Application
Titanus ProSens and Titanus TopSens are used when one encounters conditions
which hinder a standard solution or even make it impossible:
– Environmental conditions such as dirt, moisture, extreme cold, high voltage etc. in-
hibit the performance of the fire detectors.
– High halls and rooms with an intensive air change (e.g. air conditioning systems)
show a strong degree of smoke dilution, thereby delaying a rapid alarm response.
– Especially sensitive objects and a high concentration of valuable property (operating
data, data-dependant production means, software etc.) require particularly fast inter-
vention.
– In a production plant running 24 hours a day, the required maintenance work cannot
be performed on fire detectors if they are located in the production area.
– Access is often difficult or impossible in hollow spaces or vertical ducts.
– "Invisible" detection is desired in cultural buildings or design architecture.
Scope of application
ProSens TopSens
Clean rooms z
High open rooms | z
Air conditioning systems | z
Industrial production facilities z z
Refrigerated warehouses | z
Data processing service centres | z
Invisible security particularly appreciated in buildings with | z
cultural significance (churches, cathedrals, libraries, muse-
ums etc.) and with design oriented modern structures.
Rapid evacuation requiring early detection of the sources | z
of danger, which in an emergency allow rapid evacuation.
Risk of vandalism z z
Difficult access for maintenance e.g. areas of confidential- | z
ity, operating rooms, nuclear facilities, laboratories, high-
voltage facilities, penal institutions, false ceilings, false
floors, shafts, and other hard-to-access areas.
EMC-compatible z z
z Suitable | Depends on risk analysis
Non-ventilated and power-ventilated devices cabi- Rooms such as storage areas, high-rack storage, elevator
nets such as distribution cabinets, switch cabinets, shafts, museums, deep-freeze storage, floor voids, ceiling
telephone switching equipment, measuring and voids, ducts, etc.
control units etc.
Pipe system : room
Titanus ProSens and Titanus TopSens take continuous air samples from the area
monitored via a tube system with defined air sampling points. An integrated smoke
detector detects an existing smoke concentration. Different detector modules with
various sensitivity levels can be selected and set according to the type of application.
Air flow to the detection device is constantly monitored and there will be a fault sig-
detector module
nalisation in case of blockage or rupture of the tube system.
Titanus ProSens Titanus TopSens
0.30 0.30
10
Fire alarm 0.25 0.25 Fire alarm
9
0.20 8 0.20
7
6 Action alarm
0.15 0.15
5
0.10 4 0.10
i 3 Alert alarm
0.05 0.05
2
smoke level
1
(% obsc./m) 0.00 0.00
Example: Titanus ProSens in comparison with Titanus TopSens.
Both have detector modules with a fire alarm sensitivity of 0.25% obsc./m.
Titanus ProSens and Titanus TopSens are mounted on walls or cabinets. By revers-
ing the device the connection socket can be positioned upward or downwards. By
removing the device cover, full access is provided to the detector modules without
any influence on the air flow monitoring. Easy commissioning is given due to micro-
processor controlled calibration of the air flow sensor and the easy set up of the sen-
sitivity. A diagnostic device is provided for maintenance and servicing which enables
rapid fault location.