0% found this document useful (0 votes)
53 views11 pages

IEC61850 - Ex4 - Process Bus and IEEE1588 - Online

a
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
53 views11 pages

IEC61850 - Ex4 - Process Bus and IEEE1588 - Online

a
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 11

IEC61850 in Substation Automation


Exercise4: Process bus, IEEE1588 and VLAN
Task

Configure Process Bus between REF615 and REF620


Configure IEEE1588 on switch and IEDs
Configure VLANs
IEC61850 in Substation Automation
Process bus, IEEE1588 and VLAN

Step 1.1 Configure Process Bus from REF615 to REF620


– Open REF615 Application Configuration tool
– Add SMSENDER function on Communication tab

– Save and close the tool


IEC61850 in Substation Automation
Process bus, IEEE1588 and VLAN

Step 1.2 Configure Process Bus from REF615 to REF620


– Open REF615 IEC61850 Configuration tool
– Open Process Bus Communication section

– Assign Process Bus data set to REF620


IEC61850 in Substation Automation
Process bus, IEEE1588 and VLAN

Step 1.3 Configure Process Bus from REF615 to REF620


– Go to Sampled Values Controls tab

– Change properties to following from


IP_GOOSE_SV_Settings_SSC600.txt:
• MAC Address
• VLAN ID
– Save and close the tool
IEC61850 in Substation Automation
Process bus, IEEE1588 and VLAN

Step 1.4 Configure Process Bus from REF615 to REF620


– Open REF620 Application Configuration tool and make following logic
on Communication tab

– Assign ULTVTR1_ALARM and ULTVTR1_WARNING variables to LEDs

– Save and close the tool


IEC61850 in Substation Automation
Process bus, IEEE1588 and VLAN

Step 1.5 Configure Process Bus from REF615 to REF620


– Open REF615 Parameter Setting tool, locate Time settings and
change Synch source parameter to IEEE1588

– Save and close the tool


– Repeat that step for REF620
IEC61850 in Substation Automation
Process bus, IEEE1588 and VLAN

Step 1.6 Configure Process Bus from REF615 to REF620


– Write REF615 and REF620 configurations to relays one by one:

– Make sure that configurations were successfully sent to relays


IEC61850 in Substation Automation
Process bus, IEEE1588 and VLAN

Step 3.1 Testing


– Check that Time Sync is OK.
– Start the internet browser and write the IP address of the relay to the
address field
– Login as ADMINISTRATOR (use capital letters). Password is
remote0004
– Go to WebHMI settings menu, than go inside Monitoring -> IED
status -> Time Synchronization:
• Synch source must be IEEE 1588 slave
• Synch status must be Up
IEC61850 in Substation Automation
Process bus, IEEE1588 and VLAN

Step 3.2 Testing


– Open two tabs in IE and in first select REF615 simulator and in
another REF620 simulator
IEC61850 in Substation Automation
Process bus, IEEE1588 and VLAN

Step 3.3 Testing


– In REF615 simulator add some voltage and check in REF620
measurements Voltage is the same
– Add some current in REF615 simulator
– Using WebHMI check that voltage on REF615 is the same

You might also like