6.2 DX Selection Sheet

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

PROJECT NAME: Proposed 2B+G+29+Mech.

Floor, Hotel Building, Business Bay, Dubai


CLIENT: M/s Kingston Holding International Limited, Dubai, UAE
CONSULTANT: M/s MAK
CONTRACTOR M/s Gulf Asia Contracting Co.

SPECIFIED OFFERED
IND. AIR OFF
TCC SCC Air Flow EAT LAT PI KW ESP TCC SCC Air Flow EAT PI T1 PI T3 POWER SUPPLY PIPE SIZE Max Tot/Vrt ESP IDU DIMENSIONS (mm) ODU DIMENSIONS (mm)
COIL EER T1 EER T3
UNITS REF. LOCATION UNIT TYPE QTY IDU MODEL ODU MODEL NCC (TR) QTY
(BTUH/W) (BTUH/W)
KW KW LPS DBT(°C) WBT(°C) DBT(°C) Cal. DBT IU OD Pa KW KW LPS DBT(°C) WBT(°C) DBT(°C) kW kW (V / PH / HZ) Disc. (Liquid) Suction (Gas) m Pa Height Width Depth Height Width Depth

DX-FCU-LMR-01 LIFT MACHINE RM DUCTED 5.80 5.70 380.00 25.5 16.9 12.8 12.00 0.3 3 50.0 1 ARGG24CLTA-U AOGG24CBTA-U 2.00 5.82 5.57 472 25.0 18.0 14.98 1.99 2.20 12.06 9.27 220-240/1/50 1/4" 1/2" 30/25 35 300 1,000 700 632 799 290 1
DX-FCU-B1-02 SERVER RM DUCTED 10.00 9.80 880.00 22.9 17.4 13.9 13.20 0.6 5 50.0 1 ARGG60CMTA-U AOGG60CRTA-U 5.00 12.55 11.70 944 23.0 16.0 12.48 5.11 5.68 11.74 8.97 380-415V/3/50 3/8" 5/8" 75/30 70 360 1400 850 1418 970 370 1
DX-FCU-B01-02 MAIN TELECOM ROOM DUCTED 10.10 10.10 903.00 22.0 15.8 12.8 12.20 0.6 5.5 50.0 1 ARGG60CMTA-U AOGG60CRTA-U 5.00 11.49 10.83 944 21.0 15.0 11.26 5.11 5.68 11.74 8.97 380-415V/3/50 3/8" 5/8" 75/30 70 360 1400 850 1418 970 370 1
TOTAL 25.90 25.60 2163.00 1.50 13.50 3 12.0 29.86 28.10 2360 12.2 13.6 3
Note:
For purposes of continuous improvement, all specifications and design data are subject to change without prior notice.
Refrigerant- R32.
Selection done without considering the outdoor positioning.
Selection is done at High speed
The end user has ability to change up to 4 Speeds (Quiet, Low, Medium, High)
Selection is done based on 100% Indoor Design temperature with no consideration of treated or untreated fresh air
OffCoil Calculation is based on Indoor Design temperature

LEGEND:
TCC: Total Cooling Capacity in KW
SCC: Sensible Cooling Capacity in KW
NCC: Nominal Cooling Capacity in TR, at T1 rating conditions
Air Flow: Air Flow Rate in LPS
EAT: Entering Air Temperature in in °C, expressed in Dry Bulb (DB) and corresponding Wet Bulb (WB) Temperatures
PI: Electrical Power Input (Indoor Unit + Outdoor Unit) in Kw
EER: Energy Efficiency Ratio expressed in Btu/Wh at T1 and T3 Rating Conditions
Cooling (T1): Indoor Temperature of 27˚CDB/19˚CWB, and Outdoor Temperature of 35˚CDB
Cooling (T3): Indoor Temperature of 29˚CDB/19˚CWB, and Outdoor Temperature of 46˚CDB
Max Tot/Vrt: Manufacturer specified interconnecting Refrigerant Piping limitations in 'm', expressed for Total Pipe length and Vertical Pipe Length respectively