TA2 - Effects of Zinc Alloy Layer On Corrosion and Service Life of Galvanized Reinforcing Steels in Chloride-Contaminated Concrete
TA2 - Effects of Zinc Alloy Layer On Corrosion and Service Life of Galvanized Reinforcing Steels in Chloride-Contaminated Concrete
TA2 - Effects of Zinc Alloy Layer On Corrosion and Service Life of Galvanized Reinforcing Steels in Chloride-Contaminated Concrete
A R T I C L E I N F O A B S T R A C T
Keywords: Corrosion of reinforcing steel affects the service life of structures. A chloride environment exposed
Corrosion to reinforced concrete structures accelerates the corrosion process. Hot-dipped galvanized steel
Reinforcing steel was used as reinforcing steel instead of bare carbon steel to provide better protection against
Galvanized steel corrosion. The coating layers of galvanized steel have different compositions which can affect
Chloride corrosion behavior. When galvanized steel has been corroded, it will expose the zinc-alloy layer
Service life
that has a different composition than the top pure zinc layer. A comparative study on electro
Electrochemical properties
chemical properties such as concrete resistivity, polarization resistance, corrosion current density,
anodic Tafel slope, cathodic Tafel slope, and corrosion rate of bare carbon steel (BS), galvanized
steel (GS), and corroded galvanized steel (CGS) was conducted. The BS, GS, and CGS were
embedded in concrete with different mix proportions by varying water-to-binder ratios, chloride
contents, and types of binder. The electrochemical properties data were measured by the Wenner
four-probe, linear polarization resistance (LPR), and potentiodynamic polarization resistance
(PPR) tests. The measurement results show that the resistivity of 0.4 w/b concrete is higher than
0.6 w/b concrete. Corroded galvanized steel’s polarization resistance is lower than bare carbon
steel’s and galvanized steel’s. The corrosion rate calculated from the Stern-Geary equation of
corroded galvanized steel is higher than bare carbon steel and galvanized steel. Based on the
calculation results, the specimens with galvanized steel have a longer crack-initiating life than the
bare carbon steel. The crack-initiating life of the reinforced concrete structures using galvanized
steel can be more precisely predicted by considering the corroded galvanized layer.
1. Introduction
Chloride is one of the main causes of corrosion that directly damages reinforcing steel [1]. Chloride that attacks reinforced concrete
structures can come from the environment (external chloride) or the chloride-containing concrete raw materials (internal chloride)
[2]. To reduce the severity of corrosion damage by chlorides, concrete and steel quality must be improved. Variations in the concrete
* Corresponding author.
E-mail addresses: [email protected] (M.S. Dewi), [email protected] (P. Sancharoen), [email protected] (P. Klomjit), [email protected]
(S. Tangtermsirikul).
https://doi.org/10.1016/j.jobe.2023.106153
Received 19 December 2022; Received in revised form 6 February 2023; Accepted 18 February 2023
Available online 20 February 2023
2352-7102/© 2023 Elsevier Ltd. All rights reserved.
M.S. Dewi et al. Journal of Building Engineering 68 (2023) 106153
mixtures including water-to-binder ratio and binder type, and type of reinforcing steel have been conducted [2]. One option is to
replace bare carbon steel with galvanized steel.
Literature reported that galvanized steel has a longer service life than bare carbon steel [3–5]. Corrosion of bare carbon steel is
considered to have two stages; initiation and propagation stage, while galvanized steel has three stages: initiation, protection, and
propagation stages [3,6]. The initiation stage is the ingression period of chloride to reach a critical chloride level. The critical chloride
contents of bare carbon steel and galvanized steel are proposed in some research studies to be 0.4% and 1% by weight of cement,
respectively [3,7,8]. The protection stage is the stage where zinc on the steel surface sacrifices itself to protect the steel. The last stage is
the propagation stage where the steel begins to corrode, causing the reinforced concrete structures to crack, spall, and collapse [3,9,
10].
Galvanized steel consists of layers of pure zinc and zinc alloy that affects the corrosion behavior of galvanized steel [11–13].
Literature [5,14–16] reported the average corrosion rate of galvanized steel without considering the effects of the zinc alloy layer.
Fig. 1 shows an illustration of the corrosion process of galvanized steel. The corrosion occurs on 3 layers, pure zinc (thickness of 15
μm), zinc alloy (thickness of 81 μm), and iron [12,17,18]. As zinc is passivated at a pH of 8–12.5, while iron is passivated at a higher pH
of 10–13.5 [19,20]. The corrosion behavior of pure zinc and zinc alloy layers are different and needed to be studied. Zinc requires an
environment that can keep the pH from increasing and being in the passivation phase.
Concrete mix proportion also affects the corrosion behavior of reinforcing steel. Various supplementary cementitious materials are
introduced and applied in cement and concrete not only to optimize the performance of the binder system but also to reduce their
carbon footprint. It was found in a previous study that fly ash decreases the pH of concrete [2]. Passivation of zinc can be enhanced at
lower pH of fly ash concrete. Recently, Portland composite cement (PCC) according to TIS 2594–2556, has also been introduced as a
practical cement in Thailand [21]. To produce PCC, limestone powder is blended with cement clinker with the main purpose to reduce
carbon dioxide emission of the cement product [22]. The addition of limestone powder affects various concrete properties such as pH,
hydration processes, and chloride binding [23,24]. The corrosion of reinforcing steel in PCC concrete is also needed to be studied.
Electrochemical properties such as concrete resistance, polarization resistance, corrosion current density, anodic Tafel slope, and
cathodic Tafel slope are required for the evaluation of the corrosion rate of reinforced concrete structures. The experimental results can
be used to compare the electrochemical properties of various types of reinforcing steel in different concrete mixtures. In this study,
specimens with varied binder types and chloride concentrations were prepared. Three types of reinforcing steel, including bare carbon
steel (BS), galvanized steel (GS), and corroded galvanized steel (CGS) are studied. The corroded galvanized steel was used for obtaining
a more precise prediction of the galvanized steel in the actual condition during the service period of concrete structures.
2. Experiment
2.1. Materials
The reinforcing steels used were bare carbon steel (BS), galvanized steel (GS), and corroded galvanized steel (CGS). BS was a
deformed bar, grade SD40 according to TIS 24–2559 [25] having a diameter of 12 mm and a length of 150 mm. GS was a bare carbon
steel, coated with zinc by the hot-dipped galvanizing technique in the factory, resulting in a galvanized layer thickness of about 130
μm. CGS is the galvanized steel after being immersed in hydrochloric acid (HCl) for 10 min according to ASTM G1 to simulate corrosion
of the pure zinc layer and expose the zinc alloy layer [26]. CGS had a remaining galvanized layer thickness of about 80 μm and the zinc
alloy layer was reached as can be observed from the XRF test results in Table 1. The percentage of Fe is higher in the CGS than in the GS.
The tested concrete has water-to-binder ratios of 0.4 and 0.6. The chloride used is analytical-grade sodium chloride (NaCl) with
varied contents of 0%, 0.75%, and 1.5% chloride by weight of the binder. Three types of binders used were a Portland composite
cement (PCC) according to TIS 2594-2556 [21], an ordinary Portland cement (OPC) according to ASTM C 150 [27], and PCC replaced
with 30% of fly ash (FA) by weight of the binder. The fly ash was obtained from the Mae Moh powerplant, Thailand. The properties of
the fly ash follow the class 2b according to TIS 2135–2545 [28]. Table 2 shows the chemical compositions of each binder by the XRF
test. The properties of coarse aggregate and fine aggregate were according to ASTM C33 [29].
2
M.S. Dewi et al. Journal of Building Engineering 68 (2023) 106153
Table 1
Chemical compositions measured on the surface of GS, CGS, and BS.
larization resistance (RP ) test results include the effects of an ohmic drop. Therefore, a calculation of compensated polarization
′
resistance (RP ) is required as shown in Equation (1) [31] and Equation (2) [32].
(1)
′
RP = RP − Rc
The obtained electrical resistivity (ρ) was then used to calculate the concrete resistance (Rc ) as shown in Equation (2) with the
details of the notations shown in Table 5. In determining the current flow area during the LPR test, it was assumed that the current
flowing from the reinforcing steel spreads throughout the concrete area.
L
Rc = ρ (2)
A1
Similarly, the PPR test began with a 100 s delay for the open circuit potential (OCP) to be stabilized. An initial and final potential of
±200 mV from OCP and a scan rate of 0.5 mV/s were used. In this test, measurements were made to obtain anodic Tafel slope (βa ),
cathodic Tafel slope (βc ), and corrosion current density (Icorr ). βa and βc were used to calculate the value of B based on the Stern-Geary
equation as shown in Table 4 and Equation (4) and corrosion current density (Icorr ) as shown in Equation (3) [33]. Again, the details of
the notations in Equations (3) and (4) are given in Table 5.
Table 2
Chemical compositions of the binders.
PCC FA OPC
3
M.S. Dewi et al. Journal of Building Engineering 68 (2023) 106153
Table 3
Mix proportions of the tested concrete.
Name Chloride content (% by weight of binder) w/b FA (%) Unit Content (kg/m3)
Fig. 2. Prepared reinforcing steel: (a) Galvanized steel; (b) Corroded galvanized steel; (c) Bare carbon steel.
Fig. 3. Reinforcing steel coated by epoxy (C: Coated, U: Uncoated, Scale 1:1).
B
Icorr = (3)
RP × A2
βa × βc
B= (4)
2.3 × (βa + βc )
Based on the electrochemical properties, the corrosion rate can be determined as shown in Equation (5) for mg/cm2 year unit and
Equation (6) for mm/year unit according to Faraday’s law [34]. The equivalent weight (EW) and density (D) of BS, GS, and CGS were
required, and their descriptions and values are shown in Table 5 [34]. Specifically for CGS, the values of EW and D were obtained by
calculation according to ASTM G102 [34] using the chemical compositions in Table 1.
rcorr1 = 3.65 × K × Icorr × EW (5)
4
M.S. Dewi et al. Journal of Building Engineering 68 (2023) 106153
Fig. 4. (a) Wenner four-probe test specimen, (b) LPR and PPR test specimen.
Fig. 5. Electrical resistivity measurement: (a) Wenner four-probe test; (b) Directions of the test.
Fig. 6. (a) Electrochemical test setup, (b) Specimen setup in the box.
0.00327 × Icorr × EW
rcorr2 = (6)
D
5
M.S. Dewi et al. Journal of Building Engineering 68 (2023) 106153
Table 4
Anodic and cathodic Tafel slopes from PPR measurements.
βa βc βa βc βa βc
Table 5
Parameters in each equation.
6
M.S. Dewi et al. Journal of Building Engineering 68 (2023) 106153
concrete mix results in Fig. 7. The main cause of the reduction in electrical resistivity of concrete with chloride is that NaCl is
transformed into an aqueous electrolyte by absorbing water [40]. In contrast, the use of PCC in chloride-contaminated concrete shows
a higher resistivity than concrete without chloride. This is because limestone in PCC reacts with chloride causing denser pore structures
[41]. So electrical resistivity of PCC concrete increased with the amount of chloride. PCC with fly ash concrete contaminated with
chloride shows the highest electrical resistivity. This can reduce the corrosion rate of the reinforcing steel.
3.4. Time until corrosion cracking on the concrete surface (crack-initiating life)
The service life of a structure can be defined based on various stages of deterioration. In this study, the time until corrosion cracking
appears on the concrete surface (crack-initiating life) is considered and predicted based on the corrosion rate of each tested condition
as shown in Figs. 9 and 10. According to the standard specifications for concrete structures [45], cracks can be generated on the
concrete surface due to corrosion of reinforcing steel when the amount of the corroded steel reaches 10–100 mg/cm2 depending on
various factors such as covering depth, arrangement of steel, strength of concrete, etc. It was reported that a value of 10 mg/cm2
corresponded to a conservative estimation concerning the time of occurrence of corrosion cracking [45]. Based on Ueda et al. [46], the
7
M.S. Dewi et al. Journal of Building Engineering 68 (2023) 106153
Fig. 9. Corrosion rates of different steel types and concrete mix proportions (mg/cm2 year).
Fig. 10. Corrosion rates of different steel types and concrete mix proportions (mm/year).
corrosion amount that causes concrete surface cracking is equal to 10 mg/cm2 for 10 mm covering depth. An increase of 10 mm in the
covering depth requires an addition of 10 mg/cm2 of corrosion amount to initiate cracking. As the covering depth was 30 mm in this
study, the corrosion amount of 30 mg/cm2 was used as a cracking criterion to determine the time until corrosion cracking appeared on
the concrete surface.
Table 6 shows the results of predicted time until corrosion cracking occurs on the concrete surface with variations of chloride and
concrete mixture. The thickness of pure zinc and zinc alloy layer is referred from the literature [17] as shown in Fig. 1. According to
Fig. 1, corrosion process is calculated by considering and not considering the presence of the zinc alloy layer. For GS and CGS,
corrosion of the galvanized layer is firstly calculated according to Equation (6). Then the corrosion amount of BS is calculated and
compared to cracking criteria according to Equation (5). The corrosion current density (Icorr ) used to calculate corrosion rate is shown
in Table 6. It is noted that since the purpose of this study is to compare the corrosion resisting performance of the GS, CGS, and BS from
starting time of corrosion, the crack initiating life does not include the corrosion initiation life (ti ) (the period from right after the
specimens were prepared until when the chloride content around the steel reached the critical chloride content). The galvanized steel
Table 6
Service life from corrosion initiation to cracking (propagation stage).
Name Current density (Icorr ) (μA/cm2) Service life from corrosion initiation to cracking (years)
8
M.S. Dewi et al. Journal of Building Engineering 68 (2023) 106153
in 4PCC chloride-free concrete without considering Zn alloy layer demonstrates the concrete surface cracking time of 164 years, while
a shorter time of 142 years was obtained when considering Zn alloy layer and the bare carbon steel shows only 112 years of cracking
time. In a chloride environment of 1.5% by weight of binder, the cases of analysis of galvanized steel without considering Zn alloy
layer, galvanized steel considering zinc alloy and bare carbon steel result in the cracking times of 25, 24, and 16 years, respectively.
Based on the results, the galvanized steel has a longer service life than the bare carbon steel. However, considering corrosion rate of the
Zn alloy layer is necessary because the service life of galvanized steel is affected by the Zn alloy layer. Fly ash concrete has a longer
cracking time due to its higher electrical resistivity and lower corrosion rate.
4. Conclusions
This study is about electrochemical properties and corrosion rate of reinforced concrete with different reinforcing steel by con
ducting experiments and estimate the time until corrosion cracking on the concrete surface of bare carbon steel and galvanized
reinforcing steel in various mixtures of concrete with varied chloride contents, with and without considering zinc alloy layer. The
following conclusions can be made.
1) Fly ash concrete shows higher electrical resistivity than normal concrete due to pore densification and different ions concentration.
Limestone powder in PCC concrete increases electrical resistivity of the chloride-contaminated concrete due to the reaction be
tween limestone powder and chloride ion. As a result, the corrosion rate of fly ash PCC concrete is the lowest.
2) The polarization resistance of GS is higher than that of CGS and BS, especially in chloride-contaminated concrete as the passive film
of zinc is denser than iron. As the zinc alloy layer is a combination between zinc and iron, the polarization resistance of CGS is lower
than that of BS in chloride-free concrete due to galvanic corrosion. However, in the chloride-contaminated concrete, CGS shows
higher polarization resistance than BS.
3) The corrosion rate of GS is the lowest. The corrosion rate of CGS is also lower than that of BS, especially in chloride-contaminated
concrete. GS and CGS in FA concrete show lower corrosion rates than in PCC concrete because the passive film of zinc is more stable
in the lower pH environment of the fly ash mixture.
4) Prediction of concrete surface corrosion cracking time of GS-reinforced concrete needs to consider the corrosion rate of the zinc
alloy layer in CGS as the zinc alloy layer has a higher corrosion rate than the zinc layer and so causes a shorter crack-initiating life.
However, the CGS specimen still has a longer crack-initiating life than the BS specimen.
Data availability
Acknowledgements
The authors would like to acknowledge the Center of Excellence in Material Science, Construction and Maintenance Technology
Project, Thammasat University. This study was supported by Chair Professor Grant (P-19-52302), the National Science and Technology
Development Agency (NSTDA), Thailand and by AUN/Seed-Net scholarship to the first author.
References
[1] J. Roman, R. Vera, M. Bagnara, A.M. Carvajal, W. Aperador, Effect of chloride ions on the corrosion of galvanized steel embedded in concrete prepared with
cements of different composition, Int. J. Electrochem. Sci. 9 (2) (2014) 580–592.
[2] D.V.P. Tran, P. Sancharoen, P. Klomjit, S. Tangtermsirikul, Effects of concrete mix proportion and chloride content on electrochemical properties of reinforcing
steel in concrete, Eng. J. 24 (3) (2020) 23–34.
[3] S.R. Yeomans, Galvanized Steel Reinforcement: Recent Developments and New Opportunities, Proceedings of 5th International Federation for Structural
Concrete, Melbourne, Australia, 2018.
[4] L. Soufeiani, G. Foliente, K.T. Nguyen, R. San Nicolas, Corrosion protection of steel elements in façade systems–A review, J. Build. Eng. 32 (2020), 101759.
[5] D. Darwin, M. O’Reilly, O. Farshadfar, J. Browning, C. Locke Jr., Corrosion-induced Concrete Cracking for Uncoated and Galvanized Reinforcing Bars, American
Concrete Institute, 2018.
[6] R. Rodrigues, S. Gaboreau, J. Gance, I. Ignatiadis, S. Betelu, Reinforced concrete structures: a review of corrosion mechanisms and advances in electrical
methods for corrosion monitoring, Construct. Build. Mater. 269 (2021), 121240.
[7] D. Darwin, J. Browning, M. O’Reilly, L. Xing, Critical Chloride Corrosion Threshold for Galvanized Reinforcing Bars, University of Kansas Center for Research,
Inc, 2007.
9
M.S. Dewi et al. Journal of Building Engineering 68 (2023) 106153
[8] H. Zheng, J.-G. Dai, W. Li, C.S. Poon, Influence of chloride ion on depassivation of passive film on galvanized steel bars in concrete pore solution, Construct.
Build. Mater. 166 (2018) 572–580.
[9] M. Otieno, M. Alexander, H.-D. Beushausen, Corrosion in cracked and uncracked concrete–influence of crack width, concrete quality and crack reopening, Mag.
Concr. Res. 62 (6) (2010) 393–404.
[10] E. Verstrynge, C. Van Steen, E. Vandecruys, M. Wevers, Steel corrosion damage monitoring in reinforced concrete structures with the acoustic emission
technique: a review, Construct. Build. Mater. 349 (2022), 128732.
[11] A. Yadav, H. Katayama, K. Noda, H. Masuda, A. Nishikata, T. Tsuru, Effect of Fe–Zn alloy layer on the corrosion resistance of galvanized steel in chloride
containing environments, Corrosion Sci. 49 (9) (2007) 3716–3731.
[12] P. Pokorny, P. Tej, M. Kouril, Evaluation of the impact of corrosion of hot-dip galvanized reinforcement on bond strength with concrete–a review, Construct.
Build. Mater. 132 (2017) 271–289.
[13] S. Grandhi, V. Raja, S. Parida, Effect of manganese addition on the appearance, morphology, and corrosion resistance of hot-dip galvanized zinc coating, Surf.
Coating. Technol. 421 (2021), 127377.
[14] M. Jasniok, M. Sozanska, J. Kolodziej, B. Chmiela, A two-year evaluation of corrosion-induced damage to hot galvanized reinforcing steel b500sp in chloride
contaminated concrete, Materials 13 (15) (2020) 3315.
[15] Y.-q. Wang, G. Kong, C.-s. Che, B. Zhang, Inhibitive effect of sodium molybdate on the corrosion behavior of galvanized steel in simulated concrete pore
solution, Construct. Build. Mater. 162 (2018) 383–392.
[16] T. Bellezze, D. Timofeeva, G. Giuliani, G. Roventi, Effect of soluble inhibitors on the corrosion behaviour of galvanized steel in fresh concrete, Cement Concr.
Res. 107 (2018) 1–10.
[17] R.E. Wilmot, Corrosion protection of reinforcement for concrete structures, J. S. Afr. Inst. Min. Metall 107 (3) (2007) 139–146.
[18] V. Di Cocco, F. Iacoviello, L. D’Agostino, S. Natali, Damage micromechanisms in a hot dip galvanized steel, Procedia Struct. Integr. 3 (2017) 231–236.
[19] J. Thomas, T. Nurse, The anodic passivation of iron in solutions of inhibitive anions, Br. Corrosion J. 2 (1) (1967) 13–20.
[20] F.A. Cedrim, V.L.S.d. Almeida, C.A.C.d. Souza, P.R.L. Lima, M.D.d. Jesus, D.V. Ribeiro, Corrodibility and adherence of reinforced concrete rebars electroplated
with zinc and zinc-nickel alloys, Mater. Res. 22 (2019).
[21] TIS, Hydraulic cement, in: TIS 2594-2556, 2013. Thailand).
[22] M. Uddin, M. Jameel, H.R. Sobuz, M. Islam, N.M. Hasan, Experimental study on strength gaining characteristics of concrete using Portland Composite Cement,
KSCE J. Civ. Eng. 17 (4) (2013) 789–796.
[23] K.Y. Ann, H.-W. Song, Chloride threshold level for corrosion of steel in concrete, Corrosion Sci. 49 (11) (2007) 4113–4133.
[24] A. Kijjanon, T. Sumranwanich, W. Saengsoy, S. Tangtermsirikul, Chloride penetration resistance, electrical resistivity, and compressive strength of concrete with
calcined kaolinite clay, fly ash, and limestone powder, J. Mater. Civ. Eng. 35 (3) (2023), 04022462.
[25] TIS, Steel Bars for Reinforced Concrete: Deformed Bars, in: TIS 24-2559, 2016 (Thailand).
[26] ASTM, Standard Practice for Preparing, Cleaning, and Evaluating Corrosion Test Specimens, in: ASTM G 1, United States of America, 2003, pp. 1–9.
[27] ASTM, Standard Specification for Portland Cement, in: ASTM C 150, United States of America, 2018, pp. 1–9.
[28] TIS, Coal Fly Ash for Use as Admixture in Concrete, in: TIS 2135-2545, 2003 (Thailand).
[29] ASTM, Standard Specification for Concrete Aggregates, in: ASTM C 33, United States of America, 2010, pp. 1–8.
[30] S.W. Hnin, P. Sancharoen, S. Tangtermsirikul, Effects of concrete mix proportion on electrical resistivity of concrete, in: Materials Science Forum, Trans Tech
Publ, 2016.
[31] M. Daniyal, S. Akhtar, Corrosion assessment and control techniques for reinforced concrete structures: a review, c 5 (1) (2020) 1–20.
[32] H. Layssi, P. Ghods, A.R. Alizadeh, M. Salehi, Electrical resistivity of concrete, Concr. Int. 37 (5) (2015) 41–46.
[33] M.G. Sohail, S. Laurens, F. Deby, J.P. Balayssac, N. Al Nuaimi, Electrochemical corrosion parameters for active and passive reinforcing steel in carbonated and
sound concrete, Mater. Corros. 72 (12) (2021) 1854–1871.
[34] ASTM, Standard Practice for Calculation of Corrosion Rates and Related Information from Electochemical Measurements, in: ASTM G 102-89, United States of
America, 2004, pp. 1–7.
[35] S. Rath, P. Sancharoen, P. Klomjit, S. Tangtermsirikul, Effects of carbonation on corrosion rate of reinforcing steel in different concrete and repair materials, Eng.
J. 25 (6) (2021) 75–86.
[36] K. Hornbostel, C.K. Larsen, M.R. Geiker, Relationship between concrete resistivity and corrosion rate–A literature review, Cement Concr. Compos. 39 (2013)
60–72.
[37] H. Justnes, A Review of Chloride Binding in Cementitious Systems, vol. 21, Nordic Concrete Research-Publications-, 1998, pp. 48–63.
[38] T. Sumranwanich, S. Tangtermsirikul, A model for predicting time-dependent chloride binding capacity of cement-fly ash cementitious system, Mater. Struct. 37
(6) (2004) 387–396.
[39] L. Bertolini, B. Elsener, P. Pedeferri, E. Redaelli, R.B. Polder, Corrosion of Steel in Concrete: Prevention, Diagnosis, Repair, John Wiley & Sons, 2013.
[40] E. Schindelholz, B. Risteen, R. Kelly, Effect of relative humidity on corrosion of steel under sea salt aerosol proxies: I. NaCl, J. Electrochem. Soc. 161 (10) (2014)
C450.
[41] M.H. Davoudi, E. Kabir, Interaction of lime and sodium chloride in a low plasticity fine grain soils, J. Appl. Sci. 11 (2011) 330–335.
[42] T.-H. Ha, S. Muralidharan, J.-H. Bae, Y.-C. Ha, H.-G. Lee, K.-W. Park, D.-K. Kim, Accelerated short-term techniques to evaluate the corrosion performance of
steel in fly ash blended concrete, Build. Environ. 42 (1) (2007) 78–85.
[43] L. Prak, T. Sumranwanich, S. Tangtermsirikul, Time-dependent model for predicting chloride binding capacity of concrete with crystalline material, J. Mater.
Civ. Eng. 33 (2) (2021), 04020473.
[44] M. Kouril, P. Pokorny, J. Stoulil, Corrosion mechanism and bond-strength study on galvanized steel in concrete environment, Corrosion Science and Technology
16 (2) (2017) 69–75.
[45] JSCE, Standard Specifications for concrete structures, in: Maintenance JSCE No.17, 2007. Japan.
[46] H. Ueda, Y. Sakai, K. Kinomura, K. Watanabe, T. Ishida, T. Kishi, Durability design method considering reinforcement corrosion due to water penetration,
J. Adv. Concr. Technol. 18 (1) (2020) 27–38.
10