CFS61 Controls 4 7 20
CFS61 Controls 4 7 20
Project Location
Project Number
1. CONTROLS
located on the duplex pump set and in the vicinity of the day tanks. All
HMI’s shall use the same hardware and the same screen
configuration. An Operator shall be able to monitor and control any
PLC on that network from any HMI connected to any PLC.
2. Each HMI shall include a time/date stamped Alarm and Event Log for
rapid trouble shooting, verification of filtration cycles, etc.
3. The HMI shall provide remote monitoring capability via a standard
personal computer internet browser remote via the BAS Ethernet
network, with access security provided by BAS network firewalls,
routers, VPN’s, etc.
4. Software features shall include the following: Operator interaction shall
be touch screen-based to allow for easy selection of screens, manual /
automatic status changes, start/stop functions, setpoint changes,
output changes and without any special programming skills. Screen
selection shall also be available through tactile feedback function keys.
The HMI shall provide facsimiles of the local controllers and clearly
labeled English language and engineering unit display of the control
parameters.
5. Where applicable, alarm status shall be displayed on the HMI
generated process pictorials. In addition, all alarms shall be logged in
an alarm and event log. The alarm log shall indicate the time at which
the alarm occurred, the time at which the alarm was acknowledged
and the time at which the value returned to normal status. In addition to
alarm conditions, this log shall also document status changes such as
a transfer from automatic to manual, a setpoint change, etc. so that the
resultant collection of alarms and events is a true and complete log of
plant operating conditions.
6. The HMI shall be manufactured in accordance with UL50, IEC 1010-1
and EN 61010-1: Safety requirements for electrical equipment for
measurement, control, and laboratory use, Part 1.
J. BAS Interfaces: Provide a Building Automation System Protocol Convertor
into the control panel to interface all data from the fuel oil system to a BAS
system as shown on the drawings. A tag list of available data points to be
monitored shall be provided in the O&M Manual. This tag list will provide
description of the data, its format, and its address. Protocol shall be selected
by the BAS vendor and shall be either BACnet/IP or Modbus TCP/IP. BAS
vendor to provide the Ethernet routers, switches, and backbone cabling.
K. Automatic Pump Prime, Suction Line, and Day Tank Level Switches Integrity
Safety Check Test: The control system shall include a battery backed, real
time clock and must be capable of automatically energizing the lead pump
once every day. This safety check is to verify the suction piping integrity,
pump prime, and to verify pump operation including the day tank level
switches operational readiness. Once the lead pump has proven satisfactory
operation, the lag pump shall be energized and run through the same test.
These tests shall be recorded in the controller memory with a Time/Date
April 7, 2020
FUEL OIL SYSTEM 23 XX XX-4 of 5
Project Title CFS-61 Controls
Project Location
Project Number
stamp for later verification or diagnosis. If either lead or lag pump fails any of
these tests, the control system shall generate an audible and visual alarm and
log the “Failed Pump” condition. The day tank return pump(s) shall be
similarly tested whereby each return pump shall be activated and return oil
back to the main tank continuing until the day tank low level switch is
activated. The return pump shall stop and the lead supply pump will restart.
The Supply pump will refill the day tank up to the 90% level, activating that
switch again. The supply pump will shut off and the return pump restart until
the day tank level has dropped to the supply pump-off level. The supply
pump will finally restart and fill the tank back to the pump-off (80%) level and
then stop. This test sequence will demonstrate that not only the supply and
return pumps, but also all level switches in the day tank are functioning
properly. If during this sequence, any pump or level switch shall prove faulty,
the control system shall generate an audible and visual alarm and log such
event as a “failure” condition.
This automatic prime test feature is an option, found on very critical applications.
L. Wiring shall be in accordance with NEC standards, using stranded copper
conductors in liquid tight conduit. Special care shall be taken to ensure the
conduit is not over capacity in accordance with NEC.
M. Approved manufacturers
1. The only manufacturers approved shall be actively involved in the
manufacturing of fuel oil equipment. The equipment shall be a Total
Fuel Management System and manufactured by Critical Fuel Systems,
a division of BFS Industries LLC or approved
April 7, 2020
FUEL OIL SYSTEM 23 XX XX-5 of 5