Positive-Sequence Modeling of Droop-Controlled Grid-Forming Inverters For Transient Stability Simulation of Transmission Systems
Positive-Sequence Modeling of Droop-Controlled Grid-Forming Inverters For Transient Stability Simulation of Transmission Systems
This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2024.3376245
Authorized licensed use limited to: Jorge Vega. Downloaded on April 14,2024 at 15:40:28 UTC from IEEE Xplore. Restrictions apply.
© 2024 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2024.3376245
dynamic behaviors of transmission systems due to the scale models, and at the same time also achieves a high
of practical systems. Therefore, it is important to develop the computational efficiency, making it suitable for large-scale
positive-sequence model of grid-forming inverters and transmission system simulation studies. Most parts of the
investigate how accurately the model can reflect the dynamic model described in the paper have been included in a generic
behaviors of grid-forming inverters in the time frame of library positive-sequence grid-forming inverter model,
interest. The work in [20] proposed to use the Thevenin REGFM_A1 [27], which was recently adopted by the US
voltage source instead of an ideal current source to represent Western Electricity Coordinating Council (WECC) and
grid-following inverters in the positive-sequence simulation included in the model libraries of major commercial positive-
tool, which improved the convergence of the network sequence simulation tools, including PTI-PSS®E [28], GE-
solution. Reference [21] performed a comprehensive PSLF [29], PowerWorld Simulator [30], and TSAT [31],
comparative study of the EMT and positive-sequence models marking the first publicly available grid-forming inverter
of grid-following inverters and provided simulation model that is included in all major commercial transient
guidelines of grid-following inverters for grid-integration stability simulation tools used in North America.
studies. The work in [6] developed three-phase phasor The rest of the paper is organized as follows. Section II
models of grid-forming and grid-following inverters to study introduces the basic concept of grid-forming inverters.
the dynamic behaviors of large-scale distribution systems, Section III presents detailed EMT models of two widely
but the fault response of grid-forming inverters was not reported grid-forming droop controls. Section IV introduces
modeled. References [22] and [23] developed positive- the developed positive-sequence model and the interface to
sequence models of grid-forming inverters with and without the network solver. Section V and VI present the comparison
considering the dynamics of the dc bus respectively, but the between the positive-sequence model and the two detailed
comparison with detailed EMT models was not presented. EMT models in a single-GFM infinite-bus system and a
Reference [24] modeled the virtual impedance control of a modified IEEE 39-bus system, respectively. Section VII
grid-forming inverter in the phasor domain. Reference [25] presents the case study on the U.S. Western Interconnection
developed reduced-order models for grid-forming and grid- system, and Section VIII draws the conclusion of this paper.
following inverters to study the small signal stability and
compared the results with the full-order models. The work in II. GRID-FORMING CONCEPT
[26] developed positive-sequence and negative-sequence Unlike a grid-following inverter, which approximately
models of grid-forming inverters that were mainly used for behaves as a controllable current source, a grid-forming
the power system protection scheme design instead of inverter operates as a controllable voltage source behind
dynamic simulation. Literature review revealed that impedance during normal operations, as shown in Fig. 1.
significant work in the domain of positive-sequence
modeling of grid-forming inverters for transmission system E δE Vg δg
XL
transient stability simulation studies is needed. E
It is worth mentioning that although numerous recent ω
studies reported detailed EMT simulations [14-16, 19] to Grid
P,Q
examine the system transient stability, the analytical Fig. 1 Basic model of a grid-forming inverter
approaches reported in those studies were still based on the
phasor assumption, which ignored the dynamics of the If the coupling reactance XL is well designed, for example
inverter fast inner control loops and the dynamics of the between 0.05 pu and 0.2 pu on an inverter rating base, the
network. This indicates that it might be feasible to use the inverter output active power P is approximately linear with the
positive-sequence models to accurately simulate the transient phase angle δP, and the inverter output reactive power Q is
stability of power systems dominated by grid-forming approximately linear with the inverter internal voltage
inverters. magnitude E, according to (1)–(3). This decoupling
This paper describes a positive-sequence model to characteristic simplifies the controller design.
represent two widely reported droop-controlled grid-forming p = E - g (1)
inverters for the transmission system transient stability
EVg EVg
simulation studies. Methods of how to develop the P= sin p p (2)
equivalent voltage source behind impedance to represent XL XL
inverters with and without inner control loops, modeling of E 2 − EVg cos p E ( E − Vg )
P-f and Q-V droop controls, active and reactive power Q= (3)
XL XL
limiting modeling, and modeling of fault current limiting
controls are described in detail. The positive-sequence model
III. EMT MODELS OF TWO WIDELY USED DROOP CONTROLS
was validated against detailed EMT models in both a single-
GFM infinite-bus system and a modified IEEE 39-bus Droop control is one of the most popular approaches to
system. Finally, the model was tested on the U.S. Western realize the parallel operation of multiple grid-forming
Interconnection system. Study results showed that the model inverters [32]. A grid-forming inverter does not require the use
has a good level of accuracy compared to the detailed EMT of a phase-locked loop (PLL) in comparison to its counterpart,
Authorized licensed use limited to: Jorge Vega. Downloaded on April 14,2024 at 15:40:28 UTC from IEEE Xplore. Restrictions apply.
© 2024 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2024.3376245
einv il L1 vo L2 io vt einv il L1 vo io L2 vt
PWM
Comm.3-4 C
C
Comm.3-4
abc θo
dq
(a) (b)
E δE Vo δo
XL1 XL2 XL2
E Vo
ω ω
(c) (d)
Fig. 2 Dierct and multi-loop droop GFM controls. (a) Direct droop control. (b) Multi-loop droop control. (c) Equivalent circuit of the direct droop control in
the fundamental frequency. (d) Equivalent circuit of the multi-loop droop control in the fundamental frequency.
the grid-following inverter. This section introduces the variables and parameters are listed in Table I in this section,
detailed EMT models of two widely reported grid-forming and Table II in Section V, respectively.
droop controls. A detailed description of the EMT models in
1 1
this section makes it more convenient for readers to Pf = P, Q f = Q (4)
1 + Ts 1 + Ts
understand how the positive-sequence model is developed in
Section IV by making appropriate assumptions. In addition, as
TABLE I
shown in Fig. 2 (a) and (b), this paper assumes the DC bus Electrical and control variables of grid-forming inverters
voltage is constant and ignores the dynamics at the DC side. Common electrical and control variables of direct and multi-
loop droop controls
A. Two Widely Used Grid-Forming Droop Controls Symbol Description
L1 Inverter bridge side filter inductance
Historically, two types of grid-forming droop controls are C Inverter filter capacitor
widely reported in the literature [33], which are defined as the L2 Inverter grid side filter inductance
direct droop control and the multi-loop droop control in this XL1 Inverter bridge side filter reactance
XL2 Inverter grid side filter reactance
paper, as shown in Fig. 2 (a) and (b), respectively. As shown einv Inverter bridge side voltage
in Fig. 2 (a), the direct droop control directly regulates the vo Filter capacitor voltage
angular frequency ω and magnitude E of the modulation vt Inverter terminal voltage
il Inverter output current at the bridge side
waveform according to the P-f droop control and Q-V droop io Inverter output current at the grid side
control, respectively, where Pf and Qf are the active power and Pf Active power filtered by a first-order low-pass filter
reactive power filtered by a first-order low-pass filter as Qf Reactive power filtered by a first-order low-pass filter
shown in (4). In contrast, for the multi-loop droop control, Δω Output from the active power limiting
ΔV Output from the reactive power limiting
there are additional cascaded inner voltage and current loops Electrical and control variables for the direct droop control
other than the P-f and Q-V droop controls, as shown in Fig. 2 Symbol Description
(b). The purpose of the cascaded inner voltage and current E Magnitude of the modulation waveform
θ Rotating phase angle of the modulation waveform
loops is to achieve fast control of the waveform of the filter
Electrical and control variables for the multi-loop droop control
capacitor voltage vo. To achieve the fast control of vo, the Symbol Description
bandwidths of the inner voltage and current loops are typically ed, eq dq frame components of the modulation waveform
designed to be very high. For example, the bandwidths of the θo Rotating phase angle of the filter capacitor voltage
v*od, v*oq Input references of the voltage loop
voltage and current loops used in [34] are 400 Hz and 1.6 kHz, i*ld, i*lq Current references before the current limiting block
respectively. With the waveform of vo well controlled by the i*lds, i*lqs Current references after the current limiting block
inner voltage and current loops, the P-f and Q-V droop vod, voq dq frame components of the filter capacitor voltage
ild, ilq dq frame components of the inverter bridge side current
controls then regulate the angular frequency and magnitude of ild, ilq dq frame components of the inverter grid side current
vo in a relatively slow manner. The explanations of all the
Authorized licensed use limited to: Jorge Vega. Downloaded on April 14,2024 at 15:40:28 UTC from IEEE Xplore. Restrictions apply.
© 2024 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2024.3376245
Fig. 2 (c) and (d) show the equivalent circuits of the two insulated-gate bipolar transistors (IGBTs), the overcurrent
controls in the fundamental frequency. For the direct droop needs to be limited rapidly, typically within 1 ms as reported
control, because it directly regulates the magnitude and by the inverter manufacturer [36]. This subsection introduces
angular frequency of the modulation waveform, the equivalent two current limiting controls that are typically used by the
circuit can be represented by a voltage source behind direct droop and multi-loop droop controls.
impedances XL1 and XL2, as shown in Fig. 2 (c). The pulse For the direct droop control, since it does not have an inner
width modulation (PWM) control can be ignored in the current loop, the current limiting is implemented at the PWM
fundamental frequency. In addition, the filter capacitor C can control layer. The typical approach is to block the associated
be ignored because of its negligible value in the fundamental IGBTs once detecting the overcurrent, and then release the
frequency. For the multi-loop droop control, because it blocking signal once the current drops below the threshold Imax
regulates the magnitude and angular frequency of the filter using a hysteresis loop. Fig. 4 shows the current limiting
capacitor voltage vo, the equivalent circuit in the fundamental control block for phase A. Once the output current ila exceeds
frequency can be represented by a voltage source behind Imax, the hysteresis loop sends the blocking signal blka to IGBT
impedance XL2. The cascaded inner voltage and current loops, 1 and IGBT 4 of the phase A bridge, where g1 and g4 are the
the inverter side inductor L1 and filter capacitor C, and the original gate signals generated by the PWM control, and g’1
PWM control can be ignored in the fundamental frequency. and g’4 are the new gate signals modulated by the blocking
The work in [33] pointed out the above difference between the signal blka. The currents on phase B and C can be limited in
two controls and compared their small signal performances the same manner. This approach was briefly mentioned in
using detailed EMT models. [36], and explained in detail in [37]. The advantage of this
approach is that it can limit the overcurrent very quickly, for
B. Active and Reactive Power Limiting
example within 1–2 PWM cycles. However, this approach
When connecting a GFM to the bulk power system, power results in a flat-topped current waveform during faults, which
limiting controls are needed to prevent the output P and Q is shown in Section V.
from exceeding the limits under disturbances like loss of
generation units and the step change in voltage. Fig. 3 shows + blka
Imax g'1
the active and reactive power limiting control blocks. - g1
|ila|
0 0 g'4
Pmax Qmax g4
kpP kpQ
+- + +- +
0 + ωLLim 0 + VLLim
kiP/s kiQ/s Fig. 4 The current limiting used by the direct droop control.
Pf ωLLim + Δω Qf VLLim + ΔV
ωHLim + VHLim +
For the multi-loop droop control, since it has an inner
kiP/s kiQ/s current loop, the overcurrent can be limited by saturating the
0 ωHLim 0 VHLim current references. Fig. 5 shows the cascaded inner voltage
Pmin+- ++ Qmin+- ++
kpP kpQ and current loops together with the current limiting block.
0 0
(a) (b) * einvd
v*od + + + i ld i*lds + +
kpv+kiv/s kpi+kii/s
Fig. 3 Power Limiting. (a) Active power limiting. (b) Reactive power limiting. - + + - +
vod -ωC1 F -ωL1
ild
As shown in Fig. 3 (a), when Pf exceeds Pmax or drops iod Current
below Pmin, the anti-windup proportional-integral (PI) ioq Limiting
voq ωC1 ilq ωL1
controller is activated to limit Pf by changing the inverter F
- + + i*lq * - + einvq
v*oq + i lqs+
output angular frequency ω. This control was proposed by the kpv+kiv/s + + kpi+kii/s +
Consortium for Electric Reliability Technology Solutions
Fig. 5 Inner voltage and current loops of the multi-loop droop control.
(CERTS) Microgrid project and tested in the field [2, 11].
Similarly, as shown in Fig. 3 (b), once Qf exceeds Qmax or The current limiting algorithm used in this paper is shown
drops below Qmin, the reactive power limiting is activated to in (5). If the magnitude of the current reference exceeds Imax,
limit Qf by changing the inverter output voltage [35]. The both current references i*lds and i*lqs are reduced proportionally
active power and reactive power limiting controls can be according to (5). This assures that the magnitude of the current
added either on the direct droop control or on the multi-loop is limited at Imax during the fault. Such method is called
droop control. circular current limiting control according to [38]. It should be
noted that when using this approach, the saturation limits of
C. Current Limiting during Faults
the voltage loop need to be carefully designed to avoid windup
Because a GFM approximately behaves as a voltage source when the output current is saturated [10].
behind impedance during normal operations, during a severe
short-circuit fault it can generate high currents with the i* = i* , i* = i* if i* 2 + i* 2 I
possibility of damaging the inverter hardware. Therefore, lds ld lqs lq ld lq max
* * *
current limiting controls are needed to prevent GFMs from ild I max ilq I max (5)
ilds = * 2 * 2 , ilqs = * 2 * 2 if ild + ilq I max
* *2 *2
overcurrent during faults. Considering the characteristic of ild + ilq ild + ilq
Authorized licensed use limited to: Jorge Vega. Downloaded on April 14,2024 at 15:40:28 UTC from IEEE Xplore. Restrictions apply.
© 2024 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2024.3376245
Compared to the current limiting method used by the direct reactance XL2, as expressed in (6) and (7). The filter capacitor
droop control, this approach does not result in the distortion of C can be ignored because its value in the fundamental
current waveforms under balanced faults. However, its frequency is typically very small.
response speed is constrained by the bandwidth of the current
EGFM GFM = E E (6)
loop, so it is not as fast as the approach shown in Fig. 4. In
addition, this approach also results in distorted current X L = X L1 + X L 2 (7)
waveforms under unbalanced faults.
When representing the multi-loop droop control, the
It is important to note that although the two current limiting
voltage phasor EGFMδGFM refers to the filter capacitor voltage
controls described earlier can effectively limit the overcurrent
Voδo, and XL refers to the inverter grid side filter reactance
during faults, they only work for short-term faults that are
XL2 only, as expressed in (8) and (9). The cascaded inner
quickly cleared by the power system protection devices (e.g., a
voltage and current loops together with the inverter bridge side
0.1 s fault). If the fault lasts too long, these two methods can inductor L1 and filter capacitor C are ignored in the phasor
result in the loss of synchronism to the grid after the fault, as domain. As explained in Section III A, the bandwidths of the
reported in [14, 16]. inner voltage and current loops are at least in the order of a
few hundred Hz, so it is reasonable to assume those inner
IV. POSITIVE-SEQUENCE MODELING loops track ideally in the positive-sequence tool and ignore
After describing detailed EMT models of the two types of their dynamics.
GFM droop controls, this section introduces how to develop EGFM GFM = Vo o (8)
the equivalent positive-sequence model to represent them in
X L = X L2 (9)
the phasor domain. The positive-sequence modeling is based
on the phasor assumption and ignores the network dynamics. B. Droop Control and Power Limiting Modeling
In addition, the positive-sequence simulation typically runs at
In the positive sequence tool, the low-pass filter, P-f and Q-
a time step of a quarter of a cycle (e.g., 4.1667 ms for a 60 Hz
V droop control, and active and reactive power limiting of
power system), which is much larger than the time step used
GFMs can be modeled as the same as modeled in the EMT
by EMT simulations. Therefore, appropriate simplifications
simulation tool. This is because the bandwidths of those
must be made to model GFMs in the positive-sequence tool.
control loops are relatively low, so that they can be modeled in
A. Voltage Phasor behind Impedance Representation the phasor domain without causing numerical stability issues.
According to the explanation in Section III A, a GFM can Fig. 7 shows the overall control scheme. Detailed control
be represented by a voltage phasor EGFM∠δGFM behind blocks were shown in Fig. 2 and Fig. 3, and explained in
impedance XL in the positive-sequence tool, as shown in Fig. 6 Section III. In Fig. 7 (a) and (b), δdroop and Edroop are the static
(a), and the GFM controller changes the voltage magnitude phase angle and voltage magnitude obtained from the control
and phase angle of the voltage phasor. The dynamic of filter blocks. Note that in the positive-sequence tool, the static phase
inductance is ignored and is represented by an algebraic term angle δdroop should be used by the network solver instead of
“jXL” instead of a differential term. This is significantly the rotating phase angle θ. By comparing Fig. 7 (a) and Fig. 2
different from how a traditional grid-following inverter is (b), it can be seen that θ=δdroop+ω0t. Assuming the GFM
modeled in positive-sequence tools. As a grid-following output frequency is 60 Hz, then δdroop is a fixed value while θ
inverter is typically modeled as a controllable current phasor, changes from 0 to 2 periodically.
and the controller changes the active and reactive current Pset
references [39]. ω 0 δdroop
P-f Droop ++ +-
Pf s
P Low-Pass ω0pu
XL V t δt V t δt Filter
Active Power Δω
Limiting
P, Q, I φ P, Q, I φ
Pmax Pmin
EGFM δGFM IN φ N YL (a)
Vset
Edroop
Q-V Droop ++
(a) (b) Q Low-Pass Qf
Filter
Fig. 6 GFM representation. (a) Voltage phasor behind impedance Reactive Power ΔV
representation. (b) Norton equivalent circuit. Limiting
Authorized licensed use limited to: Jorge Vega. Downloaded on April 14,2024 at 15:40:28 UTC from IEEE Xplore. Restrictions apply.
© 2024 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2024.3376245
limiting method described in Section III C can be directly model. Equation (12) and (13) are used as a criterion to
modeled in the positive-sequence tool because of their high determine if the GFM will go into the current limiting or not.
bandwidths. Therefore, an equivalent modeling method must At each simulation time step, the GFM output current phasor
be developed to accurately represent their control effect and at Iφ is calculated using (12). If the current magnitude I is
the same time allows a larger simulation time step for the smaller than Imax, then the GFM will not go into the current
positive-sequence simulation. Since the current limiting limiting mode, and EGFM and δGFM are governed by the P-f and
control typically responds very fast, it is reasonable ignore its Q-V droop controls, as shown in (13-a). Once I exceed Imax
dynamics and model it algebraically in the positive-sequence caused by a fault, for example Vt drops to 0 pu, the GFM will
tool. The work in [38] pointed out that the circular current go into the current limiting mode and the voltage phasor
limiting control used by the multi-loop droop-controlled EGFMδGFM is calculated using (13-b). In the current limiting
GFMs as described in (5) is equivalent to a virtual resistor. mode, the GFM output current phasor ImaxφLim is dependent
Similarly, simulation studies show that the control effect of on the virtual resistor Re, as shown in Fig. 9. Equation (13-b)
PWM blocking method used by the direct-droop-controlled assures that the magnitude of the GFM output current is
GFMs as described in Fig. 4 is also like a virtual resistor. limited at Imax in the current limiting mode.
Therefore, those two current limiting controls described in
Section III C can be equivalently modeled as a virtual resistor Edroop droop − Vt t
Re in the positive-sequence tool, as shown in Fig. 8. I = (12)
jX L
Eq. (14)-(15)
Edroop δdroop, Vt δt
Norton Equivalent
Edroop droop − Vt t Circuit (Fig. 6(b))
I =
jX L IN φ N , Y L
Network Solver
No
I>I max ? EGFM GFM =Edroop droop
No
Yes Converged ?
Yes
E 2 droop + V 2t − 2 EdroopVt cos( droop − t )
Re = 2
− X L2
I max Fig. 10 Flow chart describing the interaction between the grid-forming
inverter model and the network solver.
Authorized licensed use limited to: Jorge Vega. Downloaded on April 14,2024 at 15:40:28 UTC from IEEE Xplore. Restrictions apply.
© 2024 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2024.3376245
equivalent circuit, as shown in Fig. 6 (b), using (14) and (15). TABLE III
The values of L1, L2, and equivalent XL
Once the current phasor INφN and admittance YL are
Equivalent XL in the
obtained, they are sent to the network solver to solve the Control Mode L1 L2
positive-sequence model
network algebraic equations for the next simulation time step. Direct droop 0.08 pu 0.07 pu 0.15 pu
Multi-loop droop 0.05 pu 0.15 pu 0.15 pu
EGFM GFM
I N N = (14)
jX L Table II shows the controller parameters of the direct droop
1 control and the multi-loop droop control. The parameters of
YL = (15) the low-pass filter, P-f and Q-V droop, and power limiting are
XL
the same for both GFM controls. The line impedance is Rg +
jXg = 0.02 + j0.15 pu. According to Fig. 2 (c) and (d), if the
V. COMPARISON IN A SINGLE-GFM INFINITE-BUS SYSTEM
values of L1 and L2 remain the same when using two GFM
To investigate how accurately the developed positive- droop controls, they will have different values of XL in the
sequence model can represent the two GFM droop controls, a fundamental frequency, resulting in different simulation
rigorous comparison between EMT and positive-sequence results. Therefore, to achieve a reasonable comparison, the
simulations was performed on a single-GFM infinite bus values of L1 and L2 were designed to assure that the two GFM
system as shown in Fig. 11. The EMT models of the two GFM controls have the same value of XL in the fundamental
controls were developed in the PSCAD simulation tool [40]. frequency, as listed in Table III. The filter capacitor C was
The IGBT-based model was used to represent the inverter in designed to have a cutoff frequency of 600 Hz. With the
PSCAD, and the PWM switching frequency was set at 10 values of XL and other major parameters remaining the same,
kHz. The positive-sequence model was developed in the it is expected that the direct droop control and the multi-loop
commercially available positive-sequence simulation tool droop control will have similar dynamic performances.
PSS/E. The time step for the PSCAD simulation was 5 μs, and
the time step for the PSS/E simulation was 4.167 ms. A. Step Change in Voltage Magnitude
In this scenario, the magnitude of grid voltage Vg dropped
vt vg to 0.8 pu at 1.2 s, resulting in the GFM terminal voltage Vt to
il L1 vo L2 io Rg Lg
drop to 0.86 pu.
C
Authorized licensed use limited to: Jorge Vega. Downloaded on April 14,2024 at 15:40:28 UTC from IEEE Xplore. Restrictions apply.
© 2024 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2024.3376245
Authorized licensed use limited to: Jorge Vega. Downloaded on April 14,2024 at 15:40:28 UTC from IEEE Xplore. Restrictions apply.
© 2024 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2024.3376245
(a) (b)
Fig. 17 GFM output current and phase angle during the delayed clearing fault.
(a) EMT simulations of two GFM controls. (b) Positive-sequence simulation.
7 31 20
36
8 10 34 33 (a) (b)
9 32
GFM32 GFM34 Fig. 19 Comparision of EMT and positive-sequence simulation results for the
modified IEEE 39-Bus System. (a) Responses of GFM 34. (b) Responses of
Fig. 18 The modified IEEE 39-bus system with 5 GFMs. GFM 30.
Authorized licensed use limited to: Jorge Vega. Downloaded on April 14,2024 at 15:40:28 UTC from IEEE Xplore. Restrictions apply.
© 2024 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2024.3376245
10
The EMT and positive-sequence simulations for each GFM The system model includes 22,000+ buses, 5,000+
and synchronous machine were compared, and all synchronous machines, and 1,000+ grid-following inverters.
comparisons achieved the same level of alignment as shown in The 2021 Heavy Summer case was selected, and the total load
Fig. 19. was around 150,000 MW. Because of its size, it would be
extremely difficult to conduct an EMT simulation for such a
B. Computational Time Summary
large system. Therefore, only positive-sequence simulations
Table IV summarizes the computational times. The were performed. A Pacific DC Intertie (PDCI) bi-pole outage
simulation runtime was 20 s. Because five IGBT-based GFM was selected as the contingency to examine the system
models were used and simulated at a time step of 5 μs, it took transient stability. Two cases were simulated. The first case
18,634 s to complete the EMT simulation. In contrast, it only simulated the original system, where synchronous machines
took 0.2 s to complete the positive-sequence simulation, which dominated the grid. For the second case, all the synchronous
shows the advantage of using positive-sequence simulations to machines were replaced by GFMs, creating a 100% inverter
study the transient stability of transmission systems. Note that case with high penetrations of GFMs. Simulations were
this paper aims to achieve a very rigorous comparison between performed in PSS/E with a time step of 4.167 ms, and the
EMT and positive-sequence simulations so that the IGBT- simulation runtime was 35 s. 25 generation units across the
based EMT models were used. The computational time of system were monitored. It took around 12.3 minutes to
EMT simulations is expected to be significantly reduced by complete Case 1, and around 18.3 minutes to complete Case 2.
using simplified models such as switching function models. Fig. 20 (a) and (b) present the simulation results of the 25
However, such studies are out of the scope of this paper. generations units for the two cases. By comparing these
TABLE IV results, it becomes evident that replacing all synchronous
Computational time (Simulation runtime: 20 s) machines with GFMs significantly improves the system
EMT simulation (IGBT-based model) Positive-sequence simulation damping. This case study shows that a) the developed
18,634 s 0.2 s
positive-sequence GFM model is numerically stable in a
practical bulk power system environment, and b) the high
VII. STUDY IN THE WESTERN INTERCONNECTION SYSTEM
penetration of GFMs can significantly enhance the system
With rigorous model validations performed in Section V damping compared to traditional synchronous machine-
and VI, the positive-sequence GFM model was finally studied dominated systems. Future work will explore additional
in the U.S. Western Interconnection system in this section. scenarios with varying levels of GFM penetration based on the
developed the GFM model.
VIII. CONCLUSIONS
As GFMs are being rapidly connected to the power grids
around the world, it is important to understand how GFMs
should be modeled in conventional positive-sequence
simulation tools for studying their impacts on the transient
stability of large-scale transmission systems. This paper
describes a positive-sequence model to represent to two
widely reported droop-controlled GFMs. Methods of how to
develop the equivalent voltage source behind impedance to
represent inverters with and without inner control loops,
modeling of P-f and Q-V droop controls, active and reactive
power limiting modeling, and modeling of fault current
limiting controls have been described in detail. The positive-
sequence model was compared against detailed EMT models
in both a single-GFM infinite-bus system and a modified
IEEE 39-bus system. Finally, the model has been tested on
the U.S. Western Interconnection system. The study results
show that the model has a good level of accuracy compared
to the detailed EMT models, and at the same time also
achieves a high computational efficiency, making it suitable
for large-scale transmission system simulation studies. Most
parts of the model described in the paper have been included
in a generic library positive-sequence grid-forming inverter
model, REGFM_A1, which was recently adopted by the US
(a) (b)
WECC and included in the model libraries of major
Fig. 20 Simulation results of the Western Interconnection system. (a) Case 1: commercial positive-sequence simulation tools, including PTI-
The original case. (b) Case 2: All synchronous machines repalced by GFMs.
PSS®E, GE-PSLF, PowerWorld Simulator, and TSAT,
Authorized licensed use limited to: Jorge Vega. Downloaded on April 14,2024 at 15:40:28 UTC from IEEE Xplore. Restrictions apply.
© 2024 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2024.3376245
11
marking the first publicly available grid-forming inverter Large Scale Grid Simulations," IEEE Transactions on Power Systems,
vol. 32, no. 1, pp. 765-773, 2017.
model that is included in all major commercial transient [21] V. A. Lacerda, E. P. Araujo, M. Cheah-Mañe, and O. Gomis-Bellmunt,
stability simulation tools used in North America. "Phasor Modeling Approaches and Simulation Guidelines of Voltage-
Source Converters in Grid-Integration Studies," IEEE Access, vol. 10, pp.
51826-51838, 2022.
IX. REFERENCES
[22] W. Du, Y. Liu, R. Huang, F. K. Tuffner, J. Xie, and Z. Huang, "Positive-
[1] R. Lasseter, Z. Chen, and D. Pattabiraman, "Grid-Forming Inverters: A Sequence Phasor Modeling of Droop-Controlled, Grid-Forming Inverters
Critical Asset for the Power Grid," IEEE Journal of Emerging and with Fault Current Limiting Function," in 2022 IEEE Power & Energy
Selected Topics in Power Electronics, pp. 1-1, 2019. Society Innovative Smart Grid Technologies Conference (ISGT), 2022,
[2] R. H. Lasseter et al., "CERTS Microgrid Laboratory Test Bed," IEEE pp. 1-5.
Transactions on Power Delivery, vol. 26, no. 1, pp. 325-332, 2011. [23] S. Roy and H. N. V. Pico, "Transient Stability and Active Protection of
[3] J. Matevosyan et al., "Grid-forming inverters: Are they the key for high Power Systems with Grid-Forming PV Power Plants," IEEE Transactions
renewable penetration?," IEEE Power and Energy Magazine, vol. 17, no. on Power Systems, pp. 1-1, 2022.
6, pp. 89-98, 2019. [24] D. Pattabiraman, R. H. Lasseter, and T. M. Jahns, "Transient Stability
[4] M. E. Elkhatib, W. Du, and R. H. Lasseter, "Evaluation of Inverter-based Modeling of Droop-Controlled Grid-Forming Inverters with Fault Current
Grid Frequency Support using Frequency-Watt and Grid-Forming PV Limiting," in 2020 IEEE Power & Energy Society General Meeting
Inverters," in 2018 IEEE Power & Energy Society General Meeting (PESGM), 2-6 Aug. 2020 2020, pp. 1-5, doi:
(PESGM), 2018, pp. 1-5. 10.1109/PESGM41954.2020.9281712.
[5] A. Crivellaro et al., "Beyond low-inertia systems: Massive integration of [25] Y. Gu, N. Bottrell, and T. C. Green, "Reduced-Order Models for
grid-forming power converters in transmission grids," in 2020 IEEE Representing Converters in Power System Studies," IEEE Transactions
Power & Energy Society General Meeting (PESGM), 2020, pp. 1-5. on Power Electronics, vol. 33, no. 4, pp. 3644-3654, 2018.
[6] W. Du et al., "Modeling of Grid-Forming and Grid-Following Inverters [26] B. Mahamedi and J. E. Fletcher, "The Equivalent Models of Grid-
for Dynamic Simulation of Large-Scale Distribution Systems," IEEE Forming Inverters in the Sequence Domain for the Steady-State Analysis
Transactions on Power Delivery, 2020. of Power Systems," IEEE Transactions on Power Systems, vol. 35, no. 4,
[7] P. F. Mayer, M. Gordon, W. C. Huang, and C. Hardt, "Improving grid pp. 2876-2887, 2020.
strength in a wide ‐ area transmission system with grid forming [27] W. Du, "Model Specification of Droop-Controlled, Grid-Forming
inverters," IET Generation, Transmission & Distribution, 2022. Inverters (REGFM_A1)," Pacific Northwest National Laboratory,
[8] D. Pattabiraman, R. H. Lasseter, and T. M. Jahns, "Comparison of Grid Richland, WA, United States, No. PNNL-35110, 2023.
Following and Grid Forming Control for a High Inverter Penetration [28] Siemens, PSS/E Software, 2022 [Online] Available:
Power System," in 2018 IEEE Power & Energy Society General Meeting https://new.siemens.com/global/en/products/energy/energy-automation-
(PESGM), 2018, pp. 1-5. and-smart-grid/pss-software/pss-e.html
[9] P. Brogan, T. Knueppel, D. Elliott, and N. Goldenbaum, "Experience of [29] GE Energy Consulting, PSLF Software, 2022 [Online] Available:
grid forming power converter control," in 17th Wind Integration https://www.geenergyconsulting.com/practice-area/software-products/pslf
Workshop, Stockholm, Sweden, 2018. [30] PowerWorld Corporation, PowerWorld Software, 2022 [Online]
[10] H. N. V. Pico and V. Gevorgian, "Blackstart Capability and Survivability Available: https://www.powerworld.com/
of Wind Turbines With Fully Rated Converters," IEEE Transactions on [31] Powertech Labs Inc, TSAT Software, 2022 [Online] Available:
Energy Conversion, vol. 37, no. 4, pp. 2482-2497, 2022. https://www.dsatools.com/tsat/
[11] W. Du, R. H. Lasseter, and A. S. Khalsa, "Survivability of Autonomous [32] M. C. Chandorkar, D. M. Divan, and R. Adapa, "Control of parallel
Microgrid During Overload Events," IEEE Transactions on Smart Grid, connected inverters in stand-alone AC supply systems," in 1991 IEEE
vol. 10, no. 4, pp. 3515-3524, 2019. Industry Applications Society Annual Meeting, 1991, pp. 1003-1009
[12] O. Schomann, "Experiences with large grid-forming inverters on various vol.1.
island and microgrid projects," in Hybrid Power Systems Workshop, [33] W. Du et al., "A Comparative Study of Two Widely Used Grid-Forming
2019. Droop Controls on Microgrid Small-Signal Stability," IEEE Journal of
[13] A. Roscoe et al., "Practical experience of providing enhanced grid Emerging and Selected Topics in Power Electronics, vol. 8, no. 2, pp.
forming services from an onshore wind park," in Proc. 19th Wind 963-975, 2019.
Integration Workshop, 2020, pp. 1-4. [34] N. Pogaku, M. Prodanovic, and T. C. Green, "Modeling, Analysis and
[14] L. Huang, H. Xin, Z. Wang, L. Zhang, K. Wu, and J. Hu, "Transient Testing of Autonomous Operation of an Inverter-Based Microgrid," IEEE
Stability Analysis and Control Design of Droop-Controlled Voltage Transactions on Power Electronics, vol. 22, no. 2, pp. 613-625, 2007.
Source Converters Considering Current Limitation," IEEE Transactions [35] A. Knobloch et al., "Synchronous energy storage system with inertia
on Smart Grid, vol. 10, no. 1, pp. 578-591, 2019. capabilities for angle, voltage and frequency stabilization in power grids,"
[15] T. Qoria, F. Gruson, F. Colas, G. Denis, T. Prevost, and X. Guillaud, in 11th Solar & Storage Power System Integration Workshop (SIW 2021),
"Critical Clearing Time Determination and Enhancement of Grid- 2021, pp. 71-78.
Forming Converters Embedding Virtual Impedance as Current Limitation [36] D. Duckwitz, A. Knobloch, F. Welck, T. Becker, C. Gloeckler, and T.
Algorithm," IEEE Journal of Emerging and Selected Topics in Power Buelo, "Experimental Short-Circuit Testing of Grid-Forming Inverters in
Electronics, vol. 8, no. 2, pp. 1050-1061, 2020. Microgrid and Interconnected Mode," in NEIS 2018; Conference on
[16] E. Rokrok, T. Qoria, A. Bruyere, B. Francois, and X. Guillaud, "Transient Sustainable Energy Supply and Energy Storage Systems, 20-21 Sept.
Stability Assessment and Enhancement of Grid-Forming Converters 2018 2018, pp. 1-6.
Embedding Current Reference Saturation as Current Limiting Strategy," [37] W. Du, Q. Nguyen, Y. Liu, and S. M. Mohiuddin, "A Current Limiting
IEEE Transactions on Power Systems, vol. 37, no. 2, pp. 1519-1531, Control Strategy for Single-Loop Droop-Controlled Grid-Forming
2022. Inverters Under Balanced and Unbalanced Faults," in 2022 IEEE Energy
[17] N. Baeckeland, D. Venkatramanan, M. Kleemann, and S. Dhople, Conversion Congress and Exposition (ECCE), 2022, pp. 1-7.
"Stationary-Frame Grid-Forming Inverter Control Architectures for [38] B. Fan and X. Wang, "Equivalent Circuit Model of Grid-Forming
Unbalanced Fault-Current Limiting," IEEE Transactions on Energy Converters With Circular Current Limiter for Transient Stability
Conversion, vol. 37, no. 4, pp. 2813-2825, 2022. Analysis," IEEE Transactions on Power Systems, vol. 37, no. 4, pp. 3141-
[18] Z. Jin and X. Wang, "A DQ-Frame Asymmetrical Virtual Impedance 3144, 2022, doi: 10.1109/TPWRS.2022.3173160.
Control for Enhancing Transient Stability of Grid-Forming Inverters," [39] P. Pourbeik et al., "Generic Dynamic Models for Modeling Wind Power
IEEE Transactions on Power Electronics, vol. 37, no. 4, pp. 4535-4544, Plants and Other Renewable Technologies in Large-Scale Power System
2022. Studies," IEEE Transactions on Energy Conversion, vol. 32, no. 3, pp.
[19] P. J. Hart, M. Gong, H. Liu, Z. Chen, Y. Zhang, and Y. Wang, "Provably- 1108-1116, 2017, doi: 10.1109/TEC.2016.2639050.
Stable Overload Ride-Through Control for Grid-Forming Inverters Using [40] Manitoba HVDC Research Centre, PSCAD Software, 2019 [Online]
System-Wide Lyapunov Function Analysis," IEEE Transactions on Available: https://hvdc.ca/pscad/
Energy Conversion, vol. 37, no. 4, pp. 2761-2776, 2022.
[20] D. Ramasubramanian, Z. Yu, R. Ayyanar, V. Vittal, and J. Undrill,
"Converter Model for Representing Converter Interfaced Generation in
Authorized licensed use limited to: Jorge Vega. Downloaded on April 14,2024 at 15:40:28 UTC from IEEE Xplore. Restrictions apply.
© 2024 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.
This article has been accepted for publication in IEEE Transactions on Power Delivery. This is the author's version which has not been fully edited and
content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2024.3376245
12
Authorized licensed use limited to: Jorge Vega. Downloaded on April 14,2024 at 15:40:28 UTC from IEEE Xplore. Restrictions apply.
© 2024 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.