FILTERS AT SUPPLY SECTION

DX PACKAGE UNIT (HEAT PUMP TYPE) BED NO 1 ***


PANEL (50 MM THICK) WASHABLE ALUMINUM G2 (65%)
CLASS (EFFICIENCY)
REFERENCE PU-02 NOTES
PANEL (50 MM THICK)
TYPE HEAT PUMP
CLASS (EFFICIENCY) WASHABLE G4(90%)
SERVED AREA SHOWROOM - 02
DAMPERS TYPE MANUAL, OPPOSED BLADES
SUPPLY AIR L/s 7700
NUMBER OF DAMPERS 3
TOTAL RETURN AIR TO MIXING BOX L/s 6314
HEAT RECOVERY
EXH. AIR FROM MIXING BOX EXHAUST AIR SECTION L/s 1386
CONDENSING UNIT (HEAT PUMP)
RETURN AIR TO MIXING BOX FRESH AIR SECTION L/s 6314
L/s 1386 TOTAL COOLING / HEATING CAPACITY kW 174.2
FRESH AIR TO MIXING BOX FRESH AIR SECTION
TOTAL RETURN AIR TO COIL L/s 7700 SENSIBLE COOLING CAPACITY kW 132.2
INSTALLATION OUTDOOR
CONDENSER

CONDENSER DESIGN AIR ENTERING TEMP °C 35.0


SINGLE SKIN ZINC COATED
CONSTRUCTION GALVANIZED STEEL PANELS
CONDENSER MAX AIR ENTERING TEMP C° 45.0
"0.7 mm OUTER"
REFRIGERANT TYPE R410a

COMPRESSOR
COOLING / HEATING COIL
TOTAL COOLING / HEATING CAPACITY kW 174.2 COMPRESSOR TYPE HERMETIC SCROLL
SENSIBLE COOLING CAPACITY kW 132.2
TYPE OF EXPANSION VALVE THERMOSTATIC
TOTAL HEATING CAPACITY kW 80
COOLING MOOD (IN SUMMER) CONTROL PANEL
PROJECT :
ENTERING AIR DRY BULB TEMPERATURE TO COIL °C 23.7
ENTERING AIR WET BULB TEMPERATURE TO COIL °C 15.9
LEAVING AIR DRY BULB TEMPERATURE °C 13.1
‫يانير بيوات ماين يربكااا ديربتلاو‬
TOTAL ELECTRICAL POWER
LEAVING AIR WET BULB TEMPERATURE °C 12.1

HEATING MOOD (IN WINTER)


kW 104 Should be verified by manufacturer
‫نبيا يررايليب يرنركا‬
ENTERING AIR DRY BULB TEMPERATURE TO COIL °C 20.3

LEAVING AIR TEMPERATURE DB °C 25.4 ELECTRIC CHARACTERISTIC 380 V/ 3 Ø / 50 Hz


MAXIMUM FACE VELOCITY m/s 2.30
AUXILIARY ELECTRIC HEATER
TYPE ELECTRIC HEATING ELEMENT
CAPACITY kW 20 Capacity should be verified by manufacturer
STAGES MULTI-STAGE
SUPPLY AIR FAN **
CENTRIFUGAL, DOUBLE
FAN TYPE
WIDTH-DOUBLE INLET

WHEEL TYPE BACKWARD CURVED

FLOW TYPE CONSTANT


MANDATORY REQUIREMENTS AND ACCESSORIES
AIR FLOW L/s 7700
EXTERNAL STATIC PRESSURE Pa 350
TOTAL PRESSURE Pa BY SUPPLIER Supply, install, test and commission Packaged roof mounted air-conditioning unit, (HEAT PUMP TYPE) according
MINIMUM FAN EFFICIENCY % 60 to the following specifications :
MINIMUM DRIVING BELTS No. 2 Heavy gauge galv. Steel sheet, with electrostatic powder paint of epoxy coating finish.
MOTOR DATA Weather proof wit single skin unit casing with suitable thermal insulation
STARTER TYPE DIRECT ONLINE Hermetic sealed scroll compressors
NUMBER OF POLES 4
Environmentally and ozone friendly Refrigerant gas
RATED OUTPUT kW 7.5 Supplementary electric heater
MOTOR SPEED RPM 1450
Supply fan with external static pressure 1.8 inch H2O
VOLTAGE V 380
Aluminium Flat Filter
PHASE Ø 3
Mixing box with manual operated dampers
Hz 50
External overload protections for all compressors and circuit
FREQUENCY
CONSTANT
Evaporator coil and condenser coil made of copper tubes andbreaker for the unit.
SPEED CONTROLLER
Thermal expansion valve and Gas control aluminum fins with wire mesh.
Filter driers,Sight glass, Solenoid valves,
Anti vibration pads, Concrete bases (Kinetic and low pressure cutouts, Oil pressure switches.
Hightype)
Approved sound levels (45-50db) @ air terminals outlets.
Inside air temperature controlling according to ASHRAE Revision :
All electrical wiring and conduits required . standards No. Description Date
Equipment capacities as tabulated on the drawings.

TITLE :

‫يراويدر ديرنديمايب‬
Designed By : Checked By : Drawing By :

H. AJLOUNI A. ELUBOUS H. AJLOUNI

Date : Project Number : Discipline

09 - 2023 MECH.

Scale : 1/100 Drawing Number Sheet Size A3

ROYAL ENGINEERING DIRECTOR: E.MAMOUN HAMOURI