8700M Quick-Start-Guide-Rosemount-8700m-Magnetic-Flowmeter-Platform-Hart-Protocol-En-175992

Download as pdf or txt
Download as pdf or txt
You are on page 1of 52

Quick Start Guide

00825-0400-4444, Rev. AA
August 2015

Rosemount® 8700M
Magnetic Flowmeter Platform
with Modbus® RS-485 Protocol
Quick Start Guide August 2015

NOTICE
This document provides basic installation guidelines for the Rosemount 8700M Magnetic
Flowmeter Platform with Modbus RS-485 Protocol. For information about installing,
configuring, maintaining, or troubleshooting this product, refer to Reference Manual
00809-0400-4444. The reference manual—as well as this quick start guide—are available online
at www.rosemount.com.

Failure to follow these installation guidelines could result in death or serious injury.
 Installation and servicing instructions are for use by qualified personnel only. Do not perform
any servicing other than that contained in the operating instructions, unless qualified.
 Verify the installation is done safely and is consistent with the operating environment.

 If installed in explosive atmospheres (hazardous areas, classified areas, or an “Ex” environment),

it must be assured that the device certification and installation techniques are suitable for that
particular environment.
 Explosion hazard—Do not disconnect equipment when a flammable or combustible atmosphere

is present.
 To prevent ignition of flammable or combustible atmospheres, disconnect power before

servicing circuits.
 Do not connect a Rosemount 8732EM Transmitter to a non-Rosemount sensor that is located in

an explosive atmosphere.
 Substitution of components may impair Intrinsic Safety.

 Follow national, local, and plant standards to properly earth ground the transmitter and sensor.

The earth ground must be separate from the process reference ground.
 Rosemount Magnetic Flowmeters ordered with non-standard paint options or non-metallic

labels may be subject to electrostatic discharge. To avoid electrostatic charge build-up, do not
rub the flowmeter with a dry cloth or clean with solvents.

NOTICE
 The sensor liner is vulnerable to handling damage. Never place anything through the sensor for
the purpose of lifting or gaining leverage. Liner damage may render the sensor inoperable.
 Metallic or spiral-wound gaskets should not be used as they will damage the liner face of the
sensor. If spiral wound or metallic gaskets are required for the application, lining protectors
must be used. If frequent removal is anticipated, take precautions to protect the liner ends.
Short spool pieces attached to the sensor ends are often used for protection.
 Correct flange bolt tightening is crucial for proper sensor operation and life. All bolts must be
tightened in the proper sequence to the specified torque specifications. Failure to observe
these instructions could result in severe damage to the sensor lining and possible sensor
replacement.
 In cases where high voltage/high current are present near the meter installation, ensure proper
protection methods are followed to prevent stray voltage/current from passing through the
meter. Failure to adequately protect the meter could result in damage to the transmitter and
lead to meter failure.
 Completely remove all electrical connections from both sensor and transmitter prior to welding
on the pipe. For maximum protection of the sensor, consider removing it from the pipeline.

Contents
Transmitter installation . . . . . . page 3 Process reference connection page 15
Handling and lifting . . . . . . . . . page 5 Wiring the transmitter . . . . . . page 18
Mounting . . . . . . . . . . . . . . . . . . page 6 Modbus configuration . . . . . . page 28
Sensor installation . . . . . . . . . . . page 9 Product Certifications . . . . . . page 36
2
August 2015 Quick Start Guide

Step 1: Transmitter installation


Installation of the Rosemount Magnetic Flowmeter includes both detailed
mechanical and electrical installation procedures.
Before installing the Rosemount 8732EM Magnetic Flowmeter Transmitter, there
are several pre-installation steps that should be completed to make the
installation process easier:
 Identify the options and configurations that apply to your application
 Set the hardware switches if necessary
 Consider mechanical, electrical, and environmental requirements

1.1 Identify options and configurations


The typical installation of the 8732EM includes a device power connection, a
Modbus RS-485 output connection, and sensor coil and electrode connections.
Other applications may require one or more of the following configurations or
options:
 Pulse Output
 Discrete Input/Discrete Output

Hardware switches
The 8732EM electronics stack is equipped with user-selectable hardware
switches. These switches set the Internal/External Pulse Power and Transmitter
Security. The factory default settings for these switches is as follows:

Table 1. Hardware Switch Default Settings

Hardware switch Default setting

Internal/External Pulse Power External

Transmitter Security Off

In most cases, it will not be necessary to change the hardware switch settings. If
the settings need to be changed, follow the steps outlined under “Changing
hardware switch settings” in Reference Manual 00809-0400-4444.

Note
To prevent switch damage, use a non-metallic tool to move switch positions.

Be sure to identify any additional options and configurations that apply to the
installation. Keep a list of these options for consideration during the installation
and configuration procedures.
1.2 Mechanical considerations
The mounting site for the Rosemount 8732EM transmitter should provide
enough room for secure mounting, easy access to conduit entries, full opening of
the transmitter covers, and easy readability of the LOI screen, if equipped.
For remote mount transmitter (8732EMRxxx) installations, a mounting bracket is
provided for use on a 2-inch pipe or a flat surface (see Figure 1).

3
Quick Start Guide August 2015

Note
If the Rosemount 8732EM is mounted separately from the sensor, it may not be subject to
limitations that might apply to the sensor.

Rotate integral mount transmitter housing


The transmitter housing can be rotated on the sensor in 90-degree increments by
removing the four mounting screws on the bottom of the housing. Do not rotate
the housing more than 180 degrees in any one direction. Prior to tightening, be
sure the mating surfaces are clean, the O-ring is seated in the groove, and there is
no gap between the housing and the sensor.

Figure 1. Rosemount 8732EM Dimensional Drawing


>@

Note
Conduit entries are 1/2- in. NPT or M20 connections. If an alternate thread connection is
required, thread adapters must be used.

1.3 Electrical considerations


Before making any electrical connections to the Rosemount 8732EM, consider
national, local, and plant electrical installation requirements. Be sure to have the
proper power supply, conduit, and other accessories necessary to comply with
these standards.
Both remotely and integrally mounted Rosemount 8732EM transmitters require
external power, so there must be access to a suitable power source.
4
August 2015 Quick Start Guide

Table 2. Electrical Data

Rosemount 8732EM Flow Transmitter

Power input 90–250VAC, 0.45A, 40VA


12–42VDC, 1.2A, 15W

Pulsed circuit Internally powered (Active): Outputs up to 12VDC, 12.1mA, 73mW


Externally powered (Passive): Input up to 28VDC, 100mA, 1W

Modbus output circuit Internally powered (Active): Outputs up to 3.3VDC, 100mA, 100mW

Termination resistors Typically 120 ohms. Refer to the MODBUS over Serial Line Specification &
Implementation Guide (http://www.modbus.org) for more details.

Um 250V

Coil excitation output 500mA, 40V max, 9W max

Rosemount 8705-M and 8711-M/L Sensor(1)

Coil excitation input 500mA, 40V max, 20W max

Electrode circuit 5V, 200uA, 1mW


1. Provided by the transmitter

1.4 Environmental considerations


To ensure maximum transmitter life, avoid extreme temperatures and excessive
vibration. Typical problem areas include the following:
 High-vibration lines with integrally mounted transmitters.
 Tropical/desert installations in direct sunlight.
 Outdoor installations in arctic climates.
Remote-mounted transmitters may be installed in the control room to protect
the electronics from the harsh environment and to provide easy access for
configuration or service.

Step 2: Handling and lifting


 Handle all parts carefully to prevent damage. Whenever possible, transport
the system to the installation site in the original shipping container.
 PTFE-lined sensors are shipped with end covers that protect it from both
mechanical damage and normal unrestrained distortion. Remove the end
covers just before installation.
 Keep the shipping plugs in the conduit connections until you are ready to
connect and seal them.
 The sensor should be supported by the pipeline. Pipe supports are
recommended on both the inlet and outlet sides of the sensor pipeline. There
should be no additional support attached to the sensor.
 Additional safety recommendations for mechanical handling:
- Use proper PPE (Personal Protection Equipment) including safety glasses
and steel toed shoes.
- Do not drop the device from any height.

5
Quick Start Guide August 2015

 Do not lift the meter by holding the electronics housing or junction box.The
sensor liner is vulnerable to handling damage. Never place anything through
the sensor for the purpose of lifting or gaining leverage. Liner damage can
render the sensor useless.
 If provided, use the lifting lugs on each flange to handle the Magnetic
Flowmeter when it is transported and lowered into place at the installation
site. If lifting lugs are not provided, the Magnetic Flowmeter must be
supported with a lifting sling on each side of the housing.
- Standard Pressure 3-in. through 36-in. Flanged Magnetic Flowmeters
come with lifting lugs.
- High Pressure (above 600#) 1-in. through 24-in. Flanged Magnetic
Flowmeters come with lifting lugs.
- Wafers and Sanitary Magnetic Flowmeters do not come with lifting lugs.

Figure 2. Rosemount 8705 Sensor Support for Handling and Lifting

A B
A. Without lifting lugs
B. With lifting lugs

Step 3: Mounting
3.1 Upstream/downstream piping
To ensure specified accuracy over widely varying process conditions, install the
sensor with a minimum of five straight pipe diameters upstream and two pipe
diameters downstream from the electrode plane (see Figure 3).

6
August 2015 Quick Start Guide

Figure 3. Upstream and Downstream Straight Pipe Diameters


5 Pipe Diameters 2 Pipe Diameters

Flow

Installations with reduced upstream and downstream straight runs are possible.
In reduced straight run installations, the meter may not meet absolute accuracy
specifications. Reported flow rates will still be highly repeatable.
3.2 Flow direction
The sensor should be mounted so that the arrow points in the direction of flow.
See Figure 4.

Figure 4. Flow Direction Arrow

3.3 Sensor location


The sensor should be installed in a location that ensures it remains full during
operation. Vertical installation with upward process fluid flow keeps the
cross-sectional area full, regardless of flow rate. Horizontal installation should be
restricted to low piping sections that are normally full.

7
Quick Start Guide August 2015

Figure 5. Sensor Orientation

FLOW

FLOW

3.4 Electrode orientation


The electrodes in the sensor are properly oriented when the two measurement
electrodes are in the 3 and 9 o’clock positions or within 45 degrees from the
horizontal, as shown on the left of Figure 6. Avoid any mounting orientation that
positions the top of the sensor at 90 degrees from the vertical position as shown
in Figure 6.

Figure 6. Mounting Position


CORRECT INCORRECT

For hazardous location installations, refer to Appendix D of Reference Manual


00809-0400-4444 for sensor orientation pertaining to specific T-code
compliance.

8
August 2015 Quick Start Guide

Step 4: Sensor installation


Flanged sensors
4.1 Gaskets
The sensor requires a gasket at each process connection. The gasket material must be
compatible with the process fluid and operating conditions. Gaskets are required on
each side of a grounding ring (see Figure 7). All other applications (including
sensors with lining protectors or a grounding electrode) require only one gasket
on each process connection.

Note
Metallic or spiral-wound gaskets should not be used as they will damage the liner face of the
sensor. If spiral wound or metallic gaskets are required for the application, lining protectors
must be used.

Figure 7. Flanged Gasket Placement

FLOW

A. Grounding Ring and Gasket (Optional)


B. Customer-supplied Gasket

9
Quick Start Guide August 2015

4.2 Flange bolts


Note
Do not bolt one side at a time. Tighten both sides simultaneously. Example:

1. Snug upstream
2. Snug downstream
3. Tighten upstream
4. Tighten downstream

Do not snug and tighten the upstream side and then snug and tighten the downstream side.
Failure to alternate between the upstream and downstream flanges when tightening bolts
may result in liner damage.

Suggested torque values by sensor line size and liner type are listed in Table 4 for
ASME B16.5 flanges and Table 5 for EN flanges. Consult the factory if the flange
rating of the sensor is not listed. Tighten flange bolts on the upstream side of the
sensor in the incremental sequence shown in Figure 8 to 20% of the suggested
torque values. Repeat the process on the downstream side of the sensor. For
sensors with greater or fewer flange bolts, tighten the bolts in a similar crosswise
sequence. Repeat this entire tightening sequence at 40%, 60%, 80%, and 100% of
the suggested torque values.
If leakage occurs at the suggested torque values, the bolts can be tightened in
additional 10% increments until the joint stops leaking, or until the measured
torque value reaches the maximum torque value of the bolts. Practical
consideration for the integrity of the liner often leads to distinct torque values to
stop leakage due to the unique combinations of flanges, bolts, gaskets, and
sensor liner material.
Check for leaks at the flanges after tightening the bolts. Failure to use the correct
tightening methods can result in severe damage. While under pressure, sensor
materials may deform over time and require a second tightening 24 hours after
the initial installation.

Figure 8. Flange Bolt Torquing Sequence

10
August 2015 Quick Start Guide

Prior to installation, identify the lining material of the flow sensor to ensure the
suggested torque values are applied.

Table 3. Lining Material

Fluoropolymer liners Other liners

T - PTFE P - Polyurethane

F - ETFE N - Neoprene

A - PFA L - Linatex (Natural Rubber)

K - PFA+ D - Adiprene

Table 4. Suggested Flange Bolt Torque Values for Rosemount 8705 (ASME)

Fluoropolymer liners Other liners

Size Class 150 Class 300 Class 150 Class 300


code Line size (pound-feet) (pound-feet) (pound-feet) (pound-feet)

005 0.5-in. (15 mm) 8 8 N/A N/A

010 1-in. (25 mm) 8 12 N/A N/A

015 1.5-in. (40 mm) 13 25 7 18

020 2-in. (50 mm) 19 17 14 11

025 2.5-in. (65 mm) 22 24 17 16

030 3-in. (80 mm) 34 35 23 23

040 4-in. (100 mm) 26 50 17 32

050 5-in. (125 mm) 36 60 25 35

060 6-in. (150 mm) 45 50 30 37

080 8-in. (200 mm) 60 82 42 55

100 10-in. (250 mm) 55 80 40 70

120 12-in. (300 mm) 65 125 55 105

140 14-in. (350 mm) 85 110 70 95

160 16-in. (400 mm) 85 160 65 140

180 18-in. (450 mm) 120 170 95 150

200 20-in. (500 mm) 110 175 90 150

240 24-in. (600 mm) 165 280 140 250

300(1) 30-in. (750 mm) 195 415 165 375


(1)
360 36-in. (900 mm) 280 575 245 525

1. Torque values are valid for ASME and AWWA flanges.

11
Quick Start Guide August 2015

Table 5. Flange Bolt Torque and Load Specifications for 8705 (EN 1092-1)

Fluoropolymer liners (in Newton-meters)

Size code Line size PN10 PN 16 PN 25 PN 40

005 0.5-in. (15 mm) N/A N/A N/A 10

010 1-in. (25 mm) N/A N/A N/A 20

015 1.5-in. (40 mm) N/A N/A N/A 50

020 2-in. (50 mm) N/A N/A N/A 60

025 2.5-in. (65 mm) N/A N/A N/A 50

030 3-in. (80 mm) N/A N/A N/A 50

040 4-in. (100 mm) N/A 50 N/A 70

050 5-in. (125 mm) N/A 70 N/A 100

060 6-in. (150mm) N/A 90 N/A 130

080 8-in. (200 mm) 130 90 130 170

100 10-in. (250 mm) 100 130 190 250

120 12-in. (300 mm) 120 170 190 270

140 14-in. (350 mm) 160 220 320 410

160 16-in. (400 mm) 220 280 410 610

180 18-in. (450 mm) 190 340 330 420

200 20-in. (500 mm) 230 380 440 520

240 24-in. (600 mm) 290 570 590 850

Other liners (in Newton-meters)

Size code Line size PN10 PN 16 PN 25 PN 40


010 1-in. (25 mm) N/A N/A N/A 20

015 1.5-in. (40 mm) N/A N/A N/A 30

020 2-in. (50 mm) N/A N/A N/A 40

025 2.5-in. (65 mm) N/A N/A N/A 35

030 3-in. (80 mm) N/A N/A N/A 30

040 4-in. (100 mm) N/A 40 N/A 50

050 5-in. (125 mm) N/A 50 N/A 70

060 6-in. (150 mm) N/A 60 N/A 90

080 8-in. (200 mm) 90 60 90 110

100 10-in. (250 mm) 70 80 130 170

120 12-in. (300 mm) 80 110 130 180

140 14-in. (350 mm) 110 150 210 280

160 16-in. (400 mm) 150 190 280 410

180 18-in. (450 mm) 130 230 220 280

200 20-in. (500 mm) 150 260 300 350

240 24-in. (600 mm) 200 380 390 560

12
August 2015 Quick Start Guide

Wafer sensors
4.3 Gaskets
The sensor requires a gasket at each process connection. The gasket material
selected must be compatible with the process fluid and operating conditions.
Gaskets are required on each side of a grounding ring. See Figure 9 below.

Note
Metallic or spiral-wound gaskets should not be used as they will damage the liner
face of the sensor.

Figure 9. Wafer Gasket Placement

4.4 Alignment
1. On 1.5-in. through 8-in. (40 through 200 mm) line sizes, Rosemount requires
installing the alignment spacers to ensure proper centering of the wafer sensor
between the process flanges.
2. Insert studs for the bottom side of the sensor between the pipe flanges and
center the alignment spacer in the middle of the stud. See Figure 9 for the bolt
hole locations recommended for the spacers provided. Stud specifications are
listed in Table 6.
3. Place the sensor between the flanges. Make sure the alignment spacers are
properly centered on the studs. For vertical flow installations, slide the O-ring
over the stud to keep the spacer in place. See Figure 9. Ensure the spacers
match the flange size and class rating for the process flanges. See Table 7.
4. Insert the remaining studs, washers, and nuts.
5. Tighten to the torque specifications shown in Table 8. Do not over-tighten the
bolts or the liner may be damaged.

13
Quick Start Guide August 2015

Table 6. Stud Specifications


Nominal sensor size Stud specifications

1.5 through 8-inch (40 through 200 mm) CS, ASTM A193, Grade B7, threaded mounting studs

Table 7. Rosemount Alignment Spacer Table


Line size
Dash no.
(-xxxx) (in) (mm) Flange rating
0A15 1.5 40 JIS 10K-20K
0A20 2 50 JIS 10K-20K
0A30 3 80 JIS 10K
0B15 1.5 40 JIS 40K
AA15 1.5 40 ASME- 150#
AA20 2 50 ASME - 150#
AA30 3 80 ASME - 150#
AA40 4 100 ASME - 150#
AA60 6 150 ASME - 150#
AA80 8 200 ASME - 150#
AB15 1.5 40 ASME - 300#
AB20 2 50 ASME - 300#
AB30 3 80 ASME - 300#
AB40 4 100 ASME - 300#
AB60 6 150 ASME - 300#
AB80 8 200 ASME - 300#
DB40 4 100 EN 1092-1 - PN10/16
DB60 6 150 EN 1092-1 - PN10/16
DB80 8 200 EN 1092-1 - PN10/16
DC80 8 200 EN 1092-1 - PN25
DD15 1.5 40 EN 1092-1 - PN10/16/25/40
DD20 2 50 EN 1092-1 - PN10/16/25/40
DD30 3 80 EN 1092-1 - PN10/16/25/40
DD40 4 100 EN 1092-1 - PN25/40
DD60 6 150 EN 1092-1 - PN25/40
DD80 8 200 EN 1092-1 - PN40
RA80 8 200 AS40871-PN16
RC20 2 50 AS40871-PN21/35
RC30 3 80 AS40871-PN21/35
RC40 4 100 AS40871-PN21/35
RC60 6 150 AS40871-PN21/35
RC80 8 200 AS40871-PN21/35

To order an Alignment Spacer Kit (qty 3 spacers) use p/n 08711-3211-xxxx where
xxxx equals the dash number above.

14
August 2015 Quick Start Guide

4.5 Flange bolts


Wafer sensors require threaded studs. See Figure 8 on page 10 for torque
sequence. Always check for leaks at the flanges after tightening the flange bolts.
All sensors require a second tightening 24 hours after initial flange bolt
tightening.
Table 8. Rosemount 8711 Torque Specifications

Size code Line size Pound-feet Newton-meter

015 1.5-in. (40 mm) 15 20

020 2-in. (50 mm) 25 34

030 3-in. (80 mm) 40 54

040 4-in. (100 mm) 30 41

060 6-in. (150 mm) 50 68

080 8-in. (200 mm) 70 95

Step 5: Process reference connection


Figure 10 through Figure 13 illustrate process reference connections only. Earth
safety ground is also required as part of the installation, but is not shown in the
figures. Follow national, local, and plant electrical codes for safety ground.
Use Table 9 to determine which process reference option to follow for proper
installation.
Table 9. Process Reference Installation
Process reference options
Reference Lining
Type of pipe Grounding straps Grounding rings electrode protectors
Conductive See Figure 10 See Figure 11(1) See Figure 13(1) See Figure 11(1)
Unlined Pipe
Conductive Insufficient See Figure 11 See Figure 10 See Figure 11
Lined Pipe Grounding
Non-Conductive Insufficient See Figure 12 Not See Figure 12
Pipe Grounding Recommended
1.Grounding ring, reference electrode, and lining protectors are not required for proess reference.
Grounding straps per Figure 10 are sufficient.

Note
For line sizes 10-inch and larger, the ground strap may come attached to the sensor body
near the flange. See Figure 14.

15
Quick Start Guide August 2015

Figure 10. Grounding Straps in Conductive Unlined Pipe or Reference


Electrode in Lined Pipe

Figure 11. Grounding with Grounding Rings or Lining Protectors in


Conductive Pipe

Figure 12. Grounding with Grounding Rings or Lining Protectors in


Non-conductive Pipe

16
August 2015 Quick Start Guide

Figure 13. Grounding with Reference Electrode in Conductive Unlined Pipe

Figure 14. Grounding for Line Sizes 10-in. and Larger

17
Quick Start Guide August 2015

Step 6: Wiring the transmitter


This section covers the wiring between the transmitter and sensor, the Modbus
output, and supplying power to the transmitter. Follow the conduit, cable, and
electrical disconnect requirements in the sections below. For sensor wiring
diagrams, see Figure 29 on page 50. For hazardous locations, refer to Appendix D
of Reference Manual 00809-0400-4444.
6.1 Conduit entries and connections
Conduit entries for the transmitter and sensor are available with 1/2-inch NPT or
M20 connections. Conduit connections should be made in accordance with
national, local, and plant electrical codes. Unused conduit entries should be
sealed with the appropriate certified plugs. The flow sensor is rated IP68 to a
depth of 33 feet (10 meters) for 48 hours. For sensor installations requiring IP68
protection, the cable glands, conduit, and conduit plugs must be rated for IP68.
The plastic shipping plugs do not provide ingress protection.
6.2 Conduit requirements
 For installations with an intrinsically safe electrode circuit, a separate conduit
for the coil cable and the electrode cable may be required. Refer to
Appendix D of Reference Manual 00809-0400-4444.
 For installations with non-intrinsically safe electrode circuit, or when using the
combination cable, a single dedicated conduit run for the coil drive and
electrode cable between the sensor and the remote transmitter may be
acceptable. Bundled cables from other equipment in a single conduit are likely
to create interference and noise in the system. See Figure 15.
 Electrode cables should not be run together and should not be in the same
cable tray with power cables.
 Output cables should not be run together with power cables.
 Select conduit size appropriate to feed cables through to the flowmeter.

Figure 15. Best Practice Conduit Preparation

A. Power
B. Output
C. Coil
D. Electrode

18
August 2015 Quick Start Guide

6.3 Connecting sensor to transmitter


Integral mount transmitters
Integral mount transmitters ordered with a sensor will be shipped assembled and
wired at the factory using an interconnecting cable. (See Figure 16). Use only the
socket module or IMS cable provided by Emerson™ Process Management.
For replacement transmitters, use the existing interconnecting cable from the
original assembly. Replacement cables are available.

Figure 16. Interconnecting Cables

Socket Module IMS Cable


08732-CSKT-0001 08732-0179-0003

Remote mount transmitters


Cables kits are available as individual component cables or as a combination
coil/electrode cable. Remote cables can be ordered direct from Rosemount using
the kit numbers shown in Table 10. Equivalent Alpha cable part numbers are also
provided as an alternative. To order cable, specify length as quantity desired.
Equal length of component cables is required.
Example: 25 feet = Qty (25) 08732-0065-0001

19
Quick Start Guide August 2015

Table 10. Component Cable Kits

Standard temperature (-20°C to 75°C)

Cable kit # Description Individual cable Alpha p/n

08732-0065-0001 Kit, Component Cables, Std Coil 518243


(feet) Temp. Coil + Electrode Electrode 518245

08732-0065-0002 Kit, Component Cables, Std Coil 518243


(meters) Temp. Coil + Electrode Electrode 518245

08732-0065-0003 Kit, Component Cables, Std Coil 518243


(feet) Temp. Coil + I.S. Electrode Intrinsically Safe Blue Electrode 518244

08732-0065-0004 Kit, Component Cables, Std Coil 518243


(meters) Temp. Coil + I.S. Electrode Intrinsically Safe Blue Electrode 518244

Extended temperature (-50°C to 125°C)

Cable kit # Description Individual cable Alpha p/n

08732-0065-1001 Kit, Component Cables, Coil 840310


(feet) Ext Temp. Coil + Electrode Electrode 518189

08732-0065-1002 Kit, Component Cables, Coil 840310


(meters) Ext Temp. Coil + Electrode Electrode 518189

08732-0065-1003 Kit, Component Cables, Coil 840310


(feet) Ext Temp. Coil + I.S. Electrode Intrinsically Safe Blue Electrode 840309

08732-0065-1004 Kit, Component Cables, Coil 840310


(meters) Ext Temp. Coil + I.S. Electrode Intrinsically Safe Blue Electrode 840309

Table 11. Combination Cable Kits


Coil and electrode cable (-20°C to 80°C)

Cable kit # Description

08732-0065-2001
(feet) Kit, Combination Cable,
Standard
08732-0065-2002
(meters)

08732-0065-3001 Kit, Combination Cable,


(feet) Submersible
(80°C dry/60°C Wet)
08732-0065-3002 (33ft Continuous)
(meters)

20
August 2015 Quick Start Guide

Cable requirements
Shielded twisted pairs or triads must be used. For installations using the individual
coil drive and electrode cable, see Figure 17. Cable lengths should be limited to
less than 500 feet (152 m). Consult factory for length between 500–1000 feet
(152–304 m). Equal length cable is required for each.
For installations using the combination coil drive/electrode cable, see Figure 18.
Combination cable lengths should be limited to less than 330 feet (100 m).

Figure 17. Individual Component Cables

Figure 18. Combination Coil and Electrode Cable

21
Quick Start Guide August 2015

Cable preparation
When preparing all wire connections, remove only the insulation required to fit
the wire completely under the terminal connection. Prepare the ends of the coil
drive and electrode cables as shown in Figure 19. Limit the unshielded wire length
to less than 1 inch on both the coil drive and electrode cables. Any length of
unsheathed conductor should be insulated. Excessive removal of insulation may
result in an unwanted electrical short to the transmitter housing or other wire
connections. Excessive unshielded lead length, or failure to connect cable shields
properly, may expose the unit to electrical noise, resulting in an unstable meter
reading.

Figure 19. Cable Ends

Shock Hazard
Potential shock hazard across remote junction box terminals 1 & 2 (40V).
Explosion Hazard
Electrodes exposed to process. Use only compatible transmitter and approved
installation practices.
For process temperatures greater than 284 °F (140 °C), use a wire rated for 257 °F
(125 °C).

22
August 2015 Quick Start Guide

Figure 20. Remote Junction Box Views


Sensor Transmitter

Wire Terminal Wire Terminal

RED 1 RED 1

BLUE 2 BLUE 2

BLACK 17 Shield 3

YELLOW 18 BLACK 17

WHITE 19 YELLOW 18

WHITE 19

For sensor wiring diagrams, see Figure 29 on page 50. For hazardous locations,
refer to Appendix D of Reference Manual 00809-0400-4444.
6.4 8732EM terminal block connections
Remove the back cover of the transmitter to access the terminal block. See Figure
21 for terminal identification. To connect pulse output and/or discrete
input/output, refer to Reference Manual 00809-0400-4444. For installations with
intrinsically safe outputs, refer to Appendix D of Reference Manual
00809-0400-4444.

Figure 21. Terminal Block Connections

Modbus (B) Modbus (B)


Modbus (A) Modbus (A)

23
Quick Start Guide August 2015

6.5 Modbus output


The Modbus output is a Modbus RTU signal using RS-485. Follow these cable
recommendations for RS-485 interface (Modbus over serial line).

Cable characteristics
Type Shielded twisted pair cable with 2 conductors and a
drain wire, or Ethernet cable of Cat 5/5e/6

Conductor gauge 20–24 AWG for lengths up to 1000 feet


16–20 AWG for lengths up to 4000 feet

Characteristic impedance 100–130 ohm

Conductor-to-conductor capacitance <30 pF/ft

Conductor-to-shield capacitance <60 pF/ft

Voltage rating 300 V/600 V

Recommended insulation material PVC (<1000 ft) or PE (≥1000 ft)

Bus cable
Bus to be connected device to device. For example, daisy chained (not star
connected).
Maximum 4000 feet depending on speeds, cable, and loads.
Cable shield must be grounded at only one point.
Due to the use of galvanically isolated Modbus connections, a third common wire
is not necessary for this product. If a 3-conductor cable is used, the third wire
should be left unterminated and insulated from ground.

Derivations (spurs)
Avoid derivations (spurs) when possible. If required, derivations from the bus
must be as short as possible (65 feet maximum).

Termination
A single 120 ohm terminator should be placed at each physical end of the bus (at
the two most remote bus devices) to minimize reflections in the transmission
cable. Do not place terminators on a spur connection.

Modbus wiring
The Modbus signal is a 24VDC active output.
Wire terminal 1 (B/D1) and terminal 2 (A/D0). See Figure 22.

24
August 2015 Quick Start Guide

Figure 22. Modbus Wiring—Internal Power

Modbus A/D0
Modbus B/D1

6.6 Powering the transmitter


The Rosemount 8732EM transmitter is available in two models. The AC powered
transmitter is designed to be powered by 90–250VAC (50/60Hz). The DC
powered transmitter is designed to be powered by 12–42VDC. Before connecting
power to the Rosemount 8732EM, be sure to have the proper power supply,
conduit, and other accessories. Wire the transmitter according to national, local,
and plant electrical requirements for the supply voltage. See Figure 23 or Figure
24.

Figure 23. DC power Requirements


1.2
1.1
1.0
Supply Current (DC Amps)

0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
12 16 20 24 28 32 36 40
Power Supply (DC Volts)

Peak inrush is 42A at 42VDC supply, lasting approximately 1ms.


Inrush for other supply voltages can be estimated with:
Inrush (Amps) = Supply (Volts) / 1.0

25
Quick Start Guide August 2015

Figure 24. AC power Requirements


AC Supply Characteristics

0.24
0.22
0.20
0.18
0.16
0.14
0.12
90 110 130 150 170 190 210 230 250

Power Supply (VAC)

Apparent Power (VA)


34
32
Apparent Power (VA)

30
28
26
24
22
20
90 110 130 150 170 190 210 230 250
Power Supply (VAC)

Peak inrush is 35.7A at 250VAC supply, lasting approximately 1ms


Inrush for other supply voltages can be estimated with:
Inrush (Amps) = Supply (Volts) / 7.0

Supply wire requirements


Use 10–18 AWG wire rated for the proper temperature of the application. For
wire 10–14 AWG use lugs or other appropriate connectors. For connections in
ambient temperatures above 122 °F (50 °C), use a wire rated for 194 °F (90 °C). For
DC powered transmitters with extended cable lengths, verify that there is a
minimum of 12VDC at the terminals of the transmitter with the device under
load.

Electrical disconnect requirements


Connect the device through an external disconnect or circuit breaker per national
and local electrical code.

Installation category
The installation category for the 8732EM is OVERVOLTAGE CAT II.

Overcurrent protection
The Rosemount 8732EM transmitter requires overcurrent protection of the
supply lines. Fuse rating and compatible fuses are shown in Table 12.

26
August 2015 Quick Start Guide

Table 12. Fuse Requirements

Input voltage Fuse rating Compatible fuse

90–250VAC rms 1 Amp, 250V, I t ≥ 1.5 A s Rating,


2 2
Bussman AGC-1, Littelfuse 31201.5HXP
Fast Acting

12–42VDC 3 Amp, 250V, I2t ≥ 14 A2s Rating, Bel Fuse 3AG 3-R, Littelfuse 312003P,
Fast Acting Schurter 0034.5135

Power terminals
See Figure 21 for terminal block connections.
For AC powered transmitter (90–250VAC, 50/60 Hz):
 Connect AC Neutral to terminal 9 (AC N/L2) and AC Line to terminal 10
(AC/L1).
For DC powered transmitter:
 Connect negative to terminal 9 (DC -) and positive to terminal 10 (DC +).
 DC powered units may draw up to 1.2A.

Cover jam screw


For flow meters shipped with a cover jam screw, the screw should be installed
after the instrument has been wired and powered up. Follow these steps to install
the cover jam screw:
1. Verify the cover jam screw is completely threaded into the housing.
2. Install the housing cover and verify the cover is tight against the housing.
3. Using a 2.5 mm hex wrench, loosen the jam screw until it contacts the
transmitter cover.
4. Turn the jam screw an additional 1/2 turn counterclockwise to secure the cover.

Note
Application of excessive torque may strip the threads.

5. Verify the cover cannot be removed.

27
Quick Start Guide August 2015

Step 7: Modbus configuration


Note
Each register is identified by its address (or starting address). Depending on the PLC that will
be used to communicate with the transmitter, you may need to subract 1 from the address
or starting address of the register. Refer to your PLC documentation to know if this applies to
you.

Local operator interface


To activate the LOI, press the DOWN arrow. Use the UP, DOWN, LEFT (E), and
RIGHT arrows to navigate the menu structure. Maps of the LOI menus are shown
in Figures 25 through 28.
The display can be locked to prevent unintentional configuration changes. The
display lock can be activated by holding the UP arrow for three seconds and then
following the on-screen instructions.
When the display lock is activated, a lock symbol will appear in the lower right
hand corner of the display. To deactivate the display lock, hold the UP arrow for
three seconds and follow the on-screen instructions. Once deactivated, the lock
symbol will no longer appear in the lower right hand corner of the display.
7.1 Address (register 109)
Configures the address of the transmitter for the Modbus network.

7.2 Floating point byte order (register 110)


Sets the order that information is sent by the transmitter.
Register value Byte order
0 0–1–2–3 (default)
1 2–3–0–1
2 1–0–3–2
3 3–2–1–0

7.3 Baud rate (Register 115)


Sets the communication speed of the transmitter.
Register value Baud rate
0 1200
1 2400
2 4800
3 9600
4 19200 (default)
5 38400
6 57600
7 115200

28
August 2015 Quick Start Guide

7.4 Parity (register 116)


Used to configure error-checking methodology for the data.
Register value Parity
0 No parity
1 Odd
2 Even (default)

7.5 Stop bits (register 117)


Sets the last bit of the data packet.
Register value Stop bits
1 1 bit (default)
2 2 bits

Step 8: Basic configuration


Once the magnetic flowmeter is installed and power has been supplied, the
transmitter must be configured through the basic setup. These parameters can
be configured through either a local operator interface or a Modbus
communication tool. Configuration settings are saved in nonvolatile memory
within the transmitter. A complete map of the Modbus registries and descriptions
of the more advanced functions is available in Reference Manual
00809-0400-4444.

Basic setup
8.1 Tag (Registers 68–71)
Tag is the quickest and shortest way of identifying and distinguishing between
transmitters. Transmitters can be tagged according to the requirements of your
application. The tag may be up to eight characters long.

29
Quick Start Guide August 2015

8.2 Flow units (Register 61)


The flow units variable specifies the format in which the flow rate will be
displayed. Units should be selected to meet your particular metering needs.
Volume units Volume units

Register value Units Register value Units


241 Barrels (31 gal) / sec 19 Cubic meters / hour
242 Barrels (31 gal) / min 29 Cubic meters / day
243 Barrels (31 gal) / hour 22 Gallons / second
244 Barrels (31 gal) / day 16 Gallons / minute
132 Barrels (42 gal) / sec 136 Gallons / hour
133 Barrels (42 gal) / min 235 Gallons / day
134 Barrels (42 gal) / hour 137 Imperial gallons / sec
135 Barrels (42 gal) / day 18 Imperial gallons / min
248 Cubic cm / minute 30 Imperial gallons / hour
26 Cubic feet / second 31 Imperial gallons / day
15 Cubic feet / minute 24 Liters / second
130 Cubic feet / hour 17 Liters / minute
27 Cubic feet / day 138 Liters / hour
28 Cubic meters / second 240 Liters / day
131 Cubic meters / minute

Mass units Other units

Register value Units Register value Units


73 Kilograms / second 20 Feet / second (default)
74 Kilograms / minute 21 Meters / second
75 Kilograms / hour 253 Special units1
76 Kilograms / day
77 Metric ton / minute
78 Metric ton / hour
79 Metric ton / day
80 Pounds / second
81 Pounds / minute
82 Pounds / hour
83 Pounds / day
84 Short tons / minute
85 Short tons / hour
86 Short tons / day
1.Refer to the “Configure special units” section of Reference Manual 00809-0400-4444.

30
August 2015 Quick Start Guide

8.3 Line size (Register 65)


The line size (sensor size) must be set to match the actual sensor connected to the
transmitter.

Register value Line size Register value Line size


0 0.10-in. (2 mm) 18 16-in. (400 mm)
1 0.15-in. (4 mm) 19 18-in. (450 mm)
2 0.25-in. (6 mm) 20 20-in. (500 mm)
3 0.30-in. (8 mm) 21 24-in. (600 mm)
4 0.50-in. (15 mm) 22 28-in. (700 mm)
5 0.75-in. (18 mm) 23 30-in. (750 mm)
6 1-in. (25 mm) 24 32-in. (800 mm)
7 1.5-in. (40 mm) 25 36-in. (900 mm)
8 2-in. (50 mm) 26 40-in. (1000 mm)
9 2.5-in. (65 mm) 27 42-in. (1050 mm)
28 44-in. (1100 mm)
10 3-in. (80 mm)
(default) 29 48-in. (1200 mm)
11 4-in. (100 mm) 30 54-in. (1350 mm)
12 5-in. (125 mm) 31 56-in. (1400 mm)
13 6-in. (150 mm) 32 60-in. (1500 mm)
14 8-in. (200 mm) 33 64-in. (1600 mm)
15 10-in. (250 mm) 34 66-in. (1650 mm)
16 12-in. (300 mm) 35 72-in. (1800 mm)
17 14-in. (350 mm) 36 78-in. (1950 mm)

8.4 Calibration number (Registers 413–420)


The sensor calibration number is a 16-digit number generated at the Rosemount
factory during flow calibration and is unique to each sensor and is located on the
sensor tag.

31
32
Totalizers View Total A Status All
View Total B Start All
View Total C Stop All TotA Direction
Reset Total A
Config/Control Reset All TotA Units
Total A Config
Total A TotA Reset Cfg
Total B
Total C TotB Direction
Reset Total B
Security TotB Units
Total B Config
TotB Reset Cfg
Quick Start Guide

TotC Direction
Reset Total C
TotC Units
Total C Config
TotC Reset Cfg
Diagnostics

LOI Control
LOI Start/Stop
Write Protect
LOI Reset
Figure 25. Totalizer Menu Map

WP Start/Stop
WP Reset

Basic Setup

Detailed Setup

REV AJ
August 2015
Test Condition
Totalizers Modbus Diag Modbus Status Test Criteria
Diag Controls Listen Only MD MV Results
Basic Diag Restart MB Com Sim Velocity
Advanced Diag Reset MB Confg Actual Velocity
Variables Flow Sim Dev
Trims Xmtr Cal Verify
August 2015

Status Sensor Cal Dev


Sensor Cal
Coil Circuit
Electrode Ckt

Test Criteria
Sim Velocity
Actual Velocity
Diagnostics Manual Results Flow Sim Dev
Coils Continual Res Coil Inductnce
Empty Pipe Electrodes Sensor Cal Dev
Process Noise Transmitter Coil Resist
Ground/Wiring Electrode Res
Elec Coating Values Coil Resist
Elect Temp Reset Baseline Coil Inductnce
Reverse Flow Recall Values Electrode Res
Cont Meter Ver
Figure 26. Diagnostics Menu Map

EP Control No Flow
EP Value Flowing, Full
Self Test EP Trig Level Empty Pipe
Pulse Out Test Coil Resist
EP Counts Continual
Empty Pipe Coil Inductnce
Elect Temp Actual Velocity
Flow Limit 1 EC Current Val Electrode Res
Manual Measure
Flow Limit 2 EC Limit 1
Continual Meas
Total Limit EC Limit 2
EC Max Value Coil Resist
Reset Max Val Coil Inductnce
Basic Setup
Electrode Res
Actual Velocity
Run Meter Ver Flow Sim Dev
View Results
Sensr Baseline Test Condition
Test Criteria Test Criteria
Measurements MV Results
Sim Velocity
Ground/Wiring Actual Velocity
Process Noise Process Noise Flow Sim Dev
Elec Coating Ground/Wiring Xmtr Cal Verify
Meter Verif Elec Coating Sensor Cal Dev
Licensing License Status Meter Verif Sensor Cal
License Key DI/DO Coil Circuit
Electrode Ckt
Empty Pipe
Elect Temp EC Current Val
Line Noise EC Max Value Test Criteria
5Hz SNR Sim Velocity
37Hz SNR Actual Velocity
Detailed Setup Elec Coating Flow Sim Dev
Signal Power Coil Inductnce
Digital Trim Sensor Cal Dev
REV AJ 37Hz Auto Zero
37Hz Auto Zero Manual Results
Coil Current Coil Resist
Universal Trim Continual Res
MV Results Electrode Res

33
Quick Start Guide
34
Totalizers
Quick Start Guide

Diagnostics
Figure 27. Basic Setup Menu Map

Basic Setup Modbus Address


Tag Flt Pt Order
Flow Units Flow Units Baud Rate
Line Size Special Units Parity Slot Indices
Cal Number Total A Units Stop Bits Slot Variables
Var Slot 0 Val Var Slot 0 Idx
Damping Total B Units Min Resp Delay
Var Slot 1 Val Var Slot 1 Idx
Total C Units Variable Slots
Var Slot 2 Val Var Slot 2 Idx
Var Slot 3 Val Var Slot 3 Idx
Var Slot 4 Val Var Slot 4 Idx
Var Slot 5 Val Var Slot 5 Idx
Var Slot 6 Val Var Slot 6 Idx
Var Slot 7 Val Var Slot 7 Idx
Var Slot 8 Val Var Slot 8 Idx
Var Slot 9 Val Var Slot 9 Idx

Detailed Setup

REV AJ
August 2015
Totalizers Address Slot Indices Var Slot 0 Idx
Flt Pt Order Slot Variables Var Slot 1 Idx
Var Slot 0 Val
Baud Rate Var Slot 2 Idx
Var Slot 1 Val
Parity Var Slot 3 Idx
Var Slot 2 Val
Stop Bits Var Slot 4 Idx
Var Slot 3 Val
Min Resp Delay
August 2015

Var Slot 4 Val Var Slot 5 Idx


Variable Slots Var Slot 6 Idx
Var Slot 5 Val
Var Slot 6 Val Var Slot 7 Idx
Var Slot 7 Val Var Slot 8 Idx
Pulse Scaling Var Slot 9 Idx
Var Slot 8 Val
Pulse Width
Var Slot 9 Val
Pulse Mode
Coil Frequency Test
Proc Density
Diagnostics Flow LSL
Flow USL DI/O 1 Control
DI 1
DO 1

Modbus Control 1
Pulse Mode 1
DI/DO Config DI/O 1 High Limit 1
More Params
Reverse Flow DO 2 Low Limit 1
Output Config
Flow Limit 1 Hysteresis
LOI Config
Flow Limit 2 Control 2
Sig Processing
Total Limit Mode 2
Figure 28. Detailed Setup Menu Map

Device Info
Diag Alert High Limit 2
Device Reset
Total Control Low Limit 2
Total Mode Hysteresis
Tot Hi Limit
Tot Low Limit
Hysteresis

Basic Setup Elec Failure


Coil Open Ckt
Empty Pipe
Reverse Flow
Ground/Wiring
Process Noise
Elect Temp
Flow Display Elec Coat 1
Language Elec Coat 2
Operating Mode Disp Auto Lock Cont Meter Ver
SP Config Backlight Coil Over Curr
Coil Frequency Sensr Elec Sat
Damping Coil Power Lim
Lo-Flow Cutoff

Tag
Description
Message
Device ID
Detailed Setup Sensor S/N Software Rev
Sensor Tag Final Asmbl #
REV AJ Write protect
Revision Num

35
Quick Start Guide
Quick Start Guide August 2015

Product Certifications
Approvals Document
July 24, 2015
08732-AP01, Rev AF
Rosemount 8700M Magnetic Flowmeter Platform
Order 8732EM 8705M and 8711M/L Certification
Region Agency
Code Transm itter Rating Flow tube Rating Num ber
USA
- Ordinary Locations * Ordinary Location * FM 3048793
EU
FM Non-Incendive FM Non-Incendive w ith Intrinsically Safe Electrodes
N5 USA FM 3048793
Class I Div 2; DIP Class I Div 2; DIP
FM Explosion-Proof FM Explosion-Proof w ith Intrinsically Safe Electrodes
K5 USA FM 3048793
Class I Div 1; DIP Class I Div 1; DIP
CSA Non-Incendive CSA Non-Incendive w ith Intrinsically Safe Electrodes USA &
N6 CSA 70030489
Class I Div 2; DIP Class I Div 2; DIP Canada
CSA Explosion-Proof CSA Explosion-Proof w ith Intrinsically Safe Electrodes
KU USA CSA 70030489
Class I Div 1; DIP Class I Div 1; DIP
CSA Flam eproof, Increased Safety, and Dust. CSA Increased Safety w ith Intrinsically Safe Electrodes and
K6 Canada CSA ***
Zone 0 & 1 Dust. Zone 0 & 1

ND ATEX Dust ATEX Dust EU DEKRA 14ATEX0071 X

ATEX Non-Sparking ATEX Non-Sparking w ith Intrinsically Safe Electrodes


N1 EU DEKRA 14ATEX0071 X
ATEX Dust ATEX Dust
ATEX Flam eproof w ith Increased Safety ATEX Increased Safety w ith Intrinsically Safe Electrodes
K1 EU DEKRA 14ATEX0071 X
ATEX Dust ATEX Dust
IECEx
NF IECEx Dust IECEx Dust Global DEKRA
DEK14.0031X
IECEx Non-Sparking IECEx Non-Sparking w ith Intrinsically Safe Electrodes IECEx
N7 Global DEKRA
IECEx Dust IECEx Dust DEK14.0031X
IECEx Flam eproof w ith Increased Safety IECEx Increased Safety w ith Intrinsically Safe Electrodes IECEx
K7 Global DEKRA
IECEx Dust IECEx Dust DEK14.0031X
EAC Non-Sparking EAC Non-Sparking w ith Intrinsically Safe Electrodes Russia
N8 *** ***
EAC Dust EAC Dust **
EAC Flam eproof w ith Increased Safety EAC Increased Safety w ith Intrinsically Safe Electrodes Russia
K8 *** ***
EAC Dust EAC Dust **
INMETRO Non-Sparking INMETRO Non-Sparking w ith Intrinsically Safe Electrodes DEKRA - DEKRA
N2 Brazil
INMETRO Dust INMETRO Dust INMETRO 15.0007 X
INMETRO Flam eproof w ith Increased Safety INMETRO Increased Safety w ith Intrinsically Safe Electrodes DEKRA - DEKRA
K2 Brazil
INMETRO Dust INMETRO Dust INMETRO 15.0007 X
KOSHA Non-Sparking KOSHA Non-Sparking w ith Intrinsically Safe Electrodes
N9 Korea *** ***
KOSHA Dust KOSHA Dust
KOSHA Flam eproof w ith Increased Safety KOSHA Increased Safety w ith Intrinsically Safe Electrodes
K9 Korea *** ***
KOSHA Dust KOSHA Dust
NEPSI Non-Sparking NEPSI Non-Sparking w ith Intrinsically Safe Electrodes
N3 China NEPSI GYJ15.1180X
NEPSI Dust NEPSI Dust
NEPSI Flam eproof w ith Increased Safety NEPSI Increased Safety w ith Intrinsically Safe Electrodes
K3 China NEPSI GYJ15.1180X
NEPSI Dust NEPSI Dust

KN CCOE Flam eproof w ith Increased Safety CCOE Increased Safety w ith Intrinsically Safe Electrodes India PESO P354747/1

Com plies w ith only the local country product safety, electrom agnetic, pressure and other applicable regulations.
* Cannot be used in a classified or zoned hazardous location environm ent. No ordering code required.
** Custom s Union (Russia, Belarus and Kazakhstan)

*** Planned subm ittal or in process w ith Agency.

36
August 2015 Quick Start Guide

Approvals Document
July 24, 2015
08732-AP01, Rev AF
Approval Markings and Logos
Marking or
Symbol Symbol Region Meaning of Marking or Symbol
Name

CE European Union Compliance with all applicable European


Union Directives.

ATEX European Union Compliance with Equipment and Protective


systems intended for use in Potentially
Explosive Atmospheres directive (ATEX)
(94/9/EC)

C-tick Australia Compliance with Australian applicable


electromagnetic compatibility standards

FM Approved United States Compliance with the applicable ANSI


standards.

CSA US = United States Indicates that the product was tested and has
met the applicable certification requirements
C = Canada for the noted countries.

Eurasian Eurasian Customs Union Compliance with all of the applicable technical
Conformity (Russia, Belarus and regulations of the EAC Customs Union
(EAC) Kazakhstan)

EAC Eurasian Customs Union Compliance with Technical regulation, (TR CU


Hazardous (Russia, Belarus and 012/2011) – The safety of equipment for use
Location Kazakhstan) in explosive environments.

INMETRO Brazil Compliance with all of the applicable technical


regulations of Brazil.

NEPSI China Compliance with all of the applicable technical


regulations of China.

KCS Korea Compliance with all of the applicable technical


regulations of Korea.

Ordinary Location labels will be marked with CE, C-tick, FM, CSA and EAC logos.

37
Quick Start Guide August 2015

Approvals Document
July 24, 2015
08732-AP01, Rev AF
European Directive Information

A copy of the EC Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent
revision of the EC Declaration of Conformity can be found at www.rosemount.com.

Electro Magnetic Compatibility (EMC) (2004/108/EC)


Transmitter and Flowtube: EN 61326-1: 2013
Transmitters with output code “B” require shielded cable for the 4-20mA output, with shield terminated at the
transmitter.

Low Voltage Directive (LVD) (2006/95/EC)


EN 61010-1: 2010

Ingress Protection Rating for dust and water per EN 60079-0 and EN 60529 – IP66/68 (The IP68 rating only
applies to the flowtube and the remote junction box when the transmitter is remotely mounted. The IP68 rating
does not apply to the transmitter. The IP68 rating is only valid at a depth of 10 meters for 48 hours)

European Pressure Equipment Directive (PED) (97/23/EC)


PED Certification requires the “PD” option code.
CE marked models that are ordered without the “PD” option will be marked “Not Complaint to (97/23/EC)”

Mandatory CE-marking with notified body number 0575, for all flowtubes is located on the flowmeter label.
Category I assessed for conformity per module A procedures.
Categories II – III assessed for conformity per module H procedures.
QS Certificate of Assessment
EC No. 4741-2014-CE-HOU-DNV
Module H Conformity Assessment

8705 M Flanged Flowtubes


Line size 40mm to 900mm (1½-in to 36-in)
EN 1092-1 flanges and ASME B16.5 class 150 and ASME B16.5 Class 300 flanges.
Also available in ASME B16.5 Class 600 flanges in limited line sizes.

8711 Wafer Flowtubes


Line size 40mm to 200mm (1½-in to 8-in)

All other Rosemount Flowtubes – line sizes of 25mm (1-in) and less: Sound Engineering Practice (SEP).
Flowtubes that are SEP are outside the scope of PED and cannot be marked for compliance with PED.

38
August 2015 Quick Start Guide

Approvals Document
July 24, 2015
08732-AP01, Rev AF
Certifications
Factory Mutual (FM)

Ordinary Location Certification for FM Approvals


As standard, the transmitter and flowtube have been examined and tested to determine that the design meets
basic electrical, mechanical, and fire protection requirements by FM Approvals, a nationally recognized testing
laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).

8732EM Transmitter
Note: For Intrinsically Safe (IS) 4-20mA and Pulse Outputs on the 8732EM, output code “B” must be selected.

N5 Non-Incendive for Class I, Division 2, Groups ABCD: T4


Dust-Ignition Proof for Class II/III, Division 1, Groups EFG: T5
-ƒ&”7D”ƒ&
Enclosure Type 4X, IP66
Install per drawing 08732-2062

Special Conditions for Safe Use (X):


1. Units marked with “Warning: Electrostatic Charging Hazard” may either use non-conductive paint thicker
than 0.2 mm or non-metallic labeling. Precautions shall be taken to avoid ignition due to electrostatic
charge on the enclosure.
2. The intrinsically safe 4-20mA and pulse output cannot withstand the 500V isolation test due to integral
transient protection. This must be taken into consideration upon installation.
3. Conduit entries must be installed to maintain the enclosure ingress rating of IP66.
4. Unused conduit entries must use either used the Rosemount-supplied blanking plugs, or blanking plugs
certified in accordance with the protection type.

K5 Explosion-Proof for Class I Division 1, Groups CD: T6


Non-Incendive for Class I, Division 2, Groups ABCD: T4
Dust-Ignition Proof for Class II/III, Division 1, Groups EFG: T5
-ƒ&”7D”ƒ&
Enclosure Type 4X, IP66
Install per drawing 08732-2062

Special Conditions for Safe Use (X):


1. Units marked with “Warning: Electrostatic Charging Hazard” may either use non-conductive paint thicker
than 0.2 mm or non-metallic labeling. Precautions shall be taken to avoid ignition due to electrostatic
charge on the enclosure.
2. The intrinsically safe 4-20mA and pulse output cannot withstand the 500V isolation test due to integral
transient protection. This must be taken into consideration upon installation.
3. Conduit entries must be installed to maintain the enclosure ingress rating of IP66.
4. Unused conduit entries must use either used the Rosemount-supplied blanking plugs, or blanking plugs
certified in accordance with the protection type.

39
Quick Start Guide August 2015

Approvals Document
July 24, 2015
08732-AP01, Rev AF
8705-M and 8711-M/L Flowtube
Note: When used in hazardous (classified) locations:
The 8705-M and 8711-M/L may only be used with a certified 8732EM transmitter.

N5 Non-Incendive with Intrinsically Safe Electrodes


for Class I, Division 2, Groups ABCD: T3…T5
Dust-Ignition Proof for Class II/III, Division 1, Groups EFG: T2…T5
-ƒ&”7D”ƒ&
Enclosure Type 4X, IP66/68 (IP68 remote mount only)
Install per drawing 08732-2062

Special Conditions for Safe Use (X):


1. Units marked with “Warning: Electrostatic Charging Hazard” may either use non-conductive paint thicker
than 0.2 mm or non-metallic labeling. Precautions shall be taken to avoid ignition due to electrostatic
charge on the enclosure.
2. If used with flammable process fluid, the electrode circuit must be installed as intrinsically safe (Ex ia).
3. Conduit entries must be installed to maintain a minimum enclosure ingress rating of IP66.
4. Unused conduit entries must use either used the Rosemount-supplied blanking plugs, or blanking plugs
certified in accordance with the protection type.

K5 Explosion-Proof with Intrinsically Safe Electrodes


for Class I Division 1, Groups CD: T3…T6
Non-Incendive with Intrinsically Safe Electrodes
for Class I, Division 2, Groups ABCD: T3…T5
Dust-Ignition Proof for Class II/III, Division 1, Groups EFG: T2…T5
-ƒ&”7D”ƒ&
Enclosure Type 4X, IP66/68 (IP68 remote mount only)
Install per drawing 08732-2062

Special Conditions for Safe Use (X):


1. Units marked with “Warning: Electrostatic Charging Hazard” may either use non-conductive paint thicker
than 0.2 mm or non-metallic labeling. Precautions shall be taken to avoid ignition due to electrostatic
charge on the enclosure.
2. If used with flammable process fluid, or if installed in a Class I Division I area, the electrode circuit must
be installed as intrinsically safe (Ex ia).
3. Conduit entries must be installed to maintain a minimum enclosure ingress rating of IP66.
4. Unused conduit entries must use either used the Rosemount-supplied blanking plugs, or blanking plugs
certified in accordance with the protection type.

40
August 2015 Quick Start Guide

Approvals Document
July 24, 2015
08732-AP01, Rev AF
Canadian Standards Association (CSA)

CLASS 2258 02 - PROCESS CONTROL EQUIPMENT - For Hazardous Locations – To Canadian Requirements.

N6 Class I, Groups A, B, C and D (Intrinsically Safe Output and Electrode circuit)


N6 Class I, Division 2, Groups A, B, C and D (Non-Incendive)
N6 Class II, Division 1, Groups E, F and G (Dust Ignition Proof)

Magnetic Flow Meter – Model 8732EM Transmitter with integral or remote mount to Model 8705M or Model
8711M/L Magnetic Flow Tubes. Enclosure Type 4X and IP 66 Rated.

For Remote Mount Configuration – Temperature Code T4 with an Ambient Operating Temperature Range: -40°C
чdĂчнϲϬΣ͕ǁŝƚŚŽƌǁŝƚŚŽƵƚ>ŵĞƚĞƌ͕ǁŝƚŚŽƌǁŝƚŚŽƵƚĚŝŐŝƚĂů/ͬKĂŶĚͬŽƌƉƵůƐĞŽƵƚƉƵƚƐǁŚĞŶŝŶƐƚĂůůĞĚƉĞƌ
Rosemount Drawing 08732-2061.

For Integral Mount Configuration – Ambient Operating Temperature Range: -29°C чdĂчнϲϬΣ. Temperature
Code T3-T6 dependent on line size of Flow Tubes for Process Temperature. The T-Code is defined as per
Rosemount Drawing 08705-00CS and 08732-00CS for ‘N6’ option or ‘KU’ option.

CLASS 2258 82 - PROCESS CONTROL EQUIPMENT - For Hazardous Locations –To US Requirements

KU Class I, Division 1, Groups C and D (Explosion Proof)


N6, KU Class I, Groups A, B, C and D (Intrinsically Safe Output and Electrode circuit
N6, KU Class I, Division 2, Groups A, B, C and D (Non-Incendive)
N6, KU Class II, Division 1, Groups E, F and G (Dust Ignition Proof)

Magnetic Flow Meter – Model 8732EM Transmitter with integral or remote mount to Model 8705M or Model
8711M/L Magnetic Flow Tubes. Enclosure Type 4X and IP 66 Rated.

For Remote Mount Configuration – Temperature Code T6 for Explosion Proof, T5 for Dust Ignition Proof, and T4
for Non-Incendive. Ambient Operating Temperature Range: -ϰϬΣчdĂчнϲϬΣ͕ǁŝƚŚŽƌǁŝƚŚŽƵƚ>ŵĞƚĞƌ͕ǁŝƚŚ
or without digital I/O and/or pulse outputs when installed per Rosemount Drawing 08732-2061.

For Integral Mount Configuration – Ambient Operating Temperature Range: -ϮϵΣч dĂчнϲϬΣ. Temperature
Code T3-T6 dependent on line size of Flow Tubes for Process Temperature. The T-Code is defined as per
Rosemount Drawing 08705-00CS and 08732-00CS for ‘N6’ option or ‘KU’ option.

Special Conditions of Safe Use:

1. For use with the appropriate 8705M and 8711M/L Flow tubes only.
2. When the 8732EM transmitter is integrally mounted to 8705M or 8711M/L Flow Tubes, the ambient
temperature ranges marked on each product need to be taken into consideration before installation.
The Ambient temperature range for 8732EM transmitter is -ϰϬΣчdĂчнϲϬΣĂŶĚƚŚĞĂŵďŝĞŶƚ
temperature range for 8705M or 8711M/L Flow Tubes is -ϮϵΣчdĂчнϲϬΣ͘ Therefore, the -29°C rating
of the flow tubes will limit the overall cold temperature range of the complete system unless other
approved temperature control methods are employed.

41
Quick Start Guide August 2015

Approvals Document
July 24, 2015
08732-AP01, Rev AF

42
August 2015 Quick Start Guide

Approvals Document
July 24, 2015
08732-AP01, Rev AF

43
Quick Start Guide August 2015

Approvals Document
July 24, 2015
08732-AP01, Rev AF

44
August 2015 Quick Start Guide

Rosemount 8700M Magnetic Flowmeter Platform


IEC EX & ATEX Approval Document
January 29, 2015,
08732-AP02, Rev AB

1. Equipment Markings – See section VI in the tables on the following pages


a. EC-Type Examination Certificate (ATEX): DEKRA 14ATEX0071_X
b. Certificate of Conformity (IEC Ex): IEC Ex DEK 14.0031X
2. Required Documentation:
a. 08732-2060 Installation Drawing Model 8732EM, 8705M, 8711-M/L ATEX/IEC Ex Hazardous (Ex)
Locations
b. 08732-1504 Installation Drawing, 8732EM Transmitter Wiring
3. Referenced Documentation:
a. 00825-0100-4444.pdf(Hart) & 00825-0400-4444(Modbus), Quick Installation Guide
b. 00809-0100-4444.pdf, Reference Manual
c. 08732-AP01, Approvals Document
4. The Required and Referenced Documents listed above address the following items:
a. Instructions for safety i.e.
i. Putting into service
ii. Use
iii. Assembling and dismantling
iv. Maintenance, overhaul and repair
v. Installation
vi. Adjustment
b. Where necessary, training instructions
c. Details which allow a decision to be made as to whether the equipment can be used safely in the
intended area under the expected operating conditions
d. Electrical parameters, maximum surface temperatures and other limit values
i. Electrical –
1. See document 08732-2060
2.

Rosemount 8732EM Flow Transmitter


Power input 90 - 250VAC, 0.45A, 40VA

12 - 42VDC, 1.2A, 15W


Pulsed circuit Internally powered (Active): Outputs up to 12VDC, 12.1mA,
73mW Externally powered (Passive): Input up to 28VDC,
100mA, 1W
4-20mA output circuit Internally Powered (Active): Outputs up to 25mA, 24VDC,
600mW Externally Powered (Passive): Input up to 25mA,
30VDC, 750mW
MODBUS Internally Powered (Active): Outputs up to 100mA, 3.3VDC,
100mW
Um 250V
Coil excitation output 500mA, 40V max, 9W max

Rosemount 8705-M and 8711-M/L Flowtube(1)

Coil excitation input 500mA, 40V max,


20W max
Electrode circuit 5V, 200uA, 1mW
(1) Provided by the transmitter
e. Special Conditions for Safe Use (X):

45
Quick Start Guide August 2015

Rosemount 8700M Magnetic Flowmeter Platform


IEC EX & ATEX Approval Document
January 29, 2015,
08732-AP02, Rev AB

i. For processes requiring EPL Ga and Gb, rated equipment: electrode, grounding ring, and lining
protector materials Titanium and Zirconium are not allowed.
ii. When “Special Paint Systems” are applied, instructions for safe use regarding potential
electrostatic charging hazard have to be followed.
iii. Terminals 1,2,3,4, for data communication, cannot withstand the 500 V isolation test between
signal and ground, due to integral transient protection. This must be taken into account upon
installation.
iv. Conduit entries must be installed to maintain the enclosure ingress rating of IP66.
v. In order to maintain the ingress protection level on the M3 and M4 electrode housing, the copper
crush washer that seals the electrode access plug shall be replaced when the plug is reinstalled.
The copper crush washer is one time use only.
vi. The flow tube and transmitter are not allowed to be thermally insulated.
vii. The property class of the special fasteners which attach the Magnetic Flow Tube or Transmitter
Remote Junction Box to the Magnetic Transmitter is A2-70 or A4-70 SST.
viii. For information on the dimensions of the flameproof joints the manufacturer shall be contacted.
ix. The Magnetic Flow Meter Tube contains nonconductive liners over the grounded tube. For
process requiring EPL Ga, precautions shall be taken to avoid the liner being charged by the flow
of nonconductive media.
f. Where necessary, the essential characteristics of tools which may be fitted to the equipment
g. List of the standards, including the issue date, with which the equipment is declared to comply:
i. ATEX - EN 60079-0: 2012 +A11, EN 60079-1: 2007, EN 60079-7: 2007. EN 60079-11: 2012, EN
60079-15: 2010, EN 60079-26: 2007, EN 60079-31: 2014
ii. IEC EX - IEC 60079-0: 2011, IEC 60079-1: 2007, IEC 60079-7: 2006 IEC 60079-11: 2011, IEC
60079-15: 2010, IEC 60079-26: 2006, IEC 60079-31: 2013
h. Supply wire requirements;
Use 10 - 18 AWG wire rated for the proper temperature of the application. For wire 10 - 14 AWG use lugs
or other appropriate connectors. For connections in ambient temperatures above 122°F (50 °C), use a
wire rated for 194 °F (90 °C).
i. Contact address;
i. Rosemount Inc.
12001 Technology Drive
Eden Prairie
MN 55344
United States of America

46
August 2015 Quick Start Guide

Rosemount 8700M Magnetic Flowmeter Platform


IEC EX & ATEX Approval Document
January 29, 2015,
08732-AP02, Rev AB

Nomenclature Magnetic Flow Transmitter Model 8732EM and electrical data

8732EM R 1 B 2 K1 … M4 RT50 … SH … V2 … F090…


I II III IV V VI VII VIII IX X

Desig-
nation
Explanation Value Explanation

I Model 8732EM Magnetic Flow Transmitter – Field Mount


R Remote Mount
II Transmitter Mount
T Integral Mount
1 AC (90 - 250 Vac, 50 / 60 Hz), not for Ex nA
III Transmitter Power Supply
2 DC (12 - 42 Vdc)
A 4 - 20 mA with digital HART Protocol & Scalable
Pulse Output
IV Outputs B 4 - 20 mA Intrinsically Safe Output with digital HART
Protocol & Intrinsically Safe Scalable Pulse Output
M Modbus RS-485
1 or 4 ½-14 NPT female
V Conduit entries
2 or 5 CM20, M20 female
II 2 (1) G Ex d e [ia Ga] IIC T6…T3 Gb
II 2 D Ex tb IIIC T80 °C…T200 °C Db
K1 ATEX
II 2 (1) G Ex d [ia Ga] IIC T6…T3 Gb *
II 2 D Ex tb IIIC T80 °C…T200 °C Db
Ex d e [ia Ga] IIC T6…T3 Gb
Ex tb IIIC T80 °C…T200 °C Db
K7 IECEx
Ex d [ia Ga] IIC T6…T3 Gb *
Ex tb IIIC T80 °C…T200 °C Db
II 3 (1) G Ex nA [ia Ga] IIC T4…T3 Gc ***
N1 ATEX
II 2 D Ex tb IIIC T80 °C…T200 °C Db
VI Safety Approval Option Ex nA [ia Ga] IIC T4…T3 Gc ***
N7 IECEx
Ex tb IIIC T80 °C…T200 °C Db
II 2 D Ex tb IIIC T80 °C…T200 °C Db
ND ATEX II 2 D Ex tb IIIC T80 °C…T200 °C Db
II (1) G [Ex ia Ga] IIC **
Ex tb IIIC T80 °C…T200 °C Db
NF IECEx Ex tb IIIC T80 °C…T200 °C Db
[Ex ia Ga] IIC **
NOTE: * Integral Mount (see II) option only
** Intrinsically Safe Output (see IV) option only
*** DC Transmitter Power Supply only (12 - 42 Vdc)
M4 LOI
VII Display Option
M5 Display
RTxx **** Standard Temperature Component
VIII Remote Cable Option RHxx **** Extended Temperature Component
NOTE: **** Length = xx x 10 ft, max. 500 ft
-- Aluminum, standard paint
IX Options SH Stainless Steel Electronics Housing
Vx Special Paint Systems *****
X Specials F090x Special Paint Systems *****
NOTE: ***** Subject to special conditions for safe use.

47
Quick Start Guide August 2015

Rosemount 8700M Magnetic Flowmeter Platform


IEC EX & ATEX Approval Document
January 29, 2015,
08732-AP02, Rev AB

Nomenclature Magnetic Flow Tube Model 8705-M and electrical data

8705 … S A 005 … M4 K1 … G1 L1 B3 … J1 SJ … V1 … SH … F090x


I II III IV V VI VII VIII IX X XI XII XIII XIV

Designation Explanation Value Explanation


I Model 8705 Magnetic Flowtube
II Electrode Material Custom See special conditions for safe use
III Electrode Types Custom Seal of electrodes comply with IEC 61010-1
005 ½” NPS (15 mm)
IV Line Size to to
360 36” NPS (900 mm)
M0 Category 2 G or 3 G, EPL Gb or Gc
M1 Category 2 G or 3 G, EPL Gb or Gc
V Electrode Housing * M2 Category 1/2 G or 1/3 G, EPL Ga/Gb or Ga/Gc
M3 Category 1/2 G or 1/3 G, EPL Ga/Gb or Ga/Gc
M4 Category 1/2 G or 1/3 G, EPL Ga/Gb or Ga/Gc
II 1/2 G Ex e ia IIC T5…T3 Ga/Gb *
II 2 D Ex tb IIIC T 80 °C…T 200 °C Db
K1 ATEX
II 2 G Ex e ib IIC T5…T3 Gb **
II 2 D Ex tb IIIC T 80 °C…T 200 °C Db
Ex e ia IIC T5…T3 Ga/Gb *
Ex tb IIIC T 80 °C…T 200 °C Db
K7 IECEx
Ex e ib IIC T5…T3 Gb **
Ex tb IIIC T 80 °C…T 200 °C Db
II 1/3 G Ex nA ia IIC T5…T3 Ga/Gc * line sizes 8”- 36”
II 2 D Ex tb IIIC T 80 °C…T 200 °C Db
VI Safety Approvals N1 ATEX
II 3 G Ex nA ic IIC T5…T3 Gc * line sizes 0.5” – 6” / **
II 2 D Ex tb IIIC T 80 °C…T 200 °C Db
Ex nA ia IIC T5…T3 Ga/Gc * line sizes 8”- 36”
Ex tb IIIC T 80 °C…T 200 °C Db
N7 IECEx
Ex nA ic IIC T5…T3 Gc * line sizes 0.5” – 6” / **
Ex tb IIIC T 80 °C…T 200 °C Db
ND ATEX II 2 D Ex tb IIIC T 80 °C…T 200 °C Db
NF IECEx Ex tb IIIC T 80 °C…T 200 °C Db
NOTE: * Electrode Housing M2, M3 and M4 only
** Electrode Housing M0 and M1 only
Grounding rings
VII Custom See special conditions for safe use
material
Lining protector
VIII Custom See special conditions for safe use
material
Mounting
IX B3 Integral Mount with Model 8732EM
Configuration
Optional conduit
X J1 CM20, M20 female
entries
Remote Junction Box -- Aluminum, Standard Paint
XI
(RJB) material SJ 316 Stainless Steel
XII Special paint options Vx Special Paint Systems ***
Wrapper (housing) -- Carbon Steel (w. Aluminum RJB), Standard Paint
XIII
material SH 316 Stainless Steel (w. Stainless Steel RJB)
XIV Specials F090x Special Paint Systems ***
NOTE: *** Subject to special conditions for safe use.

48
August 2015 Quick Start Guide

Rosemount 8700M Magnetic Flowmeter Platform


IEC EX & ATEX Approval Document
January 29, 2015,
08732-AP02, Rev AB

Nomenclature Magnetic Flow Tube Model 8711-M/L and electrical data

8711 … S A 15F L … K1 … G1 … J1 SJ … V1 … F090x


I II III IV V VI VII VIII IX X XI

Designation Explanation Value Explanation


I Model 8711 Magnetic Flow Tube
II Electrode Material Custom See special conditions for safe use
III Electrode Types Custom Seal of electrodes comply with IEC 61010-1.
015 1½” NPS (40 mm)
IV Line Size to to
080 8” NPS (900 mm)
Mounting L Remote Mount from Transmitter
V
Configuration M Integral Mount with Transmitter
K1 II 2 G Ex e ib IIC T5…T3 Gb
ATEX II 2 D Ex tb IIIC T 80 °C…T 200 °C Db
Ex e ib IIC T5…T3 Gb
K7 IECEx
Ex tb IIIC T 80 °C…T 200 °C Db
II 3 G Ex nA ic IIC T5…T3 Gc
VI Safety Approvals N1 ATEX
II 2 D Ex tb IIIC T 80 °C…T 200 °C Db
Ex nA ic IIC T5…T3 Gc
N7 IECEx
Ex tb IIIC T 80 °C…T 200 °C Db
ND ATEX II 2 D Ex tb IIIC T 80 °C…T 200 °C Db
NF IECEx Ex tb IIIC T 80 °C…T 200 °C Db
Grounding rings
VII Custom See special conditions for safe use
material
Optional conduit
VIII J1 CM20, M20 female
entries
-- Aluminum, Standard Paint *
Remote Junction
IX SJ 316 Stainless Steel *
Box material
NOTE:* Flowtube with Carbon Steel Wrapper (housing)
Special paint
X Vx Special Paint Systems **
options
XI Specials F090x Special Paint Systems **
NOTE: ** Subject to special conditions for safe use.

49
Quick Start Guide August 2015

Figure 29. Rosemount 8732EM Installation and Wiring Drawings

50
August 2015 Quick Start Guide

51
00825-0400-4444
Quick Start Guide
00825-0400-4444, Rev. AA
August 2015

Global Headquarters
Emerson Process Management
6021 Innovation Blvd
Shakopee, MN 55379, USA
+1 800 522 6277 or +1 303 527 5200
+1 303 530 8459
[email protected]

North America Regional Office


Emerson Process Management
7070 Winchester Circle
Boulder, CO 80301 USA
+1 800 522 6277 or +1 303 527 5200
+1 303 530 8459
[email protected]

Latin America Regional Office


Emerson Process Management
Multipark Office Center
Turrubares Building, 3rd & 4th floor
Guachipelin de Escazu, Costa Rica
+1 506 2505-6962
+1 954 846 5121
[email protected]

Europe Regional Office


Emerson Process Management Flow B.V.
Neonstraat 1
6718 WX Ede
The Netherlands
+31 (0) 318 495555
+31 (0) 318 495556
[email protected]

Asia Pacific Regional Office


Emerson Process Management Asia Pacific Pte Ltd
1 Pandan Crescent
Singapore 128461
+65 6777 8211
+65 6777 0947
[email protected]

Middle East and Africa Regional Office


Emerson Process Management
Emerson FZE P.O. Box 17033,
Jebel Ali Free Zone - South 2
Dubai, United Arab Emirates
+971 4 8118100
+971 4 8865465 Standard Terms and Conditions of Sale can be found at:
[email protected] www.rosemount.com\terms_of_sale.
The Emerson logo is a trademark and service mark of Emerson
Electric Co.
Rosemount and Rosemount logotype are registered
trademarks of Rosemount Inc.
All other marks are the property of their respective owners.
© 2015 Rosemount Inc. All rights reserved.

You might also like