CHW2204-00-EL-DAS-8301 RevA Data Sheet For Power Distribution Board

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

INVESTMENT OF CORROSION

PROTECTION EQUIPMENT
PROJECT
SHINDONG CONSORTIUM

Doc No.: CHW2204-00-EL-DAS-8301 DATA SHEET FOR POWER DISTRIBUTION


Page 1/12
BOARD
Rev.: A

DATA SHEET FOR POWER DISTRIBUTION BOARD


(Blasting & Painting shop BP-WS-05/06)

VENDOR DOCUMENT REVIEW

1. NO COMENTS

2. MINOR COMENTS

INVESTMENT OF CORROSION
3. MAJOR COMENTS
PROTECTION EQUIPMENT PROJECT
4. INFORMATION ONY

TECHNICAL REQUISITION No.:


REVIEWED BY:
WF2204-BD-ST-TRD-0033-2
PAKAGE: PROCUREMENT OF
EQUIPMENT/SYSTEM FOR TWO (02) BLASTING &
PAINTING WORKSHOP (BP-05/06)
PURCHASE ORDER NO.:
DATE:
79-2023/PTSC-KHDT/HD (BP-05/06)

A 19/05/2023 Issued for Review T.T.H P.T.A N.M.N


REV. DATE PURPOSE PREPARED CHECKED APPROVED
INVESTMENT OF CORROSION
PROTECTION EQUIPMENT
PROJECT
SHINDONG CONSORTIUM

Doc No.: CHW2204-00-EL-DAS-8301 DATA SHEET FOR POWER DISTRIBUTION


Page 2/12
BOARD
Rev.: A

REVISION HISTORY
No Page Content Revision Date Revision No. Note
PROJECT: Investment of Corrosion Protection Equipment Project
Procurement of Equipment/System for two (02) Blasting & Painting
PACKAGE:
Workshops (BP-05/06)
Doc. Title: Data sheet for Power Distribution Board

Doc. No: CHW2204-00-EL-DAS-8301 Rev. A


1 TAG No. JK POWER 1
2 SERVICE Power Distribution
3 LOCATION Blasting & Painting Shop (BP-05/06)
4 AREA CLASSIFICATION Safe area
5 DRAWING REF. CHW2204-00-EL-SLD-8301
GENERAL
6 SPECIFICATION CHW2204-00-EL-SPE-8301
7 AMBIENT TEMPERATURE °C 40 (During 24 hours)
8 DESIGN TEMPERATURE °C 45 (Max); 15 (Min)
9 HUMIDITY Max 90% at 40°C
10 QUANTITY 1
11 ACCORDANCE STD Yes
12 TYPE (FIXED/WITHDRAWABLE) FORM Fixed 2b
13 ENCLOSURE MATERIAL THICKNESS Galvanized Steel (Epoxy Powder Coating) 1.5 mm
14 DIMENSION (WxHxD) mm 1700 x 2000 x 800
15 MOUNTING Floor mounted
16 ACCESS (FRONT/REAR) Front
17 CABLE ENTRY (INCOMING) Bottom And Top
18 CABLE ENTRY (OUTGOING) Bottom And Top
REQUIREMENTS 19 INGRESS PROTECTION IP54 (Outdoor)
20 FINISHING COLOR Mfr'std RAL 7035
21 RATED VOLTAGE FREQUENCY 400V (± 5%), 3 Phase+N+E 50 Hz
22 CABLE/ BUSBAR CONDUCTOR RATING Copper 2500A
23 RATED CURRENT 1611.1A
24 RATED SHORT TIME SHORT CIRCUIT CURRENT 65kA
25 METER (A,V,Hz,KWh, kVAr,…) N/A
26 PHASE INDICATOR (RED/ YELLLOW/ BLUE)
27 EARTH LEAK PROTECTION RATING N/A
28 MAIN COMPONENT BRAND LS
29 INCOMING: TYPE ACB Fixed
RATED VOLTAGE NO OF POLES 400V 3P
RATED CURRENT 2500A
RATED SHORT TIME SHORT CIRCUIT CURRENT 65kA (Min)
According to the design requirements & Type of
MODEL
Manufacturer LS
30 OUT GOING: TYPE Circuit Breaker MCCB
MAIN / SUB
COMPONENTS RATED VOLTAGE NO OF POLES 400V 3P
RATED/SHORT CIRCUIT CURRENT MODEL 60A/(36kA-Min)
80A/(36kA-Min)
According to the design
100A/(36kA-Min)
requirements & Type of
250A/(36kA-Min) Manufacturer LS
600A/(36kA-Min)
800A/(36kA-Min)
31 SUB COMPONENTS Included
32 MANUFACTURER Viet Nam
33 CERTIFICATE/TEST REPORT FAT test report
Notes: VTA: Vendor to Advise TBA: To be Available N/A: not Applicable
Mfr'std : Manufacturer standard (*) At actual condition
1. Name plate shall be traffolyte, black letter with white background
2. Cable and busbar must be color code. Color code must be follows:
Ph. 1: Brown (Bn) Ph 2: Black (Bk) Ph. 3: Grey (Gy)
Neutral: Blue (Bu) Earth: Green/ Yellow

Page 3/12
PROJECT: Investment of Corrosion Protection Equipment Project
Procurement of Equipment/System for two (02) Blasting & Painting
PACKAGE:
Workshops (BP-05/06)
Doc. Title: Data sheet for Power Distribution Board

Doc. No: CHW2204-00-EL-DAS-8301 Rev. A


3. Internal wiring will be copper conductor, single core, multi-stranded cable with 600/1000V insulation.
Minimum stranded conductor cross-sectional area size will be:
+ Electrical instruments: 1.5mm2
+ Lighting, small power and control: 1.5mm2
+ Motor control circuit, if applicable: 2.5mm2

Page 4/12
PROJECT: Investment of Corrosion Protection Equipment Project
Procurement of Equipment/System for two (02) Blasting & Painting
PACKAGE:
Workshops (BP-05/06)
Doc. Title: Data sheet for Power Distribution Board

Doc. No: CHW2204-00-EL-DAS-8301 Rev. A


1 TAG No. JK POWER 2
2 SERVICE Power Distribution
3 LOCATION Blasting & Painting Shop (BP-05/06)
4 AREA CLASSIFICATION Safe area
5 DRAWING REF. CHW2204-00-EL-SLD-8301
GENERAL
6 SPECIFICATION CHW2204-00-EL-SPE-8301
7 AMBIENT TEMPERATURE °C 40 (During 24 hours)
8 DESIGN TEMPERATURE °C 45 (Max); 15 (Min)
9 HUMIDITY Max 90% at 40°C
10 QUANTITY 1
11 ACCORDANCE STD Yes
12 TYPE (FIXED/WITHDRAWABLE) FORM Fixed 2b
13 ENCLOSURE MATERIAL THICKNESS Galvanized Steel (Epoxy Powder Coating) 1.5 mm
14 DIMENSION (WxHxD) mm 1700 x 2000 x 800
15 MOUNTING Floor mounted
16 ACCESS (FRONT/REAR) Front
17 CABLE ENTRY (INCOMING) Bottom And Top
18 CABLE ENTRY (OUTGOING) Bottom And Top
REQUIREMENTS 19 INGRESS PROTECTION IP54 (Outdoor)
20 FINISHING COLOR Mfr'std RAL 7035
21 RATED VOLTAGE FREQUENCY 400V (± 5%), 3 Phase+N+E 50 Hz
22 CABLE/ BUSBAR CONDUCTOR RATING Copper 2000A
23 RATED CURRENT 1392.4A
24 RATED SHORT TIME SHORT CIRCUIT CURRENT 65kA
25 METER (A,V,Hz,KWh, kVAr,…) N/A
26 PHASE INDICATOR (RED/ YELLLOW/ BLUE)
27 EARTH LEAK PROTECTION RATING N/A
28 MAIN COMPONENT BRAND LS
29 INCOMING: TYPE ACB Fixed
RATED VOLTAGE NO OF POLES 400V 3P
RATED CURRENT 2000A
RATED SHORT TIME SHORT CIRCUIT CURRENT 65kA (Min)
According to the design requirements & Type of
MODEL
MAIN / SUB Manufacturer LS
COMPONENTS 30 OUT GOING: TYPE Circuit Breaker MCCB
RATED VOLTAGE NO OF POLES 400V 3P
RATED/SHORT CIRCUIT CURRENT MODEL 60A/(36kA-Min)
According to the design
100A/(36kA-Min)
requirements & Type of
600A/(36kA-Min) Manufacturer LS
800A/(36kA-Min)
31 SUB COMPONENTS Included
32 MANUFACTURER Viet Nam
33 CERTIFICATE/TEST REPORT FAT test report
Notes: VTA: Vendor to Advise TBA: To be Available N/A: not Applicable
Mfr'std : Manufacturer standard (*) At actual condition
1. Name plate shall be traffolyte, black letter with white background
2. Cable and busbar must be color code. Color code must be follows:
Ph. 1: Brown (Bn) Ph 2: Black (Bk) Ph. 3: Grey (Gy)
Neutral: Blue (Bu) Earth: Green/ Yellow

Page 5/12
PROJECT: Investment of Corrosion Protection Equipment Project
Procurement of Equipment/System for two (02) Blasting & Painting
PACKAGE:
Workshops (BP-05/06)
Doc. Title: Data sheet for Power Distribution Board

Doc. No: CHW2204-00-EL-DAS-8301 Rev. A


3. Internal wiring will be copper conductor, single core, multi-stranded cable with 600/1000V insulation.
Minimum stranded conductor cross-sectional area size will be:
+ Electrical instruments: 1.5mm2
+ Lighting, small power and control: 1.5mm2
+ Motor control circuit, if applicable: 2.5mm2

Page 6/12
PROJECT: Investment of Corrosion Protection Equipment Project
Procurement of Equipment/System for two (02) Blasting & Painting
PACKAGE:
Workshops (BP-05/06)
Doc. Title: Data sheet for Power Distribution Board

Doc. No: CHW2204-00-EL-DAS-8301 Rev. A


1 TAG No. JK POWER 3
2 SERVICE Power Distribution
3 LOCATION Blasting & Painting Shop (BP-05/06)
4 AREA CLASSIFICATION Safe area
5 DRAWING REF. CHW2204-00-EL-SLD-8301
GENERAL
6 SPECIFICATION CHW2204-00-EL-SPE-8301
7 AMBIENT TEMPERATURE °C 40 (During 24 hours)
8 DESIGN TEMPERATURE °C 45 (Max); 15 (Min)
9 HUMIDITY Max 90% at 40°C
10 QUANTITY 1
11 ACCORDANCE STD Yes
12 TYPE (FIXED/WITHDRAWABLE) FORM Fixed 2b
13 ENCLOSURE MATERIAL THICKNESS Galvanized Steel (Epoxy Powder Coating) 1.5 mm
14 DIMENSION (WxHxD) mm 1700 x 2000 x 800
15 MOUNTING Floor mounted
16 ACCESS (FRONT/REAR) Front
17 CABLE ENTRY (INCOMING) Bottom And Top
18 CABLE ENTRY (OUTGOING) Bottom And Top
REQUIREMENTS 19 INGRESS PROTECTION IP54 (Outdoor)
20 FINISHING COLOR Mfr'std RAL 7035
21 RATED VOLTAGE FREQUENCY 400V (± 5%), 3 Phase+N+E 50 Hz
22 CABLE/ BUSBAR CONDUCTOR RATING Copper 2000A
23 RATED CURRENT 1467A
24 RATED SHORT TIME SHORT CIRCUIT CURRENT 65kA
25 METER (A,V,Hz,KWh, kVAr,…) N/A
26 PHASE INDICATOR (RED/ YELLLOW/ BLUE)
27 EARTH LEAK PROTECTION RATING N/A
28 MAIN COMPONENT BRAND LS
29 INCOMING: TYPE ACB Fixed
RATED VOLTAGE NO OF POLES 400V 3P
RATED CURRENT 2000A
RATED SHORT TIME SHORT CIRCUIT CURRENT 65kA (Min)
According to the design requirements & Type of
MODEL
Manufacturer LS
MAIN / SUB 30 OUT GOING: TYPE Circuit Breaker MCCB
COMPONENTS 3P
RATED VOLTAGE NO OF POLES 400V
RATED/SHORT CIRCUIT CURRENT MODEL 40A/(36kA-Min)
100A/(36kA-Min) According to the design
250A/(36kA-Min) requirements & Type of
350A/(36kA-Min) Manufacturer LS

500A/(36kA-Min)
31 SUB COMPONENTS Included
32 MANUFACTURER Viet Nam
33 CERTIFICATE/TEST REPORT FAT test report
Notes: VTA: Vendor to Advise TBA: To be Available N/A: not Applicable
Mfr'std : Manufacturer standard (*) At actual condition
1. Name plate shall be traffolyte, black letter with white background
2. Cable and busbar must be color code. Color code must be follows:
Ph. 1: Brown (Bn) Ph 2: Black (Bk) Ph. 3: Grey (Gy)
Neutral: Blue (Bu) Earth: Green/ Yellow

Page 7/12
PROJECT: Investment of Corrosion Protection Equipment Project
Procurement of Equipment/System for two (02) Blasting & Painting
PACKAGE:
Workshops (BP-05/06)
Doc. Title: Data sheet for Power Distribution Board

Doc. No: CHW2204-00-EL-DAS-8301 Rev. A


3. Internal wiring will be copper conductor, single core, multi-stranded cable with 600/1000V insulation.
Minimum stranded conductor cross-sectional area size will be:
+ Electrical instruments: 1.5mm2
+ Lighting, small power and control: 1.5mm2
+ Motor control circuit, if applicable: 2.5mm2

Page 8/12
PROJECT: Investment of Corrosion Protection Equipment Project
Procurement of Equipment/System for two (02) Blasting & Painting
PACKAGE:
Workshops (BP-05/06)
Doc. Title: Data sheet for Power Distribution Board

Doc. No: CHW2204-00-EL-DAS-8301 Rev. A


1 TAG No. JK POWER 4
2 SERVICE Power Distribution
3 LOCATION Blasting & Painting Shop (BP-05/06)
4 AREA CLASSIFICATION Safe area
5 DRAWING REF. CHW2204-00-EL-SLD-8301
GENERAL
6 SPECIFICATION CHW2204-00-EL-SPE-8301
7 AMBIENT TEMPERATURE °C 40 (During 24 hours)
8 DESIGN TEMPERATURE °C 45 (Max); 15 (Min)
9 HUMIDITY Max 90% at 40°C
10 QUANTITY 1
11 ACCORDANCE STD Yes
12 TYPE (FIXED/WITHDRAWABLE) FORM Fixed 2b
13 ENCLOSURE MATERIAL THICKNESS Galvanized Steel (Epoxy Powder Coating) 1.5 mm
14 DIMENSION (WxHxD) mm 1700 x 2000 x 800
15 MOUNTING Floor mounted
16 ACCESS (FRONT/REAR) Front
17 CABLE ENTRY (INCOMING) Bottom And Top
18 CABLE ENTRY (OUTGOING) Bottom And Top
REQUIREMENTS 19 INGRESS PROTECTION IP54 (Outdoor)
20 FINISHING COLOR Mfr'std RAL 7035
21 RATED VOLTAGE FREQUENCY 400V (± 5%), 3 Phase+N+E 50 Hz
22 CABLE/ BUSBAR CONDUCTOR RATING Copper 2000A
23 RATED CURRENT 1439.1A
24 RATED SHORT TIME SHORT CIRCUIT CURRENT 65kA
25 METER (A,V,Hz,KWh, kVAr,…) N/A
26 PHASE INDICATOR (RED/ YELLLOW/ BLUE)
27 EARTH LEAK PROTECTION RATING N/A
28 MAIN COMPONENT BRAND LS
29 INCOMING: TYPE ACB Fixed
RATED VOLTAGE NO OF POLES 400V 3P
RATED CURRENT 2000A
RATED SHORT TIME SHORT CIRCUIT CURRENT 65kA (Min)
According to the design requirements & Type of
MODEL
Manufacturer LS
MAIN / SUB 30 OUT GOING: TYPE Circuit Breaker MCCB
COMPONENTS 3P
RATED VOLTAGE NO OF POLES 400V
RATED/SHORT CIRCUIT CURRENT MODEL 40A/(36kA-Min)
100A/(36kA-Min) According to the design
250A/(36kA-Min) requirements & Type of
350A/(36kA-Min) Manufacturer LS

500A/(36kA-Min)
31 SUB COMPONENTS Included
32 MANUFACTURER Viet Nam
33 CERTIFICATE/TEST REPORT FAT test report
Notes: VTA: Vendor to Advise TBA: To be Available N/A: not Applicable
Mfr'std : Manufacturer standard (*) At actual condition
1. Name plate shall be traffolyte, black letter with white background
2. Cable and busbar must be color code. Color code must be follows:
Ph. 1: Brown (Bn) Ph 2: Black (Bk) Ph. 3: Grey (Gy)
Neutral: Blue (Bu) Earth: Green/ Yellow

Page 9/12
PROJECT: Investment of Corrosion Protection Equipment Project
Procurement of Equipment/System for two (02) Blasting & Painting
PACKAGE:
Workshops (BP-05/06)
Doc. Title: Data sheet for Power Distribution Board

Doc. No: CHW2204-00-EL-DAS-8301 Rev. A


3. Internal wiring will be copper conductor, single core, multi-stranded cable with 600/1000V insulation.
Minimum stranded conductor cross-sectional area size will be:
+ Electrical instruments: 1.5mm2
+ Lighting, small power and control: 1.5mm2
+ Motor control circuit, if applicable: 2.5mm2

Page 10/12
PROJECT: Investment of Corrosion Protection Equipment Project
Procurement of Equipment/System for two (02) Blasting & Painting
PACKAGE:
Workshops (BP-05/06)
Doc. Title: Data sheet for Power Distribution Board

Doc. No: CHW2204-00-EL-DAS-8301 Rev. A


1 TAG No. JK-LP1
2 SERVICE Power Distribution
3 LOCATION Blasting & Painting Shop (BP-05/06)
4 AREA CLASSIFICATION Safe area
5 DRAWING REF. CHW2204-00-EL-SLD-8301
GENERAL
6 SPECIFICATION CHW2204-00-EL-SPE-8301
7 AMBIENT TEMPERATURE °C 40 (During 24 hours)
8 DESIGN TEMPERATURE °C 45 (Max); 15 (Min)
9 HUMIDITY Max 90% at 40°C
10 QUANTITY 1
11 ACCORDANCE STD Yes
12 TYPE (FIXED/WITHDRAWABLE) FORM Fixed 2b
13 ENCLOSURE MATERIAL THICKNESS Galvanized Steel (Epoxy Powder Coating) 1.5 mm
14 DIMENSION (WxHxD) mm 800 x 500 x 300
15 MOUNTING Wall mounted
16 ACCESS (FRONT/REAR) Front
17 CABLE ENTRY (INCOMING) Bottom
18 CABLE ENTRY (OUTGOING) Bottom
REQUIREMENTS 19 INGRESS PROTECTION IP54 (Outdoor)
20 FINISHING COLOR Mfr'std White Background
21 RATED VOLTAGE FREQUENCY 400V (± 5%), 3 Phase+N+E 50 Hz
22 CABLE/ BUSBAR CONDUCTOR RATING Copper 80A
23 RATED CURRENT 42.4A
24 RATED SHORT TIME SHORT CIRCUIT CURRENT 36kA
25 METER (A,V,Hz,KWh, kVAr,…) N/A
26 PHASE INDICATOR (RED/ YELLLOW/ BLUE)
27 EARTH LEAK PROTECTION RATING N/A
28 MAIN COMPONENT BRAND LS
29 INCOMING: TYPE MCCB Fixed
RATED VOLTAGE NO OF POLES 400V 3P
RATED CURRENT 80A
RATED SHORT TIME SHORT CIRCUIT CURRENT 36kA (Min)
MAIN / SUB According to the design requirements & Type of
MODEL
COMPONENTS Manufacturer LS
30 OUT GOING: TYPE Circuit Breaker MCCB
RATED VOLTAGE NO OF POLES 400V 3P
According to the design
RATED/SHORT CIRCUIT CURRENT MODEL 20A/(18kA-Min) requirements & Type of
Manufacturer LS
31 SUB COMPONENTS Included
32 MANUFACTURER Viet Nam
33 CERTIFICATE/TEST REPORT FAT test report
Notes: VTA: Vendor to Advise TBA: To be Available N/A: not Applicable
Mfr'std : Manufacturer standard (*) At actual condition
1. Name plate shall be traffolyte, black letter with white background
2. Cable and busbar must be color code. Color code must be follows:
Ph. 1: Brown (Bn) Ph 2: Black (Bk) Ph. 3: Grey (Gy)
Neutral: Blue (Bu) Earth: Green/ Yellow
3. Internal wiring will be copper conductor, single core, multi-stranded cable with 600/1000V insulation.
Minimum stranded conductor cross-sectional area size will be:
+ Electrical instruments: 1.5mm2
+ Lighting, small power and control: 1.5mm2
+ Motor control circuit, if applicable: 2.5mm2

Page 11/12
PROJECT: Investment of Corrosion Protection Equipment Project
Procurement of Equipment/System for two (02) Blasting & Painting
PACKAGE:
Workshops (BP-05/06)
Doc. Title: Data sheet for Power Distribution Board

Doc. No: CHW2204-00-EL-DAS-8301 Rev. A


1 TAG No. JK-LP2
2 SERVICE Power Distribution
3 LOCATION Blasting & Painting Shop (BP-05/06)
4 AREA CLASSIFICATION Safe area
5 DRAWING REF. CHW2204-00-EL-SLD-8301
GENERAL
6 SPECIFICATION CHW2204-00-EL-SPE-8301
7 AMBIENT TEMPERATURE °C 40 (During 24 hours)
8 DESIGN TEMPERATURE °C 45 (Max); 15 (Min)
9 HUMIDITY Max 90% at 40°C
10 QUANTITY 1
11 ACCORDANCE STD Yes
12 TYPE (FIXED/WITHDRAWABLE) FORM Fixed 2b
13 ENCLOSURE MATERIAL THICKNESS Galvanized Steel (Epoxy Powder Coating) 1.5 mm
14 DIMENSION (WxHxD) mm 800 x 500 x 300
15 MOUNTING Wall mounted
16 ACCESS (FRONT/REAR) Front
17 CABLE ENTRY (INCOMING) Bottom
18 CABLE ENTRY (OUTGOING) Bottom
REQUIREMENTS 19 INGRESS PROTECTION IP54 (Outdoor)
20 FINISHING COLOR Mfr'std White Background
21 RATED VOLTAGE FREQUENCY 400V (± 5%), 3 Phase+N+E 50 Hz
22 CABLE/ BUSBAR CONDUCTOR RATING Copper 100A
23 RATED CURRENT 56A
24 RATED SHORT TIME SHORT CIRCUIT CURRENT 36kA
25 METER (A,V,Hz,KWh, kVAr,…) N/A
26 PHASE INDICATOR (RED/ YELLLOW/ BLUE)
27 EARTH LEAK PROTECTION RATING N/A
28 MAIN COMPONENT BRAND LS
29 INCOMING: TYPE MCCB Fixed
RATED VOLTAGE NO OF POLES 400V 3P
RATED CURRENT 100A
RATED SHORT TIME SHORT CIRCUIT CURRENT 36kA (Min)
MAIN / SUB According to the design requirements & Type of
MODEL
COMPONENTS Manufacturer LS
30 OUT GOING: TYPE Circuit Breaker MCCB
RATED VOLTAGE NO OF POLES 400V 3P
According to the design
RATED/SHORT CIRCUIT CURRENT MODEL 20A/(18kA-Min) requirements & Type of
Manufacturer LS
31 SUB COMPONENTS Included
32 MANUFACTURER Viet Nam
33 CERTIFICATE/TEST REPORT FAT test report
Notes: VTA: Vendor to Advise TBA: To be Available N/A: not Applicable
Mfr'std : Manufacturer standard (*) At actual condition
1. Name plate shall be traffolyte, black letter with white background
2. Cable and busbar must be color code. Color code must be follows:
Ph. 1: Brown (Bn) Ph 2: Black (Bk) Ph. 3: Grey (Gy)
Neutral: Blue (Bu) Earth: Green/ Yellow
3. Internal wiring will be copper conductor, single core, multi-stranded cable with 600/1000V insulation.
Minimum stranded conductor cross-sectional area size will be:
+ Electrical instruments: 1.5mm2
+ Lighting, small power and control: 1.5mm2
+ Motor control circuit, if applicable: 2.5mm2

Page 12/12