Wire Size Specifications 0318

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Manufacturer and leading provider

of optimized electrical connection solutions

Wire Size Specifications


Table: UL486E
Assigned maximum
Amperage versus Wire Size
Wire size
ampere rating
Table: UL486E – Assigned maximum ampere
AWG or
mm2 A rating versus wire size for copper conductors.
kcmil
Values are for not more than three conductors
30 0.05 0.5
28 0.08 0.8
in raceway or cable (reference: National
26 0.13 1 Electrical Code, ANSI/NFPA 70-1999).
24 0.20 2
22 0.32 3
20 0.52 5
18 0.82 7
16 1.3 10 Wire Size and Cross-sectional Area
14 2.1 15
12 3.3 20 Approximate relationship between conductors
10 5.3 30 of cross-sectional areas in mm2 and AWG
8 8.4 50 sizes as used in North America (reference: IEC
6 13.3 65 998-1).
4 21.2 85
3 26.6 100
2 33.6 115
Cross-sectional area
1 42.4 130 Wire size AWG
mm3
1/0 53.5 150
0.5 20
2/0 67.4 175
0.75 18
3/0 85.0 200
1.0 -
4/0 107 230
1.5 16
250 127 255
2.5 14
300 152 285
4 12
350 177 310
6 10
400 203 335
10 8
500 253 380
16 6
600 304 420
25 4
700 355 460
35 2
750 380 475
800 405 490
900 456 520
1000 507 545
1250 633 590
1500 760 625
1750 887 650
2000 1010 665

WECO Electrical Connectors Inc. www.wecoconnectors.com | [email protected]


18050 Trans-Canada Highway Phone: 514 694-9136
Kirkland, Quebec, H9J 4A1 Fax: 514 694-0956
Canada Toll Free: 1 800 724-2928 (US and Canada)
Manufacturer and leading provider
of optimized electrical connection solutions

Definitions

Unprepared Conductor:

A conductor which has been cut and the insulation of which has been removed for insertion into
a terminal. The conductor end is bare.

Prepared Conductor:

A conductor, the strands of which are soldered or tinned, or the end of which is fitted with a
cable lug, eyelet, quick-connect, ring terminal, spade terminal, or similar component, prior to
insertion into the terminal.

Factory Wiring Terminal:

A terminal intended in the end application to be connected under controlled conditions, usually
at a manufacturer’s location. Such terminations shall use prepared or unprepared conductors.

Field Wiring Terminal:

A terminal to which wiring connections are made in the field and that is subjected to the
requirements of a terminal for field wiring as specified in the National Electrical Code, NFPA 70.
Such terminations shall accept unprepared conductors.

WECO Electrical Connectors Inc. www.wecoconnectors.com | [email protected]


18050 Trans-Canada Highway Phone: 514 694-9136
Kirkland, Quebec, H9J 4A1 Fax: 514 694-0956
Canada Toll Free: 1 800 724-2928 (US and Canada)

You might also like