Characteristics of Current transformers

the functional units


for SM6-24

Synthesis table by unit


Units
QMC CVM DM1-A DM1-D DM1-W DM2 GBC-A DMVL-A DMV-A IMC DM1-A DM1-W GBC-A DMV-A
DMVL-D GBC-B DMV-D DM1-D DM1-Z GBC-B DMV-D
DM1M
630 A 1250 A
ARJP1
ARM3
ARJP2

TC ARJP3
CLP2
TLP130
ARM4 (*) (*)
(*) Please, consult us.
PE60539

Transformer ARJP1/N2F
• Characteristics according to IEC standard 61869-2
• Single primary winding
• Double secondary winding for measurement and protection

Short-time withstand current Ith (kA)


I1n (A) 10 20 30 50 75 100 150 200
Ith (kA) 1.2 2.4 3.6 6 10 10 10 10
ARJP1 t (s) 1
Measurement 5A 15 VA - class 0.5
and protection 5A 2.5 VA - 5P20

Transformer ARJP1/N2F
PE60539

• Characteristics according to IEC standard 61869-2


• Single primary winding
• Double secondary winding for measurement and protection

Short-time withstand current Ith (kA)


I1n (A) 50 100 150 200
Ith (kA) 6 10
t (s) 1
ARJP1 Measurement 5A 15 VA - class 0.5
and protection 5A 2.5 VA - 5P20
Note: please consult us for other characteristics.

74 | SM6 Catalog schneider-electric.com


Characteristics of Current transformers
the functional units
for SM6-24
PE60536

Transformer ARM3/N2F
• Characteristics according to IEC standard 61869-2
• Double primary winding
• Single secondary winding for measurement and protection

Short-time withstand current Ith (kA)


I1n (A) 10/20 20/40 50/100 100/200 200/400 300/600
ARM3 Ith (kA) 5 12.5 12.5/21* 12.5/25* 12.5/25* 25
t (s) 1 0.8 1
Measurement and 5 A 7.5 VA - class 0.5
protection 1A 1 VA - 10P30
5A 5 VA - 5P10 5 VA - 5P15
* For 5 A protection

• Characteristics according to IEC standard 61869-2
• Double primary winding
• Double secondary winding for measurement and protection

Short-time withstand current Ith (kA)


I1n (A) 50/100 100/200 200/400 300/600
Ith (kA) 14.5 25 25 25
t (s) 1
Measurement 5A 30 VA - class 0.5
and protection 5A 5 VA - 5P15 7.5 VA - 5P15
5A 7.5 VA - 5P10 15 VA - 5P10

Transformer ARM4
PE60535

• Characteristics according to IEC standard 61869-2


• Single or double primary winding
• Up to 3 secondary windings (for measure and/or for protection)
• Rated highest voltage 7,2 - 12 - 17,5 - 24kV
• Rated primary current up to 630A (for SM6 cubicles)
ARM4 • Secondary currents 5A or 1A
• Version with one secondary winding: ARM4/N1F
• Version with two secondary windings: ARM4/N2F
• Version with three secondary windings: ARM4/N3F (*)
(*) Please, consult us.

Transformer ARJP2/N2F
PE60538

• Characteristics according to IEC standard 61869-2


• Single primary winding
• Double secondary winding for measurement and protection.

Short-time withstand current Ith (kA)


I1n (A) 50 100 200 400 600
Ith (kA) 25
ARJP2 t (s) 1
Measurement 5A 10 VA 15 VA 15 VA 15 VA 20 VA
and protection class 0.5 class 0.5 class 0.5 class 0.5 class 0.5
5A 2.5 VA 2.5 VA 5 VA 5 VA 7.5 VA
5P20 5P20 5P20 5P20 5P20

(*) Consult us

schneider-electric.com SM6 Catalog | 75


Characteristics of Current transformers
the functional units
for SM6-24

Transformer ARJP3/N2F
PE60537

• Characteristics according to IEC standard 61869-2


• Single primary winding
• Double secondary winding for measurement and protection.

Short-time withstand current Ith (kA)


I1n (A) 1000 1250

ARJP3 Ith (kA) 25


t (s) 1
Measurement and protection 1A 30 VA - class 0.5
1A 10 VA - 5P20
Measurement and protection 5A 30 VA - class 0.5
5A 10 VA - 5P20

Low Power Current Transformer (LPCT) CLP2


PE55661

• Characteristics according to IEC standard 60044-8


• Large primary current range
• Direct output voltage for measurement and protection
• RJ45-8 pts secondary connector
• Insulation level 24 kV.
Minimum rated primary current 5A
Rated nominal primary current 100 A
Rated extended primary current 1250 A
Rated nominal secondary output 22.5 mV
Accuracy class for measurement 0.5
Accuracy class for protection 5P
Accuracy limit factor 400
Rated short time thermal current 40 kA 1 s
Highest voltage (Um) 24 kV
Rated power-frequency withstand 50 kV

Low Power Current Transformer (LPCT) TLP130


PE57162

• Characteristics according to IEC standard 60044-8


• Large primary current range
• Direct output voltage for measurement and protection
• RJ45-8 pts secondary connector
• Insulation level 0.72 kV
• Internal diameter 130 mm.
Minimum rated primary current 5A
LPCT
Rated nominal primary current 100 A
Rated extended primary current 1250 A
Rated nominal secondary output 22.5 mV
Accuracy class for measurement 0.5
Accuracy class for protection 5P
Accuracy limit factor 250
Rated short time thermal current 25 kA 1 s
Highest voltage (Um) 0.72 kV
Rated power-frequency withstand 3 kV

76 | SM6 Catalog schneider-electric.com


Characteristics of Current transformers
the functional units
for SM6-36

Transformer ARM6T/N1 or N2
PE57222

For DM1-A, DM1-D, SM6-36, DM2, IMC, GBC-A, and GBC-B units
• Characteristics according to IEC standard 61869-2
• Double primary winding
• Double secondary winding for measurement and protection.

Short-time withstand current Ith (kA)

I1n (A) 50-100 75-150 100-200 150-300 200-400 300/600 1000/1250


Ith (kA) 16 - 20 25
Current transformer ARM6T t (s) 1 1
Measurement 5A 7.5 VA - 15 VA - class 0.5 30 VA -
and protection class 0.5
5A 2.5 VA - 5 VA - 5P20 10 VA -
5P20

Transformer ARM9T
PE58391

For DM1-A, DM1-D, and DM2 units

• Characteristics according to IEC standard 61869-2


• Double primary winding
• Double secondary winding for measurement and protection.

Short-time withstand current Ith (kA)

I1n (A) 1000/1250


Current transformer ARM9T
Ith (kA) 40
t (s) 1
Measurement 5A 30 VA - class 0.5 - Fs < 10
and protection 5A 10 VA - 5P20

Transformer TLP 130, TLP 190


PE57162

Low Power Current Transformer (LPCT) for DM1-A units, SM6-36


• Characteristics according to IEC standard 60044-8
• Large primary current range
• Direct output voltage for measurement and protection
• RJ45-8 pts secondary connector
• Insulation level 0.72 kV
• Internal diameter 130 or 190 mm
LPCT
• In SM6-36, TLP 130 can be used for 630 A, TLP 190 can be used up to 1250 A.
TLP 130 TLP 190
Minimum rated primary current 5A 5A
Rated extended primary current 1250 A 2500 A
Secondary output 22.5 mV - 100 A 22.5 mV - 100 A
Accuracy class for measurement 0.5 0.5
Accuracy class for protection 5P 5P
Accuracy limit factor 250 400
Rated short time thermal current 25 kA 1 s 40 kA 1 s
Highest voltage (Um) 0.72 kV 0.72 kV
Rated power-frequency withstand 3 kV 3 kV

schneider-electric.com SM6 Catalog | 77