Number Outlet

Circuit Voltage VA per


Load Description of Switches Rating
No. Rating Circuit
Outlets (VA)
S1 S2 S3 AN BN
1 Lighting Outlet 21 1 220 20 420 1.91
2 Lighting Outlet 13 1 220 20 260 1.18
3 Lighting Outlet 6 1 1 1 220 80 480
4 Lighting Outlet 12 2 220 20 240 1.09
5 Lighting Outlet 17 2 220 20 340 1.55
6 Convenience Outlet 9 220 180 1620
7 Convenience Outlet 6 220 180 1080 4.91
8 Convenience Outlet 8 220 180 1440 6.55
9 ACU 3TR 1 220 2238 2238
10 ACU 3TR 1 220 2238 2238 19.10
11 ACU 3TR 1 220 2238 2238 19.10
12 Emergency Light 2 220 180 360
19.1
Total
12954 46.11 28.3727
For Service Conductor For Service Protection
𝐼_𝐿=46.11+(19.10 x 0. 25) = 50.885 A 𝐼_𝑀=46.11 +(19.10 x 1.5) = 74.76 A
Size of
Size of Homerun Circuit
Breakers

CN P F T Wire Conduit
1 60 15 2-3.5 sq.mm THHN Copper Wire 15mm Ø Conduit
1 60 15 2-3.5 sq.mm THHN Copper Wire 15mm Ø Conduit
2.18 1 60 15 2-3.5 sq.mm THHN Copper Wire 15mm Ø Conduit
1 60 15 2-3.5 sq.mm THHN Copper Wire 15mm Ø Conduit
1 60 15 2-3.5 sq.mm THHN Copper Wire 15mm Ø Conduit
7.36 1 60 20 2-5.5 sq.mm THHN Copper Wire 15mm Ø Conduit
1 60 20 2-5.5 sq.mm THHN Copper Wire 15mm Ø Conduit
1 60 20 2-5.5 sq.mm THHN Copper Wire 15mm Ø Conduit
19.10 1 60 30 2-5.5 sq.mm THHN Copper Wire 15mm Ø Conduit
1 60 30 2-5.5 sq.mm THHN Copper Wire 15mm Ø Conduit
1 60 30 2-5.5 sq.mm THHN Copper Wire 15mm Ø Conduit
1.64 1 60 15 2-3.5 sq.mm THHN Copper Wire 15mm Ø Conduit

30.282
THEREFORE USE:
0 x 1.5) = 74.76 A 80 AMPERE CIRCUIT BREAKER, 3 PHASE, 5 WIRE, 400V
3 - 22 sq.mm THHN Cu Wire
1 - 22 sq.mm THHN Cu Wire NEUTRAL,
1 - sq.mm THHN Cu Wire GROUND
@ 32mm Ø Conduit
of Homerun Circuit

Grounding
1-3.5 sq.mm THHN Copper Wire (Green)
1-3.5 sq.mm THHN Copper Wire (Green)
1-3.5 sq.mm THHN Copper Wire (Green)
1-3.5 sq.mm THHN Copper Wire (Green)
1-3.5 sq.mm THHN Copper Wire (Green)
1-3.5 sq.mm THHN Copper Wire (Green)
1-3.5 sq.mm THHN Copper Wire (Green)
1-3.5 sq.mm THHN Copper Wire (Green)
1-3.5 sq.mm THHN Copper Wire (Green)
1-3.5 sq.mm THHN Copper Wire (Green)
1-3.5 sq.mm THHN Copper Wire (Green)
1-3.5 sq.mm THHN Copper Wire (Green)

REAKER, 3 PHASE, 5 WIRE, 400V


u Wire
u Wire NEUTRAL,
Wire GROUND
PRE FUNCTIONAL TESTING
MONITORING SHEET
LOCATION: TAGOLOAN WAREHOUSE - CLUSTER 1

CONTINUITY INSULATION
PASS/FAIL REMARKS
L1-L2 L1-L3 L2-L3 L1-G L2-G L3-G L1-L2 L1-L3 L2-L3 L1-G L2-G L3-G N-G
FEEDERLINE
PB-C1 High Bay Lights
High Bay Lights
High Bay Lights
Emergency Light
PB-C2 High Bay Lights
High Bay Lights
High Bay Lights
Emergency Light
PB-C3 High Bay Lights
High Bay Lights
High Bay Lights
Emergency Light
PB-C4 High Bay Lights
High Bay Lights
High Bay Lights
Emergency Light
PB-C5 High Bay Lights
High Bay Lights
High Bay Lights
Emergency Light

Prepared by: Zach L. Nerves Approved by: Rinco Panonce


Electrical Engineer Project Manager

Checked by: Apomar Cristian Quilab


Electrical Head