ANSUL ®

Detection and Control Components

AutoPulse FCM-1 Control Module

Features Upon code command from the unit, the FCM-1 will discon-
• Built-in type identification automatically identifies these nect the supervision and connect the external power supply
devices to the control unit in the proper polarity across the load device. The disconnec-
tion of the supervision provides a positive indication to the
• Internal circuitry and relay powered directly by two-wire panel that the control relay actually turned ON. The external
SLC loop; requires power for notification or releasing appli- power supply is always relay isolated from the communica-
ances tion loop so that a trouble condition on the external power
• Integral LED blinks green each time a communication is supply will never interfere with the rest of the system.
received from the control unit and turns on in steady red Rotary switches set a unique address for each module. The
when activated address may be set before or after mounting. The built-in
• LED blink may be deselected globally (affects all devices) TYPE CODE (not settable) will identify the module to the
control panel, so as to differentiate between a module and a
• High noise immunity (EMF/RFI)
sensor address.
• May be used to control a releasing appliance circuit (RAC)
The FCM-1 is used to switch 24 VDC audible/visual or
• Wide viewing angle of LED releasing appliance power.
• SEMS screws with clamping plates for wiring ease
Technical Information
• Direct-dial entry of address (01-159)*
Normal Operating Voltage: . . . . . . . . . . . . . . . . 15 to 32 VDC
• Audible/visual applications may be wired for Class B or A Maximum Current Draw:. . . . . . . . . . . . . . . . 5.1 mA (LED on)
(Style Y or Z)
Average Operating Current:. . . . . . . . . 390 µA (LED flashing)
• Face plate is made of off-white Noryl® External Supply Voltage . . . . . . . . max 80 volts (RMS or DC)
• Configured for a single Class B (Style Y) or Class A (Style between T3 and T4:
Z) Notification Appliance Circuit Drain on External . . . . . 2 µA max. (using internal EOL relay)
• FlashScan® communication protocol Supply:
EOL Resistance:. . . . . . . . . . . . . . . . . . . . . . . . . . . 47 K ohms
Applications Temperature Range: . . . . . . . 32 °F to 120 °F ( 0 °C to 49 °C)
The FCM-1 Addressable Control Module provides the Humidity Range: . . . . . . . . . . . . 10% to 93% non-condensing
AUTOPULSE IQ-301, IQ-396X, or IQ-636X control unit a cir-
cuit for Notification Appliances (horns, strobes, speakers, NAC RATINGS
etc.) or compatible releasing appliances. Addressability
allows the FCM-1 to be activated, either manually or through Load Maximum Current
panel programming, on a select (zone or area of coverage) Description Application Voltage Rating
basis. Resistive Non-Coded 30 VDC 3.0 A
FlashScan (U.S. Patent 5,539,389) is a new communication Resistive Coded 30 VDC 2.0 A
protocol that greatly enhances the speed of communication Resistive Non-Coded 110 VDC 0.9 A
between analog intelligent devices. Intelligent devices com- Resistive Non-Coded 125 VAC 0.9 A
municate in a grouped fashion. If one of the devices within the
group has new information, the panel CPU stops the group Inductive (L/R = 5 ms) Coded 30 VDC 0.5 A
poll and concentrates on single points. The net effect is Inductive (L/R = 2 ms) Coded 30 VDC 1.0 A
response speed greater than five times that of other designs. Inductive (PF = 0.35 ) Non-Coded 125 VAC 0.5 A
Description
Each FCM-1 Control Module uses one of 159* possible mod-
ule addresses on a SLC loop. It responds to regular polls
from the control unit and reports its type and status, including
the open/normal/short status of its Notification Appliance
Circuit (NAC) or Releasing Appliance Circuit (RAC). The
LED blinks with each poll received. On command, it activates
its internal relay. The FCM-1 supervises Class B (Style Y) or
Class A (Style Z) notification or control circuits. The FCM-1
can be used to replace the CMX-2 module, Part No. 417479,
in existing systems.
* 01-99 with AUTOPULSE IQ-301 and IQ-396X 2-1-06
3-9
FCM-1 CONTROL MODULE FCM-1 MODULE

CB500

007271

Listings and Approvals*


UL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . S3705
004749 ULC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CS669
Factory Mutual (FM) . . . . . . . . . . . . . . . . . . . . . . . . . Approved
NOTE: The CB500 barrier is required by U.L. for separating California State Fire Marshal (CSFM). . . . . . . 7300-0028:202
power-limited and non-power limited wiring in the same junc- MEA (NYC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 457-99-E
tion box.
Maryland State Fire Marshal. . . . . . . . . . . . . . . Permit # 2020
* Listings and Approvals are under NOTIFIER.

Ordering Information
Shipping Weight
Part No. Description lb. (kg)
428101 FCM-1 Intelligent 1 (0.45)
Control Module
FlashScan is a trademark of Honeywell International.
Noryl is a registered trademark of GE Plastics, a subsidiary of General Electric Company.

TYPICAL CONNECTION OF A 24 VDC RELEASING DEVICE TO THE FCM-1 MODULE


SLL

COMPATIBLE UL-LISTED 24 VDC


RELEASING DEVICE

NON-RESETTABLE
24 VDC POWER

BROWN RED
N.C.
REL-47K (USE WITH SUPERVISION
TYPE CODE REL CKT RELAY CONTACT
ULC, OR SEE CIRCUIT PART OF EOL-R
REQUIREMENT 3)
POWER SUPERVISION
FCM-1 RELAY (EOLR-1)
007272

ANSUL and AUTOPULSE are trademarks of Ansul Incorporated or its affiliates.

TYCO SAFETY PRODUCTS, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-200145-1 ©2006 Ansul Incorporated