Siemens 1008
Siemens 1008
Siemens 1008
Technical specification
Building Technologies
Fire Safety & Security Products
Data and design subject to change without notice. / Supply subject to availability.
We reserve all rights in this document and in the subject thereof. By acceptance of the document the recipient acknowledges these rights
and undertakes not to publish the document nor the subject thereof in full or in part, nor to make them available to any third party without our
prior express written authorization, nor to use it for any purpose other than for which it was delivered to him.
1 About this document ..............................................................................5
4 Installation .............................................................................................12
4.1 Assembly.................................................................................................12
4.2 Mounting .................................................................................................13
7 Commissioning .....................................................................................28
7.1 Procedure................................................................................................28
7.2 Testing peripheral devices ......................................................................29
3
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
8 Configuration.........................................................................................30
8.1 Programming user functions ...................................................................30
8.2 Programming steps .................................................................................32
8.3 Programmable functions .........................................................................34
8.3.1 Step 1, timer V1 ......................................................................................34
8.3.2 Step 2, timer V2 ......................................................................................34
8.3.3 Step 3, zone processing on alarm ..........................................................35
8.3.4 Step 4, LED activation mode...................................................................35
8.3.5 Step 5, activation mode of control lines ..................................................35
8.3.6 Step 6, measures against false alarms...................................................36
8.3.7 Step 7, control lines on alarm..................................................................36
8.3.8 Step 8, special zone parameters ............................................................36
8.3.9 Step 9 not used .......................................................................................36
8.3.10 Step 10, detector line short or break.......................................................36
8.3.11 Step 11, cross zoning..............................................................................37
8.3.12 Step 12, access code..............................................................................37
8.3.13 Step 13, special PMI parameters ............................................................37
8.3.14 Step 14 not used .....................................................................................38
8.3.15 Step 15, special parameters ...................................................................38
8.3.16 Step 16, programmable control input......................................................38
8.3.17 Step 22, indicating mode display ............................................................38
8.3.18 Step 23, switching mode manned/unmanned.........................................38
8.3.19 Step 24, display switching time ...............................................................39
8.3.20 Step 25, switching mode summer/winter time ........................................39
8.3.21 Step 26, switching time manned/unmanned ...........................................39
8.4 Log sheet for programmed user functions ..............................................40
8.5 Checksum ...............................................................................................41
9 Maintenance...........................................................................................42
9.1 General....................................................................................................42
9.2 Recommended system performance checks..........................................42
10 Trouble shooting...................................................................................44
10.1 Interpretation of fault LED flashing..........................................................44
4
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
About this document
Application area
The information in this document applies from the hardware / software version 6.1.
Target group
This documentation and the instructions therein are intended for the following
group(s) of persons who perform the tasks mentioned and have had the corre-
sponding training.
Before groups of persons begin work on the system they must have read and understood the related
documents, in particular Chapter 2 Safety regulations.
5
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
About this document
Reference documents
Number/Version Name
007995 Operating Manual FC10
008099 Product data sheet FC1008/12
008331 FD20 detector system
List of compatibility
Download
The most recently released technical documentation for customers can be found in
the Siemens Intranet.
Standard symbols
Result, note
Text in italic Quotation, exact match
see Cross reference
(…) Brackets contain supplementary text, suggestions etc.
Abbreviations
Abbreviation Explication
DU Divisional Unit
EOL End of line element
LED on, slow, fast LED on, flashes slowly, flashes fast
NC / NO (Contact) normally closed / normally open
PMI Person Machine Interface (operating panel)
RT Remote transmission
Document identification
Position Signification
Title page – System names
– Product type
– Purpose of the document
Last page bottom left – Document number
– Date of edition
Last page bottom right – Manual
– Register
Modification index
Version Date Brief description
A6V10265083_a_en_-- 03.2010 First edition
6
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Safety regulations
2 Safety regulations
This chapter describes the danger levels and the relevant safety regulations appli-
cable for the use of our products. Please read the work instructions as well as the
chapter About this document thoroughly before beginning any work.
The danger level – that is, the severity and probability of danger – is indicated by
the signal words listed below. Non-observance may lead to the consequences indi-
cated:
DANGER! Imminent danger!
May cause danger to life or serious bodily injury!
The symbols listed below indicate the nature and origin of the danger.
General danger
Electrical voltage
External voltage
DANGER
Disconnect the module from the power supply.
Refers to extremely important or critical decisions to be taken into account before continuing the work.
7
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Safety regulations
Country-specific standards
The products are developed and produced in compliance with the relevant interna-
tional and European safety standards. Should additional country-specific, local
safety standards or regulations concerning project planning, mounting, installation,
operation and disposal of the product apply in the place of operation, then these
standards or regulations must also be taken into account in addition to the safety
regulations mentioned in the product documentation.
Electrical installations
Work on electrical installations
Any work on electrical installations may only be carried out by qualified electri-
DANGER
cians or instructed persons working under the guidance and supervision of a
qualified electrician, in accordance with the electrotechnical regulations.
Control units must be disconnected from the power supply during commissioning
or maintenance work.
Terminals with an external voltage supply must be provided with a sign DAN-
GER - External voltage.
Mains leads to the control unit must be installed separately and provided with a
clearly marked fuse.
Earthing must be carried out in compliance with local safety regulations.
8
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
System description
3 System description
3.1 General
9
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
System description
EN54-2 Fulfilled
Basic functions x
Options and associated requirements Related FC10 configuration / Fulfilled
connection
Sounder line 1
Output to fire alarm device EN54-1 / C
7.8 Step 5 option 1 x*
( Fire alarm devices )
Step 4 option 7
Sounder line 3
7.9.1 Output to fire alarm routing equipment EN54-1 / E x*
Step 5 option 11
7.9.2 Alarm confirmation input from fire alarm routing equipment n/a -
Sounder line 1
7.10.1 Outputs to fire protection equipment EN54-1 / G x*
Step 5 option 13
Outputs to fire protection equipment
7.10.2 -
Output type B EN54-1 / G
7.10.3 Outputs to fire protection equipment -
7.10.4 Fault monitoring of fire protection equipment -
7.11.1 Delays to outputs V1/V2 timer for alarm organization Step 1 & 2 (timer V1 & V2) x
7.11.2 Switch on /off delays to outputs, V1/V2 timer for alarm organization Key 8 (Manned / unmanned) x
Dependencies on more than one alarm signal
7.12.1 Type A dependency from the same detector, or another in the same Step 6 / option 2 x
line
Dependencies on more than one alarm signal
7.12.2 Step 11 option 4 x
Type B dependency cross zoning
Dependencies on more than one alarm signal
7.12.3 n/a -
Type C dependency (option with requirement)
7.13 Alarm counter (option with requirement) FCA1002 display unit x
Zone Led
8.3 Fault signals from points (option with requirements) x
and LED 9
8.4 Total loss of the power supply (option with requirements) n/a -
Sounder line 6
8.9 Output to fault warning routing equipment according EN54-1 / J x
Step 5 option 14
10 Test condition (option with requirements) Push Key zone x x
Standardized input/output interface (option with requirements – see
11 n/a -
also Annex G)
Remarks:
* the panel provides in the standard 2 monitored control lines and with the FCA1003 control card 4 additional moni-
tored outputs. In step 5 we provide for output the options.
DC1192
EX-area
AC power input
115/230 VAC
10
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
System description
Emergency power
maximum nominal output current during
battery charging, I max. a 0.9A
Quiescent current
– 8 zones 145 mA
– 12 zones: 165 mA
– with additional control line extension card 84 mA
– with additional display module 7.5 mA
Alarm current per zone + 35 mA (without current of external alarm devices)
< 20.5 VDC
Battery low discharge cut off
Charging temperature compensated Yes
Cabinet
Assembly metal frame with plastic cover
Color metal frame grey RAL9006 / cover white RAL9003
Protection degree IP40
Dimension (W x H x D) 506 x 378 x 125 mm
Temperature range (operation) 0 … 50 °C
1) Line resistance ≤ 50 Ω if option 4 is selected in step 3 and option 8 is selected in step 15.
2) Use 5.6 V z-diode if option 4 is selected in step 3 and option 8 is selected in step 15.
3) Use 5.6 V z-diode if option 4 is selected in step 3 and option 8 is selected in step 15. In all other
cases, use 820 Ω resistor or standard call point with integrated alarm detection.
4) For details, see list of compatibility (008331)
5) The battery capacity calculation depends on the connected hardware devices, country and/or
customer required emergency lifetime.
11
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Installation
4 Installation
4.1 Assembly
Pos Components
1 Mains connection and circuit breaker (fuse), factory mounted.
230 VAC main connection from below (recomended)
2 Power supply (70 W)
3 Mainboard
4 Nock-outs for cable entries 20 mm; top 17, bottom 3
5 Display module (option)
6 Line extension card, FC1012 only
7 Control line extension card (optional) under Line extension card
8 Key switch Nordic (variant Nordic only)
9 Key switch set (option)
10 Patch work PCBA
11 Batteries
12 Battery holders
13 Relays Z3B171
12
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Installation
4.2 Mounting
Procedure
1. Remove front cover
2. Determine mounting location (not behind a door)
3. Mark position of mounting screws (use enclosed drilling template) and drill holes.
Installation accessories not included in cabinet:
– screws min. 4 x 50 mm
– plastic dowels
– c-shaped washers or lock washers
4. Mount chassis, if required with distance sleeves (1)
5. Break out cable entries (3) and mount cable glands (PG11) if required (2)
6. Insert inscription stripes (4)
Templates for inscription stripes are available as Word files at the hotline.
Protect the mounted unit with its shipping carton during construction phase by using the shipping
carton
13
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Function and design
CN14
PU18
CN5/6
CN7/8
PU9
PU11
CN3/4
CN1/2
1
3 PU10
1 3
F1 F2
PU15
PU14
PU13
PU12
ON ON
ON
PU7
PU8
ON
PU6
PU5
PU3
PU4
PU1
PU2
F4 CN26
PU20
8 1
CN9
PU26 CN11
PU16 CL23 CL24
PU19 CN10
PU25 PU17
14
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Function and design
Peripheral connections
5.1.1 Mainboard
Z-diode
5,6V
1N4007
_ _ _ _ _ _ _ _
+ + + + + + + +
DRIVER ALARM
_ _ FAULT ALARM _LIN1 _ LIN2 _ LIN3 _ LIN4 _
LIN5 _LIN6 _LIN7 _LIN8
+ + FAULT RT ALARM RT RT LIN1 LIN2 LIN3 LIN4 LIN5 LIN6 LIN7 LIN8 1 2 1/2 + + + + + + + +
F1 F2
CL22
OUT 24V
_
F4
+
Detector and control lines that are not used must be terminated
detection line with FC10xx-A /-C resistor 3.9 kΩ
detection line with FC10xx-B EOL FCE1003-B
control line EOL FCE1002
15
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Function and design
N
Mains 230 VAC
3.15 AT
If a detector head is removed from a detector line, the control unit signal a fault,
while the manual call point is still able to set off an alarm (support diode
bases BS5839Pt1)
BDZ1000-B
removed detector heads inserted detector heads Manual call point
+ +
Detector line _
_
Z-diode
Schottky diode monitoring jumper
in the detector head
Achieved with
line card FCA1007-B (factory equipped)
resistor EOL FCE1003-B (included in panel accessories) and Z-diode
special detector base (eg. DB1102A, part number 534851) equipped with Schot-
tky diode (1N5819) in parallel to the monitoring jumper inside detector head
16
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Function and design
+
Detector line EOL
_
Achieved with
option 4 selected on programming step 3 or
option 8 selected on programming step 15
Note: A z-diode in series with a resistor and a LED is not possible for call point de-
tection.
Z-diode 5,6V
or
ON
PU4
PU3
_ _ _ _
+ + + +
DRIVER
_
LIN9 _LIN10 _LIN11 _LIN12 ON
12 11 10 9 + + + +
PU2
PU1
1 2
17
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Function and design
Summery
The optional control line extension card features 4 monitored control outputs (con-
trol line 3 - 6). The following devices can be connected to the control outputs:
– Alarm devices like horns or flashlights
– Remote fire control installations
– RT devices
Functionality
The control outputs of control lines 3 – 6 have basically the same features as the
control outputs of control lines 1 and 2. For the control lines 3 - 6, attention should
be paid to the following:
– It is defined in programming step 5 when and how the control outputs are acti-
vated. In addition, each control output (control line 3 – 6) has a control
input (A – D). Input A is related with output 3 etc. An AND combination between
the setting in programming step 5 and the control input is enabled with a
Jumper, e.g. control output 3 shall only be activated in case of alarm 2 AND
driver output of zone 4 is active.
– Only control line 6 can be activated in case of a RT fault (see Step 5, activation
mode of control lines, option 14). If so, the Jumpers have to be set accordingly
(see table below).
– A LED is assigned to each control output. If the LED flashes, the corresponding
control output has either a line break or a short line.
Connection
– The board will be connected via the enclosed ribbon cable on the connector
CN10 to the main board.
– For power supply, a separate line has to run from the power supply card (termi-
nals on the right side of the card) to the control line extension card.
– If a control line is not used, it to has to be terminated with an EOL (FCE1002; in-
cluded in delivery).
The allocation of connection can be seen in the following board illustration.
For zone-specific
activation only
1N4007
control input for line 3
control input for line 6
control input for line 5
control input for line 4
A
input 24V supply
6
Ref. Control Setting / Function
line
PU1, Pos. top = if option 14 progr. step 5 is selected
PU2 6 Pos. bottom = if option 1-13 in progr. step 5 is selected
6 5 4 3 PU3 5
D C B A PU4 6 OFF = zone-specific activation (control input used)
PU5 4 ON = common activation (control input not used)
+ - + - + - + - - + PU6 3
top
PU6
CN1
PU5
DL3
DL4
DL1
18
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Function and design
FAULT RT ALARM RT
680 Ω
10 kΩ
(+ +)
12 V 1)
100 mA/T (+ +)
2)
(– –)
FAULT
RT
19
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Function and design
Programmable parameters
Zone type
via timer V1/V2 in mode manned ; for detectors
direct ; for manual call point, sprinkler alarms, etc.
internal ; for non-fire-events, e.g. technical alarm
5.2.2 Fault
The timer V1 is also valid for RT-Fault. If the reported Fault is acknowledged be-
fore V1 has expired then the contact RT-Fault will not be triggered.
Zone type ‘intern’ Zone type ‘via timer V1/V2’ Zone type ‘direct’ Processing ‘system fault’
V1 expired ? V1 expired ?
‘V1’ ‘V1’
acknowledged ? acknowledged ?
local FAULT
Start timer ‘V2’ remains until fault is
removed or reset
V2 expired ?
If all zones are set to zone type direct or internal then mode manned cannot be
activated.
Alarm 0: The activated mode for the monitored control lines are programmed in to step 5.
Only the monitored control lines will be aktivated, which are programmed to "Alarm 1" in step 5.
20
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Operation and indicator elements, mode of operation (PMI)
The system operating panel is also called Person Machine Interface - PMI.
Operating access
Level 1 Operating functions always possible
Level 2 Operating functions accessible via access code or key switch
The default access code is 4233
– automatic time-out after 3 min
set individual access code, preferably 6 digits
disable access code if a key switch is used
Level 3 For user programming only, with additional access code
Level 4 Used to upload the panel software with additional equipment. The panel
needs to be open by removing the four allen screws.
Inscription stripes
Label the individual zone texts in the Word template (available via hotline).
Each zone LED must have a clear individual zone text, which indicates the geo-
graphical location of the corresponding detectors and / or manual call points.
Inserting inscription stripes
21
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Operation and indicator elements, mode of operation (PMI)
6.1.2 Indicators
LED LED
1 7
2 8
3 9
4 10
5 11
12
13
6
14
15
1 2 3 4 17
22
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Operation and indicator elements, mode of operation (PMI)
1 12
Keys 2 8
3 Keys 9
10
4 5 6 7
1 2 3 4 11 9999
Cancel delay Level 1 to cancel alarm delay while timers V1/V2 are running in
status Alarm
– sets timers V1/V2 to zero
23
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Operation and indicator elements, mode of operation (PMI)
Zone key
2
Possible operating states zone LED zone red LED zone yellow
Alarm unacknowledged fast --
1st Alarm acknowledged slow --
Sub sequent alarm acknowledged (Alarm active) on --
Fault line break or line short 2) -- fast
Zone disabled -- 1) on
Zone in mode detector Test -- slow
Zone in mode detector Test with temporary alarm on slow
activation (≤10s)
1) state disabled does not apply for line short alarms (option 2 step 10) if option 4 step 15 is pro-
grammed
2) Fire detection might be affected when a detection line fault condition appears. The fault shall be
repaired within a short time.
24
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Operation and indicator elements, mode of operation (PMI)
Optional display module that can be added on request in order to provide the func-
tions listed below.
Note:
The functions alarm counter, clock and event memory can be individually disabled
if not required (see Step 22, indicating mode display)
Display mode
Battery operation and locked access . flashing dot (power save mode)
Counted RT alarms 0257 --
Counted zone alarms 0 . 1. 3 . 4 flashing dots
Date and time (h/min) 14.38 flashing dot except for the year indication
Time not set or not correct 88.88 all digits flash
The type of event is always shown by the corresponding indicator at the PMI ac-
cording to table below.
Indicator PMI Type of event Remark
Red zone LED Alarm corresponding zone includes also simulated alarms, but no test alarms
LED 5 RT-Alarm always registered as separate event
LED 7 System part disabled
LED 9 Fault includes all types of fault events also simulated zone faults
LED 16 Evacuation
25
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Operation and indicator elements, mode of operation (PMI)
It is only possible to go to the next option if the current entry is completed and ac-
cepted; otherwise, the buzzer will sound.
26
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Operation and indicator elements, mode of operation (PMI)
Requirement
Queries about service information are only possible if there is no alarm and operat-
ing access on level 2 is given.
Procedure
1. Hold key acknowledge then, enter the password for the corresponding service
information by using the numeric keys.
2. The requested query can be selected with the corresponding numeric keys.
3. To end the query, press key acknowledge. The request will be automatically
stopped if an alarm occurs or if there is no further entry for more than a minute.
27
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Commissioning
7 Commissioning
7.1 Procedure
Commissioning
check the correct functioning of the system
remove possible faults
set the individual user functions as required and fill out log sheet
initiate lamp test and check all LED
test each operating key for correct functioning
test all detectors, manual call points, horn control lines and remote transmission
facility, see chapter Testing peripheral devices
28
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Commissioning
Procedure
29
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Configuration
8 Configuration
8.1 Programming user functions
In order to fulfill the local requirements, the programmable user functions may be
adjusted by the single programming steps.
1 2 3 4 5 6
1 9
1
2 10
3 11
2
4 12
5 13
3
6 14
7 15
4
8 16
1 2 3 4 9999
7 8
30
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Configuration
Set user functions to factory default settings
The user functions of all programming steps can be set to factory default values
with one operation.
1. Disconnect mains and battery
2. Press and hold numeric keys (7) 1, 2, 3, 4 simultaneously followed by reconnect-
ing mains
– LED block (1) starts flashing
3. Release numeric keys (7)
4. Press numeric keys (7) 1, 2, 3, 4 simultaneously again
– LED block (1) stops flashing and double beep of buzzer occurs
– System is now set to default
5. Reconnect battery
31
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Configuration
1 9
1
2 10
3 11
2
4 12
5 13
3
6 14
7 15
4
8 16
1 2 3 4 9999
7 8
The selected programming steps are either indicated
by the LED block (4), or
– for programming steps 1 to 8 the corresponding LED is lit,
– for programming steps 9 to 16 the corresponding LED is flashing
by the optional display module (8)
The setting of an option can be selected with the zone keys (6) and is indicated
with the corresponding red and yellow zone LED (5).
32
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Configuration
Basic programming steps
LED STEP Define function
on 1 Timer V1
2 Timer V2
3 Processing of zone Alarm (zone type)
4 LED activation mode
LED Remote transmission
LED Alarm
LED System part disabled on mode manned
No Resound or not on new alarm
5 Activation mode of control lines 1 - 6
6 Measures against false alarms
alarm verification
zone disabled in mode manned
7 Control lines on Alarm
8 Special zone parameters
behavior on immediate Alarm after Reset
function of zone control outputs
flashing 9 Not used
10 Detector line evaluation on line short or line break
11 Cross-zoning
12 Access code (password)
operating access
13 Special PMI parameters
reminder beep on fault and system part disabled
Fault messages to be Reset
14 Not used
15 Special parameters
external Acknowledge and Reset
zones with special disabling procedure
Remote transmission on operating access
all zones with option 1 in step 3 react like option 4
16 Programmable control input
Do not assign functions cross zoning (step 11) and alarm verification (step 6) simultaneously to the
same zone!
33
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Configuration
1 2 3 4 5 6
1 9
1
2 10
3 11
2
4 12
5 13
3
6 14
7 15
4
8 16
1 2 3 4 9999
7 8
Procedure
1. Select the desired step with key (2) or (3)
2. Press the zone keys (6) as many times until the desired option is indicated with
the corresponding zone LED (5) according to the following tables.
34
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Configuration
1) If all zones are set to direct or internal, the function manned/unmanned is disabled.
35
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Configuration
36
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Configuration
Note: Access is permanently provided if jumper PU16 is set on mainboard (override of access
code)
37
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Configuration
38
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Configuration
39
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Configuration
40
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Configuration
Display programming steps
Programming steps and functions Set options (parameter) Individual settings of a
Selectable pre-settings selected pre-setting
Factory 1 2 3 4 5 6 7 8
8.5 Checksum
Checksum to fill in when programming is completed
41
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Maintenance
9 Maintenance
9.1 General
The fire detection installation requires only little maintenance work. It has a high
degree of self monitoring, such as
detectors monitored on presence, lines on wire break and short circuit
call points monitored on broken glass, lines on wire break and short circuit
control lines monitored on wire break and short circuit
battery monitored on presence and capacity
permanent system checking by watchdog function
programmed user functions are stored in FLASH-memory
Alarm organization
Performance checks Interval in years
1 2 5
Check the functioning of delay times V1 and V2 X
Verify switchover mode manned to unmanned and vice versa manually X
Activate automatic detectors while system is set to mode unmanned X
Activate automatic detectors while system is set to mode manned X
Activate manual call points X
Check activation of remote transmission equipment X
Alarm horn
Performance checks Interval in years
1 2 5
Activate alarm horn test and check all acoustic alarm devices X
Detector network
Performance checks Interval in years
1 2 5
Activate one detector within each line and verify zone assignment and X
parameters
Check all detectors and call points visually X
Activate all detectors and manual call points X
Check each detection line whether a short circuit or open line activates a X
fault
Overhaul all automatic detectors at the factory X
– at latest after 5 years in clean environment, otherwise earlier
Refer also to the corresponding detector manuals
42
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Maintenance
Operating panel
Performance checks Interval in years
1 2 5
Clean front panel with mild soap X
- do not use aggressive or abrasive solvents
Activate lamp test X
Check correctness and readability of the inscription stripes X
Check key-click of each key X
Check access facility X
43
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Trouble shooting
10 Trouble shooting
10.1 Interpretation of fault LED flashing
44
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Components and spare parts
11.2 Accessories
Type Part number Description Remarks
FCA1003 S54380-C6-A1 control card
FCA1002 A6E60500021 display unit
Z3B171 4843830001 fire control relay 1 contact 250VDC/10A
FCA1007 A6E60500026 kit key switch incl. mounting instruc-
tion
FA2004-A1 A5Q00019354 FA2004-A1 battery 12V, 12 Ah, VDS
FA2005-A1 A5Q00019677 FA2005-A1 battery 12V, 17 Ah, VDS
Power supply
Type Part number Description Remarks
FP2001-A1 A5Q00005568-R Power supply (70 W)
FCA1014 A6E60500069 Battery holder
Electronic cards
Type Part number Description Remarks
FCM1008 S54380-C1-A10 Mainboard 8 zone
FCA1001 A6E60500020 Line extension card 4 zones
FCA1007-B A6E60500027 Line card GB
EOL
Type Part number Description Remarks
FCE1001 A6E60500031 EOL resistor 3k9 (dedector line) (set of 10 pieces)
FCE1003-B A6E60500033 EOL element GB
FCE1002 A6E60500032 EOL element control line
Cabinet cover
Type Part number Description Remarks
FCH1008 A6E60500038 Cover with PMI 8 zone
FCH1012 A6E60500043 Cover with PMI 12 zone
FCA1013 A6E60500068 Universal accessory bag
45
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Disposal and environmental protection
12.2 Disposal
Prior to the disposal the system must be put out of service by the Technical
Customer Service of Siemens Building Technologies AG. The system must be
DANGER
disconnected from the power supply – otherwise serious bodily injury or even
danger to life could result!
Function units
The following modules should be particularly taken into consideration:
Batteries
Electronic modules (control units, all detectors)
Switching cabinets
Disposal regulations
With regard to the disposal of the Siemens fire detection system, local and regional
regulations and guidelines must be taken into account.
46
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Disposal and environmental protection
47
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
Siemens Switzerland Ltd © Siemens Switzerland Ltd 2004-2010
Industry Sector Data and design subject to change without notice.
Building Technologies Division
International Headquarters
Gubelstrasse 22
6301 Zug, Switzerland
Tel. +41 41 - 724 24 24
www.siemens.com/buildingtechnologies