Earth Leakage

Download as pdf or txt
Download as pdf or txt
You are on page 1of 11

Earth leakage

By: Michael Peace CEng MIET

How much is too much?

One question being asked in the IET Engineering Communities


Forum is ’Earth Leakage Current – How much is too much?
This question is being asked more often due to the proliferation of
electronic equipment.
What is Earth leakage current?
Earth leakage current is not specifically defined in BS
7671:2018+A1:2020, it is referred to as protective conductor current.
Protective conductor current is defined as an ‘electric current
appearing in a protective conductor, such as leakage current or
electric current resulting from an insulation fault.’
Leakage current is also defined as ‘electric current in an unwanted
conductive path under normal operating conditions.’
Earth leakage current can exist through an insulation fault in cables
or equipment, or it can occur under normal operating conditions in
electronic equipment which use capacitors for filtering purposes in
power supplies which can cause leakage to Earth when functioning.
Hence this type of equipment requires a functional earth, which is
different from a protective earth.
What are the effects of leakage current?
The extract in Figure 1 is taken from the First Edition of the IEE
Wiring Regulations in 1882 and it can be seen that leakage current
was a consideration even back then, although probably for different
reasons. It could be said that the First Edition was more concerned
with waste of energy and heat than electric shock.
‘The difficulties that beset the electrical engineer are chiefly internal
and invisible, and they can only be effectually guarded against by
“testing” or probing with electric currents. They depend chiefly on
leakage, undue resistance in the conductor, and bad joints, which
lead to waste of energy and the production of heat. These defects can
only be detected by measuring, by means of special apparatus, the
currents that are either ordinarily or for the purpose of testing,
passed through the circuit.’
In 1882 unwanted tripping of RCDs would not have been an issue,
today with most circuits requiring RCD protection for one reason or
another, and the proliferation of appliances containing electronic
equipment, unwanted tripping is a real issue.

How can Earth leakage/ protective conductor


currents be measured?
One way of measuring earth leakage is to use a leakage current clamp
ammeter. Leakage current clamp meters are similar to those used for
measuring load current, but are more sensitive and therefore more
accurate at measuring currents below 5 mA.
To determine the Earth leakage on the whole installation, place the
clamp around the live conductors for the installation a shown in
Figure 2 for single phase, or Figure 3 for three phase installations.
Figure 2

Figure 3
In the case of an installation that does not have any leakage current,
the reading should be zero as the currents should cancel each other
out, if any current is leaking to earth, the value will be displayed on
the instrument. If leakage current is identified in the installation, it
will be necessary to isolate and test individual circuits in order to
identify those that are affected.
To determine if the Earth leakage current is within the installation or
from the equipment, it is necessary to isolate current using equipment
from the installation and use the clamp ammeter to test each
individual item separately. Place the clamp around the live
conductors for the installation a shown in Figure 2 for single phase,
or Figure 3 for three phase installations
It could be that the leakage current is returning to Earth directly and
not returning via the earthing conductor. To determine if any leakage
current is returning via fortuitous connections with Earth, the clamp
ammeter can be placed around the line, neutral and protective
conductors as shown in Figure 4.
Figure 4
Insulation resistance vs insulation impedance
It is worth noting that taking a measurement of leakage current and
using the value to carry out an ohms law calculation will provide the
value of insulation impedance. The result will be different from the
value of insulation resistance which is obtained from an isolated
circuit using an insulation resistance tester. The reason being the
insulation resistance tester applies a DC voltage test that does not
take account of the capacitance of the circuit. It is the insulation
impedance value which actually exists under operating conditions.

What about DC leakage current?


Measuring DC with a clamp meter is not as simple as measuring AC.
At present, there are not any clamp ammeters which can measure DC
leakage current to any degree of accuracy.
Residual DC leakage current can cause blinding to AC type RCDs,
see IET Wiring Matters article Which RCD type? for further
information.

What does BS 7671:2018+A1:2020 say about


unwanted tripping?
Regulation 314.1 of BS 7671:2018+A1:2020 requires an installation
to be divided into circuits, as necessary to, ‘reduce the possibility of
unwanted tripping of RCDs due to excessive protective conductor
(PE) currents not due to a fault’.
Regulation 531.3 of BS 7671:2018+A1:2020 provides the
requirements for Residual current devices (RCDs). Regulation
531.3.2 states that residual current protective devices shall be
selected and erected such as to limit the risk of unwanted tripping.
Indent (ii) states that the accumulation of such currents downstream
of the RCD shall be not more than 30 % of the rated residual
operating current. So, assuming we are using an RCD with a rated
operating current of 30 mA, the maximum leakage current is 9 mA.
Note 2 of Regulation 531.3.2 states that RCDs may operate at any
value of residual current in excess of 50 % of the rated residual
current. If unwanted tripping of an RCD protecting several circuits is
experienced, it could be a cumulative effect of the leakage current of
the protected circuits.
Regulation 543.7 recognizes earth leakage currents in excess of 3.5
mA as high protective conductor currents. Specific additional
protective measures are required for circuits considered to have high
protective conductor currents.

Other causes of unwanted tripping


In some cases, unwanted tripping could be caused by RCDs or
RCBOs which are too sensitive, this can be determined with an RCD
ramp test. An RCD with a residual operating current of 30 mA could
trip anywhere between 15 mA and 30 mA, typically it will operate at
75 % of IΔn.

How does current leakage occur within electronic


equipment?
Leakage current in electronic circuits is typically from power
supplies. This is due to the use of capacitors used to filter transients
from the supply. Electrical transients are short bursts of energy with
potential to damage electronic circuits. Figure 5 illustrates the filter
capacitors connection to earth, which is the route for the leakage
current.
Figure 5

What are typical equipment maximum earth


leakage values?
BS EN 60335-1 provides the general safety requirements for
household and similar electrical appliances. Maximum values of
earth leakage for appliances are identified below, it is important to
remember these are maximum values:
 For class II appliances and for parts of class II construction - 0.25

mA.

 For class 0, 0I and III appliances: 0.5 mA b for class I portable

appliances -, 0.75 mA.

 For class I fixed motor-operated appliances - 3.5 mA.

 For class I fixed heating appliances - 0.75 mA or 0.75 mA/kW of

rated power, with a maximum of 5 mA, whichever is the higher.


The amount of leakage current will vary according to the type of
equipment. The IEC 60335 series of Standards provides requirements
for different types of products:
 Fixed PC workstation - 2 mA

 Printer - 1 mA

 Photocopier - 1.5 mA

 Laptop - 0.5 mA (with EMC filter)

 Grills, toasters/portable cooking appliances - 0.75 mA (earthed

metal)

 Fridges - 1.5 mA (class I)

 Dishwasher - 5 mA

 Hobs, ovens - 1 mA or 1 mA/kW of rated power

 Washing machine - 5 mA

 Tumble dryer – 5 mA

 Electric heat pumps - 10 mA (accessible to public)

 Floor heating - 0.75 mA or 0.75 mA/kW of rated power

Luminaires can also be a source of leakage current, BS EN 60598-1


provides the leakage current requirements for Luminaires:
 Continuous interference - 0.5 mA

 Class 0 and Class II -1 mA

 Portable, Class I - 1 mA
 Fixed, Class I up to 1 kVA of rated power, Increasing in steps of 1

mA/kVA up to a maximum of 5 mA

How much leakage current is too much?


To answer the question from the IET Engineering Communities
forum, the amount of leakage current will depend on the arrangement
of the electrical installation and the installed equipment. An
acceptable level of leakage current can be determined by information
from manufacturers of the equipment and protective devices. This
information will allow final circuits to be arranged accordingly.
In order to prevent unwanted operation of earth leakage protective
devices, the installation will need to be designed to take account of
leakage currents. See this Schneider earth fault protection
article for further information.
Summary
Installations incorporating electronic equipment are likely to have
some level of leakage current. A leakage current clamp ammeter is a
useful tool for identifying the source of protective conductor current
within an electrical installation.
Different types of equipment have different levels of permissible
leakage current according to the relevant standards. Manufacturers
information should be used to determine an acceptable level of earth
leakage current for the current using equipment. The installation
should be designed to prevent unwanted operation of earth leakage
protective devices due to the cumulative effects of leakage currents.
It is particularly important to maintain continuity of circuit protective
conductors for circuits with protective conductor currents.

You might also like