SVIB 53 840605028 PB-00317 v00 PB-750 OP
SVIB 53 840605028 PB-00317 v00 PB-750 OP
SVIB 53 840605028 PB-00317 v00 PB-750 OP
System Manual
English
PureBallast: Ballast Water Table of Contents
Treatment System
Safety 1
System Description 2
Printed 2012
Alfa Laval reserves the right to make changes at any time without prior notice.
Any comments regarding possible errors and omissions or suggestions for improvement of this
publication would be gratefully appreciated.
Copies of this publication can be ordered from your local AlfaLaval company.
Published by: : Alfa Laval Tumba AB
E-147 80 Tumba, Schweden
Telefon: +46 8 530 650 00
Telefax: +46 8 530 310 40
2 Safety instructions 7
2.1 Personnel requirements 7
2.2 Warning signs used in the manual 8
3 Environmental issues 9
3.1 Unpacking 9
3.2 Other materials 9
3
1 Introduction
This chapter contains general safety and environmental information, personnel requirements and
explanations of symbols used for the PureBallast system.
NGE R
! DA
Before maintaining the PureBallast system, make sure that the atmosphere is non-explosive.
• Use the equipment only for the purpose and parameter range specified by Alfa Laval.
• Use only Alfa Laval genuine spare parts.
• Strictly follow the instructions for installation, operation and maintenance specified in this
manual.
• Always read and follow the documentation that is included in shipment of components and
spare parts regarding handling, safety and disposal.
• Mobile cell phones must not be switched on within an area of 1 meter from an open cabinet door.
• Depressurize AOT reactors and allow equipment to cool down completely before disassembling.
• Before maintenance, read the Preparations and conditions section in chapter 7. Service manual.
• Before installation, read applicable sections in chapter 6. Installation instruction and drawings.
2.1 Personnel requirements
The PureBallast system must be operated, installed, maintained and repaired by persons trained for
respective type of work. All persons using and working with the system must know the emergency
stopping procedures.
Personnel installing, maintaining or repairing components must be of one of the following categories:
NGE R
! DA
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
NG
WARNI
!
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
ON
CAUTI
!
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
NOTE
NOTE indicates a potentially hazardous situation which, if not avoided, may result in property damage.
This section contains general rules regarding environmental issues. However, local rules and
regulations should be consulted for detailed handling of each material.
3.1 Unpacking
• Packing material consists of wood, plastics, cardboard boxes and in some cases metal straps.
• Wood and cardboard boxes can be reused, recycled or used for energy recovery.
• Plastics should be recycled or burnt at a licensed waste incineration plant.
• Metal straps should be sent for material recycling.
3.2 Other materials
• Rubber and plastics should be burnt at a licensed waste incineration plant. If not available they
should be disposed to a suitable licensed land fill site.
• Metal parts should be sent to a licensed handler for material recycling.
• Seal rings should be disposed of in a licensed land fill site. Check the local regulations.
• Worn out or defected electronic components should be sent to a licensed handler for material
recycling.
• The operator panel contain the following components with substances that might be hazardous
to health and the environment: lithium battery, electrolytic capacitor and display. They shall
be recycled according to local regulations.
• Used lithium batteries from the control unit are considered hazardous waste and should be
disposed of accordingly.
• Used UV lamps can be handled and disposed of in the same way as fluorescent lamps. Please
refer to national regulations.
• Used quarts sleeves should be disposed of as ordinary glass.
2 Process overview 11
2.1 Ballast start-up 12
2.2 Ballasting 13
2.2.1 Back-flush 14
2.2.2 Ballast after-treatment 15
2.3 Deballasting 16
2.3.1 Deballast after-treatment 16
3.2 Filter 23
3.2.1 Filter working principle 23
3.2.2 Filter description 23
3
1 Introduction
This contains general information about the PureBallast system and its components.
1.1 Abbreviations
The table below is a list of abbreviations used in this manual.
Abbreviation Explanation
AL Alfa Laval
AOT reactor The reactor house with UV lamps purifying the water
EX Explosion-proof
Abbreviation Explanation
UV Ultra violet
A PureBallast system consists of one to twelve AOTs, which can be connected in parallel to achieve
a total flow capacity between 250 and 3000 m3/h. The capacity of one AOT module is 250 m3/h.
The PureBallast system is an integral part of the vessel’s ballast water system, on the discharge
side of the vessel’s ballast water pumps. It is equipped with a bypass valve that is controlled
from the ISCS (integrated ship control system). PureBallast is also equipped with two sampling
devices, one before treatment and one after treatment. This makes it possible to take samples of
the ballast water according to IMO requirements.
PureBallast is operated from a control panel, which starts the automated ballast and deballast
processes. If integrated, it is also possible to control PureBallast from the ISCS, including the
vessel’s ballast water pump, overboard valve and power management.
• PureBallast meets the standard as set out in Regulation D-2 of International Convention for the
Control and Management of Ships’ Ballast Water and Sediments.
• PureBallast has been examined, tested and found to comply with the requirements of the
specifications contained in the IMO Resolutions:
- Guidelines for approval of ballast water management systems (G8), Res MEPC.174(58).
- Procedure for approval of ballast water management systems that make of active substance
(G9), MEPC.169(57).
• DNV Rules for Classification of ships, Pt.4 Ch.1, Pt4, Ch.6, Pt4 Ch.9 Sec.5 B.
2 59999955_ComponentsOverview
This section gives an overview of the main processes performed by PureBallast. A detailed
description of the processes, including operator actions and component activities, is given in section
Detailed process description in chapter 3. Operating instructions and control system description.
During the start-up, the UV lamps are warmed up. Cooling water is pumped through the AOTs
to secure that the UV lamps are not overheated. When the lamps are ready, the operator is
requested to start the ballast pump.
The process flow is monitored by the flow meter to secure that there is enough flow to cool the UV
lamps. If flow deviates from parameter set values, an alarm is issued and the system is shut down.
2 Startup
Ballast start-up
2.2 Ballasting
When the actual ballasting process starts, water is taken from the sea chest. The water passes the
PureBallast filter that removes particles and organisms larger than 40 µm. This also reduces the
amount of sediment build-up in the ballast water tanks. The water is finally led to the AOT reactor,
which produces radicals and UV light that breaks down and neutralize the organisms.
2 FullBallast
Ballasting
2.2.1 Back-flush
To keep the filter clean, it is automatically back-flushed. The back-flush is performed during ongoing
process without interrupting the ballasting process. The water used for back-flushing is returned to
the sea directly at the ballasting site.
2 Back-flush
Filter back-flush
First, all AOTs are simultaneously rinsed with fresh water. Then the cleaning in place (CIP) module
circulates a biodegradable solution through each AOT in sequence to remove seawater scaling.
The cleaning liquid is reused between the cleaning operations. After the cleaning is finished all
AOTs are filled with fresh water to preserve the filter and prevent scaling, algae growth etc. Also the
filter is filled with water for preservation reasons.
2 CIP
2.3 Deballasting
Deballasting also begins with a ballast start-up to warm the UV lamps. When the actual deballasting
process starts, the water passes through the AOT a second time, thus treating the water one
more time. The reason for treating the water a second time is to secure that the treatment is
fully effective. The minor part of the organisms, which were only injured during ballast, will be
rendered totally harmless during the deballast. However, the filter is bypassed since the water
has already been filtered.
The process flow is monitored by the flow meter to secure that the flow does not exceed the certified
rate and to secure that there is enough flow to cool the UV lamps.
2 FullDeballast
Deballasting
The water used in the stripping process, must be filtered from particles larger than approximately
5 mm. The water passes through the PureBallast system as a regular deballasting process, but
the filter is by-passed. The water is finally pumped into the sea.
This section gives an introduction to the most important PureBallast system components and
their functions in the system.
The Wallenius AOT process is chemical-free, similar to the technology used in many of today’s
smart products. The self-cleaning windows of skyscrapers and cars, for example, prevent the
growth of organisms through an AOT reaction that occurs when sunlight radiates titanium dioxide.
2 10_2_1_1 Cell
1. Radical
2. Cell membrane
There are no chemical substances added to the process, and there are no toxic residuals created.
Since the water is not affected chemically there are no environmental impact, and the process does
not influence corrosion in any way.
To secure that there is water in the reactor when the lamps are lit, each AOT reactor is equipped a
level switch. The level switche also secures that enough CIP liquid is pumped to the AOT reactor
during the CIP cleaning cycle. To secure that the lamps are adequately cooled by the ballast water,
each AOT reactor is equipped with one temperature transmitter. The control system monitors theses
values and will shut down the AOT if they deviate from parameter set termperature, completed with a
temperature switch that automatically shuts down the AOT reactor if the temperature reaches 70 °C.
AOT module
AOT reactor
1. Reactor housing
2. Catalyst insert
3. Quartz sleeve
4. UV lamp
The LDC is equipped with a cooling system to maintain the correct operating temperature in the
LDC, using low-temperature cooling water.
3.2 Filter
2 Filter 2_2_2
Filter
To secure efficient filtration, the filter performs a self-rinsing back-flush operation at time set
intervals or when triggered by indication of dirt in the filter. Dirt is detected by the differential
pressure transmitter installed on the filter, which monitors the differential pressure before and
after the filter. When the difference reaches a defined value, caused by particles, the automatic
back-flush operation starts. It is also possible to start back-flush manually from the control system.
The flushing arm is turned to flush each individual filter candle in sequence. At the same time, the
back-flushing discharge valve is opened which causes a high axial flow in the filter candle, so that
the dirt particles are flushed off. The water flowing lengthways through the filter candle conveys
the particles out from the filter. The control valve, placed after the AOT, secures the pressure
needed to perform the back-flush. If the differential pressure still is too high after the back-flush,
the sequence is repeated.
The back-flushing does not interrupt the filtration process, since the filter candles are cleaned one
by one by the upper and lower flushing arms alternately. The other filter candles continue the
filtration of the ballast water.
2FilterFiltering
2FilterBackFlush
Water flow inside the filter during filtration. Water flow inside the filter during self-rinsing
back-flush cycle.
During a cleaning cycle, the CIP module circulates a CIP liquid through the AOT reactor to remove
seawater scaling. After finished cycle, the liquid is returned to the CIP module; the CIP liquid is
reusable for a great number of cycles.
All ingredients in the CIP liquid are registered under HOCNF for use in the UK offshore fields.
Saltwater data is specified and all ingredients are listed in the PLONOR list (recommended
chemicals from the environment). The product is 100% PLONOR- approved for offshore. The CIP
liquid is classified as Group E in the UK (lowest environmental hazard).
To secure that there is enough CIP liquid for the process, the level switch in the AOT indicates
when it is filled with CIP liquid. To prevent intrusion of water in the fresh water system, a backflow
preventer is used in the CIP module.
• Pump P320-1 circulates the CIP liquid to and from the AOT.
• Pump P321-5 drains water (sea and fresh water) overboard from the AOT, via the drain line.
The pump is used if the vessel itself is unable to perform the drainage.
2 CIP 589741_3D_description
CIP module
1. Deaeration valve
2. Valve block
3. Regulator
4. Tank for CIP liquid
5. Pump (CIP liquid)
6. Backflow preventer
7. Pump (AOT drain)
• It ensures that the flow within the PureBallast system does not exceed its certified flow rate. If
the certified flow is exceeded a warning is issued.
• Via the flow transmitter, mounted on the flow meter, it sends valuable data to the PureBallast
control system, where it is displayed. Example of information: Current flow and data about
total amount of treated ballast water.
• PureBallast bypass valve: Makes it possible to completely bypass the PureBallast system.
The valve is solely operated from the ISCS, but the valve positioning is however indicated
in the PureBallast control system.
• Main inlet and main outlet valve: Connects the PureBallast system to the vessel’s ballast
system. The inlet valve directs the water flow into the PureBallast system and the outlet valve
returns the water to the vessel’s ballast system after treatment.
• Control valve: The valve have the following functions:
- Regulate the pressure to secure that there is enough pressure to perform a back-flush,
and that it is maintained.
- Regulates the process flow so it does not exceed the flow chosen for a process.
- Main outlet valve.
• Cooling water inlet valve: Supplies cooling water to the AOT to protect the lamps from
overheating. The valve is common for all installed AOTs.
• Filter bypass valve: During deballasting, the water does not pass the filter, since it has
already been filtered during ballasting. The bypass valve is used to direct the water flow so
that the filter is bypassed.
3.8 Control system
The control system is used to operate, monitor and administer the PureBallast system. The
system monitors the system automatically, based on input from sensors. Any deviation is either
communicated to the operator or handled automatically, based on parameter settings.
There are three alternative ways to access the control system: Main panel, remote control panel
(optional) and remote interface (optional). To avoid double command, PureBallast can only be
controlled from one place.
2ControlPanel
2RemotePanels
Note that Alfa Laval does not supply the graphical user interface to handle PureBallast in the
ISCS, only the means to enable the integration.
2RemoteInterface
PureBallast control system’s main control panel integrated with the ISCS. The interface is only an example.
3
3.8 Page 4.2 – Trend (30 s.) 34
3.9 Page 4.3 – Trend – AOT 1–6, TT201–33 34
3.10 Page 4.4 – Trend – AOT 7–12, TT201–33 34
3.11 Page 4.5 – Trend – AOT 1–6, TT401 35
3.12 Page 4.6 – Trend – AOT 7–12, TT401 35
3.13 Page 5.1 – System info 36
3.14 Page 5.2 – Main controller I/O 39
3.15 Page 5.3 – Operation timers 40
3.16 Page 5.4 Operation timers: AOT 1–12 42
3.17 Page 5.5 – Remote interface 1 43
3.18 Page 5.6 – Remote interface 2 44
3.19 Page 8.1–8.6 – Parameter pages 45
3.20 Page 5.7 – Log box 1 45
3.21 Page 5.8 – Log box 2 46
3.22 Popup windows 47
3.22.1 AOT popup 47
3.22.2 Filter popup 51
3.22.3 CIP popup 52
4 Operating instructions 53
4.1 Log in 53
4.2 Perform ballast 53
4.2.1 Start ballasting 54
4.2.2 Start ballasting with specified AOTs 54
4
4.3 Perform deballast 55
4.4 Pause ballast / deballast 56
4.5 Change ballast / deballast flow 57
4.6 Back-flush filter manually 57
4.7 CIP clean AOT after ballast / deballast 58
4.8 Stop ballast / deballast 58
4.9 Attend to alarms 59
4.10 Abort operation and deactivate the
system 60
4.11 Reset system after shut down 61
4.12 Operate components manually 61
4.13 Operate UV lamps manually 63
4.14 Set parameters 64
4.15 Restore default parameters 65
4.16 Backup control system settings 65
4.17 Restore control system settings 66
4.18 Export control system log files 67
4.19 Export control system history files 68
4.20 PID calibrate system 68
4.20.1 Calibrate pressure controlled regulation 69
4.20.2 Calibrate flow controlled regulation 70
5
4.21 Simulate power request 72
4.22 Set control panel IP address 73
4.23 Set remote control panel
communication 74
4.24 Set remote interface communication 75
4.25 Test remote interface communication 76
4.26 Update PLC software and HMI software 77
4.27 Update HMI software 79
4.28 Update control panel software 80
4.29 Calibrate the control panel’s touch
screen sensibility 81
6
1 Introduction
The control system is used to operate and monitor the PureBallast system. It also contains
functions for setting parameters, monitoring the system, saving log files etc.
This chapter describes the control system. It includes general description of the control system
pages, step-by-step instructions on how to operate PureBallast and a process descriptions with
detailed information about the components (valves, motors, pumps etc) involved in each step of
respective process.
The following control system related information is given in other chapters of the manual:
• Parameters are described in chapter 4. Parameters. Study this information before operating
the PureBallast system.
• Alarms and warnings including information about faultfinding and actions to be taken are
described in chapter 5. Alarms and fault finding.
• Information about integrating the control system with the vessel’s ISCS and power management
is described in chapter 6. Installation description and drawings.
1.1 Preparations and conditions
• Make sure all documentation is available, read and understood before start.
• Make sure not to exceed or fall below the limit values stated in chapter 6. Installation description
and drawings, section Technical data.
• During process, the control system requests that vessel valves are opened/closed. The
valves are outside the PureBallast system control. But the control system needs feedback
(opened/closed) during process. Status can either be confirmed manually in a popup or
automatically, if feedback signals are integrated via the remote interface option or via hard wire.
Please note:
- When valves are requested to be opened/closed, this means that all valves leading the
flow from the PureBallast via one of the following pipes must be opened/closed: 201, 309
and 404.
- Water does not need to be transported overboard. For example, the flow can be lead to
the bilge tank. In such cases, all relevant valves leading the flow from the PureBallast
system shall be opened.
• The input flow to the PureBallast system shall be as close as possible to the flow that has been
selected for an operation. This will reduce the stress and wear of the control valve.
• Operation with reduced number of AOTs must be done according to a or b below:
a Reduced number of AOTs according to the table below can be done without any steps
taken. In these cases, control valve V201-8 will adjust the flow.
b Operation with fewer AOTs (than stated in the table) requires that the incoming flow is
reduced to correspond with the capacity of the AOTs in use (250 m3/h per AOT).
1.1.1 Stripping
The first time a ballast tank is stripped, PureBallast must be by-passed.
If stripping is performed via PureBallast, select the number of AOTs that match the flow from
the eductor.
It is possible to perform heeling during ballast or deballasting. If it is done, the ongoing process
must be paused. During pause, cooling water is flushed through the AOT to cool the UV lamps.
After completed heeling, the operator must resume the paused process. See instruction Pause
ballast / deballast on page 56.
If external component signal for heeling mode is integrated between PureBallast and the vessel’s
ISCS, the process will be paused and resumed automatically. The user is notified of started and
stopped heeling via a message in the control system, and the event is logged.
If the system malfunction in connection with general cargo operation, ballast and deballast
operations should be avoided. In case untreated water is pumped to a ballast tank, this water shall
be discharged on open sea (200 NM) and exchanged for treated water. Note that full treatment
requires treatment both during ballast and deballast.
The procedures concerning emergency and malfunction of the ballast water treatment system
should be implemented in the ships Ballast Water Management plan.
In PureBallast, a deballast process is run with the vessel’s ballast valves positioned so that the
• pump takes water from a ballast water tank with treated water and
• the water flow is directed either overboard or to another ballast tank.
Run the process for enough time so all water in the piping is treated. Time for this depends on pipe
size and length on board.
This section describes different login levels, overview of the system interface and how to navigate
and operate the control system.
It is possible to log in if another user is logged in with the same login level, or lower. This person
will then be logged out. In this case a popup message is displayed that another user is logged in
on another panel. It is possible to continue (and logout the other user) or cancel. The logged out
user will receive a popup message that the user will be logged out. It is not possible to log in with
a lower level than a logged in user.
Level 0 Guest N/A Level 0 is the default mode of control system. This level is
not password protected.
Level 3 Alfa Laval N/A Password only available for Alfa Laval personnel.
• As level 2.
• Full access to all parameter pages.
When the remote interface is used, the panel(s) cannot be used to operate the system; it is only
possible to monitor the system and to export log files. It is possible to turn of the remote interface,
and thus activate the panels, from a panel when logged in as level 2 or 3.
The PureBallast system manual does not give any information about how to run PureBallast from
the remote interface. This is due to the fact that the remote interface is custom-made. Please
refer to the vessel specific manual.
• Heartbeat is updating. See that address +155 is updated in control system page 5.5 Remote
interface 1.
• There must be no active alarms for the AOTs to be used during operation. Always check the
alarm list (page 3.1 Alarm list in the control system) before operation.
The control system use a touch screen, where you tap the screen to “click” or drag objects. Do not
use sharp objects to touch the screen. When the screen is left idle for a defined amount of time, it
will go to screen saving mode. Time is set in page 5.1 System info. The screen is activated again
by touching it once. The touch will not activate any button that might be placed where you touch.
The illustration below shows the main areas and function buttons on the screen.
3 1.1
Login menu: Expanding menu with fields for logging in and out. Logged in user is always
displayed. If remote control panels (optional) are used, all inactive panels also displays which panel
that is active. The name used, is the on set for respective panel in page 5.1 System info.
Tabs: The top and side tabs are used to choose which page to display in the screen. Pages
are referred to as a number and a name, for example 3.2 Alarm history. The first number refers
to selected top tab, counted from left to right. The second number refers to selected side tab,
counted from top to bottom.
Top tabs: Contain the main function areas of the control system: Overview, alarm lists, trend
indication and parameters.
Side tabs: Contain sub pages for the function area selected in the top tab. Available side tabs
change depending on which function area that have been selected in the top tab. Example: If Alarm
lists is active, it is possible to choose between alarm list and alarm history.
Popup windows: Are used to display or enter detailed information. It is possible to move a popup
by touching the name bar and drag it. A popup is closed either by touching confirming entered
information by touching a function button (OK, Confirm, etc.) or the X icon in the top right corner
(data is not saved).
Data entry fields: A white field indicates that it is possible to enter data. When the field is touched,
a keyboard is displayed, which is used to enter information. Use the touch keys to enter data,
and confirm the entry by touching the Enter button. To close the keyboard without saving data,
touch the Esc button.
Tables: Individual table rows, for example an alarm, can be selected by pressing them. Column
widths can be adjusted. Press the column border in the head area and hold the finger on the
screen. The column border will turn bold, to indicate that it is possible to drag the column border
to desired width.
Function buttons: Function buttons are used during operation. They are always visible, but only
available when colored dark blue.
Status indication – Button color: The buttons appear in different colors, indicating status:
Status indication – Button light: After a function button is pressed, a light under the button is lit
to indicate status for the activated function:
Yellow Command will be processed when possible in the data work flow.
Button Description
3StopButtonBlue
Pause ballast or deballast process. This is only possible during full ballast
or full deballast. The button can be hidden, using parameter p137. Allowed
length of a pause is parameter set (p138). After defined time, the the
3Pause
paused process is stopped.
3CIP
Activate operation from control panels, instead of remote interface (if option
is used). The system can only be operated from either a remote control
panel or the remote interface. The button is only enabled in standby mode.
2 LocalButton
3Wipe
Activate night light for the panel. Night light makes the panel less bright. If
night light is activated, the button activates day light.
3 Night Degree of brightness, is set in the Night light level field in page 5.1 System
info.
Sets the control system in manual mode, which enables manual operation
of components. The button is displayed for login level 2 and 3. For detailed
3 EnableManual
information see Manual mode on page 102.
Button Description
Display PID calibration popup. PID calibration is performed to fine tune the
system so it runs with a steady and even flow. The button is displayed for
3 PIDbutton login level 2 and 3.
The button is displayed beside the control valve 201–8 in the flow chart.
To print a screen image to the USB port: Insert a USB memory at the back
of the panel. Press Utilities, and then Print to save a screen image to USB.
The USB port can also be connected to a printer.
3 Utilities
3 Help
This section describes the pages used for operation. Note that this section does not cover the
parameter pages. Please refer to chapter 4. Parameters.
The main areas are the Status box and the Flow chart.
3 1.1
Process and sub process Process: Ongoing process. Can be standby, ballast, deballast
and CIP.
Current flow (m3/h) Ballast water flow in the system, indicated by flow transmitter
FIT201-1.
Selected certified flow (m3/h) Flow (m3/h) selected for the current operation, according to
selection made in page 1.3 AOT and flow selection. Flow can
either be set by selecting a flow or select a number of AOTs. As
default value, last set flow is used.
3 PumpReq
Status indication
Green = Operating.
Green = Open.
Grey = Closed
Relevant information regarding ongoing process and component status can be monitored directly
in the flow chart. Flow in pipes is indicated by coloring of the pipes and component status are
displayed by color indications. As a complement to the status box, pressure, flow and control valve
opening percent are displayed close to respective component.
Detailed information about the main components can be monitored in popup windows for respective
component (AOT see page 47; filter see page 51; CIP see page 52). These popup are opened
by tapping the component on the screen. They display status for sub components, for example
inlet valve and individual UV lamps in the AOT.
Booster pump for AOT (P403–1) and LDC (P401–1) are only displayed if these components are
used and activated in the parameter pages.
In manual mode (login level 2 and 3) it is also possible to operate components manually: If a
component is pressed, a popup window is displayed from which the component can be operated.
Red, flashing Indicates that there is an active alarm for the component.
Blue pipes Fresh water flow. Flow is not indicated in manual mode.
Green pipes Ballast and deballast flow. Flow is not indicated in manual mode.
Grey pipes Air flow during deareation. Flow is not indicated in manual mode.
3Manual1
The main areas of the page are the Status box, Current status, Flow setpoint and AOT selection.
3 1.3
Elements Description
Setpoint is updated in the Flow setpoint field, but the flow is not changed
until the Confirm button is pressed. The field is updated with 250 m3/h
each time the button is pressed.
Decrease Press the button to decrease the flow. Functions as the Increase button.
Confirm Press the button to execute selected setpoint. If flow capacity is changed
during ballast or deballast, the flow change will take effect directly. If flow
capacity is set before ballast or deballast has been started, this is the flow
that will be used when process is started.
When the button is pressed, the text “New flow in progress” is displayed
until the new flow is reached. The Certified flow field is updated when
the lamps are started.
Elements Description
Current flow Ballast water flow in the system, indicated by flow transmitter FIT201-1.
Selected certified Maximum allowed flow as set in Flow setpoint or limited by the number of
flow AOTs selected in AOT selection popup.
AOTs selected for A list of installed AOT. Current status for respective AOT is indicated by
process colors:
Status indication
Black = Selected
Green = Operating
3 AOTselect
Elements Description
AOT A list of installed AOTs are represented by one button. Press a button to
activate that AOT for use.
Status indication:
Indicates that there is an active alarm for the component. Check alarms on
page 3.1 – Alarm list.
3Alarm
Corresponding The field indicates flow setpoint for the number of AOts selected. The field
flow setpoint is updated with 250 m3/h for each selected AOT.
Confirm Press the button to save the AOT selection and close the popup.
The page also display time remaining for ongoing CIP cycle. If no CIP required process has been
started after a ballast or deballast operation, the time remaining before CIP must be performed is
displayed.
3 1.4
Row Content
AOT Each row indicate status and time for each installed AOT.
Filter preservation This row indicate status and time for the filter preservation process, that
starts after completed CIP cycle for all AOTs after ballasting.
Total Total estimated time for a complete CIP cycle including filter preservation.
Column Content
CIP error Red square: Indicates that there is an active alarm for the component.
Check alarms on page 3.1 – Alarm list.
Status indication
Yellow = CIP required. During ongoing CIP cycle, yellow indicates that the
AOT is waiting for CIP cycle to start.
Estimated Time remaining for each AOT. If CIP cycle has not been started, total time
remaining time is displayed. During CIP cycle, the time is counting down continuously.
Required CIP Time before a CIP cycle must be performed after ballast or deballast. When
countdown CIP cycle starts, the time disappears.
3 1.5
The page can also be used to troubleshoot the power management system integration by sending
and checking each signal.
Page content
Column Content
Power Each row represent a number of AOTs to be used in a process. The rows
can be combined. For example row 1 and 2 equals three AOTs.
Common power Request maximum power, enough to run all AOTs installed, even if all AOTs
are not used. This alternative is used if power management is not installed.
Pure Ballast always asks for power before the UV lamps are lit during ballast
or deballast start-up. When a request has been sent, the vessels power
management performs a power check before the generator is started.
If there is not enough power available for the amount of AOTs, a lower
power value might be granted. This means that less AOTs will be used and,
consequently, the process will be run with a less flow capacity.
Column Content
If Common power has been selected, the value is the standard total power
according to parameter p107.
Buttons Content
Request Press to manually simulate request for a power step. The button is
displayed for login level 2 and 3.
Set run Press to manually simulate run signal for a power step. The button is
displayed for login level 2 and 3.
For further information about the specific alarms see chapter 5. Alarms and fault finding.
3 3.1
The main areas of the page are the Alarm list and the Function buttons:
Column Content
Text Descriptive alarm text written as: Area-Alarm type AlarmID Alarmtext.
Example: AOT2 A138 Error in LDC cabinet.
- A = Alarms stop the ongoing process, which can be restarted after the
problem has been attended to.
- W = Warnings are notification of a status change or a problem. Warnings
allow the process to continue.
Acknow- The time the alarm was acknowledged. The alarm remains in the alarm list
ledged time until the causing condition is resolved. For example a high temperature alarm
will remain visible, until the temperature is below the alarm setpoint.
Alarms and warnings can be active after they have been acknowledged. The table below shows
status indication for alarms and warnings in the alarm list.
Button Function
|| Pause the alarm list screen, so that the page is not updated with new alarms.
This is useful when many alarms are issued at the same time, to facilitate
selection and acknowledgement of individual alarms.
Press again to release the pause function, so that all new alarms are displayed
and the list is dynamically updated.
3 3.2
Column Content
Text Same as in Page 3.1 Alarm list.
Normal time The time the value that caused the alarm returned to normal.
3 4.1
Trends can be plotted for the following components (identified by item number) and key values:
The diagram plot trend curves for the components selected by the plot checkbox. The color of the
line corresponds with the color of the plot checkbox.
Y axis: The scale and unit used for the Y axis can only be displayed for one selected component
at a time, since different units are used. The component controlling the Y axis is selected by
pressing the Y axis selection button in the component area. Note that interval Y axis scales are
defined individually per component.
Plot checkbox Press the colored checkbox to plot trend for the component. It is possible to
plot trend curves for one or more component.
3 PlotBox1
Status indication:
Y axis Press the button to let this component control unit and Y axis scale. Only one
selection component can be selected to control the Y axis scale and unit.
Status indication:
3 YAxis1
Not selected.
3 YAxis1
Y axis - Low The Y axis low value for the diagram when this component i selected.
Y axis - High The Y axis high value for the diagram when this component i selected.
Actual value Current actual value for the component is displayed in the gray field. (This
corresponds to the diagram.)
Buttons Content
Show history Press the button to display historic trend curve. A popup is opened where it is
mode possible to display trend curve for
• latest hour
• latest day
• a customized time interval set by year, moth, day, hour, minutes and
seconds.
History mode is indicated by the word “History” at the bottom of the screen.
Leave history Press the button to leave history mode and display current trend curve.
mode
See page 4.1 Trend (1 s.) for information about function, fields and buttons.
See page 4.1 Trend (1 s.) for information about function, fields and buttons.
See page 4.1 Trend (1 s.) for information about function, fields and buttons.
See page 4.1 Trend (1 s.) for information about function, fields and buttons.
See page 4.1 Trend (1 s.) for information about function, fields and buttons.
3 5.1
HMI info CPU temperature (°C): Temperature of the central processor unit
(CPU) in the control panel.
IP-settings
Setup button: Opens popup to set IP address for the main panel
and the remote control panels (optional).
HMI date and time UTC Time and date: Only used if no GPS is connected to the control
system. If so, time is retrieved from the GPS.
Set button: Set time and date for the control panel.
HMI Backlight Screen saver timeout: Defines time before the panel is set to
screen save mode. This is set individually per control panel.
Night light level: Defines percent of full light for the night light
mode. Night light is activated by the Night function button.
PLC Info CPU temperature (°C): Temperature of the central processor unit
(CPU) in the PLC.
Backup and restore Settings to/from HMI USB: Export information to the USB port on
the control panel.
Set default button: Set all parameter values to the default values.
Export log files Export: Export (copy) event log and alarm list is saved as a set of
files in a folder named “PureBallast”.
Note that this page is only intended for Alfa Laval’s personnel and only available (displayed) for
login level 3.
3 5.3
Row Unit
Row Unit
3 5.4
AOT 1: Lamps Total runtime for the UV lamps in Lap time for installed UV lamps, since
on respective AOT. the counter was reset after previous
reset at UV lamp change.
3 5.5
For detailed information about respective address: See chapter 6. Installation description and
drawings, section Communication between PureBallast PLC and remote interface.
3 5.6
3 5.7
Column Content
Example: In the illustration Vessel ID “Valve X45” is entered for position V01.
To enter a vessel ID: Press the entry field or the document icon for the
component, and enter the ID using the keyboard displayed on the screen.
Position: For each valve, it is possible to connect two signals to log feedback
on open, closed or both. If signal “Closed” is used for a valve, the event log
will make a record each time the valve is detected closed, and each time it is
detected not closed.
Status Active signal is indicated with a green light on the I/O icon.
Logging Two parameters per valve defines if opened and/or closed signals are
connected for respective position (valve). If parameter is set to Active,
activities for the component is logged in the event log.
See page 5.7 Log box 1 for information about function, fields and buttons.
3 5.8
In manual mode (login level 2 and 3) it is also possible to operate components manually. If the
component is pressed, a popup window is displayed from which the sub components can be
operated.
Component Description
AOT number Indicates which AOT that is selected and displayed. Press the field to enter
an AOT number, or press the arrows to step up or down.
Indicates that there is an active alarm for the selected AOT. Check alarms
on page 3.1 – Alarm list.
3Alarm
Grey = Off.
Green = Started.
Yellow = Starting.
Component Description
LPS manual Open the Manual LPS operation popup, which enables manual operation
control of individual UV lamps in an AOT. See section Page 1.1 Manual LPS
operation popup and instruction Operate UV lamps manually on page 63.
LS201–29 Level switch indicates if the AOT is filled with water or not.
Status indication:
Green = Filled.
Red = Not filled.
TS201–60 Temperature switch TS201–60 automatically shuts down the AOT reactor
when the temperature reaches 60 °C.
Status indication:
Green = OK.
Red = Not OK.
Valves For status indications, see Status indication – Component color in section
Flow chart on page 19.
Each AOT is equipped with twelve lamp power supplies (LPS), which respectively supplies power to
the one UV lamp in the reactor. The UV lamps can be operated via the LPSs in manual mode. The
LPSs are installed in the lamp drive cabinet (LDC).
The popup is displayed when the LPS manual control button is pressed in the AOT popup. The
popup displays status for all individual UV lamps in a selected AOT.
In manual mode (login level 2 or 3) it is also possible to operate UV lamps manually. See instruction
Operate UV lamps manually on page 63. When manual mode is deactivated the system will return
to standby mode: All manually operated components will return to their status prior to the manual
operation.
NGE R
! DA
• Manual start of the UV lamps is only allowed (and possible) when there is water in the AOT
reactor (indicated by level switch LS201-29), and the water temperature is below 60 °C. All
necessary items – cooling water flow, water temperature, and power management – must be
supervised and verified by the authorized trained personnel operating the system. Improper
operation of this function could seriously damage the equipment and injure personnel.
3 LPSpop
Component Description
Manual LPS Indicates which AOT LPS are to be operated. Press the field to change
operation for AOT.
AOT
LPS 1–12 Press one button (1–12) to start or stop UV lamp 1 – 12 manually,
controlled by the LPS.
Status indication:
Indicates that there is an active alarm for the component. Check alarms
on page 3.1 – Alarm list.
3Alarm
Component Description
Start all lamps Press the button to start all lamps for the AOT.
Stop all lamps Press the button to stop all lamps for the AOT.
LPS mode A hand icon indicates that the component has been modified manually.
In manual mode (login level 2 or 3) it is also possible to operate components manually. If the
component is pressed, a popup window is displayed from which the sub component can be
operated. When manual mode is deactivated the system will return to standby mode: All manually
operated components will return to their status prior to the manual operation.
3 1.1 Filter
Component Description
Initiate back- Press the button to start a manual back-flush. See instruction Back-flush
flush filter manually on page 57.
Valves and motor See Page 1.1 – Overview section Status indication – Component color
for status indications.
In manual mode (login level 3) it is also possible to operate components manually. If the component
is pressed, a popup window is displayed from which the sub component can be operated. When
manual mode is deactivated the system will return to standby mode: All manually operated
components will return to their status prior to the manual operation.
Valves and motors: See Page 1.1 – Overview section Status indication – Component color for
status indications.
3 1.1 CIP
This section contains step-by-step instructions for operating the PureBallast system. Please read
and follow the preparations and conditions carefully, as well as any danger or warning notes.
• Control system pages used in the instructions: See section Control system — Detailed page
descriptions.
• Login levels required for different procedures: See section Login levels on page 11.
• Detailed information about components (valves, motors, pumps etc) involved in each step the
process. See section Detailed process description.
4.1 Log in
Follow the steps below
1. Press the expand button on the Log in tab in the top right corner of the screen.
Result: The log in menu is displayed.
2. Press the expand button on the left drop down menu to display available users. Press desired
user.
Result: A keyboard is displayed.
3. Enter password and press Enter. (See section Login levels on page 11.)
As default, last selected flow is used. If you want to, change flow according to instruction
Change ballast / deballast flow on page 57.
2. Wait for the message “Open valves ...”. Open relevant valves and then press the button in the
popup to confirm the action. Note! This component is outside the PureBallast system control.
(The popup is not displayed if the component feedback is integrated with the control system.)
Result: Ballast start-up starts, with cooling water cooling the lamps during warm-up.
3. Wait for the message “Confirm ballast pump started”. Start the pump and then press the
button in the popup to confirm the action. Note! This component is outside the PureBallast
system control. (The popup is not displayed if the component feedback is integrated with
the control system.)
Result: Cooling stops and ballasting starts.
4. When desired amount of water has been processed, press the function button Stop.
Result: Ongoing process is stopped and the lamps are switched off. An automatic filter
back-flush is performed.
5. Wait for the message “Close valves ...”. Close relevant valves and then press the button in the
popup to confirm the action. Note! This component is outside the PureBallast system control.
(The popup is not displayed if the component feedback is integrated with the control system.)
6. Wait for the message “Stop ballast water pump”. Stop the pump and then press the button in the
popup to confirm the action. Note! This component is outside the PureBallast system control.
(The popup is not displayed if the component feedback is integrated with the control system.)
NOTE
A CIP cleaning process must be performed after ballasting. It can be done immediately or within 30 hours. When
time is about to elaps, a warning is issued. If no action is taken within the time limit, an entry is made in the control
system’s log as a deviation from a correct handling of the system. Note, that it is possible to perform processes
during these 30 hours. Complete status information regarding CIP is displayed in page 1.4 CIP status. A CIP
process is started manually according to instruction CIP clean AOT after ballast / deballast on page 58.
2. Press the AOT selection button on the right hand side of the page.
Result: A popup is displayed. Installed AOT are displayed and previously activated AOTs are
indicated by a green checkmark.
3 AOTselect
As default, last selected flow is used. If you want to, change flow according to instruction
Change ballast / deballast flow on page 57.
2. Wait for the message “Open valves ...”. Open relevant valves and then press the button in the
popup to confirm the action. Note! This component is outside the PureBallast system control.
(The popup is not displayed if the component feedback is integrated with the control system.)
Result: Deballast start-up starts, with cooling water cooling the lamps during warm-up.
3. Wait for the message “Confirm ballast pump started”. Start the pump and then press the
button in the popup to confirm the action. Note! This component is outside the PureBallast
system control. (The popup is not displayed if the component feedback is integrated with
the control system.)
Result: Cooling stops and deballasting starts.
4. When desired amount of water has been processed, press the function button Stop.
Result: Ongoing process is stopped and the lamps are switched off.
5. Wait for the message “Stop ballast water pump”. Stop the pump and then press the button in the
popup to confirm the action. Note! This component is outside the PureBallast system control.
(The popup is not displayed if the component feedback is integrated with the control system.)
6. Wait for the message “Close valves ...”. Close relevant valves and then press the button in the
popup to confirm the action. Note! This component is outside the PureBallast system control.
(The popup is not displayed if the component feedback is integrated with the control system.)
NOTE
A CIP cleaning process must be performed after deballasting. It can be done immediately or within 30 hours.
When time is about to elaps, a warning is issued. If no action is taken within the time limit, an entry is made
in the control system’s log as a deviation from a correct handling of the system. Note, that it is possible to
perform processes during these 30 hours. Complete status information regarding CIP is displayed in page 1.4
CIP status. A CIP process is started manually according to instruction CIP clean AOT after ballast /
deballast on page 58.
• This is only possible in sub process full ballast or full deballast. This is indicated by the lit
Pause button.
• Allowed length of a pause is parameter set (p138). After defined time, the the paused process
is stopped.
2. Wait for the message “Stop ballast water pump”. Stop the pump and then press the button in the
popup to confirm the action. Note! This component is outside the PureBallast system control.
(The popup is not displayed if the component feedback is integrated with the control system.)
Note: If you pause to perform heeling (internal transfer) you confirm the request without
stopping the ballast water pump.
Result: Ongoing process is paused. The UV lamps remains on and cooling water is run
through the AOT to avoid overheating of the lamps. Pause mode is indicated by yellow light
under the Pause button and blinking yellow under the function button Ballast or Deballast.
3. To resume the paused process, press the function button Ballast or Deballast.
4. Wait for the message “Confirm ballast pump started”. Start the pump and press the button in the
popup to confirm the action. Note! This component is outside the PureBallast system control.
(The popup is not displayed if the component feedback is integrated with the control system.)
Result: The process is resumed.
• Flow can either be set before the operation is started, or during operation. Flow can only be
changed in the sub process full ballast or full deballast. Selected certified flow for operation is
indicated in the Status box.
• There must be available power for the increased flow. If power management is integrated, this
will be done automatically. If power management is not integrated, confirm this manually.
Follow the steps below:
2. Set flow on the left hand side of the page: Press the Increase button to increase or Decrease
arrow button arrow to decrease.
Result: Setpoint for flow is updated in the Flow setpoint field with 250 m3/h for each time
the button is pressed.
If System shut down is activated during the CIP cycle, the CIP liquid is drained to the CIP tank and
any water in the AOTs is drained overboard.
• The system must be in standby mode. This means that this operation cannot be executed
during ballast or deballast.
• Complete status information regarding CIP is displayed in page 1.4 CIP status. The page
displays remaining time for ongoing CIP cycles, remaining time before individual AOTs are
required to be CIP:ed etc.
Follow the steps below:
3. Wait for the message “Open valves ...”. Open relevant valves and then press button in the
popup to confirm the action. Note! This component is outside the PureBallast system control.
(The popup is not displayed if the component feedback is integrated with the control system.)
Result: The automatic CIP cycle starts. The CIP cycle takes 15 minutes per AOT.
4. Wait for the message “Close valves ...”. Close relevant valves and then press button in the
popup to confirm the action. Note! This component is outside the PureBallast system control.
(The popup is not displayed if the component feedback is integrated with the control system.)
1. When desired amount of water has been processed, press the function button Stop.
Result: Ongoing process is stopped and the lamps are switched off. If ballasting: The filter is
rinsed by an automatic back-flush process.
2. Wait for the message “Stop ballast water pump”. Stop the pump and then press the button in the
popup to confirm the action. Note! This component is outside the PureBallast system control.
(The popup is not displayed if the component feedback is integrated with the control system.)
3. Wait for the message “Close valves ...”. Close relevant valves and then press the button in the
popup to confirm the action. Note! This component is outside the PureBallast system control.
(The popup is not displayed if the component feedback is integrated with the control system.)
NOTE
A CIP cleaning process must be performed after ballasting and deballasting. It can be done immediately or
within a 30 hours. When time is about to elaps, a warning is issued. If no action is taken within the time
limit, an entry is made in the control system’s log as a deviation from a correct handling of the system. Note,
that it is possible to perform processes during these 30 hours. Complete status information regarding CIP is
displayed in page 1.4 CIP status.
An alarm is indicated by a audible signal and by the blinking alarm icon in the control panel:
3Alarm
NG
WARNI
!
• Never reset an alarm without first finding and attending to the problem.
Follow the steps below:
4. If the alarm is caused by a faulty AOT module, the ballast/deballast process has to be restarted
with another AOT according to the Perform ballast instruction or started when the fault has
been corrected.
5. If the process continues: Consider if the process shall be terminated. Take action to eliminate
what has caused the alarm.
Press the Ack selected button after the problem has been dealt with. If you want to
acknowledge all alarms, press the Ack all button.
Result: The alarm will change color to indicate change of status. See section Page 3.1 Alarm
list in this chapter. The acknowledge time is updated, and the Normal time will be updated
when the problem is resolved.
3 Emergency stop
One of the following methods can be used to abort any ongoing operation and stop the system:
Action Method
Abort operation Press the Stop button (2) on the control cabinet.
Result: Ongoing process is stopped in a controlled way. Valves are
returned to starting position. The power is still on.
Safety stop If an external safety stop button dedicated for PureBallast has been
installed, it will function as described above. In the alarm list, it is
referred to as stop by “external system”.
Action Method
Turn of power Turn off the main breaker (1) at the side of the control cabinet. The
completely to system is made completely dead (currentless) from the power supply
PureBallast cabinet/main switch board, including the control cabinet.
The system may only be reset after the reason for shut down is known. If the reason is not known,
follow the instruction Attend to alarms.
Manual on control cabinet: Reset the Stop button (2) or turn the main breaker (1).
Automatic on LDC: If an AOT reactor has been shut down by temperature switch TS201-60 (alarm
A137) or if the cabinet or system has been shut down by a blackout, follow the instruction below:
• Valves are recommended to be operated via the PureBallast control system. It is also possible
to open/close them manually according to instruction in chapter 7. Service manual, section
Operate valves manually.
• Filter motor (M709-42)
• CIP pump for CIP liquid (P320-1)
• CIP pump for draining (P321-5)
• Booster pumps (if used)
• UV lamps in the AOT
3 PopValve
NGE R
! DA
• Manual start of the UV lamps is only allowed (and possible) when there is water in the AOT
reactor (indicated by level switch LS201-29), and the water temperature is below 60 °C. All
necessary items – cooling water flow, water temperature, and power management – must be
supervised and verified by the authorized trained personnel operating the system. Improper
operation of this function could seriously damage the equipment and injure personnel.
Follow the steps below:
4. Open, in stated order, the following valves to fill the AOT with water: 201-19, 404-36 and
403-35.
5. Wait until the AOT is filled with water. This is indicated by the level switch, which turns green.
6. Press the LPS manual control button. (The button is displayed for login level 3.)
Result: The LPS popup is displayed for selected AOT. If an existing alarm exist, it is indicated
with an alarm icon. Each lamp is represented by a button, indicating there status:
Grey = Stopped; Green = Started; Yellow = Starting.
3 LPSpop
8. If you want to operate lamps for another AOT, go to step 3. If you want to end, continue
with step 9.
NOTE
3. Use the touch keys to enter data, and confirm the entry by touching the Enter button. To close
the keyboard without saving data, touch the Esc button.
If the parameter is set with a drop down menu, select desired choice by touching the value.
Result: The setting is saved directly, it is now safe to leave the page.
• Audit trail (tracking of actions in the control system, e.g. changed password, acknowledged
alarms, changed parameter values). Saved in file AuditTrail.sdf.
• Parameter settings. Saved in file Parameters.csv.
• Settings for trend pages, e.g. min and max values for different components. Saved in file
ValueTrendLegend.xml.
• Passwords. Saved in file Security.xml.
• Notpad.txt. Can be used to make notes for the backup.
3. Press the Backup button in page section Backup and restore, Settings to/from HMI USB.
Result: A popup is displayed and the process is started. All activities are displayed as the occur.
Read the final line of list before closing the popup: Important information might be displayed.
4. Wait for the OK / Close button to turn blue again. If the backup was successful, the last line
shall state "Backup done".
Result: A folder named PureBallast backup has been downloaded containing the backup files.
3. Press the Restore button in page section Backup and restore, Settings to/from HMI USB.
Result: A popup is displayed and the process is started. All activities are displayed as the occur.
5. Read the final line of list before closing the popup: Important information might be displayed. If
the restore was successful, the last line shall state "Restore done".
6. Press the OK button on the popup and remove the USB memory.
7. The control panel must be rebooted. At the rear side of the control panel: Pull out the power
cable from the 24V DC port, and insert it again.
Information to be Description
exported
Event log The event log includes all important events in the PureBallast system. The
log also include components connected via the log box. Intended to be
used mainly by service technicians.
Event log - Contains a selection of the complete event log, relevant to IMO.
Certificate
Alarm history A list of all alarms and warnings that has been issued from the control
system. Intended to be used mainly by service technicians.
For specific information about logged events, see section List of logged information on page 83.
• Events are only copied, hence they will remain in the control system.
• Required USB memory capacity is indicated in the Export PLC events popup.
• The program Visualog must be used to open the files saved.
Follow the steps below:
3. Wait for message: Insert USB in PLC. Place a USB memory in the Main PLC module (A01) in
the control cabinet.
4. Chose one of the following alternatives to decide time interval for the information to be copied:
• Accept suggested default time interval in the Start and End fields. Default start date is the
oldest file in the system, and default end date is today’s date.
• Select the Specify time interval box, and enter desired interval in the Start and End fields.
5. Press one of the following function buttons: Events, Cert events or Alarms.
Result: The information is copied to the USB memory indicated by a green checkmark on
the button during copying.
6. Wait for the message "Export OK" to appear. If desired, export next category of events using
the function buttons.
Result: A folder named PureBallast has been downloaded. It contains three sub folders:
Alarm, Cert and Event. The folder corresponding to your export choices contains a CSV file.
• Database, including alarm history, trend history etc. Saved in file Database.sdf.
• Audit trail (tracking of actions in the control system, e.g. changed password, acknowledged
alarms, changed parameter values). Saved in file AuditTrail.sdf.
• Settings for trend pages, e.g. min and max values for different components. Saved in file
ValueTrendLegend.xml.
• Passwords. Saved in file Security.xml.
• Notpad.txt. Can be used to make notes for the backup.
Preparations and conditions
3. Press the Backup button in page section Backup and restore, History to HMI USB.
Result: A popup is displayed and the process is started. All activities are displayed as the
occur. Be sure to read the final line of list before closing the popup: Important information
might be displayed.
4. When the message “Export done” is displayed, press the OK button on the popup.
Result: A folder called PureBallast Export is created on the USB memory.
During ballast and deballast operation, the control valve is PID regulated based on input from the
flow transmitter FIT201-1 to maintain stable flow. Desired flow is defined as selected certified flow
for the operation minus the Undershoot percentage set in parameter p111.
During back-flush, the control valve is PID regulated based on input from the pressure transmitter
PT201-16 to maintain stable pressure for efficient back-flush. Desired pressure is defined in
parameter p304.
The second goal is to shorten the time from back-flush trigger to start of actual back-flush. This is
done by shortening the time in p310 (Back-flush initial delay). This is done after the movement of
V201-8 has been calibrated.
This instruction shall be read together with the example after the instruction.
1. Perform a back-flush.
2. Open page 4.1 Trend (1 s.) and analyze the trend curve for V201-8.
Before the back-flush, the valve shall move as fast as possible to a steady position where it
creates required pressure. If not, parameter p166 shall be adjusted.
3. Adjust parameters, and perform a new back-flush.
4. See if the curve has improved. Repeat until satisfactory result has been achieved.
5. See if the time between back-flush initiation and back-flush can be shortened . If possible,
adjust parameter p310. See parameter p310 in the example below.
Example
In this example, five back-flushes are performed. After the first four back-flushes, the PID
parameters where changed for pressure regulation to adjust the movement of the control valve
V201-8 before the back-flush.
The illustration is taken from page 4.1 Trend (1 s). Back-flush is indicated by the movement of the
back-flush valve 309-1 (pink line) and the movement of control valve V201-8 is indicated by the
blue line.
1st back-flush Parameter p166 is set to 0.30. But it takes too long time for V201-8 to get into
position to create desired pressure (1). The curve slops downwards in a long bend,
which means that it takes time for V201-8 to find correct position.
2nd back-flush Parameter p166 was adjusted to 0.6. This made the valve movement much faster
in the beginning, shown by the steep curve at the beginning. But then a more slow
regulation starts, shown by the soft slope (2). This was a change for the better, but
not enough.
3rd back-flush Parameter p166 was increased to 1.2 which resulted in a satisfactory valve
movement (3): A fast movement, followed by a minor adjustment. A small
overcompensation can be noted (curve goes too low), that might be adjusted by
decreasing the value to 1.1.
4th back-flush During the first back-flushes, parameter p310 was set to 60 seconds. The
parameter defines time between a back-flush is triggered and it actually starts. But
now, when V201-8 is calibrated, this time can be shortened. Before the fourth
back-flush parameter p310 is set to 15 seconds. The shortened time span is
indicated by the braces in the illustration.
5th back-flush No parameter was changed. This back-flush is only showed to confirm that the
parameter setting is OK and that the curve (5) for V201-8 is basically the same as
for back-flush three and four (3 and 4).
3 CalibExample
The purpose is to update settings below, based on the calibration. These values are saved as
parameters, which can only be set by this process.
• Pf — Proportional
• If — Integral
• Df — Derivative
Preparations and conditions
2. Press the PID button beside the control valve 201-8 in page 1.1 Overview.
Result: PID calibration popup is opened. In the popup, the current parameter (parameter
p120–p122) values are displayed in the Actual column: Pf, If and Df.
3 PopPid
3. If you want to start the PID calibration with a manually set start value, enter the values in
the Calculated entry fields. This can be used if you have approximate values based on
experience. If
5. Start pump (This component is outside the PureBallast system control.). When done, press the
Confirm “Ballast pump” started button.
6. Press the Start calibration button in the Activate PID calib popup.
Result:
8. Wait for the popup “Confirm ballast pump stopped”. Stop ballast pump. When done, press
the Confirm ballast pump stopped button.
• Press the Save to parameter button to save the calculated calibration values to parameter.
At the same time, the Actual column is updated with these values.
• Adjust the calculated values before you save them. Enter the values in the Calculated
entry fields. Then press the Save to parameter button.
• Press the Read from parameters button to reload current parameter values. The
Calculated column is updated with the current values from the Actual column. This is
useful if you have modified the values and want to reset the values.
• Press the Abort / Exit button to exit the popup without saving any data.
1. 1. Go to page 1.1 Overview. Press the button Enable manual mode in the Flow chart.
Result: The control system is set in manual mode, indicated by a green checkmark on the
button.
3. Press the hand button in the Request column for a row with power step for desired number of
AOTs. For details, see description of page 1.5 – Power request.
4. Press the Request button for the row to simulate power request signal.
Result: Status is updated to “Requested” in the Request column.
8. Press the Set run button to deactivate the simulate running signal.
9. Go to page 1.1 Overview and press the Enable manual mode button to exit manual mode.
3 IPaddress
4. At the backside of the panel, check which port that is use for the Ethernet cable. The one
marked with the symbol below is port 1 and the other one is port 2.
3 USB
In the popup, select the tab for the port that is used. Then select the radio button Specify
an IP address.
Enter the IP address for the panel according to the list below:
5. Press OK.
7. Follow the instruction Set remote control panel communication to activate the remote control
panel.
3 RCP communication
4. Select an available remote control panel (IP address ending with 11–14 in the left list.
6. Press the Panel alias field for the new panel. Use the keyboard to enter a name, for example
the location it is placed.
To delete a connected panel: Select it in the right list and press the delete (X) icon.
NOTE
3 RI communication1
3. Press the ModubusSlave line. Make sure that the check box is still selected. Then press
the Settings button.
Result: A popup is displayed.
3 RI communication2
4. Scroll down in the list until you find the Serial section. Change the fields to match the settings
in the illustration above.
• There must be no active alarms for the AOTs to be used during operation. Always check the
alarm list (page 3.1 Alarm list in the control system) before operation.
• If the system has been shut down, it must be reset:
- Control cabinet: Stop button must be released and the main breaker must be on.
- LDC: Cabinet must be reset. If the reset button at the side of the cabinet lights blue, push
it to release it.
1. Open page 5.5 Remote interface 1. Make sure that the system is in online mode. If not,
press the Online button. Make sure that Local operation is activated. If not, press the Local
function button.
2. Make sure that values are read from the PureBallast system, for example temperature
(address +116 and +117).
3. Make sure that the heartbeat is updated in address +013 and reflected in address +155.
4. Press the Offline button to set the system in offline mode. Press the Remote function button.
Result: Communication is deactivated between the ISCS and the PLC (to avoid that any
processes is started). This also result in alarm A93 Heartbeat signal missing. This alarm
shall be ignored during this test.
6. Enter information in the output fields (100–156) to send simulated information to the ISCS.
Information in decimal form, for example processed volume, is written as actual values.
Information in binary form, for example command status, is written as a bit pattern. The key
for the bit pattern is found in chapter 6. Installation description and drawings, section System
interfaces.
Note: Only implemented signals needs to be tested.
7. Make sure that values and status information is displayed correspondingly in the ISCS.
8. Go to page 5.6 Remote interface 2. Enter information in the alarm output fields (170–199)
to send simulated information to the ISCS. Make sure that the alarms are displayed
correspondingly in the ISCS.
9. To test information from ISCS to PLC: In the ISCS, activate input commands corresponding
to address 000–099 in page 5.5. (Note that address 013 does not need to be tested; it was
tested at the beginning of this procedure.)
10. Make sure that the information is updated correspondingly in page 5.5.
11. In the control panel, restore all changed values after the communication test. If not, commands
might be executed involuntarily, when the system is set to online again. Most important is that
address 001 displays ”00000000”.
12. Press the Online button to set the system in online mode.
• Take a backup according to instruction Export control system log files on page 67. The files are
required to be saved for at least 24 months.
• Take a backup according to instruction Backup control system settings. Note that this backup is
not used to reload settings, it is only a safety backup.
• We recommend that a screen dump is taken for all parameter pages. (To do that: Insert a USB
into the panel and press function button Utilities, and Print for all pages.) Alternatively, take a
photo. This will facilitate resetting of the parameters.
• The release notes must have been read for the version to be installed.
• Flash card with correct version of the PLC software.
• USB memory with correct version of the HMI software. If the remote interface option is used,
the signal standard (RS422 or RS485) must match the standard used by the ISCS (ships
integrated control system) for communication with PureBallast.
Follow the steps below
2. Remove the old compact flash card from the PLC in the control cabinet, and insert the compact
flash card with the new software.
3. At the rear side of the control panel: Open the small cover and turn DIP switch 1 to position ON.
7BeijerMODE
4. Turn on the power to the control cabinet and wait for the panel to reboot.
5. Touch the screen to display a menu: Press “Erase project” and then answer Yes. (If the
system requests a touch calibration, perform it and then erase project.) Wait for popup to
confirm that the project is erased.
6. At the rear side: Pull out the power cable from the control panel, turn DIP switch 1 to position
OFF, insert the USB memory and reconnect the power.
7. Wait for the message “Copy project from USB”. Press Yes.
8. Wait until the program is started and page 1.1 Overview is displayed. Pull out the USB memory.
9. Go to page 5.1 System info. Press the Set default button in page section Backup and
restore, Parameters.
10. Set all parameters in Parameter page 8.1–8.6. Use the screen dumps/photos as reference.
Make sure to set new parameters included in the new version, if any. New parameters are
stated in the release notes.
11. If remote control panels are installed, update the HMI software for the other panels according
to Update HMI software below.
• USB with correct version of the software. Note that the same version must be used for the HMI
and PLC software (same version number).
• If the remote interface option is used, the signal standard (RS422 or RS485) must match the
standard used by the ISCS (ships integrated control system) for communication with PureBallast.
Follow the steps below
1. At the rear side of the control panel: Pull out the power cable from the 24V DC port. Open the
small cover on the rear side. Turn DIP switch 1 to position ON.
7BeijerMODE
2. Re-connect the power cable and wait for the panel to reboot.
3. Touch the screen to display a menu: Press “Erase project” and then answer Yes. (If the
system requests a touch calibration, perform it and then erase project.) Wait for popup to
confirm that the project is erased.
4. At the rear side: Pull out the power cable from the control panel, turn DIP switch 1 to position
OFF, insert the USB memory and reconnect the power.
5. Wait for the message “Copy project from USB”. Press Yes.
6. Wait until the program is started and page 1.1 Overview is displayed. Pull out the USB memory.
7. If remote control panels are installed, repeat this instruction for all remote control panels.
1. At the rear side of the control panel: Pull out the power cable from the 24V DC port. Open the
small cover on the rear side. Turn DIP switch 1 to position ON.
7BeijerMODE
3. Wait for request to upgrade and delete project. Answer Yes to both. (If you don’t get the
question, set DIP switch to OFF, and try again. Or copy the files to another type of USB
memory.)
4. Wait for the request on screen to update software. Press Yes within ten seconds.
Result: The new software is downloaded to the panel.
5. Wait for request to reboot: Remove the USB and reboot the panel. (Some older panels freeze
at this stage. If so, pull out the power cable and reconnect it to reboot.)
6. When the screen has rebooted: Follow the instructions on screen to perform a touch calibration.
7. In the menu displayed: Press “IP settings”, and set according to instruction Set control panel IP
address on page 73. The firmware is now installed.
8. Next step is to install the HMI software. This must be done after the firmware has been
updated. Go to step 3 in instruction Update HMI software.
9. If remote control panels are installed, repeat this instruction for all remote control panels.
1. Pull out the power cable from the 24V DC port on the rear side of the control panel.
2. Open the small cover on the rear side. Turn DIP switch 1 to position ON.
7BeijerMODE
3. Re-connect the power cable. Wait for a cross is displayed on the screen.
4. Press the cross until it changes position. Repeat until the menu is displayed again.
Result: Calibration is ready.
Alarm history and important events are logged in the control system. The log also include
components connected via the log box.
The control system store all alarms and relevant events for at least 24 months. The memory has
a vast safety margin but when it is full, data will be deleted starting with the oldest logs. Logged
information can be exported to a USB memory stick. Logged information can be exported to a USB
memory stick. See Export control system log files on page 67.
Event log certificate: Contains events relevant to the IMO certificate. These events are stored
for 24 months. Events included are equal to the events that are GPS stamped in the table below,
with exeption for events regarding the log box (5010—5220).
The GPS stamp column indicates if the event is stamped with GPS position (Y=yes, N=no).
5010 Log box: Valve V01 position change: [X]. 1=Closed. 0=Not closed. Y
5011 Log box: Valve V01 position change: [X]. 1=Open. 0=Not open. Y
5020 Log box: Valve V02 position change: [X]. 1=Closed. 0=Not closed. Y
5021 Log box: Valve V02 position change: [X]. 1=Open. 0=Not open. Y
5030 Log box: Valve V03 position change: [X]. 1=Closed. 0=Not closed. Y
5031 Log box: Valve V03 position change: [X]. 1=Open. 0=Not open. Y
5040 Log box: Valve V04 position change: [X]. 1=Closed. 0=Not closed. Y
5041 Log box: Valve V04 position change: [X]. 1=Open. 0=Not open. Y
5050 Log box: Valve V05 position change: [X]. 1=Closed. 0=Not closed. Y
5051 Log box: Valve V05 position change: [X]. 1=Open. 0=Not open. Y
5060 Log box: Valve V06 position change: [X]. 1=Closed. 0=Not closed. Y
5061 Log box: Valve V06 position change: [X]. 1=Open. 0=Not open. Y
5070 Log box: Valve V07 position change: [X]. 1=Closed. 0=Not closed. Y
5071 Log box: Valve V071 position change: [X]. 1=Open. 0=Not open. Y
5080 Log box: Valve V08 position change: [X]. 1=Closed. 0=Not closed. Y
5081 Log box: Valve V08 position change: [X]. 1=Open. 0=Not open. Y
5090 Log box: Valve V09 position change: [X]. 1=Closed. 0=Not closed. Y
5091 Log box: Valve V09 position change: [X]. 1=Open. 0=Not open. Y
5100 Log box: Valve V10 position change: [X]. 1=Closed. 0=Not closed. Y
5101 Log box: Valve V10 position change: [X]. 1=Open. 0=Not open. Y
5110 Log box: Valve V11 position change: [X]. 1=Closed. 0=Not closed. Y
5111 Log box: Valve V11 position change: [X]. 1=Open. 0=Not open. Y
5120 Log box: Valve V12 position change: [X]. 1=Closed. 0=Not closed. Y
5121 Log box: Valve V12 position change: [X]. 1=Open. 0=Not open. Y
5130 Log box: Valve V13 position change: [X]. 1=Closed. 0=Not closed. Y
5131 Log box: Valve V13 position change: [X]. 1=Open. 0=Not open. Y
5140 Log box: Valve V14 position change: [X]. 1=Closed. 0=Not closed. Y
5141 Log box: Valve V14 position change: [X]. 1=Open. 0=Not open. Y
5150 Log box: Valve V15 position change: [X]. 1=Closed. 0=Not closed. Y
5151 Log box: Valve V15 position change: [X]. 1=Open. 0=Not open. Y
5160 Log box: Valve V16 position change: [X]. 1=Closed. 0=Not closed. Y
5161 Log box: Valve V16 position change: [X]. 1=Open. 0=Not open. Y
5170 Log box: Valve V17 position change: [X]. 1=Closed. 0=Not closed. Y
5171 Log box: Valve V17 position change: [X]. 1=Open. 0=Not open. Y
5180 Log box: Valve V18 position change: [X]. 1=Closed. 0=Not closed. Y
5181 Log box: Valve V18 position change: [X]. 1=Open. 0=Not open. Y
This section gives a detailed description of the PureBallast processes. The processes are divided
into three main processes, with sub processes, with indications of automatic and manually initiated
steps.
• Ballast
• Deballast
• CIP
• Deactivate system
• Change flow (set flow before a ballast or deballast process)
• Manual mode.
3 BallastProcess
2. Request from control system to open overboard (outside PureBallast system). (Handled
automatic, if external component signal is enabled.)
3. Overboard valve opened by operator and confirmed in control system. (Handled automatic, if
external component signal is enabled.)
Component activities:
• - Start P401-1 (booster pump for LDC cooling water) (if used)
- Open V403-35 (cooling water inlet)
- Open V201-32 (filter outlet)
• Start P403-1 (booster pump for reactor cooling water) (if used).
4. Power management
Automatic power request from PureBallast to vessel’s power management system (if
integrated).
5. UV lamp warming
Component activities:
1. Component activities:
• Start automatic control of control valve (V201-8) based on input from the pressure transmitter
• Open V309-1
• Start M709-42.
2. Filter back-flush is performed (1-100 seconds).
Component activities:
• Stop M709-42
• Close V309-1
• Start automatic control of control valve (V201-8) based on input from the flow meter.
Purpose: To increase the ballast water flow during ballasting (full ballast).
• - Start UV lamps
- Start counter: UV lamp runtime
• Open V201-20 (reactor outlet)
• Close V404-36 (cooling water outlet)
• Start automatic control of control valve (V201-8) based on input from the flow meter.
1. Operator adjusts the certified flow manually from the control system.
Component activities:
• Start automatic control of control valve (V201-8) based on input from the flow meter.
• - One or more AOTs are switched of
- Stop counter: UV lamp runtime
- Close V201-19 (reactor inlet)
• Close V201-20 (reactor outlet)
• Automatic power request adjustment (if integrated).
1. Operator pause the ballast process manually. Pause can also be initiated by an external signal,
for example when heeling is initiated from the ISCS. In this case, the process is resumed
automatically when the heeling signal is deactivated.
2. Request from control system to stop ballast water pump (outside PureBallast system). (Handled
automatic, if external component signal is enabled.)
5.
Resume ballasting
Operator resumes the ballast process manually.
Component activities:
• Stop P401-1 (booster pump for LDC cooling water) (if used)
• Stop P403-1 (booster pump for reactor cooling water) (if used), only needed if stop from
pause mode
• Switch off UV lamps
• Stop counter: UV lamp runtime
• - Close V201-19 (reactor inlet)
- Close V201-20 (reactor outlet)
• Stop counter: Accumulated water
• - Close V403-35 (cooling water inlet), only needed if stop from pause mode
- Set V201-8 (control valve) to parameter set opening percent.
• Close V201-32 (filter outlet)
• Automatic withdrawal of power allocation (if integrated).
2. Filter back-flush
Back-flushing of filter starts, including the following activities:
• - Start automatic control of control valve (V201-8) based on input from the pressure
transmitter
- Open V309-1
- Start M709-42.
3. Back-flush is performed. Approximate duration: 20 seconds.
• - Stop M709-42
- Close V309-1.
4. Request from control system to stop ballast water pump (outside PureBallast system). (Handled
automatic, if external component signal is enabled.)
5. BW pump stopped by operator and confirmed in control system.
3 DeBallastProcess
• - Start P401-1 (booster pump for LDC cooling water) (if used)
- Open V403-35 (cooling water inlet)
• Start P403-1 (booster pump for reactor cooling water) (if used).
4. Power management
Automatic power request from PureBallast to vessel’s power management system (if integrated).
5. UV lamp warming
Component activities when power has been granted:
• Start UV lamps
• Start counter: UV lamp runtime
• Open V201-20 (reactor outlet)
• Set V201-8 (control valve) to parameter set opening percent.
8. Request from control system to start ballast water pump (outside PureBallast system). (Handled
automatic, if external component signal is enabled.)
9. BW pump started by operator and confirmed in control system.
Component activities:
Purpose: To increase the ballast water flow during ballasting (full deballast).
1. Operator adjusts the certified flow manually from the control system.
2. Automatic power request from PureBallast to vessel’s power management system (if integrated).
3. AOT filling:
4. Component activities when added AOTs are filled, indicated by LS201-29. During warm-up, the
lamps are cooled with fresh water.
• Start UV lamps
• Start counter: UV lamp runtime
• Open V201-20 (reactor outlet)
• Open V201-19 (reactor inlet) on running AOTs
• Close V310-6 (CIP, AOT fresh water filling)
• Close V320-4 (reactor, CIP drain)
• Close V404-36 (cooling water outlet)
5. Start automatic control of control valve (V201-8) based on input from the flow meter.
Purpose: To decrease the ballast water flow during deballasting (full deballast).
1. Operator adjusts the certified flow manually from the control system.
2. Component activities:
1. Operator pause the deballast process manually. Pause can also be initiated by an external
signal, for example when heeling is initiated from the ISCS. In this case, the process is resumed
automatically when the heeling signal is deactivated.
Component activities:
4. Resume deballasting
Operator resume the deballast process manually.
Component activities:
5. Request from control system to start ballast water pump” (outside PureBallast system).
(Handled automatic, if external component signal is enabled.)
6. BW pump started by operator and confirmed in control system.
Component activities:
• Stop P403-1 (booster pump for reactor cooling water) (if used)
• - Close 403-35 (cooling water inlet)
- Close 404-36 (cooling water outlet)
• Start counter: Accumulated water.
• Stop P401-1 (booster pump for LDC cooling water) (if used)
• Stop P403-1 (booster pump for reactor cooling water) (if used), only needed if stop from
pause mode
• Switch off UV lamps
• Stop counter: UV lamp runtime
• - Close V201-19 (reactor inlet)
- Close V201-20 (reactor outlet)
• Close V403-35 (cooling water inlet), only needed if stop from pause mode
• Set V201-8 (control valve) to parameter set opening percent
• Close V201-9 (main inlet valve).
2. Request from control system stop ballast water pump (outside PureBallast system). (Handled
automatic, if external component signal is enabled.)
3. BW pump stopped by operator and confirmed in control system.
4. Request from control system to close overboard. (Handled automatic, if external component
signal is enabled.)
6.4 CIP cycle
The CIP cycle is run to remove seawater scaling from the AOT reactor after ballast and deballast.
The process is performed for used AOT in sequence. The process can start directly after ballast or
deballast process, or be delayed. A CIP process is started manually according to instruction CIP
clean AOT after ballast / debalalst on page 58. Note that the process can be stopped at any time.
3 CIPprocess
• - Stop P321-5
- Close V571-1 (CIP, deaeration valve)
- Close V460-2 (CIP, drain valve)
- Close V321–2 (AOT, upper CIP return valve)
- Close V320–4 (AOT, lower CIP return valve).
• - Open V310-1
- Open V309-1
- Start M709-42.
2. Component activities after the filter is filled:
• - Stop M709-42
- Close V309-1
- Close V310-1.
3. Request from control system to close overboard valve (outside PureBallast system). (Handled
automatic, if external component signal is enabled.)
4. Overboard valve closed by operator and confirmed in control system.
• Operate components from the flow chart. Tap a component to operate it from the displayed
popup window. The following components can be operated: valves, motors, UV lamps etc,
digital output signals.
• Operate and simulate power management.
The following limitations exist for manual mode:
• Requires login level 2. The Manual mode button is only displayed for login level 2.
• Only login level 3 can set operate control valve V201–8.
• Flow in pipes is not indicated in flow chart.
• Can only be activate from standby mode. PID calibration can not be activated at the same time.
• No automatic processes can be run.
To activate: Press the Manual mode button in page 1.1 Flow chart and follow the instructions
Operate UV components manually and Operate UV lamps manually.
To deactivate: Press the Manual mode button again in page 1.1 Flow chart or log out. All forced
outputs and manual changes are reset and the system goes to Standby mode.
1.1 Introduction
This is a quick guide to the most common routines performed in the PureBallast control system.
More detailed instructions are found in the PureBallast manual.
• The Alarm list (page 3.1) must be controlled to verify that there are no alarms needing attention.
• There must be available power for the system. If power management is integrated, this will be
done automatically. If power management is not integrated, confirm this manually.
1.2 Ballast and deballast
Follow the steps below
2. Check the Certified flow field to see if it is OK. If not, change flow according to instruction
Change flow.
4. Wait for the message “Confirm overboard valve open”. Open the valve and then press the
button in the popup to confirm the action. (The popup is not displayed if the component
feedback is integrated with the control system.)
5. Wait for the message “Confirm ballast pump started”. Start the pump and then press the button
in the popup to confirm the action. (The popup is not displayed if the component feedback is
integrated with the control system.)
6. When desired amount of water has been processed, press the function button Stop to end
the process.
7. Wait for the message “Confirm overboard valve open” and “Confirm ballast pump started”.
Handle accordingly. (The popup is not displayed if the component feedback is integrated
with the control system.)
An alarm is indicated by a audible signal and by a blinking warning icon in the control panel.
• Never reset an alarm without first finding and attending to the problem.
Follow the steps below:
3. If the process have stopped: Take action to eliminate what has caused the alarm.
4. If the alarm is caused by a faulty AOT module, the ballast/deballast process has to be restarted
with another AOT according to the Perform ballast instruction.
5. If the process continues: Consider if the process shall be terminated. Take action to eliminate
what has caused the alarm.
Press the Ack selected button after the problem has been dealt with. If you want to
acknowledge all alarms, press the Ack all button.
• The system must be in standby mode. This means that this operation cannot be executed
during ballast or deballast.
• Complete status information regarding CIP is displayed in page 1.4 CIP status. The page
displays remaining time for ongoing CIP cycles, remaining time before individual AOTs are
required to be CIP:ed etc.
Follow the steps below
3. Wait for the message “Confirm overboard valve open”. Open the valve and then press button
in the popup to confirm the action.
Result: The automatic CIP cycle starts. The CIP cycle takes 15 minutes per AOT.
4. Wait for the message “Confirm overboard valve closed”. Close the valve and then press button
in the popup to confirm the action.
• Required USB memory capacity is indicated in the Export PLC events dialog box.
Follow the steps below:
3. Wait for message: Insert USB in PLC. Place a USB memory in the Main PLC module (A01) in
the control cabinet.
4. Chose one of the following alternatives to decide time interval for the information to be copied:
• Accept suggested default time interval in the Start and End fields. Default start date is the
oldest file in the system, and default end date is today’s date.
• Select the Specify time interval box, and enter desired interval in the Start and End fields.
5. Press one of the following function buttons: Events, Cert events or Alarms.
Result: The information is copied to the USB memory indicated by a green checkmark on
the button during copying.
6. Wait for the message "Export OK" to appear. If desired, export next category of events using
the function buttons.
Result: A folder named PureBallast has been downloaded. It contains three sub folders:
Alarm, Cert and Event. The folder corresponding to your export choice contains a CSV file.
3
1 Introduction
This chapter contains information about parameters in the control system and flow transmitter.
It covers:
This section describes all parameters set in the PureBallast control system.
NOTE
• The control system display parameters pages are login dependent according to the following:
– Login level 0: Parameter page 8.2–8.6 are displayed.
– Login level 1: Parameter page 8.2–8.6 are displayed. Full access to pages 5.7 and 5.8.
– Login level 2: Full access to parameter page 8.2–8.6 (but not set remote control settings).
– Login level 3: Full access to all parameter pages.
• The parameter settings can be exported to a USB memory for safety backup, and be restored
from a backup. See chapter 3. Operating instructions and control system description for
instructions.
The installation specific parameters are set to reflect the specific installation and shall normally only
be checked and adjusted at first start up, during preparations for commissioning.
The installation specific parameters are found in the pages listed below:
- p200: Time-out AOT draining. This parameter is evaluated during the commissioning
preparation test and adjusted if necessary.
• Page 8.4 Filter parameters:
Control system parameters are identified by item numbers with the following syntax: pX00.
Parameter pages
Parameters are sorted on the following pages according to the area of applicability:
In the parameter pages, the parameters are displayed with the following information:
Elements Description
4 8.1
p100 High pressure, 7.00 1–10 bar Setpoint for shut down due to high
shutdown trigger pressure at PT201-16.
(PT201-16)
(7 bar = 0.7 MPa)
p101 High pressure, 6.00 0–10 bar Setpoint for warning due to high pressure
warning trigger at PT201-16.
(PT201-16)
(6 bar = 0.6 MPa)
p103 Low pressure, 0 -1–2 bar Setpoint for warning due to low pressure
warning trigger at PT201-16.
(PT201–16)
(1 bar = 0.1 MPa)
p105 Transition trigger, 50 10– m3/h Defines which flow that must be
ballast flow 500 established, before the process goes
established from ballast start-up to full ballast.
(FIT201-1)
p113 Min % open for 20 10–100 % During ballast and deballast, valve
V201-8 V201–8 handles the automatic pressure
and flow control.
p114 Maximum rotation 10 1–90 °/s Defines maximum rotation rate to attain
rate for V201-8 a smooth automatic pressure and flow
control.
p115 Maximum travel 10 2–30 sec Maximum time for V201–3 and V201–9
time for valves to go from opened to closed, and vice
versa, before a warning is issued.
p116 Low flow, warning 10 10–90 % Set point for low flow warning, defined as
trigger (FIT201-1) percent of certified flow.
p117 Max delay of CIP 6 0–24 hrs Define max delay, in hours, before a CIP
cycle, hours cycle must be performed after ballast or
deballast.
p118 Max delay of CIP 1 0–30 day Define max delay, in days, before a CIP
cycle, days cycle must be performed after ballast or
deballast.
p119 Valve travelling 5 1–10 sec Maximum time for V201–8 to go from
time for 201-8 opened to closed, and vice versa, before
a warning is issued.
p120 V201–8 PID 0.30 0–10 N/A Defines proportional gain (Pf) value used
proportional gain for PID regulation of V201–8 during
ballast and deballast.
p121 V201–8 PID 7.0 0–100 sec Defines integral time (If) value used for
integral time PID regulation of V201–8 during ballast
and deballast.
p122 V201–8 PID 0 0–100 N/A Defines derivate gain (Df) value used for
derivative gain PID regulation of V201–8 during ballast
and deballast.
Normal value: 0.
p126 LDC after cooling. 5 0–60 min Defines how long after a ballast or
(Stop delay for deballast process the booster pump shall
401-1, if installed) run to cool the LDC.
p138 Timeout: Time 5 1–5 min Defines maximum time a ballast and
in Pause before deballast process can be puased. After
going to Stop defined time, the process is stopped.
p140 Timeout: 5 1–10 min Time the control system will wait for
Request "Confirm confirmation signal from ISCS, hard
overboard valve wire or manually in popup before
open" displaying message that operation was
not performed.
p141 Timeout: Request 5 1–10 min Time the control system will wait for
"Confirm ballast confirmation signal from ISCS, hard
pump started" wire or manually in popup before
displaying message that operation was
not performed.
p143 Timeout: Power 60 1–300 sec Time the control system will wait for
granted signal not confirmation signal from ISCS that the
received operation was performed.
p144 Timeout: Start-up 60 30–300 sec Time the control system will wait for
ballast flow accepted minimum flow (p105) to be
established established before automatic stop.
p145 Sequence step 1.0 0.0–5.0 sec Defines delay between each step in the
delay process.
p149 Timeout: Time in 10–300 45 sec Defines maximum time a ballast and
Auto pause before deballast process can be automatically
going to stop paused by the system. Example: When
process is paused due to low flow.
4 8.2
• Not used
• Hardwire ranged
• Hardwire fixed
• Remote interface (requires that p132
is activated)
p129 Booster pump Not N/A Drop Defines if a booster pump is used when
(P401-1) for LDC used list pressure for cooling water to LDC is too
cooling water low.
p130 Booster pump Not N/A Drop Defines if booster pump is used when
(P403-1) for used list pressure for cooling water to AOT reactor
reactor cooling is too low.
water
Alternatives: Activated or Not used.
p132 Remote interface Not N/A Drop Defines if remote interface (optional) is
via modubus used list used and connected via modbus.
p133 Max time 60 0–300 Sec Define max delay before the system
communication shuts down after communication is
loss PLC/remote lost between the PLC and the remote
interface interface (optional). The value must be
greater than the heartbeat signal interval
defined in the ISCS.
p134 External stop Not N/A Drop Defines if an additional stop button for
button used list PureBallast is installed.
p135 External shut Not N/A Drop Defines if an additional signal controlled
down signal used list stop function for PureBallast is installed.
p137 Hide Pause Not N/A Drop Defines if the Pause button is hidden in
button used list the control system.
p161 Time interval for 1 0.1–60 Min. Time interval to update the amount (m3)
log event 331 of ballast water treated in log file.
p162 Time interval for 1 0.1–60 Min. Time interval to update the amount (m3)
log event 341 of deballast water treated in log file.
p165 Additional Not N/A Drop Defines if a third additional by-pass valve
by-pass signal used list is used. The signal gives information if
3 the valve is opened during process, so
that PureBallast is by-passed.
p166 Pressure PID 0.6 0–10 N/A Defines proportional gain (Pf) value used
proportional gain for PID regulation of V201–8 during
back-flush.
p167 Pressure PID 7 0–100 sec Defines integral time (If) value used
integral time for PID regulation of V201–8 during
back-flush.
p168 Pressure PID 0 0–100 N/A Defines derivate gain (Df) value used
derivate gain for PID regulation of V201–8 during
back-flush.
Normal value: 0.
4 8.3
p200 Timeout: AOT 2 0.5–5.0 min Time the control system will wait for
draining confirmation that an AOT is drained
before an alarm is issued. Recommended
setting: Approx 0.5-1.0 minute more than
actual drain time.
p201 Timeout: Reactor 2 1–10 min Time the control system will wait for
cooling water confirmation that cooling water has filled
(LS201-29) the AOT before an alarm is issued.
p202 High temp, 60 10–100 ºC Setpoint for high water temperature alarm,
alarm trigger indicated by temperature transmitter in
(TT201-33) AOT reactor.
p204 Low temp, 0 0–40 ºC Setpoint for low water temperature alarm,
alarm trigger indicated by temperature transmitter in
(TT201-33) the AOT reactor.
p206 Alarm delay for 5 0–10 sec Delay before alarm is issued after setpoint
sensor TT201-33 temperature (p202 and p204) is reached.
p210 UV lamp warm-up 90 0–90 sec Warm up time for UV lamps before full
time ballast or deballast starts.
p211 UV lamp cooling 120 30–300 sec Cooling time for UV lamps after ballast
time or deballast.
p212 Timeout: UV lamp 100 10–100 sec Time the control system will wait for
ignition confirmation signal that UV lamps are
ignited. If no lamps are ignited or if less
lamps than set in parameter p213 are
ignited, the AOT will be automatically
stopped.
p215 Alarm delay for 5 0–10 sec Delay before shutdown when there is no
LS201-29 water in an AOT, indicated by level switch
in AOT (LS201-29).
p216 Timeout: Fluid 5 2–10 min Setpoint for max time to fill an AOT with
fill-up time AOT fresh water before an alarm is issued.
p221 Low UV intensity 20 0–500 W/m2 Setpoint for warning due to low UV
warning trigger intensity indicated by UV sensor
(optional) QT201–50 in the AOT reactor.
This warning will be logged in the Event
log.
4 8.4
p301 High filter 0.50 0.00– bar Setpoint for high pressure warning,
differential 1.00 indicated by pressure transmitter
pressure, PT201-27.
warning trigger
(PT201-27) (0,5 bar = 0.05 MPa)
p304 Required 2.50 1.00– bar Defines pressure needed for efficient
pressure to 5.00 back-flushing. This pressure must be
start back-flush attained to start back-flush.
(PT201-16)
This parameter also defines setpoint
for desired pressure during back-flush:
To maintain this pressure, control valve
p305 Back-flush 0.38 0.00– bar Setpoint for automatic start of filter
trigger, 1.00 back-flush due to dirt in the filter, indicated
differential by differential pressure transmitter on the
pressure filter.
(PT201-27)
Note: This parameter can be adjusted, but
only by Alfa Laval during commissioning.
If adjusted, parameter p301 shall be set
to 30 percent higher.
p310 Back-flush initial 10 0–60 sec Time from back-flush trigger until
delay back-flush is started. During this delay the
control valve is PID regulated to create the
required pressure defined in parameter
p304.
p311 Back-flush delay 2.0 0.0– sec Defines for how many seconds the
(p305 during x 10.0 pressure defined in p305 must last, before
sec). automatic back-flush starts.
p313 V201-8 min 5 0–30 sec Time constant for low pass filter used for
position during the differential pressure over the filter.
back-flush The low pass filter is used to smoothen
the effect of sudden changes in differential
pressure; primarily pressure peaks after
completed back-flush.
p314 Filter type Type N/A Drop Defines type of filter installed.
1 list
Alternatives: Type 1 (Boll) and Typ 2
(Hydac).
4 8.5
p400 CIP cycle time 15 1–60 min Flow 500–3000: Duration of a CIP cycle
per AOT.
4 8.6
p110 Certified flow per 250 10– m3/h Defines the max amount of ballast water
AOT module 1000 that can be treated per hour and AOT.
p112 Pipe diameter for 150 150– DN This parameter shall be set to
flow meter 600 correspond to the dimension of the flow
meter (FIT201-1).
p213 Allowed no. of 0 0–12 No. If more lamps than set in this parameter
failed UV lamps are broken, operation will be denied.
per AOT
This parameter is preset and shall not
be changed.
N/A Remote panels N/A N/A N/A Used to set IP adresses for remote
control panels (optional). See instruction
Set control panel IP address in chapter
3. Operating instructions and control
system description.
p150 Ex proof system Not N/A Drop Defines if the Ex proof version of
used list PureBallast is installed. This affects
both installation and control system.
p500 Log box Not N/A Drop Defines if the log box (optional ) is
used list activated to monitor and log external
valves and pumps, that are not part of
Alfa Laval’s scope of supply.
This section describes the parameters set in the parameter pages in the flow transmitter, installed
on the flow meter.
General (non-installation specific) parameters are preset to function for all systems. They must only
be adjusted, by Alfa Laval, if required by performance reasons or similar. They are checked during
preparations for commissioning and shall normally not be adjusted after start up.
4FTPanel
Buttons used:
2. To enter password (1000): Press Padlock. (A line appears under the first zero.)
- Press Change to change the first 0 to 1.
- Press Padlock to set the value.
- Result: The “Basic settings” menu appears after two seconds.
Set Qmax
4. Press Forward until “Qmax” is displayed. Check that the parameter is set to 1200 m3/h for
pipe size 300 .
- To change: Press Padlock.
- Press Select to select digit to change (A line is placed under the changeable digit).
- Press Change to change (toggle) the digit.
- Press Padlock to set the value.
5. Press Forward until “Empty pipe” is displayed. Check that the parameter is set to “On”.
- To change: Press Padlock.
- Press Change to change (toggle) the setting.
- Press Padlock to set the value.
8. Press Padlock to display the setting. Check that the parameter is set to “On”.
- To change: Press Padlock.
- Press Change to change (toggle) setting.
- Press Padlock to set the value.
9. Press Forward until Current output (mA setting) is displayed. Check that the parameter is
set to “4-20 mA”.
- To change: Press Padlock.
- Press Change to change (toggle) setting.
- Press Padlock to set the value.
3
1 Introduction
This chapter covers information about alarms and warnings, together with information about how
to solve the problems causing the alarms to trip. The chapter also contains a list of solutions for
problems that may occur, but that is not indicated by any system.
• control system
• lamp power supply (LPS)
• flow meter (with fault finding instruction)
• I/O system and X20 modules.
See chapter 3. Operating instructions and control system description to find
This section lists all alarms and warnings related to the PureBallast system.
3Alarm
If the optional remote interface is installed, the alarm is also indicated on the remote interface
screen. All alarms are displayed in the control panel’s page 3.1 Alarm list and are sorted in order of
occurrence; most recent alarm at the top of the list.
Column in Description
table
Alarm ID Identification number of the alarm. The number is also indicated in the control
system alarm list.
- A = Alarms stop the ongoing process, which can be restarted after the
problem has been attended to.
- W = Warnings are notification of a status change or a problem. Warnings
allow the process to continue.
• 1: If the alarm contains three digits, the first digit indicates component
according to: 1=AOT and 2 =Filter. If the alarm contains two digits, the
alarm is general and is not connected to a specific component.
Alarm text / The text displayed in the control system. Note that AOT number is indicated by
Problem “x” in the table, instead of the actual AOT number. In the control system alarm
text, the actual AOT number is stated for the AOT concerned.
For problems not indicated by an alarm, the text gives a general explanation
of a problem that can occur.
Trigger / Trigger: Source of the alarm or warning, identified by the input sensor’s item
Parameter number or equivalent.
Parameter: The parameter controlling the alarm, when applicable.
Delay: Time before the alarm is activated after the condition of the alarm is met.
Active during step: Under which steps in the process the alarm is active.
Additional information in parenthesis, for example if the alarm also stop the
ongoing process step. The steps are described in chapter 3. Operating
instructions and control system description, section Detailed process description.
Comments: Additional information or explanations.
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A01 Process Trigger: PT201-16 Delay: 2 sec. Ballast water pump Check pressure and flow from
pressure too Parameter: p100 gives too high ballast pump(s). If the pressure
high (PT201-16). Active during step: pressure. exceeds set value: Adjust incoming
Automatic stop. pressure to PureBallast.
9
Control system
10
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A03 Process Trigger: PT201-16 Delay: 2 sec. Signal missing 1. Check fuse F45 in Control
pressure or pressure cabinet to see what circuit
signal missing Active during step: transmitter PT201-16 caused the fuse trip.
(PT201-16). All steps. malfunction.
2. Use the circuit diagram to
Control system
Automatic stop.
Comment: Error check the fuse setting, adjust
in system pressure according to figures in circuit
sensor. Indication of diagram if necessary and reset
pressure -1.0 bar (-0.1 fuse.
MPa) is not an error. 3. Use the circuit diagram to
locate the component or find
the reason that caused the fuse
trip and attend to it.
4. Check cables to the
component. See Control
cabinet / Circuit diagram
in chapter 6. Installation
description and drawings.
5. Check that all electrical
connections are OK and that
the electrical wiring is not
damaged.
2
W04 Process Trigger: PT201-16 Delay: 2 sec. See possible cause See A01.
pressure too Parameter: p101 for A01.
high (PT201-16). Active during step:
All process steps.
Comment: Pressure
higher than parameter
set limit.
List of alarms and warnings
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A10 Process flow Trigger: FIT201-1. Delay: 5 sec. Signal missing or flow 1. Check fuse F45 in Control
signal missing Parameter: N/A transmitter FIT201-1 cabinet to see what circuit
(FIT201-1). Active during step: malfunction. caused the fuse trip.
All steps.
2. Use the circuit diagram to
Comment: Error in check the fuse setting, adjust
according to figures in circuit
transmitter display,
message error)
11
Control system
12
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W12 Process Trigger: FIT201–1 Delay: 30 sec. Flow rate higher than Reduce the incoming ballast water
flow higher Parameter: p101 the certified flow for flow to the PureBallast system.
than certified Active during step: the number of AOTs
(FIT201-1). in operation.
Control system
A13 Process flow too Trigger: FIT201–1 Delay: 20 sec. Flow too low. • Increase flow.
low (FIT201-1). Parameter: p116
Active during step: • Make sure the ballast water
Automatic
from the ballast pump is
pause.
• Ballast (Pause) directed to PureBallast. When
OK the process will continue
• Deballast (Pause)
2
automatically.
Comment: If flow • Check pressure and flow
is less than set in from ballast pump(s).
parameter p116, Adjust incoming pressure
the system is set in to PureBallast, if necessary.
pause mode time set in
parameter p149, where Flow sensor Check that the flow sensor is OK
after it is set to pause malfunctions. as described in Problem 7 B and
mode. 7 I in the general problems list on
page 61.
List of alarms and warnings
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
process description.
A14 Process Trigger: FIT201-1 Delay: Set in Control valve V201–8 See alarm A17.
flow too low Parameter: p105 parameter p144. malfunctions.
during start-up
(FIT201-1). Active during step: Flow too low. See alarm A13.
Automatic stop.
• Ballast start-up
(stop)
• Ballast pause
2.1
(stop)
• Deballast start-up
(stop)
• Deballast pause
(stop)
13
Control system
14
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A17 Valve error Trigger: Limit switch Delay: 15 sec. Fuse tripped. 1. Check fuses F43 in control
(V201-3). GS201-3. cabinet to see what circuit
Parameter: N/A. Active during step: caused the fuse trip.
All steps.
2. Use the Control cabinet /
Control system
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A23 Valve error Trigger: Limit switch Delay: 15 sec. See possible cause
(V201-9). GS201-9. for A17.
Parameter: N/A. Active during step:
All steps.
Comment: Error on
2.1
valve V201–9.
15
Control system
16
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A29 Valve error Trigger: Limit switch Delay: 15 sec. See possible cause
(V201-8). GS201-8. for A17.
Parameter: N/A. Active during step:
All steps. • Sensor error. 1. Check open indication in the
Control system
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A33 Bypass valve is Trigger: Limit switch Delay: 15 sec. The valve has been Close valve V212-31
open (V212-31). GS212-31. opened manually or
Parameter: N/A Active during step: via the ISCS.
• Ballast (stop)
• Back flush (stop)
• Deballast start-up
(stop)
• Deballast (stop)
Comment: If valve
V212-31 is in open
position, ballast or
deballast is cancelled.
The bypass valve is
not controlled by the
PureBallast system.
A35 Valve error Trigger: Limit switch Delay: 15 sec. See possible cause
(V212-31). GS212-31. for A17.
Parameter: N/A Active during step:
All steps.
2.1
Comment: Shutdown
of all steps exept CIP.
The alarm does not
prevent completion or
start of CIP cycle.
17
Control system
18
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W40 Process Trigger: Pressure Delay: 2 sec. Ballast water pump Check that pressure and flow
pressure too low transmitter: gives too low from ballast pump(s) is according
(PT201-16). PT201-16. Active during step: pressure. to requirements in chapter 6.
Parameter: p103. Installation description and
Control system
A48 Shutdown Trigger: Shutdown Delay: None. System shutdown Release the button.
activated button on control button on the control
(Shutdown cabinet Active during step: cabinet has been
button). Parameter: N/A All steps. activated (pressed NOTE
down).
Find out the reason why the system has
been shut down before releasing the
button.
2
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A50 Shutdown Trigger: System Delay: None. Manual shutdown Release the button.
activated outside PureBallast. from the ISCS
(External Parameter: p135 Active during step: (integrated ship
system). All steps. control system). NOTE
W58 Fuse tripped in Trigger: Control Delay: 2 sec. Possible reasons: 1. Check fuse F42–F45 in control
control cabinet. cabinet. • overload cabinet to see what circuit
Parameter: N/A Active during step: caused the fuse trip.
All process steps. • short circuit
2. Use the circuit diagram to
• overheated fuse
locate the component or find
the reason that caused the fuse
trip and attend to it.
3. Use the circuit diagram for
control cabinet to check the
fuse setting, adjust according
to figures in circuit diagram if
necessary and reset fuse.
2.1
19
Control system
20
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A66 Additional Trigger: External Delay: 2 sec. The valve has been Close the valve and resume the
bypass valve system. opened manually or process by pressing the Pause
1 is open. Parameter: p163 Active during step: via the ISCS. button in the control system.
Control system
• Ballast (stop
ballast)
• Back flush (stop
ballast)
• Deballast start-up
(stop deballast)
• Deballast (stop
deballast)
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A71 Ballast water Trigger: Control Delay: Set in Faulty connection of Check that all electrical
pump is system timer. parameter. electricity or signal connections are OK. Check that
not running. Parameter: p141. cable. the signal wiring is according to
Automatic stop. Active during step: information in chapter 6. Installation
description and drawings, section
• Ballast start-up External component signal
A75 Overboard valve Trigger: Control Delay: Set in See possible cause
is not open. system timer. parameter. for A71.
Automatic stop. Parameter: p140
Active during step:
• Ballast start-up
(stop)
• Ballast pause
(stop)
• Deballast start-up
(stop)
• Deballast pause
(stop)
• CIP
Comment: Feedback
2.1
“overboard valve is
OPEN”.
21
Control system
22
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A77 Error on all Trigger: AOT Delay: None An active alarm exist See page 3.1 Alarm list in the
operating modules on all installed AOTs. control system to see which AOT
AOT:s. Parameter: N/A Active during step: It can be the same alarms that preceded this alarm.
Automatic stop. error for all AOTs, or
Control system
W79 Power is Trigger: Control Delay: Set in Power management Investigate if the reasons for not
not granted. system timer. parameter. master system not granting power is outside the
Automatic stop. Parameter: p143 granting power for PureBallast system.
Active during step: one or more AOTs.
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W82 Heeling mode Trigger: Heeling Delay: 2 sec. Heeling mode has
requested (internal transfer) been activated by
by operator. requested in control Comment: The system external system.
Automatic system. is set in pause mode.
pause. Parameter: N/A If operation has not
been requested: See
A71.
2.1
W83 Heeling mode Trigger: Heeling Delay: None. See possible cause
cancelled (internal transfer) not for W82.
by operator. requested in control Comment: During
Process system. heeling, the system is
resumed. Parameter: N/A paused. At this point it
is resumed.
23
Control system
24
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A91 PLC lost Trigger: Control Delay: 60 sec. Panel is switched off 1. Switch on the panel.
communication system PLC. or faulty.
Active during step: 2. Restart the panel. See problem
with all control Parameter: N/A
All process steps. 1 B in the general problems list
panels.
on page 61.
Control system
W92 Master control Trigger: Control Delay: 30 sec. Master panel is See A91.
panel lost system PLC. switched off or faulty.
communication Parameter: N/A Active during step:
with the PLC. All process steps. Faulty cable See A91.
2
connection.
Comment: After
communication is lost,
ongoing process is
stopped in a controlled
way and the system
is shut down. This
message is visible
in the master control
panel.
List of alarms and warnings
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A93 Heart beat signal Trigger: Control Delay: Set in To operate PureBallast when communication is down,
from remote system PLC. parameter p133. follow the steps below:
interface is not Parameter: p133
updating. Active during step: 1. Set the system to Local mode: Press the Local button
All process steps. on the control panel.
2. Run the system from the control panel. Note that you
25
Control system
26
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
communication in chapter 3.
Operating instructions and
control system description.
A95 PLC battery low. Trigger: Control Delay: 30 sec. The voltage in the Replace PLC battery in the control
system PLC. battery in the control cabinet.
Parameter: N/A Active during step: system PLC is too
All process steps. low.
List of alarms and warnings
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W96 GPS signal not Trigger: Control Delay: N/A Faulty electrical Check that the signal wiring is
valid. system PLC. connection. according to Control cabinet /
Parameter: N/A Active during step: Interconnection diagram in chapter
All process steps. 6. Installation description and
drawings.
W97 PLC error in Trigger: N/A Delay: 2 sec. Error in module. Check the LED error indication for
control cabinet. Parameter: N/A the electronic modules in the LDC.
Active during step: See section I/O system and X20
All steps. modules on page 55.
27
Control system
28
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W100 AOT [x]: AOT Trigger: AOT Delay: Set in High temperature • Check that the inlet valves
temp too high temperature parameter p206. due to obstacles or (V201-19.x, V403-35) and
(TT201-33). transmitter TT201-33. error in one or more outlet valves (V201-20.x,
AOT shutdown. Parameter: p202 Active during step: components involved. 404-36.x) open properly by
Control system
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W101 AOT [x]: AOT Trigger: AOT Delay: Set in See possible cause
temp too low temperature parameter p206. for W100.
(TT201-33). transmitter TT201-33.
AOT shutdown. Parameter: p204. Active during step: Sea water too cold; See to that incoming water is
All steps. temperature below 0 warmer than 0 C°.
C°.
C°.
W102 AOT [x]: Trigger: AOT Delay: Set in parameter Signal missing 1. Check fuse F44 in LDC to see
AOT temp temperature p206. or transmitter what circuit caused the fuse
signal missing transmitter TT201-33 TT201-33.x trip.
(TT201-33). error. Active during step: malfunction.
All steps. 2. Use the circuit diagram to
AOT shutdown.
Parameter: N/A. check the fuse setting, adjust
according to figures in circuit
diagram if necessary and reset
fuse.
3. Use the circuit diagram to
locate the component or find
the reason that caused the fuse
trip and attend to it.
4. Check cables to the
component. See Lamp drive
cabinet (LDC) / Circuit diagram
in chapter 6. Installation
description and drawings.
2.1
29
Control system
30
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W107 AOT [x]: LDC Trigger: LDC Delay: 15 sec. No cooling water to Check that cooling water supply
Control system
cabinet temp too temperature the heat exchanger. (401) is within specification in
high (TT401). transmitter TT401. Active during step: chapter 6. Installation description
Parameter: p214 All steps. and drawings, section Connection
list in the General drawings section.
W109 AOT [x]: LDC Trigger: LDC Delay: 5 sec. Signal missing or 1. Check fuse F44 in LDC to see
cabinet temp temperature transmitter TT401 what circuit caused the fuse
2
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
damaged.
6. Replace transmitter TT401.
7. Restart the process from the
beginning.
31
Control system
32
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W116 AOT [x]: AOT Trigger: Level sensor Delay: Set in No fluid in AOT 1. Control that correct valves
fluid level LS201-29. parameter p215. reactor “x”. are opened for current
signal missing Parameter: p215 LS201-29.x is process. See Detailed process
(LS201-29). Active during step: indicating dry description in chapter 3.
Control system
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W118 AOT [x]: CIP Trigger: Level sensor Delay: Set in No fluid in AOT 1. Check that valves V320-2,
flow missing LS201-29. parameter p215. reactor “x”. V320-4.x, V321-4 and 321-2.x
(LS201-29). Parameter: p216 LS201-29.x is open and close correctly.
Active during step: indicating dry
2. Check that pump P320-1
condition.
• CIP (Stop) is functioning correctly. See
problem 6D−6I in the general
problems list on page 61.
2.1
33
Control system
34
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
Too low level in CIP Refill the tank with CIP liquid. See
tank. instruction Change and refill CIP
liquid in chapter 7. Service manual.
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W119 AOT [x]: No Trigger: Level sensor Delay: Set in No liquid in 1. Check that pressure flushing
freshwater LS201-29. parameter p216. AOT reactor “x”. water in pipe 310 is according
filling in AOT Parameter: p216 LS201-29.x is to requirements in chapter 6.
(LS201-29). Active during step: indicating dry Installation description and
condition. drawings, section Connection
• CIP (Stop fresh list.
W120 AOT [x]: AOT Trigger: Level sensor Delay: Set in Fluid in AOT reactor Restart the process from the
was not drained LS201-29. parameter p200. “x”. LS201-29.x beginning.
(LS201-29). Parameter: p215 is indicating wet
Active during step: condition.
35
Control system
36
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W122 AOT [x]: Fuse Trigger: LDC cabinet Delay: 1 sec. Fuse in LDC has Check LDC cabinet to see what
tripped in LDC for AOT tripped or has been circuit caused the fuse trip. Check
cabinet. Parameter: N/A Active during step: switched off. according to bullets.
All steps.
Control system
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W126 AOT [x]: MCB Trigger: LCD x-1 Delay: 1 sec. Motor circuit breaker 1. See LPS alarms in section
tripped in LDC Parameter: N/A (MCB) for an LPS in Lamp power supply (LPS) on
cabinet. Active during step: AOT.x has tripped or page 46.
All steps. has been switched
2. Check MCB F12 in LDC and
off.
Comment: respective cables and LPS unit.
37
Control system
38
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A130 AOT [x]: LPS Trigger: Lamp power Delay: 2 sec. • LPS malfunction. Check LED indication on the LPS
sum alarm. supply in AOT:s LDC. that triggered the alarm. See LPS
Active during step: • UV lamp
Parameter: N/A alarms in section Lamp power
malfunction.
supply (LPS) on page 46.
Control system
• Ballast start-up
• Ballast UV lamp OK signal Check that the signal wiring is
malfunction. according to electrical drawings.
• Back flush
• Ballast pause Check that all electrical
connections are OK on bus
• Ballast stop modules and that the electrical
• Deballast start-up wiring is not damaged.
• Deballast
• Deballast pause
• Deballast stop
W131 AOT [x]: UV Trigger: Lamp power Delay: 1 sec. One or more UV Change according to instruction in
system failure. supply. lamps is broken. chapter 7. Service manual.
Too many failed Parameter: p213. Active during step:
lamps. All steps
Comment: AOT is
2
deactivated.
W132 Estimated UV Trigger: AOT lap Delay: 1 sec. Lifetime for UV Recommended to change all lamps
lamp lifetime time. lamps are too after 3000 hours of operation.
exceeded. Parameter: p218. Active during step: exceed according
All steps to estimated lifetime Change according to instruction
in parameter. Replace UV lamp and quartz
Comment: This alarm sleeve in chapter 7. Service
is only displayed in the manual.
control panel(s); not in
the remote interface
(option), if installed.
List of alarms and warnings
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A137 AOT [x]: High Trigger: TS201-60 Delay: 1 sec. No water in the AOT See W100.
temperature Parameter: N/A reactor or too low
(TS201-60 Active during step: flow. After problem has been attended
tripped) and/or All steps. to, the LDC needs to be reset.
LDC powered
off. Comment: AOT is 1. Turn on the power to the
39
Control system
40
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A138 AOT [x]: PLC Trigger AOT module Delay: 2 sec. Error in module. Check the LED error indication for
error in LDC x. the electronic modules in the LDC.
cabinet. Parameter: N/A Active during step: See section I/O system and X20
All steps modules on page 55.
Control system
Comment: AOT is
deactivated.
W140 CIP schedule Trigger: Control Delay: Set in CIP not performed Control CIP status on page 1.4 CIP
timer elapsed system timer. parameter. after operation. status in control system.
Start CIP! Parameter: p117 and
p118. Active during step: Start CIP cycle.
All process steps.
W150 AOT [x]: Low Trigger: UV sensor Delay: 20 sec. Low transmittance in N/A.
UV intensity QT201-50. water.
(QT201-50) Parameter: p221. Active during step:
Quartz sleeves dirty. Clean the quartz sleeves. See
• Full ballast instruction Replace UV lamp and
2
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W151 AOT [x]: Trigger: UV sensor Delay: None. Signal missing. 1. Check fuse F45 in LDC to see
UV intensity QT201-50. which circuit that caused the
signal missing Parameter: N/A Active during step: fuse trip.
(QT201-50)
• Full ballast 2. Use the circuit diagram to
check the fuse setting, adjust
• Full deballast according to figures in circuit
W300 Filter: Motor sum Trigger: Filter. Delay: 1 sec. Motor circuit breaker See LPS alarms in section Lamp
alarm. Parameter: N/A (MCB) F1 in control power supply (LPS) on page 46.
Active during step: cabinet has tripped
All steps. or has been switched
off.
2.1
Comment: The
feedback signal “Filter Motor problem. 1. Check that breaker on the filter
SUM alarm” is not junction box is on.
detected.
2. Check that the motor is not
overloaded and can rotate
easily.
41
Control system
42
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W304 Filter pressure Trigger: Pressure Delay: 2 sec. Signal missing 1. Check fuse F45 in Control
signal missing transmitter PT201-27 or pressure cabinet to see what circuit
(PT201-27). on Boll filter. Active during step: transmitter PT201-27 caused the fuse trip.
Parameter: N/A malfunction.
• Ballast 2. Use the circuit diagram to
check the fuse setting, adjust
• Back flush according to figures in circuit
• Ballast pause diagram if necessary and reset
fuse.
• Ballast stop
2
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W306 Filter differential Trigger: Pressure Delay: 2 sec. Filter is clogged. Back-flush manually from control
pressure transmitter PT201-27 system. If not sufficient, clean
too high on Boll filter. Active during step: the filter candles according to
(PT-201–27) Parameter: p301. instruction in chapter 7. Service
• Ballast manual.
• Back flush
Valves connected Make sure that the two valves
• Ballast pause to filter differential connected to the filter differential
• Ballast stop pressure transmitter transmitter are open.
closed.
• Deballast start-up
• Deballast Pressure transmitter Hint: Pressure signal from
PT201-27 does not PT201-27 is displayed on in the
2.1
• Deballast pause work correctly. Filter popup opened from page 1.1
• Deballast stop Overview.
43
Control system
44
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
fuse.
3. Use the circuit diagram to
locate the component or find
the reason that caused the fuse
trip and attend to it.
4. Check cables to the
component. See Control
cabinet / Circuit diagram
in chapter 6. Installation
description and drawings.
5. Check that all electrical
connections are OK and that
the electrical wiring is not
damaged.
6. Replace transmitter FIT201-27.
7. Restart the process from the
beginning.
2
W500 Log box hard Trigger: Log box Delay: 10 sec. Faulty cable Check connections and cable for
ware error. (optional). connection. power cable (W10) and Ehternet
Parameter: N/A Active during step: cable (W104) between Control
cabinet and Log box.
• Ballast
• Back flush Fuse in the log box Check fuse F02 and F03 in the log
has tripped or has box.
• Ballast pause been switched off.
• Ballast stop
Error in module. Check the LED error indication for
• Deballast start-up
the electronic modules in the log
List of alarms and warnings
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
box. See section I/O system and
• Deballast
X20 modules on page 55.
• Deballast pause
• Deballast stop
• CIP
45
Control system
2.2 Lamp power supply (LPS) 2 List of alarms and warnings
LED is off.
5_2_3_03 EmpCirc
LED is blinking.
5_2_3_02 CemiCirc
5_2_3_1
5_2_3_2
3.4 The UV lamp is not • If the lamp is used for the first
successfully ignited. time: Put it on a soft bedding.
(The alarm is activated Flash twice with a normal
101 seconds after first camera on the UV lamp
ignition attempt). (functions as a ionization).
Check again.
5_2_3_4 • Check lamp cable isolation
and connection between
lamp contact and LPS
output.
• Replace UV lamp if broken.
See chapter 7. Service
manual, section Replace UV
lamp and quartz sleeve.
• Reset LED by switching
AOT breaker OFF. Wait 5
seconds and switch it ON
and reignite the lamp.
3.7 LED Temp alarm > 100 • Check the LDC cooling
°C. system.
• Check that no LPS cooling
fans are broken.
• The temperature warning
LED will automatically go
5_2_3_7
off when temperature goes
below 80 °C.
3.8 LED Temp alarm > 100 • Check the LDC cooling
°C. system.
• Check that no LPS cooling
fans are broken.
• Reset the alarm by switching
the AOT breaker OFF and
5_2_3_8
ON.
• Wait until the temp alarm
LEDs are switched off, which
indicates that the system is
ready for a restart.
• If the problem persists, check
that the cooling fans on the
LPS are rotating whilst the
UV lamps are switched on.
5_2_3_10
4FlowT_Alarm
Alarm time is displayed as time elapsed since the error occurred, and is showed as days, minutes
and hours.
Alarms and status are displayed in two lists, accessible from the Service mode screen in the flow
transmitter:
Yes: Go to step 5.
No: The tranmsitter is defect. Change.
Yes: Go to step 7.
No: Go to step 6.
7. The transmitter is OK. Check the following: Settings, application, installation, sensor, earthing,
connections etc.
8. The transmitter still not OK? Change settings according to chapter 4. Parameters, section
Flow transmitter parameters.
9. If the problem cannot be detected or corrected, the transmitter must be replaced according to
the instruction Mount flow transmitter. Note that it is not necessary to reset parameters in the
new transmitter. The settings are stored in the Sensorprom unit. When the new transmitter is
replaced, settings are downloaded automatically.
Buttons used:
2. To enter password (1000): Press Padlock. (A line appears under the first zero.)
- Press Change to change the first 0 to 1.
- Press Padlock to set the value.
- Result: The “Basic settings” menu appears after two seconds.
4. Press Padlock, and then Forward until the “Error pending” menu appears.
7C Indicates flow Unde- N/A. Measuring flow Select empty pipe cut-off
with no flow fined sensor (pipe)
in pipe empty
7I Too low flow N/A. Clogged sensor Dismount sensor tube and
signal electrodes in clean 4 sensor electrodes
sensor tube
Red Blinking Error: Internal sensor error or sensor Replace the component.
corroded.
All modules are clearly identified on the front, for example “X20 BR 9300” in the illustration below.
To the right, the state indication LEDs are visible, for example “r, e, X, I” in the illustration below.
5X20
NOTE
• Note that all status indications are not valid for all modules.
• The meaning of a status indication might vary for some modules. These variations are specified
in the Description column.
• Module IF 1082 is described in a separate table below the generic table.
The table contains the following columns and information:
Single flashes Warning / error for an I/O channel. Level monitoring for
digital outputs has responded.
1–6 Orange Light off Output status of the corresponding digital output.
Module IF 1082
The status/error light is a green/red dual LED. The status lights can have different meanings
depending on operating mode.
Green Red
S/E Green/ Various Status/error light. The status indication varies depending
Red on mode. See the two subsections in below in this table.
Starting with Automation Studio Version V 2.5.3 and with Automation Runtime V 2.90, the
interface can be operated purely as an Ethernet TCP/IP interface.
POWERLINK V1 mode
S/E Off On A fatal system error has occurred. The error type can be
light read using the PLC logbook. It concerns an irreparable
problem. The system cannot properly carry out its
tasks. This status can only be changed by resetting
the module.
Green Red
S/E Off Blinking System failure. The red blinking light signals an error
light code. See blow.
This section contains problems that can occur, but is not indicated by an alarm.
General 1A The system does not start. Power not connected to Measure that incoming 24 V DC to the control
The control panel does not the control panel. panel is present.
light up.
Fuse F42 tripped. 1. Check fuse F42 in control cabinet to see what
circuit caused the fuse trip.
2. Use the circuit diagram to check the fuse
setting, adjust according to figures in circuit
diagram if necessary and reset fuse.
3. Use the circuit diagram to locate the component
or find the reason that caused the fuse trip and
attend to it.
Fuse F4.1 in control 1. Check fuse F4.1 in control cabinet to see what
General, Filter, CIP and valve V201–8
Overheated CPU due to Check that the fan mounted on the control panel
control panel cooling fan is running and rotating in the correct direction. If
error. not, change fan rotation. If out of function, replace
the fan.
General 1B Control panel is not displaying Abnormal operating 1. Restart the control panel: Cut the power by
a normal page. condition. removing the power cable at the back of the
control panel. Wait 30 seconds, and reconnect
the cable again.
2. Restart the entire PureBallast system: Cut the
power by switching of the main breaker on the
General 1C PureBallast can not be Communication is broken See the What to do column for alarm A93.
controlled or monitored from between ISCS and PLC.
the ISCS’ graphical user
interface via the remote
interface (optional)
Filter 5A Back flush sequence starting Differential pressure Dismantle the component and inspect/rinse.
error (general) transmitter PT201–27
3.1
Error with the differential Dismantle the component and inspect/attend to.
pressure gauge electric
switches.
Valves for differential Open the two valves (ball cocks) connected to
pressure gauge PT201-27.
PT201–27 (Boll) are
closed.
General, Filter, CIP and valve V201–8
63
64
3.1
Area Problem Description Possible cause What to do?
ID
Valves for air pressure to Open the valve (ball cock) connected to V309-1.
valve V309-1 are closed.
Filter 5B Excessive back flushing The filter house is not Deaerate using the deaeration valve V201-50 on
or long back-flushing properly deaerated. the filter lid.
sequences (general)
Damaged filter candle. Check filter candles for damage. Replace if
necessary.
Large obstructions have Open the filter and remove the obstructions. See
entered the filter. chapter 7. Service manual, section Filter.
CIP 6A Insufficient pump capacity Leakage in air hoses or Locate leakage and attend to.
(general). sealings.
Air pressure too low due to Adjust setting with the manual valve under the
incorrect setting on valve valve block on the CIP module.
block on CIP.
The diaphragm in the CIP Examine the pump. See chapter 7. Service
3
CIP 6B Too high consumption of CIP Leakage in the CIP tank, Locate leakage and attend to.
liquid (> 1 cm/AOT cycle). CIP pump, pipes or AOT
reactor.
List of problems and solutions
CIP 6C CIP liquid is not returned to Insufficient pump capacity 1. Increase airflow to the pump to increase pump
CIP tank. (P321-5). capacity with the manual valve under the valve
block on the CIP module.
2. Check that pump P321-5 is functioning
correctly. See problem 6D−6I in this chapter.
CIP 6D CIP pump does not run • The air pressure is to Examine the pump and attend to problem. See
low chapter 7. Service manual, section Test CIP pump.
• The air connection is
blocked
• Muffler is blocked
• Air valve is defect
3.1
CIP 6E CIP pump runs irregularly • Valve balls are Examine the pump and attend to problem.
blocked
• Sealings are defect
in air valve or center
block
• Diaphragm
breakdown
General, Filter, CIP and valve V201–8
65
66
3.1
Area Problem Description Possible cause What to do?
ID
CIP 6F Insufficient CIP pump suction • Suction connection Examine the pump and attend to problem.
blocked or not tight.
• Muffler is blocked
• Valve balls are
blocked or damaged
CIP 6G Bad flow or pressure in CIP • Pressure fall in Examine the pump and attend to problem.
pump incoming air
• Suction or air
connection blocked
• Muffler is blocked
General, Filter, CIP and valve V201–8
CIP 6H CIP pump leakage Screws on the housing not Tighten the screws.
properly fastened
3
Valve 8A Signal change has no effect Faulty air supply Check air supply to the valve and tubing to the
V201–8 on the actuator position actuator.
See chapter 7. Service manual, section
Proportional valve for instructions regarding the
proportional valve.
Valve 8B Signal change results in Connection or signal • Check coupling between proportional valve
V201–8 actuator running to end problem and actuator.
positions
• Check input signal.
Valve 8C Signal and positioning • Inaccurate positioning. Adjust position sensor. See chapter 7. Service
V201–8 problems. manual, section Valve actuator.
67
Chapter: 6. Installation description and drawings
System manual — PureBallast 2.0 Flow 750
2 Technical data 9
2.1 PureBallast system 9
2.2 PureBallast components 10
2.3 Working pressure and pressure drop 12
2.3.1 Pressure drop for a PureBallast system 12
2.3.2 Working pressure for filter during ballast operation 12
2.3.3 Pressure calculation 13
2.3.4 Pressure during different dirt loads 14
4 Installation guidelines 23
4.1 Preparations and conditions 23
4.1.1 Safety information 23
4.1.2 Correct installation 23
4.1.3 After installation, before system is put into operation 24
4.5 Filter 34
4.5.1 Placing guidelines 35
4.5.2 Installation guidelines 35
3
4.7 Cabinets and cables 36
4.7.1 Placing guidelines 36
4.7.2 Installation guidelines 37
4.7.3 EMC cable installation 38
5 System interfaces 43
5.1 Remote control panel integration
(optional) 43
5.2 Remote interface integration (optional) 44
5.2.1 Communication between PureBallast PLC and
remote interface 44
5.2.2 Directory of addresses 45
5.2.3 Sequence example 61
4
5.6 GPS signal installation 75
7 Drawings 81
7.1 Graphic symbols used in drawings 82
7.2 General drawings 83
7.2.1 Flow chart 83
7.2.2 Connection list 84
7.2.3 Electrical system layout 89
7.2.4 Air distribution 90
7.2.5 Quality specification / Compressed air 91
7.2.6 Quality specification / Water 92
7.2.7 Quality specification / CIP liquid 93
5
7.4 Log box / dimension drawing 114
7.5 Electrical drawings 115
7.5.1 Control cabinet / Assembly drawing 115
7.5.2 Control cabinet / Circuit diagram (19 pages) 116
7.5.3 Control cabinet / Interconnection diagram (9 pages) 135
7.5.4 Control cabinet / Cable list 144
7.5.5 Remote control panel (optional) / Assembly drawing 145
7.5.6 Lamp Drive Cabinet (LDC) / Assembly drawing 146
7.5.7 Lamp Drive Cabinet (LDC) / Circuit diagram (20
pages) 147
7.5.8 Lamp Drive Cabinet (LDC) / Interconnection
diagram (5 pages) 167
7.5.9 Lamp Drive Cabinet (LDC) / Cable list 172
6
1 Introduction
This chapter contains information about how the PureBallast system is installed and stored.
The information is presented as installation guidelines per component, relevant standards and
drawings. The chapter is opened with a summary of technical data relevant for planning and
installing PureBallast.
This section states technical data for the complete PureBallast system and for individual
components. In some cases references are given to data in drawings included in this chapter.
Water requirements See section Quality specification / Water on page 92 and data for
different components in the Connection list on page 84.
• Sea water: Used for cooling UV lamps in the AOT during start-up.
• LT (low temperature) fresh water: Used for cooling the lamp drive
cabinet (LDC) during operation.
• Fresh water: Used for flushing and filling up of AOT modules after
treatment.
Based on:
Compressed air See data for individual components in Connection list on page 84 and
requirements the Quality specification for compressed air on page 91.
Piping connections See data for different components in Connection list on page 84.
Power to LDC: Max Icu 70 KA. (Fixed breaker setting: 125 amp).
AOT module (per AOT) Pressure drop See data for different components in Connection
list on page 84.
Volume 55 liters
LDC, pressurizing unit Air requirements See Quality specification / Purge air on page .
Tank volume 250 liters. Note: Total tank volume is 300, but
shall only be filled to max 250.
Remote control panel Dimensions See Remote control panel / Dimension drawing
(Optional) on page 112 and on Remote control panel
integration page 43.
Log box Dimensions See Log box / Dimension drawing on page 114.
During ballast, the filter is rinsed by an automatic back-flush operation. A differential pressure
indicator monitors the pressure drop over the filter, which fluctuates between 0.05−0.38 bar
depending on dirt load in the filter.
When the differential pressure over the filter, ∆pfilter, reaches 0.38 bar, a back-flush operation is
started automatically. To ensure sufficient back-flush flow, ∆pback-flush must be at least 1.50 bar.
6 WorkPressure
During ballasting, the ballast water flow goes through the filter and AOT which gives a pressure
drop of 0.80 bar (not including piping), as described in the table below.
AOT ≤ 0.40 bar pAOT: 0.40 bar (0.04 MPa) including PureBallast valves. Piping
is not included, since it is installation specific.
Total ≈ 0.80 bar ≈ 0.80 bar (0.08 MPa) not including piping.
During back-flush, the ballast water flow goes through the filter and AOT, and the back-flush
discharge flow goes through filter and pipe 309.
A pressure calculation must be done to secure sufficient back-flush flow in pipe 309 and to secure
that the ballast water pump can overcome pressure drop according to the table below:
∆P309 Calculated Pressure drop for pipe 309 is installation specific and must
be calculated.
Calculate value for parameter Pressure trigger for V201-8 during back-flush
To ensure that pback-flush is 1.5 bar, the pressure at the filter outlet must be calculated according
to the formula below:
In clear water, where the dirt load is low, the back-flush cycle is started by the time trigger (default:
every 30 minutes). As long as the pressure is below 0.38 bar (0.038 MPa), there is no need for the
pressure triggered back-flush. See examples below.
6 Dirtload1
6 Dirtload2
In more dirty waters the back-flush cycle will be triggered when pfilterreaches 0.38 bar, which
indicates dirt in the filter candles.
After each back-flush, the back-flush counter is reset. The filter will be back-flushed again after 30
minutes or when ∆pfilterreaches 0.38 bar, whichever comes first.
In the example below, three back-flushes are triggered due to high differential pressure over the
filter. After that, there is not so much dirt build up, so the next back-flush is performed after
30 minutes.
6 Dirtload3
In conditions with heavy dirtload the system will perform more frequent back-flushes to keep the
filter clean.
Also, the 0.38 limit might be exceeded. In this case the self rinsing cycle will run continuously
until the problem is solved and the pressure has returned below 0.38 bar. It is OK that the flow
momentarily fluctuates in an irregular curve, but it is important that the curve stabilizes.
In the example below, a series of back-flushes are performed (approx. every 4 minute). After that
the pressure rises above 0.38 where the filter is back-flushed constantly. After that, the normal
control is resumed, where the filter is back-flushed triggered pressure (2 times) or by time (last
back-flush in the example.
6 Dirtload4
Over time, the filter candles will undergo a long term build-up of particles that are not removed by
back-flushing. One effect of this is that “normal” pressure will increase over time. Therefore, the
maintenance schedule state that the candles shall be inspected and manually cleaned once a year.
The extent of the long term dirt build-up is dependent on the water conditions. In the great majority
of cases this will not cause any problems – cleaning once a year is enough. But in exceptional
cases (vessels trading very muddy waters) it might be necessary to clean the filter candles more
often. If the pressure triggered back-flushing is performed with short intervals, we suggest that the
filter candles are manually cleaned more often than once year.
This section contains information about how to handle PureBallast components during transport,
delivery and installation.
• Always read and follow the documentation included in shipment of components and spare
parts regarding handling, safety and disposal.
• Handle the delivery with care in order not to damage the equipment or cause personal injuries.
• If the PureBallast system is stored before installation, make sure to store the components
according to the Shutdown and storage section.
• Each AOT module is delivered with an extra set of loose components to secure that installation
and commissioning can be performed without any crucial parts missing. The AOT module is
delivered with the following surplus consumables, compared to the amount needed.
NG
WARNI
!
• Components must be lifted using correct lifting tools (such as a fork-lift truck, a crane) and
tackle with a load capacity greater than the weight of the component. See the Technical data
section on page for information about weight.
• Any complementary lifting instructions must be followed.
NOTE
• The AOT is delivered lying down in a wooden box. It must not be turned to vertical position.
• The AOT is delivered with a wooden bearer attached at the bottom of protect the components
around the lower flange. The bearer must remain attached to the AOT if the AOT is to be
placed standing up prior to mounting.
• Weight and center of gravity according to illustration below:
6 595570_manual
Ref. 595570
Follow the instruction to raise the AOT module to standing position. Note that two lifting devices are
needed for this operation.
1. At the bottom (left in the illustration): Attach a soft sling or webbing sling to the uppermost
fixing hole of the flange.
2. At the top (right in the illustration): Attach a soft sling to the lifting eye bolt on the girder.
3. Direct the sling from the lifting eye bolt via the valve to the lifting device. Stretch the sling in an
angle which allows approximately 100 mm safety margin from the actuator.
4. Lift the AOT module. Make sure that the slings do not damage any equipment, for example an
actuator.
5. When AOT is in the air it can be turned to vertical position by lower of the sling attached to
the bottom flange. Make sure that the slings do not damage any equipment, for example an
actuator.
3.2.2 Filter
Weight of filter (empty): 900 kg.
6 FilterLift 594949#0
Ref 594949
Ref 590857
6 CCLift 597309
Ref 597309
This section covers requirements for planning, locating and installing different components of
the system.
NG
WARNI
!
• The PureBallast system must be installed in an engine room on the vessel. The remote control
panel (optional) can also be installed in all other locations, for example cargo control room, back
office or the bridge, provided the area is not hazardous.
• The PureBallast system is not EX proofed and must not be installed in areas where an
explosive atmosphere may occur.
• Damages related to transport and installation should be recorded.
• All components must be installed and marked as specified in dimension drawings, flow charts
and other drawings included in this manual.
• Installation must be done by a fully trained professional installer.
- General drawings – overall and principle information for system layout (pipes, components,
electricity, air and water).
- Dimension drawing – detailed component information (dimensions, sizes etc).
- Electrical drawings – detailed electric (circuit diagrams, cablings etc).
NOTE
• All ballast water tanks must be well cleaned before PureBallast is put into operation. This is
valid both for new builds and retrofit installations.
• All pipes to PureBallast must be well flushed, before water is run through the filter.
System requirements The system must be designed according to the basic layout
requirements specified in the Flow chart on page 83.
Pressure and pressure The system must be designed and installed to secure required flow
drop and pressure, and the ballast water pump must be dimensioned to
handle the filter back-flush according to reference below. Pressure
calculations must be performed to secure this.
See the following sections in this chapter:
General function Note that the function and performance of PureBallast are dependent
of the installation. It is the shipyard’s responsibility to plan and
perform the installation according to the specifications given in this
manual.
Components within Alfa Information about installation requirements for individual components
Laval’s scope of supply according to section Correct installation on page 23.
• Connection list
• Quality specification for water
• Quality specification for compressed air
• Installation guidelines
• Electrical drawings
The list is compiled on the top level so that integrated components are not described, because they
are already mounted at delivery. For example, the lamp drive cabinet is not described individually in
the list, since it is already mounted as a part of the AOT module.
Main components
AOT module, AOT n, The main water treatment It is crucial that the AOT:s are installed
pieces where component in the system, so that the water flow as well as
according to “n” including reactor, lamp static and dynamic pressure is equally
order. indicate drive cabinet, valves, distributed between all AOTs.
unique temperature sensor, limit
AOT switch and temperature
number. switch.
Filter, 1 Filter Mechanical filtration of the The cover and insert are heavy.
piece water before treatment. When planning the location of the
filter, consider the need for a lifting
device to be used for installation and
maintenance.
CIP module, CIP Automatic cleaning of the The CIP module must be placed so the
1 piece AOT after treatment. pipes from the AOT have a downward
gradient towards the CIP module.
Remote Extra panel to control and Can be installed in locations from where
control panel monitor the PureBallast ballast operations are performed, for
(optional), 1 system. example on the bridge.
piece
Log box Log box Connection box to connect Max distance to the control cabinet: 100
(optional), 1 feedback signals for valves meters.
piece and pumps that are not
included in the PureBallast
system. This makes it
possible to monitor and
log the components in the
control system.
Main valves
Valve, V201-8 • Main outlet valve from The valve must be placed as last
1 piece the PureBallast system component on the ballast water outlet
including to the vessel’s ballast pipe.
junction box system after treatment.
• Control valve to
maintain pressure
needed to perform back
flush.
• Automatic flow
regulation during
operation.
The junction box function
as cable connection point
for the component.
Flow sensor FIT201-1 Flow sensor monitor As described below in this section.
the flow in the system.
Flow FIT201-1 Functions together with the
transmitter flow transmitter.
Ancillary equipment
Consumables
CIP liquid, 1 The liquid is used for the See chapter 7. Service manual,
can first filling of CIP liquid. instruction Change and refill CIP liquid.
Loose com- Each AOT module is Included items are listed in section
ponents for delivered with an extra Delivery and transport on page 17.
commission- set of lose components
ing, 1 set. to secure that installation
and commissioning can
be performed without any
crucial parts missing.
The installation of the AOTs and piping for ballast water must be designed so that the water is
distributed evenly through all AOTs. There is no standard solution for how to organize the AOTs.
Requirements
• The flow must not exceed certified flow: 750 m3/h in total for the system.
• The flow must be evenly distributed through the AOTs. A small fluctuation is allowed, but the
flow must not exceed 255 m3/h for one AOT.
• Chosen solution must be verified by a flow and pressure calculation (by installing party) to verify
that the flow is evenly distributed.
Recommendations
6 Even flow 1
• Increase the diameter for the inlet and outlet manifold with one standard pipe size (or more).
This will result in a lower velocity, and thereby a more even distribution of the flow. This is
strongly recommended for system sizes 1250–3000. See example below.
6 Even flow 2
• Strive to use as few bends and other components as possible before and after the manifolds.
This will result in smaller pressure drops and a more even distribution of the flow.
• A mechanical device can be installed to secure even flow through the AOTs, for example an
orifice or a balancing valve (not part of Alfa Laval’s scope of supply). Note that any chosen
solution must be verified.
• The LDC cabinet must be secured with a stay at the top. Use the Ø15 mm support hole at the
top of the LDC module. See A in the illustration below.
• The LDC cabinet must be secured with stays at the bottom. Use the support plate. See B in
the illustration below.
• The AOT reactor must be supported to carry the weight of the component. Stays has to be
made at site, and can be done according to of the examples below.
6 592830_support2
6 592830_support1
• The AOT module must be mounted vertically between the inlet and outlet flanges as shown in
the illustration below (flange A is the inlet and flange B is the outlet). The AOT can be mounted
in any rotational position about the center line of the inlet and outlet flanges.
• The AOT module (including the LDC) module must be secured to withstand forces of loads
according to the table and illustration below. The table indicates the calculated load applied
by a full AOT when the vessel is heeling 50°. The direction of load is shown in the illustration
below the table.
Cartesian load Flange A (inlet) Flange B (outlet)
direction
Fx ± 3200 N ± 3200 N
Fy ± 2600 N ± 2600 N
Fz + 11400 N + 5700 N
Fz support + 5000 N + 1200 N
6 592830_force diagram
4.5 Filter
Follow the guidelines below when installing the filter.
• It is recommended that the drain valve (V460–3) is connected to one of the following tanks:
bilge tank, drain tank, sludge tank or bilge wel. This will facilitate drainage of the CIP tank.
• Follow the recommended installation of pipes to and from the AOT, to minimize dilution or loss
of CIP liquid and to secure good pump efficiency (as illustrated below):
- Pipe 321: Downward gradient towards both the CIP module and the AOT reactor. There
must be no risk for water or air pockets in the pipe.
- Pipe 320: Downward gradient from the AOT towards the CIP module. Create a water lock
close to the CIP module, before the vertical pipe to the CIP module. There must be no risk
for water or air pockets in the pipe, which can effect efficiency in a negative way.
6 AOT-CIP 6_4_5_2
NOTE
• Alarms from PureBallast must be distributed as a visual and audible signal to all stations from
which ballast water operations are controlled. To achieve this, a signal device (not part of Alfa
Laval’s scope of supply) is connected to the control system alarm relay indicated as “common
alarm” in drawing Control cabinet / Interconnection diagram on page 135.
• System interfaces (optional) must be integrated according to section System interfaces on page :
• Cabinets must be firmly attached and must not amplify vibrations to or from the hull.
• Control cabinet: The component must be earthed. The earth nut is placed at the underside of
the component, marked “PE” in the drawing.
Cables
• Electrical cables must be properly suspended and supported according to applicable regulations.
• Cabling shall be done according to specification in Electrical system layout on page 89, and
the electrical drawings. This includes cable routing, cable types and cable marking to simplify
identification and fault finding.
• Power cables shall be separated from signal and bus cables. Distance between them reduces
electrical noise transfer.
- If placed on a cable rack, place power and signal cables on opposite sides.
- If cables are routed in tubes due to narrow space, the power and signal cables shall be
routed in separate tubes.
• Power cable to LDC: Max Icu 70 KA. (Fixed breaker setting: 125 amp).
• Power cable (4 cords) to V201-8 must be done according to the Control cabinet / Interconnection
diagram on page 135.
Please note the following:
• Flow sensor: A pipe with four electrodes detecting the flow. On top of the pipe, there is a
terminal box, where the flow transmitter is mounted.
• Flow transmitter: Monitor flow and transmits the information to the PureBallast control system.
The flow transmitter is also used to set parameters for the flow meter. A Sensorprom in the
flow transmitter contains the data.
6 FM install
• If there is a lack of space, it is possible to shorten the straight pipes. Note that the accuracy
is affected negatively by shorter straight pipes. It is also possible to place the flow meter in a
bend without straight pipes. In this case we recommend that the radius (R) is proportional to
the pipe diameter (⌀) according to the illustration below. Installation without straight pipes will
result in a divergence of approximately 2 %.
6 FM bend
6 FM Pipe
• Do not install the flow meter at the highest point in the pipe: This results in partially filled pipes.
Do not install in a pipe with a downward flow direction: The water shall not stream by gravity.
If there is a risk for pour measuring conditions (e.g. partially filled pipes), the flow sensor should
be located in a U tube to ensure that it is completely filled. See illustration below.
6 FM Upipe
This section covers guidelines for how to install and integrate the following, if used:
- If Cat 5e (or better) is used as communication cable (W501), the maximum distance
between control cabinet and the remote control panel is 100 meters.
- If the distance is longer, a multi-mode fiber cable with LC connector must be used.
• A signal device must be installed according information in section Cabinets and cables on page
36. Not part of Alfa Laval’s scope of supply.
• Ethernet switch connecting set in control cabinet.
• External switch including a terminal to handle the communication.
Switches and cables are installed according to instructions in chapter 7. Service manual, section
Remote control panel (optional).
IP addresses are set according to instruction in chapter 3. Operating instructions and control system
description, section Set control panel IP address and Set remote control panel communication.
PureBallast’s PLC communicate with the vessel’s ISCS via the remote interface. Data is sent to
and from dedicated addresses via modbus. Data can be commands, values (sum of bits), alarms
and status information. The data is then presented in the ISCS according to the vessel’s graphical
standard. It is possible to present all information (all addresses) or a selection. Data is sent as
binary code, with exeption for time, which is sent as hexadecimal code.
• A signal device must be installed according to information in section Cabinets and cables on
page 36. Not part of Alfa Laval’s scope of supply.
• Connection terminal (X4) must be installed in control cabinet. (Installed at delivery if remote
interface is included in original order. If remote interface is added after installation, the terminal
and wiring must be installed according to instructions in chapter 7. Service manual, section
Remote interface (optional).
• Modbus connection from ISCS to PureBallast connection terminal X4 in the control cabinet.
Connection can be either RS422 or RS485, and is connected according to Control cabinet /
Interconnection diagram. Recommended max length: 500 meters.
• Implementation of remote interface signals in the ISCS according to the guidelines in this section.
• Communication settings must be done according to chapter 3. Operating instructions and
control system description, section Set remote interface communication.
• Parameter setting must be done for parameter p132 and p133 in the control system.
• After installation and integration, the function of the remote interface must be verified according
to chapter 3. Operating instructions and control system description, section Test remote
interface communication.
Reference information about the logical flow of the PureBallast processes can be found in chapter
3. Operating instructions and control system description, section Detailed process description.
Modbus settings
ISCS modbus RTU server data shall be set according to the table below:
• Modbus: RTU
• Communication: Serial
• Baud rate: 300–187500 bps (default: 9600)
• Parity: None
• Bits per character: 8
• Stop bits: 1
• Slave ID: 10 (PureBallast is slave and ISCS is master)
• Port in master control panel: Com 1.
The following values may be changed, but it is not recommended. Note, that the information must
be the same in ISCS and PureBallast control system.
• Baud rate
• Parity
• Slave ID
• Port in master control panel.
• Address for data from ISCS to PLC are written as “+001”, “+002” etc, which means 40001,
40002 etc.
• Address for data from PLC to ISCS are written as “+101”, “+102” etc, which means 40101,
40102 etc.
The following terms are used to explain the signals in the tables below:
Address:Bit Individual address and bit for each signal (data), written as Address:bit, for
example +140:3. Values for an address is written as address=value, for
example 142=9.
Bits are the Signal reference number. Bits are right aligned, where applicable.
Function Name of the function. The name corresponds to the text used in the
PureBallast control system HMI. Parenthesis gives reference to the control
system page where the information is used/displayed. For further information
about respective piece of information, see chapter 3. Operating instructions
and control system description.
Description Additional information, for example specific conditions that must be met before
a command can be sent.
The addresses below are used to send data from PureBallast to ISCS.
+101 Processed volume (1.1) Value: Processed volume [m3] during current
ballast or deballast process. The value is resets
during next start-up.
+102 Accumulated ballast Value: Total treated volume during all ballast
volume (5.3) operations.
+103 Accumulated deballast Value: Total treated volume during all deballast
volume (5.3) operations.
+104 Current flow (1.1, 1.3) Value: Current flow indicated by FIT201-1 [m3/h]
+106 Certified flow (1.1, 1.3) Value: Selected certified flow [m3/h], which is
max flow for operation.
+107 Flow setpoint (1.3) Value: Selection for new flow [m3/h].
+108 Remaining time (hours) Value: Estimated remaining time for the ongoing
sub process. [Hrs] (Not displayed in PureBallast
control system.)
+109 Remaining time (minutes) Value: Estimated remaining time for the ongoing
sub process. (Not displayed in PureBallast
control system.)
+110 Remaining time (seconds) Value: Estimated remaining time for the ongoing
sub process. (Not displayed in PureBallast
control system.)
+114 Total CIP remaining time Value: Total estimated remaining time for all CIP
(hours) (1.4) sequences and filter preservation [hrs]
+115 Total CIP remaining time Value: Total estimated remaining time for all CIP
(minutes) (1.4) sequences and filter preservation [min]
+118 Required CIP count down Value: Time before CIP must be performed per
(1.4) AOT [hour]. Displayed per AOT [index].
+119 Required CIP count down Value: Time before CIP must be performed per
(1.4) AOT [min]. Displayed per AOT [index].
+120 Diff. pressure over filter Value: Filter differential pressure indicated by
(Filter popup) PT201-27.
The addresses below are used to send commands and status information from PureBallast to ISCS.
/ Bit
Bit 0 Start ballast accepted Status: Confirmation from PLC that requested
command is executed.
Bit 1 Start deballast accepted Status: Confirmation from PLC that requested
command is executed.
Bit 2 Start CIP accepted Status: Confirmation from PLC that requested
command is executed.
Bit 6 Sum alarm Common alarm indicating that one (any) alarm
is active. Alternative to implementation of
individual alarm signals and hard wired common
alarm. Functions in the same way as hard wired
external signal “Common alarm”.
Bit 8 Start ballast water pump Request to ISCS to start ballast water pump:
(1.1, 1.3 and popup) Address values.
1=Request to start.
0=Request to stop.
Bit 9 Open overboard valve (1.1, Request to ISCS to open overboard valve:
1.3 and popup) Address values:
1=Request to open.
0=Request to close.
+141 Process mode 1.1, 1.3 Status: Address values: Values indicating
system mode.
0=Booting
1=Standby
2=Ballast
3=Deballast
4=CIP
5=Emergency stop
6=Manual mode
7=PID calibration
0=None
1=Start-up ballast
2=Full ballast
3=Back-flush
4=Puase
5=Stop with back-flush
6=Increasing ballast flow capacity
7=Decreasing ballast flow capacity
8=Start-up deballast
9=Full deballast
10=Pause deballast
11=Stop deballast
12=Increasing deballast flow capacity
13=Decreasing deballast flow capacity
14=AOT drain 1 – Sea water
15=AOT fill 1 – Fresh water
16=AOT drain 2 – Fresh water
17=CIP
18=AOT fill 2 – Fresh water
19=Preservation filter – Fresh water
20=Heeling mode
21=CIP drain
22=Stop (If ballast process is stopped before
mode Full ballast, no back-flush is performed.)
Bit 2 AOT [index]: Sum alarm Status: Sum alarm for AOT [index]. The AOT is
(AOT popup) not ready.
Bit 3 AOT [index]: CIP error Status: Error for AOT [index] during CIP process
Bit 4 AOT [index]: CIP required Status: CIP status for AOT [index]: 0=Not
required. 1=Required.
Bit 5 AOT [index]: CIP ongoing Status: CIP status for AOT [index]: 0=CIP not
ongoing. 1=CIP ongoing.
+147 AOT ready [1–12] (1.3) Status: Respective AOT is ready, which means
that there exist no active alarm for the AOT
(146:2 = 0).
0=Not ready.
+148 AOT selected [1–12] (1.3) Status: AOT selected for process by operator. In
PureBallast, the AOT is visible in the list AOT:s
selected for process in 1.3.
+149 AOT sum alarm [1–12] Status: Sum alarm indication for AOT. The AOT
(1.3, AOT popup) is not ready.
+153 Power request [1–6] (1.5) Only relevant if PureBallast is integrated with the
vessel’s power management system.
Bit 0–5 Power request 1–6. It is only necessary to use signals (bits) to cover
the need for power request. This is defined
by the number of AOTs, alternatively use of
common power.
+154 Power running [1–6] (1.5) Power running to power management system.
The addresses below are used to send status information for components to ISCS.
/ Bit
+160 Main status (1.1 and popups for AOT, filter and CIP)
The addresses below are used to send commands and status information from ISCS to PureBallast.
/ Bit
+001 Commands
Condition: All signals for +001 must be high until PLC return an accept
or reject signal (see +140).
+002 Feedback
Bit 2 Flow controlled Status: Defines if flow capacity for process is set
selection (1.3, AOT using address +003 or +011.
selection popup)
1 = Number of AOTs to be used for process, set
using address +003.
+003 Selected flow (1.1, If set during standby: Defines which flow to be
1.3) used when ballast or deballast is started. If set
during ballast or deballast: Defines that flow shall
be increased or decreased to the new flow set.
+010 AOT index (1.3, 1.4, Only relevant if more than one AOT is installed and
1.5, AOT popup, signals for AOT status are used.
alarms etc)
PureBallast only send status and feedback
information for one AOT at the time. This address
defines for which AOT data shall be sent from PLC.
+011 Selected AOT (1.3, Defines flow for process. Flow is sent to PureBallast
AOT popup) as a bit pattern, where bits are high for each
selected individual AOT to be used in process.
Each selected AOT represent 250 m3/hour.
+012 Power granted (1.5) Only relevant if PureBallast is integrated with the
vessel’s power management system.
Address values:
1=Power granted.
0=Not granted.
Bit 0–5 Power granted 1–6. Note that it is possible for the vessel’s power
management system to grant lower power than
requested.
The table below lists all alarms sent from PureBallast to the ISCS. Each alarm is defined as a
specific bit. The bit is set to 1 when the alarm is activated. The alarm IDs refer to alarms described
in chapter 5. Alarms and faultfinding, where texts to be displayed in ISCS can be found.
Alarm can be connected and indicated in three ways. Note that alarms must be indicated in ISCS
on one of these ways:
• Individual alarm integration via remote interface (address +171 – +199 described in the table
below). This is the recommended alternative.
• Common alarm integration via remote interface, indicating that there is an (any) active
alarm/warning in PureBallast. (Address +140:6)
• Common alarm connected via hard wire, indicating that there is an (any) active alarm/warning in
PureBallast. It is recommended that this alternative is integrated a redundant safety precaution.
Example: If data at address 40172 is 000010000000100, this means that alarm A66 and warning
W83 are active (bit 2 and 10).
Note: Address +187 is not used. A66 exist two times in the table: only one (optional which)
shall be used. N/A=Not applicable.
Bit
Note 1: Individual alarms for installed AOTs 1–12: 173=AOT 1, 174=AOT 2 etc to 184=AOT 12.
The actual alarm states the AOT concerned.
Note 2: Individual alarms for installed AOTs 1–12: 188=AOT 1, 189=AOT 2 etc to 189=AOT 12.
The actual alarm states the AOT concerned.
• The system consists of at least 2 AOTs. During this example, the flow is increased.
• To start a process, a flow must have been selected. This can either be done by selecting a flow
(m3/h) or by selecting AOTs (AOT nr. 1–12). How flow is set is controlled by address +002, bit
2. Then, flow is set via address +003, or individual AOTs via address +011. In both cases,
selection must be confirmed via address +002, bit 3. Selections for these addresses are stored
in the memory, and will be used as default for next operation, if not changed. In the example
below the following selections are used as default from memory: Address +003=1, address
+002+, bit 2=1 and address +010=1 (AOT index display information for AOT nr. 1.)
• Remote control is activated (Address +140, bit 10 is 1).
• Power management (optional) is integrated.
• No alarms are active: address +171 through +199.
Ballast
6 SignalExampleBal
Deballast
The following addresses differs from a ballast process: +140, +141, +142, and +001.
6 SignalExampleDeb
CIP
6 SignalExampleCip
Note 1: Status signals for subprocess mode +142 (14–19 and 21) alters during the CIP process
depending on sub process and which AOT that is processed.
The communication is either handled by the remote interface (if the option is integrated) or via hard
wires between the vessel’s ISCS and PureBallast’s control cabinet. It is also possible to use
hard wire, even if remote interface is integrated.
Signals are defined to handle all combinations of power step (amount of power) and function
(request, grant and run). More than one signal can be sent (or received) at the same time to
achieve, for example, a request for 3 AOTs.
As an alternative, it is possible to use power step 6 (common) that always will be used, regardless
of the number of AOT:s used for a specific process. The common power is defined as the number
of installed AOT:s times the defined power consumption for one AOT.
Below, the signals sent and received are described in detail, including examples.
Power request
Power request is sent to ISCS as one or more signals, identified with a unique ID. Note that the
signals must be handled and interpreted as one package by the ISCS.
Example: A 750 m3/h process shall start, requiring 3 AOT:s. This requires power step 1 and 2 in
combination add up to 108 kW (1×36 + 2x36 = 108). Therefore signal 229 and 230 are sent to
the ISCS.
Power granted
After an availability check, power granted must be sent back to PureBallast control system. Power
granted must correspond to the request signal(s) sent from the PureBallast control system. If
not, less or more power will be available for operation. If less power than requested is available,
signals for available power must be sent. If no signals are sent within parameter set time interval
(p143), the operation will be canceled.
Example 1: Power for the 750 m3/h process (108 kW) was required by signal 229 and 230. It is
granted. Requested power is available and shall be granted. This requires that power step 1 and 2
in combination are granted. Therefore power granted signal 223 and 224 are sent to the control
system at the same time to the control system.
Example 2: Power for a 750 m3/h process (108 kW) was required by signal 229 and 230. But only
72 kW is available. Therefore power granted signal 224 is sent to the control system. The control
system will automatically reduce the number of AOTs used for the process to 2.
Power running
To confirm that the power is used, Power running is sent to ISCS using signals that corresponds
exactly with the received power granted. In example 1 above, power running signals 235 and 236
are sent. In example 2 above, power running signal 236 is sent.
6 PowerSignals
1. Power request
2. Power granted
3. Power running
4. Signal overlap (≈ 2 seconds)
t. Time
It is possible to increase flow during ongoing operation. In this case, the power request process
must be repeated, with some modifications.
Example: A 750 m3h process is ongoing (power step 1+2). In this case the power running signals
235 and 236 are active.
The flow is increased by one AOT to 1000 m3h from the control system. To handle an additional
AOT power request signal 229 (request for power step 1) is sent. The process continues and
the running signals are still active.
During the time overlap of the power granted signal, the power running signals 235 and 236 are
inactivated, and signal 237 is activated. The new power running signal is active as long as the
ballast/deballast process is running.
6 PowerSignals2
1. Power request
2. Power granted
3. Power running
4. Signal overlap
5. Partial signal overlap
t. Time
Note that It is only necessary to connect enough signals to cover the number of AOT:s installed on
the vessel. If four AOTs are installed it is only necessary to connect the following signals: request
229–231, granted 223–225 and running 235–237.
After installation, the signals need to be tested. This is done by simulating signals from the control
system, page 1.5 Power request. See chapter 3. Operating instructions and control system
description, instruction Simulate power request.
The following components cannot be connected via remote interface. If used, they must be
connected via hard wire: External stop, External system stop and External bypass 1-3.
Each signal that is used must be activated in the control system page 8.2 – Main parameters 2.
Output indicates signal from PLC and Input indicates signal from ISCS.
Common alarm (strongly Output Send an alarm/warning signal from control cabinet.
recommended to be
integrated) If an alarm is already present and a new alarm is issued,
the signal will go low for three seconds, and the be
re-activated as high.
External stop Input Send a stop signal to control cabinet. Equal to pushing
the Stop button in control system panel.
External system stop Input Send a system stop signal to control cabinet.
Heeling mode (internal Input Send a pause signal to control cabinet (to enter heeling
transfer) mode). Equal to pushing the Pause button in control
system.
External bypass 1 is Input Used to detect when an external bypass valve is open,
open used in addition to V212-31. Signals for up to three
bypass valves can be handled.
External bypass 2 is
open Active signal to control cabinet = Valve closed =
PureBallast is used for ballast and deballast processes.
External bypass 3 is Inactive signal = Valve open = PureBallast is bypassed.
open
Result: If PureBallast is bypassed, it is shut down and
the event is logged.
Feed back ’’Ballast Input Send a ballast water pump running signal to control
water pump is running’’ cabinet.
Result: System continues automatically. No popup shown
in control system.
Feed back ’’Overboard Input Send an overboard valve open signal to control cabinet.
valve is open’’ Result: System continues automatically. No popup shown
in control system.
Booster pump (P401-1), Output Send a signal from control cabinet to start/stop LDC
for LDC cooling cooling pump for line 401. P401-1 is used during ballast,
deballast and pause mode.
Booster pump (P403-1), Output Send a signal from control cabinet to start/stop reactor
for AOT reactor cooling cooling pump for line 403. P401-3 is used during start
ballast, ballast, start deballast, ballast and pause mode.
Request ’’Start BW Output Send a signal from control cabinet to start/stop ballast
pump’’ water pump.
Input signals
Input signals must be connected from the control cabinet via – W117 to the ISCS. In the ISCS,
cables must be connected to one common terminal (common DC + for all input signals) and one
terminal dedicated to respective signal used. Make notes about cable part number for the control
cabinet and the ISCS in the Control cabinet / Interconnection diagram (indicated in the illustration
below) to facilitate fault finding. In the illustration, cable part numbers 1 and 2 noted as an example.
7 ExtSignalIN
Input signals: Cable connections (bold lines) in the ISCS. Excerpt from Control cabinet / Interconnection
diagram with cable part number 1 and 2 noted.
Output signals
Output signals must be connected from the control cabinet via – W117 to the ISCS. Output signals
are connected via potential free relays. It is possible to choose either a normally opened connection
or a normally closed connection. See illustration below. Make notes about cable part number for
the control cabinet and the ISCS in the Control cabinet / Interconnection diagram (indicated in the
illustration below) to facilitate fault finding. In the illustration, cable part numbers 3 and 4 noted
as an example.
7 ExtSignalOUT
Output signals: Potential free output. Excerpt from Control cabinet / Interconnection diagram with cable part
number 3 and 4 noted.
• Valves: Max 18 valves can be integrated. Two feedback signals can be connected per valve:
Open and closed.
• Pumps: Max 4 pumps can be integrated. One feedback signal per pump: Running.
Remote interface integration requires the following additions:
• Log box is installed and signal cables for components to be logged must be connected.
• Parameter p500 Log box must be activated.
• Signals for components to be integrated and logged must be activated in parameter p501–540.
6 LogBoxCP
1. Signal cable (W104) is connected between control cabinet (connection point IF3/IPL) and log box
(connection point A40A/IF1). Cable properties: Ethernet cable, > CAT 5e with RI45 connector.
Note: This cable is not indicated in the control cabinet drawings (interconnection diagram,
circuit diagram and cable list).
2. Power cable (W10) is connected to log box (connection point -X01). Cable properties: 440
VAC, Three-phase, 1 amp.
3. Signal and power cables are connected between the log box (connection point, relay module
X1–X5) and respective component. Cable properties: Suitable, marine approved cables.
Signal and power cables are connected to the relays in the log box according to the
diagrammatic illustration below:
6 LogBoxCab
Signal cables are connected according to the table below. Relay module and Relay refers to
connection point in the log box. Position refers to ID in control system page 5.7 and 5.8.
The GPS must be connected to the module X20IF1030 in the control cabinet, using an NMEA
(RS422) serial interface with the following settings:
For details, see the illustration below (based on the Control cabinet / Interconnection diagram on
page 135).
6 GPS
This section describes requirements for decommissioning and storage. The rules must be followed
when the system shall be shutdown for a long period.
A copy of the decommissioning report must be placed inside the control cabinet. The report must
include all important information from the decommissioning, for example notes and information
about where to find stored components.
6.1 Decommissioning
Follow the process below to decommission the PureBallast system. Note that if there is a freeze
risk, the system must be completely emptied of water.
1. Run the back flush sequence for the filter three times.
2. Drain all water from the filter. Leave the drain open afterwards.
3. Run the CIP process twice.
4. Drain all liquid from the AOT reactors. Leave the drains open. (Use the drain plug at the
bottom of the AOT.)
5. Shut off the main valves for the start-up cooling system. Drain the system afterwards.
6. Isolate the start-up cooling system: Close installed service valve, or use a blind flange, to
prevent fluid to enter the section. (Pipe connection 403, 404.)
7. Drain all water from the LDC heat-exchangers. Leave the drains open afterwards (disconnect
hoses). Shut off the main valves for the cooling system (pipe connection 401).
8. Clean the CIP module with fresh water. Rinse the tank. Drain all water/liquid from the CIP
system and leave the drains open afterwards.
9. Isolate the system: Close installed service valves, or use a blind flange, to prevent fluid to
enter the section. (Pipe connection 310, 460.)
10. Drain water from the pipe systems between the main inlet valve (V201-3, V201-9) and control
valve (V201-8). Leave any open drains open afterwards.
11. Isolate the system: Close installed service valve, or use a blind flange, to prevent fluid to enter
the section. (Pipe connection 201.)
12. Drain all water from the filter back flush line. Leave the drain flange in the bottom of the filter
open afterwards.
13. Isolate the system: Close installed service valve, or use a blind flange, to prevent fluid to enter
the section. (Pipe connection 309.)
14. Shut off the breakers on the control cabinet and the lamp drive cabinet. Lock them in that
position. Label them to avoid connection by mistake.
6.2 Protection
Perform the actions below to protect the system:
• Protect all electrical cabinets from humidity with Silica gel or similar.
• Protect all metal surfaces from corrosion attacks with anti-rust oil. The oil must have long
lasting effective treatment for external surfaces.
• Disconnect the air supply to the CIP module. Use service valve if possible, otherwise plug
the air supply inlet.
• Disconnect and drain the membrane pumps (P320-1, P321-5 or P460-7). Rinse with fresh
water and reconnect the pump.
• Articles made of rubber or plastics (for example seals) must not be treated with antirust oil.
• Protect pressure gauges etc. from mechanical damages. The following components are
recommended to be removed and stored safely: PT201-27, PT201-16, and PI201-18.
• Protect components equipped with circuit boards from condensation. Recommendations:
- Remove IP201-7 and FIT201-1 and store in a non condensing environment.
- Remove and store the display for FIT201-1.
- Protect the flow sensor with silica gel or similar. Protect the sensor with the supplied plastic
cover.
• Change the battery in the control panel. If not, the stored log information can be lost during
storage.
• Put all pneumatic valves in open position.
• Every 3 months, operate each valve by close/open exercise. This will keep the valves and
actuators in best condition.
Note that control valve V201-8 must be exercised manually at the same time as the IP201-7 is
removed. Use a wrench to apply appropriate torque.
1. Locate the decommissioning report stored inside the control cabinet. Use this report to the
re-commissioning of the PureBallast system.
2. Clean away the anti-rust oil with a solvent, for example, white spirit.
3. Assemble items that have been disassembled.
4. If applicable: Remove the silica gel bags from all units.
5. Before the system can be activated, it must be checked according to the commissioning
checklist.
This section contains drawings for the PureBallast system. It is divided into three main parts:
• General drawings – overall and principle information for system layout (pipes, components,
electricity, air and water).
• Dimension drawing – detailed component information (dimensions, sizes etc).
• Electrical drawings – detailed electric (circuit diagrams, cablings etc).
See the Contents section at the beginning of this chapter to get an overview of included drawings.
573644
Main components
Q201.2
V201-25
IP201-7 IP converter
S201-7 Strainer
201 Filter inlet / outlet • Ref. filter connections drawing on page 97.
V320-4 CIP / Drain • Ref. AOT module dimension drawing on page 94.
V310-6 Valve
V310-8
S310-7 Strainer
V321-1 Valve
V321-4
6 ConListFig
581726
585828
553407
590773
594956
7.3 Dimension drawings including technical 7 Drawings
data
594657_p1
594657_p2
96
593915
Book No.9000479 02, rev. 0
7 Drawings 7.3 Dimension drawings including technical data
590527_p2
590066 1
590066 2
102 586502
Book No.9000479 02, rev. 0
7 Drawings 7.3 Dimension drawings including technical data
103
590419
Book No.9000479 02, rev. 0
7.3 Dimension drawings including technical 7 Drawings
data
594795
595261_p1
595261_p2
9002906
591773
Book No.9000479 02, rev. 0 115
7.5 Electrical drawings 7 Drawings
581701_p01
581701_p02
581701_p03
581701_p04
581701_p05
581701_p06
581701_p07
581701_p08
581701_p09
581701_p10
581701_p11
581701_p12
581701_p13
581701_p14
581701_p15
581701_p16
581701_p17
581701_p18
581701_p19
581702_p01
581702_p02
581702_p03
581702_p04
581702_p05
581702_p06
581702_p07
581702_p08
581702_p09
581703
594060
146 591097
Book No.9000479 02, rev. 0
7 Drawings 7.5 Electrical drawings
581704_p01
581704_p02
581704_p03
581704_p04
581704_p05
581704_p06
581704_p07
581704_p08
581704_p09
581704_p10
581704_p11
581704_p12
581704_p13
581704_p14
581704_p15
581704_p16
581704_p17
581704_p18
581704_p19
581704_p20
581705_p1
581705_p2
581705_p3
581705_p4
581705_p5
581706
This section contains the type approval for PureBallast together with a summary of the test result
from the land based and ship board testings.
6 TypeApproval 2
6 TypeApproval 3
6 TypeApproval 4
6 TypeApproval 5
2 Maintenance schedule 9
2.1 Serial number information 11
2.1.1 Indicating serial number 11
2.1.2 Example 11
3 AOT module 17
3.1 Safety information 17
3.2 Replace UV lamp and quartz sleeve 19
3.2.1 Disassemble UV lamp 20
3.2.2 Disassemble quartz sleeve 22
3.2.3 Assemble quartz sleeve 22
3.2.4 Check for leaks after quartz sleeve assembly 24
3.2.5 Assemble UV lamp 24
4 Filter 31
4.1 Disconnect power to filter 33
4.2 Remove filter insert 33
4.3 Remove filter candles 34
4.4 Clean filter candles 37
4.5 Replace filter candle 38
4.6 Mount filter candle and filter insert 38
4.7 Mount filter gear motor 39
4.7.1 Check filter gear motor function 40
3
4.8 Change sacrificial anode 40
5 CIP module 43
5.1 Change and refill CIP liquid 43
5.1.1 Change CIP liquid 45
5.1.2 Refill CIP liquid 45
6 Flow meter 53
6.1 Mount flow transmitter 53
6.2 Change direction of flow transmitter 55
6.3 Change direction of flow transmitter
control pad 56
6.4 Clean flow meter electrodes 58
8 Valve actuator 63
8.1 Preparations and conditions 63
8.1.1 Tightening torques for actuators 64
4
8.2 Mount actuator on valve 64
8.3 Dismount actuator 65
8.4 Change direction of actuator – without
position sensor 66
8.5 Mount pilot valve on actuator 67
8.6 Change direction of actuator – with
position sensor 68
8.7 Change direction of actuator – with
proportional valve 71
8.8 Adjust valve end position 72
8.9 Adjust position sensor 73
8.10 Adjust valve traveling speed 73
9 Proportional valve 75
9.1 Replace proportional valve 75
9.2 Replace filter in proportional valve 76
10 Ball valve 79
10.1 Replace seals in ball valve 79
11 Level switch 81
11.1 Mount level switch 81
11.2 Dismount level switch 82
11.3 Test level switch 82
13 Control panel 85
13.1 Clean control panel 85
13.2 Replace control panel 85
13.2.1 Dismount the panel 85
13.2.2 Mount the panel 86
5
14 Remote control panel (optional) 89
14.1 Mount and connect switch for remote
control panel 89
14.2 Mount and connect Ethernet switch for
remote control panel 91
16 Control cabinet 95
16.1 Cable glands 95
16.2 I/O system 97
16.2.1 Disassemble I/O system 97
16.2.2 Assemble I/O system 99
6
1 Introduction
This chapter contains information and instructions about how to service the PureBallast system.
Instructions are sorted per component. The chapter is opened with a maintenance schedule
covering checks and services that must be performed with specified intervals.
NGE R
! DA
• Before maintaining the PureBallast system, the power supply must be switched off, to avoid
accidental starts. See instruction Abort operation and deactivate the system in chapter 3.
Operating instructions and control system description.
NGE R
! DA
NOTE
• All maintenance of the PureBallast system must be logged in the vessel’s maintenance log.
• Always read and follow the documentation that are included in shipment of components and
spare parts regarding handling, safety and disposal.
• Before maintaining the PureBallast system, the following valves must be locked in closed
position: V201-3, V201-9, and V201-8. See instruction Lock valve in closed position on page 60.
• Follow local regulations for electrical installation and grounding (earthing).
• Follow general rules when handling of Alpacon descalant offshore cleaning agent, regarding
ventilation, personal protection etc.
• Cut hazards: Sharp edges on the catalyst cassettes, threads, broken UV lamps and quartz
sleeves can cause cuts.
Follow this maintenance schedule to secure performance, safety and durability of the system and
its components. The schedule is sorted per component. The table refers to instructions usable
when performing the respective action.
AOT reactor Outer inspection Once a year. If necessary, See Spare parts
of seals for change according catalogue for
leakage. to Disassemble service kit.
UV lamp and
Disassemble AOT
reactor.
Filter Inspection and Once a year. See Remove filter Replace filter
cleaning of filter insert. candles, if
insert, including damaged.
filter candles.
See Spare parts
catalogue for
service kit.
CIP liquid level Rule of thumb: See Change CIP If the CIP liquid
check. Once every 3 liquid or Refill CIP is low but the pH
months. liquid. value is below
Depending 3, CIP liquid and
on number of water can be added
AOT modules to fill up the liquid
and ballasting level in the tank.
frequency, the liquid Note: pH value
check might have to must be checked
be performed more afterwards to
regularly. secure correct pH
value.
Flow meter Clean flow meter Once a year. See Clean flow
electrodes. meter electrodes.
or:
After 5 years.
or:
Before storage for
longer periods.
Serial numbers shall be used at error reporting and other contacts where a specific component is
discussed.
• Serial number for the complete PureBallast system. See label on the side of the control cabinet.
• Serial number for the component in question. If the component is installed on, or in, another
component, the number for the mother component shall be stated.
• Item number for the component. The item number identifies a unique component in the system.
It begins with a letter abbreviation indicating the component type, for example: LS (level switch),
P (pump) and PI (pressure gauge). A complete list of abbreviations is found in chapter 6.
Installation description and drawings, section Connection list.
2.1.2 Example
If the level switch is faulty, the following information shall be stated:
7 PB 591098_SerialNo
AOT module
Filter
7 FilterSnr
Electrical cabinets
(Including breakers)
• Control cabinet
• Lamp drive cabinet (LDC)
7 CC Sernr 591773#1
NOTE
NOTE
Flow meter
NOTE
7 FM snr 576179_manual 2
NGE R
! DA
• When performing these routines, consider the need for service kits for UV and quartz sleeves,
containing O-rings, lamps, quartz sleeves etc. See Spare parts catalogue.
• Always disconnect the PureBallast system from the power supply before disassembling, and
secure it from being switched on.
• UV lamps radiate ultraviolet radiation when lit. Only operate the UV lamp when correctly
installed inside the AOT with end caps properly closed.
• Never dismount or handle UV lamps before they are completely cooled down. A hot UV lamp is
under high internal pressure, and the risk of bursting exists. A hot lamp could also cause a
burn if it is touched.
• UV lamps and quartz sleeves are fragile and can easily become damaged. Exercise great care
when handling them. Do not apply vibrations or shock to the UV lamp. This can cause breakage
and shorten lamp life. Broken glass/quartz can also cause severe cuts. Always use protective
eye glasses and clean cotton gloves when handling UV lamps and quartz glass sleeves.
• Do not touch the glass of the UV lamp. Wear gloves and hold the lamp by the ceramic end
parts only. If a lamp is stained on its surface, wipe off the glass with a clean soft piece of cloth
soaked with alcohol. If not, it could cause breakage and shorten lamp life.
• UV lamps contain a small amount of mercury (less than 0.2 grams per lamp) and must be
handled and disposed of with care. Used lamps UV can be handled and disposed of in the same
way as fluorescent lamps. Please refer to national regulations. If a UV lamp has accidentally
been broken, mercury could be spilt. Remove mercury with a special tool such as a syringe
(or use pure sulphure to bind the mercury for easy collection).
• Do not allow mercury to come in contact with your eyes or skin. Do not inhale mercury fumes.
• Free mercury must be kept in an airtight bottle, and must be disposed of according to
national regulations.
• In case of having inhaled mercury fumes, consult a doctor and follow medical instructions.
• Keep the UV lamp in its original protective cover and case when transporting, storing and
disposing of the lamp. Otherwise it could cause injury if the lamp breaks. Do not dispose of
original protective cover and case for the UV lamp, as they should be re-used for storage
and disposal. Mark cases with used UV lamps accordingly, so that they will not be mistaken
for new lamps.
ON
CAUTI
!
• Before installation, check that the UV lamps and quartz sleeves are not broken.
7 593915_replace lamp
1. Electric cable
2. UV lamp
3. Quartz sleeve
4. Hub
5. Bush
6. Cap
7. Cap nut
8. Cable connector
9. Bush
10. O-ring (inside bush)
11. Allen screw
12. Glass socket
13. O-ring
Book No.9000479 02, rev. 0 19
3.2 Replace UV lamp and quartz sleeve 3 AOT module
• The PureBallast system must be turned off, and the power disconnected.
• After UV lamps have been changed, the runtime must be reset in page control system page 5.4
Operation timers: AOT 1–12. Requires login level 2.
• Wait at least 10 minutes after completed ballast or deballast process, to allow the reactor to
cool down to ambient temperature. If the UV lamps are hot they are under internal positive
pressure and may burst if broken.
NG
WARNI
!
• The reactor must not be under pressure when dismounting the UV lamps.
NG
WARNI
!
• Burn hazard: UV lamps can be hot and cause burns.
Follow the steps below
1. Unscrew the nut (7) holding the caps (6). There is one nut on each side of the AOT per UV
lamp. If required, use a screwdriver on the nut, gently tapping with a hammer to release.
2. Carefully disconnect the two cable connectors (8) in both ends of the UV lamp (2).
7UVlampConnection
3. Carefully draw out the UV lamp and one of its bushes (5) with the electric cable (1), by holding
the electric cables in both ends. If required, use a screwdriver to press on the ceramic end of the
lamp inside the bush on the other side whilst carefully pulling the electric cable at the other end.
7UVBushScrewdriver
4. Hold the UV lamp by the ceramic ends after the bushes have been removed. Immediately after
removal, place the lamp in its protective cover.
6. If no quartz sleeves are broken, mount new UV lamps according to the instruction Assemble
UV lamp on page 24. If broken see the Preparations and conditions section above.
NG
WARNI
!
• Hot water may escape from the reactor when removing the drain plug.
Follow the steps below
1. Close the AOT inlet (V201-19.n) and outlet (V201-20.n) valves from the main panel.
2. Depressurize and drain the reactor: Remove the drain plug at the bottom of the AOT reactor.
4. Disassemble the UV lamp according to the instruction Disassemble UV lamp on page 20.
5. Unscrew the three Allen screws (11) of the glass socket (12), just a few turns to release the
sockets on both sides.
7. Carefully remove the glass sockets and the quartz sleeve (3).
8. Remove the O-rings (13) on both sides. The O-rings are firmly stuck in their seat, and will be
damaged during removal, but shall be replaced at assembly. Use an angled or hooked O-ring
tool to loosen and remove the O-ring. Be careful to avoid to break the glass.
If the O-ring is hard to remove, try the following:
– Moisten the O-ring with acetone or denatured alcohol.
– Loose the O-ring in a couple of places before removing it.
– Perforate the O-ring to get a good grip.
10. Carefully clean the surface and remove any small parts, for example glass or rubber.
• Two new O-rings for each glass socket (12) might be needed.
• Two new O-rings (13) for each quartz sleeve (3).
• Use waxed screws.
• Glass sockets and bushes must be dry and clean before mounting.
Follow the steps below
2. Wet the O-rings (13) with water and slip them over respective side of the quartz sleeve. Check
that the O-ring is correctly placed, or they may be damaged and cause leaks.
3. Check the condition of the glass socket O-rings . If needed, replace them with new O-rings.
4. Adjust the quartz sleeve so that the it is approximately 2.5 mm off-center in the AOT reactor,
towards the side you will attach the first glass sockets (12).
5. Check that the quartz sleeve (3 below) is correctly placed. The end (2 below) shall not protrude
passed the planar face (1 below) on the glass socket. The bush must be able to meet this
surface. If the glass sleeve protrudes it might get crush when the bushes are mounted.
7 GlassSocket
6. On the side with the quartz sleeve off-centered, carefully mount the first glass socket on the
quartz sleeve with three Allen screws evenly, but do not tighten the screws. Note that the
waxed screws must be used to avoid seizing. Check again, that the quartz sleeve does not
protrude passed the planar face.
7QuartzSleeve
7. Once the Allen screws (11) are evenly entered, carefully tighten them evenly to a torque
of 7 Nm.
8. Mount the second glass socket. Check again, that the quartz sleeve does not protrude passed
the planar face.
1. Pressurize the AOT reactor with water to between 2 and 4 bar (0.2 and 0.4 MPa).
• A leakage check must have been performed according to the instruction Check for leaks after
quartz sleeve assembly.
• Use waxed screws.
• New heat resistant O-rings must be used in the two bushes. Always replace used O-rings.
• Keep the UV lamp in its protective cover as long as possible. Do not touch the glass of the
lamp; hold the lamp by its ceramic end parts.
• Glass sockets and bushes must be dry and clean before mounting.
Follow the steps below
5. Make sure that the connection is clean to ensure good electric connection (no rust, burning or
fading on the connectors). Reconnect the two cable connectors for the UV lamp.
7UVlampConnection
6. Mount the UV lamp caps and tighten three Allen screws at both ends of the UV lamp, by hand
only. Make sure that the electric cable is is not squeezed between the cap and the bush when
the cap is mounted. Slack can be pushed into the bush.
7. Re-fit the drain plugs at the bottom of the reactor and/or at the flanges under the reactor.
8. Make sure there is no UV lamp failure when the lamp power supply is on.
NGE R
! DA
• Always disconnect the PureBallast system from the power supply before disassembling, and
make sure it remains switched off during service.
NG
WARNI
!
• It is recommended that two persons handle the top plate and catalyst insert, to avoid personal
injuries and damages to threads and catalyst insert.
• The top plate weighs approximately 30 kg. Wear protective footwear.
• Avoid disassembling the catalyst insert. Send it to Alfa Laval for exchange or repair if damaged.
• Wear protective gloves. Sharp edges on catalyst inserts can cause cuts.
• Note that pins and nuts in the catalyst insert are made from titanium. They must never be
replaced with components made from other materials.
Follow the steps below
1. Disassemble all UV lamps and quartz sleeves according to the instructions Disassemble
UV lamp and Disassemble quartz sleeve.
2. Remove one top plate on the reactors in question. All reactor top plates and reactor sides must
be marked to make sure that they are remounted in the same position as before.
4. Remove all nuts and washers except one at the top and one at the bottom of the top plate (to
prevent the top plate from falling).
6. When the top plate is released, remove remaining nuts and washers and carefully lift out
the plate.
NOTE
7. Carefully pull out the catalyst insert by alternately pulling it at the top and bottom. The side
reflector plates are not fixed to the reactor housing, so they might fall to the center of the
reactor housing when the catalyst insert is removed.
2. Place the two side reflector plates into the reactor housing.
3. Carefully insert the catalyst insert. Make sure the fine meshes do not get damaged. Also make
sure the catalyst insert does not protrude outside the reactor housing.
4. Place the new O-ring in its recess in the housing. Hint: Apply some O-ring grease in the recess
to make the O-ring stick.
5. Lubricate all stud threads with Molykote P40 or similar lubricant to prevent seizing.
7. Mount all washers and nuts and tighten evenly by hand, checking that the O-ring enters its
recess correctly.
If the O-ring is not correctly mounted it may be damaged and a leak may occur.
9. Proceed by mounting the quartz sleeves and UV lamps according to instructions Assemble UV
lamp on page 24 and Assemble quartz sleeve on page 22.
7 LPSreplace 7_3_4_1
1. Bracket
2. LPS’s in pair
3. Mounting screw (two per LPS)
4. Cable strap holder
5. Securing nut
• Switch off the PureBallast system and disconnect it from the power supply.
• If the signal cable for this component is damaged during the installation or maintenance, it must
be replaced with the exact same type of cable, and the Intrinsically safe system descriptive
document must be updated. If the signal cable is affected in any way it must restored.
NG
WARNI
!
• Burn hazard: The LPS can be hot and cause burns.
Follow the steps below
1. Dismount LPS
Disconnect all cable straps and cables from the two LPS:s.
NOTE
Since the LPS:s are mounted in pairs, it is necessary to disconnect both LPS:s. Carefully write down
how all cables are connected to the two LPS:s (2).
2. Dismount the bracket (1) on both sides by unscrewing the two securing nuts (5) on the brackets.
3. Release the LPS to be replaced by removing it from the brackets by the mounting screws (3).
4. Mount LPS
Place the cable strap holder (4) under the screw head and mount the LPS to the brackets by
the mounting screws (3).
NOTE
The mounting screws (3) must never be replaced by longer screws. If a screw is longer it will damage the
electronics in the LPS.
5. Remount the two LPS:s (2) mounted at the brackets (1) with the securing nuts (5).
Make sure both LPS:s in pairs are horizontal and in good contact with the rear wall while
mounting the frames and nuts.
7. Connect the cables and replace the cable straps and holders (4) to the LPS according to
marking on the LPS and the Control cabinet / Interconnection diagram in chapter 6. Installation
description and drawings.
NG
WARNI
!
• The installation must be done correctly according to the information above.
• Be careful not to let any cable strands from different cables get in contact.
8. Switch on the power and check that both LPS:s function correctly according to instruction
Test LPS installation below.
NG
WARNI
!
• This instruction must be performed after cable connection. If not hazardous situation may arise
which, if not avoided, will result in death or serious injury.
NGE R
! DA
• Before operating the AOT, make sure that there is water in the reactor.
2. Make sure that the motor circuit breaker is switched off for each LPS in the LDC cabinet(s).
3. Check that there is water in the reactor(s) (LS201-29). Check the LED on the level switch:
Steady yellow light indicates that there is water in the reactor.
4. Switch on the power to the AOT unit using the switches on the AOT breaker cabinet(s).
5. Switch on the motor circuit breaker for each LPS in the LDC cabinet(s). Only the Power on
LED shall be lit with a green light on the LPS. No other events shall be triggered.
6. Start UV lamps one by one from the control system (set to manual mode). Make sure that the
UV lamps are lit: The Power on and UV lamp on LEDs are lit with a green light on the LPS.
7. Close each group and make sure that the UV lamp on LEDs is turned off on the LPS.
8. Check all cabinets visually and make sure that the equipment inside the cabinets is behaving
OK. If necessary recheck and switch on any electric fuse that is switched off.
The VCD (V23) is placed on the ceiling inside LDC cabinet, and the varistor (V1) is placed on a
mounting plate in the upper part of LDC cabinet.
7 V1 581804#1
7 VCD 581805
Varistor (V1)
VCD (V23)
• Switch off the PureBallast system and disconnect it from the power supply.
1. Remove the power and signal cables from the VCD and varistor.
3. Position the new VCD and new varistor and mount them.
4. Reconnect the power and signal cables to the VCD and varistor.
5. Switch on the power and check that the VCD and varistor function correctly.
• Disconnect the power to the filter according to the Disconnect power to filter instruction on page
. Secure it from being switched on.
• Lock valves. See instruction Lock valve in closed position on page 60.
• Only perform maintenance and servicing work when the filter is cooled, depressurized and
drained.
• Visually inspect seals during maintenance. Replace if necessary
ON
CAUTI
!
Filter – Exploded view
1. Gear motor
2. Shaft nut
3. Lock washer
4. Bearing support
5. Cover
6. Carrier screw
7. Top flushing arm
8. Eyelets
9. Flushing device
10. Bottom flushing arm
11. Ball valve
12. Lid (sacrificial anode inside)
7 FilterLock
3. Take the separate safety lock (illustrated above) and slide the plastic part backwards, to
reveal the wire legs.
4. Put the end of the wire leg into the hole under the switch knob.
5. Compress the legs and put the other steel wire leg into the slot to the right of the knob.
6. Slide the plastic part back to cover the wire legs. It is now possible to lock the safety lock with
a padlock, inserted in the loop at the top of the safety lock.
• The filter cover and insert are heavy! Handle with care to avoid personal injuries and damages
to the equipment. Wear protective footwear.
ON
CAUTI
!
• Lifting device is needed for this instruction. Filter cover weight (kg): 72
Filter insert weight (kg) / height (mm): 110 / 800.
Follow the steps below
1. Close the following valves: V201-3, V201-32, and V310-2 according to the instruction in
the Operate valves manually on page 59.
2. Close the compressed air supply for V309-1 by closing the ball valve (11) on the filter.
3. Disconnect the power to the filter according to the Disconnect power to filter instruction on
page .
4. Open the deaeration valve (V201-50) at the top of the filter lid.
5. Disconnect all connection lines from the gear motor (1). Unscrew the screws which fasten
the gear motor.
7. Release the shaft nut (2) and the lock washer (3) and remove them.
8. Unscrew the Allen screws holding the bearing support (4) and remove the bearing support.
10. Loosen the carrier screw (6) holding the top flushing arm (7) to the shaft.
11. Remove the top flushing arm and the filter candle retaining plate.
12. Lift the filter insert vertically out of the filter using the welded-on eyelets (8). Note that the
bottom flushing arm (10) and the shaft must be left in position in the tank. If lifted, there is a
risk that a bearing for the bottom flushing arm will fall out of position.
13. Check that the O-rings on the top flushing arm and on top and bottom of the filter insert are in
good condition. Replace if necessary.
NOTE
• During assembly and disassembly of the filter candles, avoid touching other filter parts with
the filter candles.
• Please proceed with the utmost caution when transporting, assembling, disassembling and
cleaning the filter candles.
• For this operation, the following tool may be required: Drift tool for demounting filter candles.
Note that the drift tool is not part of Alfa Laval’s scope of supply, but can be manufactured
with the following diameter: 57 .
7DriftTool
1. Carrier screw
2. Carrier screw hole
3. Top flushing arm
4. Filter candle
5. Bottom flushing arm
6. Drift tool
7. Direction of filtration through filter candle
2. Fold the filter candle tool so that the gripping ends are tight together.
4. Pull the handles and make sure that the ends grip the inside of the filter candle (4).
6. Check that the O-rings on top and bottom of the filter candles are in good condition. Replace if
necessary.
NOTE
NG
WARNI
!
• Risk for eye and skin irritation. Avoid contact with eyes and wear protective gloves.
NG
WARNI
!
• If Alpacon descalant offshore comes in contact with eyes or skin, rinse thoroughly with cold
water.
• The pH value should be approximately 2.0.
• Please proceed with the utmost caution when transporting, assembling, disassembling and
cleaning the filter candles.
Follow the steps below
1. Follow the instructions Remove filter insert (page 33) and Remove filter candles (page 34) to
remove the filter candles.
2. Soak the filter candles in the cleaning agent and leave them to soak for 1–3 hours.
3. Remove loose particles which float on the top of the cleaning agent during the soaking stage.
4. Spray the filter candles with water from both directions. The water must not be warmer than
60 °C. Note: If a high-pressure cleaner is used, the pressure must not exceed a maximum
of 60 bar (6.0 MPa). If a cleaner with higher capacity than 60 bar is used, compensate
by increasing the distance.
7. Check all filter candles and seals for damage. If needed, replace any damaged filter candles
or seals.
Replace the filter candle O-rings when a candle is replaced. These must be ordered separately.
See illustrations in instructions Remove filter insert on page 33 and Remove filter candles on
page 34.
• When performing this routine, use the service kit for the filter, containing O-rings. New O-rings
for the filter candles are also recommended.
• During assembly and disassembly of the filter candles, avoid touching other filter parts with
the filter candles.
1. Carefully insert the cleaned filter candles into the filter insert from above, with the chamfered
end first. Push the filter candles all the way into the filter insert.
2. Make sure that the seals are properly in place, and fit the filter cover plate.
3. Insert the filter insert vertically into the housing from above.
4. Make sure that the seals are properly in place and put the filter candle retaining plate in place.
8. Fit the cover. Check the seal for damage. Replace any damaged seals as necessary. Tighten
the screw connection evenly, gradually tightening opposite screws step-by-step.
9. Attach the bearing support and the bearing to the coupling. Check the seal for damage.
Replace if necessary.
10. Fasten the bearing support in place with the respective screws. Tighten the screw connection
evenly, gradually tightening opposite screws step-by-step.
11. Place the lock washer on the coupling and screw the shaft nut onto the coupling.
12. Firmly tighten the shaft nut and secure it with the securing plate.
13. Fasten the motor flange in place with the respective screws. Tighten the screw connection
evenly, gradually tightening opposite screws step-by-step.
14. Place the gear motor on the bearing support. Fasten the gear motor in place with the
respective screws. Tighten the screw connection evenly, gradually tightening opposite screws
step-by-step. Re-connect all connection lines as necessary.
1. Filter crank
2. Gear motor
3. Shaft nut
4. Lock washer
5. Filter fitting
6. Bearing support
7. Axel
• When performing this routine, use the service kit for the filter, containing O-rings.
Follow the steps below
1. Put down the lock washer (4) and the shaft nut (3) in the filter fitting (5).
3. Bend one of the lock washer leafs upwards so it fits the bevel in the nut. Fasten the shaft
nut completely.
4. Lower the motor (2) into the filter fitting (5) with the electrical box directed to facilitate electrical
connection. Make sure that the wedge on the motor shaft fit into the groove in the axel (7).
Result: The motor now rests on the bearing support (6), but the bolt holes are not aligned.
6. Check the motor according to the instruction Check filter gear motor function.
1. Use the filter crank (1 in illustration on page 39) to turn the bolt on top of the motor maximum
three turns.
3. Observe the crank: If it remains steady, the motor is OK. If it reverses back, there might be a
mechanical problem that needs to be attended to.
1. Open the deaeration valve and drain valve to drain all water from the filter.
2. Open the lid (12 in the filter exploded view in the introduction of this section on).
3. Inspect the anode. Change if the anode has lost approximately 80 % of the zinc mass.
5. Fasten the lid on the filter and restore the valves in their original positions.
ON
CAUTI
!
• Risk for eye and skin irritation. Avoid contact with eyes and wear protective gloves. Follow
general rules when handling of cleaning agents regarding ventilation, personal protection etc.
ON
CAUTI
!
• If Alpacon descalant offshore comes in contact with eyes or skin, rinse thoroughly with cold
water.
• Before usage, Alpacon descalant offshore must be visually checked. It shall be transparent
light pink in color.
• The instructions requires pH test equipment (paper indicator or ph meter). This is not a part of
Alfa Laval’s scope of supply.
• The pH value should be between 2.0 and 3.0. From the beginning, the pH value is approximately
2.0. When the pH value rises to 3.0 the cleaning liquid must be changed.
• Mixing ratio for Alpacon descalant offshore is 1 part concentrated Alpacon descalant offshore to
20 parts fresh water. Follow this mixing ratio, regardless of recommendation on label.
• The CIP tank shall be filled with maximum 250 liters. Min and max filling of CIP liquid can
be read on the CIP tank.
• Store the CIP liquid according to the instructions on the bottle. General guidelines are:
7 CIP 589741_description
CIP module
1. If the drain valve (2) is connected to the bilge tank, follow the sub steps below. Otherwise, go
to step 2.
1. Open the drain valve V460-3 (2) under the CIP tank.
2. Wait for the tank to be totally drained. Then close the drain valve (2).
2. If the drain valve is not connected to the bilge tank, the steps below can be followed. This
subroutine requires login level 2 or 3 in the control system. .
1. Open valves V320-2 and V460-2 from the control valve, and V230–11 manually. Start
pump P321-5 (4) and P320-1 (4).
2. Wait for the tank to be totally drained. Then stop the pumps and close the valves in
reversed order. Go to step 3.
3. Open the cap (1) on top of the CIP tank and pour 12 liters of CIP cleaning agent into the tank.
4. Fill the tank with fresh water to the Max indication on the tank.
5. Measure the pH value in the tank to secure that it is approximately 2.0. If not, adjust the
proportions: If the pH value is too high, add more CIP cleaning agent. Measure again.
6. Go to control system page 5.3 – Operation timers. Make a note of the number of AOTs that
has been CIPed since last time the CIP liquid was changed. Press the Reset button for “Total
number CIP:ed AOTs”. Requires login level 2. If this is done each time the CIP liquid is
changed, it is possible to build up experience on how many AOTs it is possible to CIP before it
is time to change CIP liquid.
1. Measure the pH value in the tank. Based on the pH value, estimation must be done regarding
the proportions between Alpacon descalant offshore and water. Note that the mixing ratio is
stated under Preparations and conditions above.
2. Mix the cleaning agent with water separately. The result will get better than if mixed mix in
the tank.
3. Pour the mixed CIP liquid into the tank. Do not fill over Max indication on the tank.
4. Measure the pH value in the tank to secure that it is approximately 2.0. If not, adjust the
proportions: If the pH value is still too high, the CIP liquid must be changed. See the Change
CIP liquid instruction in this chapter.
For spare parts ordering, please specify pump model and serial no.
ON
CAUTI
!
• Always wear protective eye glasses and gloves while working on the pump.
NG
WARNI
!
• Always disconnect the PureBallast system from the power supply before disassembling, and
secure it from being switched on.
• Before disassembling the pump, the pneumatic hoses must be disconnected, and the extension
pipe must be removed and blocked.
• Drain the pump from liquids.
• The pump should be placed horizontally on a work bench.
7 CIP pump
1. Remove the CIP pump from the CIP module and place it on a work bench.
3. Place the pump on the side that still has the nuts (the pump lays on the nuts) on a stable ground.
5. Carefully lift up the suction and discharge connections (13). You have the centre block (12)
and one of the housings with pin screws (14) left.
6. Upend the pump and carefully pull out the pin screws (14). Be careful not to damage the
diaphragms (15).
1. Put the house wall with the flat side down on a plane surface.
4. Place one of the pin screws on the inside (behind) the valve ball stopper on the lower valve
seat (21). Carefully pull out the valve seat in the housing.
5. Remove the valve ball (23) from the valve seat, buy using a pin screw: Press out the valve ball
stopper (22), which will release the valve ball.
• Have backup spares of the sealing (36) and backup O-ring (47). There is a risk that these parts
get damaged during this operation.
Follow the steps below
1. Press the diaphragms (15) to their neutral position (both have the same distance to the
centre block).
2. Hold one of the diaphragms (15) and unscrew the other. Then pull out the remaining diaphragm
with the diaphragm shaft (16).
3. Disassemble the circlips (27) which keep the air valve (61) on its place.
4. Press out the air valve. A wood shaft of a hammer can be used. Be careful not to damage the
sealing edges towards the diaphragm or the air valve.
5. If the shaft sealings (36) seem to be worn out, carefully remove them with a pointed tool.
2. Apply some soft soap solution on the air valve O-rings (30).
3. Push the air valve (61) into the housing. Make sure that the O-rings (30) remain in the right
position. Put the circlip (27) on the other side.
4. Put the diaphragm (15) with shaft (16) into the centre block. Screw the next diaphragm (15)
onto the shaft (16) and fix the holes.
1. Make sure that the O-rings (18) are placed on the in/outlet (13) before assembling of pump.
3. Make sure all pin screws (14) have one nut (37) and one washer (38) each. Nut should only be
put on one or two threads.
4. Put all the pin screws through the housing and then turn the housing so it rests on the nuts.
5. Put the centre block (12) to the housing with screws through the centre block. Be careful not to
damage the diaphragms.
6. Place suction and discharge connections (13) in their positions in the housing. Be careful not
to damage the O-rings (18).
7. Put the second housing (11) onto the pin screws (14). Make sure that suction/discharge
connections are in right direction. Be careful with the O-rings.
8. Fasten the nuts (37) crosswise by hand, with or without washers depending on how much of
the thread comes out. Turn the nuts gently with a tool to close the pump. If some of the nuts
were fastened without washer, unscrew those and put washers underneath. After a few weeks
operation a follow up draft of the nuts is recommended.
1. Open valves V320-2 and V460-2 from the control system, and V230–11 manually. Start
pump P321-5 (4) and P320-1 (4).
2. Observe if the motors sound and functions OK. If not, check installation and connections and
attend to and test again.
NGE R
! DA
• Always disconnect the PureBallast system from the power and air supply before disassembling,
and secure it from being switched on.
NGE R
! DA
• The valve bodies does not have individual placing, they can be placed in any order.
7_3_3_1 VBlock
Valve block
2. Lift the valve body: Note: It is easy to drop the sealing when the valve body is lifted. Be
careful not to loose it.
3. Attach a new sealing on the new valve body and fasten the valve body to the valve block.
2. Lift the terminal strip from its position to facilitate cable connection.
3. Attach the cables according to electrical drawing Control cabinet / interconnection diagram in
chapter 6. Installation description and drawings.
5. Place the terminal strip in the slot to the right. Make sure it is pushed to the bottom so it
connects.
2. Operate the service air according to instruction Open and close valves manually (CIP valves)
on page 59 to blow out the dust.
1. Connect the hoses according to the sticker on the CIP module, under the valve block.
• Flow sensor: A pipe with four electrodes detecting the flow. On top of the pipe, there is a
terminal box, where the flow transmitter is mounted.
• Flow transmitter: Monitors and transmits information to the PureBallast control system. The
flow transmitter is also used to set parameters for the flow meter. A Sensorprom in the flow
transmitter contains the data.
• See chapter 6. Installation description and drawings, section Control cabinet / Interconnection
diagram for detailed information.
• It is recommend that a shielded power cable is used.
NG
WARNI
!
• Potential hazards / Grounding: The mains protective grounding wire must be connected to the
terminals in accordance with the diagram (class 1 power supply).
Follow the steps below
1. Remove and discard the lid from the terminal box on the flow sensor.
7 FM Lid
2. Fit PG13.5 cable gland for the power and signal cable.
3. Connect power and grounding to the following terminal positions marked on the circuit board:
1=+
2=–
Grounding.
4. Connect current output signals to the following terminal positions marked on the circuit board:
31 = +
32 = –
6. Mount the flow transmitter on the terminal box using the two screws. If other direction of the
flow transmitter is desired, please follow the instruction Change direction of flow transmitter on
page 55.
7 FM MountTM
7 FM MountTM
2. Disconnect the power supply (terminal positions 1, 2 and grounding) and output signal cables
(terminal positions 31 and 32) from the circuit board.
3. Remove the coil plug (1) from terminal positions 85 and 86. Remove the plug (2) from terminal
positions 82, 0 and 83.
4. Unscrew the two screws (indicated below) holding the circuit board to the terminal box and lift
up the circuit board.
Note that the sensorprom is mounted on the underside of circuit board; be careful not to loose
it. Sometimes, the sensorprom remains in its seat on the terminal box.
7 FM ScrewCricuit
5. Disconnect the grounding wire holding the circuit board to the terminal box.
• If the flow transmitter shall be turned 180°: Move the sensorprom (1 in the illustration
below) to the position on the opposite side of the circuit board and refit in reversed order.
• If the flow transmitter shall be turned 90°: Continue with next step.
6. Unscrew the four screws (2) on the terminal box to loosen it from the flow sensor.
7 FM LooseTB
7. Turn the terminal box to 90° and fasten it with the four screws.
7 FM LoosFrame
7 FMScrewPad
7 FM TurnPad
7 FMScrewPad
5. Snap-lock (a click is heard) the outer frame onto the control pad.
7 FM FastCover
It is important that the electrodes are clean to secure accurate output. If the four electrodes in the
flow sensor get dirty, it may result in inaccurate and varying output.
2. Close the main valves connecting the PureBallast pipe net to the vessel’s ballast pipe net and
secure it from being switched on. See instruction Lock valve in closed position on page 60.
3. Remove all the flange bolts on the flow meter, except one on each flange. Note that the
remaining bolts on each side must be in the same position on respective flange.
4. Loosen the nuts on the remaining bolts. Swing the flow meter outside the pipe.
This section covers instructions on how to open, close and lock/unlock valves manually.
Avoid operating valves manually. Valves are normally operated from page 1.1 Overview in
the control system (manual mode). See chapter 3. Operating instructions and control system
description for instruction.
1. Identify which button (illustrated on page 49) on the valve block that controls the valve. The
lower button operates the inner hose under the valve block, and vice versa. Also see the
sticker under the valve block.
2. Press the button on the valve body with a screw driver to operate the valve.
Valves can be operated using the position screw on the pilot valve.
Position 0 Closed (default position). If the position screw is in position 0 and the valve is
closed, it can be manually opened. But if the position screw is in position 0 and
the valve is opened, it cannot be manually closed.
Position 1 Opened.
1. If there is limited access to the screw, it is possible to remove the DIN connector.
4. When done, turn back the screw to position 0. If the DIN connector was removed, connect it
again.
• Note that the end positions of the end stop bolts are factory adjusted and must not be readjusted.
Follow the steps below
1. Set the valve to closed position from the control system. Control the position indicators, to
make sure.
2. Disconnect power and compressed air. Verify that the valve is not under pressure.
3. Open the padlock (2) on the actuator and remove the safety cover (1) from the bolts (3, 4).
7 576075_lock_manual
4. Measure exactly how far out the end stop bolt (4) is from a reference surface, for example the
actuator house. Make a note of the distance. This information is needed when unlocking
the valve.
5. Open the locking bolt (3) and turn them a couple of turns.
6. Screw the end stop bolt (4) to its bottom position and tighten the locking bolt.
8. Slide the safety cover over the end bolts and lock the safety cover with the pad lock.
• Note that the end positions of the end stop bolts are factory adjusted and must not be readjusted.
Follow the steps below
1. Disconnect all power and compressed air. Verify that the valve is not under pressure.
2. Open the padlock (2) on the actuator and remove the safety cover (1) from the bolts (3, 4).
7 576075_lock_manual
4. Adjust the end stop bolt (4) to the same position (distance from reference surface) as before
locking the valve, according to the notes made during locking.
NOTE
• It is important to adjust the ends stop bolt to the correct position. Otherwise the actuator
may be damaged.
5. Tighten the locking bolt (3).
7. Slide the safety cover in position over the end stop bolts. Lock the safety cover with the pad
lock.
7 Actuator
Valve actuator
1. Safety cover
2. Pad lock
3. Lower position for indicator screw
4. Upper position for indicator screw — with screw
5. Position indicator
6. Center screw
7. Bracket
8. Puck
9. Locking bolt
10. End stop bolt.
M5 05–06
M6 10–11
M8 23–25
M10 48–52
M12 82–86
M14 132–138
M16 200–210
M20 390–410
ON
CAUTI
!
• The actuator must not be pressurized at any time during installation as it may result in injury.
• The valve must be in closed position.
• The valve position must not be adjusted during the routine.
• The utmost cleanliness is required during air supply connection to the actuator, that is, the
connecting pipe thread, fittings and seals must be clean and dirt-free.
• Before fitting onto the valve, make sure the actuator/valve is correctly orientated, depending on
which direction of rotation is required.
• When using a spring return actuator for a fail safe operation, ensure that when air or power
failure occurs, the direction of rotation is correct for your application.
Follow the steps below
1. Make sure that the groove (2) at the top of the stem (3) is in line with the throttle. In some cases
the valve stem is fitted with one or two spindle-bushings (4) to prevent play. If so, make sure
that the bushing is in place. The illustration shows a square variant, but octagoal versions exist.
7 ValveStem
2. Make sure that the lock pin (inside the valve stem) only travels in the allowed sector (1) and
that it does not pass the opening (5).
3. Fit the actuator onto the valve stem. The actuator may only be positioned in even 90° intervals
in relation to the valve. It is not allowed to adjust the position by turning the actuator by hand
after it is fitted on the valve stem.
4. Mount the actuator on the valve with the four hexagonal screws. For each screw, one washer
and one spring washer shall be used. Tighten with torque according to the table Tightening
torques for actuators on page 64.
5. Operate the valve to make sure it operates in the desired direction of rotation. Control the
position indicators, to make sure that the valve is in correct position.
6. Next step is to mount the pilot valve on the actuator, if not already mounted.
• Verify that the actuator is not pressurized. Always use caution and double-check that ports 2
and 4 are vented and are free from any accessory and/or device.
• The valve must be in closed position.
• The valve position must not be adjusted during the routine.
• If the actuator is a spring return unit, make sure the actuator is in the failed position before
disassembling.
Follow the steps below
1. Disconnect the power to the proportional valve. Let the air connection remain.
Result: Valve goes to closed position (due to the air connection). The yellow indicators on
the puck shows position of valve: closed.
3. Unscrew the four hexagonal screws holding the actuator to the valve. Some valve stems are
equipped with one or two sockets. Make sure not to lose them.
1. Dismount the actuator from the valve according to instruction Dismount actuator on page 65.
Put the actuator on a work bench.
2. If the actuator is equipped with a bracket and junction box: Disconnect the DIN connector
from the coil: First loosen the screw (1), and then pull up the connector (2). Make sure not
to loose the screw or the gasket.
7 DisconDINcon
3. If the actuator is equipped with a bracket and junction box: Unscrew the four hexagonal screws
holding the junction box bracket on the actuator, and remove the bracket.
4. Unscrew the center screw (4) holding the puck (6) and a bracket (5).
7 ActDirectWithout
5. Lift the puck (6), rotate it 90° and fasten it with the center screw (4) and bracket (5).
6. Make sure that the yellow position indicator (3) in line with the valve throttle.
7. Mount the junction box bracket on the actuator with the four hexagonal screws.
8. Fit the actuator onto the valve stem in its new position according to instruction Mount actuator
on valve on page 64.
7 MountPilote
1. Check that the O-rings are fitted on the pilot valve, on the side facing the actuator.
2. Fit the pilot valve on in the actuator, so that the pin on the actuator fits the hole on the pilot
valve. The throttle valves (2 and 4) shall be directed downwards.
3. Mount the pilot valve with two Allen screws in the holes (1).
5. Fit the DIN connector (5) on the coil, including gasket. Then fasten the connector with the
screw (6).
This instruction is valid for the following valves: V201-3, V201-9, and V212-31.
1. Dismount the actuator from the valve according to instruction Dismount actuator on page 65.
Put the actuator on a work bench.
2. Disconnect the DIN connector (1) from the coil: First loosen the screw (1), and then pull up
the connector.
7 DisconDINcon
3. Unscrew the four screws holding the junction box cover, and remove the cover.
4. Unscrew the four Allen screws holding the junction box to the bracket, and remove the junction
box bracket.
5. Loosen the junction box bracket by unscrewing the two Allen screws holding each position
sensor. The screws are reached through the hole in the junction box bracket.
For actuators with one sensor: Unscrew the two hexagonal screws holding the junction box
bracket to the actuator on the side without sensor.
6. Unscrew the center screw (6) holding the puck (8) and a bracket (7).
7 DirActPosSnsr
7. Lift the puck (8), rotate it 90° and fasten it with the center screw (6) and bracket (7).
8. Move the indicator screws vertically on the position sensor (5): Screws on upper position (4)
shall be moved to the lower position (3), and vice versa.
For actuators with one sensor: Screw on yellow indicator is moved to the top position. Screw
on black indicator is moved to the lower position on the black indicator on the opposite side of
the puck.
9. Mount the junction box bracket, distance and position sensor on the actuator with the four
hexagonal screws. The position sensor must be in upright position. Tighten loosely.
10. Adjust the sensor to a maximum distance of 1 mm from the puck (7). The position sensor and
the position indicator must be close to give a signal. Tighten the screws to fixate the position.
12. Fit the actuator onto the valve stem in its new position according to instruction Mount actuator
on valve on page 64.
13. Make sure that the yellow indicator (5) in line with the valve throttle.
16. Check that the installation is OK, by making sure that the A1 LED is lit on the position sensor
(visible from the side).
1. Dismount the actuator from the valve according to instruction Dismount actuator on page 65.
2. Fit the actuator onto the valve stem in its new position according to instruction Mount actuator
on valve on page 64. The actuator may only be positioned in even 90° intervals in relation
to the valve. It is not allowed to adjust the position by turning the actuator by hand after it
is fitted on the valve stem.
Result: The position indicators (1) are now in the wrong positions and must be changed.
7 DirectProp
3. Change place of the 2 yellow and 2 black position indicators (1). The indicators can be pushed
upwards from the puck (4) with a screw driver. When they are pushed back, make sure that
they snap into position. The yellow indicators shall now show valve position: closed.
7 576075_lock_manual
1. Note the exact position of the position indicator for reference after adjustment.
2. Open the padlock (2) on the actuator and remove the safety cover (1).
Result: Two sets of bolts are displayed. The right set adjusts closing position and the left
set adjusts open position.
4. Adjust end position by turning the end stop blot (4) with small turns.
– Clockwise decrease the end position.
– Counterclockwise increase the end position.
NOTE
6. Tighten the locking bolt (3) to fixate the position of the end stop bolt (4).
This instruction is valid for the following valves: V201-3, V201-9 and V212-31.
1. Follow the instruction Change direction of actuator – with position sensor on page 68, but
ignore all steps concerning change of orientation of the actuator and puck.
2. When the position sensor are described, be careful to mount the position sensors close to the
puck. The position sensor must be in upright position.
3. Refit in reversed order. Do not forget to perform the check at the end of the instruction Change
direction of actuator – with position sensor.
7 AdjustTravel
1. Operate the valve manually to check traveling speed according to the instruction in the Operate
valves manuallyon page 59.
This section contains mounting and maintenance information for the proportional valve installed on
the actuator for control valve V201-8. The proportional valve is mounted together with actuator
and valve body at delivery.
NOTE
• In case of malfunction, the proportional valve should be replaced. Do not try to disassemble
or adjust the component!
• After a proportional valve has been replaced, it must be checked for correct function. Normally,
no adjustment of settings is required.
1. Disconnect the power cable from the proportional valve. Note how the cable is connected,
to be able to reconnect correctly.
2. Disconnect the air supply to the proportional valve and the air connections between the
actuator and the proportional valve. Note how the air supply is connected, to be able to
reconnect correctly.
3. Loosen the four hexagonal screws between the proportional valve and the bracket.
1. Separate the two hexagonal bolts on the hose gland (1). The filter is fitted inside.
7 CVfilter591890#0
2. Check the filter (2) and replace it, if it is discolored. At the same time, replace the O-ring (1)
and baffle (3).
7 PropFilter 595541#1
7 BallV
32 = 1¼ 20–25 Nm 14.3 Nm
inches
2. With the valve in the open position (lever to be parallel to the axis of the pipe), remove all the
body bolts (19) except one.
3. Loosen the nut (20) on the remaining bolt. Swing the body outside the pipe.
5. Replace seals (5, 6, 7, 9, 10, and 24). They are available in a spare parts kit for the ball valve.
6. Mount in reverse order. The body bolts of the valve should be tightened evenly. Tighten
one-side snugly, then the one diagonally across. Repeat for the other bolts, bringing them all
down tightly in sequence. Make sure the maximum tightening torque is observed according
to the table above:
This section contains information about the level switch LS201-29 installed in the AOT reactor. For
information about status indications, see chapter 5. Alarms and faultfinding, section Level switch.
7LS Component
Level switch
NOTE
2. Seal the level switch with lock tight or equivalent pipe seal.
4. Identify the sensor align mark (▼) on the component. Make sure that it is positioned on the
upper side of the level switch.
5. Complete the seal carefully by tightening the component with a spanner. Use the spanner on
the hexagon flats, but not on the level switch body.
• The external surface may be hot. Care must be taken to avoid possible burns.
Follow the steps below
2. Loosen the component with a spanner. Use the spanner on the hexagon flats, but not on
the level switch body.
3. Remove the level switch and remove the old seal from the threads.
1. Make sure that the component i powered (the green LED shall be lit).
2. Hold a magnet to the test point indicated on the on the level switch, indicated below.
7LS Test
3. Make sure the level switch reacts to the magnet. The component is OK if the green and
yellow LED is lit.
This section contains information about the temperature switch TS201-60 and the temperature
transmitter TT201–33 installed in the AOT reactor. The two components are similar in design, so
the same instructions can be used.
7 TS and TT
NOTE
1. Seal the component’s threads using lock tight or equivalent pipe seal.
3. Tighten the component with a spanner. Use the spanner on the hexagon flats, but not on
the components body.
• The external surface may be hot. Care must be taken to avoid possible burns.
Follow the steps below
2. Loosen the component with a spanner. Use the spanner on the hexagon flats, but not on
the components body.
3. Remove the level switch and remove the old seal from the threads.
NOTE
• Control panels may only be cleaned when set in wipe mode. This is to prevent unintended
functions from being triggered by buttons pressed during cleaning.
Preparations and conditions
• Never use aggressive solvents, chemicals, scouring agents, pressurized air or steam jet.
Follow the steps below
2. Clean the display and surrounding front cover with a soft cloth and mild detergent. Do not
spray detergent directly on the control panel.
7BeijerScrews
4. Hold the panel on the outside so it does not fall out. At the same time: Slide the brackets
and remove them. Then remove the panel.
7BeijerBracket
2. Hold the panel on the outside so it does not fall out. At the same time: Attach the brackets on
the inside by sliding them into place.
7BeijerBracket
7BeijerScrews
4. Open the small cover on the rear side. Make sure that all DIP switches are in position OFF.
7BeijerMODE
7. Remove the laminated film, to avoid static electricity that could damage the terminal.
8. Make sure that the control panel is brought to ambient temperature before it is started. If
condensation forms, ensure that the operator panel is dry before connecting it to the power
outlet. Ensure that the voltage and polarity of the power source is correct.
This section covers information on how to mount and connect communication components for the
remote control panel.
The information in this instruction is also given in the Control cabinet / Circuit diagram in chapter 6.
Installation description and drawings.
7 594060 RCP
7 RemotPanelCon
• 24 VDC cables are not included in scope of supply. Use a cable with minimum cross section of
0.75 mm2, preferably halogen free and flexible.
• The remote control panel must have been mounted on a location of your choice. See Remote
control panel (optional) / Dimensional drawing in chapter 6. Installation description and drawings.
• Switch off the PureBallast system and disconnect it from the power supply.
• Note that the terminals are marked with 4 (+), 5 (–) and 6 (GND).
• Two wires are mounted between terminal and switch power contact (2) no 1=DC–, no 2=DC+,
cables are marked + and –.
Follow the steps below
1. Mount the switch (3) at a location of your choice. Note that the delivered Ethernet cable to be
used between the switch and the control panel is 1.5 meters.
2. At the back of the remote control panel, fasten the Ethernet cable in one the Ethernet ports.
Fasten the other end of the cable in the connect switch’s Ethernet port number 1 (1).
3. Connect an Ethernet cable from the connect switch to the switch in the control cabinet. See
position 1 in illustration on page 91. Also see cable W501 in Control cabinet / Interconnection
diagram.
If the distance between the two switches are more than 100 meter, a fiber cable must be used
instead of an Ethernet cable. Fiber cables are connect to the fiber ports (7) on the connect
switches.
4. If more than one remote control panel is installed, connect an Ethernet cable from Ethernet port
number 2 (1) on the connect switch to the connect switch for the second remote control panel.
If the distance between the two switches are more than 100 meter, a fiber cable must be used
instead of an Ethernet cable. See step 3 above.
5. Connect a 3 core cable from connection switch terminals 4, 5 and 6 to the remote control
panel’s 24 VDC port (2).
7 591773 RI
1. Loosen the right end stop on the DIN rail at position (1).
3. Fasten the end stop to fixate the Ethernet switch at position (1).
4. On the PLC, disconnect the Ethernet cable (coming from the main control panel) from port IF2
and connect it to the Ethernet switch port: 1.
5. Connect an Ethernet cable in the IF2 on the PLC and connect the other cable end to the
Ethernet switch port: 2.
6. Connect wire 400 (DC–) to terminal 400 (3) and to Ethernet switch (1) terminal no: 1.
7. Connect wire 402 (DC+) to PLC terminal 15 (2) and to Ethernet switch (1) terminal no: 2.
This section covers information on how to mount and connect communication components in the
control cabinet. The information is only relevant if this option is added after installation.
The information in this instruction is also given in the Control cabinet / Circuit diagram in chapter 6.
Installation description and drawings.
• Switch off the PureBallast system and disconnect it from the power supply.
• Delivered cable shall be used.
Follow the steps below
1. Loosen the right end stop on the lowest DIN rail in the control cabinet at position (1).
2. Mount the connection terminal (X4) on the DIN rail at position (1).
7 RIintegr 591773-82
5. Lead the cable in the cable ducts in the cabinet the door to the backside of the control panel.
6. Fasten the cable (D-SUB) to the COM1 port at the backside of the control panel.
7 RemotPanelCon
7. Connect the signal cables (RS422 or RS485) from the connection terminal to the ISCS
according to drawing Interconnection diagram / Control cabinet.
This section covers maintenance information for the control cabinet and LDC.
7 Cable0
1. Lubricate the inside surfaces of the frame with Roxtec Assembly Gel or equivalent, specially
in the corners.
7 Cable1
4. Peel off layers until you achieve a 0.1-1.0 mm gap between the two module halves when
held against the cable.
7 Cable2
7 Cable3
5. Lubricate all modules thoroughly, both on the inside and the outside surfaces.
7 Cable4
6. Insert the modules from the back of the frame opening. If possible, start with the largest
modules.
7 Cable5
7. Tighten the compression unit firmly to seal the frame. Maximum 10 Nm. A good indication is
when the lubrication is squeezed out between the modules.
7 Cable6
1. Hold down the plastic clip on the top of the terminal block and pivot the block towards you.
7IO1_X025002A
3. Hold down the triangle on the top of the I/O board and loosen the board.
7IO2_X025003A
4. Pull the board straight out (otherwise it can fasten in one of its guides).
7IO3_X025004A
5. Compare the part number of the new I/O board to the old board, to make sure it is correct.
6. If changing more than one board at a time, check with the electrical diagram to ensure that
the boards are mounted in the right places.
7. Mount the new I/O board by pressing it straight into place. Make sure the board is firmly in
place, otherwise it will be impossible to mount the cable terminal.
7IO4_X025005A
8. Remount the terminal block. Make sure the clip on the bottom of the block fastens properly in
place on the axel on the bus holder.
7IO5_X025007A
9. Pivot the terminal block on the axel until the clip on the terminal block top fastens into place in
the I/O board.
7IO6_X025006A
2. Put back all additional locking clips by pushing them into their holes. The additional clips are
required to safely attach the electronic module to the bus module.
2 Control cabinet 6
2.1 Cabinet 8
2.2 Terminal block 10
5 AOT module 16
5.1 Reactor 18
5.2 Lamp drive cabinet 20
5.3 Valve 44
5.4 Valve 46
12 CIP module 66
12.1Fresh water piping 70
12.2Pipe #5 76
3
12.3Pipe #6 78
12.4Pump 80
12.5Valve block 82
12.6Air distribution, CIP 84
13 CIP liquid, 15 L 86
14 Ancillary equipment 88
14.1Sampling device 90
14.2Pressure transmitter set 92
14.3Pressure gauge set 94
14.4Valve V403-35 96
4
1 Important information
1 Important information
• State number of ordered parts. Note that the quantity in the tables do not states number of parts
delivered (only the how many of that parts that are included in the mother component).
• Safeguard your commitment to quality by always using genuine Alfa Laval spare parts.
Remember, Alfa Laval cannot accept responsibility for the failure of separator equipped with
non-original spare parts. We guarantee the quality and reliability of our products.
• When ordering, refer to part number listed in this catalogue and serial number, described in
chapter 7. Service manual, section Serial number information.
Book No. 5
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
2 Control cabinet
Machine unit number or
Subassembly description
591773-
Ref Part No Description -80 Notes
Quantity
1 594447 80 Cabinet 1 See page 8
4 595670 80 Panel 1
4A 595670 01 Panel 1
4B 595670 02 Backlight -1
7 223101 47 Washer 12 BRB 6,4x12x1,6 fzb
8 221891 04 Lock nut 12 M6M 6 fzb
10 591102 01 Power supply 1
11 591103 12 Over current prot. Relay 1
12 591103 10 Auxiliary contact 2
13 591103 29 Fuse 1
14 591103 16 Fuse 4
15 591103 17 Auxiliary contact 2
16 582212 24 End stop 9
17 591103 38 Contactor 1
18A 580986 17 Bus module 14
18B 580986 30 Supply Bus Module 1
18C 580986 58 Interface Module 1
18D 580986 76 Communication module 1
18E 580986 04 6 Digital input 5
18F 580986 32 Supply Module 1
18G 580986 11 6 Digital Output 6
18H 580986 08 4 Analogue input 1
18I 580986 33 Output Module 1
18J 580986 16 Terminal block 12-pin 15
18K 580986 44 Additional locking clip 15
18L 580986 55 Compact Flash 1
18M 580986 08 4 Analogue input 1
18N 580986 79 Battery, 3V 950mAh -1
19 582212 72 Connector 2
20 591103 36 Main breaker 1
20.1 591103 37 Breaker handles 1
21 582212 88 PIT 2,5 6
22 582212 89 D-ST2,5 1
23 582212 91 VIP-2, D 9SUB 1
24 582212 90 Cable-D 9SUB 1
25 594774 80 Terminal block 1 See page 10
27 583556 08 Cable channel 40x80 3
31 593724 02 Distance screw 8
32 593724 01 Distance screw 2
36 594009 02 Screw 4 MRX-Z 4x15 fzb
37 582221 90 PE Connection bar 1 L=450mm
38 582212 15 PE/SC Bar 1 L=500mm
39 582212 19 Sc Clamp 18
40 582212 93 Sc clamp 2
41 594781 01 Distance 5
42 594009 02 Screw 5 MRX-Z 4x15 fzb
43 591922 01 Cable seal 1
44 595361 01 Cable seal 1
46 223101 47 Washer 3 BRB 6,4x12x1,6 fzb
47 221803 02 Nut 3 M6M 6 fzb
48 582221 89 Cable fixing spiral 1
51 591103 31 Locking device 1
52 595673 01 Ethernet cable 1
65 260137 04 Pop rivet 4
67 591103 39 Over current prot. Relay 1
Z 597330 01 Cable seal -1
Z0.1 597331 01 Cable seal -1
6 Book No.
2 Control cabinet
2307
Book No. 7
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
2.1 Cabinet
Machine unit number or
Subassembly description
594447-
Ref Part No Description -80 Notes
Quantity
2 593710 01 Door 1
3 594009 01 Screw 6 MRX-Z5x6 fzb
4 26556 Spring washer 6 FBB 5,1 fzb
6 587276 02 Washer 12
7 221891 05 Hexagon lock nut 12 M6M 8 fzb
9 579385 01 T-handle 1
11 593991 01 Latch 1
12 593781 01 Rod 2
15 223107 34 Spring washer 4 FBB 6,1 fzb
16 221891 04 Lock nut 4 M6M 6 fzb
17 593240 01 Bracket 1
19 593254 01 Retaining ring 1
20 223107 34 Spring washer 2 FBB 6,1 fzb
21 221891 04 Lock nut 2 M6M 6 fzb
22 221711 19 Screw 1 MC6S 6x25 fzb
23 593282 01 Washer 1 BRB 6,4x12x1,6 polyamide
24 221803 02 Nut 2 M6M 6 fzb
25 593239 01 Nut 1
26 260154 08 Lifting eye bolt 2
27 70560 Washer, 8,4x16x1,6 2 BRB 8,4x16x1,6 fzb
28 221891 05 Hexagon lock nut 2 M6M 8 fzb
29 581688 01 Bracket 4
30 221711 16 Screw 8 MC6S 6x16 fzb
31 223101 47 Washer 8 MRM 6,4x12x1,6 fzb
32 221891 04 Lock nut 8 M6M 6 fzb
33 587276 02 Washer 3
34 221891 05 Hexagon lock nut 3 M6M 8 fzb
35 544465 04 Locking liquid 1 Loctite 270
36 593282 02 Washer 2 BRB 8,4x25x2 polyamide
37 594488 01 Washer 4
38 70560 Washer, 8,4x16x1,6 3
39 223101 73 Washer 1 BRB 6,7x16x1,5 fzb
8 Book No.
2.1 Cabinet 2 Control cabinet
2308
Book No. 9
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
10 Book No.
2.2 Terminal block 2 Control cabinet
2310
Book No. 11
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
12 Book No.
3 Remote control panel
2311B
Book No. 13
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
14 Book No.
4 Switch connecting set - Remote ctrl
panel (option)
2312B
Book No. 15
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
5 AOT module
Machine unit number or
Subassembly description
592830-
Ref Part No Description -80 Notes
Quantity
1 593915 80 Reactor 1 See page 18
2 591097 80 Lamp drive cabinet 1 See page 20
3 221803 22 Nut 8 M6M 12 A4-70
4 223101 35 Washer 8 BRB 13x24x2,5 A4
5 594412 80 Valve 1 V201-19
See page 44
6 594412 80 Valve 1 V201-20
See page 44
7 260001 40 Screw 16 M6S 20x50 fzb
8 223101 39 Washer 16 BRB 21x37x3 A4
9 594413 80 Valve 1 V320-4
See page 46
10 594413 80 Valve 1 V321-2
See page 46
11 594413 80 Valve 1 V404-36
See page 46
12 2210462 10 Screw 12 M6S 16x40 fzb
13 223101 37 Washer 12 BRB 17x30x3 A4
14 594171 01 Vibration limit switch 1 LS201-29
15 594169 01 Thermometer, resistance 1 TT201-33
16 594157 01 Temperature switch 1 TS201-60
17 1761805 05 Safety valve, 8 bar 1 RV201-23
18 597049 01 Coupling, elbow 90 1
19 594707 01 Pipe 1
20 592827 01 Bracket 2
21 27345 Nut, M8 4 M6M 8 fzb
22 70560 Washer, 8,4x16x1,6 4 BRB 8,4x16x1,6 fzb
23 592823 01 Tee, 3/4 2
24 595302 01 Valve, 3/4 DN20 2 V401-51 and V401-52
25 540006 01 U-bolt 4
26 221803 02 Nut 8 M6M 6 fzb
27 223101 47 Washer 8 BRB 6,4x12x1,6 fzb
28 594785 01 Hose, R3/4 - Rp1/2 2
29 594785 02 Hose, R3/4 - Rp1/2 2
30 591076 01 Plate 3
31 221711 08 Screw 6 MC6S 6x16 A4-70
32 583488 01 Pipe clip 3
33 591092 01 Pozidrive Countersink 6
34 581534 01 Distributor 1
36 558710 01 Nipple 5
37 592304 01 Plug 1
38 592304 02 Plug, 1/4 1
39 580759 04 Push-In Fittings 5
40 544465 06 Locking liquid 0 Or eqvivalent
41 1270001 Lifting instruction 1
42 554214 01 Cable tie 21
43 595272 01 Tube, 6x1 mm 7.5
44 956264 17 Name sign 2 Alfa Laval Logo
45 588835 01 Brand label 2 Wallenius Water Logo
48 595390 01 Lamp label A 1
49 595390 02 Lamp label B 1
53 221803 22 Nut 1 M6M 12 A4-70
54 223101 35 Washer 1 BRB 13x24x2,5 A4
55 27345 Nut, M8 1
56 587276 02 Washer 1
57 70560 Washer, 8,4x16x1,6 1
16 Book No.
5 AOT module
2314
Book No. 17
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
5.1 Reactor
Machine unit number or
Subassembly description
593915-
Ref Part No Description -80 Notes
Quantity
1 592280 80 Reactor housing 1
2 593913 80 Top plate 2
4 579376 01 O-ring, 750x5,7 2
5 589076 01 Stud bolt 56
6 221803 29 Nut 56 M6M 10 A4-70, vaxed
7 592532 01 Distance 56
8 592685 01 Reflector 1
9 592684 01 Catalyst insert 1
10 596346 01 Plug, ISO-G 1 1
12 589774 01 O-ring 24
13 526350 05 Plug 2 R-236, DN20
14 587587 01 Glass socket 24
15 221711 09 Screw 72
16 588228 01 Lamp bush 24
17 579380 01 O-ring, 15,1x2,7 24
18 590703 80 Cap 24
19 579379 01 Nut 24
21 66169 Drive screw 4
24 537086 02 Molybdenum disulfide past 0
24A 594306 02 Solid lubricant paste 1
Z 579367 98 UV Lamp set -1 1 pcs of UV lamp and 2 pcs of Ref 17.
Z0.1 579367 95 UV Lamp kit -1 12 pcs of Ref Z
Z0.2 594645 80 Quartz sleeve set -1 1 pcs of Quarts sleeve and 2 pcs of Ref
12.
Z0.3 594646 80 Sealing kit -1 2 pcs of Ref 4 and 24 pcs of Ref 12.
18 Book No.
5.1 Reactor 5 AOT module
2315
Book No. 19
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
20 Book No.
5.2 Lamp drive cabinet 5 AOT module
2318B
Book No. 21
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
22 Book No.
5.2 Lamp drive cabinet 5 AOT module
2318B
Book No. 23
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
24 Book No.
5.2 Lamp drive cabinet 5 AOT module
2376B
Book No. 25
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
26 Book No.
5.2 Lamp drive cabinet 5 AOT module
2319
Book No. 27
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
28 Book No.
5.2 Lamp drive cabinet 5 AOT module
2320C
Book No. 29
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
30 Book No.
5.2 Lamp drive cabinet 5 AOT module
2321
Book No. 31
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
32 Book No.
5.2 Lamp drive cabinet 5 AOT module
2322
Book No. 33
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
34 Book No.
5.2 Lamp drive cabinet 5 AOT module
2323
Book No. 35
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
36 Book No.
5.2 Lamp drive cabinet 5 AOT module
2324C
Book No. 37
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
38 Book No.
5.2 Lamp drive cabinet 5 AOT module
2325
Book No. 39
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
40 Book No.
5.2 Lamp drive cabinet 5 AOT module
2327B
Book No. 41
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
42 Book No.
5.2 Lamp drive cabinet 5 AOT module
2328
Book No. 43
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
5.3 Valve
Machine unit number or
Subassembly description
594412-
Ref Part No Description -80 Notes
Quantity
1 576886 02 Valve, DN150 1 Lug type
2 576075 11 Air actuator, DA301 1
3 576071 01 Pilot valve 1
4 585976 01 Coil, 24 V DC 1
5 594410 01 Valve connector 1
6 583012 01 Throttle valve, 1/4 2
Z 576075 75 Actuator spare part kit, DA/SR 301 -1 See page 98
44 Book No.
5.3 Valve 5 AOT module
2329
Book No. 45
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
5.4 Valve
Machine unit number or
Subassembly description
594413-
Ref Part No Description -80 Notes
Quantity
1 590037 01 Valve, DN32 1
2 576075 21 Air actuator, SR101 1
3 576071 01 Pilot valve 1
4 585976 01 Coil, 24 V DC 1
5 594410 01 Valve connector 1
6 583012 01 Throttle valve, 1/4 2
Z 576075 71 Actuator spare part kit, DA/SR 101 1 See page 98
46 Book No.
5.4 Valve 5 AOT module
2330
Book No. 47
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
48 Book No.
6 Filter DIN DN300
2377
Book No. 49
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
50 Book No.
6.1 Filter DIN 300 6 Filter DIN DN300
2472
Book No. 51
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
52 Book No.
6.1 Filter DIN 300 6 Filter DIN DN300
2472
Book No. 53
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
54 Book No.
6.1 Filter DIN 300 6 Filter DIN DN300
2379
Book No. 55
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
56 Book No.
7 Valve V201-3 and V201-9, DN300 PN10
2360
Book No. 57
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
58 Book No.
8 Valve V201-32, DN300 PN10
2361
Book No. 59
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
60 Book No.
9 Valve V212-31, DN300 PN10
2362
Book No. 61
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
62 Book No.
10 Valve 201-8, DN250
2317
Book No. 63
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
64 Book No.
11 Flow transmitter, DN300
2363
Book No. 65
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
12 CIP module
Machine unit number or
Subassembly description
589741-
Ref Part No Description -80 Notes
Quantity
1 590207 80 Frame 1
3 592677 01 Beam 2
4 592760 01 Beam 1
5 221035 06 Screw 14 M6S 8x20 fzb
6 70560 Washer, 8,4x16x1,6 28 BRB 8,4x16x1,6 fzb
7 27345 Nut, M8 14 M6M 8 fzb
8 592653 01 Pipe support 1
9 590425 01 Pipe support 1
10 592467 01 Pipe support 1
11 590424 01 Pipe support 1
12 590270 01 Pipe support 1
13 26853 Screw 8 M6S 6x20 fzb
14 221803 02 Nut 8 M6M 6 fzb
15 223101 47 Washer 20 BRB 6,4x12x1,6 fzb
16 590238 80 Fresh water piping 1 See page 70
17 589526 07 U-bolt clamp, c-c 56,5 2
18 589526 06 U-bolt clamp, c-c 50,5 4
19 70560 Washer, 8,4x16x1,6 12 BRB 8,4x16x1,6 fzb
20 27345 Nut, M8 12 M6M 8 fzb
21 590414 01 Tank 1
22 590260 80 Pipe #2 1
23 590255 80 Pipe #3 1
24 590253 80 Pipe #4 2
25 590252 80 Pipe #5 1 See page 76
26 590258 80 Pipe #6 1 See page 78
27 591410 80 Pipe #7 1
28 590256 80 Pipe #8 1
29 590355 80 Pipe #9 1
30 590259 80 Pipe #10 1
30A 592649 01 Nipple 1
31 590261 80 Pipe #11 1
32 221035 36 Screw 4 M6S 8x12 fzb
33 2210295 32 Screw 8 M6S 5x10 fzb
34 586773 80 Pump 1 See page 80
35 586773 80 Pump 1 See page 80
36 70560 Washer, 8,4x16x1,6 8 BRB 8,4x16x1,6 fzb
37 27345 Nut, M8 8 M6M 8 fzb
38 591411 80 Valve block 1 See page 82
39 221711 18 Screw 4 MC6S 6x12 fzb
40 590544 01 Filter regulator 1
41 591585 01 Bracket 1
42 591406 01 Mounting ring 1
43 221711 17 Screw 2 MC6S 6x10 fzb
44 1779813 01 Valve, 1/4" 1
45 589526 05 U-bolt clamp, c-c 35 2
46 70560 Washer, 8,4x16x1,6 4 BRB 8,4x16x1,6 fzb
47 27345 Nut, M8 4 M6M 8 fzb
48 591693 01 Valve, needle type 2
49 590476 01 Nipple, ISO-R 3/4-1/2 1 ISO-R 3/4 - 1/2
50 590313 01 Valve, angle seat 1
51 591688 80 Air distribution, CIP 1 See page 84
52 590539 01 Clip list 1
53 27497 Plug 1 ISO-R 1, square
54 569038 05 Hose, 32 1
55 591675 01 Hose, 32 1
56 599223 02 Hose clamp 32-44 1
57 599223 03 Hose clamp 38-50 10
59 592649 01 Nipple 1
60 592665 01 Hose, 25 1
66 Book No.
12 CIP module
2364
Book No. 67
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
68 Book No.
12 CIP module
2364
Book No. 69
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
70 Book No.
12.1 Fresh water piping 12 CIP module
2365
Book No. 71
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
72 Book No.
12.1 Fresh water piping 12 CIP module
2366
Book No. 73
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
12.1.2 Valve
Machine unit number or
Subassembly description
576953-
Ref Part No Description -82 Notes
Quantity
1 576438 06 Valve, DN32 1
2 576075 22 Air actuator, SR201 1
Z 576075 61 Actuator spare part kit, DA/SR 201 -1 See page 98
74 Book No.
12.1 Fresh water piping 12 CIP module
2367
Book No. 75
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
12.2 Pipe #5
Machine unit number or
Subassembly description
590252-
Ref Part No Description -80 Notes
Quantity
5 591659 01 Check valve, DN 25 1
7 588996 80 2
76 Book No.
12.2 Pipe #5 12 CIP module
2368
Book No. 77
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
12.3 Pipe #6
Machine unit number or
Subassembly description
590258-
Ref Part No Description -80 Notes
Quantity
6 588996 80 1
78 Book No.
12.3 Pipe #6 12 CIP module
2369
Book No. 79
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
12.4 Pump
Machine unit number or
Subassembly description
586773-
Ref Part No Description -80 Notes
Quantity
1 586773 01 Pump 1
Z 586773 02 Spare part set -1 Diaphragm, O-ring set (in/outlet), Valve
ball, Muffler, O-ring (valve seat)
Z0.1 586773 03 Diaphragm -1 Contains: O-ring set (in/outlet), Valve
ball, Muffler, O-ring (valve seat)
80 Book No.
12.4 Pump 12 CIP module
2370
Book No. 81
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
82 Book No.
12.5 Valve block 12 CIP module
2316
Book No. 83
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
84 Book No.
12.6 Air distribution, CIP 12 CIP module
2375
Book No. 85
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
13 CIP liquid, 15 L
Machine unit number or
Subassembly description
596250-
Ref Part No Description -01 Notes
Quantity
A 596250 01 CIP liquid, 15 L 1
86 Book No.
13 CIP liquid, 15 L
2377
Book No. 87
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
14 Ancillary equipment
Machine unit number or
Subassembly description
589744-
Ref Part No Description -60 Notes
Quantity
1 589745 80 Sampling device 1 See page 90
2 589745 81 Sampling device 1 See page 90
3 590436 80 Pressure transmitter set 1 See page 92
4 590437 80 Pressure gauge set 1 See page 94
5 594536 80 Valve V403-35 1 DN50 PN10
See page 96
88 Book No.
14 Ancillary equipment
2377
Book No. 89
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
90 Book No.
14.1 Sampling device 14 Ancillary equipment
2371
Book No. 91
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
92 Book No.
14.2 Pressure transmitter set 14 Ancillary equipment
2372
Book No. 93
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
94 Book No.
14.3 Pressure gauge set 14 Ancillary equipment
2373
Book No. 95
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
96 Book No.
14.4 Valve V403-35 14 Ancillary equipment
2374
Book No. 97
PureBallast 2.0 Flow 750 DIN 300 CV250 RCP
98 Book No.
15 Actuator spare part kit, DA/SR 301
2443
Book No. 99
16 Cross reference list
+ Part No. Page Ref. Part No. Page Ref. Part No. Page Ref.
Part No. Page Ref. Part No. Page Ref. Part No. Page Ref.
Part No. Page Ref. Part No. Page Ref. Part No. Page Ref.
Part No. Page Ref. Part No. Page Ref. Part No. Page Ref.
597264 32 51 93 597547 29 51 98
597264 33 51 94 597547 31 51 103
597264 38 50 14 597547 32 51 104
597264 61 50 68 597547 33 51 105
597264 66 50 69 597547 34 51 108
597298 83 51 Z 597547 38 50 39
597330 01 6 Z 597547 39 50 51
597331 01 6 Z0.1 597547 55 51 102
597361 01 20 39AA 599223 01 67 61
597361 01 20 39BA 599223 02 66 56
597361 01 20 39CA 599223 03 66 57
597361 01 20 39DA 66169 18 21
597361 01 20 39EA 70490 90 6
597361 01 20 39FA 70560 16 22
597361 01 21 39GA 70560 16 57
597361 01 21 39HA 70560 20 6
597428 02 20 39AB 70560 20 20
597428 02 20 39BB 70560 21 43
597428 02 20 39CB 70560 66 6
597428 02 20 39DB 70560 66 19
597428 02 20 39EB 70560 66 36
597428 02 20 39FB 70560 66 46
597428 02 21 39GB 70560 67 63
597428 02 21 39HB 70560 67 72
597547 01 50 18 70560 8 27
597547 02 50 19 70560 8 38
597547 03 50 35 956264 17 16 44
597547 04 50 36
597547 05 50 38
597547 07 50 40
597547 08 50 41
597547 09 50 42
597547 10 50 43
597547 12 50 45
597547 13 50 46
597547 14 50 47
597547 15 50 44
597547 15 50 49
597547 15 50 72
597547 16 50 50
597547 18 50 53
597547 19 50 54
597547 20 50 57
597547 21 50 71
597547 23 50 76
597547 24 51 77
597547 25 51 84
597547 26 51 95
597547 27 51 96
597547 28 51 97