HAP Heat Load Calc
HAP Heat Load Calc
Calculation Months .................................. Jul to Aug Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads
Total coil load ....................................................... 5.5 kW Load occurs at ................................................ Aug 1000
Sensible coil load ................................................. 4.5 kW OA DB / WB ................................................... 40.6 / 27.8 °C
Coil L/s at Aug 1000 ............................................ 320 L/s Entering DB / WB ........................................... 23.6 / 16.7 °C
Max block L/s ...................................................... 320 L/s Leaving DB / WB ............................................ 11.8 / 11.2 °C
Sum of peak zone L/s ......................................... 320 L/s Coil ADP .................................................................. 10.5 °C
Sensible heat ratio ............................................ 0.831 Bypass Factor ........................................................ 0.100
L/(s kW) .............................................................. 58.6 Resulting RH ............................................................... 50 %
m²/kW ................................................................... 7.1 Design supply temp. ................................................ 12.5 °C
W/m² ................................................................. 141.8 Zone T-stat Check ................................................. 1 of 1 OK
Water flow @ 9.0 K rise ..................................... 0.15 L/s Max zone temperature deviation ................................ 0.0 K
Actual max L/s ..................................................... 320 L/s Fan motor BHP ........................................................ 0.32 BHP
Standard L/s ........................................................ 320 L/s Fan motor kW .......................................................... 0.26 kW
Actual max L/(sꞏm²) ............................................ 8.31 L/(sꞏm²)
Calculation Months .................................. Jul to Aug Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ............................................. Calculated Space L/s Sizing .............. Individual peak space loads
Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
RETAIL AREA 1 4.1 Aug 1400 320 0.2 38.5 8.31
1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................... 0 L/s