P-T3109-EI-026 (Generator Leak Test)
P-T3109-EI-026 (Generator Leak Test)
P-T3109-EI-026 (Generator Leak Test)
DOCUMENT NO : P-T3109-EI-026
- SDCC : Original
- All Div : Copy
- All Dept : Copy
- CNEEC : Copy
B. Winarko Iman. P Agus S - PLN : Copy
REV.
ISSUED DATE EFFECTIVE DATE BRIEF OF REVISION
NO
00 26 May 2009 26 May 2009
INDRAMAYU SPP PROJECT
SCP-JO DOC. No : P-T3109-EI-026
TEST PROCEDURE
GENERATOR LEAK TEST REV. No : 00
TABLE OF CONTENT
COVER 1
1 TABLE CONTENT 2
2 PREFACE 3
3 REFERENCE DOCUMENT 3
4 EQUIPMENT TO BE USED 3
5 PREPARATION WORKS 3
6 TEST 4
8 SAFETY MEASURES 6
9 ATTACHMENT 6
INDRAMAYU SPP PROJECT
SCP-JO DOC. No : P-T3109-EI-026
TEST PROCEDURE
GENERATOR LEAK TEST REV. No : 00
1. PREFACE
This procedure is guidance for site test and commissioning of Generator and
to assure that the requirements of leak test are meets the codes
requirements and contract specifications
2. REFERENCE DOCUMENTS
3. EQUIPMENT TO BE USED
3.1 N2 Tank.
3.2 Pressure Gauge
3.3 Hand Tools
3.4 Detector
3.5 Radio Communicator (HT)
4. PREPARATION WORKS
4.1 All necessary precautions shall be taken before, during and after test.
4.2 Gas such as nitrogen or air shall be applied.
4.3 Check of pressure gauge indicator on generator showing 0 MPa
4.4 Checking all of tightness of generator like joints, seal, pipe connection
etc are operating correctly.
4.5 This test can be carried out simultaneously with test for corresponding
equipment.
5. TEST
5.6 When the pressure exceeds the pressure allowed by the pressure
gauge, seat it as allowable by the measuring instrument
5.7 Keep the pressure until 24 hours
5.8 Check leakage on connected sections with soapy water with the
pressure as table below
5.9 If the fall in pressure is more than 0.04 MPa in 24 hours, fill generator
with N2 and try and locate the leakage
5.10 As soon as the leak has been identified, ensure that’s its repairs
should be done and the leak test shall be started up again when the
nitrogen tightness is correct.
5.11 Recheck all connected, welding, hose, seal etc after 24 hours, if all
condition good that leak test meaning already done.
5.12 The single line diagram of generator leak test as per drawing
showing.
INDRAMAYU SPP PROJECT
SCP-JO DOC. No : P-T3109-EI-026
TEST PROCEDURE
GENERATOR LEAK TEST REV. No : 00
5. SAFETY MEASURES
6.1. Only persons qualified by training and familiar with Leak test involved
and lead by field engineer
6.2. Be sure that the safety equipment shall be used during test and use
safety barrier for personal isolation
6.3. The output of this N2 tank is high pressure, Ensure that tool and
equipment test are required
6.4. Worker should be used PPE (helm, safety belt etc)
6. ATTACHMENT