PLSED310053EN
PLSED310053EN
Power metering
A complete range of meters for essential electrical system measurement
PLSED310053N
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
Panorama of the
3
EasyLogic range
DM1000 series
1-Ph Volts Amps Frequency 5
Digital Panel Meters
DM3000 series
3-Ph Volts Amps 5
Digital Panel Meters
DM6000H series
7
VAF PF Digital Panel Meters
PM1120H series
13
Basic Power & Energy Meters
PM1130H series
19
Dual Source Power & Energy Meters
2 PLSED310053EN
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
Frequency b b b
CT Secondary 5 A or 1 A 5 A or 1 A 5 A or 1 A 5 A or 1 A
I nominal
Comm. ref. no. METSEDM1110 METSEDM1210 METSEDM1310 METSEDM3110 METSEDM3210 METSEDM6000 METSEDM6000
(Link to product HCL10NC HCL10RS
information)
PLSED310053N 3
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
* Refer data sheet for operating range v One power vector at a time (W/Wh or VA/VAh or VAR/ VARh)
4 PLSED310053EN
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
™
EasyLogic
DM1000/3000 series
The EasyLogic™ DM1000 series : 1-Ph V A F panel meters, DM3000 series: 3-Ph V A panel meters
The universal, user-programmable DM1000 and DM3000 series panel meters for AC circuits are ideal replacements for
analogue meters. These five compact, flexible and customizable models will meet all your panel metering requirements.
PB113034
PLSED310053N 5
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
DM1000/3000
–– Form factor
–– Flush/panel mount, 96 x 96 x 44 mm
–– IP Degree of protection
–– IP51 front & IP40 rear side
–– Auto scaling & direct readings
–– Accuracy
–– 0.5 % of full scale for V & A
–– 0.2 % of full scale for Hz
–– Safety/ EMI-EMC tests
–– CE: As per IEC 61010-1 Ed.3
–– Emission: CISPR11, Class A
DM3000 series digital panel meter front display
(above), and rear (below) –– Fast Transient: IEC 61000-4-4*
–– Surge withstand: IEC 61000-4-5*
–– ESD: IEC 61000-4-2*
–– Isolation: 4 kV for 1 minute
PB113044
Comparisons
Parameter DM1110 DM1210 DM1310 DM3110 DM3210 Accuracy
1-ph A b 0.5 %
1-ph V b 0.5 %
1-ph Hz b 0.2 %
3-ph A b 0.5 %
3-ph V b 0.5 %
Commercial METSEDM METSEDM METSEDM METSEDM METSEDM
ref number 1110 1210 1310 3110 3210
6 PLSED310053EN
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
Introducing EasyLogicTM DM6000H/ DM6200H meters that are ideal replacement for multiple analogue meters for
stand-alone metering in custom panels, switch boards, switch-gear, genset panels, motor control centres, power factor
improvement panels and OEM panel board.
DM6x00H series meters offer large 8-segment alpha-numeric LED display type, intuitive navigation with self-guided 4
buttons, bright LED’s of 14.2 mm height with 12 LEDs for indicating percentage of load in the circuit.
PB119316
PLSED310053N 7
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
DM6x00H
• Applications
PB119320
–– Cost management
–– Electrical installation remote monitoring
–– Control panels
–– Motor control centres
–– Power distribution boards
–– Original equipment manufacturers (OEM’s)
–– Building management system
–– Panel instrumentation
–– Energy management system
• Network management
–– Measurement of Power factor
–– % unbalance for voltage and current
Front view DM6000H
–– Phase angle between the respective voltage and current phase
–– Modbus RTU protocol, RS-485 communication port for integration with
energy management systems (DM6200H)
• Main characteristics
PB119325
–– Easy to install: Mounts using two retainer clips, no tools required. Compact
meter with 49 mm meter depth behind the panel, connectable up to 480 V
+10 % AC volts L-L without voltage transformers for installation complaint
with measurement category III, and double insulated
–– Easy to operate: Intuitive navigation with self-guided menus and
Heartbeat LED indicates normal functioning of meters while it conveys
the communication status when connected to RS-485 network
–– LED display: Intuitive navigation with self-guided, four buttons,
8-segment alpha-numeric LEDs of height ~14.2 mm (0.55 in), and
three lines of concurrent values with Kilo & Mega value indicator.
–– Standard compliance:
–– EMI/ EMC tests as per IEC 61326-1
Rear ISO DM6000H non comm –– CE certification as per IEC 61010-1 Edition 3
–– cULus as per UL61010-1 and CAN/CSA-C22.2 IEC 61010-1
edition 3, for 480 V AC L-L
–– Accuracy class 1.0 for V AF PF metering
–– CT nominal: 5 A, I-nominal or 1 A, I-nominal (field settable)
–– Password: Field configurable password for securing set up information
–– Cyber security: Option for disabling RS-485 port through front panel
keys against unauthorized access. This feature can also be used for
Comparisons
maintenance and troubleshooting of complex communication network
Parameters / Model DM6000H DM6200H
Class 1.0 Class 1.0 –– Analogue load bar: The colour-coded analogue load bar at the front
side indicates the percentage of load through 12 LED’s with the option
V A F – per ph & Avg b b
to select full scale based on connected load
PF – per ph & Avg b b
% Load, % V & I Unbal, –– Display: 4 digits for VAF PF parameters with auto scale and auto range
Ph-angle, RPM
b b features
Modbus RS-485 b –– Suppression current: To disregard the measurement of induced and
Commercial METSEDM METSEDM panel auxiliary load current in the circuit (settable from 5 to 99 mA)
reference no. 6000HCL10NC 6200HCL10RS
–– Protection cover to ensure that terminals screws does not detach from
the housing and touch proof against fingers
8 PLSED310053EN
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
DM6x00H
DM6x00H technical specifications
General
Use on LV & MV systems with Potential transformer (PT or VT)/ Current transformer (CT) ratio programmable at site
Digital panel meters for measurement of basic electrical parameters
Display
Bright red colour LED display, 8 segment alpha-numeric LED, ~ 14.2 mm (0.55 in) height, 3 rows with 4 digits per row, auto range, auto scale
Communication
RS-485 serial (DM6200H) Channel connection Industry standard Modbus RTU protocol
Integration with software Any Modbus compatible SCADA/ DCS/ PMS/ EMS/ BAS/ BMS software
Native Plug and Play support Schneider Electric energy management system software - EcoStruxure™ Power Monitoring Expert,
EcoStruxure™Power SCADA Operation
ION Setup utility software for set-up/programming of meters
Diagnostics
Diagnostic page Indicates the health of communication system, all LED test, device serial number, device model number
OS & RS version, communication status, error code display
Lock/ Un-Lock
Page lock and unlock features Once the commonly referred page is enabled for lock feature, the display returns to locked page in 4
minutes of inactive time
Electrical characteristics
Type of measurement True RMS, 32 samples/cycle
Measurement accuracy (Class 1.0 meters)
Current, per-phase & average ± 0.5 % of reading
Voltage, L-N, L-L, per-phase & average ± 0.5 % of reading
Power factor, per-phase & average ± 0.01 of reading
Frequency ± 0.05 % for F-nominal 50/60 Hz ± 2
± 0.2 % for Frequency range from 30 to 48 Hz, 52 to 58 Hz and 62 to 70 Hz
Input-voltage
VT (PT) connection Selectable from No VT (direct), 1 VT, 2 VT to 3 VT
VT (PT) primary 100 V L-L to 999 kV L-L max
U (V) nominal Up to 277 V L-N/ 480 V L-L (selectable VT secondary from 100, 110, 115, 120 to 415 V L-L)
Operating voltage range with accuracy 80-480 V L-L ± 10 % Category III
Measured Voltage with full range 35 to 600 V L-L
Permanent overload (withstand) 750 V L-L, continuous
Impedance ≥5 MΩ
Frequency 50/60 Hz ± 2
VA burden ≤0.2 VA at 240 V L-N at 50 Hz
Frequency – measurement
Nominal operating range 50/60 Hz ± 2
Extended operating range 30 to 48 Hz, 52 to 58 Hz and 62 to 70 Hz
Voltage input 80 to 480 V L-L ± 10 %
PLSED310053N 9
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
DM6x00H
Input-current
CT connect Solo or multi-phase current measurement by installing CT (s) in either of A1, A2, A3, A12, A23, A13, A123 phase(s)
CT primary 1 A to 32767 A, programmable
CT secondary 1 A or 5 A I-nominal (field settable)
Operating current range with accuracy 10 mA to 6 A+1
Measured Amps with over 5 mA to 10 A
range & Crest Factor
Suppression current 5 to 99 mA (to disregard negligible load)
Impedance < 0.3 mΩ
Permanent overload (withstand) Continuous 10 A, 10 s/hr 50 A, 1 s/hr 500 A
Frequency 50/60 Hz ± 2
VA Burden ≤0.1 V A at 5 A at 50 Hz
AC control power
Operating range 48 to 277 V L-N AC ± 10 %
Burden ≤4 VA at 240 V L-N 50 Hz
Frequency 50/60 Hz nominal (45 to 65 Hz operating range)
Ride-through time 200 milliseconds at 240 V L-N, 50 Hz
DC control power
Operating range 48 to 277 V DC ± 10 %
Burden ≤2 W at 240 V DC
Ride-through time 120 milliseconds at 240 V
Displays update
Instantaneous/ RMS parameters 1s
Power system
Phase labelling Configurable to 123, ABC, rst, pqr or ryb
Wiring configuration 13 wiring schemes (5 on front screen)
1ph, 2w, L-N
1ph, 2w, L-L
1ph, 3w, L-L with N (2-phase)
3ph, 3w, Delta, Ungrounded
3ph, 3w, Delta, Corner Grounded+2
3ph, 3w, Wye, Ungrounded+2
3ph, 3w, Wye Grounded+2
3ph, 3w, Wye, Resistance Grounded+2
3ph, 4w, Open Delta, Centre-Tapped+2
3ph, 4w, Delta, Centre-Tapped+2
3ph, 4w, Wye, Ungrounded+2
3ph, 4w, Wye Grounded
3ph, 4w, Wye, Resistance Grounded+2
+1
Additional error of ± 2 % between 10 mA to 50 mA, ± 1 % between 50 mA to 100 mA
+2
Through communication
10 PLSED310053EN
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
DM6x00H
DM6x00H series
Mechanical characteristics
Weight ~ 300 g (10.6 oz)
IP degree of protection IP 51 front side, IP 54 with gasket (optional accessory), IP 30-meter body, tested as per IEC 60529
Material Polycarbonate meets UL 94V-0 flammability rating
Dimensions W x H x D 96 x 96 x 49 mm (3.78 x 3.78x1.93 in) maximum depth of the meter from housing mounting flange and 13 mm (0.51 in)
protrusion of meter from housing flange
Mounting position Vertical
Panel thickness 5 mm (0.196 in) maximum
Environmental characteristics
Operating temperature -10 to 60 °C (+14 to 140 °F)
Storage temperature - 20 to 70 °C (-4 to 158 °F)
Humidity rating 5 to 95 % RH non-condensing
Pollution degree 2
Altitude ≤2000 m (6562 ft) Category III
Product life >7 years
Insulation category Double insulation for user accessible parts
Electromagnetic compatibility (tested as per IEC 61326-1)
Electrostatic discharge IEC 61000-4-2
Immunity to radiated field IEC 61000-4-3
Immunity to fast transients IEC 61000-4-4
Immunity to impulse waves IEC 61000-4-5
Conducted immunity IEC 61000-4-6
Immunity to magnetic fields IEC 61000-4-8
Immunity to voltage dips IEC 61000-4-11
Emissions Emissions FCC Part 15 Class A/CE
Safety
Europe CE, as per IEC 61010-1 edition 3
US and Canada cULus as per UL61010-1 and CAN/CSA-C22.2 IEC 61010-1 edition 3, for 480 V AC L-L
Measurement Category (Voltage inputs) CAT III up to 480 V L-L
Overvoltage Category (Control power) CAT III up to 300 V L-N
Dielectric As per IEC/UL 61010-1 edition 3
Protective Class II, Double insulated for user accessible parts
Green premium EOL, REACH , PEP, RoHS complied
Other certification RCM & EAC for Russia
Communication
RS-485 port Modbus RTU: 2-Wires, with ground & shield, 4800, 9600, 19200 or 38400 baud, Parity - Even, Odd, None, 1 stop bit if parity is
Odd or Even, 2 stop bits if None
DLF3000: Firmware update through communication port
Isolation 2.5 kV RMS, double insulated
Protection features User configurable password (selectable from 0000 to 9999) protected for set-up
Display language English
Technical publication Printed installation guide (QSG) supplied with meter in multi-language (EN, ES, FR, DE, PT, RU, TR, ZH) and user guide in soft
format
Human machine interface
Display type 8 segment Alpha-numeric LED, ~ 14.2 mm (0.55 in) height, 3 rows with 4 digits per row, 1 column of 12 LEDs to indicate
percentage of load connected in system. 4 digits for VAF PF parameters with auto scrolling and auto range
Keypad 4 buttons for navigation at the front, combination of 2 buttons for lock/unlocking of commonly viewed page
Communications activity Green LED (for indicating RS-485 interface or heartbeat pulse)
PLSED310053N 11
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
DM6x00H
DM6x00H VAF PF meter installation
PB119373
PB119374
PB119375
DM6x00H VAF PF meter mechanical dimensions
PB119372
C Up key: To navigate up
<
A
B LED indicators
E Current inputs
G Retainer clip
H Control power
I Control power
G
12 PLSED310053EN
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
™
EasyLogic
PM1120H series
The EasyLogic™ PM1120H basic power and energy meters
Offering all the measurement capabilities required to monitor the electrical installation in a single 96 x 96 mm unit, with 8
segment alpha-numeric bright, large 14.2 mm high LED display.
PB119319
PLSED310053N 13
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
PM1120H
EasyLogic™ PM1120H meters are ideal replacements for multiple analogue meters
for stand-alone metering in custom panels, switch boards, switch-gear, genset
PB119319
panels, motor control centres, power factor improvement panels and OEM panel
board.
• Application
–– Cost management applications
–– Measurement of basic electrical parameters in control panels,
motor control panels, power distribution boards, OEM’s, Building
management systems, panel instrumentation
–– Aggregation of energy consumption and cost allocation per area, per
usage, per shift and per time within the same facility
–– Network management applications
–– Power quality analysis (THD %)
–– Demand measurement
EasyLogic™ PM1120H power meter front ISO view
–– Measurement of Power factor
–– Phase angle between the voltage and current
–– % unbalance among voltage and current
PB119323
–– Class 1.0 for active energy as per the test limits given in IEC 62053-21
–– Class 0.5 for active energy as per the test limits given in IEC 62053-22
–– Class 2.0 for reactive energy as per the test limits given in IEC 62053-23
–– Tested in accordance with IEC 62052-11 for energy test requirements
–– EMI/ EMC tests: As per IEC 61326-1
–– CT nominal: 5 A or 1 A I-nominal (field settable). CT reversal auto
correction for energy consumption.
–– Password: Field configurable password for securing set up information and
prevents tampering of integrated values.
–– Cyber security: Option for disabling RS-485 port through front panel keys
against unauthorized access. This feature can also be used for maintenance
and troubleshooting of complex communication network.
–– Display: Auto scaling, 4 digits for Instantaneous parameters and 5+3 digits
EasyLogic™ PM1120H power meter rear view
for energy parameter with auto scale and auto range capability.
–– Analogue load bar: The colour-coded analogue load bar at the front side
indicates the percentage of load through 12 LED’s with the option to select
full scale based on connected load.
–– Suppression current: To disregard the measurement of induced and panel
auxiliary load current in the circuit (settable from 5 to 99 mA)
–– Protective cover: Tamper-proof terminal screws do not detach from housing
14 PLSED310053EN
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
PM1120H
PM1120H technical specifications
General
Use on LV & MV systems with Potential transformer (PT or VT)/ Current transformer (CT) ratio programmable at site
Digital panel meters for measurement of basic electrical parameters
Instantaneous rms values
Current Average line current of 3-phase, per-phase, and calculated neutral current
Voltage Average voltage of L-L, L-N parameters, per-phase
Frequency Any available line
Real (active), reactive, and apparent power Total and per-phase
True power factor Average and per-phase signed
% Unbalance Maximum % unbalance among phases for Volts & Amps
Revolution per minute (RPM) RPM of alternator or generator when number of poles set for 2, 4, 6, 8, 12, 14 or 16 (any one pole)
Energy values stored in non-volatile memory
Delivered or forward or import energy from the grid - Accumulated or integrated active (Real - Wh), reactive (VARh) and apparent (VAh) energy
Time counters such as meter ON Hrs, load RUN Hrs and power outage counters
Old registers facilitate retrieval of last cleared energy values and load Run Hrs
Display
Bright red colour LED display, 8 segment alphanumeric LED, ~ 14.2 mm (0.55 in) height, 3 rows with 4 digits per row, auto range, auto scale
Communication
RS-485 serial channel connection Industry standard Modbus RTU protocol
Native Plug and Play support for Schneider Electric energy management system software - EcoStruxure Power Monitoring Expert, EcoStruxure Power SCADA
Operation along with ION Setup programming support
Diagnostics
Diagnostic page indicates the healthiness of communication system, all LED test, device serial number, device model number OS & RS version,
communication status, error code display
Page lock
Page lock and unlock features. Once the commonly referred page is enabled for lock feature, then the display returns to locked page in 4 minutes of inactive
time
Favourite page
Number and type of parameters can be chosen and arranged in Favourite page according to the user’s requirement
Electrical characteristics
Type of measurement True RMS, 4 quadrant power and 2 quadrant energy, 32 samples/ cycle
Measurement accuracy
Current, per-phase & average ± 0.5 % of reading
Voltage, L-N, L-L, per-phase & average ± 0.5 % of reading
Power (active and apparent) ± 1.0 % for Class 1.0, ± 0.5% for Class 0.5
Power (reactive) ± 2.0 % for Class 1.0 & Class 0.5
Power factor, per-phase & average ± 0.01 of reading
Frequency ± 0.05 % for F-nominal 50/ 60 Hz ± 2
± 0.2 % for Frequency range from 30 to 48 Hz, 52 to 58 Hz and 62 to 70 Hz
Active or real energy Class 1.0 (± 1.0 %) Class 0.5 (± 0.5%)
Apparent energy ± 1.0 % & ± 0.5 %
Reactive energy Class 2.0 (± 2.0 %)
THD % ± 5 % of reading
Input-voltage
VT (PT) connection Selectable from No VT (direct), 1 VT, 2 VT to 3 VT
VT (PT) primary 100 V L-L to 999 kV L-L max
U (V) nominal (secondary) Up to 277 V L-N/ 480 V L-L (selectable VT secondary from 100, 110, 115, 120 to 415 V L-L)
Operating voltage range with accuracy 80-480 V L-L ± 10 % Category III
Measured Voltage with full range 35 to 600 V L-L
Permanent overload (withstand) 750 V L-L, continuous
Impedance ≥5 MΩ
Frequency range 50/ 60 Hz ± 2
VA burden ≤0.2 VA at 240 V L-N at 50 Hz
Frequency – measurement
Nominal operating range 50/60 Hz ± 2 (± 0.05 % accuracy)
Extended operating range 30 to 48 Hz, 52 to 58 Hz and 62 to 70 Hz (± 0.2 % accuracy)
Voltage input 80 to 480 V L-L ± 10 %
PLSED310053N 15
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
PM1120H
PM1120H technical specifications (continued)
Input-current
CT connect Solo or multi-phase current measurement by installing CT (s) in either of A1, A2, A3, A12, A23, A13, A123 phase(s)
CT primary 1 A to 32767 Amps, programmable
CT secondary 1 A or 5 Amps I-nominal (field settable)
Operating current range with accuracy 10 mA to 6 A+1
Measured Amps with full range 5 mA to 10 A
Suppression current 5 to 99 mA (to disregard negligible load)
Permanent overload (withstand) Continuous 10 A, 10 s/hr 50 A, 1s/hr 500 A
Impedance 0.3 mΩ
Frequency range 50/60 Hz ± 2
VA burden ≤0.1 VA at 5 A, 50 Hz
AC - control power
Operating range 48 to 277 V L-N AC ± 10 %
Burden ≤4 VA at 240 V L-N, 50 Hz
Frequency 50/60 Hz nominal (45 to 65 Hz operating range)
Ride-through time 200 ms at 240 V L-N, 50Hz
DC - control power
Operating range 48 to 277 V DC ± 10 %
Burden ≤2 W at 240 V DC
Ride-through time 120 ms at 240 V DC
Display update
Instantaneous/ RMS parameters 1s
Demand parameters 5s
THD % (voltage and current) 5s
Power system
Phase labelling Configurable to 123, ABC, rst, pqr or ryb
+1
Additional error of ± 2 % between 10 mA to 50 mA, ± 1% between 50 mA to 100 mA)
+2
Through communication
16 PLSED310053EN
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
PM1120H
PM1120H technical specifications (continued)
Electromagnetic compatibility (tested as per IEC 61326-1)
Electrostatic discharge IEC 61000-4-2
Immunity to radiated field IEC 61000-4-3
Immunity to fast transients IEC 61000-4-4
Immunity to impulse waves IEC 61000-4-5
Conducted immunity IEC 61000-4-6
Immunity to magnetic fields IEC 61000-4-8
Immunity to voltage dips IEC 61000-4-11
Emissions Emissions FCC Part 15 Class A/CE
Safety
Europe CE, as per IEC 61010-1 edition-3
US and Canada cULus as per UL61010-1 and CAN/CSA-C22.2 IEC 61010-1 edition-3, for 480 V AC L-L
Measurement Category (Voltage inputs) CAT III up to 480 V L-L
Overvoltage Category (Control power) CAT III up to 300 V L-N
Dielectric As per IEC/UL 61010-1 edition-3
Protective Class II, Double insulated for user accessible parts
Green premium EOL, REACH , PEP, RoHS complied
Other certification RCM & EAC for Russia
Communication
RS-485 port Modbus RTU: 2-Wires, 4800, 9600, 19200 or 38400 baud, Parity - Even, Odd, None, 1 stop bit if parity is Odd or
Even, 2 stop bits if none.
DLF3000: Firmware update through communication port
Energy+3 - delivered or forward or import energy: Wh, VAh, VARh, one energy b b
measurement at a time
Demand parameters – selectable for W, VA, VAR (one at a time) b b
Old registers - retrieval of last cleared values of energy and Run Hrs b b
Revolutions per minute (RPM) b b
Phase angle : Amp Deg (V to Amps, per-phase) b b
% Unbalance: Max unbalance Volts & Amps among 3 phase (s) b b
Life time counter - meter ON Hrs, Load Run Hrs and number of power interruptions b b
Communication: 2 wire, RS-485, Modbus RTU protocol b b
Commercial reference number METSEPM1120HCL10RS METSEPM1120HCL05RS
+3 Energy measurement depends on power parameter selected during set up (W/Wh or VA/VAh or VAR/VARh). For reactive energy (VARh), total or net VARh
on display, + VARh and - VARh through communication
PLSED310053N 17
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
PM1120H
PM1120H meter mounting
PB119373
PB119374
PB119375
PM1120H meter mechanical dimensions
PB119372
Up key: To navigate up
<
D
< Right/OK key: To navigate right/Enter key
C
B LED indicators
B
C Alpha numeric LED display
E Current inputs
I H
PB119381
F RS-485
G Retainer clip
H Control power
I Voltage inputs
18 PLSED310053EN
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
™
The EasyLogic PM1130H
dual/alternate source
power and energy meters
Two energy registers (Utility vs Genset, Utility vs Solar, Utility vs Wind, or a combination of any two power sources) separately
records consumption for dual source energy accounting. Ideal for any installation which requires split energy monitoring
for two conditions, e.g., running and Idle. Form A relay to control the load in the event of abnormality in the electrical circuit
including excess consumption of power. The meters can be used for secondary billing application in large commercial
complexes or buildings as tenant meters in custom panels, switch boards, switchgear, genset panels, non-renewable energy
panel and OEM panel board.
Offering all the measurement capabilities required to monitor the electrical installation in a single 96 x 96 mm unit, with 8
segment alpha-numeric bright, large 14.2 mm high LED display.
PB119318
PLSED310053N 19
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
PM1130H
• Applications
PB119318
–– Easy to install: two retainer clips, no tools required. Compact meter with 49
mm meter depth behind the panel, connectable up to 480 V +10 % AC V
L-L without voltage transformers for installation compliant with measurement
category III, and double insulated
–– Easy to operate: Intuitive navigation with self-guided menus and
heartbeat LED indicates normal functioning of meters while it conveys the
communication status when connected to RS-485 network
–– LED display: Intuitive navigation, four buttons, 8 segment alpha-numeric
LEDs and three lines of concurrent values with Kilo & Mega value indicator
–– Power and energy: measurement, display and recording of any one power
and energy from source 1 and source 2 at a time (W/ Wh or VA/ VAh or VAR/
VARh – selectable through panel button or configuration software)
–– Demand: measure Peak demand with occurrence time in counter, time
remaining to complete demand cycle, present cycle and last cycle demand
EasyLogic™ PM1130H dual source meter rear view values. One demand parameter selectable - either W, VA or VAR, with the
option of changing demand interval and demand technique
–– Standard compliance:
–– Class 0.5 for active energy as per IEC 62053-22
–– Class 2.0 for reactive energy as per IEC 62053-23
–– Tested in accordance with IEC 62052-11 for energy test requirements
–– EMI/ EMC tests: As per IEC 61326-1
–– CT nominal: 5 A or 1 A I-nominal (field settable). CT reversal auto
correction for energy consumption.
–– Password: Field configurable password prevents tampering
–– Cyber security: disable RS-485 port through front panel keys against
unauthorized access, also useful for maintenance and troubleshooting
–– Auto scaling, 4 digits for Instantaneous parameters and 5+3 digits for
energy parameter with auto scale and auto range capability
–– Analogue load bar: colour-coded bar indicates percentage of load via 12
LED’s with the option to select full scale based on connected load
–– Suppression current: Meter can be set to disregard the measurement of
induced/ auxiliary load current in the circuit (settable from 5 mA to 99 mA)
–– Favourite page: User selectable parameters in favourite page
–– Relay: Form A, 2 terminals mechanical relay for alarm, control or
annunciation if parameters exceeds or recedes set limit. Also activated on
decremental energy from the preset energy value.
–– Alternate/dual source power sensor: supports multiple generator paralleling
and bus coupler islanding schemes
–– Tamper cover protects against tampering with voltage and current terminals
–– Non-resettable energy counter to ensure integrity of energy readings
20 PLSED310053EN
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
PM1130H
PM1130H technical specifications
General
Use on LV & MV systems with Potential transformer (PT or VT) / Current transformer (CT) ratio programmable at site
Digital panel meters for measurement of basic electrical parameters
Instantaneous rms values
Current Average line current of 3-phase, per-phase, and calculated neutral current
Voltage Average voltage of L-L, L-N parameters, per-phase
Frequency Any available line
Real (active), reactive, and apparent power Total and per-phase
True power factor Average and per-phase signed
% Unbalance Maximum % unbalance among phases for Volts & Amps
Revolution per minute (RPM) RPM of alternator or generator when number of poles set for 2, 4, 6, 8, 12, 14 or 16 (any one pole)
Energy values stored in non-volatile memory
Energy delivered from power source no.1: Accumulated active (Real - Wh) or reactive (VARh) or apparent (VAh) energy with user programmable alpha-
numeric name
Energy delivered from power source no.2: Accumulated active (Real - Wh) or reactive (VARh) or apparent (VAh) energy with user programmable alpha-
numeric name
Time counters such as meter ON Hrs, load RUN Hrs for both source of power and power outage counters
Old registers facilitate retrieval of last cleared energy values and load Run Hrs
Display
Bright red colour LED display, 8 segment alpha-numeric LED, ~ 14.2 mm (0.55 in) height, 3 rows with 4 digits per row, auto range, auto scale
Communication
RS-485 serial Channel connection Industry standard Modbus RTU protocol, Integration with any Modbus compatible
SCADA / DCS / PMS / EMS / BAS / BMS software
Native Plug and Play support Schneider Electric energy management system software - EcoStruxure™ Power Monitoring Expert,
EcoStruxure™ Power SCADA Operation along with ION Setup programming support
Alternate or dual source sensor For sensing the presence of alternate power source to measure and record energy in separate registers
Diagnostics
Diagnostic page indicates the healthiness of communication system, all LED test, device serial number, device model number OS & RS version,
communication status, error code display
Page lock
Page lock and unlock features. Once the commonly referred page is enabled for lock feature, then the display returns to locked page in 4 minutes of inactive
time
Favourite page
Number and type of parameters can be chosen and arranged in Favourite page according to the user’s requirement
Relay
Relay can be operated based on the set limits assigned for V L-L, V L-N, A, Hz, PF, Instantaneous power (W, VA, VAR), demand parameter (W, VA, VAR)
Relay can also be programmed to activate based on decremental energy consumed in the system from the preset energy value
Electrical characteristics
Type of measurement True RMS, 4 quadrant power and 2 quadrant energy, 32 samples/ cycle
Measurement accuracy
Current, per-phase & average ± 0.5 % of reading
Voltage, L-N, L-L, per-phase & average ± 0.5 % of reading
Power (active and apparent) ± 0.5 % for Class 0.5
Power (reactive) ± 2.0 % for Class 0.5
Power factor, per-phase & average ± 0.01 of reading
Frequency ± 0.05 % for F-nominal 50/ 60 Hz ± 2
± 0.2 % for Frequency range from 30 to 48 Hz, 52 to 58 Hz and 62 to 70 Hz
Active or real energy Class 0.5 (± 0.5 %)
Apparent energy ± 0.5 %
Reactive energy Class 2.0 (± 2.0 %)
THD % ± 5 % of reading
Input-voltage
VT (PT) connection Selectable from No VT (direct), 1 VT, 2 VT to 3 VT
VT (PT) primary 100 V L-L to 999 kV L-L max
U (V) nominal (secondary) Up to 277 V L-N/ 480 V L-L (selectable VT secondary from 100, 110, 115, 120 to 415 V L-L)
Operating voltage range with accuracy 80-480 V L-L ± 10 % Category III
Measured Voltage with full range 35 to 600 V L-L
Permanent overload (withstand) 750 V L-L, continuous
Impedance ≥5 MΩ
Frequency range 50/60 Hz ± 2
VA burden ≤0.2 VA at 240 V L-N at 50 Hz
PLSED310053N 21
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
PM1130H
Frequency – measurement
Nominal operating range 50/60 Hz ± 2 (± 0.05 % accuracy)
Extended operating range 30 to 48 Hz, 52 to 58 Hz and 62 to 70 Hz
Voltage input 80 to 480 V L-L ± 10 %
Input-current
CT connect Solo or multi-phase current measurement by installing CT (s) in either of A1, A2, A3, A12, A23, A13, A123 phase(s)
CT primary 1 A to 32767 A programmable
CT secondary 1 A or 5 A I-nominal (field settable)
Operating current range with accuracy 10 mA to 6 A+1
Measured Amps with full range 5 mA to 10 A
Suppression current 5 to 99 mA (to disregard negligible load)
Permanent overload (withstand) Continuous 10 A, 10s/hr 50 A, 1s/hr 500 A
Impedance 0.3 mΩ
Frequency range 50/ 60 Hz ± 2
VA burden ≤0.1 VA at 5A, 50 Hz
AC - control power
Operating range 60 to 277 V L-N AC ±10 %
Burden ≤6 V A at 240 V L-N, 50 Hz
Frequency 50/ 60 Hz nominal (45 to 65 Hz operating range)
Ride-through time 120 ms at 240 V L-N, 50Hz
DC - control power
Operating range 60 to 277 V L-N DC ±10 %
Burden ≤3 W at 240 V DC
Ride-through time 120 ms at 240 V DC
Display update
Instantaneous/ RMS parameters 1s
Demand parameters 5s
THD % (voltage and current) 5s
Power system
Phase labelling Configurable to 123, ABC, rst, pqr or ryb
Energy source labelling – one letter alpha-numeric, A to Y (except X), or 0 to 9
programmable
Wiring configuration 13 wiring schemes (5 on front screen)
1ph, 2 w, LN
1ph, 2 w, LL
1ph, 3 w, LL with N (2-phase)
3ph, 3 w, Delta, Ungrounded
3ph, 3 w, Delta, Corner Grounded+2
3ph, 3 w, Wye, Ungrounded+2
3ph, 3 w, Wye Grounded+2
3ph, 3 w, Wye, Resistance Grounded+2
3ph, 4 w, Open Delta, Center-Tapped+2
3ph, 4 w, Delta, Center-Tapped+2
3ph, 4 w, Wye, Ungrounded+2
3ph, 4 w, Wye Grounded
3ph, 4 w, Wye, Resistance Grounded+2
Mechanical characteristics
Weight ~ 300 g (10.6 oz)
IP degree of protection IP 51 front side, IP 54 with gasket (optional accessory), IP 30-meter body, tested as per IEC 60529
Material Polycarbonate meets UL 94V-0 flammability rating
Dimensions W x H x D 96 x 96 x 52 mm (3.78 x 3.78 x 2.05 in) (D = depth of the meter from housing mounting flange)
13 mm (0.51 in) protrusion of meter from housing flange
Mounting position vertical
Panel thickness 5 mm (0.196 in) maximum
Environmental characteristics
Operating temperature - 10 to +60º C (+14 to +140º F)
Storage temperature - 20 to +70º C (-4 to +158º F)
Humidity rating 5 to 95 % RH non-condensing
Pollution degree 2
Attitude ≤2000 metres (6561 ft), Category III
Product life >7 years
Insulation category Double insulation for user accessible parts
Insulation category Double insulation for user accessible parts
+1
Additional error of ±2 % between 10 mA to 50 mA, ±1 % between 50 mA to 100 mA
+2
Through Communication
22 PLSED310053EN
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
PM1130H
Electromagnetic compatibility (tested as per IEC 61326-1)
Electrostatic discharge IEC 61000-4-2
Immunity to radiated field IEC 61000-4-3
Immunity to fast transients IEC 61000-4-4
Immunity to impulse waves IEC 61000-4-5
Conducted immunity IEC 61000-4-6
Immunity to magnetic fields IEC 61000-4-8
Immunity to voltage dips IEC 61000-4-11
Emissions Emissions FCC Part 15 Class A/CE
Safety
Europe CE, as per IEC 61010-1 edition- 3
US and Canada cULus as per UL61010-1 and CAN/CSA-C22.2 IEC 61010-1 edition-3, for 480 V AC L-L
Measurement Category (Voltage inputs) CAT III up to 480 V L-L
Overvoltage Category (Control power) CAT III up to 300 V L-N
Dielectric As per IEC/UL 61010-1 edition-3
Protective Class II, Double insulated for user accessible parts
Green premium EOL, REACH , PEP, RoHS complied
Other certification RCM & EAC for Russia
Communication
RS-485 port Modbus RTU: 2-Wires, 4800, 9600, 19200 or 38400 baud, Parity - Even, Odd, None, 1 stop bit if parity is Odd or
Even, 2 stop bits if none.
Alternate or dual source sensor 2 pin connector, suitable for pair of 1.5 sq mm multi-strand or single strand cable
AC: 80 – 277 V ±10 % ON status, 0 to 30 V OFF status
DC: 18 – 60 V ±10 % ON status, 0 to 4 V OFF status
Relay output Form A relay, 2 pin terminals, 300 V L-N AC max. / 2 A; 24 V DC / 2 A
Isolation 2.5 kV RMS, double insulated
Protection features User configurable password (selectable from 0000 to 9999) protected for set-up and clearing of energy, and
other integrated data
Display language English
Technical publication Printed installation guide (QSG) supplied with meter in multi-language (EN, ES, FR, DE, PT, RU, TR, ZH) and user
guide in soft format
Human machine interface
Display type 8 segment alphanumeric LED, ~ 14.2 mm (0.55 in) height, 3 rows with 4 digits per row, 1 column of 12 LEDs
to indicate percentage of load connected in system. 4 digits for instantaneous parameters and 5+3 digits for
energy parameters with auto scrolling and auto range
Keypad 4 buttons for navigation at the front, combination of 2 buttons for lock/unlock pages
CAL LED (pulse LED) Red colour, meter constant is configurable from 1 to 9999000 pulses/ k_h (kWh, kVAh, or kVARh)
Comm. activity Green LED (for indicating RS-485 interface or heart beat pulse)
Alternate or dual source LED Red colour LED glows continuously during the presence of AC or DC voltage across the dual source sensor
PLSED310053N 23
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
PM1130H
PM1130H dual source meter mounting
PB119373
PB119374
PB119375
PM1130H dual source meter mechanical dimensions
PB119372
Up key: To navigate up
<
D
< Right/OK key: To navigate right/Enter key
C LED indicators
C – Red: Pulse
– Green: Heartbeat
B
A D Alpha numberic LED display
L K
E Analogue load bar
PB119379
F Current inputs
I Retainer clip
L Voltage inputs
H
F
G
24 PLSED310053EN
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
EasyLogic
PM2000 series
The EasyLogic™ PM2000 multi-function power and energy meter
Offering all the measurement capabilities required to monitor and electrical installation in a single 96 x 96 mm unit, with LED or
LCD display options.
Applications
Cost management applications
• Bill checking to verify that you are only charged for the energy you use
• Aggregation of energy consumption, including WAGES, and cost allocation per area, per usage, per shift or
per time within the same facility
• Energy cost and usage analysis per zone, per usage or per time period to optimise energy usage
• Metering of electrical parameters to better understand the behaviour of your electrical distribution system
• Power quality analysis
PB115532
PLSED310053N 25
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
PM2000
PB114325
Introducing EasyLogic PM2000 series, next generation power meter which offers all
the measurement capabilities required to monitor an electrical installation in a single
96 x 96 mm unit. PM2000 meters are available in LED and LCD display variants.
• PM2100 series:
–– LED display type: Intuitive navigation with self-guided, three buttons,
bright red colour LEDs of 14.2 mm height. Two columns of LEDs
indicate the parameter name chosen for display
• PM2200 series:
–– LCD display type: Monochrome graphical LCD of 128 x 128 resolution
lets users read all three phase values simultaneously. The bright display
enables easy reading even in extreme lighting conditions and viewing
angles., with intuitive menus, multi-language text, icons and graphics.
• Network management:
PM2000 series LED display meter
–– Power quality analysis: THD % and individual harmonics to 15th and 31st order
–– Measurement of True PF and Displacement PF
–– Recording Min/Max values of instantaneous parameters with date &
PB115531
timestamp
–– Optional IO modules comprising either 2 Digital Inputs and 2 Outputs, or 2
Analogue Inputs and 2 Outputs for comprehensive WAGES monitoring
–– Calculates % unbalance for voltage & current
–– Embedded 2 D/I and 2 D/O in PM2125 and PM2225 meters
• Main characteristics:
–– Easy to install: Mounts using two clips, no tools are required. Compact
54 mm depth, connectable up to 480 ±10% AC Volts L-L without voltage
transformers for installations compliant with measurement category III, and
double insulated.
–– Easy to operate: Intuitive navigation with self-guided menus and LED for test
and calibration on site or lab. Heart-beat LED indicates normal functioning
and communication status if connected to RS-485 network.
PM2000 LCD display –– Product standard compliance
–– Active energy Class 1.0 as per IEC 62053-21
–– Active energy Class 0.5S as per IEC 62053-22 (partial compliance for
Feature selection active energy test clause only)
Commercial ref. number Model
–– Reactive energy Class 1.0 as per IEC 62053-24 (partial compliance for
METSEPM2110 PM2110 reactive energy test clause only)
METSEPM2120 PM2120 –– Tested in accordance with IEC 62052-11 standard for
METSEPM2125CL05 PM2125+1 –– 5 A, I-nominal
METSEPM2130 PM2130 –– 1 A, I-nominal (field settable).
METSEPM2210 PM2210
METSEPM2220 PM2220
METSEPM2225CL05 PM2225+1
METSEPM2230 PM2230
METSEPM2KDGTLIO22 PM2K2DIDO
METSEPM2KANLGIO22 PM2K2AIAO
METSEPM2KANLGIO11 PM2K1AIAO
+1
Available in China only
26 PLSED310053EN
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
PM2000
• Main characteristics: (cont'd)
–– Power quality analysis: The PM2000 offers THD % measurements and
Individual harmonics up to15th order in PM2x20 variants and up to 31st in
PM2x30 variants.
–– Load management: Simultaneous display of peak, present, predicted &
rising demands of all the four demand parameters (W, VA, VAR, Amps)
–– Billing: Tenant billing/utility meter cross check (where local regulations are
not applicable).
–– Timer: Active load timer, Meter operation timer and Run hours timer. These
features help advise maintenance requirements and scheduling.
–– Password: Field configurable password for securing set up information and
prevent tampering of integrated values.
–– Cyber security: Option for disabling RS-485 port through front panel
keys against unauthorized access. It helps during installation and trouble
shooting of communication network.
–– LED display: Auto scaling, 9+3 digits for energy, 4 digits for other
parameters.
–– LCD display: 5 digits for energy, 5 or 6 digits for other parameters, with auto
scaling.
–– Daily time snap shot: Snap shot of Avg Voltage, Avg Current, Total Active Power
& Energy delivered as measured by the meter at configurable time of day. The
static page will be refreshed with new values at a configured time next day..
–– Rate counters: 2 configurable counters display values in custom specified
units based on energy recorded (e.g., kgCO2 carbon emission or energy
cost).
–– Energy preset feature: For retrofit application.
PLSED310053N 27
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
PM2000
PM2000 technical specifications
General
Use on LV and MV systems with onsite programmable PT/CT ratio
Basic metering with THD %, Individual Harmonics, RTC and min/max readings
Instantaneous rms values
Current Average line current of 3-phase, per-phase, and calculated neutral
Timer Accumulated time counters for active load timer, meter operation
Old Registers Facilitates retrieval of last cleared energy values
Rear of PM2000 closed
Demand values
Current average Present, Last, Predicted, Peak, and Peak Date Time
Active power Present, Last, Predicted, Peak, and Peak Date Time
Reactive power Present, Last, Predicted, Peak, and Peak Date Time
Apparent power Present, Last, Predicted, Peak, and Peak Date Time
Demand sync methods Thermal, Timed, Command Sync, and Clocked Sync
Demand calculation mode Sliding, fixed and rolling block
Demand intervals Settable from 1 to 60 minutes, in the step of 1 minute
Display
PM2100 series Bright red colour LED display, 7 segment LED, ~ 14.2 mm height, 3 rows
PM2200 series Full scape, monochrome graphical LCD of 128 x 128 resolution with
Visualization mode for signs IEC or IEEE type in LCD display meter
Communication
RS-485 serial Channel connection Industry standard Modbus RTU protocol
Integration with software SCADA/ DCS/ PMS/ EMS/ BAS/ BMS software
Native Plug and Play support Schneider Electric energy management system software -
EcoStruxure™Power Monitoring Expert, EcoStruxure PowerSCADA
Operation, & ION Setup programming support
Alarms
Alarming with time stamping in PM2x30 A different combination of set point driven alarms and digital
meters alarms with 1 s time stamping. The alarms can be programmed and
combined to trigger digital outputs, the meter keeps an alarm logs
with the active and historical alarms with date and time stamping in
40 registers
Diagnostics
Diagnostic page Indicates LED/LCD status, sl number, diag pages, OS & RS version
Lock/ Un-Lock
Page Lock & Unlock Unique feature to ensures that commonly referred page is restored
(PM2100 series) in 4 minutes of inactive time
Rate 1 counter +2
kgCO2 emission (example) Rate counter can be configured to display the CO2 emission in
kgCO2 format based on the kWh measured either in delivered or
received direction.
Rate 2 counter+2
Tariff counter (example) Rate counter can also be configured to calculate the electricity cost
based on the energy consumption in customized currency format.
12am snap shot
12am snap shot+2 Snap shot of Avg Voltage, Avg Current, Total Active Power & Energy
Rear of PM2000 without I/O module delivered as measured by the meter at 12am. Static page is refreshed
with new values by 12am next day.
+2
Available in PM2220/PM2230 (LCD) meters
28 PLSED310053EN
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
PM2000
PM2000 electrical characteristics
Electrical characteristics
Type of measurement True RMS 64 samples per cycle
PB114320
Measurement accuracy
DC control power
Operating range 48-277 V DC ±10% (100-277 V AC ±10% with I/O card)
Burden < 2 W at 277 V DC (< 3.3 W for PM2x30 and PM2x25C)
Ride-through time 50 ms typical at 125 V DC and maximum burden
Real time clock
RTC with battery backup 3 years (when meter is in Power OFF condition)
Displays update
Instantaneous 1s
Demand 15 s
Harmonics 5s
Wiring configuration
User programmable 1ph, 2w, L-N
1ph, 2w, L-L
1ph, 3w, L-L with N (2phase)
3ph, 3w, Delta, Ungrounded
3ph, 3w, Delta, Corner Grounded+4
3ph, 3w, Wye, Ungrounded+4
3ph, 3w, Wye Grounded+4
3ph, 3w, Wye, Resistance Grounded+4
3ph, 4w, Open Delta, Center-Tapped+4
3ph, 4w, Delta, Center-Tapped+4
3ph, 4w, Wye, Ungrounded+4
3ph, 4w, Wye Grounded
3ph, 4w, Wye, Resistance Grounded+4
+3
For 1 A CT nominal, additional error of ±1 % from 50 mA to 150 mA, ±2 % for current > 10
mA to < 50 mA. Partial standard compliance for Class 0.5S meter type (energy test clause only)
+4
Through communication in PM2100 series meters
PLSED310053N 29
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
PM2000
PM2000 series mechanical characteristics
Mechanical characteristics
Weight ~ 300 gm
IP degree of protection IP54 front side, IP30 meter body as per IEC 60529
Material Polycarbonate meets UL 94V-0 flammability rating
Dimensions W x H x D 96 x 96 x 54 mm maximum (depth of the meter from housing mounting flange) and 13 mm (protrusion of meter from housing
flange). Meter depth with IO module is 74 mm
Mounting position Vertical
Panel thickness 5 mm maximum
Environmental characteristics
Operating temperature Meter -10 to +60 °C (14 to 140 °F)
Storage temperature Meter -25 to +70 °C (-13 to 158 °F)
Humidity rating 5 to 95% RH non condensing
Pollution degree 2
Altitude ≤ 2000 m (6562 ft) Category III
Product life Minimum 7 years
Electromagnetic compatibility (tested as per IEC 61326-1)
Electrostatic discharge IEC 61000-4-2
Immunity to radiated field IEC 61000-4-3
Immunity to fast transients IEC 61000-4-4
Immunity to impulse waves IEC 61000-4-5
Conducted immunity IEC 61000-4-6
Immunity to magnetic fields IEC 61000-4-8
Immunity to voltage dips IEC 61000-4-11
Emissions Emissions FCC Part 15 Class A/CE
Safety
Europe CE, as per IEC 61010-1 Ed-3
US and Canada cULus as per UL61010-1 and CAN/CSA-C22.2 No. 61010-1, for 600V AC
Measurement Category (Voltage CAT III up to 480 V L-L
Overvoltage Category (Control power) CAT III up to 300 V L-N
Dielectric As per IEC/UL 61010-1 Ed-3
Protective Class II, Double insulated for user accessible parts
Green premium EOL, REACH, PEP, RoHS complied
Other certification RCM (Australia), EAC (Russia)
Communication
RS-485 port Modbus RTU: 2-Wires, with ground & shield, 4800, 9600, 19200 or 38400 baud, Parity - Even, Odd, None, 1 stop bit if parity
is Odd or Even, 2 stop bits if None
Pulse Output – POP Max 40 V DC, 20 mA 20 ms ON time
Configurable pulse weight from 1 to 9999000 pulses/k_h (kWh, kVAh, or kVARh)
Isolation 2.5 kV RMS, double insulated
Protection features Password protected for set-up & clearing energy and Min/Max data
Display language English, Spanish, French, Chinese, German, Portugese, Russian, Turkish
Technical publication Printed installation guide (IG) with the meter in multi language (EN,ES,FR,DE,PT, RU,TR,ZH)
Human machine interface
Display type LED display: 7 segment LED, ~ 14.2 mm height, 3 rows with 4 digits per row 2 columns of LEDs, one on each side of the
LED panel to indicate the parameters under measurement
Keypad PM2100 series: 3 buttons for navigation & combination of 2 buttons for performing set-up, Lock/unlocking of page,
Diagnostic page operation
CAL LED Indicator Red colour, meter constant is configurable from 1 to 9999000 pulses/k_h (kWh, kVAh, or kVARh)
Comm. activity Green LED (for indicating RS-485 interface or heart beat pulse)
30 PLSED310053EN
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
PM2000
PM2000 series electrical characteristics of IO modules
Status Inputs (Digital Inputs)
Voltage ratings 18.5 to 36 V DC, OFF 0 to 4 V DC
PB115529
PLSED310053N 31
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
PM2000
Feature set summary PM2110 PM2120 PM2125C PM2130 PM2210 PM2220 PM2225C PM2230
Accuracy Class for Wh 1.0 0.5S 1.0 0.5S
Accuracy Class for VARh 1.0
Accuracy for VAh ±0.5 %
Amps, per-phase, average and b
Voltage, V L-N, V L-L, per-phase and b
True PF True PF
Power Factor True PF True PF
Displacement PF1 Displacement PF
Frequency, any available phase b
Power: W, VA, VAR: per phase and total
b
Current Current
3-phase unbalance % Current Current
Voltage+4 Voltage
Demand parameters (Present, Last, b b b b
Predicted and Peak for W, VA, VAR, (no timestamp) (no timestamp)
Amps) Date and Time stamp for peak
+4
Through communication only
+5
Any one IO module can be used at a time with PM2130 or PM2230 meter. The control power range with IO module (including PM2125/ PM2225
references) shall be 72 to 304 V AC L-N or 90 to 304 V DC.
+6
Battery backup duration 3 years when meter is in Power OFF condition.
+7
Individual harmonics, 12am snap shot and rate counter features not available in PM2125/ PM2225 meters
32 PLSED310053EN
EASYLOGIC POWER AND ENERGY METERS DIMENSIONS AND CONNECTION
PM2000
PM2000 LCD display legend description
E Control power
F Voltage inputs
G Current inputs
H RS-485 / POP
I Gasket
J I/O channel slot - optional accessory for PM2230, embedded in PM2225 meter
D Negative indicator
H OK Enter key
J x 1000 indicator
PB115538
K System measurements Vavg, kVA, F, lavg, kW, In, PFavg, kVAR, lunb
P Gasket
PLSED310053N 33
EASYLOGIC POWER AND ENERGY METERS DIMENSIONS AND CONNECTION
PM2000
PM2000 meter rear view Meter installation
PB114323
34 PLSED310053EN
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
EasyLogic
PM2200R Quick Click series
The EasyLogic™ PM2200R multi-function power and energy meter with Quick Click CTs
Offering the same extensive measurement capabilities of the PM2200 meters - now with the option to significantly reduce
installation time, cost, and complexity with new plug & play, 3-in-1 Quick Click CTs.
Applications
Cost management applications
• Bill checking to verify that you are only charged for the energy you use
• Aggregation of energy consumption and cost allocation per area, per usage, per shift or per time within the
same facility
• Energy cost analysis per zone, per usage or per time period to optimise energy consumption
• Metering of electrical parameters to better understand the behaviour of your electrical distribution system
• Power quality analysis
PB119508
PLSED310053N 35
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
PM2200R
Introducing the new Quick Click enabled Easylogic PM2200R series, next generation
PB119501
power meter which offers all of the measurement capabilities of the PM2200 series
with the added benefit of plug & play CT installation. For installers - time, labour, and
rework savings of over 75 % compared to traditionally wired meters and CTs.
• Applications
–– Cost management:
–– Electrical installation remote monitoring
–– Energy accounting and balancing
–– Tenant and sub-billing
–– Panel instrumentation
–– Energy management
• Network management:
PM2200R meter –– Power quality analysis: THD % and individual harmonics up to the 15th order
(PM2200R)
–– Measurement of True PF and Displacement PF
–– Recording Min/Max values of instantaneous parameters with date &
timestamp
–– Calculates % unbalance for voltage & current
• Main characteristics:
–– Simple CT connection and installation with Quick Click-enabled meters and
CTs: A single RJ-45 port on the meter allows for direct connection to the RJ-
45 port on Schneider Electric Quick Click CTs. As Quick Click CTs have a
low voltage output, the shorting block required for traditional 5 A output CTs
is no longer needed. CT input screw terminals on the meter, screw terminals
on the CTs, and screw terminals on the shorting block are all eliminated with
the Quick Click solution.
–– Easy to install: Mounts using two clips, no tools are required. Compact meter
with 54 mm depth, connectable up to 480 ±10 % V AC Volts L-L without
voltage transformers for installations compliant with measurement category
III, and double insulated.
–– Easy to operate: Intuitive navigation with self guided menus and test LED at
the front panel used for test and calibration of the meter on site or laboratory.
Heart-beat LED indicates normal functioning and communication status if
connected to RS-485 network.
–– Product standard compliance
–– Active energy Class 1.0 as per IEC 62053-21+1
–– Reactive energy Class 1.0 as per IEC 62053-24 (partial compliance for
reactive energy test clause only)
–– Power quality analysis: The PM2220R offers THD % measurements and
Individual harmonics up to the 15th order.
–– Load management: Simultaneous display of peak, present, predicted &
rising demands of all the four demand parameters (W, VA, VAR, Amps)
–– Billing: Tenant billing/utility meter cross check (where local regulations are
not applicable).
–– Timer: Active load timer, meter operation timer and run hours timer. These
features help advise maintenance requirements and scheduling.
–– Display type: Monochrome graphical LCD of 128 x 128 resolution with
viewable area of 67 x 62.5 mm lets the users read all three phase
measured values simultaneously. The bright anti-glare display features large
characters and powerful backlighting for easy reading even in extreme
lighting conditions and viewing angles. Intuitive menus, multi-language text,
icons and graphics create a user-friendly environment to learn about your
electrical network.
+1
Meters have been tested to ANSI C12.20 and IEC 62053-21 assuming an ideal CT
36 PLSED310053EN
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
PM2200R
METSECTV35xxx series CT
–– Suppression current: To disregard measurement of induced current or
negligible current flowing in the circuit, settable from 5 mA to 99 mA.
Feature selection
PB119511
PLSED310053N 37
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
PM2200R
Current average Present, Last, Predicted, Peak, and Peak Date Time
Active power Present, Last, Predicted, Peak, and Peak Date Time
Reactive power Present, Last, Predicted, Peak, and Peak Date Time
Apparent power Present, Last, Predicted, Peak, and Peak Date Time
Demand sync methods Thermal, Timed, Command Sync, and Clocked Sync
Demand calculation mode Sliding, fixed and rolling block
Demand intervals Settable from 1 to 60 minutes, in the step of 1 minute
Display
PM2200 series Full scape, monochrome graphical LCD of 128 x 128
resolution with viewable area of 67 x 62.5 mm
Visualization mode for signs IEC or IEEE type in LCD display meter
Communication
RS-485 serial Channel connection Industry standard Modbus RTU
protocol
Integration with software SCADA/ DCS/ PMS/ EMS/ BAS/ BMS software
PM2220R series meter - rear view Native Plug and Play support Native plug-and-play support for:
EcoStruxure Power Monitoring Expert, EcoStruxure
Power SCADA Operation, ION Setup.
Min/Max values
Minimum & Maximum value For 8 parameters, viz., V L-L, V L-N, Amps, PF, Hz,
recording of 3-ph average or total W, VA, VAR with date and time stamp, resettable
PB119503
38 PLSED310053EN
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
PM2200R
Electrical characteristics
PB119508
PLSED310053N 39
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
PM2200R
PM2200R series
Mechanical characteristics
Weight ~ 300 g
IP degree of protection IP54 front side, IP30 meter body as per IEC 60529
Material Polycarbonate meets UL 94V-0 flammability rating
Dimensions W x H x D 96 x 96 x 54 mm maximum (depth of the meter from housing mounting flange) and 13 mm (protrusion of meter
from housing flange).
Mounting position Vertical
Panel thickness 5 mm maximum
Environmental characteristics
Operating temperature Meter -10 to +60 °C (14 to 140 °F)
Storage temperature Meter -25 to +70 °C (-13 to 158 °F)
Humidity rating 5 to 95 % RH non condensing
Pollution degree 2
Altitude ≤2000 m (6562 ft) Category III
Product life Minimum 7 years
Electromagnetic compatibility (tested as per IEC 61326-1)
Electrostatic discharge IEC 61000-4-2
Immunity to radiated field IEC 61000-4-3
Immunity to fast transients IEC 61000-4-4
Immunity to impulse waves IEC 61000-4-5
Conducted immunity IEC 61000-4-6
Immunity to magnetic fields IEC 61000-4-8
Immunity to voltage dips IEC 61000-4-11
Emissions Emissions FCC Part 15 Class A/CE
Safety
Europe CE, as per IEC 61010-1 Ed-3
US and Canada cULus as per UL61010-1 and CAN/CSA-C22.2 No. 61010-1, for 480 V AC
Measurement Category (Voltage CAT III up to 480 V L-L
and Current inputs) CAT II up to 600 V L-L
Overvoltage Category (Control power) CAT III up to 300 V L-N
Dielectric As per IEC/UL 61010-1 Ed-3
Protective Class II, Double insulated for user accessible parts
Green premium EOL, REACH, PEP, RoHS complied
Other certification RCM (Australia), EAC (Russia)
Communication
RS-485 port (PM2220R) Modbus RTU: 2-Wires, with ground & shield, 4800, 9600, 19200 or 38400 baud, Parity - Even, Odd, None, 1 stop
bit if parity is Odd or Even, 2 stop bits if None
DLF3000: Firmware update through communication port
Pulse Output – POP (PM2210R) Max 40 V DC, 20 mA 20 ms ON time
Configurable pulse weight from 1 to 9999000 pulses/k_h (kWh, kVAh, or kVARh)
Isolation 2.5 kV RMS, double insulated
Protection features Password protected for set-up & clearing energy and Min/Max data
Display language English, Spanish, French, Chinese, German, Portugese, Russian, Turkish
Technical publication Printed installation guide (IG) with the meter in multi language (EN, ES, FR, DE, PT, RU, TR, ZH)
Human machine interface
Display type LCD display: Monochrome graphical LCD of 128 x128 mm resolution with viewable area of 67 x 62.5 mm
Keypad 4 buttons for intuitive navigation of HMI/ UI pages
CAL LED Indicator Red colour, meter constant is configurable from 1 to 9999000 pulses/k_h (kWh, kVAh, or kVARh)
Comm. activity Green LED (for indicating RS-485 interface or heartbeat pulse)
40 PLSED310053EN
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
PM2200R
1.0
Accuracy for VAh ±0.5 %
Amps, per-phase, average and calculated neutral current b
Voltage, V L-N, V L-L, per-phase and average b
True PF
Power Factor True PF
Displacement PF
Frequency, any available phase b
Power: W, VA, VAR: per phase and total b
Current
3-phase unbalance % Current
Voltage
Demand parameters (Present, Last, Predicted and Peak for b b
W, VA, VAR, Amps)
Date and Time stamp for peak demand (no timestamp)
Delivered,
Delivered,
Energy: Wh, VAh, VARh (4 quadrant) Received
Received, Total,
Delivered (Import or Forward), Received (Export or Reverse) Total, Net, Last
Net
cleared
Active load timer, meter operating timer, run hours and
power outage counter b
THD %: Voltage L-N or L-L, Amps per phase b
Individual harmonics for Voltage, Current, per-phase Up to 15th
Min/ Max with real time clock For avg or total of V L-L, V b
L-N, Amps, PF, Hz, W, VA, VAR parameters with date and
time stamp of occurrence
PM22xx panel grouping RTC/battery b
Communication Pulse Output RS-485
Daily time snap shot of Avg Voltage, Avg Current, Total
mm active power & Energy delivered as measured every day at b
a configurable time
PB119520
PLSED310053N 41
EASYLOGIC POWER AND ENERGY METERS DIMENSIONS AND CONNECTION
PM2200R
PM2200R multi-function meter mechanical dimensions
PB119517
42 PLSED310053EN
EASYLOGIC POWER AND ENERGY METERS DIMENSIONS AND CONNECTION
PM2200R
SECTV35xxx 3-in-1 LVCT mechanical dimensions
PB119514
PLSED310053N 43
EASYLOGIC POWER AND ENERGY METERS FUNCTIONS AND CHARACTERISTICS
44 PLSED310053EN
Schneider Electric Industries SAS As standards, specifications and designs develop from time to time, please ask
35, Rue Joseph Monier, for confirmation of the information given in this document.
CS 30323
F - 92506 Rueil Malmaison Cedex
Design: Schneider Electric
RCS Nanterre 954 503 439 Photos: Schneider Electric
Capital social 896 313 776
www.schneider-electric.com Over 75 % of Schneider Electric products
have been awarded the Green Premium ecolabel.
EasyLogic Catalogue
PLSED310053EN © 2017 - Schneider Electric - All rights reserved 12-2017
PLSED310053N 45