CHW2204-00-EL-ITR-7301 RevA Factory AcceptanceTest Reports and Certificates For ACB

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

TEMPORARY PRE-FAB WORKSHOPS

FOR RENEWABLE ENERGY PROJECT

Doc No.: Factory AcceptanceTest Reports and Certificates


CHW2204-00-EL-IRT-7301 for ACB Page 1 of 8
Rev. A

FACTORY ACCEPTANCE REPORT AND CERTIFICATE


FOR ACB

VENDOR DOCUMENT REVIEW

1 NO COMMENTS
PROJ. TEMPORARY PRE-FAB WORKSHOPS FOR RENEWABLE
2 MINOR COMMENTS
ENERGY PROJECT
3 MAJOR COMMENTS

TECHNICAL REQUISITION No. 4 INFORMATION ONLY


WF2204-BD-ST-TRD-0033-01

Procurement of Equipment/ Systems for four (4) Blasting REVIEWED BY:


& Painting Workshops (BP-01/02/03/04)

PURCHASE ORDER NO. 78-023/PTSC-KHDT/HD DATE:

A 2-6-2023 Issued for Review T.T.H P.T.A N.M.N


REV. DATE PURPOSE PREPARATION REVIEW APPROVAL
TEMPORARY PRE-FAB WORKSHOPS
FOR RENEWABLE ENERGY PROJECT

Doc No.: Factory AcceptanceTest Reports and Certificates


CHW2204-00-EL-IRT-7301 for ACB Page 2 of 8
Rev. A

REVISION HISTORY

Revision
No Page Content Revision Date No. Note
Ratings

Circuit Breaker

Type AN-06D AN-08D AN-10D AN-13D AN-16D


Ampere frame (AF) 630 800 1000 1250 1600
200 400
Rated current (A) (In max) at 40℃ 400 630 1000 1250 1600
630 800
Setting current (A)* Control trip relay ( ... × In max) 0.4 ~ 1.0
Rated current of neutral pole (A) 400
400
630 1000 1250 1600
630
800
Rated insulation voltage (V) (Ui) 1,000
Rated operational voltage (V) (Ue) 690
Rated impulse withstand voltage (kV) (Uimp) 12
Frequency (Hz) 50/60
Number of poles (P) 3/4
Rated breaking capacity (kA sym) 220V/230V/380V/415V 65
IEC 60947-2
AC 50/60Hz (Icu) 460V/480V/500V 65
KS C 4620
550V/600V/690V 50
Rated service breaking capacity (kA) (Ics) ... %×Icu 100%
Rated making capacity (kA peak) 220V/230V/380V/415V 143
IEC 60947-2
AC 50/60Hz (Icm) 460V/480V/500V 143
KS C 4620
550V/600V/690V 105
Rated short-time 1 sec 50
withstand current (kA) (Icw) 2 sec 42
3 sec 36
Operating time (ms) Maximum total breaking time 40
Maximum closing time 80
Life cycle (time) Mechanical 20,000
Electrical 5,000
Connections** Draw-out / Fixed Horizontal connection 
Vertical connection 
Front connection 
Mixed connection 
Weight (kg) Draw-out type Main body Motor charging type 63/74
(3P/4P) (With cradle) Manual charging type 61/72
Cradle only 29/32
Fixed type Motor charging type 34/44
Manual charging type 32/42
External dimensions (mm) Draw-out 3P 430×334×375
(H×W×D) type 4P 430×419×375
H

D
Fixed type 3P 300×300×295
W
4P 300×385×295
Trip relay N, A, P type
Certificate & Approval KS / KEMA / KERI / GOST
Marine clasiflcation -
* Refer to trip relay specification. ** : Standard, ◯: Option
Note) 1. Life time means not guarantee, but limitation.
Quality guarantee: On/Off frequency on the basis of IEC60947-2 within the term of guarantee
2. The use of AN-D, AS-D and AS-F in IT systems is limited to 500 V network voltage.
3. AS-20D, AS-40E types are equipped with vertical-only terminals.

38
AS-06D AS-08D AS-10D AS-13D AS-16D AS-20D AS-20E AS-25E AS-32E AS-40E AS-40F AS-50F AS-40G AS-50G AS-63G
630 800 1000 1250 1600 2000 2000 2500 3200 4000 4000 5000 4000 5000 6300
200 400 400, 630,
400 630 1000 1250 1600 2000 800, 1000, 2500 3200 4000 4000 5000 4000 5000 6300
1250, 1600,
630 800 2000
0.4 ~ 1.0 0.4 ~ 1.0 0.4 ~ 1.0 0.4 ~ 1.0
630, 800,
630 800 1000 1250 1600 2000 1000, 1250, 2500 3200 4000 4000 5000 4000 5000 6300
1600, 2000
1,000 1,000 1,000 1,000
690 690 690 690
12 12 12 12
50/60 50/60 50/60 50/60
3/4 3/4 3/4 3/4
70 85 100 120
70 85 100 120
65 85 85 100
100% 100% 100% 100%
154 187 220 264
154 187 220 264
143 187 187 220
65 85 85 100
50 75 75 85
42 65 65 75
40 40 40 40
80 80 80 80
20,000 15,000 10,000 10,000
5,000 5,000 2,000 2,000
 -  -  
     
 -  - - -
 -  - - -
63/74 70/85 87/103 104/147 107/139 181/223 186/230
61/72 63/83 85/101 102/145 102/145 179/221 184/228
29/32 33/40 44/50 58/70 65/85 97/117 102/124
34/44 38/47 44/55 63/100 61/81 98/123 103/130
32/42 36/45 42/53 61/98 60/80 96/121 101/128
430×334×375 430×412×375 460×629×375 460×785×375
430×419×375 430×527×375 460×799×375 460×1015×375
300×300×295 300×378×295 300×597×295 300×751×295
300×385×295 300×493×295 300×767×295 300×981×295
N, A, P type N, A, P type N, A, P type N, A, P type
KS / KEMA / KERI / GOST KS / KEMA / KERI / GOST KS / KEMA / KERI / GOST
LR, ABS, DNV, KR, BV, GL, RINA, NK LR, ABS, DNV, KR, BV, GL, RINA, NK LR, ABS, DNV, KR, BV, GL, RINA, NK

※ Derating of the rated current is required according to the ambient temperature around the breaker in a panel if it is higher than
the reference value. (See pages 123 to 126)
※ It is possible to connect power and load side reversely, but please use it for normal connection for maintenance and safety.

I 39