Electrical Data
Function range (400, 480 V) 0,85 Unom - 1,10 Unom
Operational range at Pnom (400, 480 V) 0,95 Unom - 1,10 Unom
Function range (380 V) 0,90 Unom - 1,10 Unom
Operational range at Pnom (400, 480 V) 1,00 Unom - 1,10 Unom
Withstand 0 - 1,25 Unom
Asymmetry Max. 3% of Unom , phase-phase
Power factor 0,92 (pure sinus)
Maximum interruption of supply volt- 100 ms
age without control system restart
Maximum short-circuit current, Isc, 50 kA
at input connection point
Minimum short-circuit current, Isc, 3 kA
at input connection point
The SIR4 overview with the hood
Maximum protection fuse for feeding 355 A
cable and protection covers removed
Main circuit fuses 125 A (according to IEC 60269-2-1)
Each converter circuit is protected by
IEC standard fuses of 125 A rating,
size 00, operating classification
gG / gL, 500 V
Imagination at work
GE Power Sweden AB
Steam Power Systems
ECS Control Systems
STECCS/2017 sep