Earth Leakage
Earth Leakage
Earth Leakage
Figure 3
In the case of an installation that does not have any leakage current,
the reading should be zero as the currents should cancel each other
out, if any current is leaking to earth, the value will be displayed on
the instrument. If leakage current is identified in the installation, it
will be necessary to isolate and test individual circuits in order to
identify those that are affected.
To determine if the Earth leakage current is within the installation or
from the equipment, it is necessary to isolate current using equipment
from the installation and use the clamp ammeter to test each
individual item separately. Place the clamp around the live
conductors for the installation a shown in Figure 2 for single phase,
or Figure 3 for three phase installations
It could be that the leakage current is returning to Earth directly and
not returning via the earthing conductor. To determine if any leakage
current is returning via fortuitous connections with Earth, the clamp
ammeter can be placed around the line, neutral and protective
conductors as shown in Figure 4.
Figure 4
Insulation resistance vs insulation impedance
It is worth noting that taking a measurement of leakage current and
using the value to carry out an ohms law calculation will provide the
value of insulation impedance. The result will be different from the
value of insulation resistance which is obtained from an isolated
circuit using an insulation resistance tester. The reason being the
insulation resistance tester applies a DC voltage test that does not
take account of the capacitance of the circuit. It is the insulation
impedance value which actually exists under operating conditions.
mA.
Printer - 1 mA
Photocopier - 1.5 mA
metal)
Dishwasher - 5 mA
Washing machine - 5 mA
Tumble dryer – 5 mA
Portable, Class I - 1 mA
Fixed, Class I up to 1 kVA of rated power, Increasing in steps of 1
mA/kVA up to a maximum of 5 mA