IEC61850 in Substation Automation
Exercise4: Process bus, IEEE1588 and VLAN Task
Configure Process Bus between REF615 and REF620
Configure IEEE1588 on switch and IEDs Configure VLANs IEC61850 in Substation Automation Process bus, IEEE1588 and VLAN
Step 1.1 Configure Process Bus from REF615 to REF620
– Open REF615 Application Configuration tool – Add SMSENDER function on Communication tab
– Save and close the tool
IEC61850 in Substation Automation Process bus, IEEE1588 and VLAN
Step 1.2 Configure Process Bus from REF615 to REF620
– Open REF615 IEC61850 Configuration tool – Open Process Bus Communication section
– Assign Process Bus data set to REF620
IEC61850 in Substation Automation Process bus, IEEE1588 and VLAN
Step 1.3 Configure Process Bus from REF615 to REF620
– Go to Sampled Values Controls tab
– Change properties to following from
IP_GOOSE_SV_Settings_SSC600.txt: • MAC Address • VLAN ID – Save and close the tool IEC61850 in Substation Automation Process bus, IEEE1588 and VLAN
Step 1.4 Configure Process Bus from REF615 to REF620
– Open REF620 Application Configuration tool and make following logic on Communication tab
– Assign ULTVTR1_ALARM and ULTVTR1_WARNING variables to LEDs
– Save and close the tool
IEC61850 in Substation Automation Process bus, IEEE1588 and VLAN
Step 1.5 Configure Process Bus from REF615 to REF620
– Open REF615 Parameter Setting tool, locate Time settings and change Synch source parameter to IEEE1588
– Save and close the tool
– Repeat that step for REF620 IEC61850 in Substation Automation Process bus, IEEE1588 and VLAN
Step 1.6 Configure Process Bus from REF615 to REF620
– Write REF615 and REF620 configurations to relays one by one: –
– Make sure that configurations were successfully sent to relays
IEC61850 in Substation Automation Process bus, IEEE1588 and VLAN
Step 3.1 Testing
– Check that Time Sync is OK. – Start the internet browser and write the IP address of the relay to the address field – Login as ADMINISTRATOR (use capital letters). Password is remote0004 – Go to WebHMI settings menu, than go inside Monitoring -> IED status -> Time Synchronization: • Synch source must be IEEE 1588 slave • Synch status must be Up IEC61850 in Substation Automation Process bus, IEEE1588 and VLAN
Step 3.2 Testing
– Open two tabs in IE and in first select REF615 simulator and in another REF620 simulator IEC61850 in Substation Automation Process bus, IEEE1588 and VLAN
Step 3.3 Testing
– In REF615 simulator add some voltage and check in REF620 measurements Voltage is the same – Add some current in REF615 simulator – Using WebHMI check that voltage on REF615 is the same