8700M Quick-Start-Guide-Rosemount-8700m-Magnetic-Flowmeter-Platform-Hart-Protocol-En-175992
8700M Quick-Start-Guide-Rosemount-8700m-Magnetic-Flowmeter-Platform-Hart-Protocol-En-175992
8700M Quick-Start-Guide-Rosemount-8700m-Magnetic-Flowmeter-Platform-Hart-Protocol-En-175992
00825-0400-4444, Rev. AA
August 2015
Rosemount® 8700M
Magnetic Flowmeter Platform
with Modbus® RS-485 Protocol
Quick Start Guide August 2015
NOTICE
This document provides basic installation guidelines for the Rosemount 8700M Magnetic
Flowmeter Platform with Modbus RS-485 Protocol. For information about installing,
configuring, maintaining, or troubleshooting this product, refer to Reference Manual
00809-0400-4444. The reference manual—as well as this quick start guide—are available online
at www.rosemount.com.
Failure to follow these installation guidelines could result in death or serious injury.
Installation and servicing instructions are for use by qualified personnel only. Do not perform
any servicing other than that contained in the operating instructions, unless qualified.
Verify the installation is done safely and is consistent with the operating environment.
it must be assured that the device certification and installation techniques are suitable for that
particular environment.
Explosion hazard—Do not disconnect equipment when a flammable or combustible atmosphere
is present.
To prevent ignition of flammable or combustible atmospheres, disconnect power before
servicing circuits.
Do not connect a Rosemount 8732EM Transmitter to a non-Rosemount sensor that is located in
an explosive atmosphere.
Substitution of components may impair Intrinsic Safety.
Follow national, local, and plant standards to properly earth ground the transmitter and sensor.
The earth ground must be separate from the process reference ground.
Rosemount Magnetic Flowmeters ordered with non-standard paint options or non-metallic
labels may be subject to electrostatic discharge. To avoid electrostatic charge build-up, do not
rub the flowmeter with a dry cloth or clean with solvents.
NOTICE
The sensor liner is vulnerable to handling damage. Never place anything through the sensor for
the purpose of lifting or gaining leverage. Liner damage may render the sensor inoperable.
Metallic or spiral-wound gaskets should not be used as they will damage the liner face of the
sensor. If spiral wound or metallic gaskets are required for the application, lining protectors
must be used. If frequent removal is anticipated, take precautions to protect the liner ends.
Short spool pieces attached to the sensor ends are often used for protection.
Correct flange bolt tightening is crucial for proper sensor operation and life. All bolts must be
tightened in the proper sequence to the specified torque specifications. Failure to observe
these instructions could result in severe damage to the sensor lining and possible sensor
replacement.
In cases where high voltage/high current are present near the meter installation, ensure proper
protection methods are followed to prevent stray voltage/current from passing through the
meter. Failure to adequately protect the meter could result in damage to the transmitter and
lead to meter failure.
Completely remove all electrical connections from both sensor and transmitter prior to welding
on the pipe. For maximum protection of the sensor, consider removing it from the pipeline.
Contents
Transmitter installation . . . . . . page 3 Process reference connection page 15
Handling and lifting . . . . . . . . . page 5 Wiring the transmitter . . . . . . page 18
Mounting . . . . . . . . . . . . . . . . . . page 6 Modbus configuration . . . . . . page 28
Sensor installation . . . . . . . . . . . page 9 Product Certifications . . . . . . page 36
2
August 2015 Quick Start Guide
Hardware switches
The 8732EM electronics stack is equipped with user-selectable hardware
switches. These switches set the Internal/External Pulse Power and Transmitter
Security. The factory default settings for these switches is as follows:
In most cases, it will not be necessary to change the hardware switch settings. If
the settings need to be changed, follow the steps outlined under “Changing
hardware switch settings” in Reference Manual 00809-0400-4444.
Note
To prevent switch damage, use a non-metallic tool to move switch positions.
Be sure to identify any additional options and configurations that apply to the
installation. Keep a list of these options for consideration during the installation
and configuration procedures.
1.2 Mechanical considerations
The mounting site for the Rosemount 8732EM transmitter should provide
enough room for secure mounting, easy access to conduit entries, full opening of
the transmitter covers, and easy readability of the LOI screen, if equipped.
For remote mount transmitter (8732EMRxxx) installations, a mounting bracket is
provided for use on a 2-inch pipe or a flat surface (see Figure 1).
3
Quick Start Guide August 2015
Note
If the Rosemount 8732EM is mounted separately from the sensor, it may not be subject to
limitations that might apply to the sensor.
>@
Note
Conduit entries are 1/2- in. NPT or M20 connections. If an alternate thread connection is
required, thread adapters must be used.
Modbus output circuit Internally powered (Active): Outputs up to 3.3VDC, 100mA, 100mW
Termination resistors Typically 120 ohms. Refer to the MODBUS over Serial Line Specification &
Implementation Guide (http://www.modbus.org) for more details.
Um 250V
5
Quick Start Guide August 2015
Do not lift the meter by holding the electronics housing or junction box.The
sensor liner is vulnerable to handling damage. Never place anything through
the sensor for the purpose of lifting or gaining leverage. Liner damage can
render the sensor useless.
If provided, use the lifting lugs on each flange to handle the Magnetic
Flowmeter when it is transported and lowered into place at the installation
site. If lifting lugs are not provided, the Magnetic Flowmeter must be
supported with a lifting sling on each side of the housing.
- Standard Pressure 3-in. through 36-in. Flanged Magnetic Flowmeters
come with lifting lugs.
- High Pressure (above 600#) 1-in. through 24-in. Flanged Magnetic
Flowmeters come with lifting lugs.
- Wafers and Sanitary Magnetic Flowmeters do not come with lifting lugs.
A B
A. Without lifting lugs
B. With lifting lugs
Step 3: Mounting
3.1 Upstream/downstream piping
To ensure specified accuracy over widely varying process conditions, install the
sensor with a minimum of five straight pipe diameters upstream and two pipe
diameters downstream from the electrode plane (see Figure 3).
6
August 2015 Quick Start Guide
Flow
Installations with reduced upstream and downstream straight runs are possible.
In reduced straight run installations, the meter may not meet absolute accuracy
specifications. Reported flow rates will still be highly repeatable.
3.2 Flow direction
The sensor should be mounted so that the arrow points in the direction of flow.
See Figure 4.
7
Quick Start Guide August 2015
FLOW
FLOW
8
August 2015 Quick Start Guide
Note
Metallic or spiral-wound gaskets should not be used as they will damage the liner face of the
sensor. If spiral wound or metallic gaskets are required for the application, lining protectors
must be used.
FLOW
9
Quick Start Guide August 2015
1. Snug upstream
2. Snug downstream
3. Tighten upstream
4. Tighten downstream
Do not snug and tighten the upstream side and then snug and tighten the downstream side.
Failure to alternate between the upstream and downstream flanges when tightening bolts
may result in liner damage.
Suggested torque values by sensor line size and liner type are listed in Table 4 for
ASME B16.5 flanges and Table 5 for EN flanges. Consult the factory if the flange
rating of the sensor is not listed. Tighten flange bolts on the upstream side of the
sensor in the incremental sequence shown in Figure 8 to 20% of the suggested
torque values. Repeat the process on the downstream side of the sensor. For
sensors with greater or fewer flange bolts, tighten the bolts in a similar crosswise
sequence. Repeat this entire tightening sequence at 40%, 60%, 80%, and 100% of
the suggested torque values.
If leakage occurs at the suggested torque values, the bolts can be tightened in
additional 10% increments until the joint stops leaking, or until the measured
torque value reaches the maximum torque value of the bolts. Practical
consideration for the integrity of the liner often leads to distinct torque values to
stop leakage due to the unique combinations of flanges, bolts, gaskets, and
sensor liner material.
Check for leaks at the flanges after tightening the bolts. Failure to use the correct
tightening methods can result in severe damage. While under pressure, sensor
materials may deform over time and require a second tightening 24 hours after
the initial installation.
10
August 2015 Quick Start Guide
Prior to installation, identify the lining material of the flow sensor to ensure the
suggested torque values are applied.
T - PTFE P - Polyurethane
F - ETFE N - Neoprene
K - PFA+ D - Adiprene
Table 4. Suggested Flange Bolt Torque Values for Rosemount 8705 (ASME)
11
Quick Start Guide August 2015
Table 5. Flange Bolt Torque and Load Specifications for 8705 (EN 1092-1)
12
August 2015 Quick Start Guide
Wafer sensors
4.3 Gaskets
The sensor requires a gasket at each process connection. The gasket material
selected must be compatible with the process fluid and operating conditions.
Gaskets are required on each side of a grounding ring. See Figure 9 below.
Note
Metallic or spiral-wound gaskets should not be used as they will damage the liner
face of the sensor.
4.4 Alignment
1. On 1.5-in. through 8-in. (40 through 200 mm) line sizes, Rosemount requires
installing the alignment spacers to ensure proper centering of the wafer sensor
between the process flanges.
2. Insert studs for the bottom side of the sensor between the pipe flanges and
center the alignment spacer in the middle of the stud. See Figure 9 for the bolt
hole locations recommended for the spacers provided. Stud specifications are
listed in Table 6.
3. Place the sensor between the flanges. Make sure the alignment spacers are
properly centered on the studs. For vertical flow installations, slide the O-ring
over the stud to keep the spacer in place. See Figure 9. Ensure the spacers
match the flange size and class rating for the process flanges. See Table 7.
4. Insert the remaining studs, washers, and nuts.
5. Tighten to the torque specifications shown in Table 8. Do not over-tighten the
bolts or the liner may be damaged.
13
Quick Start Guide August 2015
1.5 through 8-inch (40 through 200 mm) CS, ASTM A193, Grade B7, threaded mounting studs
To order an Alignment Spacer Kit (qty 3 spacers) use p/n 08711-3211-xxxx where
xxxx equals the dash number above.
14
August 2015 Quick Start Guide
Note
For line sizes 10-inch and larger, the ground strap may come attached to the sensor body
near the flange. See Figure 14.
15
Quick Start Guide August 2015
16
August 2015 Quick Start Guide
17
Quick Start Guide August 2015
A. Power
B. Output
C. Coil
D. Electrode
18
August 2015 Quick Start Guide
19
Quick Start Guide August 2015
08732-0065-2001
(feet) Kit, Combination Cable,
Standard
08732-0065-2002
(meters)
20
August 2015 Quick Start Guide
Cable requirements
Shielded twisted pairs or triads must be used. For installations using the individual
coil drive and electrode cable, see Figure 17. Cable lengths should be limited to
less than 500 feet (152 m). Consult factory for length between 500–1000 feet
(152–304 m). Equal length cable is required for each.
For installations using the combination coil drive/electrode cable, see Figure 18.
Combination cable lengths should be limited to less than 330 feet (100 m).
21
Quick Start Guide August 2015
Cable preparation
When preparing all wire connections, remove only the insulation required to fit
the wire completely under the terminal connection. Prepare the ends of the coil
drive and electrode cables as shown in Figure 19. Limit the unshielded wire length
to less than 1 inch on both the coil drive and electrode cables. Any length of
unsheathed conductor should be insulated. Excessive removal of insulation may
result in an unwanted electrical short to the transmitter housing or other wire
connections. Excessive unshielded lead length, or failure to connect cable shields
properly, may expose the unit to electrical noise, resulting in an unstable meter
reading.
Shock Hazard
Potential shock hazard across remote junction box terminals 1 & 2 (40V).
Explosion Hazard
Electrodes exposed to process. Use only compatible transmitter and approved
installation practices.
For process temperatures greater than 284 °F (140 °C), use a wire rated for 257 °F
(125 °C).
22
August 2015 Quick Start Guide
RED 1 RED 1
BLUE 2 BLUE 2
BLACK 17 Shield 3
YELLOW 18 BLACK 17
WHITE 19 YELLOW 18
WHITE 19
For sensor wiring diagrams, see Figure 29 on page 50. For hazardous locations,
refer to Appendix D of Reference Manual 00809-0400-4444.
6.4 8732EM terminal block connections
Remove the back cover of the transmitter to access the terminal block. See Figure
21 for terminal identification. To connect pulse output and/or discrete
input/output, refer to Reference Manual 00809-0400-4444. For installations with
intrinsically safe outputs, refer to Appendix D of Reference Manual
00809-0400-4444.
23
Quick Start Guide August 2015
Cable characteristics
Type Shielded twisted pair cable with 2 conductors and a
drain wire, or Ethernet cable of Cat 5/5e/6
Bus cable
Bus to be connected device to device. For example, daisy chained (not star
connected).
Maximum 4000 feet depending on speeds, cable, and loads.
Cable shield must be grounded at only one point.
Due to the use of galvanically isolated Modbus connections, a third common wire
is not necessary for this product. If a 3-conductor cable is used, the third wire
should be left unterminated and insulated from ground.
Derivations (spurs)
Avoid derivations (spurs) when possible. If required, derivations from the bus
must be as short as possible (65 feet maximum).
Termination
A single 120 ohm terminator should be placed at each physical end of the bus (at
the two most remote bus devices) to minimize reflections in the transmission
cable. Do not place terminators on a spur connection.
Modbus wiring
The Modbus signal is a 24VDC active output.
Wire terminal 1 (B/D1) and terminal 2 (A/D0). See Figure 22.
24
August 2015 Quick Start Guide
Modbus A/D0
Modbus B/D1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
12 16 20 24 28 32 36 40
Power Supply (DC Volts)
25
Quick Start Guide August 2015
0.24
0.22
0.20
0.18
0.16
0.14
0.12
90 110 130 150 170 190 210 230 250
30
28
26
24
22
20
90 110 130 150 170 190 210 230 250
Power Supply (VAC)
Installation category
The installation category for the 8732EM is OVERVOLTAGE CAT II.
Overcurrent protection
The Rosemount 8732EM transmitter requires overcurrent protection of the
supply lines. Fuse rating and compatible fuses are shown in Table 12.
26
August 2015 Quick Start Guide
12–42VDC 3 Amp, 250V, I2t ≥ 14 A2s Rating, Bel Fuse 3AG 3-R, Littelfuse 312003P,
Fast Acting Schurter 0034.5135
Power terminals
See Figure 21 for terminal block connections.
For AC powered transmitter (90–250VAC, 50/60 Hz):
Connect AC Neutral to terminal 9 (AC N/L2) and AC Line to terminal 10
(AC/L1).
For DC powered transmitter:
Connect negative to terminal 9 (DC -) and positive to terminal 10 (DC +).
DC powered units may draw up to 1.2A.
Note
Application of excessive torque may strip the threads.
27
Quick Start Guide August 2015
28
August 2015 Quick Start Guide
Basic setup
8.1 Tag (Registers 68–71)
Tag is the quickest and shortest way of identifying and distinguishing between
transmitters. Transmitters can be tagged according to the requirements of your
application. The tag may be up to eight characters long.
29
Quick Start Guide August 2015
30
August 2015 Quick Start Guide
31
32
Totalizers View Total A Status All
View Total B Start All
View Total C Stop All TotA Direction
Reset Total A
Config/Control Reset All TotA Units
Total A Config
Total A TotA Reset Cfg
Total B
Total C TotB Direction
Reset Total B
Security TotB Units
Total B Config
TotB Reset Cfg
Quick Start Guide
TotC Direction
Reset Total C
TotC Units
Total C Config
TotC Reset Cfg
Diagnostics
LOI Control
LOI Start/Stop
Write Protect
LOI Reset
Figure 25. Totalizer Menu Map
WP Start/Stop
WP Reset
Basic Setup
Detailed Setup
REV AJ
August 2015
Test Condition
Totalizers Modbus Diag Modbus Status Test Criteria
Diag Controls Listen Only MD MV Results
Basic Diag Restart MB Com Sim Velocity
Advanced Diag Reset MB Confg Actual Velocity
Variables Flow Sim Dev
Trims Xmtr Cal Verify
August 2015
Test Criteria
Sim Velocity
Actual Velocity
Diagnostics Manual Results Flow Sim Dev
Coils Continual Res Coil Inductnce
Empty Pipe Electrodes Sensor Cal Dev
Process Noise Transmitter Coil Resist
Ground/Wiring Electrode Res
Elec Coating Values Coil Resist
Elect Temp Reset Baseline Coil Inductnce
Reverse Flow Recall Values Electrode Res
Cont Meter Ver
Figure 26. Diagnostics Menu Map
EP Control No Flow
EP Value Flowing, Full
Self Test EP Trig Level Empty Pipe
Pulse Out Test Coil Resist
EP Counts Continual
Empty Pipe Coil Inductnce
Elect Temp Actual Velocity
Flow Limit 1 EC Current Val Electrode Res
Manual Measure
Flow Limit 2 EC Limit 1
Continual Meas
Total Limit EC Limit 2
EC Max Value Coil Resist
Reset Max Val Coil Inductnce
Basic Setup
Electrode Res
Actual Velocity
Run Meter Ver Flow Sim Dev
View Results
Sensr Baseline Test Condition
Test Criteria Test Criteria
Measurements MV Results
Sim Velocity
Ground/Wiring Actual Velocity
Process Noise Process Noise Flow Sim Dev
Elec Coating Ground/Wiring Xmtr Cal Verify
Meter Verif Elec Coating Sensor Cal Dev
Licensing License Status Meter Verif Sensor Cal
License Key DI/DO Coil Circuit
Electrode Ckt
Empty Pipe
Elect Temp EC Current Val
Line Noise EC Max Value Test Criteria
5Hz SNR Sim Velocity
37Hz SNR Actual Velocity
Detailed Setup Elec Coating Flow Sim Dev
Signal Power Coil Inductnce
Digital Trim Sensor Cal Dev
REV AJ 37Hz Auto Zero
37Hz Auto Zero Manual Results
Coil Current Coil Resist
Universal Trim Continual Res
MV Results Electrode Res
33
Quick Start Guide
34
Totalizers
Quick Start Guide
Diagnostics
Figure 27. Basic Setup Menu Map
Detailed Setup
REV AJ
August 2015
Totalizers Address Slot Indices Var Slot 0 Idx
Flt Pt Order Slot Variables Var Slot 1 Idx
Var Slot 0 Val
Baud Rate Var Slot 2 Idx
Var Slot 1 Val
Parity Var Slot 3 Idx
Var Slot 2 Val
Stop Bits Var Slot 4 Idx
Var Slot 3 Val
Min Resp Delay
August 2015
Modbus Control 1
Pulse Mode 1
DI/DO Config DI/O 1 High Limit 1
More Params
Reverse Flow DO 2 Low Limit 1
Output Config
Flow Limit 1 Hysteresis
LOI Config
Flow Limit 2 Control 2
Sig Processing
Total Limit Mode 2
Figure 28. Detailed Setup Menu Map
Device Info
Diag Alert High Limit 2
Device Reset
Total Control Low Limit 2
Total Mode Hysteresis
Tot Hi Limit
Tot Low Limit
Hysteresis
Tag
Description
Message
Device ID
Detailed Setup Sensor S/N Software Rev
Sensor Tag Final Asmbl #
REV AJ Write protect
Revision Num
35
Quick Start Guide
Quick Start Guide August 2015
Product Certifications
Approvals Document
July 24, 2015
08732-AP01, Rev AF
Rosemount 8700M Magnetic Flowmeter Platform
Order 8732EM 8705M and 8711M/L Certification
Region Agency
Code Transm itter Rating Flow tube Rating Num ber
USA
- Ordinary Locations * Ordinary Location * FM 3048793
EU
FM Non-Incendive FM Non-Incendive w ith Intrinsically Safe Electrodes
N5 USA FM 3048793
Class I Div 2; DIP Class I Div 2; DIP
FM Explosion-Proof FM Explosion-Proof w ith Intrinsically Safe Electrodes
K5 USA FM 3048793
Class I Div 1; DIP Class I Div 1; DIP
CSA Non-Incendive CSA Non-Incendive w ith Intrinsically Safe Electrodes USA &
N6 CSA 70030489
Class I Div 2; DIP Class I Div 2; DIP Canada
CSA Explosion-Proof CSA Explosion-Proof w ith Intrinsically Safe Electrodes
KU USA CSA 70030489
Class I Div 1; DIP Class I Div 1; DIP
CSA Flam eproof, Increased Safety, and Dust. CSA Increased Safety w ith Intrinsically Safe Electrodes and
K6 Canada CSA ***
Zone 0 & 1 Dust. Zone 0 & 1
KN CCOE Flam eproof w ith Increased Safety CCOE Increased Safety w ith Intrinsically Safe Electrodes India PESO P354747/1
Com plies w ith only the local country product safety, electrom agnetic, pressure and other applicable regulations.
* Cannot be used in a classified or zoned hazardous location environm ent. No ordering code required.
** Custom s Union (Russia, Belarus and Kazakhstan)
36
August 2015 Quick Start Guide
Approvals Document
July 24, 2015
08732-AP01, Rev AF
Approval Markings and Logos
Marking or
Symbol Symbol Region Meaning of Marking or Symbol
Name
CSA US = United States Indicates that the product was tested and has
met the applicable certification requirements
C = Canada for the noted countries.
Eurasian Eurasian Customs Union Compliance with all of the applicable technical
Conformity (Russia, Belarus and regulations of the EAC Customs Union
(EAC) Kazakhstan)
Ordinary Location labels will be marked with CE, C-tick, FM, CSA and EAC logos.
37
Quick Start Guide August 2015
Approvals Document
July 24, 2015
08732-AP01, Rev AF
European Directive Information
A copy of the EC Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent
revision of the EC Declaration of Conformity can be found at www.rosemount.com.
Ingress Protection Rating for dust and water per EN 60079-0 and EN 60529 – IP66/68 (The IP68 rating only
applies to the flowtube and the remote junction box when the transmitter is remotely mounted. The IP68 rating
does not apply to the transmitter. The IP68 rating is only valid at a depth of 10 meters for 48 hours)
Mandatory CE-marking with notified body number 0575, for all flowtubes is located on the flowmeter label.
Category I assessed for conformity per module A procedures.
Categories II – III assessed for conformity per module H procedures.
QS Certificate of Assessment
EC No. 4741-2014-CE-HOU-DNV
Module H Conformity Assessment
All other Rosemount Flowtubes – line sizes of 25mm (1-in) and less: Sound Engineering Practice (SEP).
Flowtubes that are SEP are outside the scope of PED and cannot be marked for compliance with PED.
38
August 2015 Quick Start Guide
Approvals Document
July 24, 2015
08732-AP01, Rev AF
Certifications
Factory Mutual (FM)
8732EM Transmitter
Note: For Intrinsically Safe (IS) 4-20mA and Pulse Outputs on the 8732EM, output code “B” must be selected.
39
Quick Start Guide August 2015
Approvals Document
July 24, 2015
08732-AP01, Rev AF
8705-M and 8711-M/L Flowtube
Note: When used in hazardous (classified) locations:
The 8705-M and 8711-M/L may only be used with a certified 8732EM transmitter.
40
August 2015 Quick Start Guide
Approvals Document
July 24, 2015
08732-AP01, Rev AF
Canadian Standards Association (CSA)
CLASS 2258 02 - PROCESS CONTROL EQUIPMENT - For Hazardous Locations – To Canadian Requirements.
Magnetic Flow Meter – Model 8732EM Transmitter with integral or remote mount to Model 8705M or Model
8711M/L Magnetic Flow Tubes. Enclosure Type 4X and IP 66 Rated.
For Remote Mount Configuration – Temperature Code T4 with an Ambient Operating Temperature Range: -40°C
чdĂчнϲϬΣ͕ǁŝƚŚŽƌǁŝƚŚŽƵƚ>ŵĞƚĞƌ͕ǁŝƚŚŽƌǁŝƚŚŽƵƚĚŝŐŝƚĂů/ͬKĂŶĚͬŽƌƉƵůƐĞŽƵƚƉƵƚƐǁŚĞŶŝŶƐƚĂůůĞĚƉĞƌ
Rosemount Drawing 08732-2061.
For Integral Mount Configuration – Ambient Operating Temperature Range: -29°C чdĂчнϲϬΣ. Temperature
Code T3-T6 dependent on line size of Flow Tubes for Process Temperature. The T-Code is defined as per
Rosemount Drawing 08705-00CS and 08732-00CS for ‘N6’ option or ‘KU’ option.
CLASS 2258 82 - PROCESS CONTROL EQUIPMENT - For Hazardous Locations –To US Requirements
Magnetic Flow Meter – Model 8732EM Transmitter with integral or remote mount to Model 8705M or Model
8711M/L Magnetic Flow Tubes. Enclosure Type 4X and IP 66 Rated.
For Remote Mount Configuration – Temperature Code T6 for Explosion Proof, T5 for Dust Ignition Proof, and T4
for Non-Incendive. Ambient Operating Temperature Range: -ϰϬΣчdĂчнϲϬΣ͕ǁŝƚŚŽƌǁŝƚŚŽƵƚ>ŵĞƚĞƌ͕ǁŝƚŚ
or without digital I/O and/or pulse outputs when installed per Rosemount Drawing 08732-2061.
For Integral Mount Configuration – Ambient Operating Temperature Range: -ϮϵΣч dĂчнϲϬΣ. Temperature
Code T3-T6 dependent on line size of Flow Tubes for Process Temperature. The T-Code is defined as per
Rosemount Drawing 08705-00CS and 08732-00CS for ‘N6’ option or ‘KU’ option.
1. For use with the appropriate 8705M and 8711M/L Flow tubes only.
2. When the 8732EM transmitter is integrally mounted to 8705M or 8711M/L Flow Tubes, the ambient
temperature ranges marked on each product need to be taken into consideration before installation.
The Ambient temperature range for 8732EM transmitter is -ϰϬΣчdĂчнϲϬΣĂŶĚƚŚĞĂŵďŝĞŶƚ
temperature range for 8705M or 8711M/L Flow Tubes is -ϮϵΣчdĂчнϲϬΣ͘ Therefore, the -29°C rating
of the flow tubes will limit the overall cold temperature range of the complete system unless other
approved temperature control methods are employed.
41
Quick Start Guide August 2015
Approvals Document
July 24, 2015
08732-AP01, Rev AF
42
August 2015 Quick Start Guide
Approvals Document
July 24, 2015
08732-AP01, Rev AF
43
Quick Start Guide August 2015
Approvals Document
July 24, 2015
08732-AP01, Rev AF
44
August 2015 Quick Start Guide
45
Quick Start Guide August 2015
i. For processes requiring EPL Ga and Gb, rated equipment: electrode, grounding ring, and lining
protector materials Titanium and Zirconium are not allowed.
ii. When “Special Paint Systems” are applied, instructions for safe use regarding potential
electrostatic charging hazard have to be followed.
iii. Terminals 1,2,3,4, for data communication, cannot withstand the 500 V isolation test between
signal and ground, due to integral transient protection. This must be taken into account upon
installation.
iv. Conduit entries must be installed to maintain the enclosure ingress rating of IP66.
v. In order to maintain the ingress protection level on the M3 and M4 electrode housing, the copper
crush washer that seals the electrode access plug shall be replaced when the plug is reinstalled.
The copper crush washer is one time use only.
vi. The flow tube and transmitter are not allowed to be thermally insulated.
vii. The property class of the special fasteners which attach the Magnetic Flow Tube or Transmitter
Remote Junction Box to the Magnetic Transmitter is A2-70 or A4-70 SST.
viii. For information on the dimensions of the flameproof joints the manufacturer shall be contacted.
ix. The Magnetic Flow Meter Tube contains nonconductive liners over the grounded tube. For
process requiring EPL Ga, precautions shall be taken to avoid the liner being charged by the flow
of nonconductive media.
f. Where necessary, the essential characteristics of tools which may be fitted to the equipment
g. List of the standards, including the issue date, with which the equipment is declared to comply:
i. ATEX - EN 60079-0: 2012 +A11, EN 60079-1: 2007, EN 60079-7: 2007. EN 60079-11: 2012, EN
60079-15: 2010, EN 60079-26: 2007, EN 60079-31: 2014
ii. IEC EX - IEC 60079-0: 2011, IEC 60079-1: 2007, IEC 60079-7: 2006 IEC 60079-11: 2011, IEC
60079-15: 2010, IEC 60079-26: 2006, IEC 60079-31: 2013
h. Supply wire requirements;
Use 10 - 18 AWG wire rated for the proper temperature of the application. For wire 10 - 14 AWG use lugs
or other appropriate connectors. For connections in ambient temperatures above 122°F (50 °C), use a
wire rated for 194 °F (90 °C).
i. Contact address;
i. Rosemount Inc.
12001 Technology Drive
Eden Prairie
MN 55344
United States of America
46
August 2015 Quick Start Guide
Desig-
nation
Explanation Value Explanation
47
Quick Start Guide August 2015
48
August 2015 Quick Start Guide
49
Quick Start Guide August 2015
50
August 2015 Quick Start Guide
51
00825-0400-4444
Quick Start Guide
00825-0400-4444, Rev. AA
August 2015
Global Headquarters
Emerson Process Management
6021 Innovation Blvd
Shakopee, MN 55379, USA
+1 800 522 6277 or +1 303 527 5200
+1 303 530 8459
[email protected]