Design Calculation Sheet-VD3-Extension
Design Calculation Sheet-VD3-Extension
Dunamale Gauging station covers a major part of the road profile. Therefore use IDF
relationship for Dunamale calculations.
I = 3269(10 + 23.15511)-0.7609 = 227.7mm/hr
In terms of T;
T= Qxn ^0.375
Ku x SX1.67 x SL0.5
Where:
Q = Flow, m3/s
KU = 0.376
n = Manning’s coefficient (Table 4-3 of FHWA-NH1-10-009)
Reference Description Output
Generally, the value of “n” to be adopted will be 0.013 for smooth asphalt pavement
unless the longitudinal slope is less than 0.3% where the value will be increased
to 0.015.
T = Width of flow (spread), m
SX = Cross slope, m/m
SL = Longitudinal slope, m/m
Note 1: Curve widening width will added to the allowable ponded width if curve
widening available.
Note 2:When attempting to use the above formula for calculating spread widths at
sag or crest locations, the longitudinal grade tends to zero, and therefore the
Guide to Road
Design Part
spread width tends to infinity. Increasing spread widths are in turn met with a
5A: Drainage corresponding decrease in captured flows, theoretically approaching zero, as the
– Road longitudinal grade falls below 0.1%. In reality the presence of an inlet on an
Surface, otherwise flat section of road will induce flow. It is recommended that a minimum
Networks, longitudinal grade of 0.1% be used for all capture calculations.
Basins and
Subsurface
Section 5.5.1
Page 74
Sample Calculation for inlet at 22+693.673 RHS Shoulder
The depth of flow at the curb can be calculated by the following formula;
d = T SX Equation 4-3 in FHWA-NH1-10-009
Where,
d = Depth of flow at the curb, m
Where,
S’W = cross slope of gutter measured from cross slope of pavement, m/m
= a / [W] for W in m
a = Gutter depression, mm
W = Width of depressed section of the gutter, m
E0 = Ratio of flow in a chosen width of gutter to total gutter flow (Qw /Q)
QW = Flow rate in the depressed section of the gutter, m3/s
Q = Gutter flow rate, m3/s
The ratio of flow (E0) can be calculated based on equation 4-4 in FHWA-NH1-10-009
E0 = 1 / 1 + Sw / SX
1+ Sw / SX 2.67
-1
T/W - 1
Considered to adopt a curb inlet length (LT) equal to 1.0m and the gutter depression (a)
of 75mm.
E0 = (1/(1+(11/((1+11/(4.948-1))^2.67-1))))
= 0.755
Se = 0.025+0.25x0.755
Reference Description Output
0.214
LT,Req = 0.817*0.0213^0.42*0.0149^0.3*(1/(0.013*0.214))^0.6
Qi = 0.0073 m3/s
Where,
Qp = Discharge into pipe, m3/s
C = Constant, =0.6
A = Area of inlet outlet pipe, m2
g = Gravity, = 9.81m2/s
H = Head above pipe, m - taken as 0.075m
2.7 Aquaplanning
For checking aquaplaning considered following the Road Research Laboratory Report
No. LR 236 (1968) for the calculation of surface water depth.
d = 0.046 x (Lf I)0.5
Sf0.2
Where,
d = depth of flow at the end of the flow path, mm
I = Rainfall intensity, mm/hr
Sf = Flow path slope Sf = (SL2 + SX2)0.5
Lf = Length of flow path, m Lf = W (Sf /Sx)
Where,
Lf = Length of flow path, m
W = Width of pavement contributing to the flow, m
Sf = Flow path slope
SX = Cross fall of the pavement
Lf = (30-0.45*2)*(0.029/0.025)
= 33.861 m
01. An inlet length of 1m not enough for the capture 100% flow from the gutter
although flow width T is much lower than the allowable flow width in some inlets.
Therefore by-pass flow considered in next inlet for the calculation.
02. Water film thickness for the following segment slightly above the permissible 5mm
limit from Ch.22+730.465 to Ch.22+793.458 (Both sides).
However, according to the approved AIP, the maximum depth of flow for the main
viaduct is 5mm, with flexibility for up to 6.5mm.
As a result, the aquaplanning requirements for this part can be considered met.