As2941-08 Diesel Fire Pump Controller (Combined) - LR
As2941-08 Diesel Fire Pump Controller (Combined) - LR
As2941-08 Diesel Fire Pump Controller (Combined) - LR
1
-2-
FUNCTION Designed to automatically operate a diesel fire pump engine when the
contacts of a remote water pressure switch close.
OPERATION: Starting - System is designed to automatically start the engine by closing a remote
pressure switch. System may be test run by pressing the start button on the
controller fascia.
Stopping - Push controller stop/reset button.
1.1
-
JOCKEY PUMP: If fitted, automatically maintains water pressure in system pipe work.
AUTO button - Automatically starts and stops the jockey pump upon the closure or
opening of a remote located jockey pressure switch.
JOCKEY PUMP ISOLATE button - Jockey pump will not operate.
MANUAL button - Allows the Jockey pump to run continuously whilst pressed.
INTRODUCTION
This controller is a dedicated microprocessor that operates in a similar fashion to an IBM or Macintosh
Computer.
It has specific input, output and display capabilities that have been designed to meet all the requirements of
AS2941-2008 (The Australian Fire Pump Standard).
AS2941 REQUIREMENTS
A fire pump controller must „start‟ the diesel engine driving a fire pump in response to an external „start‟ signal,
usually a pressure switch that is plumbed into the fire service ring main.
Once started the engine must continue to run until it is manually stopped or runs out of fuel.
In the event of an engine not starting immediately it must be „cranked‟ for 15 seconds followed by a pause in
cranking of 15 seconds. This cycle must be repeated 6 times or until the engine starts.
1.2
-4-
CONTROL SWITCHES
CRANK ISOLATE SWITCH
A two position rotary key lockable switch located to the left of the liquid crystal display.
In the isolate position the engine cranking circuits are disconnected from the controller. Automatic pressure switch
starting and controller manual starting are disabled.
This switch position will allow routine maintenance to be undertaken without concern about the engine
starting.
In the normal position the controller will crank the engine whenever an external start signal is present or when
the controller start button is pressed.
Note that turning this switch to the isolate position will cause the controller to generate an alarm condition.
When this switch is in the isolate position the engine can still be started using the emergency manual start
buttons located adjacent to the controller.
CONTROL BUTTONS
DISPLAY SCROLL BUTTONS
Two buttons located to the right of the liquid crystal display. Many sorts of information can be displayed on the
liquid crystal; theses buttons allow an operator to „scroll‟ through display items to get to specific required
information. You may scroll „up‟ or „down‟ to get to the required information.
1.3
-5-
Engine Alternator
- Amps DC
Fuel Remaining
--- %
Coolant Temperature
-- C
--- KPA
Control Battery
--.- Volts DC
Control Charge Rate
-.- Amps DC
1.4
-6-
START BUTTON
Allows an operator to test start the fire pump engine in order to carry out routine maintenance. It can also be used
to start the engine if external start signals have failed or are not present.
Note: that the crank isolate key switch must be in the normal position for the start button to operate.
When pressed will send a stop signal to the engine fuel stop solenoid.
Note: if an external start signal is present (pump on call) the engine will not stop. The stop button also
functions as a reset on any „latched‟ alarm information i.e. „Charger Supply Fail‟ or „Oil Pressure Low‟.
Note: if alarm condition is still present then stop /reset button cannot clear the alarm indication.
Will cause all 32 alarm and status light emitting diodes to illuminate. It is provided as a test for indicator failure.
When pressed will test the external alarm bell if connected to the controller bell circuit. It will also test the
flashing alarm light or strobe if connected to the controller visible alarm circuit.
When pressed will mute the alarm bell if it is currently operating. The alarm cause will continue to be
indicated by the alarm and status LED‟s. Alarm mute will automatically cancel when all alarm causes are
cleared or reset.
When an alarm condition is muted a further alarm condition will not cause the bell to operate.
Note: that the flashing light or strobe is not turned off when alarm mute is pressed.
The battery chargers are current limited constant potential type that will maintain an optimum charge level in
each set of batteries. Chargers will turn on at maximum charge rate when battery voltage has fallen to
nominal voltage plus .75V. Charger will turn off completely when battery voltage has risen to nominal voltage plus
approximately 2.5V.
1.5
-7-
Note: That the chargers are not a trickle charger and must have a battery connected for correct operation. When
the boost button is pressed the charger will turn on at maximum charge rate, charging the battery up to the high
charge turn off point.
When diesel engine is running press button to simulate an over speed. Engine will stop and indicate over
speed. To reset press stop reset button.
POWER AVAILABLE
These green LED‟s should be continuously lit and indicate the presence of the AC supply.
CONTROL INDICATORS
PUMP STANDBY
These green LED‟s should be continuously lit and indicate a normal standby situation.
PUMP RUNNING
CRANK ISOLATED
Will indicate that the crank isolate key switch is not in the normal position.
1.6
-8-
START FAIL
Will indicate that the diesel engine has not started after completing 6 crank cycles.
This indicator will flash if alarm cause has occurred but is no longer present. Cancel flashing by pressing
STOP/RESET.
Indicates failure of the AC to battery chargers. When supply fail LED‟s are lit the green power available LED‟s
must be off.
Indicates when fuel tank level is low. This level is adjustable with a factory setting of 75%. Flashing LED‟s
indicate that fuel level was low and is now normal. Pressing the STOP/RESET button will cancel the
flashing.
ALARM MUTED
Indicates that an alarm condition exists and the alarm mute button has been pressed.
The LED‟s will turn off automatically when the alarm condition ceases.
Refer to above.
Indicates when start battery voltage has fallen to an unacceptable low level. This level is adjustable, with a factory
setting of 12 / 24 volts.
Flashing LED‟s indicate that start battery voltage was unacceptably low and is now normal. Pressing the
stop/reset button will cancel the flashing. Although the controller can deem a start battery as "failed" it may
continue to attempt starting.
1.7
-9-
Refer to above.
ENGINE OVERSPEED
Indicates when diesel engine speed exceeds programmed set point, this level is adjustable.
An over speed alarm status will display then the engine will stop.
If this condition occurs during routine testing, check program settings or call a service technician.
This indicator will flash if alarm cause has occurred but is no longer present. Cancel flashing by pressing
STOP/RESET.
Indicates when the diesel engine coolant temperature exceeds that’s recommended by the engine
manufacturer. This level is adjustable with a factory setting of 95°C.
Although a Coolant Temperature High alarm may be displayed the engine is not stopped.
If this condition occurs during routine testing the engine should be immediately stopped and attended to by a
competent mechanic.
For engines fitted with a water jacket heater; failure of which could prevent engine starting; a low
temperature alarm can be indicated. This condition will be indicated by the "Coolant Temperature High" LED’s
flashing at a fast rate. The engine should be attended to immediately by a competent mechanic.
This indicator will flash if alarm cause has occurred but is no longer present. Cancel flashing by pressing
STOP/RESET.
Indicates when the diesel engine lubricating oil pressure is less than that recommended by the engine
manufacturer. This level is adjustable with a factory setting of 50KPA.
Although an oil pressure low alarm status may be displayed, the engine is not stopped.
If this condition occurs during routine testing the engine should be immediately stopped and attended to by a
competent mechanic.
This indicator will flash if alarm cause has occurred but is no longer present. Cancel flashing by pressing
STOP/RESET.
1.8
- 10 -
CONTROLLER FAIL
Indicates if the microprocessor stops operating. Detected by “Hard Wired‟ circuitry outside of the
microprocessor. This alarm status may or may not indicate that the controller is unable to start the diesel
engine in a fire situation. However competent technicians should attend to this situation at the earliest
possibility.
Are rated for a maximum current of 1A @ AC1 and a maximum voltage of 32VDC. If these ratings are
exceeded, even for the shortest possible time, permanent damage may result, causing the controller to be
unable to start the engine.
Is normally “energised‟ and changes to the state indicated on the drawings for microprocessor failure.
Note: that both batteries flat or disconnected will also cause this condition.
Will energise when all systems are normal and controller / engine are ready to start in a fire situation.
Will energise when low battery volts on start and control condition exists, or has existed.
Note: that engine fault does not necessarily mean the engine has stopped.
Note: that if both batteries fail or are disconnected the microprocessor will eventually stop and this alarm will
disappear.
Will energise when diesel engine is at a speed higher than starter motor cut out speed.
1.9
- 11 -
Will energise when the engine has been told by the control panel to start and has not. This contact is most suited
when a pump fail contact is required to drive external circuitry.
Power is continually being consumed by the controller and under normal conditions this power is being
replaced by the battery chargers. If a charger supply failure condition exists for 24 hours the power
consumed by the controller will cause batteries to go flat.
Attention from competent personnel should happen at the earliest possible time. If competent repair people are
not available, isolate AC supply and disconnect both batteries.
Notification to Local Fire Authorities and continual supervision should occur until all systems are back to
normal.
INSTALLATION
The controller should be mounted in a position away from vibration, heat and hot exhaust pipes and potential diesel
fuel and water spills.
If located outdoors considerations must be given to a sun shade. Direct sunlight combined with high ambient
temperatures will cause controller failure.
Note: that PVC insulated engine and control wiring will also fail if continually subjected to UV radiation (i.e.
sunlight).
The controller is certified to IP54 AS 1939 and has a "Lexan" membrane fascia. Continual UV radiation on fascia
will cause permanent damage and possibly controller failure.
Controller should be wired to solenoid panel, engine, external start signal and alarm circuits. Using the
schematic drawings and termination diagrams supplied with the controller.
Note: that even though the controller has fuses and reverse polarity protection, various components of the
controller can suffer permanent damage if incorrectly connected.
1.10
- 12 -
Before connecting AC supply or batteries, double check all wiring and stated voltage rating which will be on a Silver
or White /Black ID Sticker located on inside of controller door.
TESTING
Verify that engine is okay to run; fuel; lube oil; coolant etc.
Controller will take a few seconds to initialize and will then display serial no. and software revision.
Scroll up twice.
Display will show start battery voltage and charge rate. Both should be zero.
Leaving crank isolate switch in "isolate" position; scroll up & down, press a few buttons to get a "feel" for what’s
happening.
Apply AC supply to controller. Battery charge rate should now be about 3 AMPS DC.
If display shows 0.0 AMPS DC momentarily press the appropriate charger boost button; correct charge rate
should now be displayed.
1.11
- 13 -
FUSES
Fuses are fitted to several of the cards fitted to the controller. They have been fitted to protect the controller
components from abnormal load conditions and unusual transients. If a fuse "blows" replace only with size and
rating specified. Fitting larger fuses than that specified will eventually lead to permanent irreplaceable
damage to controller and/or components. Before replacing fuses or removing plug in cards, turn off AC supply
and disconnect batteries.
F1 Control Battery
5A Blade Automotive
F2 Start Battery
5A Blade Automotive
F3 AC Mains Supply
5A Automotive
F5 Auxiliary Supply
5A Blade Automotive
F1 Charger Protection
7.5A Blade Automotive
1.12
- 14 -
F1 Alarm Bell
F2 Flashing Light
1A Resettable Fuse
To install an electric Jockey Pump with the Diesel Fire Pump Panel, switch dipswitch 4 to the “on‟ position
(on the processor card), remove mains power, remove both Start and Control batteries, wait 1 minute,
replace both batteries and mains, and a scrollable Jockey Pump screen will appear on the LCD, displaying
Jockey Pump Status, and Jockey Pump switch status.
AUTO: The Jockey Pump will automatically Start/Stop when the Jockey Pump pressure switch is closed /
opened.
JOCKEY PUMP ISOLATE: The Jockey Pump will not operate when the Jockey Pump pressure switch is closed
/ opened. The Jockey Pump will not run.
1.13
-1-
AS2941-08
DIGITAL DIESEL FIRE
PUMP CONTROLLER
INSPECTION & TEST SHEET
2
-2-
EQUIPMENT LIST:
START CHARGER 80-PCB-207212 12v or 24v
CONTROL CHARGER 80-PCB-207212 12v or 24v
PCB'S (POWER SUPPLY CARD 80-PCB-207207
MOTOR CONTROLLER 80-PCB-207206
I/O CARD 80-PCB-207204
LED CARD 80-PCB-207210
PROCESSOR 80-PCB-207209
I/O TERMINAL 80-PCB-207205
JOCKEY PUMP 80-PCB-207211
2x TRANSFORMERS: 240/28 80-TRANS-1PH-028V
2.1
-3-
DESCRIPTION / MODIFIED:
2.2
WELLING & CROSSLEY PTY LTD
59 EXPORT DR BROOKLYN VIC 3012
1042 CANLEY VALE RD WETHERHILL
PARK NSW 2164
5/235 CAMBOON RD MALAGA WA 6090
2/55 CHIRSTENSEN RD STAPYLTON QLD 4207
53 ELIZABETH KNOX PLACE
MT.WELLINGTON AUCKLAND
1072 NZ
WELLING & CROSSLEY PTY LTD
50-58 NEW STREET STH KINGSVILLE VIC. 3015
2/6-8 ALLEN PLACE WETHERILL PK NSW 2164
5/235 CAMBOON RD MALAGA WA 6090
11/1909 IPSWICH ROCKLEA QLD 4106
EMAIL: [email protected]
WELLING & CROSSLEY PTY LTD
50-58 NEW STREET STH KINGSVILLE VIC. 3015
2/6-8 ALLEN PLACE WETHERILL PK NSW 2164
5/235 CAMBOON RD MALAGA WA 6090
11/1909 IPSWICH ROCKLEA QLD 4106
EMAIL: [email protected]
INSTALLATION INSTRUCTIONS FOR FUEL SENDER
1. To install the float arm loosen screw "h", remove the short piece of rod and discard it.
(Refer to Fig. 1)
1. Insert the float arm/rod to the proper length. (Length located in table 1R on following
page)
1. Allow 25mm to protrude out from the "h" point. (Refer to Fig. 2)
1. Carefully cut off any excess arm/rod with a bolt cutter or a similar tool, taking care not to
damage the assembly.
18
2.3
Installation of the tank unit sender into the fuel tank using a flange tank
19
2.4
1. Slide the rubber gasket up to the bottom of the fuel sender flange. Than slide the second
flange over fuel sender to bottom of rubber gasket. Align the pre-threaded holes in mounting
flange and rubber gasket with those in fuel sender flange. Use 25 mm screw to loosely attach
mounting flange. Do not tighten completely. (Refer to Fig. 3)
CAUTION: Make certain float arm has a clear field of motion before tightening screws in
flange assembly.
1. Slip the fuel sender assembly into the 59mm hole in the tank and turn until it goes into the
tank. (Refer to Fig. 4)
NOTE: Make sure the float is installed as shown in Fig. 1, if installed backwards, the fuel
gauge will indicate "full" when the tank is actually empty and vice versa.
20
2.5