 P1F/EN M/1.2.1
Installation Protection Relay
Figure 12. Correct and not correct connecting the logic inputs
dc dc
+ dc + dc
38 P1F/EN M/1.2.1
Protection Relay Installation
Connection Diagram
+
+
Connection Precautions
The number of connected PowerLogic P1F relays must not exceed 32 and the total
cable length must not exceed 1300 m (4265 ft).
If the PowerLogic P1F is at the end of the line, install a Ω impedance matching
resistor between terminals A18 and A19.
39 P1F/EN M/1.2.1
Installation Protection Relay
The PowerLogic P1F phase and earth fault current inputs can be connected to
standard 1 A or 5 A CTs.
CT Selection Principle
The CTs must be dimensioned so that they do not become saturated at currents
where accuracy is required (with a minimum of 5 In).
The condition to be fulfilled by the CT saturation current (Isat) depends on the type
of overcurrent protection time delay:
Time Delay Condition to be Illustration
Fulfilled
Is . Is Isat
Practical Information
In the absence of any information about the settings, the characteristics below are
suitable for most situations:
40 P1F/EN M/1.2.1
Protection Relay Installation
If the CT load complies with the rated burden, i.e. Rw x Ins 2 ≤ ct, the saturation
current is higher than FLP x Inp.
If the resistance Rct is known, it is possible to calculate the actual CT FLP, which
takes account of the actual CT load. The saturation current equals actualFLP x Inp,
where:
To have an FLP of at least 20, i.e. a saturation current of 20 x Inp = 2 kA, the load
resistance Rw of the CT must be less than:
VAct 2.5
Rw, max = = 2 = 0.1
Ins 2 5
This represents 12 m (39 ft) of wire with cross-section 2.5 mm2 (AWG 12) for a
resistance per unit length of 8 /km (2.4 m/ft) approximately.
For an installation with 50 m (164 ft) of wiring with section 2.5 mm2 (AWG 12),
Rw = 0.4 .
As a result:
41 P1F/EN M/1.2.1
Installation Protection Relay
42 P1F/EN M/1.2.1
Protection Relay Installation
The specifically designed CSH120, CSH200 and CSH300 core balance CTs are for
direct earth fault current measurement. Due to their low voltage insulation, they can
only be used on cables.
• CSH120, CSH200 and CSH300 are closed CTs, with different inner diameters:
• The CSH120 inner diameter is 120 mm (4.75 in).
• The CSH200 inner diameter is 196 mm (7.72 in).
• The CSH300 inner diameter is 291 mm (11.46 in).
Figure 14. CSH120, CSH200, CSH300 core balance CTs photo
1 CSH300
2 CSH200
3 CSH120
43 P1F/EN M/1.2.1
Installation Protection Relay
Characteristics
Operating temperature – …+ C
(- …+ F)
Storage temperature – …+ C
(- …+ F)
Dimension A B D E F H J K L
44 P1F/EN M/1.2.1
Protection Relay Installation
Mounting Precaution
DANGER
HAZARD OF ELECTRIC SHOCK, ELECTRIC ARC OR BURNS
Only qualified personnel should install this equipment. Such work should be
performed only after reading this entire set of instructions and checking the
technical characteristics of the device.
• NEVER work alone.
• Turn off all power supplying this equipment before working on or inside it.
Consider all sources of power, including the possibility of backfeeding.
• Always use a properly rated voltage sensing device to confirm that all power is
off.
• Screw tight all terminals, even those not in use.
• Install the core balance CTs on insulated cables (the CTs do not have MV
insulation).
• Cables with a rated voltage of more than 1000 V must also have shielding
connected to the protective earth.
Failure to follow these instructions will result in death or serious injury.
45 P1F/EN M/1.2.1
Installation Protection Relay
Connection Characteristics
46 P1F/EN M/1.2.1
Protection Relay Commissioning
Commissioning
Safety Precautions
Before Starting
You are responsible for compliance with all the existing international and national
electrical codes concerning protective grounding of any device.
You should also read the safety precautions described below. These instructions
must be followed strictly when installing, servicing or repairing electrical equipment.
DANGER
HAZARD OF ELECTRIC SHOCK, ELECTRIC ARC, BURNS OR EXPLOSION
• Only qualified personnel should install this equipment. Such work should be
performed only after reading this entire set of instructions.
• NEVER work alone.
• Turn off all power supplying this equipment before working on or inside it.
• Always use a properly rated voltage sensing device to confirm that all power
is off.
• Before performing visual inspections, tests, or maintenance on this
equipment:
o Disconnect all sources of electric power.
o Assume that all circuits are live until they have been completely de-
energized, tested and tagged.
o Pay particular attention to the design of the power system. Consider all
sources of power, including the possibility of back-feeding.
• Beware of potential hazards, wear personal protective equipment, and
carefully inspect the work area for tools and objects that may have been left
inside the equipment.
• The successful operation of PowerLogic P1 depends upon proper installation,
setting, and operation.
• Setting the PowerLogic P1 relay requires relevant expertise in the field of
electrical network protection. Only competent people who have this expertise
are allowed to set this product.
CAUTION
HAZARD OF DAMAGE
• Before performing Dielectric (Hi-Pot) or Megger testing on any equipment in
which the relay is installed, disconnect all input and output wires to the relay.
High voltage testing may damage electronic components contained in the
relay.
• Do not open the device case. The PowerLogic P1 relay contains components
that are susceptible to electrostatic discharge. It is assembled in specially
equipped premises.
Principles
PowerLogic P1F Tests
Protection relays are tested prior to commissioning, with the dual aim of maximizing
availability and minimizing the risk of malfunction of the assembly being
commissioned. The question is to define the list of tests required at the time of
commissioning.
These tests are not necessary for relays based on digital technology:
48 P1F/EN M/1.2.1
Protection Relay Commissioning
Not all the checks and tests described in this chapter apply to all PowerLogic P1F
models (L, N, B, A, E, E+). Each check or test begins with indicating which
PowerLogic P1F models it applies to: it does not apply to models whose identifier (L,
N, B, A, E, E+) has a bar over it.
Example
49 P1F/EN M/1.2.1
Commissioning Protection Relay
To check the current input connections, use a sinusoidal AC current generator of the
following type:
● 50 or 60 Hz frequency (according to the country of use)
● Single-phase (as minimum), adjustable from 0 to 32 A RMS
● Three-phases (recommended), adjustable from 0 to 32 A RMS per phase
● With injection-controlled digital chronometer, accurate to 10 ms
● With connector suited to the built-in test terminal block in the current input
connection diagram
If the current generator is equipped with electronic on/off controls, check that the
current is definitely zero in the automatic stop position (depending on the cursor
position, the solid state contactor can allow more than 5% of the current to flow
through).
Voltage Generator
To check that the PowerLogic P1F (B, A, E, E+) logic inputs are connected correctly
and directional earth fault protection use one of the following:
● A DC voltage generator, adjustable from 0 to 200 V DC for adaptation to the
voltage level of the tested input
● A DC voltage auxiliary power supply the same as the PowerLogic P1F auxiliary
supply voltage
● A AC voltage generator, adjustable from 0 to 130 V AC to check directional earth
fault protection function
Accessories
Metering Devices
Documents
50 P1F/EN M/1.2.1
Protection Relay Commissioning
51 P1F/EN M/1.2.1
Commissioning Protection Relay
Energization
Checks to be Performed Prior to Energization
Apart from the mechanical state of the equipment, use the diagrams and BOMs
provided by the contractor to check:
● The PowerLogic P1F label
● Conformity of the PowerLogic P1F power supply voltage (indicated on the
identification label on the front panel) with the power supply voltage of the
switchboard (or cubicle)
● Correct connection of the auxiliary power supply:
● Whether an earth CT is present
● The presence of test terminal blocks upstream from the current inputs
● Conformity of connections between the PowerLogic P1F terminals and the test
terminal blocks
With the equipment de-energized, check that the connections are tightened.
Energization Procedure
Record the PowerLogic P1F serial number (found on the identification label on the
top of the relay or menu cell OP PARAMETERS/Serial number) on the test sheet.
Record the PowerLogic P1F software version number (menu cell OP
PARAMETERS/ Firmware Version and Firmware Release) on the test sheet.
52 P1F/EN M/1.2.1
Protection Relay Commissioning
The complete protection chain is validated during the simulation of a fault that
causes tripping of the circuit breaker by PowerLogic P1F.
Simply testing one function can help to ensure that the whole system is working
correctly, provided it has been installed correctly.
Procedure
53 P1F/EN M/1.2.1
Commissioning Protection Relay
Checking Settings
Determining Parameter and Protection Settings
All the PowerLogic P1F parameter and protection settings are determined
beforehand by the design department in charge of the application and should be
approved by the customer.
It is presumed that the study has been carried out with all the attention necessary, or
even consolidated by a discrimination study.
All the PowerLogic P1F parameter and protection settings should be available for
commissioning in the form of a dossier.
Checks should be made when the PowerLogic P1F parameter and protection
settings have not been entered during commissioning tests, to confirm the
conformity of the parameter and protection settings entered with the values
determined during the study.
These checks consist of:
● Going through all the PowerLogic P1F parameter and protection setting cells
● For each menu cell, comparing the values entered in the PowerLogic P1F relay
with the values recorded in the parameter and protection settings file
● Correcting any parameter and protection settings that have not been entered
correctly.
NOTE: Once the checks are complete, as of that phase, the parameter and
protection settings should not be changed any further and are considered to be final.
The tests which follow must be performed with these parameter and protection
settings. It will not be possible to modify any values, even temporarily. The only
exception to this is the disabling of protection functions in order to isolate the
protection function being tested.
54 P1F/EN M/1.2.1
Protection Relay Commissioning
In the context of checking the complete protection chain, checking each CT verify
that its transformation ratio conforms to expectations and is identical for the 2 or 3
phase CTs.
Purpose
The CT conformity certificates can be used as a basis for the check. If these
documents are missing, proceed as follows:
Step Action
1 Check that the CT primary circuit is accessible, de-energized and
completely isolated.
2 Using documents (diagrams, etc.), determine the expected ratio and
check the corresponding PowerLogic P1F setting.
3 Make sure that the CT secondary is connected to the PowerLogic P1F
relay or short-circuited and install a clamp ammeter on the secondary
circuit of the first CT.
4 Connect the generator to the CT primary circuit.
5 Inject a current of at least 0.2 In (In: CT primary rated current) if possible
and measure the injected current.
6 Read the current measured in the secondary circuit by the clamp ammeter
and check that the transformation ratio conforms to expectations.
If the CT is connected to PowerLogic P1F, check that the current
displayed by PowerLogic P1F is the same as the current injected in the
CT primary.
7 Repeat steps 3 to 6 for the other phase CT(s) and check that the results
obtained are identical for both or all 3 CTs.
8 If the earth fault current is measured by a 1 A or 5 A CT, repeat steps 3 to
6 to check its transformation ratio.
9 Record your measurements on the test sheet.
55 P1F/EN M/1.2.1
Commissioning Protection Relay
L N B A E E+
Wiring Diagram
To inject a current into the phase A current input, connect the single-phase current
generator to the test terminal block, as shown in the diagram below.
Figure 16. Phase currents input connections diagram
test bloc
IB
Io
I
current
generator
Procedure
DANGER
HAZARD OF ELECTRIC SHOCK, ELECTRIC ARC OR BURNS
• Never leave the current transformer secondary in open circuit. The high
voltage that would result from opening the circuit is dangerous for the
operator and for the equipment.
• Never undo the ring lugs on the cables of the CT secondaries when there is
current on the primary.
DANGER
HAZARD OF ELECTRIC SHOCK, ELECTRIC ARC OR BURNS
• Wear insulating gloves to avoid any contact with a conductor that has
accidentally been energized.
• Short-circuit secondary current transformer winding by use test block without
disconnecting the wires from it. This connector ensures continuity of the
current transformer secondary circuits.
56 P1F/EN M/1.2.1
Protection Relay Commissioning
Step Action
1 Connect the current generator to inject a current into a phase current input.
2 Turn on the generator.
3 Inject the CT secondary rated current (1 A/5 A).
4 On the P1F display, check that the value of the phase A current is
approximately equal to the CT primary rated current or related to In
(depends on setting).
5 Turn off the generator.
6 Repeat steps 1 to 5 for the other two phase current inputs.
7 Replace the cover on the test terminal block.
57 P1F/EN M/1.2.1
Commissioning Protection Relay
L N B A E E+
Wiring Diagram
Connect the single-phase current generator to the test terminal block, as shown in
the diagram below (two applications – a) measurement residual earth fault current
and b) measurement earth fault current from core balance current transformer):
Figure 17. Earth fault current input connections diagrams
a)
test bloc
IB
Io
I
current
generator
b)
test bloc
IB
Io
I
current
generator
58 P1F/EN M/1.2.1
Protection Relay Commissioning
Step Action
1 Connect the current generator to inject a current into a phase current input.
2 Turn on the generator.
3 Inject the CT secondary rated current (1 A/5 A).
4 Check on the P1F display that the earth fault current value is approximately
equal to 1 A/5 A.
5 Turn off the generator.
6 Replace the cover on the test terminal block.
59 P1F/EN M/1.2.1
Commissioning Protection Relay
L N B A E E+
The phase overcurrent protection test is used to check the setting values for the
following protection functions:
● Tripping threshold
● Tripping time delay
Wiring Diagram
To inject current into the phase A current input, connect the single-phase current
generator as shown in the diagram below.
Use one of the P1F output relays to stop the chronometer. If you are using a circuit
breaker contact to stop the chronometer, the measured time includes the circuit
breaker operating time.
Figure 18. Connection diagram to phase overcurrent protection function tests
test bloc
IB
Io
I
current
generator
au iliary
voltage
stop
60 P1F/EN M/1.2.1
Protection Relay Commissioning
DANGER
HAZARD OF ELECTRIC SHOCK, ELECTRIC ARC OR BURNS
• Never leave the current transformer secondary in open circuit. The high
voltage that would result from opening the circuit is dangerous for the
operator and for the equipment.
• Never undo the ring lugs on the cables of the CT secondaries when there is
current on the primary.
DANGER
HAZARD OF ELECTRIC SHOCK, ELECTRIC ARC OR BURNS
• Wear insulating gloves to avoid any contact with a conductor that has
accidentally been energized.
• Short-circuit secondary current transformer winding by use test block without
disconnecting the wires from it. This connector ensures continuity of the
current transformer secondary circuits.
A definite time protection function uses two settings that are independent of one
another:
● The current set point (I>, I>> or I>>>)
● The time delay
Threshold check:
Step Action
1 If necessary disable:
• the earth fault protections (if they are based on the sum of the 3 phase
CTs).
• negative sequence overcurrent protection function.
• Switch on to fault protection function (B, A, E, E+).
• Broken conductor protection function (E, E+).
• thermal overload protection (N, B, A, E, E+).
• cold load pick up.
• auto reclose (if is triggered by current protection functions, E, E+).
2 Inject a current approximately equal to 80% of the threshold value.
3 Increase the current slowly until the P1F relay trips or until the overcurrent
protection (signals: tI>, tI>>, tI>>>) LED flashes quickly (if are assigned).
4 Record the current value at the time of tripping on the test sheet and
compare it with the value on the settings sheet.
5 Reset P1F (R key).
6 If you are not performing any other checks:
• Re-enable the protections and functions required by the settings sheet.
• Reset the thermal capacity used to 0%.
• When a blocking input is used, re-enable the back-up time delay
associated with each threshold.
61 P1F/EN M/1.2.1
Commissioning Protection Relay
The test consists of testing a few points on the curve, in the tripping zone for the
threshold I>.
62 P1F/EN M/1.2.1
Protection Relay Commissioning
L N B A E E+
The earth fault protection test is used to check the setting values for the following
protection functions:
● Tripping threshold
● Tripping time delay
There are two possible wiring diagrams, depending on whether the earth fault
current is being measured:
● Using the electrical sum of the currents measured by the 3 phase CTs – residual
current
● Using an earth fault core balance CT
To inject current into the phase A current input, connect the single-phase current
generator as shown in the diagram below.
Use one of the P1F output relays to stop the chronometer. If you are using a circuit
breaker contact to stop the chronometer, the measured time includes the circuit
breaker operating time.
63 P1F/EN M/1.2.1
Commissioning Protection Relay
test bloc
IB
Io
I
current
generator
au iliary
voltage
stop
To inject current into the phase Io current input, connect the single-phase current
generator as shown in the diagram below.
Use one of the P1F output relays to stop the chronometer. If you are using a circuit
breaker contact to stop the chronometer, the measured time includes the circuit
breaker operating time.
64 P1F/EN M/1.2.1
Protection Relay Commissioning
Figure 20. Connection diagram to earth (CBCT) fault protection function tests
test bloc
IB
Io
au iliary
I voltage
current
generator
stop
A definite time protection function uses two settings that are independent of one
another:
● The current set point (IN_1, IN_2 or IN_3 (E, E+))
● The time delay
Threshold check:
Step Action
1 If necessary disable:
• Phase overcurrent protections.
• negative sequence overcurrent protection function.
• Switch on to fault protection function (B, A, E, E+).
• Broken conductor protection function (E, E+).
• thermal overload protection (N, B, A, E, E+).
• cold load pick up.
• auto reclose (if is triggered by current protection functions, E, E+).
2 Inject a current approximately equal to 80% of the threshold value.
3 Increase the current slowly until the P1F relay trips or until the overcurrent
protection (signals: tIN_1, tN_2, tIN_3) LED flashes quickly (if are
assigned).
4 Record the current value at the time of tripping on the test sheet and
compare it with the value on the settings sheet.
5 Reset P1F (R key).
6 If you are not performing any other checks:
65 P1F/EN M/1.2.1
Commissioning Protection Relay
66 P1F/EN M/1.2.1
Protection Relay Commissioning
67 P1F/EN M/1.2.1
Commissioning Protection Relay
L N B A E E+
The thermal overload protection test is used to check the operation setting values for
this protection functions:
● Calculation of the thermal capacity used
● Alarm set point
● Tripping time delay
Wiring Diagram
To inject current into the phase A current input, connect the single-phase current
generator as shown in the diagram below.
Use one of the P1F output relays to stop the chronometer. If you are using a circuit
breaker contact to stop the chronometer, the measured time includes the circuit
breaker operating time.
Figure 21. Connection diagram to overload protection function tests
test bloc
IB
Io
I
current
generator
au iliary
voltage
stop
68 P1F/EN M/1.2.1
Protection Relay Commissioning
69 P1F/EN M/1.2.1
Commissioning Protection Relay
L N B A E E+
70 P1F/EN M/1.2.1
Protection Relay Commissioning
Operational Commissioning
Final Check
When the tests are complete, proceed as follows for the final check:
Step Action
1 Put the cover back on the test block
2 Look through all the screens relating to the PowerLogic P1F protection
functions and check that only the desired protections are active.
3 Check the conformity of the validated parameters in PowerLogic P1F
against the settings sheet.
4 Record the last event recorded by PowerLogic P1F on the test sheet so that
you can distinguish between the values attributable to the tests and those
due to subsequent activation of the protections by a fault on the installation.
The PowerLogic P1F relay is now operational.
71 P1F/EN M/1.2.1
Commissioning Protection Relay
This test sheet can be used to record the results of the commissioning tests.
Each test is described in detail in the Commissioning chapter.
Only carry out the tests required, depending on the relay type and the functions in
use.
Check the box when the check has been made and is conclusive.
Identification
Overall Checks
Type of Check
Preliminary inspection, prior to energization
Energization
Checking parameters and settings
Connecting the logic inputs (PowerLogic P1F, model B, A, E, E+)
Validation of the Complete Protection Chain
72 P1F/EN M/1.2.1
Protection Relay Commissioning
73 P1F/EN M/1.2.1
Commissioning Protection Relay
74 P1F/EN M/1.2.1
Protection Relay Commissioning
75 P1F/EN M/1.2.1
Commissioning Protection Relay
CLPU I>>
CLPU I>>>
CLPU IN_1
CLPU IN_2
CLPU IN_3
CLPU Brkn
Cond
CLPU Itherm
CLPU I2>
LEDs Tests
76 P1F/EN M/1.2.1
Protection Relay Commissioning
Comments
…………………………………………………………………………………………………
…………………………………………………………………………………………………
…………………………………………………………………………………………………
…………………………………………………………………………………………………
…………………………………………………………………………………………………
…………………………………………………………………………………………………
…………………………………………………………………………………………………
…………………………………………………………………………………………………
…………………………………………………………………………………………………
…………………………………………………………………………………………………
…………………………………………………………………………………………………
…………………………………………………………………………………………………
…………………………………………………………………………………………………
…………………………………………………………………………………………………
…………………………………………………………………………………………………
…………………………………………………………………………………………………
…………………………………………………………………………………………………
…………………………………………………………………………………………………
…………………………………………………………………………………………………
…………………………………………………………………………………………………
Date: Date:
77 P1F/EN M/1.2.1
Use Protection Relay
Use
Human Machine Interface
Front Panel
The Human Machine Interface (HMI) on the front panel of P1F relays consists of a
display, LEDs, keys and front local communication port (mini USB).
A sealable pivoting flap can help to prevent access to the setting keys by
unauthorized persons (optional equipment).
1 – ed “ rip” E
2, 3, 4, 5, 6, 7, – Freely programmable LED (second LED is yellow, rest of them red)
8 – Green “Healthy” E ( atchdog)
9 – Display (graphic liquid crystal display - LCD)
10 – Home key, return to top menu “ ecord” when pressed
11 – Reset/Clear key, return to upper level menu when pressed
12 – 4 arrow keys, and confirm entry OK key
Return to upper level menu
Enter lower level menu
Go to previous menu at same level
Go to next menu at same level
+ Enter edit mode
+ + Exit edit mode
13 – CB Open key
14 – CB Close Key
15 – Mini-USB type B port for local connections
78 P1F/EN M/1.2.1
Protection Relay Use
Display
I hreshold
. In
. . .
B
Menu organization
The menu content depends on the PowerLogic P1F model. The list of screens by
menu, for each model, is given at the end of this chapter – Menu Map. Menu in
PowerLogic P1F has got pulldown structure.
Default Display
A default screen is displayed automatically 10 minutes after the last keystroke. This
default screen is (depends on settings GLOBAL SETTINGS/LOC/Default Display):
• The screen displaying the three phase and earth fault currents per unit (in
reference to In or Ion)
• The screen displaying the three phase and earth fault currents in amperes
• The screen displaying CB status and possibility to CB control
• The screen displaying auto reclose status and possibility to blocking of auto
reclose
• The screen displaying control mode status and possibility to change the control
mode
79 P1F/EN M/1.2.1
Use Protection Relay
Operation
Access to Data
When the P1F operate, the user can read all the data contained in the relay.
The operator can acknowledge faults locally by pressing the Reset key.
The fault and signals LEDs light up to indicate a fault or any other signals assigned
to LEDs (depending on configuration).
Trip and Healthy LEDs are fixed, the rest of LEDs are freely configurable. LEDs can
be latched or not. If latching of LED is disabled, the LED goes out once the cause
disappeared.
Fault screens (column) inform the operator about the characteristics of the last fault
detected by the P1F relay.
The operator can consult the other cells using the , or keys. If the relay is
reset the operator can still consult the 20 last recorded faults in the FAULT
RECORDS menu (column).
80 P1F/EN M/1.2.1
Protection Relay Use
Fault Acknowledgement
After acknowledgement, the P1F relay displays the default display (set in GLOBAL
SETTINGS/LOC/Default Display).
81 P1F/EN M/1.2.1
Use Protection Relay
ecord umber
ault
ecord umber
larm
ecord umber
tart
Readout Counters
Each above counter can be reset in below cell (in the end of each counter column)
ounter eset
eset
• CB MONITORING COUNTER
82 P1F/EN M/1.2.1
Protection Relay Use
Reset of latched LEDs and relay outputs is possible if the causes disappeared.
Reset can be done by:
• Use reset key
• Assigned binary inputs
• From Scada system (depends on select control mode)
LED Test
The LED test is used to check that each LED on the front panel are working
correctly.
To perform the test (when any protections are not triggered and PowerLogic P1F is
energized from the voltage), press R button from default display cell level. After this,
all LEDs on the front panel light up for approx. 1s.
83 P1F/EN M/1.2.1
Use Protection Relay
Settings
Access to Parameters and Settings
These parameters and settings are divided into the following menus:
• The protection menu (SETTING GROUP x), which contains the essential settings
for setting up the protection functions
• The parameters menu (GLOBAL SETTINGS), which contains the parameters that
can be used to adapt PowerLogic P1F operation to particular applications
Setting a Parameter
Step Action
1 Select the menu cell for the function to be set using the , , or
keys.
Example:
I hreshold
. In
. . .
84 P1F/EN M/1.2.1
Protection Relay Use
Step Action
• To abort the current parameter entry, back to step 2 and set again
previous value or set.
5 • If the set parameter is completely set, then you can select a new settings
(menu cells) using the , , and keys and set as
described in step 3.
6 If all required P1F protection and parameter settings are completely set then
to confirm all new settings it is necessary exit from setting mode. To exit
from setting mode select Edit settings? cell from menu (SETTING
CHANGE MODE column):
Edit settings
E it ress
Step Action
1 Using the , , or keys to select in SETTING GROUP x/
OUTPUT RELAYS CONFIGURATION Gx signal or signals which to be
assigned to the outputs.
Example (E, E+)
rotect
rip
85 P1F/EN M/1.2.1
Use Protection Relay
Step Action
3 Using the , , or keys select output or outputs to assigned
definite signal. Digit 0 (in second row) under the relay output number means
that signal is not assigned to output. Digit 1 (in second row) under the relay
output number means that selected signal is assigned to selected output
(for example to RL 1 and RL 4):
rotect
rip
4 Press the OK key to confirm the new settings for relay outputs: the set
parameter value is displayed (not flashing) to indicate that it has been
considered by P1F only after exit from setting mode.
5 If the relay outputs is completely set, then you can select a new signals
using the and keys and set as described in step 2 and 3.
6 If all required P1F relay outputs are completely set then to confirm all new
settings it is necessary exit from setting mode (refer section Setting a
Parameter).
86 P1F/EN M/1.2.1
Protection Relay Use
Step Action
3 Using the , , or keys select input or inputs to assigned
definite signal. Digit 0 (in second row) under the binary input number means
that signal is not assigned to input. Digit 1 (in second row) under the binary
input number means that selected signal is assigned to selected input (for
example to BI 2 and BI 8):
tatus
B
4 Press the OK key to confirm the new settings for binary inputs: the set
parameter value is displayed (not flashing) to indicate that it has been
considered by P1F only after exiting from setting mode.
5 If the binary inputs is completely set, then you can select a new signals
using the and keys and set as described in step 2 and 3.
6 If all required P1F binary inputs are completely set then to confirm all new
settings it is necessary exit from setting mode (refer section Setting a
Parameter).
Step Action
1 Using the , , or keys to select in SETTING GROUP x/
LEDS CONFIGURATION Gx signal or signals which to be assigned to the
LED indicators.
Example:
rotect.
rip
87 P1F/EN M/1.2.1
Use Protection Relay
Step Action
and refer to the Entering the Password section.
3 Using the , , or keys select LED or LEDs to assigned
definite signal. Digit 0 (in second row) under the LED indicator number
means that signal is not assigned to this LED. Digit 1 (in second row) under
the LED indicator number means that selected signal is assigned to
selected LED (for example to LED 5 and LED 7):
rotect.
rip
4 Press the OK key to confirm the new settings for LED indicators: the set
parameter value is displayed (not flashing) to indicate that it has been
considered by P1F only after exit from setting mode.
5 If the LED indicator is completely set, then you can select a new signal using
the and keys and set as described in step 2 and 3.
6 If all required P1F LED indicators are completely set then to confirm all new
settings it is necessary exit from setting mode (refer section Setting a
Parameter).
The 4 password digits must be entered common. The procedure for entering the
password is as follows:
Step Action
1 The password entry screen is displayed and the first from the right digit (0)
flashes:
Edit settings
Enter
Lost Password
If you lost the password, read the serial number on the PowerLogic P1F label and
contact your local Schneider Electric after-sales service.
NOTICE
Please take care of your modified new password, reseting password may cause
some inconvenience or extra cost.
88 P1F/EN M/1.2.1
Protection Relay Use
More information about possibility to reset thermal image can be found in Thermal
Overload Protection (ANSI 49) section, page 144.
89 P1F/EN M/1.2.1
Use Protection Relay
Password Protection
More details are described in Password subchapter in Function and Parameters
chapter (see on page 162).
90 P1F/EN M/1.2.1
Protection Relay Use
Mini-USB type B front port is dedicated to local connection with eSetup Easergy Pro
setting and operating software tool for configuring PowerLogic P1 devices. By
default, port is disabled.
NOTICE
USB communication port is dedicated to set the relay; extract settings, event,
disturbance recorder files. USB port is not dedicated to energizing the device.
Operation
After downloading the FW, the USB port is enabled and keep enabled. When USB
communication is active then on LCD following pictogram is displayed:
Enable B port
Enable
B
Setting
Settings for the COMMUNICATION USB port can be found in GLOBAL SETTINGS/
COMMUNICATION USB menu:
91 P1F/EN M/1.2.1
Use Protection Relay
92 P1F/EN M/1.2.1
Protection Relay Use
RS485 rear port is dedicated to connection with SCADA system. By default port is
disabled.
Setting
Settings for the COMMUNICATION USB port can be found in GLOBAL SETTINGS/
COMMUNICATION RS485 menu:
93 P1F/EN M/1.2.1
Use Protection Relay
eSetup Easergy Pro is a setting and operating software tool for configuring
PowerLogic P1 devices, local operation and customization functions. The eSetup
Easergy Pro software is supplied directly through the Schneider – Electric website
www.schneider-electric.com, along with the eSetup Easergy Pro program for
recovering disturbance recording files, and all the PowerLogic P1 documentation in
PDF format.
Figure 24. eSetup Easergy Pro menu bar and tool bar
The eSetup Easergy Pro software has a graphical interface where the protection
relay settings and parameters are grouped under nine menu tabs:
• General
• Measurements
• Control
• Protection
• Matrix
• Logs
• Communication
The contents of the tabs depend on the device type and the selected application
mode. Refer to the User Manual of eSetup Easergy Pro for detailed information on
the setting views of each menu.
The eSetup Easergy Pro stores the device configuration in a setting file. The
configuration of one physical device is saved in one setting file. The configurations
can be printed out and saved for later use.
When starting to work with eSetup Easergy Pro, you have three options:
protection relay
• Connect to a relay and read the settings from the protection relay.
eSetup Easergy Pro can be connected to a single relay via the USB port in the
protection relays front panel or via RS485 in the protection relays rear port.
Operation Modes
The eSetup Easergy Pro software can be used in three operation modes:
• Disconnected mode
94 P1F/EN M/1.2.1
Protection Relay Use
The disconnected mode allows you to prepare parameters and settings files for
PowerLogic P1 prior to commissioning.
The parameter and protection setting files prepared in disconnected mode will be
downloaded later to the PowerLogic P1 protection relays in connected mode.
In Disconnected mode, the user can create a setting file from scratch, or open a
previously saved setting file as a basis for creating configuration for a protection
relay of the same type. Refer to the User Manual of eSetup Easergy Pro for more
information.
NOTICE
After writing new settings, configurations or firmware to a protection relay, perform
a test to verify that the protection relay operates correctly with the new settings.
• To have all the measurements and supporting data available for commissioning.
The PC fitted with the eSetup Easergy Pro software is connected to the USB port on
the front panel of the PowerLogic P1 using a USB cord.
• Connectors:
PC: type A male
95 P1F/EN M/1.2.1
Use Protection Relay
The PC fitted with the eSetup Easergy Pro software is connected to a group of
PowerLogic P1 units via a communication network (connection via serial link).
1. Install the USB driver from the eSetup Easergy Pro file package (location:
Drivers/P3 – for the PowerLogic P1 is the same driver as PowerLogic P3) for the
first time connecting the PowerLogic P1 protection relay to a PC running eSetup
Easergy Pro
2. Connect the USB cable between the PC running eSetup Easergy Pro and the
local port of the PowerLogic P1 protection relay, with the mini-USB type B connector
of the cable plugged into the protection relay and the type A connector to the PC.
3. On the eSetup Easergy Pro toolbar, click the ON connection button. The Login
pop-up window opens.
5. Click Connect.
A new window showing the relay information opens.
96 P1F/EN M/1.2.1
Protection Relay Use
Figure 28. Window of access level selection in the eSetup Easergy Pro
Name of the login for each levels are given in below table.
Level Login
Configurator conf
Operator oper
User user
97 P1F/EN M/1.2.1
Use Protection Relay
NOTE: If you connect for the first time to a device on which the default users and
passwords are used, see Password subchapter in Function and Parameters
chapter, page 162.
98 P1F/EN M/1.2.1
Protection Relay Use
Menu Map
The menu content depends on the PowerLogic P1F model. Binary inputs and relay
outputs menu cells content maximum number of binary inputs and relay outputs
which are different depends on the model. For example, for model A in relay outputs
menu cells is displayed 7 relay outputs (maximum), and for model E (or E+) 5 relay
outputs only.
Model L 0 3+WD
Model N 0 5+WD
Model B 4 3+WD
Model A 4 7+WD
Model E 8 5+WD
Model E+ 8 5+WD
CB status:Opened
CTRL: No operat.
0.00A 0.00A
0.00A 0.0mA
PJ104ENd
99 P1F/EN M/1.2.1
Use Protection Relay
RECORDS
RECORDS
Record Number Record Number Record Number CONTROL FAULT AUTORECLOSE CB MONITORING SPRING CHARGING
1:Fault 1 1:Alarm 1 1:Start 1 COUNTER COUNTER COUNTER COUNTER TIME COUNTER
Trip Alarm: Start: No.Trips No.Fault Trips No.[79]Action CB Close counter Record Number
tI> tI>> I> 0 0 Total 0 0 1: Char. Time 1
Fault Time Alarm Time Start Time No.Close No.Fault Starts No.Trips &Lockout CB Oper. counter Operating time
12:05:23.197 12:05:23.197 12:05:23.192 0 0 Total 0 0 4.0s
Figure 33. Menu map submenu part 2
Fault Date Alarm Date Start Date Counter Reset No.Alarms No.Successful CB Trips counter Time
01/01/20 01/01/20 01/01/20 CTRL:No operat. 0 Total 0 0 03:40:30.713
Active Set Group Active Set Group Active Set Group No.HW Warnings Cycle 1 Reclose CB AMPS Value Date
Group 1 Group 1 Group 1 0 No. 0 0.0MA 01/12/19
Fault Origin Alarm Origin Start Origin Counter Reset Cycle 2 Reclose
Phase A Phase B Phase A CTRL:No operat. No. 0
P1F/EN M/1.2.1
Use
Use Protection Relay
PROTECTION G1
PHASE O/C G1 SOTF G1 E/GND FAULT G1 NEGATIVE SEQ.O/C BROKEN CONDUCTOR THERM OVERLOAD
[50/51] [50/51] [50/51N/67N] [46] G1 G1 [49] G1
I> Threshold SOTF Threshold IN_1 Threshold I2> Threshold Ratio I2/I1 Itherm
1.00In 4.00In 0.10Ien 1.00In 20% 1.00In
Reset Delay Type Reset Delay Type Reset Delay Type Theta Trip
I> 0:IDMT IN_1 0: DMT I2> 0: DMT 100%
I>>> Threshold
4.00In
tI>>>
1.00s
CB Fail Time tBF tAUX1 tSel1 Cold Load PU Dead Time tD1 Close Shot? 4321
0.10s 10.00s 0.40s Lebel 100% 0.20s tI>>> 0000
I< Threshold tAUX2? Sel2? Cold Load PU Dead Time tD2 Inhib.Trip 4321
CBF 0.10In 2: Alarm 1: Enabled tCL 1.0s 20.00s tI>>>:Shot 0000
IN< Threshold tAUX2 tSel2 Cold Load PU Dead Time tD3 Close Shot? 4321
CBF 0.10Ien 10.00s 1.00s I> 0: No 1.00s tIN_1 0000
Block I>? tAUX3? Cold Load PU Dead Time tD4 Inhib.Trip 4321
0: No 1: Trip I>> 0: No 20.00s tIN_1:Shot 0000
Block IN>? tAUX3 Cold Load PU Reclaim Time tR Close Shot> 4321
0: No 10.00s I>>> 0: No 2.00s tIN_2 0000
LEDS
CONFIGURATION G1
PJ006ENa
0: Disabled
0: Disabled
HCDFT
COMMISSIONING
Enable RS485 por Enable USB por Pre-Time Relay O/P W54321
1: Enable 1: Enable 0.10s Status 000000
P1F/EN M/1.2.1
Protection Relay
Protection Relay Use
3) Open Power Operation connection from P1F via Easergy Pro or HMI:
Protocol: Modbus PO
L N B A E E+
Description
The phase CT ratio can be accessed in the protection menu and must always be set
at the time of commissioning. It is used by all PowerLogic P1 functions which deal
with the current.
NOTE: Good practice is to set this ratio before implementing the protection settings.
The parameter to be set is:
● Phase CT ratio setting (GLOBALSETTINGS/CT RATIO menu cell).
Settings
L N B A E E+
Description
The earth CT ratio (or core balance CT rating) can be accessed in the protection
menu and must always be set at the time of commissioning. It is used by all
PowerLogic P1 functions which deal with the earth fault current.
NOTE: Good practice is to set this ratio before implementing the protection settings.
Example of PowerLogic P1 Relays for Standard or Sensitive Earth Fault
Protection
The PowerLogic P1 relays concerned are:
● PowerLogic P1F (0,05-12)Ion -•1• (standard earth fault protection)
● PowerLogic P1F (0,01-2)Ion - • • (sensitive earth fault protection)
If connected to the common point of the 3 phase CTs, this parameter must be set to
the same value as the phase CT ratio.
Example of PowerLogic P1 Relays for Sensitive Earth Fault Protection
The PowerLogic P1 relays concerned are PowerLogic P1F – 2 (sensitive earth fault
protection). This type of PowerLogic P1 is designed to be connected to a core
balance current transformer (e.g. CSH120).
• For CSH core balance current transformer (CT ratio 470A / 1A) measuring
range for primary side is from 4,7A to 940A.
• For another core balance current transformer (CT ratio 100A / 1A)
measuring range for primary side is from 1A to 200A.
Settings
Network Frequency
Applicable to PowerLogic P1F Series
L N B A E E+
Description
The network frequency can be accessed in the protection menu and must always be
indicated (50 or 60 Hz) at the time of commissioning. It is used by all PowerLogic
P1F functions which deal with the phase current and the earth fault current.
PowerLogic P1F uses this parameter to adapt operation of the measurement and
protection algorithms to the network frequency. If the setting is implemented
incorrectly, the accuracy of the metering and protection functions will be seriously
affected.
Settings
L N B A E E+
Description
The overcurrent protection included in the PowerLogic P1F relays provides three-
stage, non-directional overcurrent protection with independent time-delay
characteristics. All overcurrent settings apply to all three phases but are independent
for each of the three stages.
Each protection stage can be selected to Trip the CB or to issue a signal (Alarm)
only.
If an overcurrent protection stage (I>?, I>>? Or I>>>? Menu) is set to Trip, Trip-
Inrush Bl (applicable for model A, E, E+), Trip-Latch (A, E, E+), Trip-Phase A
(A, E, E+), Trip-Phase B (A, E, E+) or Trip-Phase C (A, E, E+) it means that stage
is linked to the Protect.Trip and Prot.Trip pulse functions (see Setting a LED
indicators and Setting a Relay Output in chapter Use).
If Trip-Latch is selected, the overcurrent stage will remain high after a trip, until it is
reset via a binary input, the HMI or a remote RESET command.
3 independent stages (I>, I>> and I>>>) can be set to offer optimal discrimination:
● The first two stages (I> and I>>) have either a definite time (DMT) or inverse
definite minimum time (IDMT) setting with different types of standardized curve
(IEC, IEEE, RI).
● The third stage (I>>>) only has a definite time (DMT) setting. The minimum
setting can be used to obtain instantaneous operation (ANSI 50 function).
Example 1: Example of typical application: Protection curve with a first IDMT I>
stage and a second DMT I>> stage
I I
I I I
Additional Functions
The first two stages of the overcurrent protection in the PowerLogic P1F relays are
provided with a timer hold facility, which may either be set to zero or to a definite
time value. Setting of the timer to zero means that the overcurrent timer for that
stage will reset instantaneously once the current falls below 95% of the current
setting. Setting of the hold timer to a value other than zero, delays the resetting of
the protection element timers for this period. When the reset time of the overcurrent
relay is instantaneous, the relay will be repeatedly reset and not be able to trip until
the fault becomes permanent. By using the Timer Hold facility the relay will integrate
the fault current pulses, thereby reducing fault clearance time.
The timer hold facility can be found for the first and second overcurrent stages as
settings DMT tReset I> (and RTD/RTMS Reset I>) and DMT tReset I>> (and
RTD/RTMS Reset I>>), respectively.
The IEEE/US/IEC curves may have an inverse time reset characteristic (I> (I>>)
Reset Delay Type 1: IDMT setting) or instantaneous reset (I> (I>>) Reset Delay
Type 0: DMT setting). If IDMT reset is selected (I> (I>>) Reset Delay Type 1: IDMT
setting) then the following menu will be available: Ι> (I>>) RTD/RTMS RESET.
For more details and equations that can be used to calculate the inverse reset time
for IEEE/US/IEC curves refer to: Overcurrent Protection Tripping Curves, page 129.
When a feeder is energized, the current levels that flow for a period of time following
energizing may differ greatly from the normal load levels. Consequently, overcurrent
settings that have been applied to give short circuit protection may not be suitable
during this period.
For more information on Cold Load Pick-up refer to: Cold Load Pick-up, page 139.
Crossing the SOTF Threshold will initiate the SOTF function. The tSOTF time-delay
will then be started. If the SOTF element is set to Trip, Trip-Inrush Bl (A, E, E+) or
Trip-Latch (A, E, E+), it means that it is linked to the Protect. Trip and Prot. Trip
pulse functions (see Setting a LED indicators and Setting a Relay Output in chapter
Use).
If the SOTF element is set to Alarm, it means that it is linked to the Alarm function
(see Setting a LED indicators and Setting a Relay Output in chapter Use).
If Trip-Inrush Bl (A, E, E+) is selected, the SOTF element is blocked via the Inrush
Blocking function (refer to Inrush Blocking section, page 141).
If Trip-Latch (A, E, E+) is selected, the SOTF element will remain high after a trip,
until it is reset
The Inrush Blocking function measures the ratio of second to fundamental harmonic
currents. It can be used as a “bloc ing logic” of I>, I>>, I>>>, IN_1, IN_2, (A, E, E+)
IN_3 (E, E+), I2> (E, E+), SOTF (A, E, E+), Broken Cond (E, E+), CB Fail (A, E,
E+), and AUXn (A, E, E+) in cases where the 2nd harmonic ratio is higher than the
settable threshold. Indeed, inrush blocking functions will reset the selected
protection function starts.
Blocked by the second harmonic ratio of a protection element is set in the main
setting cell for that element (for example: I>? 3: Trip-Inrush Bl). Each protection
element set to 3: Trip-Inrush Bl will be blocked by the Inrush current function.
The minimum duration of an overcurrent threshold inhibition (tReset) can be also set
(GLOBAL SETTINGS/INRUSH BLOCKING/Inrush Reset Time). This value
depends on the transformer power transient inrush duration: between 0.1 second
(for a 100 kVA transformer) to 1.0 second (for a large unit). It is used to avoid any
maloperation during a fixed time period in case of too sensitive a setting.
In the case of Logic Selectivity (Sel), the start contacts are used to raise the time-
delays of upstream relays, instead of blocking them. This provides an alternative
approach to achieving non-cascade types of overcurrent scheme. This may be more
familiar to some utilities than the blocked overcurrent arrangement. The Logic
Selectivity function provides the ability to temporarily increase the time-delay
settings of the second and third stages of phase overcurrent and measured earth
fault protection elements.
Two independent Logic Selectivity functions are available: Sel1 and/or Sel2.
This logic is initiated by energization of the appropriate binary input assigned to Sel1
(Sel2).
To allow time for a start contact to initiate a change of setting, the time settings of
the second and third stages should include a nominal delay.
Each stage of the phase protection element can be blocked via an appropriately
configured binary input. Binary inputs can be assigned to various functions (for the
list of available functions refer to Connecting Binary Inputs and Outputs Relays,
page 37). Such a configured input can be used by the blocking logic function or by a
protection element disabling function (Auto-reclose (E, E+), CB Fail or AUX (B, A, E,
E+)).
Block Diagram
& B OR
Start I>C Threshold
&
I>? 5: Trip-Phase A
I>? 6: Trip-Phase B
& Start I>
I>? 7: Trip-Phase C C
CBF: Block I> INSTANTENOUS
& Recorder
PJ154ENd
Additional Functions
Settings
The overcurrent protection included in the PowerLogic P1F relay provides non-
directional three-phase overcurrent protection with independent time-delay
characteristics. All overcurrent settings apply to all of the three phases but are
independent for each of the three stages.
The first two overcurrent stages have time-delayed characteristics which are
selectable between inverse definite minimum time (IDMT) and definite time (DMT).
The third stage has definite time characteristics (DMT) only.
Setting the I> and I>> stages Authorized Values Default Setting
I>? Disabled
I>>? Trip,
Alarm
Trip-Inrush Bl (A, E, E+)
Disabled
Trip-Latch (A, E, E+)
Trip-Phase A (A, E, E+)
Trip-Phase B (A, E, E+)
Trip-Phase C (A, E, E+)
2> Threshold . … . In (step: 0.01 In)
1.2 In
I>> Threshold 1.4 In
Delay Type DMT
For more information on tripping curves and IEC SI
the reset time, refer to Overcurrent IEC VI
Protection Tripping Curves, page 129. IEC EI
LTI IEC SI
STI
RC
RI
IEEE MI
IEEE VI
IEEE EI
US CO2-P20
US CO8
RXIDG
BNP EDF
US CO2-P40
US CO5
US CO6
US CO7
US CO9
US CO11
HV_Fuse
tI>
. … s (step . s) 1s
tI>>
2> TMS
. … .5 s (step: 0.01 s) 1s
I>> TMS
2> Time Dial . … s (step . s) 1s
I>> Time Dial
Reset Delay Type I> DMT
DMT
Reset Delay Type I>> IDMT
DMT tReset I>
0.0… s (step . s) 0s
DMT tReset I>>
RTD/RTMS Reset I>
0.0… 00 (step: 0.01) 0
RTD/RTMS Reset I>>
IDMT tripping can be blocked if any DMT stage is started (L, N, A, B, E, E+),
settings: IDMT interlock by DMT (GLOBAL SETTINGS/O/C ADVANCED column).
This setting is common for E/Gnd Fault [50N/51N] and Phase O/C [50/51]:
L N B A E E+*
*available directional (67N) and/or admittance (21YN) earth fault protection
Description
Two (L, N, B, A) or three (E, E+) independent stages (IN_1, IN_2, IN_3) can be set
to offer optimum discrimination:
● The IN_1 stage has either a definite time (DMT) or inverse definite minimum
time (IDMT) setting with different types of standardized curve (IEC, IEEE,
RI).
● The IN_2 stage only has a definite time (DMT) setting. The minimum setting
can be used to obtain instantaneous operation (ANSI 50N function).
● The IN_3 stage only has a definite time (DMT) setting. The minimum setting
can be used to obtain instantaneous operation (ANSI 50N function). Third
IN_3 stage is applicable for models E and E+ only.
If an earth fault stage (IN_1 stage?, IN_2 stage? Or IN_3 stage? (E, E+) menu) is
set to Trip, Trip-Inrush Bl (A, E, E+) or Trip-Latch (A, E, E+), Incos Trip (E+),
Insin Trip (E+), GN Trip (E+), BN Trip (E+), YN Trip (E+), it means that stage is
linked to the Protect. Trip and Prot. Trip pulse functions (see LED configuration,
page 308).
If an earth fault stage (IN_1 stage?, IN_2 stage? Or IN_3 stage? (E, E+) menu) is
set to Alarm, Incos Alarm (E+), Insin Alarm (E+), GN Alarm (E+), BN Alarm (E+),
YN Alarm (E+), it means that stage is linked to the Alarm function (see LED
configuration, page 308).
If an earth fault stage (IN_1 stage? Or IN_2 stage? Menu) in E+ model is set to
Incos Trip (E+), Incos Alarm (E+), Insin Trip (E+), Insin Alarm (E+), GN Trip
(E+), GN Alarm (E+), BN Trip (E+), BN Alarm (E+), YN Trip (E+), YN Alarm (E+),
it means that stage operate depends on fault direction.
If Trip-Inrush Bl (A, E, E+) is selected, the earth fault stage is blocked via the
Inrush Blocking function (refer to Inrush Blocking, page 141).
If Trip-Latch (A, E, E+) is selected, the earth fault stage will remain after a trip, until
it is reset via a binary input, the HMI or a remote RESET command.
Operation of the IN_1, IN_2 and IN_3 stages can be associated with the Earth Fault
Cold Load Pick-Up (N, B, A, E, E+) and Inrush Blocking (A, E, E+) function (see
page 141), which is used to avoid nuisance tripping of the protection when the
installation is energized. In particular, the CLPU Io function incorporates the option
of activating restraint based on the detection of a second harmonic component in the
phase currents.
Example: Curve for IDMT type IN_1 stage and DMT type IN_2 stage
Figure 4. Tripping curve for IN_1 and IN_2 stages for earth fault protection
I I
Depending on the sensitivity level required, two types of PowerLogic P1F relay are
available. Each type authorizes one or more connection diagrams to measure the
earth fault current.
Diagram 1 Diagram 2
Earth fault current measurement using the Current measurement from an earth CT with 1 A
common point of the 3 phase CTs, with 1 A or 5 or 5 A secondary rating.
A secondary rating.
The connection is as follows: The connection is as follows:
B B
I I
IB IB
I I
Io Io
However, if the protection stage needs to be set with low-level current values, use of
an core balance CT is strongly recommended (diagram 2). In the case of diagram 1,
precision errors in the 3 phase CTs can result in incorrect earth fault current
measurement. For stage below 5% CT In, this inaccuracy could lead to nuisance
tripping of the protection.
Additional Functions
Reset time
With an IDMT setting, the stage parameters are set in order to activate an IDMT
reset time. This enables coordination with electromechanical relays. By default, the
reset time is not active. Refer to Reset IDMT Characteristic, page137.
Operation of the IN_1, IN_2 and IN_3 stages can be associated with the CLPU
function, which is used to avoid nuisance tripping of the protection when the
installation is energized. By default, the CLPU function is not active. Refer to Cold
Load Pick-up and Inrush Blocking, page 139 and 141 respectively.
In the case of Logic Selectivity, the start contacts are used to raise the time-delays
of upstream relays, instead of blocking them. This provides an alternative approach
to achieving non-cascade types of overcurrent scheme. This may be more familiar to
some utilities than the blocked overcurrent arrangement. The Logic Selectivity
function provides the ability to temporarily increase the time-delay settings of the
second and third stages of phase overcurrent and measured earth fault protection
elements.
Two independent Logic Selectivity functions are available: Sel1 and/or Sel2.
This logic is initiated by energization of the appropriate binary input assigned to Sel1
(Sel2).
To allow time for a start contact to initiate a change of setting, the time settings of
the second and third stages should include a nominal delay.
Logic discrimination
PowerLogic P1F can be integrated in the logic discrimination system. This system
can be used when the installation requires the fault to be cleared within a short time.
It is used to bypass the time interval between the protection stages, imposed by time
discrimination. By default, on the PowerLogic P1F logic discrimination is not
assigned, therefore to use is has to be configured. Refer to Logic Discrimination
(ANSI 68), page 152.
Block Diagram
INSTANTENOUS
& Recorder
P0922ENb
Earth Fault protection logic diagrams for IN_1, IN_2 and IN_3 are the same but
without the IDMT characteristics for IN_2 and IN_3.
Additional Functions
Settings
The earth fault element operates from earth fault current that is measured directly
from the network; either by means of a separate CT located in a power system earth
connection or via a residual connection of the three line CTs.
All overcurrent settings are independent for each of the two stages (Model E, E+:
three stages).
Advanced earth fault settings (E+) concerning directional and admittance protections
can be found in following menu column: GLOBAL SETTINGS/E/F ADVANCED:
IDMT tripping can be blocked if any DMT stage is started (L, N, B, A, E, E+),
settings: IDMT interlock by DMT (GLOBAL SETTINGS/O/C ADVANCED column).
This setting is common for E/Gnd Fault [50N/51N] and Phase O/C [50/51]:
• In compensated network:
Incos(o)>Is
• In isolated network:
Insin(o)>Is
where:
Is – threshold of earth fault protection (in P1F – IN_1 and IN_2)
On the figures 1 and 2 bellow are presented tripping and inhibit area for criteria:
1. Incos
a) operation in line direction, b) operation in bus direction.
2. Insin
2) operation in line direction, b) operation in bus direction.
The above cases were considered for the maximum characteristic angle 90
(GLOBAL SETTINGS/E/F ADVANCED/Incos, Insin Sector Angle). Characteristic
angle can be set from 10 to 90 with step 1.
Inhibit Inhibit
Tripping Tripping zone
area
area area
-VN -VN
Io Io
Io Io
IN_1 threshold IN_1 threshold
-VN -VN
Conductance criterion GN
In order to help to ensure selective operation of earth fault protection in
compensated networks, is recommended to use conductance criterion GN.
Conductance criterion based on zero sequence (GN) of conductance, which is
determined following equation:
3𝐼𝑜
𝐺𝑁 = cos(𝜑𝑜) ∗ 1000
3𝑉𝑜
a) b)
IN_1 threshold IN_1 threshold IN_1 threshold
jBN jBN
Inhibit GN GN
area
Susceptance criterion BN
In order to help to ensure selective operation of earth fault protection in networks
with isolated neutral point, is recommended to use susceptance criterion BN.
Susceptance criterion based on zero sequence (BN) of susceptance, which is
determined following equation:
3𝐼𝑜
𝐵𝑁 = sin(𝜑𝑜) ∗ 1000
3𝑉𝑜
Conditions to operate susceptance protections are following:
𝐵𝑁 ≥ 𝐵𝑠
and
𝑉𝑜 ≥ 𝑉𝑜 𝑠𝑒𝑡 𝑣𝑎𝑙𝑢𝑒
where:
Bs – threshold of susceptance protection (in P1F – IN_1 and IN_2, if BN Trip or BN
Alarm are selected),
Operation mode of the susceptance protection can be directional or non-directional.
On the Figure 9 bellow is presented tripping and inhibit area for susceptance
criterion: a) for non-directional set, b) for directional set.
jBN jBN
Tripping Tripping Tripping Tripping
area area area area
IN_1 Threshold IN_1 Threshold
GN Inhibit Inhibit GN
Inhibit area
area area
IN_1 Threshold
Tripping Tripping
area area
Admittance criterion YN
In the case of compensated networks admittance protection can be used as a
backup protection.
The criterion is to act in the event of a network over- or undercompensation by
etersen’s coil in the case where an earthing resistor gets damaged. Admittance
criterion is non-directional protection only.
Admittance criterion based on zero sequence (YN) of admittance, which is
determined following equation:
3𝐼𝑜
𝑌𝑁 = ∗ 1000
3𝑉𝑜
Conditions to operate admittance protections are following:
𝑌𝑁 ≥ 𝑌𝑠
and:
𝑉𝑜 ≥ 𝑉𝑜 𝑠𝑒𝑡 𝑣𝑎𝑙𝑢𝑒
where:
Ys – threshold of admittance protection (in P1F – IN_1 and IN_2, if YN Trip or YN
Alarm are selected),
This criterion can be use in networks with isolated neutral point also.
On the Figure 10 bellow are presented tripping and inhibit area for admittance
criterion:
Tripping Tripping
area area
IN_1 Threshold
GN
Inhibit area
Tripping Tripping
area area
L N B A E E+
Introduction
Phase, earth fault and negative sequence overcurrent protection can be delayed
using the following types of tripping curve:
• Definite time (DT): I>, I>>, I>>>, Io> and Io>>, Is2> stages
In the case of standardized IDMT curves (IEC and IEEE type), a reset time can be
activated. This reset time enables PowerLogic P1F coordination with
electromechanical relays, placed upstream.
In definite time (DT) protection functions, the tripping time is constant. The time
delay is initialized as soon as the operating threshold Is is passed.
IDMT Curve
In IDMT protection functions, the tripping time depends on the measured value
(phase, earth fault or negative sequence current).
Equation
k
• t = T +c
I α
−P
Is
where:
t - Operating time in [s]
k, P, c, - Constants
Is - Current threshold setting [A]
I - Measured current in [A]
T - TMS – Time multiplier setting for IEC curves (setting range 0.02 – 1.5)
- TD – Time dial setting for IEEE and BNP (EDF) curves (setting range
0.02 – 100)
- Time coefficient for RI curve (setting range 0.1 – 10)
- Time coefficient for HV_Fuse curve (setting range 0.5 – 2)
Type of Curve
according to IEC 60255-151 Standard k c P
std definition
IEC Standard Inverse Time
IEC/A 0.14 0 0.02 1
(SI)
IEC Very Inverse Time (VI) IEC/B 13.5 0 1 1
IEC Extremely Inverse Time
IEC/C 80 0 2 1
(EI)
IEC Long Time Inverse (LTI) IEC 120 0 1 1
FR Short Time Inverse (STI) FR 0.05 0 0.04 1
UK Rectifier (Rect) UK 45900 0 5.6 1
IEEE Moderately Inverse IEEE
0.0515 0.114 0.02 1
Time (MI) (IEC/D)
IEEE
IEEE Very Inverse Time (VI) 19.61 0.491 2 1
(IEC/E)
IEEE Extremely Inverse Time IEEE
28.2 0.1217 2 1
(EI) (IEC/F)
US Short Time Inverse
US 0.02394 0.01694 0.02 1
(CO2 P20)
US Short Time Inverse
US 0.16758 0.11858 0.02 1
(CO2 P40)
US Long Time (CO5) US 4.842 1.967 1.1 1
US Definite Minimum Time
US 0.3164 0.1934 1.4 1
(CO6)
US Moderately Inverse Time
US 0.0094 0.0366 0.02 1
(CO7)
US Time Inverse (CO8) US 5.95 0.18 2 1
US Very Inverse Time (CO9) US 4.120 0.0958 2 1
US Extreme Inverse Time
US 5.570 0.028 2 1
(CO11)
BNP (EDF) EDF 1000 0.655 2 1
RI -4.2373 0 -1 1.43644
HV_Fuse 80 0 3 1
A time multiplier setting TMS is used to adjust the operating time of IEC & UK IDMT
curves.
A time multiplier setting TD is used to adjust the operating time of IEEE or US IDMT
curves.
Note:
1. For (CO2 P20), TD is defined like in MiCOM P20 series
These equations can only be used to draw graphs or when the measured value l is
constant during the fault.
1
t = 5.8 − 1.35 ln
k Is
I
Where:
t = tripping time
k = coefficient (from 0.3 to 1, by steps of 0.01), k = TMS/TD
Is = value of the programmed threshold (Pick-up value)
I = value of measured current
which is same as
−4,237
𝑡 = TD ∙
𝑙 −1
( ) − 1,436
ls
Where:
t = tripping time
k = coefficient (from 0.02 to 10, by steps of 0.01), k = TMS/TD
Is = value of the programmed threshold (Pick-up value)
100 100
10
10
Time [s]
Time [s]
A A
1
B B
C
C
1
D
0.1
D
0.1
E 0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
100 100
10
10
A
Time [s]
Time [s]
1
B
A C
1
B
0.1 C D
E
0.01 E 0.1
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Multiples of pickup setting: I/Is Multiples of pickup setting: I/Is
E: TMS=0.05 D: TMS=0.2 C: TMS=0.5 E: TMS=0.05 D: TMS=0.2 C: TMS=0.5
B: TMS=1 A: TMS=2 B: TMS=1 A: TMS=2
10
100
Time [s]
Time [s]
A 1
10 A
B
B
C
C
D 0.1
1 D
E
E
0.01
0.1
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
10
10
A
Time [s]
Time [s]
1 B
1
D
0.1
0.1
E D C B A 0.01
0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Multiples of pickup setting: I/Is
Multiples of pickup setting: I/Is
E: TMS=0.05 D: TMS=0.2 C: TMS=0.5 E: TD=0.05 D: TD=0.2 C: TD=0.5
B: TMS=1 A: TMS=2 B: TD=1 A: TD=2
10
10
Time [s]
Time [s]
1 A
1
B
A
C
B
0.1 D 0.1 C
D
E
0.01 E
0.01
0 1 2 3 4 5 6 7 8 9 1011121314151617181920
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Multiples of pickup setting: I/Is
Multiples of pickup setting: I/Is
E: TD=0.05 D: TD=0.2 C: TD=0.5
E: TD=0.05 D: TD=0.2 C: TD=0.5 B: TD=1 A: TD=2
B: TD=1 A: TD=2
100 100
10
10
A
Time [s]
Time [s]
1
B
A
C
B
1
0.1 C
D
D
E 0.01 E
0.1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Multiples of pickup setting: I/Is
Multiples of pickup setting: I/Is E: TD=0.05 D: TD=0.2 C: TD=0.5
E: TD=0.05 D: TD=0.2 C: TD=0.5 B: TD=1 A: TD=2
B: TD=1 A: TD=2
100 100
10
10
1
Time [s]
Time [s]
A A
B
B
0,1 C
1 C D
D 0,01 E
0,1 E
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
0 1 2 3 4 5 6 7 8 9 101112 1314 15 16171819 20
Multiples of pickup setting: I/Is Multiples of pickup setting: I/Is
10 10
1 1
Time [s]
Time [s]
A A
B B
0,1 C 0,1 C
D D
0,01 E 0,01 E
10
Time [s] 1
A
B
0.1 C
0.01 E
The IEEE/US/IEC curves may have an inverse time reset characteristic (I> (I>>)
Reset Delay Type 1: IDMT setting) or instantaneous reset (I> (I>>) Reset Delay
Type 0: DMT setting). If IDMT reset is selected (I> (I>>) Reset Delay Type 1: IDMT
setting) then the following menu will be available: Ι> (I>>) RTD/RTMS RESET. The
following equation can be used to calculate the inverse reset time for IEEE/US/IEC
curves:
tr
reset time = RTMS
I P
1−
Is
• For IEEE/US standard curves:
tr
reset time = RTD
I P
1−
Is
where:
tr, P - Constants
Is - Current threshold setting [A]
I - Measured current in [A]
RTD - Time dial setting for IEEE/US curves
RTMS - A time multiplier setting for IEC and HV_Fuse curves
Note:
To be in line with IEEE/US/IEC the RTMS (RTD) value should be equal to the TMS
(TD) value. The setting for RTMS or RTD is given to adjust the reset characteristic to
specific applications. Typically, RTMS = TMS and RTD = TD.
L N B A E E+
Description
The Cold Load Pick-up feature allows selected settings of P1F relays to be changed
to react to temporary overload conditions that may occur during cold starts. This
condition may happen by switching on large heating loads after a sufficient cooling
period, or loads that draw high initial starting currents.
When a feeder is energized, the current levels that flow for a period of time following
energizing may differ greatly from the normal load levels. Consequently, overcurrent
settings that have been applied to give short circuit protection may not be suitable
during this period.
NOTE: In the rest of this manual, this function is referred to by abbreviation: CLPU.
Block Diagram
Figure 13. Operating principles diagram for cold load pick-up
I> setting value
MAX SETTING GROUP 1(2)
IA, IB, IC /PROTECTION/
[50/51] PHASE O/C G1(2) Start I> Threshold
& Reset
tCL
&
Pulse
Cold Load PU Input SETTING GROUP
& 1(2)
/PROTECTION/
Cold Load PU? 2:Input COLD LOAD PU G1
OR (I> setting value {see above}) x
Cold Load PU? 1:Cur.+Input Reset (Cold Load PU Level {SETTING GROUP
1(2)/PROTECTION / COLD LOAD PU G1(2))} &
T TIMER 0
& &
OR
10s
I< 5% In
Time Delay
I> 10% In
& P0930ENb
Operation
The Cold Load Pick-up feature allows selected settings of P1F relays to be changed
to react to temporary overload conditions that may occur during cold starts. This
condition may happen by switching on large heating loads after a sufficient cooling
period, or loads that draw high initial starting currents.
When a feeder is energized, the current levels that flow for a period of time following
energizing may differ greatly from the normal load levels. Consequently, overcurrent
settings that have been applied to give short circuit protection may not be suitable
during this period.
The Cold Load Pick-up (CLPU) logic raises the settings of selected stages for a set
duration (tCLPU). This allows the protection settings to be set closer to the load
profile. Cold load pick-up cannot restart until the end of tCLPU duration. The CLPU
logic provides stability, without compromising protection performance during starting.
The CLPU can be triggered by a digital logic Input Cold Load PU (Cold Load PU?
1: Cur+Input or Cold Load PU? 2: Input (A, E, E+)) which can be assigned to 52a
CB status or by current stages logic (Cold Load PU? 1: Cur+Input). If the CLPU
logic has to be triggered by current criteria only, Cold Load PU Input (A, E, E+)
function must not be configured to any digital input. Typically, Cold Load PU (A, E,
E+) binary Input is wired to 52A CB status. If this function is configured to selected
input, both criteria will work in parallel way.
Additional Functions
Settings
Additional Info
Inrush blocking
Applicable to PowerLogic P1F
L N B A E E+
Description
The inrush blocking function help to ensure protection stability during transformer
energizing based on the presence of harmonic 2. The Inrush Blocking function
measures the ratio of second to fundamental harmonic currents. It can be used as
“bloc ing logic” for I , I , I , (B, A, E, E+), IN_1, IN_2, IN_3 (E, E+), I2>
(E, E+), Broken Conduct (E, E+), in cases where the harmonic 2 ratio is higher than
the set threshold. Indeed, inrush blocking functions will reset selected protection
starts.
1: Yes
2: Closing
If 2: Closing is selected, the protection element block is active after the CB closes
until Unblock Inrush Time elapses (this can be also set in the GLOBAL
SETTINGS/INRUSH BLOCKING menu column). If 1: Closing is selected, the
minimum duration of the overcurrent stage inhibition (Inrush Reset Time) can be
also set (see above: 1: Yes). This option can increase protection reliability, because
inrush blocking is limited to cases where inrush current can appear (closing of CB).
Therefore it can be used on outgoing lines with transformers. Note that for incoming
feeders the inrush current can be also present when CB is closed and an outgoing
line with a transformer is closing. In such a case the CB status of the incoming
feeder is not changed but Inrush current can trip protection element. The 2: Closing
option is not recommended for such an application.
Block Diagram
Figure 14. Diagram depicts the example for the I> protection element only
Inrush Blocking? 1:Yes
Inrush
Reset Time
Calculation for curents above Pulse
0.2In: IA2h, IB2h, IC2h 2nd Harmonic Inrush detection (I2h/I1h)
MAX Ratio setting & setting
{IA2h, GLOBAL SETTINGS
If IA<0.2In then IA2h=0% GLOBAL SETTINGS
/INRUSH BLOCKING
IB2h, /INRUSH BLOCKING
If IB<0.2In then IB2h=0%
IC2h}
If IC<0.2In then IC2h=0%
OR
Inrush Blocking? 2:Yes,
Closing
T TIMER 0
P0932ENb
Operation
For each of the three phases currents (IA, IB, IC), the harmonic restraint function
compares the ratio of 2nd harmonic to the fundamental with the set ratio (Harmonic
2/Fundamental settable from 10 % up to 50 % in steps of 1%).
The minimum fundamental current value required for operation of the Inrush
Blocking function is 0.2 In, and there is no upper limit to disable this feature.
However, in transformer protection, the high set overcurrent stage should not be
controlled by this Inrush Blocking feature; this enables detection of all high current
faults without inrush blocking.
It is possible to set two options for Inrush Current logic in the GLOBAL SETTINGS/
INRUSH BLOCKING/Inrush Blocking? Menu:
1: Yes – monitoring is permanent. The Inrush Blocking function will block the
selected protection stages every time inrush conditions are present on the line
(Ratio of 2nd Harmonics measured greater than Inrush set ratio), and will be active at
least for the duration of Inrush Reset Time. This timer defines the minimum
duration of overcurrent threshold inhibition (0-200 s, settable). This timer starts as
soon as operating inrush current threshold picks up:
● If the inrush condition lasts less than the set value for Inrush Reset Time, the
selected overcurrent function will be inhibited for the duration of Inrush Reset
Time.
● If the inrush condition lasts longer than the set value for Inrush Reset Time, the
selected overcurrent function will remain inhibited as long as the inrush condition
is present.
2: Closing – monitoring is based on the Close CB order output. The Inrush
Blocking function will block the selected protection stages every time a close
command is executed and the Ratio of measured 2nd harmonics is greater than the
set Inrush set ratio, and will be active at least for the duration of Unblock Inrush
Time.
Additional Functions
Settings
Additional Info
The 2nd harmonic blocking detects high inrush current flows that occur when
transformers or machines are connected. The function will then block the following
functions:
● PHASE O/C [50/51]
● SOTF [50/51] (B, A, E, E+)
● E/GND FAULT [50/51N]
● NEGATIVE SEQ. O/C [46] (E, E+)
● BROKEN CONDUCTOR (E, E+)
● AUX TIMERS (B, A, E, E+)
The 2nd harmonic blocking function identifies an inrush current by evaluating the
ratio of the second harmonic current components to the fundamental wave. If this
ratio exceeds the set thresholds, then the inrush stabilization function operates.
The minimum fundamental current value required for operation of the inrush
blocking function is 0.2 In, and there is no upper limit to disable this feature.
L N B A E E+
Description
The relay incorporates a current-based thermal replica, using r.m.s. load current to
model heating and cooling of the protected plant. The element can be set with both
alarm and trip stages.
The heat generated within an item of plant, such as a cable or a transformer, is the
resistive loss (I2R x t). Thus, heating is directly proportional to current squared. The
thermal time characteristic used in the relay is therefore based on current squared,
integrated over time. The relay automatically uses the largest phase current for input
to the thermal model.
This characteristic is used to help to protect cables, dry type transformers (e.g. type
AN), and capacitor banks.
K ² -
p
tTrip = Te ln
K ² − t rip
Where:
tTrip = Tripping time (in seconds)
Te = Thermal time constant of the equipment to be protected (in seconds)
θP = Steady state pre-loading thermal state before application of the overload
θtrip rip thermal state. If the trip thermal state is set at , then θ trip
I eq
K = Thermal overload equal to
1.05 Itherm
Ieq = Equivalent current corresponding to the R.M.S. value of the largest phase
current
Itherm = Setting value. It is full load current rating
The tripping time varies according to the load current carried before application of
the overload, i.e. whether the overload was applied from ‘hot” or “cold”.
The parameter settings are available in the various menus. The calculation of the
thermal state is given by the following formula:
Ieq
2
−t −t
+1 = 1 − e Te + e Te
1.05 Itherm
θ is calculated every 10 ms.
If all the phase currents are above 0.1 x Itherm the value of Tr (time constant for
cooling) is used instead of Te (time constant for heating):
Ieq
2
−t −t
+1 = 1 − e Tr + e Tr
1.05 Itherm
In a typical application (transformer, cable, ...) Tr should be equal to Te. Different
setting values of Te and Tr are only used in motor applications.
Block Diagram
Figure 15. Operating principle diagram for thermal overload protection
HMI Reset Theta val.
OR
Reset Theta val. Input
Alarm
IA Theta
Alarm
IB MAX Threshold
IC Alarm Recorder
Thermal Characteristic
Block. Itherm Input SETTING GROUP 1(2)
/PROTECTION/
[49] THERM OVERLOAD G1(2) Theta Trip
Therm OL? 1: enabled Threshold
Protect. Trip
P0926ENb
Operation
The magnitudes of the three phase currents are compared and the largest
magnitude selected as the input to the thermal overload function. If this current
exceeds the thermal trip threshold setting a start condition is asserted.
Additional Functions
Settings
Additional Info
The magnitudes of the three phase currents are compared and the largest
magnitude selected as the input to the thermal overload function. If this current
exceeds the thermal trip threshold setting a start condition is asserted.
The Thermal Trip signal remains high until the thermal state drops below the thermal
reset threshold.
The thermal reset threshold is settable using the Theta Trip/Reset Ratio value.
If the Thermal State is above the Theta Trip threshold and then drops, the Thermal
Trip signal will reset when the Thermal State drops below the Thermal Reset
Threshold.
If Blocking Ithermal Input (B, A, E, E+) is in high state, for calculation Thermal
Characteristic uses current value 0xIn instead of measured value.
The reset function in the menu is also found in the MEASUREMENTS column with
the thermal state menu.
L N B A E E+
Description
The P1F relays includes the following options for control of a single circuit breaker:
- Local tripping and closing, via the relay menu or function keys (L, N, B, A, E, E+)
- Local tripping and closing, via relay binary inputs (B, A, E, E+)
- Remote tripping and closing, using the relay communications (N, B, A, E, E+)
Operation
A manual trip will be permitted provided that the circuit breaker is initially closed.
Likewise, a close command can only be issued if the CB is initially open. To confirm
these states, it will be necessary to use the breaker 52A (assigned to CB status
52A input (B, A, E, E+)) and/or 52B (assigned to CB status 52B input (B, A, E, E+))
contacts. Under these circumstances manual CB control will be possible, but the
Auto-reclose function will not be available. Additionally, it will be not possible to see
the CB status in the Control default cell.
Once a CB Close command is initiated the output contact (Close CB order) can be
set to operate following a user-defined time-delay (Time delay for Close setting in
GLOBAL SETTINGS/CIRCUIT BREAKER menu). This would give personnel time
to move away from the circuit breaker following the close command. This time-delay
will apply to all manual CB Close commands.
The length of the trip or close control pulse can be set via the tOpen pulse and
tClose Pulse settings respectively (GLOBAL SETTINGS/CIRCUIT BREAKER
menu). These should be set long enough to ensure the breaker has completed its
open or close cycle before the pulse has elapsed.
Note: The manual trip and close commands are found in the default Control cell and
the Close/Trip keys on the front panel.
If an attempt to close the breaker is being made, and a protection trip signal is
generated, the protection trip command overrides the close command.
If CB FLT Ext.Sign. (B, A, E, E+) is assigned to a binary input this signal is checked
before manual closing of the CB. This function uses the signal received at the relay’s
binary input to confirm whether the breaker is capable of closing (sufficient circuit
breaker energy for example). A user-settable time-delay, tCB FLT Ext.Sign. (B, A,
E, E+), is included for manual closure. If, following a close command, the CB does
not signal a healthy condition before that timer elapses, then the relay will lockout
and issue an alarm.
If PowerLogic P1F detects a fault, closing of the output relay RL1 normally open
contact trips opening of the circuit breaker by supplying power to the shunt trip coil.
This contact stays closed after the circuit breaker trips, until the fault is
acknowledged.
Undervoltage trip coil
Figure 17 Undervoltage trip coil application
In this case, it is necessary to invert the control logic for output relay RL1. The
normally open contact will be kept in the closed position continuously, until a fault
appears. If P1F detects a fault, opening of the contact trips opening of the circuit
breaker by opening the undervoltage trip coil power supply circuit. This contact stays
open after the circuit breaker trips, until the fault is acknowledged.
If P1F detects a fault, opening of the RL2 output relay normally closed contact cuts
the closing coil power supply circuit. This contact stays open after the trip order, until
the fault is acknowledged. In this state, all close orders are inhibited.
Additional Functions
L N B A E E+
Description
Using a binary input, PowerLogic P1F relays can be used to take account of a trip
order issued by an external protection device.
For example, specific protection devices for power transformers (Buchholz, gas-
pressure-temperature detectors, etc.) can be hard-wired on an PowerLogic P1F
binary input to trip the circuit breaker.
The external devices can be hard-wired directly into the circuit breaker trip circuit,
but there are three advantages in connecting a PowerLogic P1F binary input:
● External trip orders will be memorized by the ANSI 86 function, integrated in the
PowerLogic P1F unit. Trip lockout will apply until the fault is acknowledged.
● The trip order and its origin will be indicated on the PowerLogic P1F front panel.
The trip will be saved and time tagged in the log of the last 20 faults.
● The circuit breaker trip circuit is simplified, and hence more reliable.
Block Diagram
Figure 19. Operating principle diagram for exteranal trip (auxiliary timers)
n= 1, 2, 3, 4
Alarm
AUXn? 2: Alarm
&
Inrush detection (I2h/I1h)
& T TIMER 0
Alarm Recorder
AUXn? 3: Trip-Inrush Bl
INSTANTENOUS
& Recorder
RESET LEDs
& OR Protect. Trip
Standard Operation
Four auxiliary timers, tAux1, tAux2, tAux3 and tAux4, are available and associated
with logic inputs Aux1, Aux2, Aux3 and Aux4 (refer to the SETTING GROUP
x/INPUTS CONFIGURATION menu). When these inputs are energized, the
associated timers start and, when the set time has elapsed, the associated LEDs
(SETTING GROUP 1(2)/LEDs CONFIGURATION menu) are lit or/and the
associated output relays close (refer to the SETTING GROUP 1(2)/OUTPUT
RELAYS CONFIGURATION menu). Time-delays can be independently set from 0
ms to 600 s.
Additional Functions
By default, this function is off.
L N B A E E+
All PowerLogic P1F relays can send a logic discrimination blocking order.
Description
The logic discrimination function can achieve a significant reduction in tripping times
for circuit breakers located right next to the source. It can mitigate the disadvantages
of the conventional time discrimination process.
This function exploits the hard-wiring of a logic data item between the protection
functions, making it possible to block the protection upstream by protection functions
located downstream. With logic discrimination, the protection settings should be
fixed in relation to the element to be protected without worrying about the
discrimination aspect.
Block Diagram
Figure 20. Operating principles diagram for logic discrimination
T TIMER 0
[79] Inhib.Trip tI>
tI> Time Delay
DMT/IDMT
Block.tI> Input & with DMT or IDMT
tI>
RESET
SETTI NG GROUP 1(2)
/PROTECTION/
I>? 0: disabled [50/51] PHASE O/C G1
&
Start I> Threshold
Start I>
&
CBF: Block I>
P0931ENb
Standard Operation
Each stage of the phase protection element can be blocked via an appropriately
configured binary input. Binary inputs can be assigned to the following functions
(SETTING GROUPx/INPUT CONFIGURATION Gx ):
• Block.tI> (ABE)
• Block.tI>> (ABE)
• Block.tI>>> (ABE)
• Block.tSOTF (ABE)
• Block.tIN_1 (ABE)
• Block.tIN_2 (ABE)
• Block.tIN_3 €
• Block.tI2> €
• Block.tBrkn Cond €
• Block.Itherm (ABE)
• Block.AUX1 (ABE)
• Block.AUX2 (ABE)
• Block.AUX3 (ABE)
• Block. [79] €
Such a configured input can be used by the blocking logic function or by a protection
element disabling function (Auto-reclose I, CB Fail or AUX (ABE)).
The blocking logic function can be applied to radial feeder circuits where there is
little or no back feed. For parallel feeders, ring circuits or where there can be a back
feed from generators, directional relays should be considered.
The blocking logic function allows the upstream IDMT relay to be blocked by the
start output of a downstream relay that has detected the presence of a fault current
above its threshold. Thus both upstream and downstream relays can have the same
current and time settings, and the blocking feature will automatically provide grading.
If in SETTING GROUPS x/PROTECTION Gx/[[50BF] CB Fail the function: Block I>
(IN>)? I is set to 0: Yes and the Circuit Breaker Fail protection is enabled, the
blocking command on the upstream relay will be removed if the downstream circuit
breaker fails to trip.
Additional Functions
By default, this function is off.
Operating Language
Applicable to PowerLogic P1F Series
L N B A E E+
Description
Settings
Selection of the operating language can be accessed in the parameter’s menu. The
parameter to be set is GLOBAL SETTINGS/LOC/LANGUAGE screen.
L N B A E E+
Description
The trip circuit extends beyond the relay’s enclosure and passes through more
components, such as fuses, wires, relay contacts, auxiliary switch contacts and so
on.
These complications, coupled with the importance of the circuit, have directed
attention to its supervision.
The simplest arrangement for trip circuit supervision contains a healthy trip lamp in
series with a resistance placed in parallel with the trip output relay contacts of the
protection device.
Block Diagram
Figure 21. Operating principle diagram for trip circuit supervision
CB closed (52A)
OR CB Alarm
TCS 52 Fail
Protect Trip
Prot.Trip pulse OR
Trip CB Order
P0933ENb
Standard Operation
The Trip Circuit Supervision function included in the PowerLogic P1F relays is
described below:
When the TC Supervision function is set to Yes under the CIRCUIT BREAKER sub-
menu, the relay checks continuously on trip circuit continuity whether the CB’s status
is open or closed.
When the TC Supervision function is set to Yes-52A under the CIRCUIT BREAKER
sub-menu, the relay checks continuously on trip circuit continuity in case when the
CB’s status is closed only.
during a time longer than the settable timer tSUP (in GLOBAL
CONFIGURATION/CIRCUIT BREAKER menu).
Example 1
In this example only the 52a auxiliary contact is available, the PowerLogic P1F relay
monitors the trip coil whatever the CB status is (CB open or CB closed).
Figure 22. Example 1 – Trip Coil Monitoring
Example 2
In this example both 52a and 52b auxiliary contacts are available; the PowerLogic
P1F relay monitors the complete trip circuit when the CB is closed and a part of the
trip circuit when the CB is open.
In this case it is necessary to insert a resistor R1 in series with 52b, if either the
output trip is latched or if it stays accidently closed, or if a long-time trip pulse is
programmed.
Example 3
In this example both 52a and 52b auxiliary contacts are available, the PowerLogic
P1F relay monitors the complete trip circuit whatever the CB status (CB open or CB
closed).
In this case it is necessary to insert a R1, if either the output trip is latched, or if it
stays accidently closed, or if a long-time trip pulse is programmed.
Figure 24. Example 3 – Trip Coil and Auxiliary Contact Monitoring Whatever
the Position of the CB contacts
The calculation of the R1 resistor value will consider the fact that a minimum current
is flowing through the logic input. This minimum current value is a function of the
relay auxiliary voltage range (Uaux).
1 – Case of example 2:
The R1 resistor maximum value (in Ohm) is defined by the following formula:
Where:
Uaux = auxiliary voltage value (in this case a DC voltage; range is given on label
under the top hinged cover. See table below).
Umin = input limit voltage at state 1 (see table on page 316).
Imin = minimum current value needed for the opto logic input to operate.
Imin = Umin/Rinput
R1 < (0.8 x Uaux – 19V)/ (19V/6000) R1 < (0.8 x Uaux – 72V)/ (72V/109000)
PR1 2
(1.2 Uaux )2 Watts
R1
2 – Case of example 3:
The R1 resistor maximum value (in Ohm) is defined by the following formula:
Where:
Uaux - auxiliary voltage value (in this case a DC voltage; its range is given on the
label - under the top hinged cover. See table below.)
Umin - internal minimum voltage value needed for the opto-input to operate.
Imin - minimum current value needed for the opto-input to operate.
Rcoil - trip coil resistance value.
R1 < R1 <
(0.8 x Uaux – 19)/(19V/6000) – Rcoil (0.8 x Uaux – 72)/ (72V/109000) – Rcoil
Example 4
In this example both 52a and 52b auxiliary contacts are available, the PowerLogic
P1F relay monitors the complete trip circuit whatever the CB status (CB open or CB
closed).
This application needs to assign two Binary Inputs to one TC Sup. Input logic
function.
In this case it is necessary to insert a RL1, if either the output trip is latched, or if it
stays accidently closed, or if a long-time trip pulse is programmed.
Figure 25. Example 4 – Trip Coil and Auxiliary Contact Monitoring by using
two Binary Inputs
Example 5
In this example 52a auxiliary contacts is available, the PowerLogic P1F relay
monitors the complete trip circuit if the CB status is closed.
This application needs to assign one Binary Input to TC Sup. Input logic function.
In this case it is necessary to insert a RL1, if either the output trip is latched, or if it
stays accidently closed, or if a long-time trip pulse is programmed.
Figure 26. Example 5 – Trip Coil and Auxiliary Contact Monitoring by using
two Binary Inputs
Additional Functions
Settings
L N B A E E+
Description
PowerLogic P1F has an internal clock which can be used to assign a date and time:
● To events recorded by the time-tagged record of the last 200 events function
● To other time-tagged events (Fault recorder), which can be accessed via the
communication
If the relay is powered from auxiliary voltage then the internal clock is maintained
from this voltage. In the event of failure of the PowerLogic P1F auxiliary power
supply, the internal clock is maintained by a backup capacitor (no battery inside). If
the backup capacitor will be discharged (161pprox.. after 72hours without voltage),
the internal clock will reset itself to 01/01/2015 00:00:00.
Settings
The date and time setting can be accessed in the OP PARAMETERS menu.
The date and time setting in the parameter’s menu is not considered when the
PowerLogic P1F date and time are synchronized via the communication.
Password
Applicable to PowerLogic P1F Series
L N B A E E+
Description
− User (Control only) – this level is used for tests and/or control execution
only (no changing of setting parameters) so signaling of SETTING
CHANGE MODE differs from above. On this password level all
programmable LEDs (from 3 up to 7 LEDs) flashing in the same time.
All password levels are additionally signaled by the special sign: , which informs
that change settings or controls (depend on password level) are allowed.
If the first password is different, this means that the Configurator password has been
changed.
The Operator password is still 0000. Therefore, to help to protect settings against
unauthorized access it is necessary to change the Protection setting password by
first entering 0000 then a new value.
The User password is still 0000. Therefore, if it is necessary to change it, first enter
0000 then the new value (Control right) of the password.
Notes: 1. If the Operator rights have not been changed, or if it has been set to
the default value (0000), it is possible to change all the settings in the
PROTECTION column, reset the counters and control the CB without
entering a password, simply by pressing the OK navigation key. This
makes it possible to change a chosen parameter by automatically
switching the P1F to the SETTING CHANGE MODE (the programmable
LEDs are flashing). This means that even after changing only one
parameter it is necessary to switch the P1F back to PROTECTION
MODE in order to activate the new settings (warm restart).
2. If the User rights password has not been changed or if it has been set to the
default value (0000) it is possible to control the CB in menu without password
protection.
Additional Functions
Using the SETTING CHANGE MODE helps to ensure that all changed parameters
will be applied simultaneously so as to avoid any problems caused by possible
setting inconsistencies.
The SETTING CHANGE MODE makes it possible to change settings while the relay
is active without any risk (the P1F continues to use the previous settings).
After exiting the SETTING CHANGE MODE, a warm reset of firmware is applied so
that all the protection counters are reset.
Note: Latched LEDs and outputs are reset (stored values are cleared during a
P1F reset).
To switch the P1F to the SETTING CHANGE MODE navigate to the SETTING
CHANGE MODE main header, then press the key:
Edit settings?
Enter PSWD
Edit settings?
Enter PSWD 0000
1. If the digit is flashing, change the digit to the required value by pressing the
key or the key.
The LCD displays ‘OK’ during approximately 1 second, then the new SETTING
CHANGE cell is displayed:
- Configurator rights:
Setting change:
Configurator
To indicate that the P1F is in SETTING CHANGE MODE on the level: Configurator
the programmable LEDs are sequential flashing
- Operator settings:
Setting change:
Operator
To indicate that the P1F is in SETTING CHANGE MODE on the level: Operator the
programmable LEDs are sequential flashing
- User only:
Setting change:
User
To indicate that the P1F is in SETTING CHANGE MODE on the level: User the
programmable LEDs are flashing (all LEDs in the same time). User mode is active
by 5 minutes only (since the last menu activity). After this time the relays
automatically leaves this mode.
Note: The parallel pressing: and keys it makes jump from any place
to:
Edit settings?
Enter PSWD
the menu cell in which the password can be entered (hot keys).
Press the OK navigation key to apply a warm reset and display the following cell:
Setting change:
Protected
Note: In SETTING CHANGE MODE all functions use the previously stored
settings (before the SETTING CHANGE MODE was entered).
Enter the password and then press OK navigation key to confirm the password and
switch to SETTING CHANGE MODE.
To change the password, first enter the existing password to obtain the appropriate
password protection rights.
Press OK navigation key to confirm the new password and jump to the cell
displaying information on protection rights.
Switch from SETTING CHANGE MODE to PROTECTION MODE. After this the
settings are password-protected and the P1F is in PROTECTION MODE.
Additionally the programmable LEDs stop flashing.
Watchdog Relay
Applicable to PowerLogic P1F Series
L N B A E E+
Description
PowerLogic P1F
PowerLogic P1F relays are equipped as standard with a watchdog relay (WD,
terminal numbers A3-A4-A5, see Installation chapter). This is a changeover relay
output which is kept permanently in the on-position (A3 – A5) by PowerLogic P1F. In
the event of PowerLogic P1 failure, or if the auxiliary power supply fails, the
watchdog relay reverts to the off-position.
When WD relay is used as typical WD contacts (not assigned Alarm signal to WD)
then WD status in COMMISSIONING/RELAY O/P Status cell is not visible.
L N B A E E+
Description
[79]: Ready
CTRL: no operation
The first line informs about the current state of the auto-reclose function. The
following can be displayed:
● [79] Ready – The auto-reclose function is unblocked and ready to operate.
● [79] In progress – An auto-reclose cycle is in progress.
● [79] Tempor.Block. – The auto-reclose function is temporary blocked after
Closing of CB (from RS485, Front Panel or via configured Binary Input) during
Inhibit Time tI on Close (GLOBAL SETTINGS/[79] ADVANCED
SETTINGS/Inhibit Time tI on Close). Also, temporary blocking feature is
activated when breaker closes (either 52a contact energizes or 52b contact de-
energizes) and [79] – IN PROGRESS is inactive. In this way the temporary
blocking feature will not be activated when the [79] function initiates the reclose,
only when its manually done by an operator who turns a control switch.
● [79]: Lockout – The auto-reclose function is internally blocked up to reset
signaling (Input assigned to Reset Latched Signals, C clear key on the front
panel, Reset Latched Signals via RS485, closing of CB command via P1F or
Unlockout command in CTRL line).
● [79] Block:CTRL. – The auto-reclose function is blocked via the communication
port or from P1F menu via the Auto-reclose default cell (CTRL line)
● [79] Block:Input – The auto-reclose function is blocked via a binary input
assigned to this effect.
● [79] Disabled – The auto-reclose function is disabled in the SETTING GROUP
x/PROTECTION Gx/AUTORECLOSE Gx [79] submenu.
There are two menu columns in which the Auto-reclose function can be configured:
● SETTING GROUP x/PROTECTION Gx/AUTORECLOSE Gx [79] – separate
settings for each setting group,
● GLOBAL SETTINGS/ [79] ADVANCED SETTING – common settings for all
setting groups.
The Auto-reclose function of the PowerLogic P1F is available only if the following
conditions are verified:
● The auxiliary contact of the CB status, 52a or 52b, must be connected to the
relay. Refer to the SETTING GROUP Gx/INPUTS CONFIGURATION Gx menu.
● The auto-recloser is ready for operation (neither disabled nor blocked). The
Autoreclose default cell should display: [79]: Ready.
● The trip output relay must be set to Prot.Trip pulse (recommended if an output
contact is used) or/and Protect Trip (if an energy trip output is used) and not
latched in the protection element’s settings (for example I>? Trip-Latch). The
trip output must not be latched either.
● The Close CB Order command must be assigned to the close CB output. The
close contact output must not be latched.
● In the SETTING GROUP x/PROTECTION Gx/AUTORECLOSE Gx [79] menu
all settings are properly configured.
NOTE: If the auxiliary supply is lost during an auto-reclose cycle, the auto-reclose
function is totally disabled.
In addition to [79] AUTORECLOSE Gx settings, the user will be able to fully link the
auto-reclose function to the protection function using the menus:
● SETTING GROUPS x/PROTECTION Gx/[50/51] PHASE O/C Gx,
● SETTING GROUPS x/PROTECTION Gx/[50/51N] E/GND FAULT Gx,
● SETTING GROUPS x/PROTECTION Gx/AUX TIMERS Gx.
Logic Inputs
The auto-reclose function has four inputs that can be assigned to the auto-reclose
logic. These inputs can be mapped to opto-isolated inputs in the SETTING GROUP
x/PROTECTION Gx/INPUTS CONFIGURATION Gx menu. External contacts can
then be wired to these inputs and influence the auto-recloser scheme. These four
logic inputs are:
● one external CB FLT Ext Sign. – external information that CB is not ready to
close (a spring not charged, too low level of CB gas, etc.),
● AUX 1 or AUX 2 assigned to trip and [79] shots – the external starting
commands,
● Block [79] – the external blocking command (for example: an external switch).
Logic Description
Dead times for all the shots (reclose attempts) can be independently adjusted.
The number of shots is directly related to the types of fault likely to occur on the
system and the voltage level of the system (for instance medium voltage networks).
The Dead Time (tD1, tD2, tD3 and tD4) and the minimum drop-off time start when
the CB has tripped (when the 52a input has dropped off – Start Dead t on 1: CB
trips or the protection element has reset – Start Dead t on 0: Protect.Reset
configuration option). The Dead Time is set to initiate the auto-recloser when the
circuit breaker is opened.
At the end of the relevant dead time the close command (Close CB Order) is
executed and the CB supervision timer is started. The length of this timer is equal to:
tClose Pulse (GLOBAL SETTINGS/CIRCUIT BREAKER) + 150 ms (Auto-reclose
CB Supervision logic). If the CB is not closed after this time-delay, the auto-
recloser is locked out ([79] Lockout) and the Alarm is issued (Alarm CB Time
Monitor).
The reclaim time (Reclaim Time tR) starts when the CB has closed. If the circuit
breaker does not trip again, the auto-reclose function resets at the end of the reclaim
time.
If a protection element operates during the reclaim time, the relay either advances to
the next shot programmed in the auto-reclose cycle, or it locks out (see Inhib.Trip
function description).
Standard Operation
The auto-reclose function provides the ability to automatically control the recloser,
with one, two, three, or four shot cycles. Each cycle implements a dead time and
a reclaim time.
During the auto-reclosing cycle, if the relay receives a command to switch setting
groups, this command is kept in memory, and will be executed only after the timer
elapses.
In addition to these settings, the user can fully link the auto-reclose function to the
protection function using the menus PROTECTION G1 / Phase OC and
PROTECTION G1/ E/Gnd.
Additional Functions
Most circuit breakers provide one trip-close-trip cycle. A time-delay is necessary for
the CB to return to its nominal state (for example, the spring that allows the circuit
breaker to close should be fully charged). The state of the CB can be checked using
an input assigned to the CB FLT Ext.Sign. function. If the CB FLT Ext.Sign. signal
is detected during Closing time, the Auto-reclose Close Command is interrupted and
blocked and the CB remains open. In this case the Autorecloser will be Lockout by
not successful close command monitored by Auto-reclose CB Supervision logic
(it’s separate function to CB Supervision in GLOBAL SETTINGS/CIRCUIT
BREAKER column). If, on completion of the tCB FLT ext time (GLOBAL
SETTINGS/CIRCUIT BREAKER submenu), the CB FLT ext (Alarm) indicates a
failed state of the CB, a lockout occurs and the CB remains open.
Two independent and programmable inputs (AUX1 and AUX2) can be used to
initiate the auto-reclose function from an external device (such as an existing
overcurrent relay). These logic inputs may be used both independently and in
parallel with the overcurrent elements.
Note:
3.The tAUXx Close Shot cell must be set for every cycle (Close shot).
The external block is executed by the Block. [79] input, Blocking via RS485, [79]
default cell in CTRL line, or temporary blocked after a close command made by an
operator until Time Inhibit tI on Close set in GLOBAL SETTINGS/ [79]
ADVANCED SETTINGS column.
The internal block can be executed by a final trip, a number of valid A/R rolling
demands or an A/R conflict.
Auto-reclose in Progress
Final Trip
The Final trip signal indicates that a complete auto-reclose cycle has been
performed and that the fault has not been cleared.
The Final trip signal can be reset after a manual closing of the CB after the settable
Inhibit Time tI on Close (GLOBAL SETTINGS/ [79] ADVANCED SETTING)
time-delay or reset via a Reset Command (assigned Binary Input, RS485 Reset
Latched Signaling command, C clear key).
Freely settable the inhibit of the trip after closing command issued via the [79], set
separately for each protection element:
- application where for example the setting for the I> stage covers more than
the protected zone, so that the [79] can clear faults downstream too, but the
final trip will be executed by the downstream relay or a fuse, therefore in the
upstream relay, tI> should be inhibited – waiting for tI>> trip of the
downstream relay).
Note: for this case Fast Trip O/C function can be used too (see below).
It is recommended to set another protection stage with setting for Alarm only, to
inform that this fault was not cleared by autorecloser so it’s still present (tripping
from this protection element is inhibited). For above case when the auto-reclose is
successful, the reset of inhibition is applied after reset of protection stage (current
below the stage value). For another case when during inhibition of protection
element, another protection element (set to run [79]) makes a trip after going to the
next cycle (the next [79] close command is executed) the inhibition is reset and the
further action depends on the configuration:
if in the next cycle this protection element is still set with inhibition, the protection
element is still inhibited
if in the next cycle this protection element is not set with inhibition, but the fault is still
not cleared, this protection element will trip CB (If another protection element moves
auto-reclose to the next cycle, the inhibition is removed automatically and [79] logic
checks configuration for the next [79] shot).
configuration the setting for chosen trip shot is ‘ 0 ‘, the trip is executed after the
time-delay of the protection element. If it is set to ‘ 1 ‘, the time-delay set in the Fast
O/C Trip Delay menu cell is applied. In some regions the typical setting of the fast
trip for a 2-shot AR is set:
- Fast O/C Trip (trip shots): 00011 (The first and second trips with Fast O/C
Trip Delay to reduce to minimum the resulting power arc; The third – final
– trip after the time-delay of the protection element to help to ensure the
grading in the power system – trip selectivity)
- Fast E/GND Trip (trip shots): 00000 (all trips re executed after the time-
delays of the protection elements).
Fast O/C Trip – refers to all O/C stages in the PHASE O/C menu column: I>, I>>,
I>>>.
Fast E/GND Trip – refers to all E/GND stages in the PHASE E/GND menu column:
IN_1, IN_2, IN_3.
Fast O/C (E/GND) Trip Delay is associated with a DMT characteristic even if the
protection element is set to an IDMT characteristic. For the fast trip the reset time-
delay of the protection element is not applied.
Recloser Lockout
If a protection element operates during the reclaim time, following the final reclose
attempt, the relay will lockout and the auto-reclose function will be disabled until the
lockout condition is reset.
The lockout condition is reset by a manual closing after the Inhibit Time tI on Close
timer elapses.
Additionally, the lockout condition is reset by a reset signaling command (via Inputs,
HMI key, Remote Reset command),
The auto-recloser can also be locked out using a CB FLT Ext.Sign. input. This
information can be issued from the “not charged” or “Low gas pressure” indications
of CB springs.
In the lockout condition the ALARM with the cause: ALARM [79] Lockout is
displayed up to reset of the lockout condition.
During the auto-reclose cycle, if the relay receives a command to switch setting
groups, it is executed after the end of auto-reclose action (if auto-reclose is not in
progress).
Rolling Demand
The rolling demand is used when a defined number of successful recloses are
performed over a defined time. If it is happened auto-reclose function is Lockout and
he ALARM with the cause: ALARM [79] Roll.Demand is displayed up to reset the
lockout condition.
If after Alarm [79] Rolling Demand signaling, the lockout condition reset is applied,
the recorded number of rolling demand shots are cleared.
This function signals the final trip only and clears signaling if the CB remains closed
(Auto-reclose is successful). This function is recommended if the P1F is integrated
into a SCADA system or if the substation is rarely supervised by maintenance
personnel. In this case it is not necessary to clear signaling if the fault has
disappeared and the line is healthy.
Note: Reset of signaling and of latched outputs can be done using the General
resetting function.
This configuration can be set in the GLOBAL SETTINGS/LOC submenu:
- LEDs Reset:
- 0: Manual only (via Inputs, HMI key, Remote Reset command)
The Start protect option allows signaling of the latest trip only.
Additional Functions
Settings
Auto-reclose settings, common for Group 1 and Group 2, are available in column:
GLOBAL SETTINGS/[79] Advanced Settings.
L N B A E E+
Description
Any unbalanced fault condition will produce negative sequence current. Thus,
a negative phase sequence overcurrent element can detect both phase-to-phase
and phase-to-earth faults.
The negative phase sequence overcurrent element included in the PowerLogic P1F
relays provides one stage non-directional overcurrent protection with independent
time-delay characteristics, which are selectable between inverse definite minimum
time (IDMT) and definite time (DMT). The inverse time-delayed characteristics
support both IEC and IEEE curves. Please refer to Overcurrent Protection Tripping
Curves in this chapter for the detailed description.
This section describes how negative phase sequence overcurrent protection may be
applied in conjunction with standard overcurrent and earth fault protection in order to
solve some application problems.
● Negative phase sequence overcurrent protection is more sensitive to resistive
phase-to-phase faults than phase overcurrent elements, which may not operate.
● In some applications, an earth fault relay may not be able to detect a residual
current because of the configuration of the network. For example, an earth fault
relay connected on the delta side of a delta-star transformer is unable to detect
earth faults on the star side. However, negative sequence current will be present
on both sides of the transformer in any fault condition, independently of the
transformer configuration. Therefore, negative phase sequence overcurrent
element may be used to provide time-delayed back-up protection for any
uncleared asymmetrical faults.
● Where fuses are used to protect motors on rotating machines, a blown fuse
produces a large amount of negative sequence current. This is a dangerous
condition for the machine because negative phase sequence current generates
overheating. Then, a negative phase sequence overcurrent element may be
used to back-up motor protection relays.
● It may also be required to trigger an alarm to announce the presence of negative
phase sequence currents in the system. Operators are then prompted to
investigate the cause of the unbalance.
The negative phase sequence overcurrent elements have a current pick up setting,
I2>, and can be time-delayed using configurable timer tI2>.
The current pick-up stage I2> must be set to a value that is higher than the normal
negative phase sequence current because of the normal unbalance conditions on
the network. This can be done practically during the commissioning, using the
MEASUREMENTS menu of the relay to display the negative phase sequence
current value. Then, this value has to be increased by 20%.
It is essential to set correctly the time-delay associated with this function. It should
also be noted that this element is used primarily as a back-up protection to other
protective devices or to provide an alarm. Therefore, this function is usually set with
a long time-delay.
NOTE: care must be made to help to ensure that the time-delay is set above the
operating time of any other protection device (at minimum fault level) present on the
system and that may react to unbalanced faults, such as:
• Phase overcurrent elements.
• Earth fault elements.
• Broken conductor elements.
• Negative phase sequence influenced thermal protection elements.
The tI2> time-delay associated with the I2> stage can be set under the menu
SETTING GROUP x/PROTECTION Gx/[46] NEGATIVE SEQ. O/C.
Block Diagram
Figure 27. Operating principle diagram for negative sequence overcurrent
Operation
If the I2> protection element is set to Alarm, it means that that element is linked to
the Alarm function (see Setting a LED indicators and Setting a Relay Output
sections in chapter Use).
Additional Functions
Settings
L N B A E E+
Description
Most of the faults that affect a power system occur between one phase and the
earth or between two phases and the earth. These faults are shunt faults and are
caused by lightning discharges and other overvoltages generating flashovers. They
may also arise from birds on overhead lines or mechanical damage on underground
cables, etc.
Such faults lead the current to increase appreciably and therefore they can easily be
detected in most applications. Open circuit faults are a different type of faults that
can happen in electrical networks. These faults can be caused by broken
conductors, blown fuses or maloperation of a pole of a circuit-breaker.
Series faults will not lead to an increase in phase current and therefore they cannot
easily be detected by common overcurrent relays. However, this type of fault
produces an unbalance that creates negative phase sequence current, which can be
detected. The use of negative phase sequence overcurrent is then recommended to
detect such faulty conditions. However, on lightly loaded lines, the value of the
negative sequence current caused by a faulty condition may be very close to, or
even inferior, to the full load steady state unbalance generated by CT errors, load
unbalances, etc. As a consequence, a negative sequence protection element would
not work for low level of loads.
As a solution, the PowerLogic P1F have a protection element that measures the
ratio between the negative and the positive phase sequence current (I2/I1). By using
this ratio rather than only the measured I2, the relay will be able to detect a fault
condition independently of the load level on the power system, since the ratio
remains approximately constant whatever the variations in load current. It is then
possible to have a more sensitive setting.
Block Diagram
Figure 28. Operating principle diagram for broken conductor protection
Operation
The relay incorporates an element that measures the ratio of negative to positive
phase sequence of current (I2/I1). This will be affected to a lesser extent than the
measurement of negative sequence current alone, since the ratio is approximately
constant with variations in load current. Hence, a more sensitive setting may be
achieved. The logic diagram is as shown below. The ratio of I2/I1 is calculated and
compared with the Ratio I2/I1 threshold. If it exceeds the threshold then the time-
delay tBCond is initiated. The Brkn Cond I< block signal is used to disable Broken
Conductor function if the max current value from three phases is too low. The Brkn
Cond I< block undercurrent threshold is settable (GLOBAL SETTINGS/O/C
ADVANCED/[46BC]Brkn.Cond. I< Block.). Factory setting value is 0.1 In.
Additional Functions
Settings
O/C ADVANCED
Menu Text Authorized Values Default Setting
[46BC]Brkn.Cond. I< Block. . … . In (step . In) 0.10 In
Additional Info
The Broken Conductor function can be set to: Trip, Trip-Inrush Bl, Trip-Latch or
Alarm.
If the Broken Conductor element is set to Trip, Trip-Inrush Bl or Trip-Latch, it
means that it is linked to the Protect.Trip and Prot.Trip pulse functions (see LED
configuration, page 308).
If the Broken Conductor element is set to Alarm, it means that it is linked to the
Alarm function (see LED configuration, page 308).
If Trip-Inrush Bl is selected, the I2/I1 threshold is blocked via the Inrush Blocking
function (refer to Inrush Blocking, page 141).
If Trip-Latch is selected, the Broken Conductor element will remain high after a trip,
until it is reset via a binary input, the HMI or a remote RESET command.
NOTE: The Broken Conductor function is inhibited if the value of the current flowing
in each of the three phases is below [46BC]Brkn.Cond I< Block. Undercurrent
threshold (factory setting: 10% of the nominal current).
Switch-On-To-Fault
Applicable to PowerLogic P1F Series
L N B A E E+
Description
In some feeder applications, fast tripping may be required if a fault is still present on
the feeder after the reclosure of the circuit breaker (Close on to fault).
Some faults may not be cleared after a reclose due to the fact that the conditions
that led to the fault have not been removed from the feeder after a reclosing cycle or
a manual trip, or due to earthing clamps left on after a maintenance visit. In these
cases, it may be desirable to clear the fault more quickly, rather than wait for the
DMT or IDMT trip time-delay associated with the involved protection to elapse.
Enabling and setting the SOTF (Switch-On-To-Fault) function can be done under the
SETTING GROUP x/PROTECTION Gx/SOTF Gx submenu.
Crossing of SOTF threshold will initiate the SOTF function which can be activated
with the following functions:
● closing by Input (Manual Close binary input order),
● manual closing controlled by the HMI, (close key order),
● front panel communication control (HMI order),
● rear communication control (rear RS485 communication port order),
Block Diagram
Figure 29. Operating principle diagram for switch on to fault
Inrush detection (I2h/I1h)
&
SOTF? 2: Alarm
SOTF? 3: Trip-Inrush Bl Alarm
P0921ENb
Operation
When at least one of the selected signals has been detected, a 52 Ublock.SOTF
Time (GLOBAL SETTINGS/CIRCUIT BREAKER/52 Unblock.SOTF Time
submenu) timer starts to activates SOTF protection element
Once this timer (52 Ublock.SOTF Time) is active and SOTF thresholds have been
crossed, the tSOTF settable time-delay starts. This settable time-delay is particularly
useful in applications where fault selectivity in stages two or three is required.
This time-delay (tSOTF) is also useful in cases where serious transients may be
present, where the three poles of the CB do not all close at the same time and in
cases where the CB may not close instantaneously.
tSOTF can also be considered as a trip time-delay that substitutes itself to the trip
time-delay associated with the crossed threshold so that the tripping time is
accelerated.
If a trip due to switch on to fault occurs during the reclaim time of the ARC, the trip
will be final and the ARC will be locked.
If the SOTF stage is reset before the settable time-delay tSOTF elapses, the SOTF
function is reset.
Additional Functions
Settings
The SOTF overcurrent element is activated after the CB’s state changes from open
to closed. SOTF is blocked when the auto-recloser is running (E, E+).
L N B A E E+
Description
When a fault is detected, one or more main protection elements will issue a trip
command to the associated circuit breaker(s). To isolate the fault, and prevent
(further) damage to the power system it is essential that the circuit breaker operates
correctly.
A fault that is not cleared quickly enough threatens the stability of the system. It is
therefore common practice to install circuit breaker failure protection
devices/elements that check that the circuit breaker has opened within a reasonable
period of time. If the fault current has not been eliminated after the set time-delay,
breaker failure protection (CB Fail) will send a signal.
The CB Fail protection element can be used to back-trip upstream circuit breakers to
ensure that the fault is correctly isolated. The CB Fail protection element can also
clear all blocking commands associated with logic selectivity.
Block Diagram
Figure 30. Operation principle diagram for circuit breaker failure
CBF? 0: Disabled
&
AUX n Trip
P0927ENb
Operation
The circuit breaker failure protection function incorporates one timer allowing
configuration for the following scenario: upon any protection trip, CB Fail Timer tBF
is started, and normally reset when the circuit breaker opens to isolate the fault. If
breaker opening is not detected, CB Fail Timer tBF times out and closes an output
contact assigned to CB Fail. This contact is used to backtrip upstream switchgear,
generally tripping all infeeds connected to the same busbar section.
The CBF element CB Fail Timer tBF operates for trips triggered by protection
elements within the relay or via an external protection device (binary input). The
latter is achieved by assigning one of the relay opto-isolated inputs to AUX n (B, A,
E, E+) set for tripping or Strt tBF (B, A, E, E+) (depends on the application).
When it is triggered via the AUX n (B, A, E, E+) input, CBF is reset by an
undercurrent element.
When it is triggered via the Strt tBF input (B, A, E, E+), CBF is reset by the low
state of this input only.
The Block I>? (E, E+) and Block IN>? (E, E+) settings are used to cancel starts
issued by the overcurrent and earth fault elements, respectively, following a breaker
fail time out. The start is cancelled when the cell is set to Yes.
If the Retrip option is selected for the CB Fail function, it means that it is linked to
the Protect.Trip and Prot.Trip pulse functions (see LED and Output
configuration).
If CB Fail is set to Alarm, any outputs and LEDs assigned to the Alarm or tCBF
function are energized.
If CB Fail is not set to Disabled, any outputs and LEDs assigned to the tCBF
function are energized.
Additional Functions
Settings
NOTE: One of the following options must be set in order to enable CB Fail
protection:
● Retrip: a retrip signal is issued concurrently with the CB Fail output
(Protect.Trip and Prot.Trip pulse output). The TRIP LED is activated,
● Alarm: typical setting. In case of CB Failure, an alarm is issued concurrently with
the CB Fail output. The Alarm LED is lit.
Additional Info
The CB Fail Timer tBF timer is initiated when a trip command is issued by a
protection element. Note that the trip command can be issued either by a protection
element, or by a logic input (B, A, E, E+) assigned to an AUX counter. Then the
relay monitors the current signal of each phase and compares each phase current
signal with the band zone made by the undercurrent I< threshold. This value can be
set under the SETTING GROUP x/PROTECTION Gx/[50BF] CB FAIL Gx menu.
Communication Orders
Applicable to PowerLogic P1F Series
L N B A E E+
Description
• Comm.Order 1 is used for control of outputs via an RS485 command. The pulse
duration is set at GLOBAL SETTING/COMMUNICATION ORDER/Pulse Time
tCOM1
Settings
L N B A E E+
Description
Periodic maintenance of circuit breakers is necessary to help to ensure that the trip
circuit and mechanism operate correctly and that the interrupting capability has not
been compromised due to previous fault interruptions. The PowerLogic P1
protection relay records various statistics related to each circuit breaker operation,
allowing an accurate assessment of the circuit breaker condition. Statistics are
recorded to allow evaluation of both the electrical wear of the breaker contacts and
the mechanical wear of the breaker mechanism.
4 100 1
5 100 1
6 100 1
7 100 1
8 100 1
• urrent
This parameter can be set to the CB’s nominal current or any typical application
current for the first alarm, and to a typical fault current for the second alarm.
• perations left
his parameter determines when an alarm is activated. hen the “operations left” at
the given current level drops below this limit, the alarm is started.
The permitted operations at these two alarm levels can be calculated automatically
according to the breaker curve and logarithmic interpolation (see next section). Any
actual interrupted current is logarithmically weighted for the two given alarm current
levels and the number of operations left at the alarm points is decreased
accordingly. As shown in the figure below, the PowerLogic P1 protection relay
shows the allowed “operations left” based on the brea er curve, logarithmic
interpolation and actual interrupted current.
Figure 42. Permitted “Operations left” settings for the alarms
Logarithmic interpolation
The permitted number of operations for the currents between the defined points is
logarithmically interpolated using this equation:
a
C=
In
where:
C = permitted operations
I = broken current
CurveN, Curve(N+1) in the breaker curve table, and Ik/Ik+1 is the corresponding
broken current defined by CurveIk, CurveI(k+1) in the breaker curve table.
a = C k I kn
C
ln k
n = k +1
C
I
ln k +1
Ik
Each time a trip signal is detected, the corresponding permitted operations should
be calculated based on the broken current Ibrk:
a
Cbrk = n
I brk
According to the equations above and the breaker operation curve points definition
taken from Values of the above circuit breaker wear characteristic graph,
• 80 operations at 31 kA
if the alarm 2 current setting is 6 kA, then the permitted number of operations can be
calculated as follows:
10000
ln
n=
80
= 1.5038
31000
ln
1250
a 454 10 6
Cbrk = n
= = 945
I brk 60001.5038
If the interrupted three phase currents are L1 = 12.5 kA, L2 = 12.5 kA and L3 = 1.5
kA, the corresponding decreased number of operations of phase L1, L2 for alarm 2
are calculated as:
a 454 10 6
Cbrk 1,2 = n
= = 313
I brk 12500 1.5038
945
Δ= =3
313
In phase L3, the current is less than the alarm limit current 6 kA. For such currents,
the decrement is one.
In addition to the total cumulative broken current, there are five cumulative broken
current ranges to assess the breaking device pole condition. Each range’s high limit
value is configurable and the low limit value equals to the high limit of its previous
range. Each range has three different counters, one for each phase, to record how
many times the broken current falls into the range. See figure below.
Figure 43. Cumulative broken current record
The cumulative broken current is also computed by phase. When the PowerLogic
P1 protection relay is in test mode, the cumulative broken current and counters are
not updated.
An alarm signal will be generated when the cumulative broken current of any phase
exceeds the broken current alarm setting.
Mechanical wear
CB Open counter, Protection Trip counter and Rack out counter
he “ rotection rip” counter is to record B open times issued from trip (global
trip). This counter can also be set to a custom value but it does not increment during
test mode.
If, for whatever reason the circuit breaker does not open successfully after the pulse
setting time out (500ms), the trip counters are not incremented.
he “ ac out” counter is to record the number of rac ing in out operations of the
CB truck. It is incremented in test mode.
If two different digital signals are used to indicate the 52a and 52b status of the CB
position, the open time is measured from the moment when the “ b” status
becomes false to the moment when the “ a” status becomes true; the close time is
measured from the moment when the “ a” status becomes false to the moment
when the “ b” status becomes true.
However, if the CB position is only configured as 52a or 52b, the open time and
close time will not be recorded.
The charging time is computed from the moment when the CB position changes to
the moment when the spring status changes to ready. The spring status is
configured through CB FLT Ext.Sign_G1 for Setting group 1 and CB FLT
Ext.Sign_G2 for Setting group 2 setting in MATRIX/Inputs configuration.
Totally 8 the last CB open/close times and charging times are recorded in the
PowerLogic P1, each with a timestamp. If the time recorded exceeds the range, the
time will be tagged as an “out of range“, which allows the customer to easily detect
something is wrong with the CB.
These CB open times, close times and charging times are also recorded when the
PowerLogic P1 is in test mode.
Figure 44. Open and close time calculation
Standard Operation
The relays record the following controls and statistics related to each circuit breaker
trip operation:
● time-delay setting
● monitoring time for CB open and close operations
● CB open count
● summation of the current interrupted by the CB
● exponent for the summation
● tripping and closing pulse time
For each circuit breaker trip operation, the relay records statistics. The RECORDS/
COUNTERS/CB Monitoring menu cells shown are counter values only:
● No.CB Close Mon. – number of closing circuit breaker
● No.CB Open Mon. – number of opening circuit breaker
● CB AMPS Value. – sum of the current (in Amps or square Amps) interrupted by
the circuit breaker
Additional Functions
By default, this function is off. Its mean that all counters are incremented, but not
generate alarms. When the functions is enabled all counters are incremented and
generate alarms signals.
Settings
CB monitoring status
Alarm 1
Current 0.00 – 100.00 kA Alarm1 current level Editable
Cycles 100,000 – 1 Alarm1 limit for operations Editable
left
Alarm 2
Current 0.00 – 100.00 kA Alarm2 current level Editable
Cycles 100,000 – 1 Alarm2 limit for operations Editable
left
Cumulative broken
current setting
High limit / Iprim 0.0 – 100.0 kA High limit setting for each Editable
bin
Broken current alarm 0 – 65,535 Cumulative broken current Editable
setting alarm threshold
L N B A E E+
Description
If two inputs are assigned to both the above inputs, CB status is based on both
indications.
If only one function is used, CB status is based on a single-bit information only (the
second is derived from the first one).
The CB status is indicated on the LCD display in control menu cell as follows:
CB status: Opened
CTRL: No operat.
CB status is used by various protection and monitoring functions (e.g. auto-reclose,
open time etc.) for proper operation.
Example
In the above configuration LED7 indicates the CB closed position and LED8
indicates the CB open position.
L N B A E E+
Description
Standard Operation
The relays record the following controls and statistics related to each circuit breaker
trip or close operation:
If CB closing time is longer than Max CB Close Time the Alarm is issued
(Alarm CB Time Monit.). This function can be activated in the menu: GLOBAL
SETTINGS/CIRCUIT BREAKER/ CB Supervision: 1: Yes,
Settings
L N B A E E+
Description
The Local / Remote Mode function is to make possible blocking commands sent
remotely through communication networks (such as setting parameters, control
commands, etc.), to help to prevent any accidents or maloperation during
maintenance work performed on site.
Standard Operation
PowerLogic P1 can be operated in three modes “Remote”, “Local” and “L+R” (local
and remote) depending on the user selected settings. Main setting is available at
GLOBAL SETTINGS/CIRCUIT BREAKER/Remote CTRL Mode:
0: Remote only – remote control is permitted only. All manual controls (HMI,
Close/Trip function keys, Binary Inputs assigned to Manual Close or Trip) are
blocked.
In Remote only mode the menu default control mode cell looks as follow:
LR Stat.: Remote
CTRL: Remote
Remote only status means that remote control via RS485/USB is possible only
(local control is rejected by PowerLogic P1F).
This control mode can be changed (the second line (CTRL) of menu cell) from
Remote to Local and inversely.
LR Stat.: Local
CTRL: Local
Local status means that local control is possible only. Remote commands via
RS485/USB are rejected by PowerLogic P1F (except the synchronizing time signal,
CTRL: Remote or CTRL: Local, Comms. Order commands).
With Local/Remote control mode functionality the digital input label “Local CTRL
mode“ can be associated. hen this signal is assigned to any digital input then
Local/remote control mode gets following functionality:
● With Local CTRL Mode binary input energized the menu cell looks as follow:
LR Stat.: Local
LR Stat.: Local status means that only local control is possible. It is not possible to
change the control mode from the HMI.
● With Local CTRL Mode binary input deenergized the menu cell looks as follow:
LR Stat.: Remote
LR Stat.: Remote status means that remote control commands can be issued. It is
not possible to change the control mode from the HMI.
In Remote + Local mode the menu default control mode cell looks as follow:
LR Stat.: L+R
CTRL: Remote
Remote only status means that both the local (HMI, control buttons on the front
panel, binary inputs) and remote control (RS485/USB) is possible.
This control mode can be changed (the second line (CTRL) of menu cell) from L+R
to Local and inversely.
LR Stat.: Local
CTRL: Local
ith ocal emote control mode functionality the digital input label “Local CTRL
mode“ can be associated. When this signal is assigned to any digital input then
Local/remote control mode gets following functionality:
● With Local CTRL Mode binary input energized the menu cell looks as follow:
LR Stat.: Local
LR Stat.: Local status means that only local control is possible. It is not possible to
change the control mode from the HMI.
● With Local CTRL Mode binary input deenergized the menu cell looks as follow:
LR Stat.: Remote
LR Stat.: Remote status means that remote control commands can be issued. It is
not possible to change the control mode from the HMI.
Settings
L N B A E E+
Description
Standard Operation
If a group is used in an application it is not possible to remove the other group from
the menu. If one group only is chosen the relay uses Group 1 even if the other
parameters are set to Group 2 (Inputs(B, A, E, E+), Menu, Remote Group Setting).
Switching between groups can be done via:
● the selected binary input (B, A, E, E+) assigned to the Setting Group 2 logic
input (SETTING GROUP x/INPUTS CONFIGURATION Gx submenu)
● the relay front panel interface (GLOBAL SETTINGS/SETTING GROUP
SELECT/ Setting Group: 1: Group1 or 2: Group2),
● through the communications port (refer to the Mapping Database for detailed
information).
Switching between setting groups can be done even while a protection function is
active, but it resets all timers, LEDs on P1F front panel).
The user can check which one of the setting groups is active in the menu OP
PARAMETERS/Active Set Group cell.
The user can also assign the active group (Setting Group x function) to an output
relay (SETTING GROUP x/OUTPUT RELAYS CONFIGURATION Gx) or to an LED
(SETTING GROUP x/LEDs CONFIGURATION G1).
It is possible to change the setting group by energizing a digital input (B, A, E, E+)
(operates on level: logic input is low – setting group 1, logic input is high – setting
group 2).
If the setting group switchover is done via a binary input (B, A, E, E+), the change
from Group 1 to Group 2 is executed after the set time-delay: t Change Setting G1
->G2 (GLOBAL SETTINGS/SETTING GROUP SELECT) (B, A, E, E+). The
switching from Group 2 back to Group 1 is instantaneous.
NOTE: If the digital input that has been assigned to the setting group change
operates on level (low or high), it is not possible to change the setting group via
remote communications.
If the programmed logic input starts being supplied with +V, then after the t Change
Setting G1->G2 time-delay the active group will be G2. If the programmed logic
input is not supplied with +V, the active group will be G1.
If the programmed logic input is supplied with +V, then the active group will be G1.
If the programmed logic input stops being supplied with +V , then after the t Change
Setting G1->G2 time-delay the active group will be G2.
Switch between Active Groups via the Menu or a Remote Command (RS485,
USB)
By using the relay front panel interface it is possible to change the active setting
group:
This menu cell is commonly used for switching groups from the front panel interface
and via a remote command (RS485 or USB).
NOTE: If the digital input that has been assigned to the setting group change
operates on level (low or high), it is not possible to change the setting group via
neither remote communications nor the front panel.
The detailed logic table for setting group selection is shown below:
NOTE: If a setting group change initiated by a remote command has not been
effected due of priority settings, that command is ignored (not recorded in the P1F’s
logic for the future, when priority settings allow changing).
If Active Group signaling is required, some LEDs should be assigned to the Setting
Group x function (SETTING GROUP x/LEDs CONFIGURATION Gx).
Settings
Commissioning Mode
Applicable to PowerLogic P1F relays
L N B A E E+
Description
Commissioning Mode in PowerLogic P1F relays (A, E, E+) has three modes:
Maintenance mode, Output tests and Functional test, amongst which the last two
are available only if Maintenance mode is active.
Maintenance Mode
Maintenance mode menu allows the user to check the operation of the protection
functions.
This option allows the user to check the operation of the protection functions without
actually sending any external command (Tripping or signaling).
Independently on the rear protocol selected in menu (Modbus RTU or IEC 60870-5
-103), transmission of information to SCADA is active with additional information to
know that PowerLogic P1F is in Maintenance mode (refer to Communication chapter
and IEC 60870-5-103 standard).
Changing of setting from No to Yes or Yes – Bl.Out. from the front panel activate
this mode for 10 minutes only. After this time setting is automatically switched to No.
The selection of the maintenance mode is possible by logic input (the level), control
command (rear or front port), or by front panel HMI. The maintenance mode is
terminated by:
● Low state of logic input assigned to Maintenance mode function.
● Control command which activate this mode (rear command or setting: Yes,
Yes – Bl.Out. ) and by turning off the power supply.
In Yes – Bl.Out. case, all the output contacts are blocked, and no command can be
issued to these contacts, even if a protection threshold associated with one of these
output contacts has been crossed. (If a protection threshold is crossed, all
associated LEDs will be ON, even the TRIP LED, if protection element is set to
Trip).
If the input assigned to Maintenance mode is logical high the Maintenance Mode is
active (without any time limitation) up to low state of the logical input.
Outputs Test
The commissioning cells allow the user to check the external wiring to the relay’s
output contacts. To do this, the user has only to set to 1 the desired output contact’s
corresponding bit, and this will close the contact and allow the continuity of the
wiring to be checked.
Test 7654321
Pattern 0000000
If the outputs for test are selected and Time for output closing is set, the closing
command can be executed in this cell:
Test output
0: no operation
To execute the test, press OK key, select 1: Apply test and confirm action by OK.
The contact will be closed for the duration of the Contact Test Time pulse.
Functional Test
This functionality is used to check the functional outputs of the PowerLogic P1F. To
do this, the user has only to select which protection element will be triggered, and
this will close the contact assigned to this protection element and allow the continuity
of the wiring to be checked. If the protection element is disabled there will be no
action.
Functional Test
0: I>
In the cell below the end of the functional test can be configured:
Functional Test
End 0: CB trip
To execute this test, press the OK key, select 1: Operate and confirm action by
pressing OK. The contact will be closed for the duration of the Functional Test
Time pulse.
NOTE: In Maintenance mode PowerLogic P1F works with full functionality (ready to
trip in a fault condition, even during functional test). During functional test of selected
stage (for example tI>), P1F measures currents so the rest active stages (for
example tI>>, tIN>, etc) work on the measured current from the field. Only the tested
stage (for example tI>) sees test current: two times greater than tI> current setting
value in all phases. After functional test of Thermal replica, the thermal value is set
to 0%. After test, in the fault record all recorded current values are based on the
currents measured in the field.
If Functional Test will be applied for protection element which is disabled there will
be no any action done.
L N B A E E+
Description
Any of the available binary inputs on the PowerLogic P1F relay can be selected for
synchronization. Pulsing this input will result in the real time clock snapping to the
nearest minute.
Recommended pulse duration is 20 ms, repeated no more than once per minute.
Standard Operation
L N B A E E+
Description
The way or resetting the latched LEDs and outputs is determined by the inputs
assigned to the resetting of latched LED. Outputs can be reset via external inputs,
by pressing the R key on the PowerLogic P1F’s front panel if the LCD shows the
default display or via the communication port.
NOTICE
Resetting of LEDs and relay outputs is impossible if reason of the triggering
and/or tripping any protections or functions still exist (e.g. trip signal occurred, but
CB is closed and fault current flowing thru analog inputs of the relay).
In this case if R button was pushed on the relay LCD is displayed following
window:
It is mean that reset of the LEDs and outputs in this moment is impossible.
Standard Operation
● Ltchd Outp.Reset:
● Alarms Info.:
● 0: Self Reset – This option means that if an alarm signal has disappeared
no information is available in the ALARM STATUS column
The Manual only option helps to prevent a close command from being issued
without readout of the cause of trip by maintenance personnel. It reduces the risk to
switch on to fault.
The Start protect and Protect.Start options allows to signal the latest trip only:
Start of any protection element set to trip the CB, reset all latched LEDs and show
the default display.
Settings
L N B A E E+
Description
The specified, for each type of PowerLogic P1F series, data is recorded for any
relevant elements that operated during a fault or an alarm. The recorded data can
be viewed in each of the last 20 fault records for fault elements and 5 records for
alarm elements.
Standard Operation
● Fault records
The following data is recorded for any relevant elements that operated during
a fault, and can be viewed in each of the last 20 fault records:
2> trip
I>> trip
I>>> trip
SOTF trip (A, B, E, E+)
IN_1 trip
IN_2 trip
IN_3 trip (E, E+)
I2> trip (E, E+)
Brkn Cond (E, E+) trip
CB Fail trip
AUX1 trip (B, A, E, E+)
AUX2 trip (B, A, E, E+)
AUX3 trip (B, A, E, E+)
AUX4 trip (B, A, E, E+)
Therm OL (N, A, B, E, E+)
● Fault Origin: type of fault (for example: phase A-B, A-B-C, etc.)
● Event Value:
Per phase record of the current value during the fault:
I , and ( o) φ
● Alarm records
The following data is recorded for any relevant elements that operated during an
alarm, and can be viewed in each of the last 5 alarm records:
tI> Alarm
tI>> Alarm
tI>>> Alarm
tSOTF Alarm (B, A, E, E+)
tIN_1 Alarm
tIN_2 Alarm
tIN_3 Alarm (E, E+)
tI2> Alarm (E, E+)
tBrkn Cond Alarm (E, E+)
tCB Fail Alarm
tAUX1 Alarm (B, A, E, E+)
tAUX2 Alarm (B, A, E, E+)
tAUX3 Alarm (B, A, E, E+)
tAUX4 Alarm (B, A, E, E+)
tTherm OL Alarm (N, A, B, E, E+)
● Alarm Origin: type of alarm (for example: phase A-B, A-B-C, etc.)
● Event Value:
Per phase record of the current value during the fault:
I , and ( o) φ
Instantaneous Records
Applicable to PowerLogic P1F relays
L N B A E E+
Description
Each time any of set thresholds are crossed, an instantaneous record is created and
displayed in the RECORDS/INSTANTANEOUS RECORD menu. The last five
starting records are available, with the duration of the signal.
Standard Operation
Instantaneous record are stored in non-volatile memory (FRAM memory). This type
of memory does not require any maintenance (no battery inside the PowerLogic P1F
is required). Instantaneous record is stored without any time limitation even if the
PowerLogic P1F is not supplied from any power source.
Alarm Status
Applicable to PowerLogic P1 Series
L N B A E E+
Description
Standard Operation
The Alarm signals information can be realized with latching or without latching,
depending on the GLOBAL SETTINGS/LOC/Alarms Info value:
Event Records
Applicable to PowerLogic P1F relays
L* N B A E E+
*event recorder is not available if model L is not equipped with RS485
communication port (hardware option).
Description
The PowerLogic P1F relay records and time tags up to 200 events and stores them
in non-volatile FRAM memory. This enables the system operator to establish the
sequence of events that occurred within the relay following a particular power
system condition, switching sequence etc. When the available space is exhausted,
the oldest event is automatically overwritten by the most recent one.
The real time clock within the relay provides the time tag for each event, with a
resolution of 1 ms.
The event records are available for remote viewing, via the communications ports
RS485 or USB.
For extraction from a remote source via communications ports, refer to the SCADA
Communications section where the procedure is fully explained.
Standard Operation
Any event may be a change of state of a control input or output relay, a trip
condition, etc.
The following sections show the various items that constitute as an event:
If one or more of the binary inputs has changed state since the last time that the
protection algorithm ran, the new status is logged as an event. The information
is available if the event is extracted and viewed via a PC.
If one or more of the output relay contacts have changed state since the last
time that the protection algorithm ran, then the new status is logged as an event.
The information is available if the event is extracted and viewed via PC.
Any alarm conditions generated by the relays will also be logged as individual
events. The following table shows examples of some of the alarm conditions and
how they appear in the event list:
The above table shows the abbreviated description that is given to the various
alarm conditions and also a corresponding value between 0 and 31. This value
is appended to each alarm. It is used by the event extraction software, such as
eSetup , to identify the alarm. Either ON or OFF is shown after the description to
signify whether the particular condition is operational or has reset.
L N B A E E+
Description
Standard Operation
The directly measured power system quantities available in PowerLogic P1F relay
are listed below:
IA, IB, IC - R.M.S. values
I1 (E, E+) - calculated positive (I1)
I2 (E. E+) - calculated negative (I2)
I2/I1 (E, E+) - calculated negative to positive ratio
IN - measured fundamental harmonic only
(E/F analogue input)
Thermal (N, B, A, E, E+) - thermal state based on RMS value from
the max phase current
IA 2nd harmonic (A, E, E+) - second harmonic in phase A
IB 2nd harmonic (A, E, E+) - second harmonic in phase B
IC 2nd harmonic (A, E, E+) - second harmonic in phase C
NOTE: All the measured current values depends on the CT Ratio setting (GLOBAL
SETTINGS/CT RATIO). The typical deviations of measurements for phase and
earth currents is ±2% at In and ±2% at Ien.
Standard Operation
The following settings under the measurements heading can be used to configure
the relay measurement function:
● CT Ratio setting – responsible for phase and earth currents transformer input’s
primary and secondary current ratings, can be found in: GLOBAL
SETTINGS/CT RATIO menu.
Counters
Applicable to PowerLogic P1F Relays
L N B A E E+
Description
The PowerLogic P1F’s counters gather information on the vast number of various
events during relay operation, e.g.: manual trip commands, trip commands from
protection elements, hardware problems detected by the self-monitoring function,
auto-recloser starts, etc.
Standard Operation
● FAULT COUNTER:
● No. Fault Trips – number of trip commands from protection elements
(current based protection element trip, AUX trips and Auto-recloser trips).
● No. Fault Starts – Number of timer starts by protection elements set to trip
(current-based protection element and AUX).
● No. Alarms – number of Alarm signals from protection elements set to
Alarm or functions mapped to an Alarm signal.
● No. HW Warnings – Number of hardware problems detected by the self-
monitoring function.
Counters can be reset in the FAULT COUNTER column – Counter Reset cell.
NOTE: For a 4-shot auto-reclose sequence (TCTCTC, the next TCTC, the next
TCTCTCTCT and the next TCT (lockout)) the counters shows:
Disturbance Records
Applicable to PowerLogic P1F Relays
L N B A E E+
Description
Standard Operation
The total number of records available in PowerLogic P1F’s model E+ (with Vo)
disturbance recorder is:
● One – for set Max Record Time from in range: 2.51s – 3.00s
● Two – for set Max Record Time from in range: 1.67s – 2.50s
● Three – for set Max Record Time from in range: 1.26s – 1.66s
● Four – for set Max Record Time from in range: 1,01s – 1.25s
● Five – for set Max Record Time from in range: 0.10s – 1,00s
The recorder stores actual samples that are taken at a rate of 16 samples per cycle.
The recording is in COMTRADE format. Each disturbance record consists of eight
analog data channels and thirty-two digital data channels. The relevant CT ratio for
the analog channels are also extracted to enable scaling to primary quantities.
NOTE: If a CT ratio is set to less than a unit, the relay will choose a scaling factor of
zero for the appropriate channel.
Settings
It is not possible to display the disturbance records locally on the LCD; they must be
extracted using suitable software such as eSetup Easergy Pro.
Communication
Introduction
Applicable to PowerLogic P1F Series
L* N B A E E+
*hardware option
• MODBUS.
• IEC 60870-5-103.
NOTE:
This document shows all available functions in P1F. To see which function are
available in model refer to the rest chapters/sections of this manual.
Glossary
MODBUS PROTOCOL
PowerLogic P1F relay can communicate by a RS 485 link behind the unit following
the MODBUS MODICON RTU protocol.
In PowerLogic P1F the status of the rear communication port is signaled by flashing
rectangles in the top and bottom right corners of the display. Tx (Transmit) is
assigned to the top right corner, Rx (Receive) is assigned to the bottom right corner
of the display. Flashing of the rectangles indicate the operation of the
communication port only (not frames received and/or transmitted).
Baud rate
4800
9600
38400
57600
115200
Mode
1 start / 8 bits / 1 stop: total 10 bits
1 start / 8 bits / even parity / 1 stop: total 11 bits
1 start / 8 bits / odd parity / 1 stop: total 11 bits
1 start / 8 bits / 2 stops: total 11 bits
All character received after a silence on the line with more or equal to a transmission
time of 3 characters is considered as a firm start.
The frame validity is working with a cyclical redundancy code CRC with 16 bits. The
generator polynomial is:
The address of the PowerLogic P1F relay on a same MODBUS network is situated
between 1 and 247. The address 0 is reserved for the broadcast messages.
Master slave protocol, all exchange understands a master query and a slave
response
Slave number:
Function code:
CRC16:
Note: The PowerLogic P1F relay does not respond to globally broadcast frames
sent out by the master.
Slave number:
Function code:
Data:
CRC 16:
When PowerLogic P1F relay receive a master query, it validates the frame:
• If the CRC is false, the frame is invalid. PowerLogic P1F relay do not reply
to the query. The master must retransmit its query. Excepting a broadcast
message, this is the only case of non-reply by PowerLogic P1F relay to a
master query.
• If the CRC is good but the PowerLogic P1F relay cannot process the query,
it sends an exception response.
Slave number:
The slave number is situated between 1 and 247.
Function code:
The function code returned by the PowerLogic P1F relay in the warning frame is the
code in which the most significant bit (b7) is forced to 1.
Warning code:
On the 8 warning codes of the MODBUS protocol, the PowerLogic P1F relay
manages two of them:
CRC16:
Settings
Disturbance Records
Before uploading any disturbance record, a service request must be sent to select
the record number to be uploaded.
• Phase CT ratio
• Earth CT ratio
The mapping pages used for this service request are from 38h to 3Ch.
The disturbance data pages contain the sample of a single channel from a record.
Page 22h: contains the index of the disturbance
Page 3Dh: A dedicated request allows to know the number of disturbance records
stored in FRAM memory.
Event records
Page 35h: Request to upload an event record without acknowledge of this event.
Used addresses:
3500h: EVENT 1
.....
35C8h: EVENT 200
Page 36h: Request to upload the non-acknowledged oldest stored event record.
In automatic acknowledgement, the bit1 of the remote order frame (format F38B –
mapping address 0402h) should be set to 1. On event retrieval, this event record is
acknowledged.
In manual acknowledgement, the bit12 of the remote order frame (format F38 –
mapping address 0400h) should be set to 1. On event retrieval, this event record is
not acknowledged. To acknowledge this event, another remote order should be sent
to the relay. The bit 13 of this frame (format F38 – mapping address 0400h) should
be set to 1.
Fault records
Used addresses:
3700h: FAULT 1
3701h: FAULT 2
.....
3713h: FAULT 20
Page 3Eh: Request to upload the non-acknowledged oldest stored fault record.
Characteristics
Values Default
Address Group Description Step Unit Format
range Value
Product
Information
0000 Relay description 32-127 1 - F10 P1
characters 1 and 2
0001 Relay description 32-127 1 - F10 F1
characters 3 and 4
0002 Relay description 32-127 1 - F10
characters 5 and 6
0003 Unit reference characters 32-127 1 - F10 SE
1 and 2
0004 Unit reference characters 32-127 1 - F10
3 and 4
0005 Software Version 10 to 99 1 - F15
0006 Hardware Version 0 to 3 1 - F58
0007 Line CT Sec 9 1 - F23
0008 E/Gnd CT Sec 0, 3, 4 1 - F23A
0009 Active Set Group 0 to 1 1 - F32 0
000A Nominal frequency 0 to 1 1 - F57 0
000B Software Version Number 0 to 99 1 - F90
000C-000F Reserved -
Remote
signaling
0010 Logical inputs 0 to 255 1 bits F11
Values Default
Address Group Description Step Unit Format
range Value
001B CB status 0 to 4 1 - F30
001C [79] Status 0 to 32767 1 - F59
001D [79] Blocking Status 0 to 6 1 - F60
001E Local/Remote Mode Status 0 to 2 1 - F61
001F Maintenance Mode 0 to 2 1 - F62
0020 Hardware Warning 0 to 31 1 - F26
0021 Output information: I> 0 to 255 1 bits F37
0022 Output information: I>> 0 to 255 1 bits F37
0023 Output information: I>>> 0 to 255 1 bits F37
0024 Output information: IN_1 stage 0 to 255 1 bits F50
0025 Output information: IN_2 stage 0 to 255 1 bits F50
0026 Output information: IN_3 stage 0 to 255 1 bits F50
0027 Output information: AUX1 0 to 127 1 bits F51
0028 Output information: AUX2 0 to 127 1 bits F51
0029 Output information: CB Fail 0 to 127 1 bits F51
002A Output information: tCB ext. 0 to 127 1 bits F51
sign
002B Output information: SOTF 0 to 255 1 bits F37
002C Output information: I< 0 to 255 1 bits F50
002D Output information: I2> 0 to 255 1 bits F50
002E Output information: Brkn.Cond 0 to 255 1 bits F50
002F Output information: Thermal 0 to 255 1 bits F50
OL
0030 Output information: AUX3 0 to 127 1 bits F51
0031 Output information: AUX4 0 to 127 1 bits F51
0032 Output information: Input 0 to 4095 1 bits F101
Protection blocking 1
0033 Output information: Input 0 to 255 1 bits F102
Protection blocking 2
0034 Output information: Input 0 to 255 1 bits F103
Selective logic 1
0035 Output information: Trip latch 0 to 32767 1 bits F17
status 1
0036 Output information: Trip latch 0 to 2047 1 bits F17A
status 2
0037 Output information: Input logic 0 to 32767 1 bits F104
data
0038 – 0039 Reserved
003A CB Status 0 to 255 1 bits F14
003B LR Status 0 to 15 1 bits F13
003C Maintenance Mode Status 0 to 15 1 bits F13A
003D – Reserved
003F
Values Default
Address Group Description Step Unit Format
range Value
Remote
measurements
0040 Phase IA (L1) secondary 0 to 60 000 1 [A]/100 F1
current [A]
0041 Phase IB (L2) secondary 0 to 60 000 1 [A]/100 F1
current [A]
0042 Phase IC (L3) secondary 0 to 60 000 1 [A]/100 F1
current [A]
0043 E/GND IN (IE) secondary 0 to 60 000 1 [A]/1000 F1
current [A]
0044 I2 (negative sequence) 0 to 60 000 1 [A]/100 F1
secondary current [A]
0044 I1 (positive sequence) 0 to 60 000 1 [A]/100 F1
secondary current [A]
0045-004F Reserved
0050 Phase IA (L1) current [In] 0 to 60 000 [In]/100 F1
0051 Phase IB (L2) current [In] 0 to 60 000 1 [In]/100 F1
0052 Phase IC (L3) current [In] 0 to 60 000 1 [In]/100 F1
0053 E/F current [Ien] 0 to 60 000 1 [Ien]/100 F1
0054 I2 (negative sequence) current 0 to 60 000 1 [In]/100 F1
[In]
0055 I1 (positive sequence) current 0 to 60 000 1 [In]/100 F1
[In]
0056-005F Reserved
0060 I2/I1 current [%] 0 to 100 1 [%] F1
0061 Thermal Overload [%] 0 to 300 1 [%] F1
0062 2th harmonic [%] Phase A 0 to 100 1 [%] F1
0063 2th harmonic [%] Phase B 0 to 100 1 [%] F1
0064 2th harmonic [%] Phase C 0 to 100 1 [%] F1
0066-00FF Reserved
Line phase current value (primary value) = phase sampled value (e.g. address
0040h, 0041h or0042h) * {line primary CT ratio (address 0120h)/Line CT sec
(address 0121h)} A/100.
Line phase current value (primary value) = earth sampled value (e.g. address
0043h) * {line primary CT ratio (address 0122h)/Line CT sec (address 0123h)}
A/1000.
Values Default
Address Group Description Step Unit Format
range Value
Remote
parameters
0100 Address 1 to 247 1 - F1 247
Counters
0110 Trips Number 0 to 65535 1 - F1 0
CT Ratio
0120 Line CT primary 1 to 30000 1 A F1
Blocking Inrush
0130 Inrush Blocking? 0 to 2 1 - F74 0
Values Default
Address Group Description Step Unit Format
range Value
0133 Unblock Inrush Time 0 to 20000 1 1/100 s F1 100
0134-013F Reserved
O/C Advanced
Settings
0137 I< stage for Broken Conductor 10 to 100 1 [In]/100 F1 10
0138 IDMT interlock by DMT stage 0 to 1 1 - F88 0
GLOBAL SETTINGS
LOC
0140 Language 0 to 5 1 - F52 0
014B-014F Reserved
SETTING GROUP
SELECT
0150 Number of Setting Groups 0 to 1 1 - F71 0
E/F ADVANCED
0155 UN Threshold 5.0 to 90.0 0.1 v F1 5.0 v
[79] ADVANCED
SETTINGS
0160 [79] CB Healthy Monit? 0 to 1 1 - F63
Values Default
Address Group Description Step Unit Format
range Value
0163 Rolling Demand? 0 to 1 1 - F54 0
0164 Max cycles Nb Rol.Demand 2 to 100 1 - F1 2
0165 Time Period Rol.Demand 1 to 1410 1 mn F1
0166 [79] Time Inhibit on Close 1 to 60000 1 1/100 s F1 100
0167 [79] Reset Signaling on Close 0 to 1 1 - F106 0
0168-017F Reserved
CIRCUIT
BREAKER
0180 tOpen pulse min 10 to 1000 1 1/100 s F1 50
DISTURBANCE
RECORDER
019A Pre-Time 10 to 700 1 1/100 s F1 10
019E-01A4 Reserved
COMMISIONING
01A5 Maintenance Mode 0 to 2 1 - F62 0
Values Default
Address Group Description Step Unit Format
range Value
01AC Functional Test 0 to 1 1 - F75 0
01AD-01AF Reserved
01C3-01FF Reserved
042D Reserved
0431-043E Reserved
Access in writing.
MODBUS Function 6
Note: A one control can be executed in a one message only. Two control commands
in a one message will be rejected by P1F
Examples of messages
The example 1
Query to apply “ hermal tate reset” via PowerLogic P1F:
The example 2
Query to apply “ emote B lose ommand” via PowerLogic P1F:
MODBUS Function 5
Remote
04 See format: F113 0 to 21 1 FF 00
control
An example of request to “remote CB close command” (force coil 0F – ON) in slave 17 (dec):
Field name Value (Hex) Remarks
Slave Address 11 P1F setting value
Function 05
Coil Address Hi 04 See table above
Coil Address Lo 0F See format F113
Force Data Hi FF Fixed value
Force Data Lo 00 Fixed value
Error Check (CRC) - -
Pages 5h/6h
Page 7h
Access in writing for n words (function 16). The time synchronization format is based
on 8 bits (4 words) (Inverted IEC 60870-5-4 CP56Time2a):
Address Nb Mask
Timer Values range Unit
(hex) bytes (hex)
1 (Hi)
0800 0 – 99
Year 1 (Lo) 7F Year
(2000-2099)
Month 1 (Hi) 0F 1 – 12 month
Day of week 0801 1 (Lo) E0 Not used in P1F -
day of month 1 (Lo) 1F 1 – 31 Day
0–1
Season 1 (Hi) 80 (summer-winter)
Not used
Hour 0802 1 (Hi) 1F 0-23 Hour
Invalidity 1 (Lo) 80 0 -1 (valid – invalid)
Minute 1 (Lo) 3F 0-59 Minute
Millisecond pF+pf 0803 2 FFFF 0 – 59999 ms
PAGE 03h
0300h to 03Feh
PAGE 08h
0800h to 0803h
Not available
PAGE 04h
0400h to 0402h
Address Contents
0900h to 09Fah 250 disturbance data words
0A00h to 0AFAh 250 disturbance data words
0B00h to 0BFAh 250 disturbance data words
0C00h to 0CFAh 250 disturbance data words
0D00h to 0DFAh 250 disturbance data words
0E00h to 0DFAh 250 disturbance data words
0F00h to 0FFAh 250 disturbance data words
1000h to 10Fah 250 disturbance data words
1100h to 11Fah 250 disturbance data words
1200h to 12Fah 250 disturbance data words
1300h to 13Fah 250 disturbance data words
1400h to 14Fah 250 disturbance data words
1500h to 15Fah 250 disturbance data words
1600h to 16Fah 250 disturbance data words
1700h to 17Fah 250 disturbance data words
sample_VN Internal_V N
Value VN = 2
20
Where:
Internal_VN: Internal scaling (Page 38h to 3Ch)
• Frequency channel:
Time between two samples in microseconds
• Logic channels:
Address Contents
Word Contents
Page 32h (addresses 3200h to 3207h): Spring charging record data (6 words)
Address Contents
Each value read is a floating point type (4 bytes). More than one value can be read.
MODBUS
Code Meaning of the event Type
address
00 No event - -
01 CB closing (Remote/menu HMI) F38 0400h (bit 15)
02 CB tripping (Remote/menu HMI) F38 0400h (bit 7)
03 Reset latched outputs (Remote) F38 0400h (bit 2)
04 Reset signaling (Remote) F38 0400h (bit 1)
05 Reset signaling and latched outputs (Remote) F38 0400h (bit 3)
06 Clear fault and disturbance recorder F38A 0401h (bit 0)
07 Clear event recorder F38A 0401h (bit 1)
08 Setting group change - -
09 Warm restart -
10 Reserved - -
11 Current Protection disable status -
12 START I> F37 0021h (bit 0)
13 START I>> F37 0022h (bit 0)
14 START IN_1 F50 0024h (bit 0)
15 START IN_2 F50 0025h (bit 0)
16 tI> F37 0021h (bit 6)
17 tI>> F37 0022h (bit 6)
18 tIN_1 F50 0024h (bit 6)
19 tIN_2 F50 0025h (bit 6)
20 tAUX1 F51 0027h (bit 6)
21 CB status: opened F30 001Bh (value 0)
22 CB status: closed F30 001Bh (value 1)
23 CB status: faulty F30 001Bh (value 3)
24 CB status: undefined F30 001Bh (value 4)
25 tCB Faulty External Signal. F31A 001Ah (bit 10)
26 Start tCB Fail Ext. F51 002Ah (bit 0)
27 CHANGE OF INPUT LOGIC STATE F11 0010h
28 CHANGE OF OUTPUT LOGIC STATE F24 0013h
29 START I>>> F37 0023h (bit 0)
30 tI>>> F37 0023h (bit 6)
MODBUS
Code Meaning of the event Type
address
31 Start I2> F50 002Dh (bit 0)
32 tI2> F50 002Dh (bit 6)
33 tAUX2 F51 0028 (bit 6)
34 tCB Fail F51 0029h (bit 6)
35 Setting Group 1 active F32 0009h (bit 0)
36 Setting Group 2 active F32 0009h (bit 1)
37 tI> Alarm F31 0019h (bit 0)
38 tI>> Alarm F31 0019h (bit 1)
39 tI>>> Alarm F31 0019h (bit 2)
40 tIN_1 Alarm F31 0019h (bit 4)
41 tIN_2 Alarm F31 0019h (bit 5)
42 tAUX1 Alarm F31A 001Ah (bit 5)
43 tAUX2 Alarm F31A 001Ah (bit 6)
44 tI2> Alarm F31 0019h (bit 8)
45 tCB Fail Alarm F31 0019h (bit 10)
46 Start AUX1 F51 0027h (bit 0)
47 Start AUX2 F51 0028h (bit 0)
48 [79] Autoreclose blocked (Remote/menu HMI) F38 0400h (bit 8)
49 [79] Autoreclose unblocked (Remote/menu HMI) F38 0400h (bit 9)
50 Reset latched Alarms F38 0400h (bit 5)
51 Reserved - -
52 Reserved - -
53 Reserved - -
54 Ack oldest disturbance recorder record F38A 0401h (bit 8)
55 Reserved - -
56 Disturbance recorder start (Remote) F38A 0401h (bit 5)
57 Communication order 1 F38A 0401h (bit 14)
58 Communication order 2 F38A 0401h (bit 15)
59 Reserved - -
60 Thermal state reset (Remote/menu HMI) F38A
61 Recloser counters reset (Remote/menu HMI) F38A 0401h (bit 3)
62 Fault counters reset (Remote/menu HMI) F38A 0401h (bit 10)
63 Control counters reset (Remote/menu HMI) F38A 0401h (bit 12)
64 Maintenance mode F38A 0401h (bit 13)
65 End of maintenance mode F38A 0401h (bit 6)
66 START IN_3 F38A 0401h (bit 7)
67 tIN_3 F50 0026h (bit 0)
68 tIN_3 Alarm F50 0026h (bit 6)
69 Start SOTF F31 0019h (bit 6)
70 tSOTF F37 002Bh (bit 0)
MODBUS
Code Meaning of the event Type
address
71 tSOTF Alarm F37 002Bh (bit 6)
72 Reserved - -
73 Reserved - -
74 Reserved - -
75 Start Broken Conductor F31 0019h (bit 7)
76 tBroken Conductor F50 002Eh (bit 0)
77 tBroken Conductor Alarm F50 002Eh (bit 6)
78 Itherm> F31 0019h (bit 9)
79 Thermal OL Trip F50 002Fh (bit 0)
80 Thermal OL Alarm F50 002Fh (bit 6)
81 START AUX3 F31 0019h (bit 11)
82 tAUX3 F51 0030h (bit 0)
83 tAUX3 Alarm F51 0030h (bit 6)
84 Start AUX4 F31A 001Ah (bit 7)
85 tAUX4 F51 0031h (bit 0)
86 tAUX4 Alarm F51 0031h (bit 6)
87 Reserved - -
88 Reserved - -
89 Reserved - -
90-95 Reserved - -
96 Local CTRL mode F61 001Eh (value: 2)
97 Remote CTRL mode F61 001Eh (value: 1)
98 Local and remote CTRL mode F61 001Eh (value: 0)
99 Reserved - -
100 Reserved - -
101 Reserved - -
102 Setting Group 2 set via Input F104 0035h (bit 8)
103 Relays Test (Commissioning Test) active -
104 Test I> On -
105 Test I> Off -
106 Test I>> On -
107 Test I>> Off -
108 Test I>>> On -
109 Test I>>> Off -
110 Test SOTF On -
111 Test SOTF Off -
112 Test IN_1 On -
113 Test IN_1 Off -
114 Test IN_2 On -
115 Test IN_2 Off -
MODBUS
Code Meaning of the event Type
address
116 Test IN_3 On -
117 Test IN_3 Off -
118 Reserved - -
119 Reserved - -
120 Test I2> On -
121 Test I2> Off -
122 Test Brkn. Cond. On -
123 Test Brkn. Cond. Off -
124 Test Thermal OL On
125 Test Thermal OL Off
126 Test CBF On -
127 Test CBF Off -
128 Blocking tI> active F101 0032h (bit 0)
129 Blocking tI>> active F101 0032h (bit 1)
130 Blocking tI>>> active F101 0032h (bit 2)
131 Blocking tSOTF active F101 0032h (bit 3)
132 Blocking tIN_1 active F101 0032h (bit 4)
133 Blocking tIN_2 active F101 0032h (bit 5)
134 Blocking tIN_3 active F101 0032h (bit 6)
135 Reserved - -
136 Blocking tI2> active F101 0032h (bit 8)
137 Blocking tBrkn. Conductor active F101 0032h (bit 9)
138 Blocking Itherm. Active F101 0032h (bit 11)
139 Blocking tAUX1 active F102 0033h (bit 5)
140 Blocking tAUX2 active F102 0033h (bit 6)
141 Blocking tAUX3 active F102 0033h (bit 7)
142 Blocking CB Fail active F101 0032h (bit 10)
143 Blocking [79] active F102 0033h (bit 0)
144 Sel1 tI>> active F103 0034h (bit 0)
145 Sel1 tI>>> active F103 0034h (bit 1)
146 Sel1 tIN_2 active F103 0034h (bit 2)
147 Sel1 tIN_3 active F103 0034h (bit 3)
148 reserved - -
149 Sel2 tI>> ACTIVE F103 0034h (bit 4)
150 Sel2 tI>>> ACTIVE F103 0034h (bit 5)
151 Sel2 tIN_2 ACTIVE F103 0034h (bit 6)
152 Sel2 tIN_3 ACTIVE F103 0034h (bit 7)
153 reserved - -
154 Cold Load PU active F104 0035h (bit 3)
155 Manual Close via Input -
MODBUS
Code Meaning of the event Type
address
156 Manual Close via Function Key -
157 Manual Trip via Input -
158 Manual trip via Function Key -
159 TC Supervision alarm F31A 001Ah (bit 11)
160 Theta Reset via Input F104 0035h (bit 12)
161 Start Disturbance recorder via Input -
162 Changing CTRL mode via Input F104 0035h (bit 14)
163 Changing CTRL mode (Remote/menu HMI) F38 0400h (bit 4)
164 Active [79] in Progress F59 001Ch (bit 1)
165 [79] Final trip F59 001Ch (bit 4)
166 [79] Lockout F59 001Ch (bit 6)
167 [79] Blocked F59 001Ch (bit 0)
168 [79] Successful F59 001Ch (bit 5)
169 [79] tD1 counting F59 001Ch (bit 8)
170 [79] tD2 counting F59 001Ch (bit 9)
171 [79] tD3 counting F59 001Ch (bit 10)
172 [79] tD4 counting F59 001Ch (bit 11)
173 [79] tR counting F59 001Ch (bit 12)
174 Fast O/C trip Delay Elapsed F59 001Ch (bit 13)
175 Fast E/GND Trip Delay Elapsed F59 001Ch (bit 14)
176 [79] Reclose order F59 001Ch (bit 3)
177 [79] Inhibit Trip tI> active -
178 [79] Inhibit Trip tI>> active -
179 [79] Inhibit Trip tI>>> active -
180 [79] Inhibit Trip tIN_1 active -
181 [79] Inhibit Trip tIN_2 active -
182 [79] Inhibit Trip tIN_3 active -
183 [79] Inhibit Trip tAUX1 active -
184 [79] Inhibit Trip tAUX2 active -
185 [79] Rolling demand blocking active -
186 [79] Inhibit time on close counting F60 001Dh (bit 2)
187 Autoreclose: T-C -
188 Autoreclose: T-C-T -
189 Autoreclose: T-C-T-C -
190 Autoreclose: T-C-T-C-T -
191 Autoreclose: T-C-T-C-T-C -
192 Autoreclose: T-C-T-C-T-C-T -
193 Autoreclose: T-C-T-C-T-C-T-C -
194 Autoreclose: T-C-T-C-T-C-T-C-T -
195 Reserved -
MODBUS
Code Meaning of the event Type
address
196 Reserved - -
197 CB Time Supervision Alarm F31A 001Ah (bit 12)
198 Unblock SOTF active -
199 tReset I> active F37 0021h (bit 5)
200-399 Reserved - -
400 tReset I>> active F37 0022h (bit 5)
401 tReset IN_1 active F50 0024h (bit 5)
402 tReset I2> active F50 002Dh (bit 5)
403 Reserved - -
404 Reserved - -
405 Reserved - -
406 Reserved - -
407 Reset signaling via Input F104 0035h (bit 1)
408 Reset latched outputs via Input F104 0035h (bit 2)
409 Inrush threshold active F28A 0016h (bit 4)
410 Inrush unblock active -
411 Reset Signaling via Close command
412 State of CB Alarm F31A 001Ah (bit 2)
413 [79] Rolling demand Alarm F31A 001Ah (bit 9)
414 CB current diagnostic Alarm F31A 001Ah (bit 0)
415 CB number diagnostic Alarm F31A 001Ah (bit 1)
416 Max CB open number - -
418 Automatic acknowledgement of events enabled -
419 Automatic acknowledgement of events disabled -
421 LED Status F25 0014h
422 Communication protocol changed 0101h
423 [79] Status Changed F59 001Ch
424 [79] Blocking Status Changed F60 001Dh
425 Front Panel Operation F2 000Ch
426 Cold Restart -
Note: The double arrow means the event is generated on event occurrence
() and on event disappearance ().
Page 36h
Address Contents
Address Contents
Words n° 2 & 3 & 4 & 5: see table below (Inverted IEC 60870-5-4 CP56Time2a)
Nb
Address Mask
Timer byte Values range Unit
(hex) (hex)
s
1 (Hi)
Word n° 2 0 – 99
Year 1 (Lo) 7F Year
(2000-2099)
Month 1 (Hi) 0F 1 – 12 month
Day of week Word n° 3 1 (Lo) E0 Not used in P1F
day of month 1 (Lo) 1F 1 – 31 Day
0–1
Season 1 (Hi) 80 (summer-winter)
Word n° 4 Not used
Hour 1 (Hi) 1F 0-23 Hour
Word n° 6: Reserved
0= none
1= phase A
2= phase B
3= phase C
4= phases A-B
5= phases A-C
6= phases B-C
7= phases A-B-C
8= earth
00 Null event
01 Reserved
02 Thermal Overload
03 tI> trip
04 tI>> trip
05 tI>>> trip
06 tlN>_1 trip
07 tlN_2 trip
08 tlN_3 trip
09 Reserved
10 tBrkn Cond
11 t Aux 1 trip
12 t Aux 2 trip
13 tI2> trip
14 Reserved
15 t Aux 3 trip
16 t Aux 4 trip
17 CB Fail trip
18 tSOTF
19 Reserved
20 Cbext trip
Line phase current value (primary value) = phase sampled value (e.g. address
0040h, 0041h or 0042h) * {line primary CT ratio (address 0120h)/Line CT sec
(address 0121h)} A/100.
Line phase current value (primary value) = earth sampled value (e.g. address
0043h) * {line primary CT ratio (address 0122h)/Line CT sec (address 0123h)}
A/1000.
Address Contents
Selection of the disturbance record and channel (34 bytes are uploaded for each
address reading)
Access in word reading (function 03)
3800h 1 IA
3801h 1 IB
3802h 1 IC
3803h 1 IN
3804h 1 Logic input and outputs
3805h 1 Frequency
3900h 2 IA
3901h 2 IB
3902h 2 IC
3903h 2 IN
3904h 2 Logic input and outputs
3905h 2 Frequency
3A00h 3 IA
3A01h 3 IB
3A02h 3 IC
3A03h 3 IN
3A04h 3 Logic input and outputs
3A05h 3 Frequency
3B00h 4 IA
3B01h 4 IB
3B02h 4 IC
3B03h 4 IN
3B04h 4 Logic input and outputs
3B05h 4 Frequency
3C00h 5 IA
3C01h 5 IB
3C02h 5 IC
3C03h 5 IN
3C04h 5 Logic input and outputs
3C05h 5 Frequency
Selection of the disturbance record and channel (38 bytes are uploaded for each
address reading)
3800h 1 IA
3801h 1 IB
3802h 1 IC
3803h 1 IN
3804h 1 VN
3805h 1 Logic input and outputs
3806h 1 Frequency
3900h 2 IA
3901h 2 IB
3902h 2 IC
3903h 2 IN
3904h 2 VN
3905h 2 Logic input and outputs
3906h 2 Frequency
3A00h 3 IA
3A01h 3 IB
3A02h 3 IC
3A03h 3 IN
3A04h 3 VN
3A05h 3 Logic input and outputs
3A06h 3 Frequency
3B00h 4 IA
3B01h 4 IB
3B02h 4 IC
3B03h 4 IN
3B04h 4 VN
3B05h 4 Logic input and outputs
3B06h 4 Frequency
3C00h 5 IA
3C01h 5 IB
3C02h 5 IC
3C03h 5 IN
3C04h 5 VN
3C05h 5 Logic input and outputs
3C06h 5 Frequency
CODE DESCRIPTION
F1 Unsigned integer – numerical data: 1 – 65535
F2 Edit mode – unsigned integer:
0: Edit mode not active
1: Edit mode active
2: Front panel (CB) operation
F3 Relay forward direction – unsigned integer:
0: Line
1: Bus
2: no direction
F10 Characters ASCII
byte 1: ASCII character 32-127
byte 2: ASCII character 32-127
F11 Binary input status – unsigned integer (16-bits flag field):
bit 0: logic input 1
bit 1: logic input 2
bit 2: logic input 3
bit 3: logic input 4
bit 4: logic input 5
bit 5: logic input 6
bit 6: logic input 7
bit 7: logic input 8
bit 8-15: reserved
F12 Current Protection disable status – unsigned integer (16-bits flag field):
bit 0: I> disabled
bit 1: I>> disabled
bit 2: I>>> disabled
bit 3: SOTF disabled
bit 4: IN_1 disabled
bit 5: IN_2 disabled
bit 6: IN_3 disabled
bit 7: reserved
bit 8: I2> disabled
bit 9: Brkn Cond. Disabled
bit 10: CB Fail disabled
bit 11: Thermal OL disabled
bit 12 to 15: reserved
F12A Protection Function disable status – unsigned integer (16-bits flag field):
bit 0: 79 Autoreclose disabled
bit 1: SEL1 disabled
bit 2: SEL2 disabled
bit 3: Cold Load PU disabled
bit 4: Blocking Inrush disabled
bit 5: AUX1 disabled
bit 6: AUX2 disabled
bit 7: AUX3 disabled
bit 8: AUX4 disabled
bit 9 to 15: reserved
F13 LR Status – unsigned integer (16-bits flag field)
bit 1: L+R
bit 2: Remote
bit 3: Local
bit 4: reserved
bit 5: reserved
bit 6: reserved
bit 7: reserved
bit 8: reserved
bit 9: reserved
bit 10: reserved
bit 11: reserved
bit 12: reserved
bit 13: reserved
CODE DESCRIPTION
bit 14: reserved
bit 15: reserved
F13A Maintenance Mode Status – unsigned integer (16-bits flag field)
bit 1: Maintenance Off
bit 2: Maintenance On without out blocking
bit 3: Maintenance On without blocking
bit 4: reserved
bit 5: reserved
bit 6: reserved
bit 7: reserved
bit 8: reserved
bit 9: reserved
bit 10: reserved
bit 11: reserved
bit 12: reserved
bit 13: reserved
bit 14: reserved
bit 15: reserved
F14 CB Status – unsigned integer (16-bits flag field)
bit 0: CB open
bit 1: CB close
bit 2: CB Faulty
bit 3: CB not defined
bit 4: reserved
bit 5: reserved
bit 6: reserved
bit 7: reserved
bit 8: reserved
bit 9: reserved
bit 10: reserved
bit 11: reserved
bit 12: reserved
bit 13: reserved
bit 14: reserved
bit 15: reserved
F15 Two-digit decimal number – Firmware version – unsigned integer
1st digit – major version
2nd digit – minor version
10: 1A
11: 1B
12: 1C
13: 1D
etc.
F16 Configuration – unsigned integer
0: disabled
1: Trip
2: Alarm
3: Trip with Inrush Blocking
4: Trip with Latching
F16A Configuration – unsigned integer
0: disabled
1: Trip
2: Alarm
3: Trip with Inrush Blocking
4: Trip with Latching
5: Trip-Phase A
6: Trip-Phase B
7: Trip-Phase C
F17 Trip latch status 1 – unsigned integer (16-bit flag field)
bit 0: I>
bit 1: I>>
bit 2: I>>>
bit 3: IN_1
bit 4: IN_2
bit 5: IN_3
bit 6: AUX1
bit 7: AUX2
CODE DESCRIPTION
bit 8: AUX3
bit 9: AUX4
bit 10: reserved
bit 11: Is2
bit 12: BC
bit 13: reserved
bit 14: SOTF
bit 15: reserved
F17A Trip latch status 2 – unsigned integer (16-bit flag field)
bit 0: reserved
bit 1: reserved
bit 2: reserved
bit 3: reserved
bit 4: reserved
bit 5: reserved
bit 6: reserved
bit 7: reserved
bit 8: reserved
bit 9: reserved
bit 10: reserved
bit 11: Ext CBF
bit 12: reserved
bit 13: reserved
bit 14: reserved
bit 15: reserved
F18 Curves type – unsigned integer
0: DMT
1: SI IEC
2: VI IEC
3: EI IEC
4: LTI (IEC)
5: STI (IEC)
6: RC Rectifier curve
7: RI curve
8: MI IEEE
9: VI IEEE
10: EI IEEE
11: STI (US C02-P20)
12: LTI (US C08)
13: RXIDG
14: BPN EDF
15: STI (US C02-P40)
16: US C05
17: US C06
18: US C07
19: US C09
20: US C011
21: HV_Fuse
F19 Baud rate value – unsigned integer
0: 4800 baud
1: 9600 baud
2: 19200 baud
3: 38400 baud
4: 57600 baud
5: 115200 baud
F20 Parity – unsigned integer
0: NONE
1: ODD
2: EVEN
F22 Stop – unsigned integer
0: 1 stop
1: 2 stop
F23 Line CT Sec – unsigned integer
9: In = 1A/5A; 0.1-40In
F23A E/GND Sec – unsigned integer
0: 0.01-2Ien
CODE DESCRIPTION
3: 0.05-12Ien
4: 0.01-12Ien
F24 Logical output status – unsigned integer (16-bits flag field):
bit 0: logic output RL1
bit 1: logic output RL2
bit 2: logic output RL3
bit 3: logic output RL4
bit 4: logic output RL5
bit 5: logic output RL6
bit 6: Reserved
bit 7-15: reserved
F25 Logical LED status – unsigned integer (16-bits flag field):
bit 0: Trip
bit 1: Alarm
bit 2: LED3
bit 3: LED4
bit 4: LED5
bit 5: LED6
bit 6: LED7
bit 7: Healthy
bit 8-15: reserved
F26 Logical heathy status – unsigned integer (16-bits flag field):
bit 0: reserved
bit 1: HW_OFFSET exceeded
bit 2-3: reserved
bit 4: Healthy
bit 10-15: reserved
F28 Protection start status – unsigned integer (16-bits flag field):
bit 0: I>
bit 1: I>>
bit 2: I>>>
bit 3: SOTF
bit 4: IN_1
bit 5: IN_2
bit 6: IN_3
bit 7: reserved
bit 8: I2>
bit 9: Brkn Cond.
bit 10: tCB Fail Start
bit 11: Itherm Start
bit 12: starting in phase A
bit 13: starting in phase B
bit 14: starting in phase C
bit 15: starting in N
F28A Protection start status – unsigned integer (16-bits flag field):
bit 0: Reserved
bit 1: Reserved
bit 2: Reserved
bit 3: Cold Load PU active
bit 4: Blocking Inrush active
bit 5: AUX1
bit 6: AUX2
bit 7: AUX3
bit 8: AUX4
bit 9-15: Reserved
F29 Current Protection trip status – unsigned integer (16-bits flag field):
bit 0: tI>
bit 1: tI>>
bit 2: tI>>>
bit 3: tSOTF
bit 4: tIN_1
bit 5: tIN_2
bit 6: tIN_3
bit 7: reserved
bit 8: tI2>
bit 9: tBrkn Conductor
CODE DESCRIPTION
bit 10: CB Fail
bit 11: Thermal Overload
bit 12: starting in phase A
bit 13: starting in phase B
bit 14: starting in phase C
bit 15: starting in N
F29A Protection Function trip status – unsigned integer (16-bits flag field):
bit 0: Reserved
bit 1: reserved
bit 2: reserved
bit 3: reserved
bit 4: reserved
bit 5: tAUX1
bit 6: tAUX2
bit 7: tAUX3
bit 8: tAUX4
bit 9-15: reserved
F30 CB status – unsigned integer (decimal value)
0: CB opened
1: CB closed
2: Not set state
3: CB position faulty
4: CB position undefined
F31 Protection Alarm status – unsigned integer (16-bits flag field):
bit 0: tI>
bit 1: tI>>
bit 2: tI>>>
bit 3: tSOTF
bit 4: tIN_1
bit 5: tIN_2
bit 6: tIN_3
bit 7: reserved
bit 8: tI2>
bit 9: tBrkn Conductor
bit 10: tCB Fail
bit 11: Thermal Overload
bit 12-15: reserved
F31A Alarm Function status – unsigned integer (16-bits flag field):
bit 0: CB current Diagnostic (Square Amps sum overreach)
bit 1: CB number Diagnostic (operation number overreach)
bit 2: State of CB Alarm
bit 3: reserved
bit 4: reserved
bit 5: tAUX1
bit 6: tAUX2
bit 7: tAUX3
bit 8: tAUX4
bit 9: [79] Rolling demand Alarm
bit 10: t CB Faulty ext sign
bit 11: TC Supervision (Trip circuit self-test)
bit 12: CB Time Supervision (time overreach)
bit 13-15: reserved
F32 Setting group – unsigned integer
0: Setting group 1
1: Setting group 2
F33 Output configuration – unsigned integer (16-bits flag field):
bit 0: RL1
bit 1: RL2
bit 2: RL3
bit 3: RL4
bit 4: RL5
bit 5: RL6
bit 6: RL7
bit 7: WD
bit 8-15: reserved
CODE DESCRIPTION
F35 Input configuration – unsigned integer (16-bits flag field):
bit 0: Input L1
bit 1: Input L2
bit 2: Input L3
bit 3: Input L4
bit 4: Input L5
bit 5: Input L6
bit 6: Input L7
bit 7: Input L8
bit 8-15: reserved
F36 Output configuration – unsigned integer (16-bits flag field):
bit 0: RL1
bit 1: RL2
bit 2: RL3
bit 3: RL4
bit 4: RL5
bit 5: RL6
bit 6: RL7
bit 7-15: reserved
F37 I>, I>>, I>>>, SOTF, CBF, Therm threshold phase information status – unsigned
integer (16-bits flag field):
bit 0: information threshold exceeded
bit 1: Instantaneous IA
bit 2: Instantaneous IB
bit 3: Instantaneous IC
bit 4: Blocking signal active
bit 5: tReset active
bit 6: Time delay elapsed
bit 7: Alarm
bit 8 to 15: reserved
F38 Remote control word – unsigned integer (16-bits flag field):
0: Warm restart
1: Reset LEDs
2: Reset Outputs
3: Reset LEDs and Outputs
4: Local Mode
5: Reserved
6: Setting change to Group 1
7: Remote or HMI CB open order
8: Remote or HMI [79] Autoreclose blocking
9: Remote or HMI [79] Autoreclose unblocking
10: Remote Mode
11: Setting change to Group 2
12: Disable automatic acknowledgement of events
13: Oldest event acknowledge
14: Oldest fault acknowledge
15: Remote or via HMI CB close order
F38A Remote control word – unsigned integer (16-bits flag field):
0: Clear Recorders
1: Clear Events
2: reserved
3: Thermal state reset
4: Reserved
5: Disturbance record remote start
6: Maintenance mode
7: End of maintenance mode
8: Acknowledgement of the oldest disturbance record
9: Reserved
10: Recloser reset counters
11: Reserved
12: Reset Fault counters
13: Reset control counters
14: Communication Order 1
15: Communication Order 2
F38B Remote control word – unsigned integer (16-bits flag field):
0: [79] Unlockout
CODE DESCRIPTION
1: Enable automatic acknowledgement of events
2: Change Modbus S1 to Modbus Std
3: Change Modbus Std to Modbus S1
4: Clear CB Open Time Recorder
5: Clear CB Close Time Recorder
6: Clear Spring Charging Time Recorder
7: Clear CB Counters
8: Clear Interval Square Breaking Current and Interval Counters
9: Clear Racking Counter
10-15: reserved
F39 LED function – unsigned integer (16-bits flag field):
bit 0: LED2
bit 1: LED3
bit 2: LED4
bit 3: LED5
bit 4: LED6
bit 5: LED7
bit 6-15: reserved
F40 Output configuration – unsigned integer (16-bits flag field):
bit 0: RL1
bit 1: RL2
bit 2: RL3
bit 3: RL4
bit 4: RL5
bit 5: RL6
bit 6: RL7
bit 7-15: reserved
F41 Curve Type – unsigned integer
0: DT
1: IDMT
F49 relay status – unsigned integer (16-bits flag field):
bit 0: Relay status (major alarms)
bit 1: Minor hardware alarm
bit 2: Presence of non-acknowledged event
bit 3: Synchronization state
bit 4: Presence of non-acknowledged disturbance record
bit 5: Presence of non-acknowledged fault record
bit 6: Local Maintenance Ack state
bit 7-15: reserved
F50 Current protection IN_1, IN_2, IN_3, I2>, BC – unsigned integer (16-bits flag
field):
bit 0: information threshold exceeded
bit 1: reserved
bit 2: reserved
bit 3: reserved
bit 4: Blocking signal active
bit 5: tReset active
bit 6: Time delay elapsed
bit 7: Alarm information – Therm OL only
bit 8 to 15: reserved
F51 Information status about additional protection AUX1, AUX2, AUX3, AUX4 CB
Fail ext. sign. – unsigned integer (16-bits flag field):
bit 0: start
bit 1: Reserved
bit 2: Reserved
bit 3: Reserved
bit 4: Blocking active
bit 5: Start after blocking
bit 6: Time delay elapsed
bit 7 to 15: reserved
F52 Information about language in menu – unsigned integer
0: English;
1: German;
2: French;
3: Spanish
CODE DESCRIPTION
4: Russian
5: Turkish
6: Language 7
F53 Information about language in menu – unsigned integer
0: Measurements referred to In or Ien
1: Measurements referred to A
2: CB CTRL window
3: 79 CTRL window
4: CTRL Mode (Local/Remote)
F54 Unsigned integer:
0: Manual only
1: Start Protection
2: Close command
F55 Alarm Display Reset – unsigned integer
0: Self-Reset
1: Manual Reset
F56 Protocol – unsigned integer
0: Modbus S1
1: IEC103
2: Modbus Std
3: GetSet
4: Modbus PO
F57 Nominal Frequency – unsigned integer
0: 50Hz
1: 60Hz
F59 [79] status – unsigned integer (16-bits flag field):
bit 0: Recloser blocked
bit 1: Recloser in progress
bit 2: reserved
bit 3: Closing command executed via Autorecloser
bit 4: Recloser final trip
bit 5: Recloser successful
bit 6: Recloser lockout
bit 7: Trip locked via Recloser (inhibit of protection stage)
bit 8: Dead Time tD1 counting
bit 9: Dead Time tD2 counting
bit 10: Dead Time tD3 counting
bit 11: Dead Time tD4 counting
bit 12: Reclaim Time tR counting
bit 13: Fast O/C Trip Delay elapsed
bit 14: Fast E/GND Trip Delay elapsed
bit 15: reserved
F60 [79] blocking status – unsigned integer
0: Ready
1: In progress
2: Temporary blocked (after close signal)
3: Lockout
4: Blocked via CTRL (HMI+RS485)
5: Blocked via input
6: Disabled
F61 Local/Remote Mode – unsigned integer
0: Local and Remote
1: Remote only
2: Local only
F62 Maintenance Mode – unsigned integer
0: No
1: Yes
2: Yes- Bl.Outputs
F63 Configuration – unsigned integer
0: No
1: Yes
CODE DESCRIPTION
F64 79 dead time configuration – unsigned integer
0: Protection reset
1: CB trips
F65 Disturbance recorder configuration – unsigned integer
0: On Instantaneous
1: On Trip
F66 Configuration – unsigned integer
0: Disabled
1: Current+Input
2: Input only
F67 Close Shot – unsigned integer (16-bits flag field):
bit 0: First Reclose Shot
bit 1: Second Reclose Shot
bit 2: Third Reclose shot
bit 3: Fourth Reclose shot
bit 4-15: reserved
F71 Number of setting groups – unsigned integer
0: One Group
1: Two Groups
F72 AR trips cycle – unsigned integer (16-bits flag field):
bit 0: First trip shot
bit 1: Second trip shot
bit 2: Third trip shot
bit 3: Fourth trip shot
bit 4: Fifth trip shot
bit 5-15: reserved
F73 Remote Mode configuration – unsigned integer
0: Remote Only
1: Remote + Local
F74 Inrush Blocking configuration – unsigned integer
0: No
1: Yes
2: Closing
F75 Unsigned integer
0: No operation
1: Apply Test
F76 Function Test Pattern – unsigned integer (16-bits flag field):
bit 0: tI>
bit 1: tI>>
bit 2: tI>>>
bit 3: tSOTF
bit 4: tIN_1
bit 5: tIN_2
bit 6: tIN_3
bit 7: tI2>
bit 8: tBrkn Conductor
bit 9: Reserved
bit 10: Thermal OL Trip
bit 11: CB Fail
bit 12-15: reserved
F77 Functional Test End – unsigned integer
0: CB Trip
1: Time elapsed
F81 I>, I>>, I>>> (1 harmonic or True RMS) – unsigned integer
0: 1 Harmonic
1: True RMS
F82 Control keys Mode – unsigned integer
0: Disabled
1: No confirm
2: With confirm
3-15: reserved
CODE DESCRIPTION
F84 Configuration – unsigned integer
0: Disabled
1: Trip
2: Alarm
3: Trip – Inrush Blocking
4: Trip – Latch
5: IN act, Trip
6: IN act, Alarm
7: IN react, Trip
8: IN react, Alarm
9: GN Trip
10: GN Alarm
11: BN Trip
12: BN Alarm
13: YN Trip
14: YN Alarm
F88 IDMT Interlock by DMT – unsigned integer
0: No
1: Yes
F90 Software Version Number: numeric data 0-99 – unsigned Integer
F91 Line CT Sec. – unsigned integer
0: In=1A
1: In=5A
F92 E/GND CT Sec. – unsigned integer
0: In=1A
1: In=5A
F101 Input Protection Blocking 1 - -unsigned integer (16-bits flag field):
bit 0: tI>
bit 1: tI>>
bit 2: tI>>>
bit 3: tSOTF
bit 4: tIN_1
bit 5: tIN_2
bit 6: tIN_3
bit 7: reserved
bit 8: tIs2>
bit 9: tBCond
bit 10: tCB Fail
bit 11: Thermal OL
bit 12-15: reserved
F102 Input Protection Blocking 2 – unsigned integer (16-bits flag field):
bit 0: blocking [79] Autoreclose
bit 1-4: reserved
bit 5: AUX1
bit 6: AUX2
bit 7: AUX3
bit 8-15: Reserved
F103 Input Selective Logic – unsigned integer (16-bits flag field):
bit 0: SEL1 tI>>
bit 1: SEL1 tI>>>
bit 2: SEL1 tIN_2
bit 3: SEL1 tIN_3
bit 4: SEL2 tI>>
bit 5: SEL2 tI>>>
bit 6: SEL2 tIN_2
bit 7: SEL2 tIN_3
bit 8-15: Reserved
F104 Input Logic Data – unsigned integer (16-bits flag field):
bit 0: Maintenance Mode
bit 1: Reset Latched Signaling
bit 2: Reset Latched Outputs
bit 3: Cold Load PU
bit 4: reserved
bit 5: CB status 52a
CODE DESCRIPTION
bit 6: CB status 52b
bit 7: CB FLT External Signal
bit 8: Setting Group 2
bit 9: Manual Close
bit 10: Manual Trip
bit 11: Trip Circuit Supervision
bit 12: Reset Theta value
bit 13: Start Disturbance Recorder
bit 14: Local CTRL Mode
bit 15: reserved
F106 Unsigned integer – Signaling Reset on
0: No
1: Close via 79
F107 TC supervision? – unsigned integer (16-bits flag field):
0: No
1: Yes
2: Yes-52a
F109 Configuration – unsigned integer
0: Disabled
1: Enabled
F110 Configuration – unsigned integer
0: Disabled
1: enable Trip
2: enable Alarm
3: enable Trip with Inrush Blocking
4: enable Trip with Latching
5: Load shedding
6: AR after LS Hi
7: AR after LS Lo
F111 Configuration – unsigned integer
0: Disabled
1: Retrip
2: Alarm
3: Retrip-Inrush
4: Retrip-Latch
F113 Modicon Modbus Coil Address Lo (hex) – unsigned integer
00: Warm restart
01: Reset LEDs
02: Reset Outputs
03: Reset LEDs and Outputs
04: Local Mode
05: Reserved
06: Setting change to Group 1
07: Remote CB open order
08: Remote [79] Autoreclose blocking
09: Remote [79] Autoreclose unblocking
0A: Remote Mode
0B: Setting change to Group 2
0C: Disable automatic acknowledgement of events
0D: Oldest event acknowledge
0E: Oldest fault acknowledge
0F: Remote CB close order
10: Clear Recorders
11: Clear Events
12: reserved
13: Thermal state reset
14: Reserved
15: Disturbance record remote start
16: Maintenance mode
17: End of maintenance mode
18: Acknowledgement of the oldest disturbance record
19: Reserved
1A: Recloser reset counters
1B: Reserved
1C: Reset Fault counters
CODE DESCRIPTION
1D: Reset control counters
1E: Communication Order 1
1F: Communication Order 2
20: [79] Unlockout
21: Enable automatic acknowledgement of events
22: Modbus S1 to Modbus Std
23: Modbus Std to Modbus S1
This event request may be answered an error message with the error code:
The bit1 of the remote order frame (format F38B – mapping address 0402h) should
be set to 1. On event retrieval, this event record is acknowledged.
The bit12 of the remote order frame (format F38 – mapping address 0400h) should
be set to 1. On event retrieval, this event record is not acknowledged. To
acknowledge this event, another remote order should be sent to the relay. The bit 13
of this frame (format F38 – mapping address 0400h) should be set to 1.
This event request may be answered an error message with the error code:
Note: On fault retrieval, two possibilities exist regarding the fault record
acknowledgement:
a) Automatic fault record acknowledgement on fault retrieval.
b) Non-automatic fault record acknowledgement on fault retrieval.
The bit12 of the remote order frame (format F38 – mapping address 0400h) should
be set to 1. On fault retrieval, this fault record is not acknowledged.
To acknowledge this fault, another remote order should be sent to the relay. The bit
14 of this frame (format F38 – mapping address 0400h) should be set to 1.
Note: This fault value retrieval does not acknowledge this fault record.
The IEC 60870-5-103 interface is a master/slave interface with the relay as the slave
device. This protocol is based on the VDEW communication protocol. The relay
conforms to compatibility level 2, compatibility level 3 is not supported.
Initialization (Reset)
Time Synchronization
General Interrogation
Cyclic Measurements
General Commands
Connection is available for IEC 60870-5-103 through the rear RS485 port. It is
possible to select both the relay address and baud rate using the front panel
interface. Following a change, a reset command is required to re-establish
communications.
Even Parity
8 Data bits
1 stop bit
Initialization
Whenever the relay has been powered up, or if the communication parameters have
been changed a reset command is required to initialize the communications. The
relay will respond to either of the two reset commands (Reset CU or Reset FCB),
the difference being that the Reset CU will clear any unsent messages in the relay’s
transmit buffer.
The relay will respond to the reset command with an identification message
ASDU 5, the Cause of Transmission COT of this response will be either Reset CU or
Reset FCB depending on the nature of the reset command. The following
information will be contained in the data section of this ASDU:
Software Identification Section, Byte 0: Numerical part of device type, hex, low
Software Identification Section, Byte 1: Numerical part of device type, hex, low
Letters in the software version are converted to numerical values according to the
following rule: A=0, B=1, C=2, D=3 etc.
The Software Identification Section of PowerLogic P1F, version 1A, will then contain
‘ ’ and ‘ ’ as he adecimal coded values
Byte 0: 6FH
Byte 1: 00H
Byte 2: 10H
Byte 3: 00H
In addition to the above identification message, if the relay has been powered up it
will also produce a power up event.
Time Synchronization
Spontaneous Events
The events created by the relay will be passed to the master station using the
compatible range and the private range of IEC 60870-5-103 function types and
information numbers.
Common Address
Function Type
Information number
Below tables contains a complete listing of all events produced by the relay.
General Interrogation
The GI request can be used to read the status of the relay, the function numbers,
information numbers and common address offsets that will be returned during the GI
cycle are indicated in below tables.
Cyclic Measurements
The relay will produce measured values using ASDU 3 and ASDU 9 on a cyclical
basis. They can be read from the relay using a Class 2 poll.
It should be noted that the measurands transmitted by the relay are sent as a
proportion of 2.4 times the rated value of the analogue value. The selection of 2.4 for
a particular value is indicated in below tables.
Commands
A list of the supported commands is contained in below tables. The relay will
respond to all other commands with an ASDU 1, with a cause of transmission (COT)
of negative acknowledgement of a command
The relay does not support a facility to block messages in the Monitor direction.
In the list below, events only generated on rising edge will be tagged with a ‘*’.
The following list of processed events contains the messages for the compatible and
the private range for all Overcurrent protection functions, with the associated
FUNCTION TYPE, INFORMATION NUMBER, ASDU TYPE, CAUSE OF
TRANSMISSION
FUN <160>: Function type in Public range for Overcurrent Protections (compatible).
FUN <162>, <163>, <164>, <165>, <168>: Function type in Private range
(Reserved for Overcurrent Protections).
DPI
<0000 0000> “Undefined / Between closed and opened”
DPI
<0000 0000> “Undefined / Between closed and opened”
Processed Commands
System Commands:
Synchronization Command (ASDU 6): FUN<255>, INF <0>; TYP <6>; COT<8>
This command can be sent to a specific relay, or global. The time sent by master is
the time of the first bit of the frame. The relay synchronizes with this time, corrected
by the frame transmission delay. After updating its time, the relay sends back an
acknowledge to the master, by giving its new current time.
The relay then sends a list of data containing the relay state (see list described
above).
The GI command contains a scan number which will be included in the answers of
the GI cycle generated by the GI command.
If a data has just changed before extracted by the GI, the new state is sent to the
master station.
When an event is generated during the GI cycle, the event is sent in priority, and the
GI cycle is temporarily interrupted. The end of the GI consists in sending an ASDU 8
to the master station.
Output Reset:
This command reset Latched Outputs:
FUN<162>; INF<46>, TYP<20>, COT <20>, <ADDR>
Relay re initialization
Each identification message of the relay (ASDU 5) contains the manufacturer name
in 8 ASCII characters (“PowerLo “) and 4 free bytes containing:
The values are stored with a rate of 2,4 * nominal value = 4096.
Characteristics
Function Characteristics
General Characteristics
CT Transformation Ratio
Step 1A
Step 1A
Phase Currents
Characteristic Values
Measuring range . … In
Unit A or kA
Sensitive . … Ion
Unit A or kA
Characteristic Values
Measuring range … ac
Unit V or kV
In order to achieve 40ms min trip time, the submenu “LOC - H ” need to be
set to Enabled during “I>, I>>, I>>> (1 harmonic or True RMS)” set to harmonic,
and “time delay” of I>>>, IN>>>, IN>> set to 0ms.
HCDFT means that I>>>, IN>>>, IN>> protection function can use Half cycle Fourier
algorithm to detect big fault current faster.
Characteristics Values
Cold Load PU? Disabled,
Input+Curr
Input Only
Activity Cold Load PU I>
Cold Load PU I>>
Cold Load PU I>>>
Cold Load PU IN_1 (IN>)
Cold Load PU IN_2 (IN>>)
Cold Load PU IN_3 (IN>>>) (E, E+)
Cold Load PU Brkn Cond (E, E+)
Cold Load PU Itherm (N, A, B, E, E+)
Cold Load PU I2> (E, E+)
Characteristics Values
Therm OL? Disabled,
Enabled
Tripping curve DMT
Itherm Alarm Setting range … (step ) of the permissible
thermal capacity used (tripping set point)
Threshold
Accuracy ±5% or ±0.01 In
Trip Setting range . … . In (step . In)
Accuracy Itherm ±5% or ±0.01 In
Drop-off 0.95 Itherm ±5% or ±0.01 In
Time constant Setting range … min (step min)
Te (heating)
Setting range … min (step min)
Tr (cooling)
Characteristics Values
AUX1? Disabled,
AUX2? Trip,
AUX3? Alarm,
AUX4? Trip-Inrush Bl (A, E, E+),
Trip-Latch (A, E, E+),
Load Shedding (E, E+),
AR after LS Hi (E, E+),
AR after LS Lo (E, E+)
Tripping curve DMT
Time delay Setting range . … . s (step: 0.01 s)
tAUX1?
tAUX2? Accuracy ±2% or ±50ms
tAUX3?
tAUX4?
Broken Conductor
Switch on to Fault
Autoreclose
Default Settings
Phase O/C [50/51]
I> ? Disabled*
I> Threshold 1.2 x In
I> Delay Type IEC SI
tI> 1s
I> TMS 1
I> Time Dial 1
Reset Delay Type I> DMT
DMT tReset I> 0s
RTD/RTMS Reset I> 0.0 s
I>> ? Disabled*
I>> Threshold 1.4 x In
Delay Type I>> IEC SI
tI>> 1
I>> TMS 1
I>> Time Dial 1
Reset Delay Type I>> DMT
DMT tReset I>> 0s
RTD/RTMS Reset I>> 0.02 s
I>>> ? Disabled*
I>>> Threshold 4 x In
tI>>> 0.0 s
*If the stage/function is disabled all settings concerning this stage/function in the
menu cells are hidden.
Menu Text Default Setting
IDMT interlock by DMT No
Broken Conductor I
CB Fail [50BF]
*If the stage/function is disabled all settings concerning this stage/function in the
menu cells are hidden.
Logic Selectivity I
Autoreclose [79] I
Output settings define which signals are mapped to the P1F’s outputs. Matrix
configuration allows free mapping of any one function to each output.
Note:
• Model L have RL1 to RL3 + WD outputs
• Model N have RL1 to RL5 + WD outputs
• Model B have RL1 to RL3 + WD outputs
• Model A have RL1 to RL7 + WD outputs
• Model E have RL1 to RL5 + WD outputs
Input Configuration
Binary Input settings define which signals are mapped to the P1F’s opto-isolated
inputs. Matrix configuration allows free mapping of any one function to each input.
Note:
• Model L have no inputs
• Model N have no inputs
• Model B have 4 binary inputs (L1 to L4)
• Model A have 4 binary inputs (L1 to L4)
• Model E have 8 binary inputs programmable (L1 to L8).
LED Configuration
LED configuration settings define which signals are mapped to the P1F’s LEDs.
Matrix configuration allows free mapping of any one function to each LED.
GLOBAL SETTINGS
LOC
CT Ratio
Circuit Breaker
OP PARAMETERS
This column contains menu cells to show some of the P1F’s parameters (column to
read only).
Technical Characteristics
General Characteristics
Characteristics Values
Dimensions (W x H x D): 116,5 x 116,5 x
108 mm
Weight Approx. 0.80kg
Maximal internal clock drift +/-12 min a year
*Half of the binary inputs and half of the output relays should be energized.
Communication modules should be activated. (EN 60255-26).
Characteristics Values
Nominal current In 1 or 5 A (as setting)
Input impedance 0.002
RMS measurement in range 40Hz – 1kHz
Fundamental harmonic measurement in
40Hz – 70Hz
range
Operating range 0.1 – 40 In
Nominal burden at In <0.3 VA at In = 5A
<0.1 VA at In = 1A
Continuous thermal withstand 4 x In
Overload in accordance with IEC 60255-6 100 In at 1.00s
40 In at 2.00s
30 In at 10.00s
Characteristics Values
Nominal current Ion 1 or 5 A (as setting)
Input impedance 0.002
Fundamental harmonic measurement in
40Hz – 70Hz
range
Operating range 0.01 – 2Ion
(depends on hardware option) 0.05 – 12Ion
Nominal burden at Ion <0.3 VA at In = 5A
<0.1 VA at In = 1A
Continuous thermal withstand 4 x In
Overload in accordance with IEC 60255-6 100 In at 1.00s
40 In at 2.00s
30 In at 10.00s
Current transformer requirement Detailed information and CT
requirement are given in
Installation chapter
Dimensioning the CTs section.
Characteristics Values
Nominal voltage range 57 – 130 Vac
Input impedance 40 k
Operation range 5 – 130 Vac
1st harmonic measurement in range 40 – 70 Hz
Nominal burden at voltages
57 V 0.08 VA
100 V 0.25 VA
110 V 0.3025 VA
Binary Inputs
Note:
2) Filtering time is declared for Nominal Voltage range. For voltage value below
this range additional filtering time delay: < 20ms must be considered.
Below data applies following relay outputs: WD, RL1, RL2, RL3.
Characteristics DC Values AC Values
Contact relay Dry contact, Ag Ni Dry contact, Ag Ni
Rated voltage 250 V 250 V
Continuous 5A 5A
current
250 Vdc; 1250 VA resistive (cos = unity)
Braking
50 W resistive 1250 VA inductive (cos = 0.7)
capacity 30 W inductive (L/R = 40 ms)
Making capacity 250 V, 30 A, 200 ms 250 V, 30 A, 200 ms
2000 operations 2000 operations
Loaded contact 10000 operations minimum 10000 operations minimum
Unloaded 100000 operations minimum 100000 operations minimum
contact
Operate time Less than 10ms
Reset time Less than 5ms
Signal Relays
Below data applies following relay outputs: RL4, RL5, RL6, RL7.
Characteristics DC Values AC Values
Contact relay Dry contact, Ag Ni Dry contact, Ag Ni
Rated voltage 250 V 250 V
Continuous 5A 5A
current
250 Vdc; 1000 VA resistive (cos = unity)
Braking
30 W resistive 1000 VA inductive (cos = 0.7)
capacity
15 W inductive (L/R = 40 ms)
Loaded contact 10000 operations minimum 10000 operations minimum
Unloaded 100000 operations minimum 100000 operations minimum
contact
Operate time Less than 10 ms
Reset time Less than 5 ms
Communication Port
Characteristics Values
Type 2-wire RS485 differential
Line impedance 120 *
*Lack of internal terminating resistor
Environmental Characteristics
Electromagnetic Compatibility
40 % of residual voltage:
200 ms (50 Hz), 200 ms(60 Hz)
200 ms (dc)
70 % of residual voltage:
500 ms (50 Hz), 500 ms(60 Hz)
500 ms (dc)
Mechanical Robustness
Climatic Requirements
Cyclic temperature EN 60068-2-30 Db Damp heat cyclic, six (12 + 12) hour
with humidity test cycles,
93% RH, +25 °C to +55 °C
Safety Requirements
Impulse voltage withstand EN 60255-27 Front time: 1.2 µs, Time to half-value: 50 µs,
Peak value: 5 kV
Source Characteristics: 500 Ohm, 0.5 J.
Enclosure Protection
Certification/declaration
Maintenance
Preventive Maintenance
Introduction
Nonetheless, elements outside the P1F are not subject to these self-tests and it is
therefore necessary to carry out regular preventive maintenance.
Nothing inside the PowerLogic P1F requires preventive maintenance, nor can
anything be replaced by the user.
List of Interventions
The table below gives the typical frequency of interventions. The intervals between
visual inspections depends on the installation operating conditions.
Intervention Frequency
Routine check Weekly
LED test Annual
Inspection of the rear panel
Checking the complete trip chain Every 5 years
Routine Check
• Veryfi that the phase currents and the earth fault current measured by
PowerLogic P1F are appropriate for the load being powered.
LED Test
The LED test is used to check that each LED on the front panel are working
correctly.
To perform the test (if any protections are not triggered and PowerLogic P1F is
energized from the voltage), press R button from default display menu level. After
this, all LEDs on the front panel light up for 322pprox.. 1 s.
Check that the connections are tight and free from corrosion, paying particular
attention to the earth terminal and the CT connections.
If the CT connections are not tightened properly, this generates excessive heat rise
which can lead to the destruction of terminals and the CTs.
It is important to check regularly that the complete trip chain, from the CTs to the
P1F and through to the trip coil, is always operational.
Troubleshooting Assistance
Introduction
The paragraphs below list the actions to be taking after observing abnormal
PowerLogic P1F behavior. In the event of an anomaly, do not cut off the auxiliary
power supply before making a diagnosis.
Flashing of the Healthy LED indicates that PowerLogic P1F has gone into the fail
position following detection by the embedded self-tests of the failure of one of its
components.
During normal operation, the status of the rear communication port is signaled by
flashing rectangles in the top and bottom right corners of the display. Tx (Transmit)
is assigned to the top right corner, Rx (Receive) is assigned to the bottom right
corner of the display. Flashing of the rectangles indicate the operation of the rear
communication port.
If the PowerLogic P1F relay is not communicating with the SCADA system, check:
• That the supervisor is sending frames to the relevant P1F
• All the P1F communication parameters
• The wiring of each P1F
• The tightness of the screw terminals on connector C of each P1F
• The bus polarization, at a single point, in general by the master
• The line matching at the ends of the RS 485 network
If the problem persists, connect the P1F relays one by one on the communication
network to determine which P1F relay is responsible for the problem.
Lost Password
If you lost the password, read the serial number on the PowerLogic P1F label and
contact your local Schneider Electric after-sales service.
NOTICE
Please take care of your modified new password, reseting password may cause
some inconvenience or extra cost.
DANGER
HAZARD OF ELECTRIC SHOCK, ELECTRIC ARC, BURNS OR EXPLOSION
• Wear insulating gloves to avoid any contact with a conductor that has
accidentally been energized.
• Short-circuit secondary current transformer winding by use test block without
disconnecting the wires from it. This connector ensures continuity of the
current transformer secondary circuits.
• If you need to disconnect the wires connected to the test block, short-circuit
the current transformer secondary circuits.
If returning the PowerLogic P1F for expert assessment, use the original packaging
or packaging offering level 1protection against vibrations (standard IEC 60255-21-1)
and against shocks (standard IEC 60255-21-2).
The PowerLogic P1F relay must be returned accompanied by its settings sheet and
the following information:
• Name and address of the initiator
• PowerLogic P1F type and serial number
• Date of the incident
• Description of the incident
• LED status and message displayed at the time of the incident
• List of stored events
End of Life
Step Action
1 Remove the PowerLogic P1F as indicated above.
2 Dismantle the PowerLogic P1F in accordance with the End-of-Life
Instructions for PowerLogic P1. These instructions provide:
• Recyclability rates for our products.
• Guidance for mitigating personnel hazards during the dismantling of
your products and before recycling operations.
• Parts identification for recycling or for selective treatment, to mitigate
environmental hazards/incompatibility with standard recycling processes.
Application Cases
2CTs and CBCT application
Description
Each model (L, N, B, A, E, E+) PowerLogic P1F relays can be use in following
applications.
Details:
● Phase currents are measured in A and C phase
● B phase current is obtained from A and C phase currents
● Earth fault current is measured from dedicated earth CT
● Trip Signal is assigned to relay output 1
IB
Io
au iliary
voltage
+
I
oil
+
Each model (L, N, B, A, E, E+) PowerLogic P1F relays can be use in following
applications.
Details:
● Phase currents are measured in A, B and C phase
● Earth fault current is measured on the common point of the 3 phase CTs
● Trip Signal is assigned to relay output 1
IB
Io
au iliary
voltage
+
I
oil
+
Details:
● Phase currents are measured in A, B and C phase
● Earth fault current is measured by core balance CT
● Trip and Trip CB Order signals are assigned to relay output 1
● Close CB Order signal is assigned to relay output 2
● CB status is assigned to binary inputs 1 (close) and 2 (open)
● Communication port RS 485 is connected to SCADA system (CB control is
possible from SCADA also – depending on selected control mode)
IB
Io
au iliary
voltage
B status a
B status b
I lose
Each model (L, N, B, A, E, E+) PowerLogic P1F relays can be use in following
applications.
Details:
● Earth fault current is measured from dedicated earth CT (a) or measured on the
common point of the 3 phase CTs (b)
● Trip Signal is assigned to relay output 1
Figure 48. Examples of single-phase application diagrams
Variant no. 1 Variant no. 2
Earth fault measured by dedicated CT Earth fault measured on the common point of 3 phase
CTs
a) b)
B B
I I
IB IB
I I
Io Io
au iliary au iliary
voltage voltage
+ +
I I
oil oil
+ +
Logic Discrimination
Description
This type of protection (B, A, E, E+) can be applied to radial feeder circuits where
there is little or no back feed. For parallel feeders, ring circuits or where there can be
a back feed from generators, directional relays should be considered.
The blocking logic function allows the upstream IDMT relay to be blocked by the
start output of a downstream relay that has detected the presence of a fault current
above its threshold. Thus, both upstream and downstream relays can have the
same current and time settings, and the blocking feature will automatically provide
grading. If the CB failure protection is active, the blocking command on the upstream
relay will be removed if the down-stream circuit breaker fails to trip.
Thus, for a fault downstream from relay C, the start output from relay C aim to
prevent relay B from operating and the start output of relay B aim to prevent relay A
from operating. Therefore all 3 relays could have the same timer and current
settings and grading would be obtained by the blocking signal received from a relay
closer to the fault. This gives a constant, close time grading, but there will be no
back-up protection in the event of pilot wires being short-circuited.
In practice it is recommended to set the upstream relay to a value that is 10% higher
than the downstream relay setting. This helps to ensure that the downstream relay
successfully blocks the upstream relay when required.
The “Blocking Logic” functions are assigned in the SETTING GROUP x/ INPUT
CONFIGURATION Gx/ menu. Every protection element can be assigned a blocking
function: Block.tI>, Block.tI>>, Block.tI>>>, Block.tSOTF, Block.tIN_1, Block.tIN_2,
Block.tIN_3 (E, E+), Block.tIs2>(E, E+), Block.tBrkn Cond (E, E+), Block.Itherm,
Block.AUX1, Block.AUX2, Block.AUX3, Block.CB Fail, Block.[79] (E, E+).
PowerLogic P1F relays have separate blocking functions, which can be used to
block every protection element, for example: Earth fault and phase overcurrent
stages.
Version History
Firmware Date of Manual
Description
version issue Version
2.E.16 First version. V1.0
1. Fix wrong pictogram in cell “Functional Test, setting 0:CB Trips”;
2. Add the .pro files in the release folder;
3. Correct the CB open and close keys;
2.E.17 4. 485 protocol default setting correct, need update the SET file; Nov 25, 2020 V1.1
5. E_U0.epro file update
6. Fix missing event and fault recorder when Vx goes down and return after several seconds;
7. Fix external protection generate maltrip signal for scenario with reverse BI and loss of Vx and return;
2.E.18 1. Fix connection issue to ePro in Chinese module; Jan 07, 2021 V1.2
1. P1F Chinese module been found a connect issue to ePro;
2. Change USB deactivation time from 10mins to 60mins;
3. FCT side change default setting from MODBUS to GETSET;
4. Bug fix: AUX1 trip enabled with delay of 1s, input 1 reversed and assigned to AUX1. In this case AUX is
activated when no signal. With USB connected (AUX logic functions), when Vx power up, the AUX delay
2.E.19 timer is reset and the trip is retook after the timer 1s; Sept 01, 2021 V1.2
5. P1F Chinese issues fix (almost translation error);
6. Bug fix: cannot read anything from 0X3E00H, request to retrieve the oldest non-acknowledge fault record;
7. Bug fix: modify USBport issue;
8. Bug fix: ADDR 3800H, reading 34 bytes will get nothing;
9. Bug fix: Latched RLs are not off when automatically exit maintenance mode;
2.E.20 fix GetSet/IEC103, disable USBPORT and then recycle power, the relay not work Nov 26, 2021 V1.2
1. Easergy -> PowerLogic in OP Parameters in Menu (LCD display);
2. MENU version update frome M_09 to M_0A (this version can't be compatible with version before 2.E.21);
3. Easergy -> PowerLogic in Device Information when using Easergy Pro to connect relay;
4. Fixed operate valid time enlarge from 13s to 90s in keyboard self-test;
5. Change answer ”Easergy” to “PowerLo” when IEC103 protocol asks device info;
2.E.21 6. Bug fix: P1F DR Current info is lost when In(Ien) CTsec=5A and CTprim=1A; Nov 22, 2023 V1.2.0
7. Bug fix: P1F1&P116 DR 2200h need to read 16 words when only 7 is needed
8. Bug fix: P1F Easergy Studio could not poll DR
9. Bug fix: P1F TCS function RL and LED is somehow latched
10. Bug fix: P1 timestamp swapped when read the oldest fault and event
11. Bug fix: P1F1E error trip without origin
1. Add HalfDFT, PO Modbus new feature;
2. Fix CB diagnostic function issue;
2.E.22 3. After password correctly input, menu navigated back to where PASSWORD menu insert; Jan 05, 2024 V1.2.1
4. Add enable soft-switch of the keys O/I on front-panel in menu;
5. Change RI curve TMS setting range to 0.02…10 from 0.1…10, with STEP 0.01;
1. Add control setting to enable or disable half cycle DFT algorithm
2. Bug fix: P1F IN measurement display not accurate when there is 2nd Harmonic wave
2.E.23 Mar 06, 2024 V1.2.1
3. Bug fix: P1F will be locked eternally when wrong password
4. Bug fix: P1F chinese menu display issue on output/password editing
Notes:
Schneider Electric
35 rue Joseph Monier
92506 Rueil-Malmaison FRANCE
Phone: +33 (0) 1 41 29 70 00
Fax: +33 (0) 1 41 29 71 00
www.se.com