Basically, we recommend that you always use the original project instead of
a station upload, as a station upload cannot read all the files back.
13:136 The maximum possible number of slots within all More slaves have been configured than permitted by the master system Split the slaves across different segments if possible or reduce the number
inserted slaves has been exceeded by %1 slot(s)." of slaves for the master system concerned.
13:181 Internal error:Multicomputig cannot have the type Error in HW Config of first 4.02.x version Add another CPU and then deleted it. The CPU is then automatically set to
"inhomogenous" single-computing again
13:422 No master system is assigned to the DP slave. Missing object Right-click for pop-up menu, select "Add master system" and then configure
the CP again as slave
13:520 The address entered is already occupied. STEP 7 Confirm the address suggested by STEP 7 or enter a new address.
has already calculated the next free address.
13:4003 Module cannot be inserted here. You can use only An attempt was made to connect a device directly to the DP bus, which In the HW catalog insert a hierarchy level for this device as DP slave
DP slaves in a master system. does not have its own interface.
13:4040 The number of slots of the CPU or the master Maximum number of modules already configured. New modules can only be slotted after deleting slaves or their modules.
system has been exceeded or exhausted.
30:504 There are no parameter and local variable names The description of the parameter and local variable names has a different This conflict first arises when you open a block and interface changes made
available because there is a time stamp conflict time stamp to the interface of the opened block. This is why the online have not been stored in the S7 user program offline and now the
between the interface of the block and the parameters and local variables are displayed as pseudosymbols without online block is being opened.
description of the parameter and local variable comments. Interface changes made offline have not been loaded into the CPU and now
names. the online block is being opened.
The interface of a function block or UDT has been changed and now the
associated instance data block or the data block derived from the UDT is
being opened.
An online block that already has a time stamp conflict is copied offline into
the S7 user program and now the offline block is being opened.
The cause for this can be an actual hardware fault, or an interrupt conflict In this case the customer can check whether the MPI LED lights on the
with another module. CP5611 during this time.
- If the LED does not light, the module could be defective or there is an
address conflict on the PCI bus (though unlikely).
- If the LED lights, then there is an interrupt conflict.
- NT Diagnostics ->Resources.
- Warning: with some modules you have to switch the computer off/on
after BIOS changes.
A possible remedy could also be to plug the CP5611 into a different PCI
slot.
30:53 Problems occurred during the automatic There are protected blocks in the selection list of the STL source to be Remake the selection list, but without the protected blocks. Press the Details
generation of STL sources. See Details! generated. button in the error message to obtain a Detailed List of the protected blocks.
The block is available online in the automation system, but not offline in
the S7 user program.
The block has been copied from the automation system into an S7 user
program and now this S7 user program is to be opened where it did not
exist before.
A block is opened via "Available Users". In this case there is no S7 user
program linked with the automation system.
The associated function block of an instance data block to be opened
does not exist.
32:282 PG Resourcen Error, by program status of a longer In Step7 V5.0 SP2 with PLCSIM V4.0 under NT, project and block were In Step7 V5.0 SP2 with PLCSIM V4.0 do not open the project online, but
FB in PLCSIM opened online. This probably led to high internal use of resources. select the status function from the offline project. Setting the virtual memory
to 256MB does not help
33:11
33:384 The triggered action cannot be executed at this The communications module is probably already being operated with Please check the baud rate on the PG/PC via "Set PG/PC interface" and the
time. Check all other STEP 7 applications and exit other settings (e.g. with a different transmission rate). baud rate of the CPU configured.
them where necessary.
There might be other online functions active. Close any other active online functions (e.g. by closing the relevant
windows) and try again.
Attempt to run the firmware update of a CPU directly via STEP 7 on a Firmware update is only possible via flash card.
CPU.
33:496 The called function is not available in S7-DOS or in Deinstallation and reinstallation of STEP7
the CPU.
33:498 Internal error: Function '%1' not implemented. Delete metafiles
33:501 System error! Attempt to get online as normal user under WinNT.
33:511 System error! Mixed installation Manual deinstallation of STEP 7 and S7 options packages
NT: insufficient access rights. You must have at least main user access rights!
NT: main user access rights already assigned! Check that the domain user with the main user rights has also been
transferred into the Main User group on the local computer.
EPROM: Memory card is missing
Bus monitor Amprolyzer has been installed. Manual deinstallation of STEP 7 and S7 options packages according to
FAQ.
30:527 The interface of the multi instance call can only be If you click "Yes" in the dialog box, the system corrects the corresponding In case it is impossible to acknowledge the dialog box with "Yes" and, hence
updated, if the declaration of the multi instance is entry in the detailed variable view for you. to have the corresponding entry corrected by the system in the tag detail
valid in the tag declaration table. view, verify the system date of your PC. The system date of your PC has to
be set to the current date.
If you want to carry out the necessery changes yourself, proceed as follows:
1. Click "No" in the dialog box.
2. Eliminate the invalid multiple instance declaration by highlighting the
relevant line in the detailed variable view and selecting the pop-up context
menu command "Update Declarations".
3. Position the cursor on the block call in the code section and repeat the
function.
33:3100 When you have set the option "PG/PC is the only master on the bus" in
the dialog by "Set PG/PC Interface" and you will make an online
connection by "Display Accessible Notes" to the CP5412 A2, so you will
receive this error number if not a partner is connected on this modul.
33:8242 The EPROM driver cannot support the set PC + external prommer. Cause of error not yet known: probably a setup Under
programming interface on this computer problem where the Registry entries are not checked. HKEY_LOCAL_MACHINE\SOFTWARE\SIEMENS\SINEC\LOGDEVICES
there exist the directories MCDCENT and MCDPG. Where this is the case,
when using an external prommer, you must delete the MCDPG directory.
When using an internal prommer, you must remove the MCDCENT
directory.
Same message with a PG 720/740/760 Bad installation of STEP 7
33:8256 The external prommer is not connected to the The external prommer is not connected to the configured LPT interface. Connect the external prommer to the configured LPT.
corresponding port or the power supply has been
interrupted.
The S7DOS-DLL attempts to start the server. If this does not work, then it In STEP 7 V5 and higher the server checks whether it has the same version
tries again and again. It has a timeout of 30 seconds in which time the as the DLL. If not, it doesn't start.
server should be up. If nothing happens during 30seconds - no refresh of
the application - then this is a clear indication of an unsuccessful server
start.
33:16418 The monitoring time for a STEP 7 frame was
exceeded.
33:16418 Timeout by wait of WM_ENDE_L7. The monitoring time for a STEP 7 telegram has expired.
Faulty parameterization of the access point on the MPI, L2 and H1 card or Correct the access point via "Set PG/PC interface" or PG/PC ONLINE card.
on the corresponding bus.
There is already a communications load at the moment due to a Repeat attempt to set up connection or check the S7 connections in the S7
configured S7 communication and therefore no ONLINE connection is project.
possible.
Cold or warm restart of communications partner. Repeat attempt to set up connection or check the power supply of the
communications partner.
The partner is not a module in the PLC. Check the addresses given.
The partner is a different PG or an external device. Using the "Module Status" function check whether the selected partner is a
CPU. Check whether its communications partner is slotted in the place
configured (rack/slot).
The partner cannot set up any more connections. Close any further connections to the partner.
Connection setup via DP interface without the CPU retaining it's relevant First configure the CPU also as DP master and load the SDBs onto the
SDBs. CPU.
33:16914 Online: Station not online. Power supply of the S7 is switched off. Check whether the CPU is switched on.
Connecting cable is not plugged in or is defective. Check that the MPI cable is plugged in.
Check the cable for breaks.
Configured bus parameters do not match the S7 system. Check the following bus parameters: Baud Rate, Highest User Address
(these parameters must be set correctly on all stations in the network) and
Timeout.
In the Control Panel call "Set PG/PC interface" to correct the bus
parameters.
Restart MS-Windows and check the error messages of the drivers.
Incorrect access point is selected. Select correct access point.
PG: hardware fault Send PG to PG service shop to have the interface checked.
33:16917 The function is not supported by the selected Occurs if you set up an ONLINE connection via a CP5412 A2 with the Incorrect message, the connection is set up as soon as a user is connected.
hardware. option "PC is the only master" (in the "Set PG/PC interface" tool) via
"Available Users" and there is no user connected to the CP 5412 A2.
33:16944 Online: It is not found an active contact. User not connected to the bus. Check the connecting cables and the connection to the network. Check the
PLC for power failure.
On the PC/TS adapter the LED for correct power supply lights. This LED Check the connection and whether the 24V and 5V power supplies reach
lights if only the 24V supply is connect and the 5V supply is missing. The the PC/TS adapter.
PC/TS adapter however needs the 24V and the 5V power supply through
the PLC.
The TS adapter is set to the wrong transmission rate on the MPI side. Correct the network transmission rate under Set PG/PC interface -> MPI.
The PC/TS adapter hardware is damaged. Replace the TS adapter or send it in for repair.
The wrong driver is preset under "Set PG/PC interface". Preset the correct driver for the TS adapter.
33:17072 Online: no hardware is found. No driver selected or incorrect address area of the MPI interface PG/PC interface - MPI Properties
->Select or add driver
Occurs with SCENIC PRO M6, Onboard Controller occupies many IRQs Deactivate primary and secondary controllers in the BIOS.
WIN 95 does not clearly recognize the interrupt occupied through the Select a different interrupt for MPI card.
3Com-Etherlink 3 (ISA) 3c0509b. This can lead to interrupt sources being
double-occupied.
The reason for this can be an actual fault in the hardware, or an interrupt In this case the customer can check whether the MPI LED on the CP5611
conflict with another module. lights during this time.
-If the LED does not light, the module might be defective or there is an
address conflict on the PCI bus (not very likely).
-If the LED lights, then there is an interrupt conflict.
-NT diagnostics ->Resources.
-Warning: with some modules it is necessary to switch the computer
off/on after BIOS changes
Under circumstances, one remedy is to plug the CP5611 into a different
PCI slot.
33:17077 Online: The setting local address of participant is The TS adapter had the same MPI address (0) as another user in the MPI Via the "Parameterize Adapter" function, assign to the TS adapter an MPI
assigned network. address that has not yet been assigned and save it. The TS adapter has
MPI address 0 as works default setting.
33:17108 Exit the application which is currently using the Another application already occupies the serial interface or faulty setting With NT check in the Control Panel that STANDARD is not set for
required port (COM port or USB) of COM-IF upon display under NT. Addresses and INT in the settings of the COM interfaces under "Advanced".
If not, remove COM IF and then restart the PC. Now COM IF should be
newly installed with the STANDARD option.
33:33285 It is a copied object variant available. Please set up the connection by closing all the S7 applications and then
restarting them.
33:33540 Message from the module. Too few resources Message from the PLC when reading block when, for example, two Start Trace (Level=0x11000000)
available. upload processes are triggered simultaneously by 2 PG.
33:33794 Illegal request of service The CFB in the communications partner is in the wrong state. Check the block call in the user program of the communications partner.
PRINT block: Paper out. Check the printer when printing via the module.
The program instance in the communications partner is in the wrong state Set the key switch to RUN or RUN-P before starting the module.
(cf. START, STOP, RESUME block).
When implementing a CPU with DP interfacing, you might get the Download the SDBs and restart manually.
following situation: a user is not available on the DP bus, the CPU
remains about 30 seconds in startup and the RUN LED blinks. Then the
CPU goes into RUN (as long as no I/O access to the missing I/Os puts
the CPU into STOP). This is obviously a TIMEOUT effect, because the
CPU doesn't acknowledge the service in the relevant time.
33:34562 The service requested is not supported by the The service requested is not supported by the module. Note the restrictions of the CPU used (menu command PLC > Module
module. status, Performance Data tab or look up the performance data in the
documentation for the module used).
Use a more powerful module.
The object addressed does not exist on the module. Check the addressing of the object.
33:53347 (D063) Resources error: the trigger event is It is no longer possible to monitor a block. This behavior is triggered by 1. Unplug the online cable of the CPU and wait at least 1 minute. It is not
occupied. irregular termination of the process in the operating system. enough to unplug the CPU just briefly.
2. Shut down your programming device and wait 1 minute before switching it
on again. A simple reboot is not always sufficient.
Message from the module. This function cannot be executed at the Delete the jobs that you no longer need (e.g. delete stop points, close the
moment, because the resource required is already occupied. There are "Monitor/control variables" function, close the "Program Status" function).
also too many test functions activated at the same time and the resources
available on the module are exhausted.
33:53772 Note the restrictions of the module being used. Message from a module. Note the restrictions of the module implemented. (See also in the Message
from Modules area.)
33:53790 The module to be assigned parameters is currently Remedy: reset the CP via Online HW Config and Download HW Config.
busy assigning parameters to subordinate devices. Repeat the module download when all stations and field devices on the bus
It was been by the modules: 416-2DP + CP443-5 are started up and in operation. To ensure that the module to be
Extended downloaded temporarily cannot assign parameters to subordinate devices,
remove the interconnecting bus cable from the DP interface for the duration
of the downloading process.
In the case of an IM 467, you must do a POWER OFF/ON. This resets the
IM and the HW Configuration can now be downloaded.
33:53797 The distributed I/O system data block is structured A diagnostics address outside the address area has been specified. (For Change the diagnostics address.
incorrectly. example, Win AC lite was installed.)
33:53824 D204: The rules of coordinations were broken. When attempting to load the system data, there was still a variable table Close the variable table and retransfer the system data.
open online.
33:59906 The communication software (S7DOS) and the The customer has a STEP 7 V5+SP1 + new PDM and a CP 443-5 Ext > Upgrade CP 443-5 to a version >V2.7.
interface module (CP) have not the same protocol. V2.7. The new protocol RPC 7 that is used for data record routing
between the CP and S7DOS. Unfortunately versions up to version V2.7 of
the CP do not have this function.
The user is implementing the right components STEP 7 V5 + SP2 + PDM, Check the configuration and replace the CP implemented with a different CP
but has a CP that does not include the DSGW. that includes this function.
34:11 Compiler information: handle not valid. When monitoring an empty network with the LAD/FBD/STL editor. Delete empty network.
34:21 Compiler information: element not found. The element could not be found in the referenced database. Check the spelling of your search key and your database reference.
34:38 Compiler information: Compiler error
34:39 You have attempted to rename a variable, but the name is already being
used.
34:152 Reference data could not be generated. Error in the database. The project can be correct+D191ed with "Save As with reorganization".
34:168 The moduls in the comand structure are protected One or more direct or indirect reference module is know how protected Please deactivate the option "Include reference blocks" in the menue
and can not be generated. and can not be generated "Generate source ...". You have to create the list of the moduls via manual
without the protected moduls.
34:173 At least one symbol assignment has changed If you copy a symbolically addressed block from the library of an S7 1. Please make sure that the source is generated with the setting "absolute".
project into another project and after you open the block. 2. Copy the source into the new project; the project can be configured as
In the original project you generate an STL source from the block. symbolically addressed.
3. Now compile the source and so generate the block.
After that you can adapt the symbols as required without the behavior
described above occurring.
34:178 Block call invalid because interface was changed With Step7 V5.0 the instance DB of the DB type is entered in the symbol Enter the instance DB of the FB type in the symbol list.
in the meantime. list for an FB call. This is no longer permitted with Step7 V5.0. In this case
the "Update Call" function doesn't work.
34:4469 The declaration range of your formal parameter It is not allowed, that an OUT variable of the calling function block is We recommend first saving the data temporarily on a static variable. In a
does not match the declaration range of the actual parameterized with the IN variable of the function block called. further network this static variable is parameterized with the IN variable of
parameter, for example, no OUTPUT paramater the FB called. The output variable of the higher-level block, the static
from the actual end can be assigned to an INPUT variable and the input variable of the lower-level block must be of the same
parameter from the formal end. data type.
34:4485 The parameter assignments can be specified in any order in the ASCII If you have entered comments for parameters, then when assigning the
source. The comments, however, are stored separately from the actual parameters, please keep to the order in which the parameters of the block
online block in the order entered. Thus, when exchanging parameters in called are declared.
the source, the order of comments might then be wrong. When the block
is opened, the comments are then assigned incorrectly. In the worst case
comments might even be lost. The following comments in the network are
also affected, even when the exchanged parameters are not even
commented.
Message appears when opening a VAT. The directory S7USS is missing Reinstall STEP 7.
in the SIEMENS\STEP7 directory.
88:47 Unable to reach the module %1 by means of the Programming device is connected to the MPI interface of the CPU. Check whether the CPU is routing-compatible. If Not, then please set your
online interface that is set. MPI driver to PROFIBUS and connect up with the PROFIBUS DP. Then
repeat the desired function.
256:24 Function open Environment is not implemetiert Multiple start of the SIMATIC Manager In the STEP7_V2/S7met directory delete the files S7CacheA.dat and
S7ser.dat with Win95 Explorer. The ending .dat can be left out; depending
on the options package, there is also an S7CacheB -E.dat
256:26 Internal OLE Error. Not enough space on the hard disk, the database cannot be started. Create space on the hard disk and set user-defined virtual memory.
Wrong DLL in Windows/System and/or wrong Registry entry. Start program editor via Explorer and evaluate error message.
With V3.1 when printing With V3.1 copy block comment into network comment.
WIN 95: the OLE was not installed properly when installing WINDOWS. Delete Windows directory and then reinstall WINDOWS.
256:32 Not valid objects. A link has obviously been lost. In V2.1 projects the solution is to use "Save As with Reorganization"
256:35 Internal system error is not repairable.
256:49 The quoted entry is not in the registry by Windows Error occurred when downloading SDBs into a remote CPU via Set up the connection over and over again and wait for a better line quality.
or contains a not valid value. TeleService. The cause here was a bad telephone line connection Try to get a higher transmission rate (<- indicator for better line quality at
(analog) (in the USA). After several attempts to set up an ONLINE the time of connection set up).
connection, the SDBs could be transferred without this error message. An
attempt was also made to achieve a higher transmission rate with the
ONLINE connection.
256:53 Internal error: Not valid pointer. In PLCSIM an attempt was made to load the last simulation in PLCSIM Create a new simulation via Simulation -> New PLC. The next time you run
via the menu item Simulation -> Last Simulation. Since the old project the last simulation the latest new simulation will be loaded without error
data (e.g. also block interfaces) has perhaps changed in the meantime, message.
some of the data of the simulation originally created no longer matches
the current project.
256:56 There is an internal error in the system. Project might be damaged. Terminate application and restart.
256:93 The rights of write is missing in the directory. The directory in which the S7P file is located is write-protected. Remove the write-protection from all directories that have to do with the
project.
Not enough space on the disk < 100 bytes
If STEP 7 V4.x is concerned, then it might be that a file has not been Delete S7APROMX.TXT in the root directory of the project.
deleted, which still specifies that the project is still on a write-protected
drive.
256:104 Authorization of optional package is not found. No user rights (authorization) found for the options software on drive C:. Install the options authorization from the authorization floppy disk included in
the delivery package. If you have lost the authorization (e.g. through a fault
on the hard disk), you can install the emergency authorization to be able
continue working for a limited period of time. You must then procure a
replacement for the lost authorization during this limited time.
WIN NT: insufficient access rights. To operate S7 software under NT you need at least main user rights.
256:107 The object specified could not be copied. There might not be enough Press the "Yes" button to continue the copy or save operation for the
space left on the data medium. Possibly the target directory is remaining objects. The copied objects might possibly be incomplete or
momentarily blocked by another application. defective in the new environment. If you press the "No" button, the copy or
save operation is aborted.
Possibly another STEP 7 application has opened the object to be copied
and has thus blocked it. In this case, close all other STEP 7 applications
and trigger the process again.
256:111 Access denied Your have repeatedly loaded a program in the SPS and now it is not Start the service "Server" in the control panel.
possible to load the program again, also not after a new start.
256:119 There is no authorization for STEP 7. To operate No authorization installed or the path in which the STEP 7 project is Install the authorization or shorten the project path as appropriate.
this optional package, you require the authorization located is too long.
for "STEP 7 V4.x".
257:5 One or more objects of a type cannot be The process variable server cannot be started. Installation problem with Please check the version of the software package installed against the
represented. Unable to load the server STEP 7. There must not be any incompatible version of WinCC installed compatibility list. This is located in your STEP 7 directory as the file
's7uvpomx.dll' for _S7UV_LIST_CT-objects. Make on the computer. S7KOMP_x.PDF. x stands for the language:
sure that the required optional packages are a=German b=English, c=French, d=Spanish, e=Italian.
installed.
Mixed installation, a V4.0 or V4.01 was installed before the installation Deinstall STEP 7 manually and then reinstall it.
STEP 7 V5.x. See FAQ 189025
One or more objects of a type cannot be The NCM package is not installed and the S7 project contains Please install the options packages concerned; in this case the NCM
represented.Unable to load the server 's7wb53ax corresponding objects. options package.
dll' for _S7H_6GK7_443_1BX00_0Xe_CT-objects.
Make sure that the required optional packages are
installed.
One or more objects of a type cannot be Toolbox of SINUMERIK 810 is missing or badly installed. Reinstall the toolbox for SINUMERIK 810.
represented.Unable to load the server
S7HK31AX.DLL for
_S7H_PLC314_Modul_CT_objects. Make sure
that the required optional packages are installed.
One or more objects of a type cannot be The error is probably caused by the permanent upgrading of STEP 7. Deinstall STEP 7 manually and then reinstall it.
represented.Unable to load the server There are several older versions of STEP 7 one on top of the other.
"s7hsl7ax.dll" for
_S7H_DP_PA_LINK_1_ETER_CT-objects. Make
sure that the required optional packages are
installed.
One or more objects of a type cannot be
represented.Unable to load the server
"p7ss357x.dll" for
_P7_FM357_6ES7_4AH00_0AE0_CT-objects.
Make sure that the required optional packages are
installed.
One or more objects of a type cannot be
represented. Unable to load the server
S7HK31AX.DLL for _P7_PUSTCH_CPU
314_CT_objects. Make sure that the required
optional packages are installed.
If the remedies under the last above points do not help, close STEP 7 again
and delete the project in the Explorer. You can find the folder for the saved
project in Fig. 01 under
"<Drive>\Program Files\Siemens\Step7\S7Proj\<Project>
It is possible that the data areas of the HW Config, NetPro, Symbol Table or
other STEP 7 components have not been released again completely after
being closed. You should be able to delete the projects again after rebooting
your PC.
291:416 The symbol table is occupied by another process In this case you can no longer edit, delete or import the symbol table. The One possible cause of the error is that after a program crash of the symbol
symbol table is not occupied by any other application for writing. You editor, temporary files are not deleted in the S7 data management. In order
have stored the project locally on the hard disk. The same error is also to control this, check your project:
displayed with the "Save with Reorganization" function of the project. 1. In each project there is a "..\YDBs" directory where all the symbol lists are
stored.
2. Use Explorer to find files with the suffix .dbf__tmp in this and all
subordinate directories.
3. Terminate the STEP7 applications and delete these files. Then you can
edit all the symbol lists again.
It is imperative to make sure that you do not delete other files by mistake in
the project, because this could destroy the project.
291:560 Internal error: Incorrect object ID. The symtabs function has failed - ambiguous entry in the symbol list for Delete the line for the FC in the symbol table.
FC names.
When calling an FB, a DB was assigned that is already assigned to Assign a different DB in the call or correct the assignment in the symbol
another FB in the symbol table. table.
Copy out the symbol table, then open and close the block, and then copy
back the symbol table.
291:1392 No symbol table found. No symbol could be
created.
292:19 Error by opening of a file. The file either has no valid B+C287trieve format or it is damaged. Replace the file or delete it.
293:1 The reference data could no be generated. The data medium is write-protected. Remove write-protection.
Under NT: possibly insufficient access rights. You need at least main user rights.
293:2 The reference data could no be generated for the Use the function "Save as" together with the option "With Reorganization
SFC14 or the FC22. (slowly)".
294:6 Unable to copy the block %2. The OBxy is not supported by the CPU. This OBxy cannot and must not be downloaded into this CPU. You can
possibly use another OBxy with a similar function, which is suitable for this
CPU and then download it.
When programming an EPROM via an external prommer: the prommer Plug in the prommer cable so that the connector with the yellow sticker is
cable is plugged in incorrectly. connected to the prommer.
Illegal command in the modul The module FCxx could not be copied. This message appears, if your program has a marker (example M8000.0)
(D280) Error during compiling of module in the S7-300. which address is not supported in the CPU. Change the address and repeat
the download. If the SF LED is not still erased after download, switch the
CPU into STOP and after in RUN again.
294:23 Unable to copy the block %2. Do you want to A block of this type already exists and it may not be overwritten. Delete the equivalent block in the ONLINE database and repeat the transfer.
continue the copy procedure?
The automation system is in the RUN operating mode. Put the automation system into an operating mode that permits copying.
Possibly the terminator on the PROFIBUS cable on the system side Switch off the bus terminator.
(TeleService) is switched on.
Possible the modem is sending too much information to the TS adapter Add W0 to the Initstring in the adapter (this suppresses the sending of
so that it doesn't get the CONNECT. (Occurs with V5 adapters) extended data)
If you attempt to get connected via long telephone routes (abroad), then it In TeleService under Options -> Settings -> Monitoring Times, change the
might happen that some feedback messages have too long a runtime. value for Acknowledgment/Signal from Automatic to 5000ms / 4000ms.
295:20484 There is not installed a modem which is Install a suitable modem and set the modem to correspond with your
compatible with teleservice. configuration. Define the TeleService-specific properties of your installed
modem in the menu command Options > Settings.
295:20486 The TAPI-Order was closed with the error "Order Basically communication between (local) PC and modem (via the serial Check the connection between the (local) PC and modem for both hardware
failure". connection) is not correct or cannot even be started. and software/driver faults.
Under Windows (Start --> Settings --> Control Panel --> Modems) an Install the appropriate modem driver for this modem. Also set this new
incorrect (or no) modem driver has been installed, which does not work in modem in TeleService under Set Connection ---> Modem (double-click the
conjunction with the modem connected. telephone book entry and then select the Modem item).
The wrong modem driver was selected under TeleService from the Set the correct modem driver in the selection list.
selection list of modems that are already installed under Windows.
The modem is not connected to a serial interface (or to the wrong one). Connect the modem to the correct serial interface.
For example, for the "Deissw01" project on drive "C" in the standard STEP 7
project directory you enter
dbsrv50 -f c:\Siemens\step7\S7proj\deissw01\Amobjs\Amdbase.db
The -f (force) switch has the effect that the DB file is recovered to the last
status saved even if the necessary log file is not available.
Occurs after dearchiving a project in STEP 7 V5.0. It has been created in After <Save as...><with reorganization> again clears the problem.
the version V4.02.x.
314:8 At least one of the selected variables cannot be If, while you are processing a project in STEP 7 V5.3 which has been In this event, the name "Ret_Val" must be renamed.
inserted at this point. created with STEP 7 V5.1 and the error message described above 1. From STEP 7 version V5.2 onwards, users may no longer define the key
appears in the LAD/STL/FBD editor when you insert a declaration line term "Ret_Val" for the formal parameters. Version V5.2 still supported the
within an FB or FC, please check the names of the formal parameters in entry "Ret_Val" in the declaration line in STEP 7 projects which were
the declaration line for the block in question. This could be due to the fact created in V5.1 and did not stop the block.
that the name "Ret_Val" has been assigned to a formal parameter (IN, 2. However, STEP 7 version V5.3 no longer supports the name "Ret_Val" in
OUT, IN_OUT, STAT or TEMP variable). the declaration line, and the behavior described above occurs.
724:21 OM TD/OP: Data basis conflict of version The versions of STEP 7 and ProTool are incompatible with those of the Upgrade STEP 7 to V5.x or deinstall ProTool and install V4.02 of ProTool
file: C:\[step7-pfad]\[Projektname]\S7TDOP.DBF project. STEP 7 is V4.02.x and ProTool V5.
has the version 50000.
This program expected the version 10000.
1230:1001 Opening of the station failed.
1230:2001 Unable to insert the object. You have tried to slot an object that is not available (e.g. the header for an Select an object (subrack, module, interface module...) from the hardware
object group or module class). catalog, which you can slot in the required location.
1230:2015 Creating the configuration data failed. Hard disk is full. Deleted all the unnecessary files on the hard disk.
No folder "...SIEMENS\STEP7\S7TMP" available or the folder is write- Remove the write-protection from the folder "...SIEMENS\STEP7\S7TMP" or
protected. create the folder.
S7 program or M7 program container is missing. Create S7 program or M7 program container.
Defective project? Use "Save as... with reorganization"
The compilation (= creation of the configuration data) has been Reinstall STEP 7.
interrupted.
Error attempting to generate the configuration data. Subnet addresses of different networks are identical. Check the subnet addresses and make appropriate corrections in the case
Message refers to the V2-projects by Save as with of identical subnet addresses.
Reorganization.
1230:2016 No changes can be made in this station. No more modules can be inserted in the HW Config. Use "Save as... with reorganization" for the project. Please see also the
instruction by the error message 256:92.
1230:2018 Another application made changes to your station. Another S7 application has changed, for example, via network, the station You can remove the block by closing the station and re-opening it. This
Close this station and re-open it. currently being processed. The changed objects (subrack, modules, makes the changes of the other application effective.
slaves, etc.) can no longer be displayed.
The station has been blocked for further processing.
1230:3000 The system data could not be recreated because Check consistency.
the configuration is inconsistent.
2508:1099 Error by programming of error diagnostic data for Group message, behind it detailed messages are listed that occurred Please press the "Details" button and analyze the detailed messages.
<name of variable>. during the last function executed.
2517:5 The start of an application has occurred an error. Message appears when opening a HIGRAPH source. Cleared with K4.01.2.
With the following software constellation:
STEP 7 V5.0 + SP 3
S7-HIGRAPH V4.01.1
S7 project created with S7-Higraph V5.x
2775:777 Address is not correct. You have selected a user address that is already occupied. Please select another address or connect your user to another subnetwork.
2775:785 The bit rate of 187,5 kbit/s for the modul MBK-P is In STEP7 V5+SP3 and higher the baud rate must not be written with a Open and edit the file: enter '187.5_supp =1' instead of '187,5_supp =1'.
not supported in station SIMATIC 400(1). comma, e.g. 187,5_supp =1 Execute Options -> UPDATE CATALOG.
2775:1829 The data management of "Set PG/PC interface" An attempt was made to save a parameter value in the database of the
can not save the requested value. program "Set PG/PC interface". This write procedure could not be
concluded successfully.
2775:1834 The highest address on PROFIBUS subnet <xx> is In the properties of the PROFIBUS system, you can set the highest Open in the HW Config the properties of PROFIBUS interface your CPU and
set to <xx>. "The highest PROFIBUS subnet permitted Profibus address. If you have set the address e.g. 32, a higher click in register "General" on "Properties". Select in the follow dialogue the
'PROFIBUS(1)' is set to 32. Due to the steps PROFIBUS station address is no longer permitted and the message PROFIBUS network and click on "Properties". Set the value for the highest
available for the settings, this cannot be set". appears. PROFIBUS address, e.g. 126 in register "Network Settings".
3020:47 This processing status is triggered by PKUnZip in different situations, in In this - most common - case you can ignore the message.
particular always when an existing project is overwritten during
dearchiving and in the dearchiving options the entry "Overwrite objects
with identical names" is not set to "All Files".
The archive file has not been created with PKZip. In particular archives Execute dearchiving with the archiving program used to create the archive.
that have been created with WinZip or "PKZip for Windows" and contain
"long file names" can lead to this error.
The archive file has been created with a version of PKZip that is newer If you are using an old version of PKUnZip, install the latest version.
than the version of PKUnZip that is installed on the computer.
The archive file is damaged. Checksum errors (so-called CRC errors)
have been detected for one or more files. Therefore the files could not be Try to get a good copy of your archive file. If this is not possible, you can try
dearchived correctly. The cause of such checksum errors can in particular to save what is possible to save using the repair option of PKZip. Start the
be: MS-DOS prompt and enter the command 'pkzipfix archiv'. A file is created
damaged floppy disks, transfer errors when copying, called pkfixed.zip - if pkzipfix can even identify the file as being ZIP-
in particular with network drives, file transfer or e-mail, compatible. From the SIMATIC Manager dearchive the file pkfixed.zip
or at the time of archiving the project or parts of it were still open. instead of your original archive file.
The directories in the archive file have too great a nesting depth to be You can either dearchive the archive file with PKUnZip as follows: select the
able to be unpacked under the specified target directory. PKUnZip cannot target directory for dearchiving the Root directory of drive. Close all the
create any directories whose absolute path name is longer than 66 STEP 7 applications. Move the dearchived project directory with the
characters (from the drive designation to the ‘\’ at the end of the path). Explorer to the location where the project is to be stored. Start the SIMATIC
Manager and open the project via the "Browse" button in the "Open" dialog.
Or you can use WinZip or PKZIP 2.50 directly at the required location.
The project already exists and individual files could not be overwritten Delete the file attribute "write-protected". You can do this for example for
when dearchiving, because they are write-protected. individual files from the Explorer via the file properties, or you start the MS-
DOS prompt, get into the project directory using "cd" and then enter the
command "attrib -r /s". Now repeat the dearchiving procedure.
D330
3020:49 Unable to retrieve the project. The archive file The archive file has not been created with PKZip. In particular archives Dearchive using the archiving program with which the archive was created.
might be defective. that have been created with WinZip or "PKZip for Windows" and include
"long file names" can lead to this error.
The archive file has been created with a version of PKZip that is newer If you are using an old version of PKUnZip, then install the latest version.
than the version of PKUnZip installed on this computer.
The archive file is damaged. Try to get a good copy of your archive file. If this is not possible, you can try
to save what is possible to save using the repair option of PKZip.
1. Start the MS-DOS prompt and enter the command 'pkzipfix archiv'. A file
is created called pkfixed.zip - if pkzipfix can even identify the file as being
ZIP-compatible. From the SIMATIC Manager dearchive the file pkfixed.zip
instead of your original archive file.
The data medium or the directory in which the dearchived project is to be Remove the write-protection or obtain write authorization for the network
stored is write-protected, or you have no write authorization for the drive or dearchive the project into a different directory.
network drive.
3022:4121 The FB is not available If during compilation in S7-PDIAG the mentioned error message, then it is 1. Delete all SFBs. Open and save the FBs, FCs and OBs, which fetches
The instance declaration is missing probably the case that the S7-PDIAG blocks have also been copied from the SFBs from the current library.
another STEP 7 during the copying procedure. This is not permissible, 2. Now compile the blocks of the S7 program again with S7-DIAG, which
because the associated SFBs are then no longer up to date. should solve the problem.
Make the Check Block Consistency and compile the complete STEP 7
program.
3022:4121 Invalid data type...", The error message is probably caused by an associated value with an Excerpt of the Online Help of S7-PDIAG:
invalid data type. Please also refer to the information in the Online Help of "This associated value can have a parameter of the type BOOL, BYTE,
S7-DIAG concerning the data types that are valid for associated values. CHAR, WORD, INT, DWORD, DINT or REAL from the E, A, M or DB areas.
Likewise you can enter local variables of an FB to which an error definition is
attached. These are extended upon generation according to the type
instance concept.
3280:503 The registry database is not set up correctly for the Installation is faulty.
SIMATIC Manager. Install STEP 7 again.
3534:94 Inconsistent of hardware configuration The hardware configuration is either inconsistent or it was made changing If it is not possible to compile the hardware configuration after this message,
which are not still save and compiled. so make a little change in the hardware configuration. After it is possible
again to save and compile.
4502:625 An error occured while creating or interpreting the Regarding mentioned messages occur while saving and translating in HW Step7 has to be reinstalled or the missing ".err" files have to be copied from
system SDB's....". config if the following applies: a different computer in order to be able to translate the hardware
Error while creating systemdata....". 1. You projected and assigned a CP to a subnet in your Hardware configuration again.
configuration. Files with the extension ."err" are missing in the folder Attention:
"<Siemens-index>\Step7\S7WBX\RUL". If you copy the files from a second STEP 7 installation, please make sure
2. Files with the extension ."err" will be deleted by some optimization that this installation contains exactly the same STEP 7 version, the same
programs - like e.g. TuneUp. servicepack and the same hotfix.
4561:142 The Authorisation for Standard PID Control is not .. ..
installed.
Meldung von
Baugruppen
D033 Error of protokol Job jam on the CPU. In the HW Config increase the setting for the communications load for the
CPU.
D042 Error during notice by module status of CPU400. A PQW is being monitored. You cannot read back PQWs, the CPU then Monitor values with VAT and wait for new CPUs.
reports this error.
D043 Error of data: The reference order is not available. When controlling using Variable Monitoring it might happen that if too Acknowledge the message and reduce the frequency of control jobs.
many control jobs are sent to the CPU, they are rejected by the CPU
because its buffer is full.
D062 Resources error, job list is too full. Please see the informations by error message 33:53346.
D063 Same as D064
D064 CPU 300 does not delete trigger events, the events then build up. Switch CPU off/on. Problem cleared in the following CPUs:
6ES7 313-1AD01-0AB0
6ES7 314-5AE01-0AB0
6ES7 314-1AE02-0AB0
6ES7 315-1AF01-0AB0
6ES7 315-2AF01-0AB0
D0AA D0AA: The time limit is exceeded in process Communications load is too high. Increase the communications load of the CPU from (default) 20% to 50%.
operating.
Error during opening of a empty document. Error An incompatible OPC Manager is installed. In the system path of Delete this file and the file vcf132.ocx and reinstall STEP 7.
during opening of a symbolic table. Windows vcf1.lic is responsible for this.
Setup does not start with error message: in The _isres.dll is needed for switching languages. Start Setup with the extension ol:b, then the Setup is forced to start in
function "Sdbitmap":unable to crate dialog make English.
sure the _isres.dll is in _setup.lib
D280 Error during compilation of a modul in S7-300. The This message appears, when the defined variable (marker, in- or output) Example, this message appears if the number of outputs is 8192 byte by the
module OB1 could not be copied. in a module is not in the power range of the CPU. CPU and you have defined a variable outside of this range. Check the
addresses with the definition of your variables.
D406 The requested informations are not available. Number of possible connections has been exceeded. Check the connections and reduce where appropriate. Static connections
can be converted into dynamic connections.
EA 02 The protocols of communication software (S7DOS) The customer has a STEP 7 V5+SP1 + recent PDM and a CP 443-5 Ext Upgrade CP 443-5 to a version >V2.7.
and the interface module (CP) are not compatible. > V2.7. The new RPC 7 protocol is used for data record routing between
the CP and S7DOS. Unfortunately the CP up to version V2.7 does not
support this function.
The user is using the correct components STEP 7 V5 + SP2 + PDM, but Check the configuration and replace the CP being used with a different CP
has a CP that does not have the DSGW. that has this function.
Set PG/PC interface
None Error message by diagnostic: "Profibus/MPI Firmware/driver error This behavior no longer occurs in SOFTNET PROFIBUS S7 V5.0.
Network diagnostic".
Error: requested parameter could not be read from
the register data basis!
Message without numerical order
S7OTBLSTX Incompatible versionen by S7OTBLDX.DLL and S7 applications are still running at Setup of STEP 7. Please close all S7 applications and restart SETUP.
S7OTBLSX.DLL.
Frei verwendbar
ARJ Fehlertexte
Fehlermeldung:
<filename> does not exist
<filename> exists
Bad header
Break signaled
CRC error
NOT found
NOT matched
Nothing to do
Signal failed
end of document
Fehlerursache:
The file <filename> could not be found on the disk
This error may occur in a multiple volume extraction if ARJ is trying to
extrace a split file. If this split file is not the file on the disk. If thie is
missing, ARJ will report this error.
This error will also occur during an extraction to freshen existing files.
The file <filename> does not have a valid ARJ archive header in the initial
portion of the file. This file may not be an ARJ archive or it may be
demaged.
The file <filename> that is being appended to does not have the correct
file date-time stamp. This message occurs during multiple volume
extraction was interrupted by a "quit" response.
The <filename> has the same or newer file date-time stamp than the
matching file in the archive.
The ARJ command is missing the name of the ARJ archive filename
This message is displayed when ARJ has verified that the archive has a
valid ARJ-SEC envelope. This indicates that the archive contents are
intact and unmodified as originally distributed by the individual indentified
in the text that follows this message
The file in the ARJ archive is damaged and has invalid data in it. It is not
possible to recover thes file in an undamaged format.
The file in the ARJ archive is damaged or you may have supplied the
wrong password to the "-g" option. Check the password that you specified.
This error usually means that there is not enough disk space to copy the
intermediate archive file to its destination drive. ARJ does not purge the
intermediate archive file so that the file can be copied manually to a drive
with enough disk space.
ARJ cannot delete the file <filename>. Most likely, the file is in use or is
set as readonly.
During the scan of the specified index file, ARJ could not find a line of text
similar to the following: Next volume - 001 1 19931 C:\ARC\VGA640.DRV
This can happened if the index file is damaged or was created by a
version of ARJ prior to 2.39.
ARJ could not read the volume label of the drive specified.
ARJ cannot open the file <filename>. The file may be set to readonly or it
may already be in use.
This error message usually occurs if the end of the file has been reached
when ARJ is expecting more data.
ARJ could not rename <filename>. The target filename may already exist.
ARJ could not seek to the position in the file. This file may not be as large
as the position specified.
ARJ always uses the filename stored in the archive ta access the file
during the compare operation. The -e and -e1 options strip significant
information from the filename.
Self-explanatory.
The file in the ARJ archive is damaged and has involid data in it. It is not
possible to recover this file in an undamaged format. If this error is
encounted when ARJ initally starts up, this indicates that the ARJ runfile is
probably damaged.
A DOS critical error has occurred. ARJ has trapped this error condition
and returned a error.
This ARJ archive has been damaged or corrupted. The contents of the
archive are not in the same condition as when it was created.
The small self-extractor module does not support the extraction of garbled
files.
The file description header record in the archive is damaged. This cannot
be fixed. The use of the "-jr" option will allow the recovery of files after the
damaged section.
The specified volume size was too small. Only 360,720,1200, and 1440
are acceptable abbreviations.
This message is displayed when the filename in the archive is not found
on disk.
ARJ has run out of memory and cannot store the name <filename>.
Specifying fewer filenames or using a listfile are two ways to work around
the lack of memory. The new "-hm" option sets ARJ to use disk space to
store avoiding this memory problem.
At least one search string must be specified for the ARJ "w" command.
Self-explanatory.
Self-explanatory.
Self-explanatory.
There is not enough small model memory for ARJ to complete iis
operation. It can occur if there is a large amount of enviroment space
allocated to enviroment variables. the use of "COMMAND /C/E:200 ARJ
<command>..." can work around this problem.
...
ARJ could not set the volume lable to the volume lable stored in the
archive. This can happen if the volume label in the archive is not standard
DOS volume label.
This message is displayed when the option (-he1) has been specified and
ARJ has just accessed an ARJ archive that has an ARJ-SECURITY
envelope on it. This does NOT indicate the validity or integrity of the ARJ-
SECURITY envelope.
The ARJ small self-extraction module (-je1) does not support extraction of
files compressed in text mode (-t1).
This ARJ archive has been damaged or corrupted. The contents of the
archive are not in the same condition as when it was created.
This ARJ archive has been ARJ-SECURED and most probably is in the
same condition as when it was created.
ARJ has encountered an unknown file type in the archive. You may need
a newer version of ARJ to process this archive.
Self-explanatory.
S7ubtoox.exe auf single stellen und alle Netze aus Phoenix 79742 1
S7ubtoox.exe auf single stellen und alle Netze aus Siemens 77940 1
S7ubtoox.exe auf single stellen und alle Netze aus Krauss-Maffei 67726 1
Siemens 68026 1
S7ubtoox.exe auf single stellen und alle Netze aus Romero 65983 1
S7ubtoox.exe auf single stellen und alle Netze aus Siemens 84269 1
S7ubtoox.exe auf single stellen und alle Netze aus Benteck 76740 1
S7ubtoox.exe auf single stellen und alle Netze aus Siemens 68303 1
S7ubtoox.exe auf single stellen und alle Netze aus Siemens 80012 1
Siemens 62107 1
IFA Flensburg 60490 1
Fehlertext: Fehlerursache:
Abhilfe: Aktuell
Frei verwendbar
OM VERB UDP 0 S7WNUDE?.DLL
S7WRI 0 s7wri\s7wriem?.dll
S7asrcom 0 s7asrer?.dll
OM Fremd 0 s7noems?.dll
S7nonfgx 0 s7noems?.dll
S7 Archive-Services 0 s7arcem?.dll
OM PtP 0 S7NPEMS?.DLL
s7tgtop 0 s7topem?.dll
s7tbrow 0 s7topem?.dll
S7jthom 0 S7jthom?.dll
OM VERB FDL 0 S7WNFDE?.DLL
OM VERB RFC1006 0 S7WNRFE?.DLL
S7NAKVAX 0 s7nakva?.dll
M7Config 0 s7mfger?.dll
OM VERB ISO 0 S7WNISE?.DLL
SINEC NCMS7 0 s7wber1?.dll
S7WNSVVX 0 s7wnsvv?.dll
Frei verwendbar
1
s7sym\s7yedeh?.hlp 3
s7ngd\s7lgdeh?.hlp 7
s7ieceh?.hlp 9
s7inf\s7usieh?.hlp 11
s7homeh?.hlp 13
S7scl\s7scleh?.hlp 15
s7uss\s7usseh?.hlp 16
s7ska\s7kafeh?.hlp 30
s7otbeh?.hlp 33
s7icceh?.hlp 34
S7JSEXP?.hlp 241
S7Hlp\s7jswgn?.hlp 242
S7JM7CG?.hlp 243
S7JS7CG?.hlp 244
s7jcomf?.hlp 245
s7jcomf?.hlp 246
S7JM7EF?.hlp 247
S7JS7EF?.hlp 248
S7JM7TI?.hlp 249
S7JS7TI?.hlp 250
S7JM7IM?.hlp 251
S7JS7IM?.hlp 252
s7jsfca?.hlp 253
s7jcfca?.hlp 254
s7jcomf?.hlp 255
s7aceeh?.hlp 256
s7aaaeh?.hlp 257
s7apreh?.hlp 258
S7NLEHP?.HLP 275
S7NHEHP?.HLP 276
s7hrseh?.hlp 288
s7xut\s7xuteh?.hlp 289
s7yomeh?.hlp 291
s7umgeh?.hlp 292
s7ombeh?.hlp 294
s7wm_eh?.hlp 296
s7upoeh?.hlp 298
s7utxeh?.hlp 299
s7ubseh?.HLP 300
s7uvaeh?.hlp 301
S7uvmeh?.hlp 302
C:\SIEMENS\STEP7\s7dpr\s7ppdeh?.hlp 304
S7BIN\S7IFXEH?.HLP 309
310
S7Hlp\S7jwzlr?.hlp 732
s7hcoeh?.hlp 1230
1417
1419
S7WNFME?.HLP 1420
s7ums\s7umseh?.hlp 1489
s7bin\s7nnehp?.hlp 2263
Frei verwendbar
S7WNUDE?.HLP 2443
s7wri\s7wrieh?.hlp 2511
s7asreh?.hlp 2517
s7noehp?.hlp 2775
s7noehp?.hlp 2775
s7arceh?.hlp 3020
S7NPEHP?.HLP 3225
s7topeh?.hlp 3280
s7topeh?.hlp 3280
S7Hlp\S7jthom?.hlp 3283
S7WNFDE?.HLP 3463
S7WNRFE?.HLP 3467
s7nakve?.hlp 3785
s7mfgeh?.hlp 4049
S7WNISE?.HLP 4495
4502
s7wnsve?.hlp 4578
Frei verwendbar
a
Fehlernummer:Fehlertext: Fehlerursache:
Abhilfe: Aktuell