SquareD NF2000G3 InstallInstructions
SquareD NF2000G3 InstallInstructions
SquareD NF2000G3 InstallInstructions
04/2008
LaVergne, TN, USA
POWERLINK® G3 Controller
NF2000G3 and NF3000G3 for use with
POWERLINK G3 Systems
Class 1210
This is the safety alert symbol. It is used to alert you to potential personal
injury hazards. Obey all safety messages that follow this symbol to avoid
possible injury or death.
DANGER
DANGER indicates an immediately hazardous situation which, if not
avoided, will result in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided,
can result in death or serious injury.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not
avoided, can result in minor or moderate injury.
CAUTION
CAUTION, used without the safety alert symbol, indicates a potentially
hazardous situation which, if not avoided, can result in property damage.
Class A FCC Statement This equipment has been tested and found to comply with the limits for a
Class A digital device, pursuant to part 15 of the FCC Rules. These limits
are designated to provide reasonable protection against harmful
interference when the equipment is operated in a commercial environment.
This equipment generates, uses, and can radiate radio frequency energy
and, if not installed and used in accordance with the instruction manual,
may cause harmful interference to radio communications. Operation of this
equipment in a residential area is likely to cause harmful interference, in
which case the user will be required to correct the interference at his own
expense.
U.S. Patent Statement The products described herein are protected under one or more of the
following U.S. Patents: 4,901,219; 4,964,058; 5,028,853; 4,940,903;
4,623,859; 4,965,694; D317,906; 5,083,103; 5,180,051; 5,184,278;
5,231,565; 5,233,511; 5,249,115; 5,253,159; 5,315,499; 5,323,307;
5,455,760; 5,532,660; 5,892,449; 5,909,180; 6,055,144; 6,612,873; and
6,813,525. Additional issued and pending patents may apply.
63249-401-205/A5 POWERLINK® G3 Controller
03/2008 Table of Contents
TABLE OF CONTENTS
CHAPTER 1 — INTRODUCTION
OVERVIEW This bulletin explains how to install and operate the POWERLINK® G3
NF2000G3/NF3000G3 Controller, which is used to control the operation of a
POWERLINK G3 system. The controller uses remotely operated circuit
breakers to control up to 168 remotely operated branch circuits. Control
signals originate externally from dry-contact inputs, from the internal time
scheduler, or from commands received via the communications network.
Typical control devices include low voltage pushbutton wall switches,
occupancy sensors, photocell controllers, and security and building
management systems.
KIT CONTENTS The following items are provided for installation of the POWERLINK
NF2000G3/NF3000G3 controller:
• NF2000G3/NF3000G3 controller
• Class 2 barrier
• Connector hardware kit
x 8 three-terminal connectors
x 1 five-terminal connector
x 1 two-terminal connector
• Miscellaneous hardware kit
x screwdriver
x tie wrap
x panelboard reference label
FIRMWARE This bulletin also describes the features and operation of a controller using
version 5 firmware. To find your controller’s firmware version, see “Viewing
Controller Information” on page 103.
FRONT PANEL OVERVIEW Figure 1 – 1 shows the parts of the controller’s front panel. A brief description
of each part follows in Table 1 – 1.
Figure 1 – 1: Controller Front Panel
A. LCD Screen A
B. Wiring Compartment Cover
C. RS-232 Port
D. Plus Key/Enter Key
E. Minus Key
F. Next Key
SQUARE D COMPANY
G. Back Key POWERLINK
H. Reset Button
NF2000G3
Rx THU 01-MAR-2001 RUN
Tx 02:55:40 PM MENU >
H G F E D C B
WIRING COMPARTMENT OVERVIEW Figure 1 – 2 shows the parts of the controller’s wiring compartment. A brief
description of each part follows in Table 1 – 2.
Figure 1 – 2: Controller Wiring Compartment
A B
D
E
G H
IN THIS CHAPTER This chapter contains important safety precautions that must be followed
before attempting to install, service, or maintain electrical equipment.
Carefully read and follow the safety precautions below.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• This equipment must be installed and serviced only by qualified electrical
personnel.
• Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E.
• Turn off all power supplying this equipment before working on or inside
equipment.
• Always use a properly rated voltage sensing device to confirm that
power is off.
• Replace all devices, doors, and covers before turning on power to this
equipment.
• Before energizing panelboard, all unused spaces must be filled with
blank fillers.
INTRODUCTION This chapter is a quick reference listing the steps necessary to install an
NF2000G3/NF3000G3 controller in a POWERLINK G3 system. The steps in
this chapter are provided as an installation checklist. For complete
installation instructions, refer to the chapter listed.
QUICK START CHECKLIST Use the following table as a quick start checklist for the controller:
CHAPTER 4 —INSTALLATION
INSTALLING THE CONTROLLER Follow these steps to install the controller in an NF panelboard (refer to
Figure 4–1):
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E.
• Turn off all power supplying this device and the equipment it is installed
before working on it.
• Use a properly rated voltage sensing device to confirm that power
is off.
1. Turn off all power supplying this device and the equipment it is installed.
2. Remove the panelboard cover and deadfront. Verify that the power is off
using a properly rated voltage sensing device.
3. Insert the controller’s two bus connectors into the vertical bus
connections on the right control bus (see Figure 4–1).
NOTE: If you are using a standard NF panelboard, the controller is
installed at the top of the right control bus. If you are using a column-
width NF panelboard, the controller is installed at the top of the
panelboard (see Figure 4–1).
Controller
4. Push the controller onto the control bus until the mounting feet snap onto
the panelboard interior.
A captive screw on the left side of the controller is lined up with a hole on
the panelboard interior. Use a screwdriver to secure the screw. Torque to
20–30 in-lbs.
NOTE: If not already installed, install the power supply according to its
instruction bulletin.
5. Push the power supply connector plug into the power connection on the
controller (see Figure 4–2).
NOTE: If you are using a column-width NF panelboard, the column-width
controller cable NFCWG3 is required to connect the power supply and
controller.
Physical vs. Communications The controller supports up to 16 physical inputs and up to 64 communication
inputs. Physical inputs receive their signals to turn ON or OFF from
dry-contact type switches (such as wall switches and occupancy sensors)
that are wired to a controller’s input terminals. Communications inputs do not
exist physically, rather they receive commands to turn ON or OFF across the
communications network. For example, a building management system can
send a command (by writing to a specific register in the controller) to turn a
communication input ON or OFF across Ethernet or RS-485
communications.
CONNECTIONS A connector plug is provided for each of the eight sets of terminals. The
wiring compartment label identifies each terminal as shown below in
Figure 5– 1.
Figure 5– 1: Input/Output Connector Diagram
Input Terminal
EXTERNAL DEVICE WIRING External control devices, such as wall switches, photocells, occupancy
sensors, and relays can be easily connected to the controller’s input
terminals. Most of these devices have a single set of contacts that provide a
control signal, requiring two wires for connection (see Figure 5– 3). Some
devices use two sets of contacts to provide a control signal, requiring three
wires for connection (see Figure 5– 3). The contact closure activity is
monitored by the controller and is interpreted according to an input type
configuration setting that is appropriate for the external device. The bi-
directional terminal shown in Figure 5– 3 is used as an input when a 3-wire
device is used.It also can be used as an independent input, as shown in
Figure 5– 4.
Figure 5– 3: 2- and 3-wire Input Connections
2-wire device
3-wire device
A pilot light, relay, or other device that requires an output from the controller
uses the bi-directional terminal as an output. The output function, shown in
Figure 5– 5, is only available if the bi-directional terminal is not being used as
an input. Use this connection to obtain a powered signal representing the
zone status of the input located on the same 3-terminal connector.
Figure 5– 5: Output connection
+
L
–
Terminals The diagram below illustrates the position of each connector in a controller.
Numbered terminals are input terminals. Numbered terminals in parenthesis
can be used as either input or output terminals, allowing for up to 16 inputs.
Figure 5– 6: Terminal Diagram
+24 V
(13) (9) 2-wire device
Input 9
6 2
Dual momentary inputs
Input 1 ON
(14) (10)
+24 V 3-wire device
7 3 Input 1 OFF
Status Output
L pilot light
(16) (12)
COMMON INPUT TYPES Table 5-1 describes the types of typical input configurations used in
POWERLINK G3 systems. The contact activity of the external device is
monitored by the controller and is interpreted according to the selected input
type configuration.
Table 5 – 1: Common Input Types
Input Type Application Operation Connection Diagram
External control devices such as The input state is commanded ON
photocells, time clocks and when the contacts are closed and
Maintained Normally Open
occupancy sensors that contain a is commanded OFF when the
normally open contact. contacts are opened.
Same as above. Associated
Maintained Normally Open Notifies an occupant when the breakers will blink (if configured ON when closed
with Blink lights are about to turn OFF. with Blink Type) in response to an
OFF command.
External control devices such as The input state is commanded
photocells, time clocks and OFF when the contacts are closed
Maintained Normally Closed
occupancy sensors that contain a and is commanded ON when the
normally closed contact. contacts are opened.
Same as above. Associated
Maintained Normally Closed Notifies an occupant when the breakers will blink (if configured ON when opened
With Blink lights are about to go OFF. with Blink Type) in response to an
OFF command.
ON
The input state alternates between
Maintained switches used to or
Maintained Toggle ON and OFF each time the switch OFF
switch lights ON and OFF
changes position.
INPUT TIMERS Any input can be configured with a timer that will automatically turn OFF or
ON the input after a period of time. The duration of the input timer can be set
for up to 18 hours. See Table 5 – 2 for a description of the available timer
types.
Table 5 – 2: Timer Types
Timer Type Operation
No Timer The input is not affected by the timer.
The timer countdown starts or restarts whenever the
Timed ON input is turned ON. The input is commanded OFF when
the timer value reaches zero.
The timer countdown starts or restarts whenever the
OFF Delay input is commanded OFF, but the input remains ON
until the timer reaches zero.
The timer countdown starts or restarts whenever the
ON-Delay input is commanded ON, but the input remains OFF
until the timer reaches zero.
WIRING AN EXTERNAL DEVICE TO An external device may be wired to multiple controllers. It is recommended
TWO OR MORE CONTROLLERS that the source voltage be provided to the external device by one controller.
The input signal from the external device and the circuit common terminal on
the auxiliary power connector are connected to the other controllers.
Figure 5– 7: Connecting an External Device To Multiple Controllers
To Next Controller
External Device
Circuit Circuit
Common Common
Terminal Terminal
To Next Controller
Controller 1 Controller 2
APPLICATIONS FOR COMMON The following table shows how the input configuration types can be used in
INPUT TYPES common applications.
Switch Input
Momentary Switch
ON/OFF wall
(configured for Switch toggles lights ON and OFF.
switch
momentary toggle) L
+
Neutral
Circuit 1
Sensor Input 1
Occupancy-rated Control
Occupancy sensor wired to Input 1 is mapped to Circuit 1 and
sensor Input 1 (configured + Circuit 2. When motion is detected, the
controlling a for maintained N.O.) occupancy sensor contact will close,
group of circuit Control power Neutral causing circuit breakers 1 and 2 to
24 Vdc
breakers supplied by auxiliary + Circuit 1 close.
Common
power supply. – Circuit 2
Aux. Power
INTRODUCTION
controller
power supply
control buses
The second level of the communication network connects the system (one or
more controllers) to devices such as personal computers, modems, or a
building management system with the appropriate interface drivers. This
communication network is referred to as the automation network (see
Figure 6–1).
Figure 6–1: Automation and Subnet Communications Networks
Power Power
Supply Subnet Supply
Subnet
Slave Panel Slave Panel Master Panel Slave Panel Slave Panel Master Panel
Subnet Components In a subnet network, the master panel contains the controller and power
supply. Other panels connected to the controller are referred to as slave
panels. Figure 6–2 illustrates these components.
Figure 6–2: Subnet System Communications Wiring
Power
Supply
Controller To Next
Power Supply Panel
Subnet Connector
Slave Address
Slave Bus
Selector Interconnect Cable
POWERLINK® G3
(NF2HG3 )
POWERLINK® G3
Right
Control
Bus
Left
Control
Master Panel Slave Panel Bus
4-wire, 18 AWG
subnet cable from
the subnetwork
+
–
A
B
Subnet Wiring The power supply, located in the master panel, is connected to each slave
address selector in a daisy chain as shown in Figure 6–4. Only one slave
address selector is required for each slave panel.
+
– To next Slave
–
Address Selector
A
A
B
B
Power Supply Slave Address Slave Address
in Master Panel Selector in Slave Selector in Slave
Panel 1 Panel 2
Wiring the controller to the subnet is not necessary. The connection between
the controller and the power supply provides the subnet communications for
the controller.
Slave Address Selector The slave address selector enables you to set the address of the slave
panel. A dial switch on the face of the selector is labeled 0 –7, with each
number representing a unique address. Address 0 is reserved for the master
panelboard. If the power supply or controller is plugged into any control bus
on the subnet, address 0 should not be used as a slave address.
Figure 6–5: Dial switch On The Address Selector
address
setting
dial
Subnet Conductors The National Electrical Code (NEC) classifies the POWERLINK G3 subnet
communications wiring as a Class 1 circuit. Thus, the conductors must be
sized and insulated from the line voltage of the panelboard. To meet Class 1
requirements, conductors should be 18 AWG and installed in conduit or an
appropriate raceway.
Four conductors are required for the subnet. Two conductors carry 24 Vdc
power to the control buses, while the other two are used for the data path.
Approved cables are 4-wire, 18 AWG, Class 1 subnet cables such as
General Cable 236100, Belden 27326, or equivalent.
The total distance of the conductor length from the power supply to the
farthest control bus depends on the power supply voltage. Table 1 list
maximum wiring distances based on nominal voltages.
Table 6–1: Maximum Wiring Distances
Power Supply Maximum
Nominal Voltage➀
Part Number Cable Length
120 V NF120PSG3 400 ft (122 m)
220 V NF240PSG3 100 ft (30 m)
240 V NF240PSG3 400 ft (122 m)
277 V NF277PSG3 400 ft (122 m)
➀ Phase to neutral voltage
NOTE: If you are using a T- connection to connect the power supply to the
subnet, the subnet distance limits above apply to each direction of the
T-connection. Star connections are not recommended.
With the exception of setting the slave address selectors, no additional setup
is required for commissioning the subnet communications network.
The RS-232 and RS-485 ports are connected internally to the same controller
serial communication port. Therefore, only one master device can be
connected through one of the ports to the controller. For example, you
cannot simultaneously connect a computer to the RS-485 port and a PC to
the RS-232 serial port. Attempting to do so may result in improper operation.
RS-232 Port
(requires serial cable
NFFPCG3 for
temporary PC
connection)
RS485
+
–
COM 1
Serial Port
RS232
TX
RX
Ethernet Port
RS-485 Communications Multiple controllers can be networked together by wiring the system using
the RS-485 port on the controllers. Figure 6–7 illustrates a typical
configuration where three master panels are shown (each controlling its own
independent subnet.)
Personal Computer
or Modem
RS-232 to
RS-485 RS-485 Daisy Chain,
Converter 2-Wire, Twisted Pair
Belden 9841 or equivalent
Power Supply
RS-232 Port
Maximum Distances
Baud Rate
1–8 Controllers 9–16 Controllers 17–32 Controllers
76,800* 4,000 ft (1,219 m) 4,000 ft (1,219 m) 3,000 ft (914 m)
38,400 4,000 ft (1,219 m) 4,000 ft (1,219 m) 3,000 ft (914 m)
19,200 5,000 ft (1,524 m) 4,000 ft (1,219 m) 4,000 ft (1,219 m)
9,600 5,000 ft (1,524 m) 5,000 ft (1,524 m) 4,000 ft (1,219 m)
4,800 5,000 ft (1,524 m) 5,000 ft (1,524 m) 4,000 ft (1,219 m)
2,400 5,000 ft (1,524 m) 5,000 ft (1,524 m) 4,000 ft (1,219 m)
1,200 5,000 ft (1,524 m) 5,000 ft (1,524 m) 4,000 ft (1,219 m)
* NOTE: BACnet MS/TP only
RS-485 Controller Connections Using a Connection from the network to a personal computer, modem, or a building
RS-232/485 Converter management system with the appropriate interface drivers often requires the
use of a converter that will convert the RS-485 signal to an RS-232 signal.
When the automation network is connected to the serial port (comms port)
on the computer, the POWERLINK Controller Software (PCS-101) can be
used. A female DB9 to female DB9 cable is required for the connection from
the computer serial port to the converter. Square D offers a standard RS-
232/485 converter kit that includes the converter, power supply, and serial
cable (Square D catalog number 6382RS485G3KIT). Connection of this kit
to the automation network is shown in Figure 6–8. The communication wires
are daisy-chained from one controller RS-485 port to the next in the following
manner: positive to positive (+ to +), negative to negative (– to –), and shield
to shield.
Figure 6–8: 2-wire, RS-485 Connection Using a Converter Kit
RS-485
serial cable
RD (A) – –
Shield
RS-232 RD (B)
RS-232
Female TX TX To
DB-9
GND Next
RX RX Controller
+12 VDC +12 V Master
COM 1 COM 1
Panel
ECHO
OFF Power
ON Supply
Black/White Stripe
Ground shield in Jumper on
one place only. ECHO OFF
RS-485 Controller Connections Using A DMX512 master may be connected to the controller via the internal RS485
DMX512 port. See “Using a G3 Controller with DMX512 Systems” on page 131 for
more information.
NOTE: All connection methods, except for Ethernet connections, share the
same serial port. A separate Ethernet port is located in the wiring
compartment. Potential communication errors may occur if multiple
computers access any controller’s serial port at the same time. Do not
attempt to communicate through the front panel connection while a
permanent computer connection, such as a DMX512 console, is actively
communicating with the controller. However, simultaneous serial port and
Ethernet communications is permitted.
Automation Communications Wiring The National Electric Code (NEC) classifies automation communications
Specifications wiring as a Class 2 circuit. Conductors may range in size from 24 to 18 AWG
and consist of a single set of twisted pair conductors with a shield (Belden
9841 or equal). Maximum wiring distance should not exceed 5000 ft (1524
m) at 19,200 baud for eight controllers. See Table 6–2 on page 31 for the
maximum communication cable distances at various baud rates.
Shielding and Grounding The automation network shield should be grounded in one place only,
typically at the RS-232/485 converter as shown in Figure 6–9 on page 35.
The controller’s input terminals and auxiliary power source are part of the
Class 2 circuitry. External devices connected to the controller must meet the
isolation requirements and other Class 2 wiring standards. Do not connect
the controller to external voltage sources or earth ground.
Alternate RS-485 Wiring An alternate RS-485 wiring scheme that uses a third reference wire is
preferred in certain applications:
• When you cannot avoid connecting the Class 2 input circuitry to
earth ground.
• When an external device’s isolation from ground is minimal.
• When the controller is installed on a network with non-isolated devices.
Shield
Controller Comms Controller Comms Controller Comms
Terminal in Master Terminal in Master Terminal in Master
TD (A) Panel 1 Panel 2 Panel (n) To next
+ Controller
TD (B) + + + –
RS-485
RD (A) – – –
Reference Wire
RD (B)
RS-232
TX TX TX
GND
RX RX RX
+12 V +12 V
COM 1 COM 1 COM 1
ECHO
OFF
ON
Power Supply
Black/White Stripe
RS-232 Serial Communications In addition to the RS-485 communications port, the controller has an RS-232
port for direct connection to personal computers, modems, or other devices
that support MODBUS ASCII or RTU communications as shown in
Figure 6–10. Because it is a direct RS-232 connection, no converter is
required. However, the total length of the RS-232 wiring should not exceed
50 ft (15 m).
Figure 6–10: RS-232 Controller Serial Connections
Power Supply
RS-232 Connection to a Personal To make the serial communications connection using the RS-232 port of the
Computer controller, use a standard RS-232, 9-pin DB-9 connector and serial cable.
Figure 6–11 shows these connections.
Figure 6–11: RS-232 Controller Serial Connection Detail
Controller
Terminal
PC Serial Connection Cable +
DB9 Male
SIGNAL GND 5
RX 2
DB9 Female
5 SIGNAL GND
TX
} RS-485
TX 3 3 TX
RX
} RS-232
DTR 4 4 DTR
DSR 6 6 DSR
Note:
RX = Receive Data
RTS 7 7 RTS TX = Transmit Data
DTR = Data Terminal Ready
CTS 8 8 CTS
DSR = Data Set Ready
DCD 1 1 DCD (no connection)
RTS = Request to Send
CTS = Clear to Send
RI 9 9 RI (no connection) DCD = Data Carrier Detect
RI = Ring Indicator
GND = Signal Ground
Ethernet Communications The controller has an Ethernet port for connection to a LAN or other devices
that support Modbus TCP/IP communications (see Figure 6–12).
PC or Network Server
Ethernet Cable
Controller’s Ethernet Port
(see Figure 6–6 for
connection detail)
Power Supply
Master Master
Panel A Panel B
INSTALLING THE CLASS 2 BARRIER Follow the instructions below to install the Class 2 barrier.
DANGER
DANGER OF ELECTRIC SHOCK, BURN OR ARC FLASH
• Turn off all power supplying this equipment before working on or inside
the equipment.
• Always use a properly rated voltage sensing device to confirm that power
is off.
Failure to follow this instruction will result in death or serious injury.
1. Turn off all power supplying this device and the equipment it is installed.
Verify that the power is off using a properly rated voltage sensing device.
2. Remove the connector cap by pressing down on the retaining tab that
secures the cap, then slide the cap up and away from the controller
(see Figure 7–1).
3. Remove the conduit plug by pulling down and out on the conduit plug.
retaining tab
connector cap
conduit
plug
4. Thread the supplied tie wrap through the holes on the controller (see
Figure 7–2).
tie wrap
5. Locate and remove a knockout on the top of the panelboard near the
controller.
6. If not using a conduit, apply a fitting where the knockout was removed.
This will protect the wires coming into the panelboard.
7. Pull the Class 2 wires into the panelboard through the hole in the
panelboard.
8. Determine the length of the barrier by measuring the distance from
where the wires enter the panelboard to the controller wiring
compartment.
9. Cut the barrier slightly longer than the measured length to allow enough
of the barrier to enter the wiring compartment.
10. Thread the wires into the barrier and slide the barrier up to the hole in the
panelboard.
11. Cut the wires to length and terminate them according to the input wiring
and communication wiring requirements, as described in Chapter 5—
Input Wiring and Chapter 6—Communications Wiring.
12. Close the tie wrap around the barrier to secure the wires and barrier to
the controller (see Figure 7–3).
CHAPTER 8 — OPERATION
OPERATING THE DISPLAY The LCD screen displays information as dark text against a light
background. The cursor position is indicated by light text against a dark
background. Placing the cursor on a screen path symbol (< or >) allows you
to move between screens, and placing the cursor on a value field allows you
to change that value. Underlined text indicates a selected item (or items) in a
group of multiple choices (see Figure 8–1 for examples of these features).
Figure 8–1: Typical Screen
Screen path
symbol
Cursor location /
Highlighted item
Selected item
Using the Keys The four keys on the display let you navigate and change information on
each screen, as well as move from screen to screen. Table 8–1 shows the
keys and their descriptions.
Table 8–1: Keys of a controller
Key Name Key Key Application
* The right-pointing screen path symbol (>) is used to move to a lower level screen, and the left-
pointing screen path symbol (<) is used to move to a higher level screen.
Selecting a Screen To select a screen or to return to a previous screen, follow these steps:
1. To view a screen:
a. Press the Back key or Next key to highlight the right-pointing screen
path symbol (>).
b. Press the Plus key to view the screen.
In the screen examples below, the cursor in the MAIN MENU screen
is highlighting the CONTROLLER screen path symbol, leading to the
CONTROLLER MENU screen.
Screen Navigation To indicate multiple screen navigation, this manual uses the following
format:
1. From the MAIN MENU, select SOURCE > INPUTS > INPUT SYNC.
This means you would select SOURCE from the MAIN MENU screen, then
select INPUTS from the SOURCE MENU screen, and finally select INPUT
SYNC from the INPUTS screen.
Selecting from a List If you are selecting from a list, note that there are two types of lists:
1. Scrolling List – only ONE choice is displayed at a time
a. Press the Back key or Next key to move the cursor over the option
you want to change.
This highlights the first item in a scrolling list.
b. Use the Minus key or Plus key to scroll through the available choices.
The highlighted text changes each time to indicate the next choice. In
the example below, SINGLE is selected from four different choices.
2. Marked List – all available choices are displayed; selected options are
marked with an underline
a. Press the Back key or Next key to move the cursor over an item in
the list.
b. To select the item, press the Plus key while the item is highlighted.
The item is now underlined. In the example below, the days Monday
through Friday are selected.
c. To deselect an item, press the Minus key while the item is
highlighted.
The underline disappears from the item.
Saving Your Changes Changes to controller data are saved automatically when you exit a screen.
For example, if changing an ON time from 7:00 AM to 7:30 AM, after
highlighting “00” and changing it to “30,” the new time becomes valid after
you exit the screen.
Pop-up Error Screen The controller automatically checks your changes and alerts you to data
entry errors with an error screen. Examples of data entry errors are entering
illegal dates, such as February 31, or placing an end date prior to a start
date. In these instances, upon exiting the screen, an ENTRY ERROR screen
(see below) displays with a message describing the error. The screen path
symbol leads you to the previous screen so you can correct the error.
SCREEN OVERVIEW This section explains the available controller screens, and it briefly describes
the general use of the screens.
Main Screen The Main screen is the first screen you see before using the controller. This
screen is automatically displayed if none of the keys are pressed during a 5
minute period.
The current time and date are displayed. The Rx (receive) and Tx (transmit)
indicators show communications activity (they are blank at other times). The
RUN or HALT mode is displayed next to the time and day fields (see
“Selecting the Operating Mode” on page 105 for more information about
RUN and HALT modes).
NOTE: To assign a name for this controller, see the section “Entering a
Controller Name” on page 106.
Accessing the Menu Screens Upon power-up or reset, the Main screen displays.To view the MAIN MENU
screen, do as follows:
1. From the Main screen, select MENU.
The MAIN MENU screen displays.
2. From the MAIN MENU screen, select the menu you want to view.
Main Menu Screens The MAIN MENU screen provides paths to all other screens. Each of the
MAIN MENU sub-headings represents a major topic. Except for ACCESS,
each sub-heading leads to another menu screen (see Figure 8–2 for
illustrations of the various menu screens. Each sub-heading is described
briefly below:
• ACCESS: From this screen you can enter an access code, which allows
access to various levels of screen operation.
NOTE: If this sub-heading does not appear upon entering this screen, no
access codes are currently set, allowing access to all screens.
• STATUS: From this menu, you can view the live status of circuit breakers,
zones, inputs, schedules, communications, and systems.
• SOURCE: From this menu you can set up remote sources, schedules,
local inputs, and status outputs.
• ZONE: From this menu, you can add or delete circuit breakers from a
zone, assign sources defined in the SOURCE menu, and schedule zone
priorities for both normal and special days.
• CONTROLLER: From this menu, you can set up the various functions of
the controller, including the time and date, special days, circuit breakers,
control buses, and communications.
• TOOLS: From this menu, you can override zones, change the operating
mode, set access codes, enter a controller name, and clear the controller
memory.
Figure 8–2: Main Menu Screens
Screen Access Level Every screen has a fixed assigned access level. An access level enables or
disables access to certain controller screens. To control user access, an
access level must be assigned an access code. Once an access code is
defined, you will need to login to use the controller’s screens. For example,
Level 1 has an access code of 1234, and Level 2 has an access code of
9876. You must login using 1234 to gain Level 1 access, or you must login
using 9876 to gain Level 2 access. If you are unable to provide any of the
correct access codes, you will not be able to use the controller.
See Table 8–2 on page 49 for the access level of each screen.
Example: If you enter an access code of 5555 for Level 2, but leave Level 1
as 0000, then Level 2 inherits Level 1 access permissions.
The Clear function is not an individual screen, but is listed because of the different login level required.
The Control function is not an individual screen, but is listed because of the different login level required.
The Clear function is not an individual screen, but is listed because of the different login level required.
The Control function is not an individual screen, but is listed because of the different login level required.
Entering Access Codes To enter your access code, follow these steps:
1. From the MAIN MENU screen, select ACCESS.
NOTE: If the ACCESS sub-heading does not appear on the MAIN MENU
screen, access codes are not currently set, allowing access to all
screens (see “Setting Access Codes” on page 106).
The ACCESS LOGIN screen displays.
On entering this screen, the current login access code is not shown
(**** is displayed). Access codes are 4 digits in length.
2. Position the cursor over each digit, using the Plus key or Minus key to
increase or decrease the number.
3. Move the cursor to the left-pointing screen path symbol to save your
code entry.
The entered access code is compared to the access code table, and the
login level is displayed.
NOTE: A 5-minute timer restarts every time a key is pressed. When this
timer expires, the entered access code is cleared and the user is logged
out.
PROGRAMMING A NEW SYSTEM Use a top-down approach to controller setup and programming. The
following flowchart shows a recommended sequence of tasks.
SETTING UP CONTROLLER To set up items in the controller not specific to any zone, you use the
OPTIONS CONTROLLER MENU. To access the CONTROLLER MENU, do as follows:
NOTE: For information about zones, see the section “Setting Up Zones” on
page 79.
From the MAIN MENU screen, select CONTROLLER.
The CONTROLLER MENU screen displays.
From this screen, you can access all controller setup screens, from
which you can do the following tasks:
x Set the time and date and the clock options
x Enter special days information
x Set up circuit breaker parameters
x Set up control bus parameters
x Set up communication parameters
Setting Up Communication Parameters To set up communication parameters for the controller (refer to Table 8–3
for communications option descriptions), follow these steps:
1. From the CONTROLLER MENU screen, select COMMUNICATIONS.
The COMMUNICATIONS screen displays.
2. The control module has a port that is used for both the front panel and
the wiring compartment connections.
3. Follow the steps below to set up serial or Ethernet communications:
Enabling Comms Loss Action POWERLINK G3 controllers allow you to set the action of a zone in the
event of an extended loss of communications with a building automation
system (BAS).
NOTE: This feature should be enabled only when the controller is being
used as part of a BAS and the BAS is continuously communicating to the
controller.
Setting Comms Loss Action 1. From the COMMUNICATIONS screen, select COMMS LOSS ACTION.
The COMMS LOSS ACTION screen displays.
Setting Comms Loss Zones To enable comms loss action for a zone, do the following:
1. From the COMMS LOSS ACTION screen, select COMMS LOSS
ZONES.
The COMMS LOSS ZONES screen displays.
When communication is restored, all overrides for all zones remain in effect.
The BAS will need to restore the correct operating condition when it detects
the controller is back on line.
Setting Time and Date 1. From the CONTROLLER MENU screen, select TIME/DATE.
The TIME/DATE screen displays.
Clock 12 HR (AM and PM) The Clock Format option lets you select how
Format 24 HR. time is displayed.
DST YES = ON The DST Enabled option lets you select whether
Enabled NO = OFF Daylight Savings Time is ON or OFF.
The Latitude option lets you enter the latitude of
the controller’s location. Used with the Longitude
value, it enables the controller to more
0–64 degrees North accurately calculate sunrise and sunset. For the
Latitude
or South latitude of major cities in the United States and
other countries, refer to Table 8–10 on page 58.
NOTE: The latitude range is limited so that sunrise and
sunset always occur on the same day.
The Longitude option lets you enter the longitude
of the controller’s location. Used with the
0–180 degrees East Latitude value, it enables the controller to more
Longitude
or West accurately calculate sunrise and sunset. For the
longitude of major cities in the United States and
other countries, refer to Table 8–11 on page 58.
The Time Zone option lets you select the time
zone for the controller. The time zone typically
See Table 8–9
Time Zone shows the hours offset from Greenwich Mean
on page 57
Time (GMT), although names appear for times
zones located in the US and Canada.
Setting Up Time Synchronization The controller’s real-time clock can be synchronized via a network time
protocol (NTP) server. Synchronization occurs at the configured rate, but if
the controller does not receive a response from the NTP server, it will
continue to operate with its current time information. To set up time
synchronization, follow these steps.
1. From the TIME/DATE screen, select SYNC.
The TIME SYNC(1) screen displays (see Table 8–12).
SETTING UP SPECIAL DAYS Special Days are exception periods that override normal day operation. A
special day period can range from one day to several days. A special day
starts at 12:00 AM (midnight) and ends at 12:00 AM (midnight). Up to 32
special days can be defined in a controller
.
NOTE: If a calendar day is a member of more than one Special Day, the
highest priority Special Day is the only Special Day used. All other Special
Days in a period are ignored.
NOTE: To schedule the Special Day ON and OFF times for individual zone
schedules, see “Setting Up Schedules” on page 72.
UNDEFINED Special Day is not defined The rest of the screen remains blank.
Repeats every week on a specific day 1. In the On field, select a day of the
with start and end dates week.
2. In the For field, select the number of
EVERY WEEK days the Special Day is enabled.
For example: Every Friday for 1 day 3. In the With field, select START/END
starting April 1, 2004 and ending DATES to configure the dates the
June 1, 2004 Special Day begins and ends.
Start and end dates may be applied to the special day to create a one-time special day or special day schedule extending for several years for special days occurring
on different dates every year.
Repeats every month on a specific 1. In the first “On the” field, select a
day of a specific week for an indefinite week of the month (1ST, 2ND, 3RD,
period of time 4TH, LAST).
EVERY MONTH 2. In the second “On the” field, select a
day of the week.
For example: Every first Friday of the 3. In the For field, enter the number of
month and continuing for 3 days days the Special Day is enabled.
Start and end dates may be applied to the special day to create a one-time special day or special day schedule extending for several years for special days occurring
on different dates every year.
Start and end dates may be applied to the special day to create a one-time special day or special day schedule extending for several years for special days occurring
on different dates every year.
Assigning Special Day Names To assign or change special day names, follow these steps:
1. From the SPECIAL DAYS screen, select NAME.
The SPECIAL DAY NAME screen displays.
2. Enter the name of the Special Day (see “Entering or Changing a Name”
on page 45).
SETTING UP CONTROL BUSES The CONTROL BUSES screen enables you to set up the controller’s circuit
breaker programming to match the physical numbering of the panelboard.
In this screen, the control bus number is 0L, and the control bus name is
blank. If the control bus had a name, it would appear under the BUS line.
2. Select the desired BUS (control bus) number.
The control bus name (if entered) displays. The NAME screen path
symbol leads to the BUS NAME screen.
3. To assign or change a control bus name, see “Naming Control Buses” in
the section below.
4. Select the desired First Breaker Number, starting at the vertical bus
connection end of the control bus.
5. Select the Numbering Sequence for the other circuit breakers on the bus.
Sequence and pattern examples are listed in Table 8–17.
NOTE: The choices listed depend on the selected first breaker number,
and the selected option sets the numbering pattern.
Naming Control Buses To assign or change control bus names, follow these steps:
1. From the CONTROL BUSES screen, select NAME.
The CONTROL BUS NAME screen displays.
Naming Circuit Breakers 1. From the BREAKERS screen, select CIRCUIT NAME.
The CIRCUIT NAME screen displays.
Blink Notice Controllers can be configured to notify occupants that circuits have been
commanded OFF. Typically, this feature is used to give notice that the lights
will turn OFF in a specified amount of time. Circuits blink according to the
blink type selected for the circuit during configuration (see “Blink Type”
below).
NOTE: Breakers should not be configured for blink notice if blink notice is
not desired.
Blink Type The blink type refers to the behavior of circuit breakers when they are
commanded OFF.
Table 8–18: Circuit breaker blink types
Blink Type Description
None The circuit breaker turns OFF immediately, without a blink notice (default setting).
The circuit breaker blinks once to notify that the circuit breaker will turn OFF in a specified amount of time,
Single
unless it is commanded back ON.
The circuit breaker blinks twice to notify the circuit breaker is about to turn OFF. A second blink occurs one
Double
minute prior to the circuit turning OFF.
The circuit will turn OFF in the specified amount of time, but will not blink. This is typically used for loads that
you cannot blink, such as high intensity discharge (HID) lights. These loads are generally assigned to the
same zone with loads that can blink.
For example, in a factory setting both the HID lights and normal lighting are assigned to the same zone. The
Delay only normal lighting has a blink type of SINGLE, and the HID lighting has a blink type of DELAY ONLY. At the
end of the scheduled time period, the normal lighting blinks, signaling that the lights will be turned OFF; the
HID lighting does not blink, and the lighting remains ON. The occupant can turn ON the zone's override
switch to keep both types of lighting ON. Otherwise, both sets of lights will turn OFF at the end of the
countdown (see “Setting Up Circuit Breaker Timing” on page 69).
Pulse OFF* The circuit breaker is turned OFF for a predetermined time and then returns to the ON state.
Pulse Repeat* The circuit breaker is turned OFF based on a preset amount of time.
* These blink type options are provided for use with a sweep switch. See “Using a Controller with Sweep Switches” .
Using a Controller with Sweep Switches A sweep switch, such as a Sentry® 1switch, is a line-voltage wall switch that
will automatically reset itself to the OFF position when power is interrupted.
The Pulse OFF and Pulse Repeat blink types are provided for use with a
sweep switch.
Effect on Circuit Voltage Remotely operated circuit breakers normally turn ON or OFF in response to
a command. When Pulse OFF or Pulse Repeat is selected, circuit voltage
will remain ON at all times, with the following exceptions:
• The brief time of the OFF pulse. A single, momentary OFF pulse will
occur whenever the breaker state is commanded OFF. When Pulse
Repeat is selected, additional pulses will occur at the pulse repeat
frequency as long as the breaker remains commanded OFF.
• When first configuring a blink type as either Pulse OFF or Pulse Repeat.
If the breaker is OFF when the blink type is selected, it will remain OFF
until it is commanded ON. It will remain ON thereafter, except during an
OFF pulse.
Configuration Here are examples for the two Pulse blink types:
Setting a Blink Type See “Setting Up Circuit Breaker Timing” on page 69 to set the time period
between a blink and a circuit turning OFF.
In this screen, the Blink Type for circuit breaker 12 (named ROW 1) on
control bus 5L (named LP5A) is set to DOUBLE.
2. Select the BUS (control bus) number and the BKR (circuit breaker)
number.
If set up, the BUS and BKR names display.
3. Select a Blink Type (see Table 8–18 for descriptions of the six different
blink types).
Setting Up Circuit Breaker Timing Circuit breaker timing settings are used to control the length of time between
a blink notice and when the breakers are turned OFF, the minimum amount
of time between successive switching operations, and the amount of time
the controller waits to verify that a circuit breaker is in its commanded state
(ON or OFF).
SETTING UP CONTROL SOURCES A control source contributes to a controller’s decision to turn a zone ON or
OFF. NF2000G3 and NF3000G3 controllers support up to four control
sources per zone. Each user-selectable control source can be any schedule,
any input, any zone, or any remote source. For example, you could define
the control sources for Zone 1 as Schedule 1, Schedule 3, and Input 16. The
logic type you choose when setting up the zone determines how the control
sources are combined to control the zone. See “Assigning Control Sources”
on page 84 to learn how to assign a control source to a zone. This section
describes how to set up schedules, inputs, and remote sources.
Setting Up Inputs The input function combines dry-contact input activity with timers to
determine a logical ON/OFF state for each input.
The INPT line displays the selected input and the input’s nametag. Refer
to “Naming An Input” on page 72 to assign the input a name. See
Table 8–23 for input types and their abbreviations. Refer to Table 8–22
for all other screen options.
2. Set up the input options listed in Table 8–22.
NOTE: Setup is limited to inputs 1–16. Because inputs 17–64 do not exist
physically, no input type configuration is available. Inputs 9–16 do not have
the choice of Dual Momentary, but they do have the choice Status Output.
In this screen, you can enter a name for the sixth input.
2. Enter the name of the input (see “Entering or Changing a Name” on
page 45).
Setting Up Schedules The NF1000G3, NF2000G3, and NF3000G3 controllers have internal time
clocks that allow you to create schedules of operation. Each controller
supports up to 16 schedules. Each schedule supports up to 24 time periods,
which are labeled simply as periods. The controller logically “ORs” the
periods to determine if a schedule is ON. In other words, a schedule is ON if
any of its periods are ON. You can specify two types of days in a schedule:
normal days and special days. Normal days refer to particular days of the
week. Special days refer to a set of conditions, and are exceptions that have
priority over normal days.
NOTE: Normal day schedule periods will not execute on special days unless
the special day is included in that period. See “Creating Special Day
Schedules” on page 74
The SCHL line displays the selected schedule number (06) and nametag
(TOOL SHOP).
2. For the Period, select the desired time period for this zone (range: 1–24).
Creating Special Day Schedules Because special days are exceptions to normal days, no time periods will be
valid on special days unless the special day is included in a time period. A
time period may also be created that is valid only on a special day to create
a unique special day time period.
NOTE: A special day affects all periods in all schedules.
All 32 possible special day numbers appear (see the left screen above),
including the configured special days, which are set up in the section
“Setting Up Control Sources” on page 70. Numbers for Special Days that
are not italicized, and UNDEFINED SPECIAL DAY appears when you
highlight the number. If a Special Day is configured, the number is in
regular text. When a number is highlighted the Special Day name and
the priority level appears. For example, in the image above, highlighting
number 07 reveals that it is a configured special day named
THANKSGIVING with a priority level of 01. The underlines indicate that
special day numbers 05 and 12 are included in the schedule period.
2. To create a unique special day schedule, select a configured special day
number for the schedule period, making sure the schedule has no days
of the week selected.
In the example below, the SCHL 04, PERIOD 03 screen is a special day
schedule for performing inventory in the Manufacturing department. To
validate the schedule: On the + SPECIAL DAY(S) screen, select 11,
which is the number for the configured special day named INVENTORY.
The schedule is set up as follows:
Clearing the Schedule To clear the zone schedule for one or more time periods, follow these steps:
1. From the SCHEDULES screen, select CLEAR.
The CLEAR SCHEDULE screen displays.
Setting Up Remote Sources Controllers make decisions to turn a zone ON or OFF by monitoring the
status of control sources. NF2000/3000G3 controllers support up to four,
user-selectable control sources per zone. (See “Setting Up Zones” on
page 79). Each user-selectable control source can be any schedule, input,
zone, or remote source.
The remote source feature lets one controller share a control source from
another controller. For example, in Figure 8–4 on page 76 the controller on
Master Panel A can make zone control decisions based on the status of the
controller on Master Panel B’s schedule, input, zone, or even another
remote source. A common application of the remote source feature is the
sharing of an input. Other applications for the remote source feature include:
• Small numbers of controllers sharing one input for a lighting zone served
by multiple panels (for example, a factory department with a local
override)
• Small number of controllers sharing more than one input to control a zone
from multiple locations (for example, gymnasium lights with a switch at
each entrance)
• All controllers sharing a single input to control all zones (for example, a
contact closure from a security system or fire alarm)
• Many controllers sharing a single input to control selected zones (for
example, a cleaning crew switch in which half the lights come on)
• Control and annunciator panel that can control and show remote status of
selected zones from multiple controllers (for example, prisons)
NOTE: The Remote Source feature is available using Ethernet
communications only. The feature is not available for NF2000/3000G3
controllers that communicate solely via serial (RS-232 or RS-485)
communications.
Figure 8–4 on page 76 shows a simple example in which the remote source
feature is used to share the status of an input. In this example, a facility has
two parking lots, East Parking and West Parking. Circuits in Controller A’s
panel serve the East Parking lights, and circuits in Controller B’s panel serve
the West Parking lights. You can turn the lights in both parking lots ON and
OFF at the same time, using photocells as inputs. You can place a photocell
in the East Parking lot and wire it to an input in Controller A, and place a
second photocell in the West Parking lot and wire it to an input in Controller
B. But since both controllers are NF2000/3000G3 controllers, and since both
controllers communicate via Ethernet, you can save the time and expense of
installing two photocells, and instead use the remote source feature to
“share a photocell” by sharing the status of an input.
Figure 8–4: Remote source example
CONTROLLER A CONTROLLER B
(Subscriber) Controller B (Publisher)
publishes state
changes
ZONE 1 ZONE 2
Remote Ethernet Input 1
EAST WEST
Source 1
PARKING PARKING
LOT Controller A LOT
subscribes to the
state of Input 1
Photocell
Naming Remote Sources To assign or change remote source names, follow these steps:
1. From the REMOTE SOURCES screen, select the right-pointing selection
arrow.
The REMOTE SRC NAME screen displays.
2. To assign or change a remote source Name, use the Back and Next
keys to move to each desired character, and use the Plus and Minus
keys to change each character at the cursor location.
3. Move the cursor away from the characters to save the new name.
SETTING UP ZONES A zone is comprised of circuit breakers from one or more panelboards
connected to the controller. You can define up to 64 zones for each
controller at a location. Controller’s make the decision to turn a zone ON or
OFF by monitoring the status of control sources. A circuit breaker must be
assigned to a zone to respond to a control source.
Figure 8–5 on page 79 illustrates how control sources relate to a zone in the
controller.
Figure 8–5: Zone diagram
NOTE: The figure above uses all four possible control sources: zone,
schedule, input, or remote source. However, any control source combination
is possible. For example, you can use two inputs, one schedule, and one
remote source; or you can use one source and not assign the other three.
2. Select the Zone number for the zone you want to set up.
The Zone name (if one is assigned) displays.
2. To assign or change a zone name, use the Back and Next keys to move
to each desired character, and use the Plus and Minus keys to change
each character at the cursor location.
3. Move the cursor away from the characters to save the new name.
Viewing and Editing Circuit Breakers To view and edit circuit breakers, follow these steps:
1. From the ZONE BREAKERS screen, select VIEW/EDIT.
The VIEW/EDIT BRKRS. screen displays.
The Zone line displays the selected zone number and nametag, the Bus
line displays the selected bus number and nametag, and the circuit
breakers for the selected zone and control bus display.
NOTE: The Bkr line displays only when the cursor is over a circuit
breaker position.
2. Change the Bus number to show the zone members for that bus.
The circuit breakers assigned to the zone are underlined.
3. Use the Back and Next keys to position the cursor over a circuit breaker
number, and use the Plus or Minus keys to add or remove a circuit
breaker from zone membership.
The circuit breaker at the cursor position displays on the Bkr line.
NOTE: The circuit breaker numbering shown here is an example. The
displayed numbering sequence may be modified to match the panel (see
“Setting Up Circuit Breakers” on page 65).
Using Learn Mode to Add or Delete Circuit You can use the self-learning feature as an alternative method for assigning
Breakers from a Zone circuit breakers to a zone. “Learn” refers to the controller’s ability to
automatically add to or delete circuit breakers from a zone based on a user
manually toggling the circuit breaker handles.
NOTE: The controller learns which circuit breakers are to be added or
deleted by monitoring voltage changes at the circuit breaker load terminal.
As such, panelboards must be energized while creating zones.
Changing Circuit Breakers from Auto to To use the self-learning feature to add or delete circuit breakers from a zone,
Manual Mode the circuit breakers must be in MANUAL mode. The panelboard cover and
deadfront should be in place while using this feature.
NOTE: All panelboards that are assigned to a zone must have power.
OFF
ON
OFF
ON
Testing Circuit Breakers You can use the “Test” feature to verify circuit breakers assigned to a zone.
The Zone line displays the selected zone number and nametag.
3. Change Test State from OFF to ON or from ON to OFF to operate the
circuit breakers assigned to this zone.
NOTE: Circuit breakers will switch ON and OFF in response to changing
the test state. The circuit breakers will return to their original states upon
leaving this screen.
Clearing Circuit Breakers To clear circuit breakers from a zone, follow these steps:
1. From the ZONE BREAKERS screen, select CLEAR.
The CLEAR BREAKERS screen displays.
The Zone line displays the selected zone number and nametag.
2. To clear all circuit breakers from this zone, select the “Clear ALL
breakers assigned to this zone” screen path symbol (<), and press the
Plus key to exit the screen.
Assigning Control Sources NF2000G3 controllers support up to four control sources per zone. Each
user-selectable control source can be any schedule, any input, any zone, or
any remote source. The logic type you choose when setting up the zone
determines how the control sources are combined to control the zone.
3. From the Logic Type, select the logical operator that the controller will
use to combine sources in determining the zone state (ON or OFF). See
Table 8–26 for a description of each logic type.
4. Select up to four control sources for the zone. The sources can be inputs
(INPT), schedules (SCHL), zones (ZONE), or remote sources (REMT).
After selecting a control source type, you will need to select the source
number. The name of the control source (if configured) will appear next
to the control source. The screen should look similar to the screen below:
NOTE: You do not have to define all control source rows on the screen.
Undefined control sources are ignored.
5. Exit the ZONE SOURCES screen to save your changes.
Logic Configuration Additional configuration may be required when choosing LAST EVENT or
COMBO as the logic type for a zone. Follow these steps to access the
configuration screen:
1. From the ZONE SOURCES screen, select LAST EVENT or COMBO as
the logic type.
2. Move the cursor over the right facing arrow that appears next to the right
of the logic type selection. (Note: This arrow will not appear for AND or
OR logic type selections.)
3. Press the “+” button to proceed to the configuration screen and complete
the setup.
COMBO Logic Setup Boolean combination logic, or COMBO logic, allows different types of
Boolean operators to be used together to determine how the zone will
combine assigned sources. The controller provides a simple, sentence-type
programming screen for defining a logic expression for the zone. To
configure, select a Boolean operator and a comparison state for each of the
sources selected for the zone.
Operators
In the screen above, AND was selected as the operator used to combine the
first and second sources. Next to each source is a test condition that defines
when the state of the first source is considered to be TRUE. Together, the
source and the test condition form a Boolean statement. In this example,
INPUT 1 is TRUE when it is ON, and INPUT 2 is TRUE when it is OFF. You
can choose AND, OR, XOR, NAND, NOR, or XNOR as the Boolean
operator. Boolean statements are evaluated in order by pairs from top-to-
bottom.
The table below shows the behavior for each type of logic operator. For
example, the statement “INPUT 1 = ON” is FALSE whenever INPUT 1 is in
the OFF state and TRUE whenever INPUT 1 is in the ON state.
Table 8–27: Boolean Operators
AND OR
1st Statement 2nd Statement Result 1st Statement 2nd Statement Result
FALSE FALSE FALSE FALSE FALSE FALSE
FALSE TRUE FALSE FALSE TRUE TRUE
TRUE FALSE FALSE TRUE FALSE TRUE
TRUE TRUE TRUE TRUE TRUE TRUE
XOR NAND
1st Statement 2 nd
Statement Result 1st Statement 2nd Statement Result
FALSE FALSE FALSE FALSE FALSE TRUE
FALSE TRUE TRUE FALSE TRUE TRUE
TRUE FALSE TRUE TRUE FALSE TRUE
TRUE TRUE FALSE TRUE TRUE FALSE
NOR XNOR
st nd
1 Statement 2 Statement Result 1st Statement 2nd Statement Result
FALSE FALSE TRUE FALSE FALSE TRUE
FALSE TRUE FALSE FALSE TRUE FALSE
TRUE FALSE FALSE TRUE FALSE FALSE
TRUE TRUE FALSE TRUE TRUE TRUE
The result of the top-to-bottom logic evaluation is used to set the zone state.
The final line of the zone logic screen is used to define whether the zone will
be ON or OFF when the logic evaluation is TRUE. By selecting ZONE = ON,
the zone state will be ON whenever the logic evaluation result is TRUE. By
selecting ZONE = OFF, the zone state will be OFF whenever the logic
evaluation result is TRUE.
LAST EVENT Logic Setup LAST EVENT logic can be configured to determine how the zone will
respond to a change in the state of a control source. An important difference
between LAST EVENT and all of the other logic types is that the zone logic
state is only updated when a source changes state.
The Event column is used to describe which events can affect the zone.
Valid choice combinations are ON:OFF, ON:---, or ---: OFF. The --- choice
indicates that any transition to the opposite state is to be ignored. For
example, choose ON:--- to update the zone state when the source turns ON,
but do nothing when the source turns OFF.
The Response column is used to select the state that will be applied to the
zone when the corresponding event occurs. Choose either ON or OFF for
any event that is set in the Event column. Note: If an event is ignored (---),
then a corresponding Response choice will not be allowed. For example,
when Input 1 changes to ON, the zone state will be set to ON. When Input 1
changes to OFF, the zone state will not be affected.
Selecting the Zone Priority The Zone Priority setting determines how a circuit breaker responds if it is
included in more than one zone. For most zones the Zone Priority will remain
at the default setting of Normal ON.
When zones are set to the Normal ON priority level, a circuit breaker
belonging to more than one zone will be ON if any of the zones are ON. The
circuit breaker will only turn OFF when all of the zones are OFF.
If a zone is set to Priority OFF, any circuit breaker belonging to the Priority
OFF zone will be forced OFF whenever the zone is ON. Otherwise, the
circuit breaker will not be affected.
If a zone is set to Priority ON, any circuit breaker belonging to the Priority ON
zone will be forced ON whenever the zone is ON, even if it belongs to an
active Priority OFF zone. Otherwise, the circuit breaker will not be affected.
For example, you want to turn OFF a portion of the office lights in response
to a load-shed signal. (You are required to reduce your energy consumption
to avoid peak demand charges or in response to a directive from the utility
company.) Create a zone containing the non-essential lighting circuits and
set the zone priority to Priority OFF. Turning this zone ON via a contact
closure or communications command will force OFF the non-essential lights.
The ZONE line displays the previously selected zone and nametag.
2. Select the appropriate priority level:
x Level 0 — Normal ON: When the zone is ON, then any breaker
assigned to that zone is ON. If no zones are commanding a breaker
ON, then that breaker turns OFF.
x Level 1 — Priority OFF: When the zone is ON, then any breaker
assigned to that zone is forced OFF. The blink notice will not operate
in this mode.
x Level 2 — Priority ON: When the zone is ON, than any breaker
assigned to that zone is forced ON. If a breaker receives forced ON
and forced OFF commands at the same time, then the forced ON
command has priority. The blink notice, if set, will operate when
Priority ON is released.
SYNCHRONIZING INPUTS Synchronizing inputs allows you to associate an input with another input,
schedule, zone, or remote source. This lets you better coordinate and refine
how they work together in more complex lighting schemes. The input sync
feature has three main functions:
• Input sync —You can turn an input ON or OFF when an event occurs.
The event is the ON or OFF action of another input, schedule, zone, or
remote source. For example, you could sweep a wall switch OFF at night
when the input is synchronized with a schedule.
• Input Inhibit — You can disable or enable an input based on an event.
For example, you could inhibit a wall switch in a public area during the
day when it is synchronized with the schedule for that area.
• Timer Inhibit — If a timer is set up for the input, you can disable the input
timer based on an event. For example, disable the timer during the day,
but allow it to operate as a timed override at night.
In addition, the NF2000G3 and NF3000G3 controllers let you reverse the
ON/OFF action of the input in relation to the event. For example, the input
turns ON when a schedule turns OFF.
NOTE: All synchronization types have a NO SYNC synchronization method. If selected, the input is not synchronized with any synchronization source.
VIEWING STATUS This section explains how you can view status data of the various controller
functions.
From this screen, you can view the following status functions:
x Circuit breaker status
x Zone status
x Source status
x Communications status
x System status (including controller status and control bus status)
Viewing Circuit Breaker Status To view circuit breaker status, follow these steps:
1. From the STATUS MENU screen, select BREAKER.
The BREAKER STATUS screen displays.
From this screen, you can view the following circuit breaker status
functions:
x Circuit breaker status details
x Circuit breaker status by control bus
x Circuit breaker status by zone
Viewing Circuit Breaker Details To view detailed status of individual circuit breakers, follow these steps:
1. From the BREAKER STATUS screen, select DETAILS.
The BREAKER DETAILS screen displays. See Table 8–30 for
descriptions of the circuit breaker status options
Viewing Status By Control Bus To view circuit breaker status by control bus, follow the steps below:
1. From the BREAKER STATUS screen, select BY BUS.
The STATUS BY BUS screen displays.
Viewing Status By Zone To view circuit breaker status by zone, follow the steps below:
1. From the BREAKER STATUS screen, select BY ZONE.
The STATUS BY ZONE screen displays.
where circuit breakers are not present are blanked. For ACTUAL STATE
= ON, all circuit breakers that are not ON (OFF) are blanked.
NOTE: The breaker numbering shown here is an example. The
numbering sequence may be modified to match the panel. Also, only the
motorized poles are displayed on 2- and 3-pole breakers.
View Zone Status Details To view zone status details, follow the steps below:
1. From the ZONE STATUS screen, select DETAILS.
The ZONE DETAILS (1) screen displays.
The zone nametag, logic type, and four control sources for the zone are
displayed. See Table 8–32 for descriptions of the second screen of zone
status options.
View By Source To view zone status by control source, follow the steps below:
1. From the ZONE STATUS screen, select BY SOURCE.
The STATUS BY SOURCE screen displays.
The control source nametag, status, and zone membership value for the
control source is displayed. In the screen above, the remote source is a
member of four zones. If the control source was not a member of any
zones, NONE would appear where 04 is located. See Table 8–33 for
descriptions of the STATUS BY SOURCE screen options.
2. Select the control source from the following options:
x INPT (Input)
x SCHL (Schedule)
x ZONE
x REMT (Remote Source)
3. Select the control source number for the control source you chose in
Step 2.
4. Select VIEW SOURCE ZONES to view the zone information for each
zone the selected control source is a member.
The VIEW SOURCE ZONES screen displays.
View By Breaker To view zone status by circuit breaker, follow the steps below:
1. From the ZONE STATUS screen, select BY BREAKER.
The STATUS BY BRKR screen displays.
The control bus, circuit breaker number, actual circuit breaker state, the
direct breaker action, and the number of zones the breaker is a member
are displayed. If the circuit breaker was not a member of any zones,
NONE would appear where 02 is located. See Table 8–35 on page 97
for descriptions of the STATUS BY SOURCE screen options.
2. Select the BUS (control bus) number and the BKR (circuit breaker)
number.
3. Select VIEW BREAKER ZONES to view the zone information for each
zone the selected circuit breaker is a member.
The control bus, circuit breaker number, actual circuit breaker state, the
direct breaker action, zone assignment, zone status, override state, and
priority level for the circuit breaker and the zone it’s assigned to are
displayed. See Table 8–36 on page 97 for descriptions of the control
source options.
4. To view other zones the circuit breaker is a member, select a different
zone number.
Viewing Control Source Status To begin viewing the status of a control source, follow these steps:
1. From the STATUS MENU screen, select SOURCE.
The SOURCE STATUS screen displays.
Viewing Schedule Status The SCHEDULE STATUS screen lets you see at a glance which scheduled
periods and which special days are currently active. To view schedule
status, follow these steps:
1. From the STATUS MENU screen, select SCHEDULES.
The SCHEDULE STATUS screen displays.
Viewing Input Status The Input Status screen displays the actual status of inputs defined for the
selected controller.To view input status, follow these steps:
1. From the STATUS MENU screen, select SOURCE > INPUT > DETAILS.
The INPUT DETAILS screen displays.
NOTE: The displayed settings reflect the values you entered in the
ZONE INPUT screen in the section “Setting Up Inputs” on page 70.
2. Select the desired INPUT number.
The status for the zone’s input is displayed. Some options may not
appear, depending on the current settings for the selected zone.
NOTE: The status of all 64 inputs is available. Inputs 17–64 are used to
display virtual input status. The input object state and timer value lines
will display the actual real-time value of these variables. The Input Inhibit
line is only visible for physical inputs (inputs 1–16).
Viewing Remote Source Status The REMOTE SRC STATUS screen displays the actual status of remote
sources defined for the connected controller. To view remote source status,
follow these steps:
1. From the STATUS MENU screen, select REMOTE SOURCE.
The REMOTE SRC STATUS screen displays.
Viewing Communications Status The COMMS STATUS screen displays the actual status of communications.
To begin viewing communications status, do this step:
1. From the STATUS MENU screen, select COMMUNICATIONS.
The COMMS STATUS screen displays.
Viewing Serial Status To view serial communications status, follow these steps:
1. From the COMMS STATUS screen, select SERIAL STATUS.
The SERIAL STATUS screen displays. See Table 8–40 for descriptions
of the serial status options
Viewing Ethernet Status To view Ethernet communications status, follow these steps:
1. From the COMMS STATUS screen, select ETHERNET STATUS.
The ETHERNET STATUS screen displays. See Table 8–41 for
descriptions of the serial status options.
This screen displays the total number of messages sent by the master to
the sub-net, and the total number of errors.
2. Select the desired BUS (control bus) number.
The screen displays the number of good messages received, the number
of bus timeouts, and the number of LRC errors.
3. To clear messages for the selected control bus, highlight the CLR?
option, and change NO to YES. If you want to clear all messages for all
control buses, change NO to ALL.
NOTE: The CLR? option appears with Level 1 access only.
Viewing System Status To begin viewing controller and control bus system status, do as follows:
From the STATUS MENU screen, select SYSTEM.
The SYSTEM STATUS screen displays.
Viewing Control Bus Status To view control bus status, follow these steps:
1. From the SYSTEM STATUS screen, select CONTROL BUS.
The CTRL BUS STATUS screen displays.
2. Select the desired BUS (control bus) number (range is 0L, 0R, 1L, 1R ...
7L, 7R.)
The control bus Model Number and Firmware version is displayed. If the
selected bus is not present, these fields are blanked. Only currently
installed buses are displayed.
NOTE: The bus model type is displayed as catalog #, i.e. NF12SBR,
NF12SBL, NF18SBR, NF18SBL NF21SBR, NF21SBL, etc.
CONTROLLER TOOLS To access the TOOLS MENU screen, go to the MAIN MENU screen and
select TOOLS. The TOOLS MENU screen displays.
Overriding Zones Overrides can be enabled or disabled (released) to force the state of a zone
ON or OFF. For example, if a zone override is enabled and the override
state is set to ON, the zone will be forced ON. It remains ON until either the
override is disabled, the Timer Value (if used) expires, or the zone is
overridden OFF.
NOTE: If the controller is in HALT mode when you attempt to execute a zone
override, no circuit breaker switching will occur. This is because the HALT
command freezes the circuit breakers in their current position. When the
controller is put back into RUN mode, the circuit breakers in the zone will
switch.
In the screen above, the “Enable” option is set to YES, and the Override
Type (override state) is set to ON, enabling an override and forcing
Zone 6 ON for a duration of five hours. The Timer Value indicates that
2 hours, 22 minutes, and 45 seconds remain. See Table 8–44
on page 104 for descriptions of the zone override options.
2. Select the desired ZONE number.
3. Select the Override Type as ON or OFF.
4. Select the Duration time, if desired.
Use a time setting of zero for a continuous override.
5. For the Enable option, change NO to YES to enable the override timer.
The timer is re-started whenever Enable changes from NO to YES. The
Enable option automatically changes back to NO when the timer expires.
Selecting Direct Breaker Control Direct circuit breaker control is used as a temporary one-time override. It allows
you to test an individual circuit breaker, or temporarily change the circuit breaker
state until the next control event initiates based on the zone’s logic.
1. From the TOOLS MENU screen, select DIRECT BREAKER CONTROL.
The DIRECT BRKR CTRL screen displays.
The circuit breakers for the first control bus is displayed by default.
Underlined circuit breaker numbers indicate circuit breakers that are ON.
2. Select the desired BUS (control bus) number.
The circuit breakers for the selected control bus appear.
3. Select a circuit breaker number.
The BKR (breaker) line displays.
4. Select the number of the circuit breaker you want to control, then press
the Plus key or Minus key to command ON or OFF the circuit breaker.
The selected circuit breaker is commanded ON or OFF, depending on its
previous state.
Selecting the Operating Mode There are two operating modes: RUN and HALT. In RUN mode (the default),
all circuit breaker programs that have been set up operate automatically. In
HALT mode, system operation is stopped.
NOTE: The controller’s operating mode displays on the Main screen.
2. Highlight the Operating Mode, then change between the RUN and HALT
modes.
The screen displays the current codes for each of the three levels. The
screen above is the default ACCESS CODES screen.
NOTE: If at least one of the access level codes have been set, the
Access Login is set to ENABLED. If none of the codes have been set (all
are set to 0000), the Access Login is set to DISABLED, allowing
unprotected access to all controller screens and functions.
2. Use the Back and Next keys to move the cursor over the desired digits,
then use the Plus and Minus keys to change each number (0–9) at the
cursor position.
3. Save the new codes by moving the cursor away from the password area.
NOTE: Be sure to record your access code. You will not be able to access
the controller without this code.
Entering a Controller Name To enter a descriptive name for the controller, follow these steps:
1. From the TOOLS MENU screen, select CONTROLLER NAME.
The CONTROLLER NAME screen displays.
2. To assign or change a controller name, use the Back and Next keys to
move the cursor over the desired character positions, then use the Plus
and Minus keys to change each character.
3. Move the cursor away from the Name field to save the controller name.
Using the Service Tools To begin clearing the controller memory or viewing controller subscribers, do
as follows:
From the TOOLS MENU screen, select SERVICE TOOLS.
The SERVICE TOOLS screen displays.
Clearing the Memory To clear the controller memory and restore all factory defaults, follow these
steps:
1. From the SERVICE TOOLS MENU screen, select CLEAR MEMORY.
The CLEAR MEMORY screen displays.
NOTE: As stated in this screen, clearing the memory will delete ALL
programming and setup information, except for communications setup
parameters (see “Setting Up Communication Parameters” on page 52).
2. To clear the controller memory, highlight the first choice, and change NO
to YES. The default value for both choices presented is NO.
3. To confirm the clearing of memory, highlight the Clear memory NOW
screen path symbol (<), and press the Plus key to exit the screen.
Viewing Subscribers The controller lets you view subscribers. This means that you can view the
network address, the remote source number, and the mapped local control
source of any controller connecting to your controller via Ethernet
communications.
The screen indicates that there are currently 28 subscribers. The second
subscriber, whose information is currently displayed, has an IP address
of 106.203.010.005, and its first remote source is your controller’s
INPT 01.
NOTE: If there are no subscribers, a message displays saying, “No
Subscriptions Active.”
2. To view a different IP Addr (IP address), select the current IP Addr, then
press the Plus key or Minus key.
3. To view a different Remote Source, select the current Remote Source
number, then press the Plus key or Minus key.
CHAPTER 9 —LOGGING
INTRODUCTION Logs are files stored in the nonvolatile memory of the controller. When an
event occurs, including an alarm event, it is written to the event log. The
event log can store up to 512 event records. When the event log is full and a
new event occurs, the oldest event is deleted to make room for the new
entry. This circular recording method is more commonly known as FIFO:
when space is needed for a new record, the First item In is the First item
Out.
NOTE: Viewing event log information and configuring alarm events is
possible only with PCS software. For more information, see the PCS Help
file.
EVENT LOG The event log records the following status changes:
• Schedule Object State (1–16)
• Input Object State (1–64)
• Zone State (1–64)
• Remote Source State (1–32)
• Remote Source Time-out (1–32)
• Zone Override Enable (1–64)
• Zone Override Type (1–64)
• Override Time-out Enable (1–64)
• Timer Inhibit (1–64)
• Input Inhibit (1–64)
• Latched Input State (1–64)
• Non-responding Breaker State
• Breaker Present
• Bus Present
• Communications Time-out
• Halt Mode
• Front Panel Access
• Power Outage
The controller does not need to be configured to record the event conditions
above, but the event log is viewable only with PCS software. For more
information about the event log, refer to the PCS Help file.
ALARM LOGS Using PCS software, events can be configured as alarm points. Additionally,
the NF3000G3 controller can be configured to notify a user via E-mail as
soon as an alarm occurs. There are two different types of alarm points:
• Change of value—Change of value alarm points reflect a change of
status to an undesired condition. For example, a user connects the status
contact from an external device to an input. The input is operating
normally when it is OFF. The alarm point is set so that whenever the input
is ON, an alarm event occurs.
• Intrinsic—Intrinsic alarm points are alarm events that are typically
considered abnormal operating behavior, so they do not require special
setup. For example, a user does not have to define the normal and
abnormal states of a non-responding circuit breaker. In order to set up the
alarm, the user only has to enable non-responding circuit breaker
alarming.
Table 9–1: Alarm Point Types
Point Type Event
• Input Object Status (1–64)
Change of Value
• Zone Object Status (1–64)
• Power Loss
• Non-responding Circuit Breaker
• Circuit Breaker Run-time
Intrinsic
• Subnet Communications Loss
• RS485 Communication Loss
• Ethernet Communications Loss
INTRODUCTION The NF3000G3 controller has embedded web pages, making controller
information available via the Web. The web pages are accessed by typing
the controller’s IP address into the Address text box of a web browser and
then pressing ENTER. There are five embedded web pages:
• Home
• Monitoring
• Control
• Diagnostics
• Maintenance
• Setup
When the IP address is entered into a web browser, the user is prompted to
enter a user name and password. The username is “admin” and the default
password is “admin”. The password can be changed by following the steps
in “Password Administration” on page 119.
NOTE: An Ethernet connection is required to view the embedded web pages
(see “Setting Up Communication Parameters” on page 52 to set up Ethernet
communications).
HOME PAGE The Home page is the first page displayed when the controller’s IP address
is entered into a web browser.
Figure 10–1: Sample Home Page
Navigation Bar
From the Home page, you can use the navigation bar to access the
Monitoring, Control, Diagnostics, Maintenance, and Setup pages. If you
want to return to the Home page, click the Home link above the navigation
bar. To logout when you are finished, click the Logout link above the
navigation bar.
MONITORING PAGE The Monitoring page contains detailed circuit breaker, zone, input, schedule
and remote source information for each panelboard. The information
includes the panelboard name, the panelboard layout, circuit breaker
numbers, circuit breaker names, and whether a circuit breaker is ON, OFF,
or tripped. In addition to text, the circuit breaker status is indicated using
color-coded squares.
• White square = ON
• Green square = OFF
• Red square = Tripped or Non-responding
Detailed Breaker Information Detailed circuit breaker information is available by moving the mouse pointer
over a Breaker number (see Figure 10–3).
Figure 10–3: Detailed Breaker Information
Detailed Zone Information Zone summary information is available to show zone number, name, and
status.
Figure 10–4: Detailed Zone Information
or...
1. Expand the “Zone Summary” menu under “Sources”.
2. Click the appropriate zone name.
Detailed Input Information Input summary information is available to show input number, name, and
status.
Figure 10–5: Detailed Input Information
Detail Screen
or...
1. Expand the “Input Summary” menu under “Sources”.
2. Expand appropriate “Inputs” menu
3. Click the input name.
Detailed Schedule Information Schedule summary information is available to show the schedule number,
name, and status.
Figure 10–6: Detailed Schedule Information
Detail Screen
or...
1. Expand the appropriate “Schedule Summary” menu under “Sources”.
2. Click the schedule name.
Detailed Remote Source Information Remote Source summary information is available to show remote source
number, name, and status.
Figure 10–7: Detailed Remote Source Information
Click Remote
Source number
Expand the “Remote
Summary” menu and click
the schedule name
Detail Screen
or...
1. Expand the appropriate “Remote Summary” menu under “Sources”.
2. Click the remote source name.
Control Page Pages under the Control tab provide much of the same information for zones
and inputs as the “Monitoring” tab. The “Control” tab also provides you with
the option to command zone overrides ON or OFF, release zone overrides
or turn inputs ON or OFF.
Figure 10–8: Control Web Pages (Zone and Input)
DIAGNOSTICS PAGE The Diagnostics page contains two different sets of information. The first set
is a panelboard summary, which displays the panelboard address, the
control bus names, the current control bus operating state, the control bus
model number, and the control bus firmware version (see Figure 10–9). The
second set is a controller summary, and it is viewed by clicking the
“Controller Summary” link to the left of the page. This summary includes
information about the controller, such as the model number, firmware
version, the current operating environment, the time clock, and
communications (see Figure 10–10).
Figure 10–9: Sample Panelboard Summary Page
MAINTENANCE PAGE The Maintenance page contains product support and technical support
information.
Figure 10–11: Maintenance Page
SETUP PAGE The Setup page allows you to remotely access a physical controller via a
simulated controller. Buttons clicked on the simulation work just like the
corresponding buttons on the physical controller. If the screen simulation
does not refresh after clicking a button, press the Refresh button.
NOTE: As you use the simulated controller, the physical controller screen
updates with each mouse click. For example, if you click to view the zone
status of a particular zone, the physical controller’s screen will update to
display the zone status.
Password Administration By clicking the Password Administration link to the left of the page, you can
change the password used to login to view the controller’s web pages. To
change the password, follow these steps:
1. Click the Password Administration link on the Setup page.
Password Administration opens (see Figure 10–13).
2. Click in the Old Password text box, then type your old password.
3. Click in the New Password text box, then type your new password.
4. Click in the Confirm New Password text box, then type your new
password again.
5. Click the Update button.
The text “Password Change Successful” will appear next to the User
Name text box if the update was successful.
APPENDIX A — TROUBLESHOOTING
TROUBLESHOOTING THE Use the following table if you need to troubleshoot the NF2000/3000 G3
CONTROLLER controller:
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• This equipment must be installed and serviced only by qualified electrical
personnel.
• Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E.
• Carefully inspect the work area for tools and objects that may have been
left inside the equipment.
• Use caution while removing or installing panels so that they do not
extend into the energized bus; avoid handling the panels, which could
cause personal injury.
Wiring error. Verify wiring of inputs with respect to the external switching device and its pilot
light. An LED pilot light must be wired observing the proper polarity. Refer to
Pilot light on switch Chapter 5—Input Wiring for more information.
connected to input The total draw of all devices connected to all status feedback terminals must not
does not illuminate. exceed 60 mA. The status feedback power source is internally protected and will
Excessive current draw.
shut down if this limit is exceeded. A status indicator LED for this source is
located in the upper-left corner of the wiring terminal compartment. Refer to
Chapter 5—Input Wiring for more information.
Barrier kit
Power
Supply
Controller
1 2 3 4 5 6 7 8
Control
Circuit bus
breakers
Panelboard
Control Bus The control buses provide control and data monitoring for POWERLINK G3
remotely operated circuit breakers and are connected to the POWERLINK
G3 power supply and controller. Installed control buses will not interfere with
the installation of standard circuit breakers into the panelboard.
Figure B–2: Control Buses
Remotely Operated Circuit Breakers POWERLINK G3 Remotely Operated Circuit Breakers provide the same
overcurrent protection as standard circuit breakers, and have an integral
operator that can remotely switch the circuit breaker ON and OFF. The
circuit breaker works with the POWERLINK G3 controller, power supply, and
control buses to provide a remote power switching system in a panelboard.
Power Supply The POWERLINK G3 Power Supply provides power to the POWERLINK G3
system.
Figure B–4: Power Supply CL1
CL2
Part numbers:
NF120PSG3
NF240PSG3
NF277PSG3
NF120PSG3L
NF240PSG3L
NF277PSG3L
Barrier Kit If external control wiring is used, a Class 2 barrier is recommended. Two
types of barrier kits (shown below) are available: standard and fixed. The
standard barrier kit ships with the controller, while the fixed barrier kit is
optional.
The fixed barrier kit provides an expanded wiring compartment and fittings
for a wider range of barrier types. A piece of corrugated plastic conduit is
included with the kit.
Figure B–6: Class 2 Barrier Kits
Slave Address Selector The slave address selector is used to set an address for a slave panelboard
in a POWERLINK G3 subnetwork. A slave panelboard can have an address
setting from 0–7.
Figure B–7: Slave Address Selector
Slave Bus Connect Harness The slave bus connect harness (NF2HG3) is used to connect a right control
bus to the slave address selector on the left control bus so that the right
control bus is able to communicate with the rest of the subnetwork
components. The tie wrap on the cable can be removed if the cable is not at
the required length.
Figure B–8: Slave Bus Connect Harness
CONTROLLER SPECIFICATIONS The following sections list the specifications for the controller:
Table B–1 Controller Specifications
Inputs independently configurable dry-contact inputs
• 2-wire maintained N.O.
• 2-wire maintained N.C.
• 2-wire maintained toggle
Input Types • 2-wire momentary pushbutton
• 2-wire momentary timed ON
• 2-wire momentary delayed OFF
• 3-wire dual momentary
Input Timer 1 second to 18 hours
• 24 Vdc (60mA maximum load for all outputs
Status Output combined)
• available for 2-wire input types only
Auxiliary Power Supply 24 Vdc (100mA maximum current)
COM 1 (four methods of connection):
• RS-485 (2-wire MODBUS ASCII/RTU) inside
terminal compartment
• RS-485 (2-wire DMX512) inside terminal
compartment (see“Using a G3 Controller with
DMX512 Systems” on page 131)
Communication Interface • RS-232 (MODBUS ASCII/RTU) inside terminal
compartment
• RS-232 (MODBUS ASCII/RTU) on front panel
COM 2:
• 10 Base-T Ethernet (Modbus TCP/IP) inside
terminal compartment
• No blink (default)
• Single blink (2–30 minutes)
• Dual blink (1st blink: 2–30 minutes; 2nd blink: 1
Circuit Breaker Blink Notice minute)
• Delay with no blink (2–30 minutes)
• Pulse duration (1-10 seconds)
• Pulse repeat (1-240 minutes)
Circuit Breaker Stagger Delay 0.10 second (default) to 1 second
Zones are configured for logical operation.
System Logic
• AND, OR, LAST EVENT
• Inputs (removable Phoenix): #24–18AWG
• Auxiliary Power (removable Phoenix): #24–
18AWG
Terminals
• Network (removable Phoenix): #24–18AWG
• Front Panel: RJ-11
• Ethernet: RJ-45
• Operating Temperature: –5°C to +65°C (internal
panelboard temperature)
Environmental Standards
• Storage Temperature: –20°C to 85°C
• Operating Humidity: 5% to 95%
Standards UL Listed 916 Energy Management Equipment
ESD Immunity IEC 1000, Level 4
RF Susceptibility IEC 1000, Level 3
Electrical Fast Transient
IEC 1000, Level 3
Susceptibility
Electrical Surge Susceptibility –
IEC 1000, Level 4
power line
Electrical Surge Susceptibility –
IEC 1000, Level 3
data line
SETTING UP COMMUNICATIONS Follow the steps below to set up communication parameters when using a
PARAMETERS controller with DMX512.
1. From the CONTROLLER MENU screen, select COMMUNICATIONS.
The COMMUNICATIONS screen displays.
3. Select the DMX512 option under MODE. The controller screen will
automatically change to show setup fields for the DMX512 mode.
Enter in the desired starting slot and low and high thresholds.
Table C–1 on page 132 shows the default threshold settings for the
DMX512 mode.
CONFIGURATION WHEN USING The minimal required configuration is to assign desired breakers to zones.
DMX512 This is all that needs to be done in many instances when using DMX512. All
normal controller functions and logical capabilities continue to be available
when the DMX512 mode is selected. Combining DMX512 with controller
features, such as local inputs or schedules, may be desired in some
applications.
NOTE: The default input type is set to Maintained Normally Open. Inputs 1–
16, when configured for Maintained Normally Open or Normally Closed
contact, will synchronize to current contact state when the controller is
powered up. This behavior may or may not be desired when using DMX512,
especially where no contacts will be connected to an input. To disable power
up synchronization, it is recommended that the input configuration be
changed to Momentary Toggle.
DMX512 RELATIONSHIP TO INPUTS The controller responds to 64 contiguous DMX512 slots. These slots
correspond to inputs 1 – 64 in the controller. When a DMX512 slot increases
beyond the high threshold, then the corresponding input will change to ON.
When a DMX512 slot decreases below the low threshold, then the
corresponding input will change to OFF. DMX512 changes interact with
input changes from other sources on a last-event basis.
DMX512 RELATIONSHIP TO ZONES Zones that are configured to respond to an input will respond to the
corresponding DMX512 slot. By default on all controllers, Zone 1 is mapped
to Input 1, etc. The zone to input relationship can be reconfigured on
NF2000/3000G3 controllers.
DMX512 RELATIONSHIP TO COMMS The comms loss feature is available when using the DMX512 mode. Unlike
LOSS FEATURE the standard mode behavior, where an override that was triggered by a data
loss will remain set when data is restored, overrides will be released when
data resumes when in the DMX512 mode. The following table summarizes
the differences in behavior:
Table C–2: DMX512 with Comms Loss feature
Loss Behavior Resumption Behavior
Default Action Standard DMX Standard DMX
No change to Override
ON Override set to ON (Same)
override state. released.
No change to Override
OFF Override set to OFF (Same)
override state. released.
Override set to current No change to Override
LAST STATE (Same)
state, ON or OFF override state. released.
No change to override No change to Override
NO ACTION (Same)
state override state. released.
No change to Override
RUN Override released (Same)
override state. released.
BLINK NOTICE DMX512 mode allows blink notice to occur on circuits when they are
configured for blink notice and are commanded OFF. See “Blink Notice” on
page 66
NOTE: Breakers should not be configured for blink notice if blink notice is
not desired.
INTRODUCTION
The BACnet protocol allows Powerlink panels to be easily integrated into a
BAS employing this open communication standard without the need for
communication bridges or gateways.
Capability for BACnet communications is provided in accordance with
ANSI/ASHRAE Standard 135-2004: "A Data Communication Protocol for
Building Automation and Control Networks".
FEATURES
BACnet Classification
Each device is classified as a BACnet Application Specific Controller (B-ASC).
Firmware Modifications
Powerlink G3 controllers must have the appropriate firmware levels installed
for the BACnet features to function. See the table below for the appropriate
controller firmware versions.
Table 1: Controller Firmware Versions
Controller Program Module
NF2000G3 v5.22 or greater
NF3000G3 v5.22 or greater
NF3000G3C v5.62 or greater
BACnet Communications
The Powerlink controller models listed in the table below provide native
BACnet communication capability. They can be integrated into a BACnet
system in one of two ways:
• Ethernet (BACnet/IP)
• RS-485 (MS/TP)
Table 2: BACnet Communication Capabilities
Controller Model Ethernet (BACnet/IP) RS-485 (MS/TP)
NF2000G3 Yes Yes
NF3000G3 Yes Yes
NF3000G3C Yes No*
Device Management-Dynamic Object Binding-B The B device provides address Who-Has No Yes
(DM-DOB-B) information about its objects upon
I-Have Yes No
request.
Device Management-DeviceCommunicationControl-B The B device responds to DeviceCommunicationControl No Yes
(DM-DCC-B) communication control exercised by the
A device. (See Note 3 for password
required.)
Device Management-TimeSynchronization-B The B device interprets time TimeSynchronization No Yes
(DM-TS-B) synchronization messages from the A
device.
Device Management-UTCTimeSynchronization-B The B device interprets UTC time UTCTimeSynchronization No Yes
(DM-UTC-B) synchronization messages from the A
device.
Device Management-ReinitializeDevice-B The B device performs reinitialization ReinitializeDevice No Yes
(DM-RD-B) requests from the A device. (See Notes
1 and 2 for a description of the
WARMSTART and COLDSTART device
states.)
1. WARMSTART means to reboot the device and start over, retaining all data and programs that would normally be retained during a brief power outage. See
Note 3 for password required.
2. COLDSTART means to perform a ‘clear memory’ function on the device, setting applicable parameters back to factory default values. If front panel security is
enabled, the password required is the front panel Level 1 access code. If security is disabled, the required password is ‘0000’.
3. If front panel security is enabled, the password required is any valid front panel access code (Level 1, 2, or 3). If security is disabled, the required password is
‘0000’.
BACnet/IP Screen
This screen allows configuration of communication parameters for BACnet/IP.
The factory default setting for BACnet/IP is NO (disabled). This setting must be
changed to YES (enabled) in order for BACnet/IP communications to function.
NOTE: Selecting YES (enabled) displays the BACnet > screen link. Selecting
NO (disabled) will hide the BACnet > screen link.
Figure 1: BACnet/IP Screen
UDP Port 0 – 65535 The UDP network port that the device will use for B/IP communications.
Default value: 47808 (BAC0 hex)
BBMD IP Any valid IP address The IP address of the BBMD to which this device will register itself as a ‘foreign device’.
Default value: 000.000.000.000
BBMD Time to Live 0 – 65535 The time interval in seconds at which the device will renew its ‘foreign device’ subscription
with the BBMD.
Default value: 300
* Default value
• Control Enabled: BACnet clients may control any commandable object in the
controller (e.g., Input Control, Zone Control, or Breaker Control). This feature
determines if the BACnet control objects associated with the device can be controlled
directly via the BACnet network.
Access Level
The BACNET OBJECTS screen is assigned Level 3 access. The release
command requires Level 2 access.
2. Scroll to Mode and select BACnet MS/TP. The BACnet > screen link will
appear below Mode.
3. Set the desired serial address of the controller.
NOTE: Each device operates as a master node on a single MS/TP network
(device address 0-127).
4. Set the desired baud rate. Supported baud rates for MS/TP are 9600,
19200, 38400, and 76800. Refer to the "Maximum Communications Cable
Distances table in "Chapter 6—Communications Wiring".
5. For additional communication settings, select the BACnet > screen link to
navigate to the BACNET COMMS screen.
Figure 6: BACnet Comms Screen
Refer to the table “BACnet Status Screen Parameters” for more information
when verifying the status of BACnet communications. Select the BACnet
Objects > screen link to view the status of individual BACnet objects. Refer to
the "Overview of BACnet Screens" and "Objects" sections for more information
on BACnet object screen parameters and values.
CONTROLLER OPERATION
Internal Commands
The controller writes to the object’s priority array (always at priority 10) upon
any internal command to update the object’s status (non-BACnet operations).
This includes the events listed in the table below.
Present_Value
All internal commands written to the priority array are arbitrated along with
external commands from BACnet clients to determine the object’s present
value.
Relinquish Default
The controller takes the following action if all 16 levels of the priority array
contain the NULL value.
Table 13: Priority Array Relinquish Defaults
Object Relinquish Default Action
Input Control 3 Turn input Off, allow optional blink notice
Breaker Control 3 Turn breaker Off, allow optional blink notice
Zone Control 3 Release zone override
OBJECTS
BACnet Status and Control Objects
Table 14: Powerlink G3 Supported Status and Control Objects
Description Type Functionality
Device (1)
C. Analog Value Object Type 1. Dynamically creatable using the CreateObject service – NO.
2. Dynamically deletable using the DeleteObject service – NO.
3. Optional properties supported – Description.
4. Properties that are writable where not otherwise required by this standard – NONE.
5. Proprietary properties – NONE.
6. Property range restrictions – NONE
D. Multi-state Value Object Type 1. Dynamically creatable using the CreateObject service – NO.
2. Dynamically deletable using the DeleteObject service – NO.
3. Optional properties supported – Description, Reliability (Zone Control), State_Text, Priority_Array,
Relinquish_Default.
4. Properties that are writable where not otherwise required by this standard – Present_Value.
5. Proprietary properties – NONE.
6. Property range restrictions – Present_Value: 1 – 4 (Input Control), 1 – 3 (Zone Control).
E. Multi-state Output Object Type 1. Dynamically creatable using the CreateObject service – NO.
2. Dynamically deletable using the DeleteObject service – NO.
3. Optional properties supported – Description, Device_Type, Reliability, State_Text.
4. Properties that are writable where not otherwise required by this standard – NONE.
5. Proprietary properties – NONE.
6. Property range restrictions – Present_Value: 1 – 3 (Breaker Control).
Data Link Layer Options (X) BACnet IP, (Annex J)
(X) BACnet IP, (Annex J), Foreign Device
(_) ISO 8802-3, Ethernet (Clause 7)
(_) ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)
(_) ANSI/ATA 878.1, EIA-485 ARCNET (Clause 8), baud rate(s) ____________
(X)¹ MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400, 76800
(_) MS/TP slave (Clause 9), baud rate(s):
(_) Point-To-Point, EIA 232 (Clause 10), baud rate(s):
(_) Point-To-Point, modem, (Clause 10), baud rate(s):
(_) LonTalk, (Clause 11), medium: __________
(_) Other:
Device Address Binding Is static device binding supported?
This is currently necessary for two-way communication with MS/TP slaves and certain other devices.
(_) Yes (X) No
Networking Options (_) Router, Clause 6 - List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc.
(_) Annex H, BACnet Tunneling Router over IP
(_) BACnet/IP Broadcast Management Device (BBMD)
Does the BBMD support registrations by Foreign Devices (_) Yes (_) No
Character Sets Supported Indicating support for multiple character sets does not imply that they can all be supported simultaneously.
(X) ANSI X3.4
(_) ISO 10646 (UCS-2)
(_) IBM™/Microsoft™ DBCS
(_) ISO 10646 (UCS-4)
(_) ISO 8859-1
(_) JIS C 6226
Communication Gateway If this product is a communication gateway, describe the types of non-BACnet equipment/networks(s) that
the gateway supports: N/A.
(X) = supports; (_) = does not support
¹ NF2000G3 and NF3000G3 only; the NF3000G3C serial port is dedicated to C-Bus communications.
² Version shown or greater
INDEX
DMX512, relationship to zones 132 momentary ON 20 maintained normally open with blink 20
DMX512, using a G3 controller with 131 momentary toggle 20 manual mode of circuit breakers 83
English
English
safety precautions 11
description 53 description 53
saving changes 46
photo sensor 24 setting 53
schedule status 98
plus key 8 subnet network 26
schedules
poles, circuit breaker 92 subscriber 107
clearing of 75
port sunrise and sunset 56
normal days 72
ethernet 30 sweep switch, blink type options 67, 69
of zones 72
RS-232 30 sweep switch, circuit breaker timing/pulse
special days 74
RS-485 30 duration 69
sunrise and sunset 73
serial 25, 33 sweep switch, example 68
screen
power sweep switch, pulse repeat 69
LCD 43
auxiliary 17 Sweep Switch, using controllers with 67
selecting a 44
LED 9 switch
screens 47
source, auxiliary 9 wall 23
selecting
status 9 switching
from a list 45
power supply 16, 126 remote 125
operating mode 105
auxiliary 129 system
screens 44
precautions, safety 11 logic 129
Sentry, see also "sweep switch" 67
programming system components 125
serial cable 30
a new system 51 system programming
serial status 100
Pulse OFF, application 68 flowchart 51
service tools 107
Pulse OFF, blink type 124 system status 102
setting
Pulse OFF, effect on circuit voltage 67
access codes 106 T
Pulse OFF, using with sweep switch 67
baud rate 52, 131
Pulse repeat 129 TCP/IP 25
circuit breaker timing 69
Pulse Repeat, application 68 temperature
clock 56
Pulse Repeat, effect on circuit voltage 67 operating 129
time/date 55
Pulse Repeat, options 69 storage 129
zone inputs 70
Pulse Repeat, using with sweep switch 67 terminal
zones 79
bi-directional input/output 18
Q shield, grounding the 34
output 17
shielding 34
quick start guide 13 terminals 129
single contact inputs 19
auxiliary power 9
R slave address selector 128
bi-directional 17
slave bus connect harness 128
remote source 76 class 2 17
source menu 47
example of 76 communications 9
special days
name 78 input 9, 17
configuring 60
offline options 78 testing
scheduling 74
options 77 of circuit breakers 83
types of 61
setting up 76–77 specifications
tie wrap 41
remote source status 99 tie wrap, controller 40
of controller 129
remote sources time zone
standards
naming of 78 reference 57
environmental 129
remote switching 26, 125 UL Listing 129
time/date, setting 56
remotely operated circuit breakers 125 time-out feature 46
status
removing the controller 16 timer
communications 100
repeater, line 30 5-minute 50
control busses 103
reset button 8 blink 92
control source 97
RS-232 30, 36 controller 103
delay 54
communications port 8 input 71
ethernet 101
controller serial connections 36 override 104
input 98
maximum length of wiring 36 timing
of circuit breakers 91
serial communications 36 of circuit breakers 69
of system 102
RS-232/485 converter 32 tools
of zones 94
RS-485 30, 34 remote source 99
controller 103
alternate wiring 35 service 107
schedule 98
communications 30 tools menu 48
serial 100
RTU 25 sub-net communications 102
RTU/ASCII 53 U
system 102
run mode 105 viewing 91 UL Listing 129
Rx and Tx LEDs 46 status menu 47 V
status output 20–21, 71, 129
status power LED 9 values
changing 44
view subscribers 107
English
viewing
of status 91
W
wall switch 23
wire
size 34
specifications 34
wiring compartment
cover 8
wiring external device 22
Z
zone
overriding 103–104
zone input options 71
zone menu 47
zone status 94
by breaker 96
by source 95
details of 94
zones
adding or deleting circuit breakers to 82
assigning circuit breakers to 80
naming of 80
setting up 79
status of 94
Schneider Electric USA 295 Tech Park Drive Electrical equipment should be serviced only by qualified personnel. No responsibility
LaVergne, TN 37086 is assumed by Schneider Electric for any consequences arising out of the use of this
1-888-Square D (1-888-778-2733) material. This document is not intended as an instruction manual for untrained
www.squaredlightingcontrol.com persons.
Bulletin No. 63249-401-205/A5 dated 03/2008 replaces 63249-401-205/A4
All Rights Reserved
80043-842-01
Addendum Anexo Annexe 08/2018
All trademarks are the property of Todas las marcas comerciales son propiedad de Toutes les marques commerciales sont la propriété de
Schneider Electric SE, its subsidiaries, and Schneider Electric SE, sus filiales y compañías Schneider Electric SE, ses filiales et compagnies
affiliated companies. afiliadas. affiliées.
Importado en México por:
Schneider Electric USA, Inc. Schneider Electric México, S.A. de C.V. Schneider Electric Canada, Inc.
800 Federal Street Av. Ejercito Nacional No. 904 5985 McLaughlin Road
Andover, MA 01810 USA Col. Palmas, Polanco 11560 México, D.F. Mississauga, ON L5R 1B8 Canada
888-778-2733 55-5804-5000 800-565-6699
www.schneider-electric.us www.schneider-electric.com.mx www.schneider-electric.ca
© 2018 Schneider Electric All Rights Reserved / Reservados todos los derechos / Tous droits réservés