Packaged Gas/Electric

Rooftop Units
Precedent™
3 - 10Tons — 60 Hz

February 2004 RT-PRC006-EN


Introduction

PrecedentTM . . . The same Trane With its sleek compact cabinet, rounded
quality... with added flexibility. corners and beveled top, it may just be
Precedent is a flexible line of packaged the most aesthetically pleasing
units that covers a wide variety of packaged unit on the planet. And, of
applications. course, Precedent carries the Trane
Electromechanical controls are available reputation for excellence, quality, and
for simpler applications, and for the reliability.
more sophisticated, Reliatel™ From simple applications, to the most
microprocessor controls. In addition to complex, Precedent has the solution.
controls, Precedent offers many other
outstanding features and option choices.

© 2004 American Standard Inc. All rights reserved RT-PRC006-EN


Contents

Introduction 2
Features and Benefits 4
Application Considerations 10
Selection Procedure 11
Model Number Description 13
General Data 14
Performance Data 27
Cooling Performance 27
Fan Performance 36
Heat Performance 74
Controls 76
Electric Power 78
Dimension and Weights 86
Mechanical Specifications 95

RT-PRC006-EN 3
Features and
Benefits

Easy Access Panels


Remove two screws for access to the
standardized internal components and
wiring.
Easy-Adjust Idler Arm
With the Easy-Adjust Idler Arm, the belt
and sheaves on belt drive units can be
quickly adjusted without moving the
mounted fan motor. The result is a major Patented Condenser Coil
savings in time and money.
Precedent boasts a patented 1+1+1
Hybrid coil, permanently gapped for
easy cleaning.
Unit Cabinet
The compact cabinet with rounded
corners takes up less room and is less
costly to ship. The beveled and ribbed
top is not only aesthetically pleasing, it is
designed to prevent water from pooling.
Single Point Power
A single electrical connection powers the
unit. Colored And Numbered Wiring
You save time and money tracing wires
and diagnosing the unit.
Convertible Units
• The units ship in a downflow Sloped Drain Pans
configuration. They can be easily Every Precedent unit has a non-
converted to horizontal by simply corrosive, removable, double-sloped
moving two panels. drain pan that’s easy to clean and
reversible to allow installation of drain
• Units come complete with horizontal trap on either side of the unit.
duct flanges so the contractor doesn’t
Compressors Through the Base Condensate
have to field fabricate them. These
Precedent™ contains the best duct flanges are a time and cost saver. Every unit includes provisions for
compressor technology available to through the base condensate drain
achieve the highest possible connections. This allows the drain to
performance. Our compressor line be connected through the roof curb
includes Trane built Climatuff® instead of a roof penetration.
reciprocating and scrolls.
Foil-Faced Insulation
Easy Access Panels
All panels in the Evaporator section of
Easy access panels reduce the number of the unit have cleanable foil-faced
possible water entry points. insulation. All edges are either
Low Ambient Cooling captured or sealed to ensure no fibers
get into the airstream.
All Precedent microprocessor units have
cooling capabilities down to 0°F as
standard. Electromechanical models
have cooling capabilites to 40°F as built,
or to 0°F by adding the optional low Unit Base
ambient control (Frostat). For added water integrity, Precedent has
a raised 11/8" lip around the unit’s
downflow supply and return to prevent
water from blowing into the ductwork.

4 RT-PRC006-EN
Features and
Benefits

Standardized Components Progressive Tubular Heat Exchanger


• Components are placed in the same The compact cabinet features a tubular
location on all Precedent™ units. heat exchanger in low, medium and high
Familiarize yourself with one Precedent heat capacities.
and you are familiar with every The heat exchanger is fabricated using
Precedent. stainless steel burners and corrosion-
resistant aluminized steel tubes as
standard on all models. It has an induced
draft blower to pull the gas mixture
through the burner tubes. The heater
has a direct spark ignition system which
doubles as a safety device to prove the
flame.
Gas electric Precedent models exceed all
California seasonal efficiency
requirements. They also perform better
than required to meet the California NOx
emission requirments.

Flexible Applications
Easy Access Low Voltage Terminal Board • Only two roof curbs for the 3-10 ton
Precedent line. . .simplifies curb
Precedent’s Low Voltage Terminal Board selection.
is external to the electrical control • Standard or High Efficiency Cooling.
cabinet. It is extremely easy to test • Electromechanical or ReliaTel
operation of all unit functions. This is microprocessor controls to meet either
another cost and time saving installation the simple or the more complex
feature. application.
• Low, medium or high gas heat
capacities.
• Airflow is outstanding. The Precedent
can replace an older machine with old
ductwork and, in many cases, improve
comfort through better air distribution.
• Belt or direct drive —standard or
oversized supply fan motors meet a
wide airflow range.
Low Voltage Connections • Precedent offers ultimate flexibility.
The wiring of the low voltage Options and components are not pre-
connections to the unit and the zone packaged at the factory. Units are built
sensors is as simple as 1-1, 2-2, and 3-3. to order in our standard “shortest in
This simplified system makes it easy for the industry”ship cycle time.
the installer to wire.
Single-Side Service
Single-side service is standard on all
Precedent units.

RT-PRC006-EN 5
Features and
Benefits

• Eliminates the need for field-installed


components with its built-in anti-short-
cycle timer, time delay relay and
minimum ‘’on’’ time controls. These
controls are factory tested to assure
proper operation.
• Requires no special tools to run the
Precedent unit through its paces
during testing. Simply place a jumper
between Test 1 and Test 2 terminals on
the Low Voltage Terminal Board and
the unit will walk through its
Micro Controls operational steps. The unit
automatically returns control to the
Several years ago, Trane was the first to zone sensor after stepping through the
introduce microprocessor controls into test mode a single time, even if the
the Light Commercial Market. That jumper is left on the unit.
design, along with immeasurable
experience, has provided the technology • As long as the unit has power and the
for Trane’s second-generation ReliaTel™ LED is lit, the Micro is operational. The
microprocessor controls. light indicates that the Micro is
functioning properly.
ReliaTel Micro: • Features expanded diagnostic
• Provides unit control for heating, capabilities when used with Trane’s
cooling, and ventilating by utilizing Integrated ComfortTM Systems.
input from sensors that measure • As an energy benefit, softens electrical
outdoor and indoor temperature. ‘’spikes’’ by staging on fans,
compressors and heaters.
• Improves quality and reliability
through the use of time-tested • The Intelligent Fallback or Adaptive
microprocessor controls and logic. Control is a benefit to the building
occupant. If a component goes astray,
• Prevents the unit from short cycling, the unit will continue to operate at
considerably improving compressor predetermined temperature set points.
life.
• Intelligent Anticipation is a standard
• Ensures that the compressor will run feature of the Micro. Functioning
for a specific amount of time, which constantly, the Micro and zone sensors
allows oil to return for better work together in harmony, to provide
lubrication, enhancing the reliability of tight comfort control.
the compressor.
Electromechanical Controls
• Reduces the number of components
required to operate the unit, thereby • For the simpler job that does not
reducing possibilities for component require a building automation system,
failure. or expanded diagnostics capabilities,
Precedent offers electromechanical
controls. This 24-volt control includes
the control transformer and contactor
pressure lugs for power wiring.

6 RT-PRC006-EN
Features and
Benefits

Factory-installed Options Economizer Trane Communication Interface


Dehumidification (Hot Gas Reheat) Equipped with either dry bulb, reference Available factory or field-installed.This
Option or comparative enthalpy sensing, this module, when applied with ReliaTel™,
feature provides free cooling as the easily interfaces with Trane’s Integrated
This option allows for increased outdoor outdoor temperature and/or humidity ComfortTM System.
air ventilation. It reduces humidity levels decreases. Economizers, correctly
while increasing comfort level in the air installed, offer valuable energy savings.
space. Cooling can operate without a Factory-installed economizers save time
demand for dehumidification. The hot and ensure proper installation.
gas reheat coil is designed to deliver
maximum reheat temperatures and Through the Base Utility Access
pivot to allow for easy access cleaning. Factory provided through the base
openings simplify electrical wiring
and gas piping. Because these utility
openings frequently minimize the
number of roof penetrations, the integrity
of roofing materials is enhanced.
Phase Monitor
Phase monitor shall provide 100%
protection for motors and compressors
against problems caused by phase loss,
phase imbalance, and phase reversal.
Phase monitor is equipped with an LED
that provides an ON or FAULT indicator.
Clogged Filter/Fan Fail Switches
These sensors allow a zone sensor
Hinged Access Doors service light or Integrated Comfort
These doors permit easy access to the System to indicate a dirty filter or a fan
filter, fan/heat, and compressor/control that’s not working.The field installation
sections. They reduce the potential roof charges for these valuable feedback
damage from screws or sharp access devices often eliminate them from
door corners. consideration. Factory installation can
make such features a good investment.
Unit Mounted Disconnect or Circuit
Breaker
Codes require a method of assured unit
shutdown for servicing. Field-installed
disconnects sometimes interfere with
service access. Factory installation of unit
disconnects reduces costs, assures
proper mounting and provides the
opportunity to upgrade to unit circuit
breaker protection.

Unit Disconnect Switch

Convenience Outlet

RT-PRC006-EN 7
Features and
Benefits

The following options round-out the


complete line of Precedent™ options:
— 0 - 50% Manual or Motorized
Outside Air
— Electric Heaters
— Discharge Air Sensor
— Hail Protection Quality Coil Guards
— Supply and/or Return Smoke
Detectors
— High Pressure Cutout
(standard on 3 phase models with
scroll compressor and all standard
efficiency 3-ton models)
— Thermal Expansion Valve for a wider
range of applications
— Wide array of Zone Sensors and
Thermostats
— Liquid Propane Conversion Kits
— Factory built Roof Curb
— Power Exhaust
— LonTalk Communications Interface

One of Our Finest Assets:


Trane Sales Representatives are a
Support group that can assist you with:
— Product
— Application
— Service
— Training
— Special Applications
— Specifications
— Computer Programs and much more
Precedent has the features and benefits
that make it first class in the light
commercial rooftop market. Designed
with input from field contractors and
engineers, its airflow performance is
outstanding.
Precedent…The same Trane
quality…with added flexibility.

8 RT-PRC006-EN
Features and
Benefits

Quality And Reliability Testing • We perform a 100% coil leak test at the
• All Precedent™ designs were factory. The evaporator and condenser
coils are leak tested at 200 psig and
rigorously rain tested at the factory to
ensure water integrity. pressure tested to 450 psig.

• Actual shipping tests were performed • All parts are inspected at the point of
to determine packaging requirements. final assembly. Sub-standard parts are
Units were test shipped around the identified and rejected immediately.
country to determine the best • The requirement for cycle testing of
packaging. heat exchangers is 10,000 cycles by
• Factory shake and drop tests were ANSI Z21.47. This is the standard
used as part of the package design required by both UL and AGA for cycle
process to help assure that the unit test requirments. Trane requires the
arrives at the job site in top condition. design to be tested to 2½ times this
current standard.
• Rigging tests include lifting a unit into
the air and letting it drop one foot, • Every unit receives a 100% unit run test
assuring that the lifting lugs and rails before leaving the production line to
hold up under stress. make sure it lives up to rigorous Trane
requirements.

We test designs at our factory not on


our customers!

VariTrac™

VariTrac
When Trane’s changeover VAV System
for light commercial applications is
coupled with Precedent, it provides the
latest in technological advances for
comfort management systems and can
allow thermostat control in every zone
served by VariTrac.

RT-PRC006-EN 9
Application
Considerations

Application of this product should be NOTE:THE EFFECTIVENESS OF


within the cataloged airflow and cooling BAROMETRIC RELIEF DAMPER
considerations. DURING ECONOMIZING OPERATION
IS SYSTEM RELATED. PRESSURE
Low Ambient Cooling
DROP OF THE RETURN AIR SYSTEM
The Precedent™ line features, as SHOULD BE CONSIDERED TO
standard, low ambient cooling down to CONTROL BUILDING
0°F with the ReliaTel™ microprocessor PRESSURIZATION.
controls and 40°F with
electromechanical controls. Contact Condensate Trap
your local Trane Representative for more The evaporator is a draw-thru
assistance with low ambient cooling configuration. A trap must be field
applications. provided prior to start-up on the
Barometric Relief cooling cycle.
This product offers an optional Clearance Requirements
barometric relief damper for use in The recommended clearances
conjunction with economizer option. identified with unit dimensions should
This option consists of gravity dampers be maintained to assure adequate
which open with increased pressure. As service, maximum capacity and peak
the building air pressure increases, the operating efficiency. Actual clearances
pressure in the unit return air section which appear inadequate should be
also increases, opening the dampers and reviewed with the local Trane sales
relieving the conditioned space. personnel.
Heating Operation Unit Pitch
The heat exchanger is manufactured These units have reversible sloped
with aluminized steel. To prevent condensate drain pans. Units must be
condensation within the heat exchanger, installed level; any unit slope must be
do not exceed 50% outside air. toward side of unit where condensate
drain is connected.

10 RT-PRC006-EN
Selection
Procedures

Cooling Capacity Step 4 Heating Capacity


Step 1 In order to select the correct unit which Step 1 — Calculate the building heating
Calculate the building’s total and sensible meets the building’s requirements, the load using the Trane calculation form or
cooling loads at design conditions. Use fan motor heat must be deducted from other standard accepted method.
theTrane calculation methods or any the gross cooling capacity.The amount of
Step 2 — Size the system heating
other standard accepted method. heat that the fan motor generates is
capacity to match the calculated
dependent on the effort by the motor -
building heating load. The following are
cfm and static pressure.To determine the
Factors used in unit selection: building heating requirements:
total unit static pressure:
A a. Total heating load of 60.0 MBh
Total Cooling Load: 58 MBh External Static (duct system) b. 2000 cfm
B 0.52 wg c. Fuel - Natural gas
Sensible Cooling Load: 40 MBh For the YSC060A4 there are three
C Standard Filter 1 in. 0.06 wg
heating capacities available, 60 MBh, 80
Airflow: 2000 cfm from Table PD-89
MBh and 130 MBh input models shown
D Economizer 0.18 wg inTable PD-91.The output capacities of
Electrical Characteristics: 460/60/3 (100% Outside Air) from Table these furnaces are 48 MBh, 64 MBh
E PD-89 and 104 MBh respectively. The medium
Summer Design Conditions: Entering heat model with 64 MBh best matches
Evaporator Coil: 80 DB, 67 WB Outdoor the building requirements, indicating a
Ambient: 95 Total Static Pressure 0.76 wg YHC060A4*M should be selected.
F
Air Delivery Selection
External Static Pressure: 0.52 in. wg
G Note: The Evaporator Fan Performance External static pressure drop through
Downflow Configuration Table PD-64 has deducted the pressure the air distribution system has been
H drop for a 1 in. filter already in the unit calculated to be 0.7 inches of water.
High Efficiency (see note below Table PD-64). Therefore, Enter Table PD-64 for a YHC060A4*M at
I the actual total static pressure is 0.76 - 2000 cfm and 0.70 static pressure.The
Economizer 0.06 (fromTable PD - 89) = 0.70 wg. standard motor will give the desired
airflow with 1.07 bhp and 1094 rpm .
Step 2 With 2000 cfm and 0.70 wg. Accessory Selection
As a starting point, a rough determination Table PD-64 shows 1.07 bhp for this unit.
must be made of the size of the unit.The Note below the table gives a formula to Select accessories needed to
final selection will be made after calculate Fan Motor Heat, accommodate the application.
examining the performance at the given 2.829 x bhp + .4024 = MBH.
conditions. Divide the total cooling load by 2.829 x 1.07 + .4024 = 3.43 MBH.
nominal BTUH per ton (12 MBh per ton);
then round up to the nearest unit size.
Now subtract the fan motor heat from
the gross cooling capacity of the unit:
58 MBh / 12 MBh = approx. 5 tons
NetTotal Cooling Capacity
= 62.4 MBH - 3.43 = 58.97 MBH.
Step 3
Table PD-13 shows that a YHC060A4 has Net Sensible Cooling Capacity
a gross cooling capacity of 62.4 MBh and = 48.4 MBH - 3.43 = 44.97 MBH.
48.4 MBh sensible capacity at 2000 cfm
and 95 DB outdoor ambient with 80 DB, Step 5
67 WB air entering the evaporator. If the performance will not meet the
required load of the building’s total or
sensible cooling load, try a selection at
To Find Capacity at Intermediate the next higher size unit.
Conditions Not in the Table
When the design conditions are between
two numbers that are in the capacity
table, interpolation is required to
approximate the capacity. Note:
Extrapolation outside of the table
conditions is not recommended.

RT-PRC006-EN 11
Selection
Procedure

Dehumidification Selection Step 3: Determine reheat


Typical 10 ton YHC120A temperature rise
3200 cfmTotal Supply airflow Go to PD-92 for reheat temperature rise:
1280 cfm Outside Air (40%) 21°F db
1920 cfm Return Air
0.35” External Static Pressure

OA Conditions 68°F DB,


OA 67°F WB
Part load day and raining
68°F db RA'
75°F DB,
67°F wb 52% RH

MA' 72.2°F DB
RA’ conditions 65°F WB
OA
75°F db SA' 53°F DB
63°F wb MA'
SA 74°F DB RA'
Step 1: Determine the mixed/
entering air condition (MA’) SA' REHEAT SA
MA’ = (% outside air*outside air dry-bulb
temperature) + (% return air*return air
dry-bulb temperature)
MA’ = (0.40*68°F) + (0.60*75°F)
Chart C-1
MA’ = 72.20°F db
Note: Repeat for wet-bulb
temperature (wb).
Plot on psychrometric chart.
Note: Reheat temperature rise is based Step 5: Determine static pressure
MA’ on supply airflow and leaving evaporator drop add for reheat
72.2°F db coil temperature. Table PD-61 shows a static pressure drop
65°F wb of 0.09” wc 0.35”+ 0.09” = 0.5” wc
Step 4: Determine leaving unit
Step 2: Determine leaving unit temperature Table PD-54 indicates that a standard
temperature Reheat temperature (obtained in step 3) motor and field installed low static drive
Leaving Unit Temperature = SA’ + SA’ kit is needed for this airflow and static
Utilize theTOPSS™ program to 21°F db + 53°F = 74°F db pressure range.
determine the leaving unit temperature. SA=74°F

53.8°F db Consider Chart C-1. If the space relative


52.7°F wb humidity is equal to or above the space
51.8°F dp relative humidity setpoint, the
Dehumidification Option will:

• Energize compressor or both


compressors (2 stage compressor units).
• Hot gas reheat valve is energized and
hot gas is diverted to the reheat coil.
• Dehumidification/reheat is terminated
when space humidity is reduced to 5%
below relative humidity setpoint.

At MA’, air enters the RTU.The RTU filters,


cools, and dehumidifies the air as it
moves through the evaporator coil. Air
leaves the evaporator coil saturated at
the preset dew point condition (SA’) and
is reheated by the hot gas reheat coil to
deliver 74°F (SA) supply air to the space.

12 RT-PRC006-EN
Model
Number
Description

Y S C 036 A 3 R L A ** C 0 0 0 C 1 0 0 0 1 A 1
1 2 3 4,5,6 7 8 9 10 11 12,13 14 15 16 17 18 19 20 21 22 23 24 25

DIGIT 1 - Unit Function DIGIT 14 - Fresh Air Selection DIGIT 20 - Convenience Outlet
Y = DX Cooling, Gas Heat 0 = No Fresh Air 0 = No Convenience Outlet
A = Manual Outside Air Damper 0-50% A = Unpowered Convenience Outlet
DIGIT 2 - Efficiency B = Motorized Outside Air Damper 0-50% B = Powered Convenience Outlet
C = Economizer, Dry Bulb 0-100% (3 phase only)
S = Standard Efficiency
without Barometric Relief
H = High Efficiency
D = Economizer, Dry Bulb 0-100% DIGIT 21 - Communications Options
with Barometric Relief 0 = No Communications Interface
DIGIT 3 - Airflow E = Economizer, Reference Enthalpy 1 = Trane Communications Interface
C = Convertible 0-100% without Barometric Relief 2 = LonTalk® Communications Interface
F = Economizer, Reference Enthalpy 3 = Novar 2024 Controls
DIGITS 4,5,6 - Nominal Gross Cooling 0-100% with Barometric Relief 4 = Novar 3051 Controls
G = Economizer, Comparative Enthalpy
Capacity (MBh) 0-100% without Barometric Relief
036 = 3-Ton H = Economizer, Comparative Enthalpy DIGIT 22 - Refrigeration System Option
048 = 4-Ton 0-100% with Barometric Relief 0 = Standard Refrigeration System
060 = 5-Ton A = Thermal Expansion Valve (TXV)
072 = 6-Ton DIGIT 15 - Supply Fan/Drive Type/Motor B = Dehumidification (Hot Gas Reheat Coil)
090 = 7½-Ton, Single Compressor
092 = 7½-Ton, Dual Compressors 0 = Standard Drive
1 = Oversized Motor DIGIT 23 - Refrigeration Controls
102 = 8½-Ton
120 = 10-Ton 2 = Optional Belt Drive Motor 0 = No Refrigeration Control
1 = High Pressure Control
DIGIT 16 - Hinged Service AccessFilters 2 = Frostat
DIGIT 7 - Major Design Sequence 3 = Crankcase Heater
A = First 0 = Standard Panels/Standard Filters 4 = High Pressure Control and Frostat
A = Hinged Access Panels/Standard Filters 5 = High Pressure Control and Crankcase
B = Standard Panels/2” Pleated Filters Heater
DIGIT 8 - Unit Voltage C = Hinged Access Panels/2” Pleated Filters 6 = Frostat and Crankcase Heater
1 = 208-230/60/1
7 = High Pressure Control, Frostat and
3 = 208-230/60/3 DIGIT 17 - Condenser Coil Protection Crankcase Heater
4 = 460/60/3
W = 575/60/3 0 = Standard Coil
K = 380/60/3 1 = Standard Coil with Hail Guard DIGIT 24 - Smoke Detector
2 = Epoxy Coated Condenser Coil 0 = No Smoke Detector
3 = Epoxy Coated Condenser Coil with A = Return Air Smoke Detector
DIGIT 9 - Unit Controls Hail Guard
E = Electromechanical B = Supply Air Smoke Detector
R = ReliaTel™Microprocessor C = Supply and Return Air Smoke
DIGIT 18 - Through the Base Provisions Detectors
0 = No Through the Base Provisions
DIGIT 10 - Heating Capacity A = Through the Base Electric DIGIT 25 - Monitoring Controls
L = Low B = Through the Base Gas Piping
M = Medium 0 = No Monitoring Control
C = Through the Base Electric and Gas
H = High 1 = Clogged Filter Switch
Piping
2 = Fan Failure Switch
3 = DischargeAir Sensing Tube
DIGIT 11 - Minor Design Sequence DIGIT 19 - Disconnect/Circuit Breaker/ 4 = Clogged Filter Switch and Fan Fail
A = First Sequence Phase Monitor (3 phase only) Switch
0 = No Disconnect/NoCircuit Breaker/No 5 = Clogged Filter Switch and Discharge
DIGITS 12, 13 - Service Sequence Phase Monitor Air Sensing Tube
1 = Unit Mounted Non-Fused Disconnect 6 = Fan Fail Switch and Discharge Air
**= Factory Assigned
2 = Unit Mounted Circuit Breaker Sensing Tube
3 = Phase Monitor 7 = Clogged Filter and Fan Fail Switches
4 = Phase Monitor & Non-Fused and Discharge Air Sensing Tube
Disconnect Switch 8 = Novar Return Air Sensor
5 = Phase Monitor & Circuit Breaker
Example:
Model number YSC036A3RLA**C000C10001A10 describes a unit with the following characteristics: DX Cooling with natural gas heating, 3 ton nominal cooling capacity, 208-230/60/3 power supply,
ReliaTel™ controls, low heat model. 0-100% dry bulb economizer without barometric relief, standard direct drive motor, standard access panels, standard condenser coil with no coil protection,
through the base electric and gas access, non-fused disconnect, no convenience outlet or communications interface, standard refrigeration coil, high pressure control, return air smoke detector, and
clogged filter switch.

RT-PRC006-EN 13
General (3 - 4 Tons)
Data Standard Efficiency

Table GD-1 — General Data


3-Ton Convertible Units 4-Ton Convertible Units
YSC036A1 YSC036A3, A4, AW YSC048A1 YSC048A3, A4, AW
Cooling Performance1
Gross Cooling Capacity 37,400 37,400 50,300 49,200
SEER2 10.5 10.7 10.1 10.0
Nominal CFM / ARI Rated CFM 1,200/1,200 1,200/1,200 1,600/1,600 1,600/1,600
ARI Net Cooling Capacity 36,000 36,000 48,000 47,000
System Power (KW) 3.91 3.79 5.28 5.40
Heating Performance4
Heating Models Low Medium High Low Medium High Low Medium High Low Medium High
Heating Input (Btu) 60,000 80,000 120,000 60,000 80,000 120,000 60,000 80,000 120,000 60,000 80,000 120,000
Heating Output (Btu) 47,000 63,000 95,000 48,000 64,000 96,000 47,000 63,000 95,000 48,000 64,000 96,000
AFUE %5 80 80 80 81 81 81 80 80 80 81 81 81
Steady State Efficiency (%) 80 80 80 81 81 81 80 80 80 81 81 81
No. Burners 2 2 3 2 2 3 2 2 3 2 2 3
No. Stages 1 1 1 1 1 1 1 1 1 1 1 1
Gas Supply Line Pressure
Natural (minimum/maximum) 4.5/14.0 4.5/14.0 4.5/14.0 4.5/14.0
LP (minimum/maximum) 10.0/14.0 10.0/14.0 10.0/14.0 10.0/14.0
Gas Connection Pipe Size (in.) 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2
Compressor
No./Type 1/Climatuff Hermetic 1/Climatuff Hermetic 1/Climatuff Scroll 1/Climatuff Scroll
Outdoor Sound Rating (dB)6 83 83 86 82
Outdoor Coil - Type Lanced Lanced Lanced Lanced
Tube Size (in.) OD 0.3125 0.3125 0.3125 0.3125
Face Area (sq ft) 7.19 7.19 6.17 9.59
Rows/FPI 2/17 2/17 2/17 1/17
Indoor Coil - Type Lanced Lanced Lanced Lanced
Tube Size (in.) 0.3125 0.3125 0.3125 .3125
Face Area (sq ft) 5.67 5.67 6.68 6.17
Rows/FPI 2/16 2/16 3/16 3/16
Refrigerant Control Short Orifice Short Orifice Short Orifice Short Orifice
Drain Connection No./Size (in.) 1/¾ NPT 1/¾ NPT 1/¾ NPT 1/¾ NPT
Outdoor Fan - Type Propeller Propeller Propeller Propeller
No. Used/Diameter (in.) 1/22 1/22 1/22 1/22
Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1
CFM 2,550 2,550 2,850 3,610
No. Motors/HP 1/0.20 1/0.20 1/0.33 1/0.33
Motor RPM 1,075 1,075 1,075 1,075
Direct Drive Indoor Fan - Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter (in.) 1/10 x 10 1/10 x 10 1/11 x 11 1/11 x 11
Drive Type/No. Speeds Direct/2 Direct/2 Direct/2 Direct/2
No. Motors 1 1 1 1
Motor HP (Standard/Oversized) 0.33/0.50 0.33/0.50 0.60/0.80 0.60/0.80
Motor RPM (Standard/Oversized) 950/1,1009 930/1,1009 1,000/1,100 1,000/1,100
Motor Frame Size (Standard/Oversized) 48/48 48/48 48/48 48/48

14 RT-PRC006-EN
General (3 - 4 Tons)
Data Standard Efficiency

Table GD-1 — Continued


3-Ton Convertible Units 4-Ton Convertible Units
YSC036A1 YSC036A3, A4, AW YSC048A1 YSC048A3, A4, AW
Belt Drive Indoor Fan -Type — FC Centrifugal —
No. Used/Diameter (in.) — 1/11 x 11 — 1/11 x 11
DriveType/No. Speeds — Belt/Variable Sheave —
No. Motors — 1 — 1
Motor HP (Standard/Oversized) — 1.00/— — 1.00/—
Motor RPM (Standard/Oversized) — 1,750/— — 1,750/—
Motor Frame Size (Standard/Oversized) — 56/— — 56/—
Filters -Type Furnished 10 Throwaway Throwaway Throwaway Throwaway
8
(No.) Size Recommended (2) 20 x 25 x 1 (2) 20 x 25 x 18 (2) 20 x 25 x 18
(2) 20 x 25 x 18
Refrigerant Charge (Lbs of R-22)7 3.8 3.8 4.4 3.8
NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the
effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is
based on ARI Standard 210/240 except AK (380V/60 Hz).
2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80° F ambient, 80° F entering dry bulb, and 67° F entering wet bulb at ARI rated cfm.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards.
Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
5. AFUE is rated in accordance with DOE test procedures.
6. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For additional information refer to Table PD-90.
7. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
8. 20 x 25 filter on medium and low heat models. 20 x 30 filter on high heat models
9. Motor RPM shown is low speed. High speed RPM is 1,060/1,145.
10. Optional 2” pleated filters also available.

RT-PRC006-EN 15
General (5 - 6 Tons)
Data Standard Efficiency

Table GD-2 — General Data


5-Ton Convertible 6-Ton Convertible
YSC060A1 YSC060A3, A4, AW, AK YSC072A3, A4, AW, AK
1
Cooling Performance
Gross Cooling Capacity 63,100 63,100 72,000
SEER/EER2 9.90/— 10.20/— —/10.212
Nominal CFM / ARI Rated CFM 2,000/2,000 2,000/2,000 2,400/2,100
ARI Net Cooling Capacity 60,000 60,000 69,000
3
Integrated Part Load Value — — —
System Power (KW) 6.86 6.78 6.77
Heating Performance4
Heating Models Low Medium High Low Medium13 High Low Medium13 High
Heating Input (Btu) 60,000 80,000 130,000 60,000 80,000 130,000 80,000 120,000 150,000
Heating Output (Btu) 47,000 63,000 103,000 48,000 64,000 104,000 64,800 97,200 121,500
AFUE%5 81 81 80 81 81 80 81 81 81
Steady State Efficiency (%) 81 81 80 81 81 80 81 81 81
No. Burners 2 2 3 2 2 3 2 3 3
No. Stages 1 1 1 1 1 1 1 1 2
Gas Supply Line Pressure
Natural (minimum/maximum) 4.5/14.0 4.5/14.0 4.5/14.0
LP (minimum/maximum) 10.0/14.0 10.0/14.0 10.0/14.0
Gas Connection Pipe Size (in.) 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 3/4
Compressor
No./Type 1/Climatuff Scroll 1/Climatuff Scroll 1/Climatuff Scroll
Outdoor Sound Rating (dB)6 84 84 88
Outdoor Coil - Type Lanced Lanced Lanced
Tube Size (in.) OD 0.3125 0.3125 0.3125
Face Area (sq ft) 8.81 8.81 13.88
Rows/FPI 2/17 2/17 2/17
Indoor Coil - Type Lanced Lanced Lanced
Tube Size (in.) 0.3125 0.3125 0.3125
Face Area (sq ft) 5.00 5.00 9.89
Rows/FPI 3/16 3/16 2/16
Refrigerant Control Short Orifice Short Orifice Short Orifice
Drain Connection No./Size (in.) 1/¾ NPT 1/¾ NPT 1/¾ NPT
Outdoor Fan - Type Propeller Propeller Propeller
No. Used/Diameter (in.) 1/22 1/22 1/26
Drive Type/No. Speeds Direct/1 Direct/1 Direct/1
CFM 3,470 3,470 6,100
No. Motors/HP 1/0.33 1/0.3315 1/0.7014
Motor RPM 1075 1,075 1,075
Direct Drive Indoor Fan - Type FC Centrifugal FC Centrifugal N/A
No. Used/Diameter (in.) 1/11 x 118 1/11 x 118 N/A
Drive Type/No. Speeds Direct/2 Direct/2 N/A
No. Motors 1 1 N/A
Motor HP (Standard/Oversized) 0.90/1.00 0.90/1.0016 N/A
Motor RPM (Standard/Oversized) 985/1,0809 985/1,0809 N/A
Motor Frame Size (Standard/Oversized) 48/48 48/48 N/A

16 RT-PRC006-EN
General (5 - 6 Tons)
Data Standard Efficiency

Table GD-2 — Continued


5-Ton Convertible 6-Ton Convertible
YSC060A1 YSC060A3, A4, AW, AK YSC072A3, A4, AW, AK
Belt Drive Indoor Fan -Type — FC Centrifugal FC Centrifugal
No. Used/Diameter (in.) — 1/11 x 11 1/12 x 12
DriveType/No. Speeds — Belt/Variable Sheave Belt/Variable Sheave
No. Motors — 1 1
Motor HP (Standard/Oversized) — 1.00/— 1.00/2.0017
Motor RPM (Standard/Oversized) — 1,750/ — 1,750/1,750
Motor Frame Size (Standard/Oversized) — 48/— 56/56
Filters -Type Furnished 11 Throwaway Throwaway Throwaway
(No.) Size Recommended (2) 20 x 25 x 110 (2) 20 x 25 x 110 (4) 16 x 25 x 2
Refrigerant Charge (Lbs of R-22)7 4.7 4.9 7.1
NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes
the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air-Conditioner Equipment certification program,
which is based on ARI Standard 210/240 except AK (380V/ 60 Hz) units.
2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80° F ambient, 80° F entering dry bulb, and 67° F entering wet bulb at ARI rated cfm.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards.
Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
5. AFUE is rated in accordance with DOE test procedures.
6. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For additional information refer to Table PD-90.
7. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
8. YSC060A1,3,4,W Oversized Motor and YSC060AK Standard Motor Fan Diameter is 12 x 11.
9. Motor RPM shown is low speed. High speed RPM is 1100/1135.
10. Filter size shown is for low and medium heat models. High heat model filter size recommended is 20 x 30 x 1.
11. Optional 2” pleated filters also available.
12. YSC072A when used in a horizontal application has an EER of 10.1 and System Power (kW) of 6.83.
13. Medium heat is not available for AK (380V/ 60 Hz) units.
14. Outdoor motor is 0.75 hp for AK (380V/60 Hz) units.
15. Outdoor motor is 0.40 hp for AK (380V/60 Hz) units.
16. Standard Motor is 1.00 hp for YSC060AK (380V/ 60 Hz) units.
17. Standard Motor is 2.00 hp for the YSC072AK (380V/ 60 Hz) units.

RT-PRC006-EN 17
General (7½ - 8½ Tons)
Data Standard Efficiency

Table GD-3 — General Data


7½-Ton Convertible 8½-Ton Convertible
Single Compressor Dual Compressor
YSC090A3, A4, AW, AK YSC092A3, A4, AW YSC102A3,A4,AW, AK
Cooling Performance1
Gross Cooling Capacity 95,000 92,000 105,000
EER2 10.1 10.48 10.1
Nominal CFM / ARI Rated CFM 3,000/2,625 3,000/2,625 3,400/3,000
ARI Net Cooling Capacity 90,000 87,000 100,0009
Integrated Part Load Value3 — 11.08 11.89
System Power (KW) 8.91 8.378 9.99
Heating Performance4
Heating Models Low Medium11 High Low Medium High Low Medium11 High
Heating Input (Btu) 120,000 150,000 200,000 120,000 150,000 200,000 120,000 150,000 200,000
Heating Output (Btu) 97,200 121,500 162000 97,200 121,500 162000 97,200 121,500 162000
AFUE%5 81 81 81 81 81 81 81 81 81
Steady State Efficiency (%) 81 81 80 81 81 80 81 81 81
No. Burners 3 3 4 3 3 4 3 3 4
No. Stages 1 2 2 1 2 2 1 2 2
Gas Supply Line Pressure
Natural (minimum/maximum) 4.5/14.0 4.5/14.0 4.5/14.0
LP (minimum/maximum) 10.0/14.0 10.0/14.0 10.0/14.0
Gas Connection Pipe Size (in.) 1/2 3/4 3/4 1/2 3/4 3/4 1/2 3/4 3/4
Compressor
No./Type 1/Trane Scroll 2/Climatuff Scrolls 2/Climatuff Scrolls
Outdoor Sound Rating (dB)6 90 87 86
Outdoor Coil - Type Lanced Lanced Lanced
Tube Size (in.) OD 0.3125 0.3125 0.3125
Face Area (sq ft) 17.0 17.0 19.83
Rows/FPI 3/17 2/17 2/17
Indoor Coil - Type Lanced Lanced Lanced
Tube Size (in.) 0.3125 0.3125 0.3125
Face Area (sq ft) 9.89 9.89 12.36
Rows/FPI 3/16 3/16 3/16
Refrigerant Control Short Orifice Short Orifice Short Orifice
Drain Connection No./Size (in.) 1/¾ NPT 1/¾ NPT 1/¾ NPT
Outdoor Fan - Type Propeller Propeller Propeller
No. Used/Diameter (in.) 1/26 1/26 1/26
Drive Type/No. Speeds Direct/1 Direct/1 Direct/1
CFM 6200 6500 7100
No. Motors/HP 1/0.7012 1/0.70 1/0.75
Motor RPM 1075 1,075 1,075

18 RT-PRC006-EN
General (7½ - 8½ Tons)
Data Standard Efficiency

Table GD-3 — Continued


7½-Ton Convertible 8½-Ton Convertible
Single Compressor Dual Compressor
YSC090A3, A4, AW, AK YSC092A3, A4, AW YSC102A3,A4,AW, AK

Belt Drive Indoor Fan - Type FC Centrifugal FC Centrifugal FC Centrifugal


No. Used/Diameter (in.) 1/12 x 12 1/12 x 12 1/15 x 15
Drive Type/No. Speeds Belt/Variable Sheave Belt/Variable Sheave Belt/Variable Sheave
No. Motors 1 1 1
Motor HP (Standard/Oversized) 2.00/3.00 2.00/3.00 2.00/3.00
Motor RPM (Standard/Oversized) 1,750/1,750 1,750/1,750 1,750/1,750
Motor Frame Size (Standard/Oversized) 56/56 56/56 56/56
Filters - Type Furnished 10 Throwaway Throwaway Throwaway
(No.) Size Recommended (4) 16 x 25 x 2 (4) 16 x 25 x 2 (4) 20 x 25 x 2
Refrigerant Charge (Lbs of R-22)7 11.9 6.2 Circuit 1/3.4 Circuit 2 7.9 Circuit 1/4.0 Circuit 2
NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect
of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on
ARI Standard 210/240 except AK (380V/60 Hz) units.
2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80° F ambient, 80° F entering dry bulb, and 67° F entering wet bulb at ARI rated cfm.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards.
Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
5. AFUE is rated in accordance with DOE test procedures.
6. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For additional information refer to Table PD-90.
7. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
8. YSC092A when applied in a horizontal configuration has a 10.1 EER, 10.7 Integrated Part Load Value, and 8.61 System Power (KW).
9. YSC102A when applied in horizontal configuration has an 11.3 Integrated Part Load Value, 9.8 System Power (KW) and 99,000 ARI Net Cooling Capacity.
10. Optional 2” pleated filters also available.
11. Medium heat is not available for AK (380V/60 Hz) units.
12. Outdoor motor is 0.75 hp for AK (380V/60 Hz) units.

RT-PRC006-EN 19
General (10 Tons)
Data Standard Efficiency

Table GD-4 — General Data


10-Ton Convertible
YSC120A3, A4, AW, AK
Cooling Performance1
Gross Cooling Capacity 118,000
EER2 10.28
Nominal CFM / ARI Rated CFM 4,000/3,200
ARI Net Cooling Capacity 114,0008
Integrated Part Load Value3 11.38
System Power (KW) 11.188
Heating Performance4
Heating Models Low Medium10 High
Heating Input (Btu) 150,000 200,000 250,000
Heating Output (Btu) 121,500 162,000 202,500
AFUE%5 81 81 81
Steady State Efficiency (%) 81 81 81
No. Burners 3 4 5
No. Stages 2 2 2
Gas Supply Line Pressure
Natural (minimum/maximum) 4.5/14.0
LP (minimum/maximum) 10.0/14.0
Gas Connection Pipe Size (in.) 3/4 3/4 3/4
Compressor
No./Type 2/Climatuff Scrolls
Outdoor Sound Rating (dB)6 86
Outdoor Coil - Type Lanced
Tube Size (in.) OD 0.3125
Face Area (sq ft) 19.83
Rows/FPI 2/17
Indoor Coil - Type Lanced
Tube Size (in.) 0.3125 .
Face Area (sq ft) 12.36
Rows/FPI 4/16
Refrigerant Control Short Orifice
Drain Connection No./Size (in.) 1¾NPT

20 RT-PRC006-EN
General (10 Tons)
Data Standard Efficiency

Table GD-4 — Continued


10-Ton Convertible
YSC120A3, A4, AW, AK
Outdoor Fan - Type Propeller
No. Used/Diameter (in.) 1/26
Drive Type/No. Speeds Direct/1
CFM 7000
No. Motors/HP 1/0.75
Motor RPM 1,075
Belt Drive Indoor Fan - Type FC Centrifugal
No. Used/Diameter (in.) 1/15 x 15
Drive Type/No. Speeds Belt/Variable Sheave
No. Motors 1
Motor HP (Standard/Oversized) 3.00/5.00
Motor RPM (Standard/Oversized) 1,750/3,450
Motor Frame Size (Standard/Oversized) 56/56
Filters - Type Furnished 9 Throwaway
(No.) Size Recommended (4) 20 x 25 x 2
Refrigerant Charge (Lbs of R-22)7 7.2 Circuit 1/5.3 Circuit 2
NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect
of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on
ARI Standard 210/240 except AK (380V/60 Hz).
2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80° F ambient, 80° F entering dry bulb, and 67° F entering wet bulb at ARI rated cfm.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards.
Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
5. AFUE is rated in accordance with DOE test procedures.
6. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For additional information refer to Table PD-90.
7. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
8. YSC120A when applied in a horizontal configuration has a 10.1 EER, 112,000 ARI Net Cooling Capacity, 10.7 Integrated Part Load Value and 11.09 System Power (KW).
9. Optional 2” pleated filters also available.
10. Medium heat is not available for AK (380V/60 Hz) units.

RT-PRC006-EN 21
General (3 - 4 Tons)
Data High Efficiency

Table GD-5 — General Data


3-Ton Convertible Units 4-Ton Convertible Units
YHC036A1, A3, A4, AW YHC048A1, A3, A4, AW
Cooling Performance1
Gross Cooling Capacity 38,000 49,800
SEER2 12.50 12.0
Nominal CFM / ARI Rated CFM 1,200 / 1,200 1,600/1,600
ARI Net Cooling Capacity 36,600 47,500
System Power (KW) 3.33 4.48
Heating Performance3
Heating Models Low Medium High Low Medium High
Heating Input (Btu) 60,000 80,000 120,000 60,000 80,000 120,000
Heating Output (Btu)7 48,000 64,000 96,000 48,000 64,000 96,000
AFUE %4 8 81 81 81 81 81 81
Steady State Efficiency (%)8 81 81 81 81 81 81
No. Burners 2 2 3 2 2 3
No. Stages 1 1 1 1 1 1
Gas Supply Line Pressure
Natural (minimum/maximum) 4.5/14.0 4.5/14.0
LP (minimum/maximum) 10.0/14.0 10.0/14.0
Gas Connection Pipe Size (in.) 1/2 1/2 1/2 1/2 1/2 1/2
Compressor
No./Type 1/Climatuff Scroll 1/Climatuff Scroll
Outdoor Sound Rating (dB)5 83 85
Outdoor Coil - Type Lanced Lanced
Tube Size (in.) OD 0.3125 0.3125
Face Area (sq ft) 7.19 9.59
Rows/FPI 2/17 3/17
Indoor Coil - Type Lanced Lanced
Tube Size (in.) 0.3125 0.3125
Face Area (sq ft) 6.68 6.68
Rows/FPI 3/16 4/16
Refrigerant Control Short Orifice Short Orifice
Drain Connection No./Size (in.) 1/¾ NPT 1/¾ NPT
Outdoor Fan - Type Propeller Propeller
No. Used/Diameter (in.) 1/22 1/22
DriveType/No. Speeds Direct/114 Direct/114
CFM 2,550 3,050
No. Motors/HP 1/0.20 1/0.33
Motor RPM 1,075 1,075

22 RT-PRC006-EN
General (3 - 4 Tons)
Data High Efficiency

Table GD-5 — Continued


3-Ton Convertible Units 4-Ton Convertible Units
YHC036A1, A3, A4, AW YHC048A1, A3, A4, AW
Direct Drive Indoor Fan - Type FC Centrifugal FC Centrifugal
No. Used/Diameter (in.) 1/10 x10 1/11 x 11
DriveType/No. Speeds Direct/2 Direct/2
No. Motors 1 1
Motor HP (Standard/Oversized) 0.33/0.50 0.60/0.80
Motor RPM (Standard/Oversized) 950/1,1009 930/1,0009
Motor Frame Size (Standard/Oversized) 48/48 48/48
Belt Drive Indoor Fan -Type FC Centrifugal FC Centrifugal
No. Used/Diameter (in.) 1/11 x 11 1/11 x 11
DriveType/No. Speeds Belt/Variable Sheave 12 Belt/Variable Sheave 12
No. Motors 1 1
Motor HP (Standard/Oversized) 1.00/— 1.00/—
Motor RPM (Standard/Oversized) 1,750/— 1,750/—
Motor Frame Size (Standard/Oversized) 56/— 56/—
Filters -Type Furnished 13 Throwaway Throwaway
(No.) Size Recommended (2) 20 x 25 x 110 (2) 20 x 25 x 110
Optional Hot Gas Reheat Coil -Type Lanced Lanced
Tube Size (in.)OD 0.375 0.375
Face Area (sq. ft.) 2.22 2.22
Rows/FPI 1/16 1/16
Refrigerant Charge (Lbs of R-22)6
Standard 5.311 7.711
Optional Hot Gas Reheat Coil 5.3 8.5
NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes
the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is
based on ARI Standard 210/240.
2. SEER are rated at ARI conditions and in accordance with DOE test procedures.
3. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown
are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
4. AFUE and Steady State Efficiency is rated in accordance with DOE test procedures.
5. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For additional information refer to Table PD-90.
6. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
7. YHC036A1 and YHC048A1 Heating Output (Btu) is Low 47,000, Medium 63,000, High 95,000.
8. YHC036A1 and YHC048A1 AFUE (%) and Steady State (%) is Low, Medium and High 80.0.
9. Motor RPM shown is low speed. High speed Motor RPM is : YHC036A 1,060/1,145, YHC048A 1,000/1,100.
10. Filter size shown is for low and medium heat models. High heat model filter size recommended is 20 x 30 x 1.
11. Refigerant charge shown is for three phase. YHC036A1 Refrigerant Charge is 4.5, YHC048A1 refrigerant charge is 8.1.
12. Belt Drive motor is not available for YHC036A1, YHC048A1
13. Optional 2” pleated filters also available.
14. With Dehumidification (Hot Gas Reheat) option: Direct/2.

RT-PRC006-EN 23
General (5 - 6 Tons)
Data High Efficiency

Table GD-6 — General Data


5-Ton Convertible Units 6-Ton Convertible Units
YHC060A1 YHC060A3, A4, AW YHC072A3, A4, AW
Cooling Performance1
Gross Cooling Capacity 62,100 62,400 73,000
SEER / EER2 11.8 / — 12.0/ — — /11.510
Nominal CFM / ARI Rated CFM 2,000 / 2,000 2,000/2,000 2,400/2,100
ARI Net Cooling Capacity 59,000 59,500 70,000
System Power (KW) 5.73 5.56 6.0910
Heating Performance4
Heating Models Low Medium High Low Medium High Low Medium High
Heating Input (Btu) 60,000 80,000 130,000 60,000 80,000 130,000 80,000 120,000 150,000
Heating Output (Btu) 48,000 64,000 103,000 48,000 64,000 104,000 64,800 97,200 121,500
AFUE %5 81 81 80 81 81 80 81 81 81
Steady State Efficiency (%)5 81 81 80 81 81 80 81 81 81
No. Burners 2 2 3 2 2 3 2 3 3
No. Stages 1 1 1 1 1 1 1 1 2
Gas Supply Line Pressure
Natural (minimum/maximum) 4.5/14.0 4.5/14.0 4.5/14.0
LP (minimum/maximum) 10.0/14.0 10.0/14.0 10.0/14.0
Gas Connection Pipe Size (in.) 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 3/4
Compressor
No./Type 1/Climatuff Scroll 1/Climatuff Scroll 1/Climatuff Scroll
Outdoor Sound Rating (dB)6 84 84 89
Outdoor Coil - Type Lanced Lanced Lanced
Tube Size (in.) OD 0.3125 0.3125 0.3125
Face Area (sq ft) 10.96 10.96 17.00
Rows/FPI 3/17 3/17 3/17
Indoor Coil - Type Lanced Lanced Lanced
Tube Size (in.) 0.3125 0.3125 0.3125
Face Area (sq ft) 7.71 7.71 9.89
Rows/FPI 4/16 4/16 3/16
Refrigerant Control Short Orifice Short Orifice14 Short Orifice
Drain Connection No./Size (in.) 1/¾ NPT 1/¾ NPT 1/¾ NPT
Outdoor Fan - Type Propeller Propeller Propeller
No. Used/Diameter (in.) 1/22 1/22 1/26
Drive Type/No. Speeds Direct/1 Direct/113 Direct/1
CFM 3,170 3,370 6100
No. Motors/HP 1/0.33 1/0.33 1/0.70
Motor RPM 1,075 1,075 1,075

24 RT-PRC006-EN
General (5 - 6 Tons)
Data High Efficiency

Table GD-6 — Continued


5-Ton Convertible Units 6-Ton Convertible Units
YHC060A1 YHC060A3, A4, AW YHC072A3, A4, AW
Direct Drive Indoor Fan -Type FC Centrifugal FC Centrifugal N/A
No. Used/Diameter (in.) 1/11 x 118 1/11 x 118 N/A
DriveType/No. Speeds Direct/2 Direct/2 N/A
No. Motors 1 1 N/A
Motor HP (Standard/Oversized) 0.90/1.00 0.90/1.00 N/A
Motor RPM (Standard/Oversized) 985/1,0809 985/1,0809 N/A
Motor Frame Size (Standard/Oversized) 48/48 48/48 N/A
Belt Drive Indoor Fan -Type FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter (in.) 1/11 x 11 1/11 x 11 1/12 x 12
DriveType/No. Speeds Belt/Variable Sheave 11 Belt/Variable Sheave11 Belt/Variable Sheave
No. Motors 1 1 1
Motor HP (Standard/Oversized) 1.00/— 1.00/— 1.00/2.00
Motor RPM (Standard/Oversized) 1,750/— 1,750/— 1750,1750
Motor Frame Size (Standard/Oversized) 56/— 56/— 56/56
Filters -Type Furnished Throwaway Throwaway Throwaway
(No.) Size Recommended (2)20 x 30 x 112 (2) 20 x 30 x 112 (4) 16 x 25 x 212
Optional Hot Gas Reheat Coil -Type — Lanced —
Tube Size (in.)OD — 0.375 —
Face Area (sq. ft.) — 2.22 —
Rows/FPI — 2/16 —
Refrigerant Charge (Lbs of R-22)7
Standard 7.9 8.4 10.7
Optional Hot Gas Reheat Coil — 10.7 —
NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes
the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air-Conditioner Equipment certification program,
which is based on ARI Standard 210/240.
2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80° F ambient, 80° F entering dry bulb, and 67° F entering wet bulb at ARI rated cfm.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings
shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
5. AFUE is rated in accordance with DOE test procedures.
6. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For additional information refer to Table PD-90.
7. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
8. YHC060A Oversized Motor Fan Diameter is 12 x 11.
9. Motor RPM shown is low speed. High speed Motor RPM is 1,100/1,135.
10. YHC072A when applied in a horizontal configuration has an 11.3 EER and 6.2 System Power (kW).
11. Belt Drive Motor is not available for YHC060A1.
12. 2" pleated filters is a factory installed option. 2" pleated filters is standard with the Dehumidification (Hot Gas Reheat) option.
13. With Dehumidification (Hot Gas Reheat) option: Direct/2.
14. TXV is supplied from the factory as standard with the Dehumidification (Hot Gas Reheat) option.

RT-PRC006-EN 25
General (7½ - 10 Tons)
Data High Efficiency

Table GD-7 — General Data


7½-Ton Convertible 8½-Ton Convertible 10-Ton Convertible
YHC092A3, A4, AW YHC102A3, A4, AW YHC120A3, A4, AW
Cooling Performance1
Gross Cooling Capacity 94,000 103,000 117,000
EER2 11.58 11.59 11.210
Nominal CFM / ARI Rated CFM 3,000/2,625 3,400/3,000 4,000/3,200
ARI Net Cooling Capacity 90,0008 98,0009 109,00010
Integrated Part Load Value3 11.88 11.89 11.710
System Power (KW) 7.838 8.529 9.7310
Heating Performance4
Heating Models Low Medium High Low Medium High Low Medium High
Heating Input (Btu) 120,000 150,000 200,000 120,000 150,000 200,000 150,000 200,000 250,000
Heating Output (Btu) 97,200 121,500 162000 97,200 121,500 162000 121,500 162,000 202,500
AFUE%5 81 81 81 81 81 81 81 81 81
Steady State Efficiency (%) 81 81 80 81 81 80 81 81 81
No. Burners 3 3 4 3 3 4 3 4 5
No. Stages 1 2 2 1 2 2 2 2 2
Gas Supply Line Pressure
Natural (minimum/maximum) 4.5/14.0 4.5/14.0 4.5/14.0
LP (minimum/maximum) 10.0/14.0 10.0/14.0 10.0/14.0
Gas Connection Pipe Size (in.) 1/2 3/4 3/4 1/2 3/4 3/4 3/4 3/4 3/4
Compressor
No./Type 2/Climatuff Scrolls 2/Climatuff Scrolls 2/Climatuff Scrolls
Outdoor Sound Rating (dB)6 91 89 88
Outdoor Coil -Type Lanced Lanced Lanced
Tube Size (in.) OD 0.3125 0.3125 0.3125
Face Area (sq ft) 17.5 19.83 27.21
Rows/FPI 3/17 3/17 3/17
Indoor Coil -Type Lanced Lanced Lanced
Tube Size (in.) 0.3125 0.3125 0.3125
Face Area (sq ft) 12.36 12.36 12.36
Rows/FPI 3/16 4/16 5/16
Refrigerant Control Short Orifice Short Orifice Short Orifice
Drain Connection No./Size (in.) 1/¾ NPT 1/¾ NPT 1/¾ NPT
Outdoor Fan -Type Propeller Propeller Propeller
No. Used/Diameter (in.) 1/26 1/26 1/26
DriveType/No. Speeds Direct/1 Direct/1 Direct/1
CFM 6200 6600 7000
No. Motors/HP 1/0.70 1/0.75 1/0.75
Motor RPM 1075 1,075 1,075
Belt Drive Indoor Fan -Type FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter (in.) 1/15 x 15 1/15 x 15 1/15 x 15
DriveType/No. Speeds Belt/Variable Sheave Belt/Variable Sheave Belt/Variable Sheave
No. Motors 1 1 1
Motor HP (Standard/Oversized) 2.00/3.00 2.00/3.00 3.00/5.00
Motor RPM (Standard/Oversized) 1,750/1,750 1,750/1,750 1,750/3,450
Motor Frame Size (Standard/Oversized) 56/56 56/56 56/56
Filters -Type Furnished 11 Throwaway Throwaway Throwaway
(No.) Size Recommended (4) 20 x 25 x 2 (4) 20 x 25 x 2 (4) 20 x 25 x 2
Optional Reheat Coil -Type Lanced Lanced Lanced
Tube Size (in.) OD 0.375 0.375 0.375
Face Area (sq. ft.) 5.19 5.19 5.19
Rows/FPI 2/16 2/16 2/16
Refrigerant Charge (Lbs of R-22)7 6.4 Circuit 1/6.2 Circuit 2 7.4 Circuit 1/7.1 Circuit 2 11.0 Circuit 1/7.3 Circuit 2
NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect
of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on
ARI Standard 210/240.
2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80° F ambient, 80° F entering dry bulb, and 67° F entering wet bulb at ARI rated cfm.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for
elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
5. AFUE is rated in accordance with DOE test procedures.
6. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For additional information refer to Table PD-90.
7. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
8. YHC092A when applied in a horizontal configuration has an 11.3 EER, 89,000 ARI Net Cooling Capacity, 11.4 Integrated Part Load Value, and 7.88 System Power (KW).
9. YHC102A when applied in horizontal configuration has an 11.3 EER, 11.3 IPLV, 97,000 ARI Net Cooling Capacity and 8.58 System Power (KW).
10. YHC120A when applied in a horizontal configuration has an 10.7 EER, 11.2 IPL, 108,000 ARI Net Cooling and 10.09 System Power (KW).
11. Optional 2” pleated filters also available.

26 RT-PRC006-EN
Performance (3 Ton)
Data Standard Efficiency

Table PD-1 — Gross Cooling Capacities (MBH) 3-Ton Single/Three Phase YSC036A1, A3, A4, AW
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 34.6 29.0 38.6 22.3 40.6 14.7 31.2 27.3 36.6 21.1 39.5 13.8 28.2 25.6 33.4 19.6 37.8 12.9 25.1 24.1 29.6 18.2 35.5 11.9
80 35.6 35.0 38.8 27.3 41.0 20.2 32.6 32.6 36.8 26.6 39.8 19.5 30.0 30.0 33.5 25.2 38.0 18.5 27.3 27.3 29.9 23.5 35.6 17.5
1080
85 37.6 37.6 39.2 32.5 41.5 24.7 35.6 35.6 37.2 32.2 40.1 24.2 32.8 32.8 34.2 31.0 38.2 23.8 30.1 30.1 30.7 29.3 35.8 23.0
90 39.3 39.3 39.7 37.6 42.0 29.2 37.8 37.8 37.9 37.6 40.4 29.1 35.7 35.7 35.7 35.7 38.5 28.9 33.0 33.0 32.9 32.9 36.0 28.4
75 35.6 30.9 39.0 22.8 40.9 14.9 32.2 29.2 37.3 22.1 39.8 14.1 29.0 27.5 34.3 20.7 38.2 13.1 25.9 25.9 30.4 19.0 36.0 12.1
80 36.7 36.7 39.3 28.4 41.4 20.6 34.3 34.3 37.4 28.1 40.2 20.3 31.4 31.4 34.5 26.9 38.4 19.3 28.6 28.6 30.7 25.2 36.1 18.3
1200
85 38.7 38.7 39.7 33.9 41.9 25.3 37.0 37.0 37.9 34.0 40.5 25.0 34.5 34.5 35.3 33.2 38.7 24.8 31.5 31.5 31.7 31.6 36.3 24.2
90 40.2 40.2 40.4 39.2 42.3 30.1 38.8 38.8 38.8 38.8 40.9 30.2 37.1 37.1 37.0 37.0 39.1 30.3 34.6 34.6 34.6 34.6 36.6 30.0
75 36.4 32.6 39.4 23.5 41.1 15.1 33.2 31.0 37.7 23.0 40.1 14.3 29.8 29.3 34.9 21.8 38.5 13.4 26.8 26.8 30.9 20.0 36.3 12.4
80 37.7 37.7 39.7 29.4 41.6 20.9 35.7 35.7 37.9 29.3 40.4 21.2 32.7 32.7 35.2 28.5 38.7 19.9 29.8 29.8 31.4 26.8 36.5 19.0
1320
85 39.4 39.4 40.2 35.2 42.1 25.9 37.9 37.9 38.5 35.6 40.8 25.7 35.9 35.9 36.2 35.3 39.1 25.7 32.9 32.9 32.9 32.9 36.7 25.3
90 40.8 40.8 40.9 40.5 42.6 30.8 39.7 39.7 39.6 39.6 41.2 31.2 38.0 38.0 38.0 38.0 39.5 31.6 35.9 35.9 35.9 35.9 37.1 31.5
75 37.0 34.1 39.7 24.0 41.3 15.3 34.1 32.8 38.0 23.7 40.3 14.5 30.6 30.6 35.5 22.7 38.7 13.6 27.7 27.7 31.4 21.0 36.6 12.6
80 38.4 38.4 40.0 30.3 41.8 21.2 36.7 36.7 38.3 30.5 40.8 21.0 33.9 33.9 35.8 30.0 39.0 20.4 30.8 30.8 32.0 28.4 36.8 19.7
1440
85 40.0 40.0 40.6 36.3 42.4 26.4 38.7 38.7 39.0 37.0 41.2 26.7 36.8 36.8 36.8 36.8 39.4 26.6 34.2 34.2 34.2 34.2 37.0 26.4
90 41.4 41.4 41.4 41.4 42.9 31.6 40.3 40.3 40.3 40.3 41.5 32.1 38.7 38.7 38.7 38.7 39.9 32.7 36.7 36.7 36.7 36.7 37.6 33.0
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

RT-PRC006-EN 27
Performance (4 Ton)
Data Standard Efficiency

Table PD-2 — Gross Cooling Capacities (MBH) 4-Ton Single Phase YSC048A1
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 45.5 38.7 52.4 30.0 56.4 20.1 41.6 36.6 49.0 28.3 54.4 18.9 37.6 34.5 44.4 26.7 51.8 17.5 33.5 32.3 39.8 24.5 48.0 15.8
80 46.5 46.5 52.5 37.6 56.8 28.1 43.2 43.2 49.1 35.9 54.8 26.7 39.9 39.9 44.6 33.8 52.0 25.2 36.5 36.5 40.1 31.6 48.2 23.4
1440
85 50.3 50.3 53.0 45.1 57.4 34.9 47.0 47.0 49.7 43.7 55.0 33.9 43.6 43.6 45.3 41.6 52.2 32.8 40.2 40.2 41.0 39.5 48.3 31.0
90 53.3 53.3 53.8 52.5 57.7 41.1 50.8 50.8 50.8 50.8 55.5 41.0 47.5 47.5 47.5 47.5 52.5 40.1 44.0 44.0 44.0 44.0 48.6 38.6
75 46.8 41.3 53.1 31.3 56.9 20.5 42.7 39.1 50.1 29.7 55.0 19.2 38.7 37.0 45.4 27.5 52.4 17.9 34.4 34.4 40.8 25.4 48.9 16.3
80 48.7 48.7 53.4 39.5 57.5 28.9 45.2 45.2 50.3 38.2 55.4 27.8 41.8 41.8 45.7 36.0 52.7 26.3 38.2 38.2 41.1 33.9 49.1 24.7
1600
85 52.2 52.2 53.9 47.5 58.1 36.1 49.3 49.3 51.0 46.7 55.7 35.3 45.7 45.7 46.7 44.7 52.9 34.5 42.1 42.1 42.1 42.1 49.2 33.0
90 54.9 54.9 54.9 54.9 58.4 42.8 52.7 52.7 52.7 52.7 56.2 42.9 49.8 49.8 49.8 49.8 53.3 42.5 46.2 46.2 46.2 46.2 49.7 41.3
75 48.1 43.8 53.6 32.5 57.3 20.8 43.8 41.6 50.8 31.1 55.5 19.6 39.8 39.5 46.3 29.0 52.9 18.2 35.8 35.8 41.5 26.7 49.6 16.7
80 50.5 50.5 54.0 41.2 58.0 29.6 47.1 47.1 51.1 40.3 55.9 29.0 43.4 43.4 46.7 38.2 53.2 27.4 39.8 39.8 42.0 36.0 49.7 25.8
1760
85 53.6 53.6 54.8 49.8 58.6 37.1 51.1 51.1 52.0 49.4 56.3 36.6 47.7 47.7 48.1 47.9 53.5 36.1 43.9 43.9 43.9 43.9 49.9 34.9
90 56.1 56.1 56.1 56.1 59.0 44.2 54.2 54.2 54.1 54.1 56.9 44.8 51.5 51.5 51.5 51.5 54.1 44.7 48.2 48.2 48.2 48.2 50.5 43.9
75 49.1 46.3 54.2 33.5 57.7 21.2 44.9 44.0 51.5 32.4 55.9 20.0 40.7 40.7 47.1 30.4 53.3 18.6 37.0 37.0 42.2 28.1 50.1 17.0
80 51.9 51.9 54.6 42.7 58.4 30.1 48.8 48.8 51.8 42.2 56.3 30.2 45.0 45.0 47.7 40.4 53.7 28.5 41.2 41.2 42.9 38.2 50.3 26.9
1920
85 54.7 54.7 55.5 51.8 59.1 38.1 52.5 52.5 52.9 51.8 56.8 37.8 49.4 49.4 49.4 49.4 54.1 37.6 45.5 45.5 45.5 45.5 50.5 36.6
90 57.1 57.1 57.1 57.1 59.4 45.6 55.3 55.3 55.3 55.3 57.4 46.4 52.8 52.8 52.8 52.8 54.7 46.7 49.8 49.8 49.8 49.8 51.3 46.2
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table PD-3 — Gross Cooling Capacities (MBH) 4-Ton Three Phase YSC048A3, A4, AW
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 44.8 38.6 51.4 29.8 56.1 20.1 41.0 36.6 48.2 28.2 53.7 18.9 37.3 34.7 44.2 26.4 50.8 17.6 33.4 32.7 39.6 25.2 47.1 16.0
80 46.0 46.0 51.6 37.4 56.5 27.9 42.9 42.9 48.3 35.8 54.0 26.6 39.7 39.7 44.4 34.0 51.0 25.2 36.4 36.4 40.0 32.0 47.2 23.6
1440 85 49.6 49.6 52.0 44.8 56.7 34.8 46.8 46.8 48.9 43.6 54.2 34.0 43.6 43.6 45.1 41.8 51.2 32.7 40.3 40.3 41.0 39.8 47.4 31.1
90 52.5 52.5 52.9 52.2 57.2 41.6 50.2 50.2 50.1 50.1 54.6 41.1 47.2 47.2 47.2 47.2 51.5 40.1 43.9 43.9 43.9 43.9 47.7 38.6
75 46.1 41.1 52.1 31.1 56.7 20.5 42.1 39.0 49.1 29.6 54.4 19.3 38.3 37.1 45.1 27.8 51.5 18.0 34.3 34.3 40.6 25.7 47.9 16.5
80 48.1 48.1 52.4 39.3 57.2 29.0 44.9 44.9 49.2 37.9 54.7 27.7 41.5 41.5 45.4 36.2 51.7 26.3 38.1 38.1 41.0 34.2 48.0 24.8
1600 85 51.4 51.4 53.0 47.3 57.7 36.7 48.7 48.7 50.0 46.4 55.0 35.5 45.6 45.6 46.3 44.8 51.9 34.6 42.1 42.1 42.1 42.1 48.2 33.0
90 54.2 54.2 54.2 54.2 58.0 43.5 51.9 51.9 51.9 51.9 55.4 43.2 49.1 49.1 49.1 49.1 52.3 42.5 45.9 45.9 45.9 45.9 48.7 41.3
75 47.2 43.5 52.8 32.3 57.3 20.9 43.3 41.5 49.8 30.9 54.9 19.7 39.1 39.1 45.8 29.1 52.0 18.3 35.6 35.6 41.3 27.1 48.5 16.8
80 49.7 49.7 53.1 41.0 57.8 30.1 46.7 46.7 50.1 40.0 55.3 28.8 43.3 43.3 46.2 38.3 52.3 27.4 39.7 39.7 41.8 36.3 48.7 25.9
1760 85 52.8 52.8 53.8 49.7 58.1 37.7 50.3 50.3 51.0 49.1 55.6 37.0 47.2 47.2 47.2 47.2 52.5 36.1 43.7 43.7 43.7 43.7 48.9 34.9
90 55.5 55.5 55.5 55.5 58.7 45.3 53.4 53.4 53.4 53.4 56.1 45.2 50.7 50.7 50.7 50.7 53.1 44.7 47.6 47.6 47.6 47.6 49.5 43.8
75 48.2 45.8 53.3 33.4 57.8 21.3 44.4 43.8 50.4 32.1 55.4 20.0 40.3 40.3 46.5 30.4 52.5 18.6 36.6 36.6 41.9 28.3 49.0 17.2
80 51.0 51.0 53.7 42.7 58.3 31.1 48.1 48.1 50.7 41.9 55.7 29.6 44.7 44.7 47.0 40.3 52.8 28.4 41.1 41.1 42.6 38.3 49.2 26.9
1920 85 53.9 53.9 54.6 51.8 58.6 38.7 51.6 51.6 51.9 51.5 56.2 38.4 48.6 48.6 48.6 48.6 53.1 37.7 45.2 45.2 45.2 45.2 49.4 36.6
90 56.6 56.6 56.6 56.6 59.3 47.0 54.6 54.6 54.5 54.5 56.8 47.1 52.0 52.0 52.0 52.0 53.8 46.9 49.0 49.0 49.0 49.0 50.3 46.1
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

28 RT-PRC006-EN
Performance (5 - 6Ton)
Data Standard Efficiency

Table PD-4 — Gross Cooling Capacities (MBH) 5-Ton Single/Three Phase YSC060A1,A3,A4,AW, AK
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 57.4 49.1 64.8 37.9 69.2 25.3 53.3 47.0 61.8 36.3 67.2 24.1 49.4 45.0 57.6 34.3 64.3 22.8 45.2 42.9 52.4 32.7 60.6 21.2
80 59.0 59.0 65.1 47.1 69.8 35.0 55.6 55.6 62.0 45.7 67.6 33.8 52.2 52.2 57.8 43.9 64.6 32.3 48.6 48.6 52.8 41.6 60.8 30.6
1800
85 63.1 63.1 65.7 56.2 70.2 42.9 60.3 60.3 62.7 55.3 68.0 42.3 56.8 56.8 58.9 53.6 64.9 41.3 52.9 52.9 54.0 51.4 61.0 39.9
90 66.4 66.4 66.9 65.2 70.8 51.0 64.1 64.1 64.1 64.1 68.5 50.8 61.1 61.1 61.1 61.1 65.4 50.1 57.5 57.5 57.5 57.5 61.5 49.0
75 59.0 52.2 65.7 39.4 69.8 25.7 54.9 50.1 62.8 37.9 67.8 24.6 50.7 48.0 58.9 36.1 64.9 23.2 46.5 45.9 53.5 33.8 61.3 21.6
80 61.3 61.3 66.0 49.2 70.2 35.6 58.1 58.1 63.1 48.2 68.1 34.8 54.4 54.4 59.2 46.6 65.3 33.7 50.6 50.6 54.0 44.3 61.5 32.0
2000
85 65.1 65.1 66.8 59.1 70.9 44.2 62.5 62.5 64.0 58.5 68.7 43.8 59.3 59.3 60.4 57.3 65.7 43.1 55.2 55.2 55.8 55.2 61.8 41.9
90 68.1 68.1 68.0 68.0 71.6 52.9 65.9 65.9 65.9 65.9 69.4 52.9 63.1 63.1 63.1 63.1 66.3 52.5 59.7 59.7 59.7 59.7 62.4 51.7
75 60.3 55.2 66.3 40.6 70.2 26.1 56.3 53.1 63.6 39.5 68.2 25.0 52.0 51.0 59.9 37.8 65.4 23.6 47.7 47.7 54.5 35.4 61.8 22.0
80 63.1 63.1 66.8 51.2 70.8 37.9 60.2 60.2 64.0 50.5 68.7 35.6 56.5 56.5 60.3 49.1 65.8 34.6 52.4 52.4 55.2 46.9 62.1 33.3
2200
85 66.5 66.5 67.7 61.6 71.5 45.4 64.2 64.2 65.0 61.3 69.4 45.2 61.2 61.2 61.7 60.5 66.4 44.7 57.3 57.3 57.3 57.3 62.5 43.8
90 69.4 69.4 69.3 69.3 72.2 54.6 67.3 67.3 67.3 67.3 70.1 54.9 64.6 64.6 64.6 64.6 67.1 54.8 61.2 61.2 61.2 61.2 63.2 54.2
75 61.5 58.0 66.9 41.8 70.6 26.5 57.6 56.0 64.2 40.8 68.6 25.4 53.0 53.0 60.6 39.3 65.9 24.0 49.1 49.1 55.4 37.1 62.2 22.4
80 64.5 64.5 67.5 53.0 71.2 38.8 61.8 61.8 64.7 52.5 69.1 36.4 58.3 58.3 61.1 51.4 66.3 35.5 53.9 53.9 56.3 49.5 62.5 34.3
2400
85 67.7 67.7 68.5 63.9 72.0 46.5 65.4 65.4 65.9 63.9 69.9 46.5 62.5 62.5 62.5 62.5 66.9 46.2 58.9 58.9 58.9 58.9 63.0 45.5
90 70.4 70.4 70.4 70.4 72.8 56.1 68.4 68.4 68.4 68.4 70.6 56.6 65.8 65.8 65.8 65.8 67.7 56.8 62.4 62.4 62.4 62.4 63.9 56.5
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table PD-5 — Gross Cooling Capacities (MBH) 6-Ton Three Phase YSC072A3,A4,AW, AK
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 65.9 55.0 73.4 43.5 76.7 28.3 61.0 52.5 70.7 40.9 75.4 27.3 56.3 50.1 66.3 38.8 73.2 26.0 51.7 47.7 60.9 36.4 70.3 24.6
80 67.6 66.2 73.7 52.2 77.5 38.9 63.2 63.2 70.9 51.1 76.0 37.8 59.2 59.2 66.4 49.1 73.7 36.4 55.3 55.3 61.0 46.6 70.6 34.9
2160 85 71.4 71.4 74.2 61.9 78.6 47.4 68.5 68.5 71.4 61.3 76.5 46.6 64.4 64.4 67.3 59.7 74.0 46.0 60.4 60.4 62.2 57.3 70.8 45.0
90 74.6 74.6 75.3 71.3 79.3 55.7 72.4 72.4 72.8 71.3 77.2 55.5 69.5 69.5 69.5 69.5 74.6 55.4 65.7 65.7 65.6 65.6 71.2 54.8
75 67.7 58.3 74.0 43.8 77.1 28.7 62.9 55.9 71.7 42.6 75.9 27.7 57.9 53.4 67.9 40.8 73.7 26.4 53.2 51.0 62.4 38.3 70.9 25.0
80 69.7 69.7 74.6 54.1 78.0 39.5 66.2 66.2 72.0 53.6 76.6 39.2 61.8 61.8 68.0 52.0 74.3 37.9 57.8 57.8 62.6 49.6 71.3 36.3
2400 85 73.4 73.4 75.3 64.5 79.0 48.2 70.9 70.9 72.7 64.5 77.2 47.9 67.4 67.4 69.1 63.6 74.8 47.6 63.2 63.2 64.2 61.4 71.7 47.0
90 76.2 76.2 76.5 74.3 79.9 57.1 74.3 74.3 74.3 74.3 77.9 57.4 71.7 71.7 71.7 71.7 75.5 57.7 68.5 68.5 68.4 68.4 72.2 57.5
75 69.1 61.4 74.7 44.9 77.4 29.0 64.5 59.1 72.5 44.3 76.2 28.1 59.4 56.6 69.0 42.5 74.2 26.9 54.7 54.2 63.6 40.1 71.3 25.4
80 71.6 71.6 75.3 55.8 78.4 40.0 68.6 68.6 72.8 55.8 77.0 41.1 64.2 64.2 69.1 54.7 74.6 38.6 60.0 60.0 63.9 52.4 71.9 37.7
2640 85 74.8 74.8 76.1 66.8 79.4 49.1 72.7 72.7 73.8 67.3 77.8 49.3 69.7 69.7 70.5 66.9 75.4 49.1 65.7 65.7 66.1 65.4 72.3 48.7
90 77.4 77.4 77.5 76.8 80.3 58.4 75.8 75.8 75.8 75.8 78.5 59.0 73.4 73.4 73.3 73.3 76.2 59.7 70.5 70.5 70.5 70.5 73.0 59.8
75 70.2 64.1 75.2 45.8 77.6 29.4 66.1 62.3 73.1 45.4 76.5 28.5 60.9 59.7 69.8 44.2 74.5 27.3 56.2 56.2 64.7 41.9 71.7 25.8
80 72.9 72.9 75.9 57.4 78.7 40.4 70.3 70.3 73.6 57.8 77.3 41.8 66.5 66.5 70.1 57.1 75.2 41.1 62.0 62.0 65.2 55.2 72.1 38.5
2880 85 75.9 75.9 76.8 68.8 79.7 49.9 74.0 74.0 74.7 69.8 78.5 50.6 71.3 71.3 71.6 69.8 75.9 50.4 67.8 67.8 67.7 67.7 72.9 50.1
90 78.3 78.3 78.3 78.3 80.7 59.6 76.8 76.8 76.8 76.8 79.0 60.5 74.6 74.6 74.6 74.6 76.7 61.6 71.9 71.9 71.9 71.9 73.7 61.9
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

RT-PRC006-EN 29
Performance (7½Ton)
Data Standard Efficiency

Table PD-6 — Gross Cooling Capacities (MBH) 7½-Ton Single Compressor Three Phase YSC090A3,A4,AW, AK
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 87.4 73.8 96.2 56.7 98.8 36.7 80.6 70.3 93.3 54.3 98.8 35.6 73.5 66.6 86.9 51.2 96.8 33.9 66.6 63.1 78.4 48.2 92.8 31.8
80 89.6 88.9 96.6 68.7 100.0 49.9 83.4 83.4 93.5 68.3 99.9 50.2 77.6 77.6 87.2 65.3 97.4 48.2 71.6 71.6 78.9 61.5 92.9 46.0
2700 85 94.2 94.2 97.5 81.6 101.2 60.4 90.4 90.4 94.4 82.2 100.9 61.9 84.8 84.8 88.5 79.8 97.8 61.4 78.5 78.5 80.7 76.2 93.2 59.9
90 98.0 98.0 98.7 93.9 102.3 71.0 95.8 95.8 96.2 95.8 101.2 72.9 91.6 91.6 91.6 91.6 98.5 74.3 86.0 86.0 86.0 86.0 93.7 73.5
75 89.7 78.4 96.7 57.3 99.1 37.2 83.0 75.0 94.6 56.7 99.2 36.1 75.8 71.3 88.9 53.9 97.5 34.5 68.7 67.7 80.3 50.1 93.8 32.5
80 92.2 92.2 97.5 70.9 100.3 50.4 87.4 87.4 95.0 71.8 100.4 50.9 81.4 81.4 89.3 69.5 98.3 50.3 75.0 75.0 81.1 65.8 94.1 48.1
3000 85 96.5 96.5 98.5 84.4 101.5 61.2 93.8 93.8 96.1 86.6 101.6 63.4 88.9 88.9 91.0 85.5 98.8 63.7 82.5 82.5 83.7 82.1 94.4 63.1
90 99.5 99.5 99.9 97.0 102.6 72.3 98.2 98.2 98.2 98.2 101.9 75.0 94.9 94.9 94.9 94.9 99.7 77.4 90.1 90.1 90.0 90.0 95.3 77.7
75 91.5 82.5 97.7 59.0 99.3 37.7 85.2 79.6 95.5 58.8 99.5 36.6 78.0 76.0 90.5 56.5 98.0 35.1 70.5 70.5 82.1 52.8 94.5 33.2
80 94.4 94.4 98.1 72.8 100.5 55.0 90.7 90.7 96.2 74.8 100.8 51.6 84.7 84.7 91.1 73.5 98.9 51.5 78.0 78.0 83.2 70.0 95.0 50.1
3300 85 98.0 98.0 99.2 86.8 101.7 62.0 96.1 96.1 97.5 90.5 102.0 64.7 92.0 92.0 93.1 90.6 99.5 65.6 86.2 86.2 86.2 86.2 95.4 65.8
90 100.5 100.5 100.7 99.4 102.8 73.4 99.9 99.9 99.9 99.9 102.4 76.8 97.2 97.2 97.2 97.2 100.5 80.1 93.0 93.0 93.0 93.0 96.5 81.4
75 92.9 86.2 98.1 59.9 99.4 38.2 87.3 84.1 96.3 60.6 99.8 37.2 79.6 79.6 91.7 58.9 98.3 35.7 72.9 72.9 83.7 55.4 95.1 33.8
80 96.0 96.0 98.6 74.3 100.7 56.8 93.1 93.1 97.1 77.5 101.0 55.7 87.6 87.6 92.5 77.2 99.5 52.7 80.7 80.7 85.1 74.1 95.5 51.6
3600 85 99.0 99.0 99.7 88.7 101.8 62.7 97.8 97.8 98.6 93.7 102.3 65.8 94.4 94.4 94.4 94.4 100.0 67.3 89.1 89.1 89.1 89.1 96.3 68.3
90 101.1 101.1 101.1 101.1 103.0 74.4 101.0 101.0 101.0 101.0 102.8 78.4 98.9 98.9 98.9 98.9 101.2 82.4 95.1 95.1 95.1 95.1 97.5 84.6
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table PD-7 — Gross Cooling Capacities (MBH) 7½-Ton Dual Compressors Three Phase YSC092A3,A4,AW
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 84.6 72.9 93.9 55.3 98.4 36.4 78.2 69.6 90.1 53.3 96.9 35.1 71.8 66.3 83.9 50.4 94.0 33.3 65.3 63.1 76.5 47.1 89.4 31.2
80 86.8 86.8 94.4 68.5 99.6 50.0 81.8 81.8 90.5 67.5 98.0 49.7 76.4 76.4 84.3 64.7 94.5 47.5 70.9 70.9 77.1 61.4 89.6 45.3
2700 85 92.2 92.2 95.4 81.7 100.8 61.3 88.4 88.4 91.5 81.5 99.0 62.4 83.2 83.2 85.8 79.3 94.9 60.9 77.6 77.6 79.0 76.1 89.9 59.3
90 96.3 96.3 96.9 94.4 102.0 72.8 93.6 93.6 93.6 93.6 99.3 73.4 89.6 89.6 89.6 89.6 95.8 74.0 84.5 84.5 84.5 84.5 90.6 73.0
75 86.8 77.5 94.7 57.0 98.9 37.1 80.5 74.4 91.5 55.8 97.6 35.7 74.0 71.1 85.6 53.1 94.8 34.0 67.1 67.1 78.2 49.8 90.5 31.9
80 90.1 90.1 95.6 71.2 100.2 50.8 85.4 85.4 92.0 71.1 98.7 50.7 79.9 79.9 86.3 68.9 95.5 49.6 74.1 74.1 79.1 65.7 90.8 47.4
3000 85 94.7 94.7 96.8 85.3 101.4 62.7 91.5 91.5 93.3 86.2 99.7 63.7 86.9 86.9 88.2 84.9 96.1 63.5 81.3 81.3 81.2 81.2 91.2 62.6
90 98.3 98.3 98.3 98.3 102.7 74.8 96.2 96.2 96.1 96.1 100.3 76.2 92.7 92.7 92.7 92.7 97.1 77.5 88.0 88.0 88.0 88.0 92.2 77.4
75 88.7 81.9 95.7 58.9 99.3 37.6 82.6 79.0 92.5 58.2 98.1 36.2 75.5 75.5 87.1 55.7 95.4 34.6 69.6 69.6 79.6 52.4 91.3 32.5
80 92.3 92.3 96.5 73.7 100.7 51.5 88.4 88.4 93.2 74.4 99.3 51.7 82.9 82.9 87.9 72.8 96.1 51.0 76.9 76.9 80.8 69.8 91.7 49.5
3300 85 96.5 96.5 97.8 88.4 102.0 63.9 93.8 93.8 94.8 90.3 100.0 65.0 89.8 89.8 89.8 89.8 96.9 65.8 84.4 84.4 84.4 84.4 92.3 65.5
90 99.7 99.7 99.7 99.7 103.3 76.5 98.0 98.0 98.0 98.0 101.1 78.5 94.9 94.9 94.9 94.9 98.1 80.6 90.7 90.7 90.7 90.7 93.5 81.3
75 90.2 85.7 96.4 60.6 99.7 38.1 84.6 83.6 93.3 60.0 98.5 36.8 77.9 77.9 88.2 58.1 96.0 35.2 71.8 71.8 80.9 55.0 92.0 33.2
80 94.0 94.0 97.2 75.8 101.0 52.1 90.7 90.7 94.3 77.4 99.7 52.6 85.6 85.6 89.2 76.6 96.6 52.0 79.5 79.5 82.3 73.8 92.5 51.5
3600 85 97.8 97.8 98.7 91.1 102.4 65.0 95.6 95.6 96.1 93.9 100.5 66.3 91.9 91.9 91.9 91.9 97.6 67.9 86.9 86.9 86.9 86.9 93.1 68.2
90 100.8 100.8 100.8 100.8 103.7 78.1 99.3 99.3 99.3 99.3 101.7 80.7 96.6 96.6 96.6 96.6 98.9 83.4 92.7 92.7 92.7 92.7 94.6 84.9
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

30 RT-PRC006-EN
Performance (8½ - 10 Ton)
Data Standard Efficiency

Table PD-8 — Gross Cooling Capacities (MBH) 8½ Ton Three Phase YSC102A3, A4, AW, AK
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 96.3 82.3 106.6 62.7 112.5 41.5 89.0 78.5 103.2 60.6 110.9 40.0 81.8 74.9 96.6 57.5 107.6 38.1 74.9 71.3 87.6 55.2 102.5 35.8
80 98.0 98.0 107.2 77.1 113.7 57.0 92.9 91.4 103.4 76.3 111.5 57.1 86.3 86.2 96.9 73.3 108.2 54.0 80.2 80.2 88.1 69.4 102.8 51.5
3060 85 103.9 103.9 108.1 91.7 114.8 69.6 100.1 100.1 104.3 91.7 112.4 70.0 94.3 94.3 98.3 89.5 108.6 68.9 87.6 87.6 89.9 85.7 103.1 67.1
90 108.6 108.6 109.6 105.7 116.0 82.4 105.9 105.9 105.9 105.9 113.2 83.0 101.6 101.6 101.9 100.2 109.3 83.4 95.6 95.6 95.6 95.5 103.6 82.3
75 98.7 87.2 107.8 65.9 113.0 42.0 91.8 83.8 104.7 63.7 111.8 40.7 84.2 80.0 98.7 60.5 108.6 38.9 76.3 76.3 89.6 58.6 103.7 36.5
80 101.6 100.0 108.5 80.1 114.6 58.1 96.9 96.5 105.0 80.1 112.8 57.8 90.3 90.3 99.1 77.9 109.3 56.3 83.8 83.8 90.3 74.0 104.0 53.8
3400 85 106.8 106.8 109.6 95.7 115.8 71.4 103.6 103.6 106.2 96.7 114.0 70.7 98.7 98.7 100.9 95.5 109.8 71.7 91.7 91.7 91.7 91.7 104.3 70.7
90 111.0 111.0 111.0 111.0 117.0 84.9 108.8 108.8 108.9 107.2 114.4 86.1 105.1 105.1 105.0 104.8 110.7 87.4 99.8 99.8 99.7 99.7 105.2 87.1
75 100.7 91.7 109.2 64.5 114.0 42.8 93.8 88.7 106.1 66.5 113.5 41.7 85.4 85.4 100.4 63.3 109.4 39.6 79.4 77.5 91.3 59.4 104.6 37.2
80 104.1 103.6 109.6 82.9 115.3 59.0 100.0 100.0 106.6 84.3 113.7 59.0 94.0 94.0 100.9 82.2 109.6 60.2 87.0 87.0 92.2 78.5 105.1 56.0
3740 85 108.9 108.9 110.9 99.2 116.6 73.0 106.7 106.7 108.3 102.4 114.8 74.4 102.0 102.0 102.0 102.0 110.8 74.3 95.6 95.6 96.4 93.7 105.5 73.9
90 112.8 112.8 112.8 112.8 117.8 87.2 111.8 111.8 111.8 111.2 116.0 90.0 107.7 107.7 107.7 107.7 111.9 90.9 102.9 102.9 102.9 102.9 106.6 91.4
75 102.3 95.8 110.2 66.1 114.6 43.5 95.2 95.2 106.7 68.3 113.1 42.2 88.2 88.2 101.6 65.9 110.1 40.3 81.6 80.6 92.7 62.1 105.3 38.1
80 106.2 106.2 110.5 85.3 115.9 59.8 102.8 102.8 107.4 86.8 114.3 60.0 97.4 97.4 102.4 86.2 111.0 58.6 89.9 89.9 94.1 82.9 105.9 58.2
4080 85 110.5 110.5 111.9 102.3 117.2 74.4 108.3 108.3 109.2 105.1 115.5 76.3 104.5 104.5 104.4 104.4 111.5 77.2 98.7 98.7 99.0 97.4 106.4 76.8
90 114.2 114.2 114.2 114.2 118.5 89.3 112.7 112.7 112.7 112.7 116.8 92.7 109.7 109.7 109.7 109.7 112.9 94.2 105.2 105.2 105.2 105.2 107.8 95.4
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table PD-9— Gross Cooling Capacities (MBH) 10 Ton Three Phase YSC120A3, A4, AW, AK
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 108.6 95.7 120.5 71.5 126.0 46.0 100.1 91.3 115.5 68.8 123.6 43.3 91.0 86.5 107.2 64.9 119.3 41.0 82.2 82.0 96.5 60.1 113.1 37.9
80 112.8 112.8 121.2 89.2 127.5 65.7 106.3 106.3 116.1 88.1 124.8 62.8 98.5 98.5 108.2 84.5 120.1 60.5 90.5 90.5 97.8 79.7 113.6 57.4
3600
85 119.5 119.5 122.6 106.9 129.0 78.5 114.8 114.8 117.7 107.0 126.2 79.2 108.2 108.2 110.5 104.5 121.8 76.8 100.1 100.1 100.1 100.1 114.2 76.6
90 124.3 124.3 124.6 123.6 130.4 93.6 121.0 121.0 121.0 121.0 127.6 95.7 116.0 116.0 116.0 116.0 122.0 95.1 109.4 109.4 109.4 109.4 115.3 94.5
75 111.6 102.3 121.7 73.9 126.7 46.9 103.4 98.1 117.1 72.3 124.5 42.7 94.2 93.4 109.5 68.7 120.2 41.9 85.3 85.3 98.8 64.0 114.3 38.8
80 116.7 116.7 122.6 92.7 128.2 64.5 111.1 111.1 118.0 93.0 125.7 64.2 103.4 103.4 110.8 90.4 121.4 63.2 95.0 95.0 100.6 85.8 114.9 60.3
4000
85 122.3 122.3 124.2 111.4 129.7 80.2 118.5 118.5 120.0 113.1 127.1 81.6 112.8 112.8 113.6 112.1 122.6 82.1 105.1 105.1 105.1 105.1 115.6 80.4
90 126.9 126.9 126.4 126.4 131.3 96.0 123.7 123.7 123.7 123.7 128.7 99.0 119.3 119.3 119.3 119.3 124.1 100.7 113.4 113.4 113.4 113.4 117.1 100.0
75 114.1 108.4 122.5 75.8 127.3 47.7 106.5 104.9 118.4 75.8 124.9 45.4 97.1 97.1 111.3 72.3 121.3 40.2 88.6 88.6 100.9 67.7 115.1 39.7
80 119.5 119.5 123.8 96.1 128.9 65.5 114.7 114.7 119.5 97.3 126.3 69.2 107.7 107.7 112.9 95.9 122.2 64.9 99.0 99.0 103.1 91.7 115.8 63.2
4400
85 124.9 124.9 125.5 115.5 130.4 81.9 121.1 121.1 121.8 118.3 127.9 83.7 116.0 116.0 116.0 116.0 123.6 85.0 109.2 109.2 109.2 109.2 116.8 84.0
90 127.9 127.9 128.0 128.0 132.0 98.3 126.1 126.1 125.6 125.6 129.5 101.8 121.7 121.7 121.7 121.7 125.3 104.7 116.2 116.2 116.2 116.2 118.5 104.7
75 116.1 113.8 123.1 77.6 127.8 48.5 108.9 108.9 119.2 78.1 125.4 46.2 100.5 100.5 112.8 76.1 121.4 43.6 91.6 91.6 102.6 71.3 115.8 40.6
80 121.4 121.4 124.5 98.6 129.4 66.4 117.3 117.3 120.8 101.1 126.9 66.5 111.1 111.1 114.6 100.9 122.9 66.4 102.5 102.5 105.4 97.5 116.5 65.7
4800
85 126.0 126.0 126.4 118.6 130.9 83.4 122.9 122.9 123.2 122.6 128.5 85.6 118.4 118.4 118.4 118.4 124.3 87.5 112.1 112.1 112.1 112.1 117.8 87.3
90 129.1 129.1 129.1 129.1 132.5 100.4 127.2 127.2 126.9 126.9 130.2 104.4 124.0 124.0 123.7 123.7 126.2 108.0 118.2 118.2 118.2 118.2 119.7 108.9
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

RT-PRC006-EN 31
Performance (3 - 4 Tons)
Data High Efficiency

Table PD-10 — Gross Cooling Capacities (MBH) 3-on YHC036A1, A3, A4, AW
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 34.2 29.2 39.8 22.7 43.1 15.2 31.1 27.4 37.0 21.2 41.3 14.1 28.0 25.7 33.3 19.8 39.0 12.9 24.8 24.0 29.8 18.1 36.1 11.6
80 34.9 34.9 40.0 28.5 43.5 21.3 32.3 32.3 37.1 27.1 41.6 20.1 29.7 29.7 33.5 25.3 39.2 18.8 27.1 27.1 30.0 23.6 36.2 17.5
1080
85 37.9 37.9 40.3 34.3 44.0 26.5 35.3 35.3 37.5 33.0 41.9 25.6 32.6 32.6 34.0 31.3 39.5 24.6 30.0 30.0 30.6 29.6 36.4 23.2
90 40.5 40.5 40.9 40.0 44.5 31.7 38.4 38.4 38.4 38.4 42.3 31.0 35.7 35.7 35.7 35.7 39.7 30.3 32.9 32.9 32.9 32.9 36.7 29.0
75 35.3 31.2 40.4 23.7 43.5 15.5 32.0 29.4 37.8 22.4 41.8 14.4 28.8 27.7 34.1 20.6 39.5 13.2 25.5 25.5 30.5 18.8 36.7 11.9
80 36.7 36.7 40.7 30.0 44.0 21.9 33.9 33.9 38.0 28.9 42.1 20.9 31.2 31.2 34.4 27.1 39.8 19.7 28.5 28.5 30.8 25.3 36.9 18.4
1200
85 39.6 39.6 41.1 36.3 44.6 27.4 37.1 37.1 38.5 35.4 42.5 26.8 34.3 34.3 35.1 33.8 40.0 26.0 31.5 31.5 31.5 31.5 37.1 24.8
90 41.9 41.9 41.9 41.9 45.1 33.0 39.9 39.9 39.9 39.9 42.9 32.6 37.6 37.6 37.6 37.6 40.4 32.1 34.7 34.7 34.7 34.7 37.4 31.1
75 36.2 33.2 40.9 24.7 43.8 15.8 32.8 31.4 38.4 23.4 42.1 14.7 29.4 29.4 34.8 21.7 39.9 13.5 26.5 26.5 31.0 19.9 37.2 12.2
80 38.2 38.2 41.2 31.4 44.4 22.4 35.4 35.4 38.7 30.5 42.6 21.7 32.5 32.5 35.2 28.9 40.2 20.5 29.7 29.7 31.5 27.1 37.4 19.2
1320
85 40.8 40.8 41.8 38.1 45.0 28.3 38.7 38.7 39.4 37.6 43.1 28.0 35.9 35.9 36.2 36.2 40.5 27.2 32.9 32.9 32.9 32.9 37.6 26.2
90 42.9 42.9 42.9 42.9 45.6 34.2 41.1 41.1 41.1 41.1 43.4 34.0 38.9 38.9 38.9 38.9 41.0 33.8 36.3 36.3 36.3 36.3 38.1 33.1
75 37.1 35.1 41.3 25.5 44.1 16.1 33.6 33.3 38.9 24.4 42.4 15.0 30.4 30.4 35.5 22.8 40.2 13.8 27.5 27.5 31.5 21.0 37.5 12.5
80 39.4 39.4 41.7 32.6 44.7 22.9 36.8 36.8 39.3 32.1 42.9 22.3 33.8 33.8 35.9 30.6 40.6 21.4 30.8 30.8 32.1 28.8 37.8 20.1
1440
85 41.7 41.7 42.4 39.7 45.3 29.0 39.8 39.8 40.1 39.5 43.5 29.0 37.3 37.3 37.3 37.3 40.9 28.3 34.2 34.2 34.2 34.2 38.0 27.6
90 43.7 43.7 43.7 43.7 45.9 35.3 42.1 42.1 42.1 42.1 43.9 35.3 40.0 40.0 40.0 40.0 41.5 35.4 37.5 37.5 37.5 37.5 38.6 34.9
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table PD-11— Gross Cooling Capacities (MBH) 4-Ton YHC048A1, A3, A4, AW
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 45.3 39.9 51.4 30.3 54.9 19.9 41.1 37.7 48.4 28.8 53.1 18.7 37.1 35.6 43.9 26.7 51.0 17.4 33.2 33.2 39.3 24.6 47.8 16.0
80 47.1 47.1 52.0 38.4 55.5 28.1 43.8 43.8 48.7 36.9 54.6 27.2 40.3 40.3 44.3 34.9 51.3 25.6 36.9 36.9 39.8 32.8 47.9 24.1
1440
85 50.5 50.5 52.5 46.3 56.2 34.5 47.8 47.8 49.4 45.2 54.9 34.9 44.3 44.3 45.3 43.3 51.6 33.6 40.9 40.9 40.9 40.9 48.1 32.2
90 53.1 53.1 53.5 53.5 56.9 41.4 51.2 51.2 51.2 51.2 54.6 41.4 48.4 48.4 48.4 48.4 52.0 41.2 45.0 45.0 45.0 45.0 48.6 40.2
75 46.7 42.7 52.7 31.9 55.2 20.2 42.4 40.5 49.4 30.3 54.4 19.3 38.2 38.2 45.0 28.4 51.6 17.8 34.7 34.7 40.2 26.2 48.6 16.4
80 49.2 49.2 52.8 40.4 55.9 28.2 46.0 46.0 49.8 39.4 55.2 28.4 42.3 42.3 45.6 37.5 51.9 26.9 38.7 38.7 40.9 35.3 48.7 25.4
1600
85 52.1 52.1 53.5 48.8 56.6 35.4 49.9 49.9 50.6 48.3 55.7 36.8 46.7 46.7 47.0 46.8 52.2 35.2 43.0 43.0 42.9 42.9 49.0 34.3
90 54.5 54.5 54.8 54.8 57.4 42.7 52.8 52.8 52.8 52.8 55.2 42.9 50.5 50.5 50.5 50.5 52.9 43.5 47.4 47.4 47.4 47.4 49.6 43.0
75 47.8 45.4 53.2 33.4 55.5 20.6 43.7 43.3 50.1 31.8 54.7 19.6 39.7 39.7 46.0 30.0 51.9 18.2 36.1 36.1 41.0 27.7 49.1 16.8
80 50.6 50.6 53.4 42.1 56.2 28.7 47.8 47.8 50.5 41.5 55.7 29.4 44.1 44.1 46.7 39.9 52.4 28.1 40.4 40.4 41.9 37.8 49.3 26.7
1760
85 53.1 53.1 54.2 50.9 57.0 36.2 51.4 51.4 51.6 51.0 56.2 38.0 48.6 48.6 48.6 48.6 52.8 36.7 44.9 44.9 44.9 44.9 49.7 36.3
90 55.1 55.1 55.7 55.7 57.7 43.8 53.9 53.9 53.9 53.9 55.6 44.3 51.9 51.9 51.9 51.9 53.5 45.6 49.2 49.2 49.2 49.2 50.5 45.7
75 48.8 48.1 53.6 34.4 55.7 20.9 45.0 45.0 50.6 33.2 55.0 20.0 41.0 41.0 46.8 31.5 52.3 18.5 37.3 37.3 41.7 29.3 49.6 17.2
80 51.7 51.7 53.9 43.5 56.4 31.7 49.3 49.3 51.2 43.5 56.0 30.1 45.8 45.8 47.6 42.3 52.8 28.9 41.8 41.8 42.8 40.2 49.8 27.9
1920
85 53.9 53.9 54.8 52.7 57.2 36.9 52.4 52.4 52.4 52.4 56.5 39.1 50.0 50.0 50.0 50.0 53.2 38.1 46.6 46.6 46.6 46.6 50.3 38.1
90 55.7 55.7 56.3 56.3 58.0 44.8 54.7 54.7 54.7 54.7 56.0 45.6 53.0 53.0 53.0 53.0 54.0 47.4 50.5 50.5 50.5 50.5 51.2 48.1
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

32 RT-PRC006-EN
Performance (5 Ton)
Data High Efficiency

Table PD-12 — Gross Cooling Capacities (MBH) 5-Ton Single Phase YHC060A1
AmbientTemperature (F)
85 95
105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 56.2 48.2 64.3 37.8 68.4 24.8 51.4 45.6 60.5 35.2 66.7 23.5 46.8 43.2 55.3 32.8 63.9 21.9 42.2 40.8 50.0 31.0 59.9 20.1
80 57.6 57.6 64.6 46.6 69.3 34.7 53.7 53.7 60.7 44.8 67.3 33.1 49.8 49.8 55.5 42.3 64.2 31.5 45.9 45.9 50.5 39.9 60.1 29.6
1800
85 62.2 62.2 65.2 55.8 70.1 42.6 58.4 58.4 61.4 54.5 68.0 42.2 54.5 54.5 56.5 52.0 64.6 40.9 50.6 50.6 51.6 49.7 60.3 39.0
90 65.8 65.8 66.3 64.9 70.9 50.8 63.0 63.0 63.0 63.0 68.2 52.0 59.3 59.3 59.2 59.2 65.0 49.9 55.3 55.3 55.3 55.3 60.7 48.5
75 57.8 51.4 65.2 38.8 69.6 25.4 52.9 48.8 61.8 37.0 67.3 23.9 48.2 46.3 56.5 34.6 64.6 22.4 43.3 43.3 51.2 32.1 60.9 20.7
80 60.3 60.3 65.6 48.8 69.8 35.2 56.2 56.2 62.1 47.6 68.0 34.6 52.1 52.1 56.9 45.1 65.0 32.9 48.1 48.1 51.7 42.7 61.2 31.1
2000
85 64.4 64.4 66.3 58.7 70.7 43.8 61.2 61.2 63.0 58.1 68.7 43.9 57.1 57.1 58.2 56.0 65.4 42.8 53.0 53.0 53.0 53.0 61.4 41.5
90 67.6 67.6 67.6 67.6 71.6 52.5 65.2 65.2 65.2 65.2 69.5 53.3 62.0 62.0 62.0 62.0 66.0 52.6 58.0 58.0 58.0 58.0 62.0 51.8
75 59.4 54.5 65.7 40.1 69.3 25.6 54.3 51.9 62.7 38.7 67.7 24.3 49.6 49.4 57.6 36.3 65.1 22.8 45.0 45.0 52.2 33.8 61.6 21.1
80 62.4 62.4 66.3 50.7 70.3 35.8 58.4 58.4 63.1 50.1 68.5 35.4 54.2 54.2 58.2 47.9 65.7 34.2 50.0 50.0 52.9 45.4 61.9 32.5
2200
85 66.0 66.0 67.3 61.2 71.2 44.8 63.3 63.3 64.2 61.3 69.4 45.3 59.4 59.4 59.9 59.8 66.1 44.6 55.2 55.2 55.2 55.2 62.2 43.7
90 68.9 68.9 68.9 68.9 72.2 54.0 66.9 66.9 66.9 66.9 70.2 55.4 64.0 64.0 64.0 64.0 66.8 55.1 60.4 60.4 60.4 60.4 63.0 54.6
75 60.6 57.4 66.1 41.5 69.7 26.0 55.6 54.9 63.4 40.3 68.1 24.7 50.8 50.8 58.5 38.0 65.5 23.2 46.5 46.5 53.0 35.5 62.1 21.5
80 64.0 64.0 67.0 52.5 70.6 38.5 60.4 60.4 63.9 52.4 69.0 36.1 56.1 56.1 59.2 50.5 66.1 35.8 51.8 51.8 54.0 48.1 62.5 33.8
2400
85 67.2 67.2 68.0 63.5 71.5 50.9 64.9 64.9 65.3 64.2 69.9 46.6 61.4 61.4 61.4 61.4 67.0 46.8 57.2 57.2 57.2 57.2 62.9 45.6
90 69.8 69.8 69.8 69.8 72.6 55.3 68.1 68.1 68.1 68.1 70.8 57.1 65.5 65.5 65.5 65.5 67.5 57.3 62.2 62.2 62.2 62.2 63.9 57.2
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table PD-13 — Gross Cooling Capacities (MBH) 5-Ton Three Phase YHC060A3, A4, AW
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 56.6 49.0 64.4 37.5 67.7 24.7 52.0 46.8 60.9 35.7 66.2 23.3 47.0 44.2 55.9 33.3 63.6 21.8 42.3 41.7 50.0 30.7 59.8 20.0
1800 80 58.5 58.5 64.6 47.0 68.6 34.7 54.7 54.7 61.2 45.5 66.8 33.3 50.6 50.6 56.3 43.2 64.1 31.7 46.4 46.4 50.5 40.5 60.0 29.8
85 62.9 62.9 65.3 56.4 69.4 42.2 59.6 59.6 61.9 55.5 67.7 42.3 55.6 55.6 57.3 53.2 64.3 41.1 51.2 51.2 51.9 50.7 60.3 39.5
90 66.2 66.2 66.4 65.6 70.3 50.3 63.7 63.7 63.7 63.7 68.4 51.2 60.3 60.3 60.3 60.3 64.9 50.3 56.4 56.4 56.3 56.3 60.8 49.1
75 58.3 52.5 65.0 39.1 68.1 25.1 53.6 50.0 62.0 37.6 66.6 23.8 48.6 47.7 57.2 35.4 64.2 22.3 43.8 43.8 51.2 32.7 60.6 20.5
2000 80 61.1 61.1 65.6 49.2 69.0 34.6 57.3 57.3 62.4 48.4 67.5 34.8 53.2 53.2 57.8 46.2 64.7 33.2 48.7 48.7 52.0 43.6 60.9 31.4
85 64.9 64.9 66.4 59.2 69.9 43.1 62.1 62.1 63.4 59.1 67.8 43.0 58.4 58.4 59.2 57.5 64.9 43.9 54.0 54.0 54.0 54.0 61.2 42.0
90 67.7 67.7 67.7 67.7 70.8 51.7 65.7 65.7 65.7 65.7 68.6 52.2 62.8 62.8 62.8 62.8 65.9 52.9 59.0 59.0 59.0 59.0 61.9 52.3
75 59.9 55.8 65.8 40.7 68.4 25.5 55.2 53.4 62.9 39.5 67.0 24.2 50.0 50.0 58.3 37.3 64.6 22.7 45.6 45.6 52.4 34.7 61.2 21.0
2200 80 63.1 63.1 66.3 51.0 69.3 35.2 59.7 59.7 63.5 51.0 67.9 35.1 55.5 55.5 59.0 49.2 65.4 34.5 50.8 50.8 53.4 46.6 61.6 32.9
85 66.4 66.4 67.2 61.6 70.2 43.9 64.0 64.0 64.6 62.4 68.8 44.9 60.6 60.6 60.6 60.6 66.0 45.1 56.4 56.4 56.4 56.4 62.0 44.2
90 68.7 68.7 68.7 68.7 71.2 52.8 67.1 67.1 67.1 67.1 69.7 54.9 64.5 64.5 64.5 64.5 66.9 55.8 61.0 61.0 61.0 61.0 62.9 55.3
75 61.2 59.0 66.2 41.7 68.6 25.9 56.3 56.3 63.6 41.3 67.3 24.6 51.9 51.9 59.2 39.0 65.0 23.1 47.2 47.2 53.4 36.6 61.7 21.4
2400 80 64.5 64.5 67.0 53.1 69.6 35.6 61.6 61.6 64.2 53.3 68.2 35.7 57.5 57.5 60.1 52.1 65.8 35.5 52.8 52.8 54.7 49.6 62.1 34.3
85 67.3 67.3 68.1 64.0 70.5 44.7 65.4 65.4 65.6 65.2 69.1 46.0 62.4 62.4 62.3 62.3 66.6 46.8 58.4 58.4 58.4 58.4 62.6 46.2
90 69.4 69.4 69.5 69.5 71.5 53.9 68.1 68.1 68.1 68.1 70.1 56.3 65.7 65.7 65.7 65.7 67.6 58.0 62.5 62.5 62.5 62.5 63.7 57.9
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

RT-PRC006-EN 33
Performance (6 - 7½ Ton)
Data High Efficiency

Table PD-14 — Gross Cooling Capacities (MBH) 6-Ton Three Phase YHC072A3,A4,AW
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 67.3 56.6 73.6 42.5 74.5 27.6 61.6 53.5 71.8 41.9 75.1 26.6 55.8 50.4 66.8 38.7 74.1 25.3 49.8 47.2 59.9 36.3 71.3 23.5
80 68.7 68.2 73.8 51.7 75.4 37.0 63.6 63.6 72.0 52.1 76.0 38.1 58.9 58.9 66.9 49.7 74.7 36.4 54.1 54.1 60.2 46.5 71.5 34.5
2160 85 72.2 72.2 74.5 61.4 76.2 44.5 69.2 69.2 72.5 62.8 76.8 46.1 64.6 64.6 67.8 60.9 75.0 46.2 59.5 59.5 61.3 57.7 71.7 45.4
90 74.7 74.7 75.3 70.6 77.0 51.9 73.4 73.4 73.7 73.2 77.7 55.1 70.1 70.1 70.1 70.1 75.6 56.1 65.4 65.4 65.4 65.4 72.1 55.8
75 69.0 60.1 74.0 43.3 74.5 27.9 63.5 57.2 72.7 43.1 75.2 27.0 57.5 54.0 68.4 40.9 74.5 25.7 51.8 51.0 61.5 37.6 72.0 24.0
80 70.7 70.7 74.3 52.9 75.4 37.2 66.8 66.8 73.0 54.6 76.2 37.8 61.9 61.9 68.7 53.0 75.1 37.4 56.7 56.7 61.9 49.8 72.4 36.1
2400 85 73.8 73.8 75.0 63.0 76.2 44.9 71.9 71.9 73.8 66.0 77.1 47.0 67.9 67.9 69.7 65.4 75.5 47.5 62.7 62.7 63.6 62.4 72.6 47.7
90 75.6 75.6 75.9 72.4 77.0 52.5 75.2 75.2 75.1 75.1 78.0 56.3 72.8 72.8 72.7 72.7 76.4 58.2 68.8 68.8 68.8 68.8 73.2 59.0
75 70.3 63.2 74.2 43.9 74.6 28.3 65.2 60.8 73.2 44.5 75.4 27.4 59.2 57.7 69.6 42.9 74.7 26.2 53.2 53.2 62.9 39.8 72.5 24.6
80 72.3 72.3 74.5 53.9 75.4 37.4 69.5 69.5 73.8 56.7 76.3 38.2 64.6 64.6 70.0 56.1 75.6 38.5 59.2 59.2 63.5 53.0 73.0 37.7
2640 85 74.7 74.7 75.3 64.3 76.2 45.2 73.7 73.7 74.7 68.7 77.3 47.6 70.5 70.5 71.3 69.3 76.1 48.9 65.6 65.6 65.6 65.6 73.4 49.7
90 76.1 76.1 76.2 73.6 76.9 53.0 76.2 76.2 76.2 76.2 78.1 57.2 74.5 74.5 74.5 74.5 76.9 59.9 71.2 71.2 71.2 71.2 74.1 61.7
75 71.3 65.8 74.3 44.4 74.6 28.7 66.8 64.4 73.7 45.6 75.5 27.8 60.5 60.5 70.6 44.8 74.9 26.6 55.1 55.1 64.1 41.8 72.9 25.0
80 73.3 73.3 74.7 54.8 75.4 37.6 71.4 71.4 74.4 58.5 76.4 38.5 67.0 67.0 71.0 58.9 75.9 39.1 61.4 61.4 64.9 56.2 73.3 38.6
2880 85 75.1 75.1 75.5 65.3 76.2 45.6 74.8 74.8 75.4 70.8 77.4 48.2 72.4 72.4 72.4 72.4 76.4 49.9 68.2 68.2 68.1 68.1 74.0 51.5
90 76.3 76.3 76.3 74.5 76.9 53.5 76.9 76.9 76.9 76.9 78.2 58.0 75.7 75.7 75.7 75.7 77.2 61.3 72.9 72.9 72.9 72.9 74.8 64.1
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table PD-15 — Gross Cooling Capacities (MBH) 7½-Ton Dual Compressors Three Phase YHC092A3,A4,AW
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 85.7 72.4 95.8 56.8 99.9 37.1 79.3 69.3 92.0 53.7 98.8 35.8 72.8 66.0 85.9 50.8 96.1 34.2 66.1 62.6 78.5 49.1 91.8 32.2
80 87.5 87.0 96.2 68.5 101.1 50.4 81.8 81.8 92.4 67.4 99.6 50.2 76.6 76.6 86.2 64.6 96.7 48.0 71.1 71.1 79.0 61.4 92.0 45.8
2700 85 92.8 92.8 97.0 81.6 102.3 61.3 88.5 88.5 93.1 81.1 100.3 61.3 83.4 83.4 87.1 78.6 97.0 60.9 77.9 77.9 80.3 75.4 92.3 59.4
90 97.2 97.2 98.3 94.2 103.5 72.4 94.3 94.3 94.3 94.3 101.1 73.1 90.0 90.0 90.0 90.0 97.8 73.7 84.9 84.9 84.9 84.9 92.9 72.7
75 87.9 77.0 96.6 57.3 100.4 37.6 81.5 73.7 93.5 56.1 99.4 36.4 74.9 70.5 87.8 53.4 96.9 34.8 67.4 67.4 80.5 50.2 92.8 32.8
80 90.5 90.5 97.4 71.2 101.6 51.1 85.6 85.6 94.0 71.0 100.4 50.9 80.2 80.2 88.2 68.7 97.3 49.8 74.5 74.5 81.0 65.5 93.2 47.9
3000 85 95.6 95.6 98.4 85.1 102.9 62.5 92.2 92.2 95.0 85.8 101.3 63.3 87.3 87.3 89.5 84.1 98.1 63.3 81.8 81.8 82.9 81.2 93.6 62.5
90 99.4 99.4 99.9 98.1 104.1 74.1 97.2 97.2 97.2 97.2 102.1 75.5 93.6 93.6 93.5 93.5 99.1 77.0 88.8 88.8 88.7 88.7 94.4 76.9
75 89.8 81.3 97.5 59.0 100.7 38.1 83.6 78.2 94.6 58.3 99.8 37.1 77.0 75.0 89.2 55.9 97.5 35.4 70.0 70.0 82.1 52.8 93.6 33.4
80 93.2 93.2 98.3 73.5 102.0 51.7 88.9 88.9 95.2 74.2 101.0 52.0 83.4 83.4 89.8 72.6 97.9 50.6 77.6 77.6 82.8 69.5 94.1 49.9
3300 85 97.6 97.6 99.4 88.0 103.3 67.9 94.9 94.9 96.5 90.0 101.9 64.8 90.5 90.5 91.7 89.4 99.0 67.3 85.2 85.2 85.1 85.1 94.7 65.2
90 100.9 100.9 100.9 100.9 104.6 75.6 99.2 99.2 99.2 99.2 102.8 77.7 96.1 96.1 96.1 96.1 100.1 80.0 91.8 91.8 91.8 91.8 95.7 80.7
75 91.5 85.3 98.2 60.6 101.0 38.6 85.5 82.6 95.4 60.2 100.2 37.5 78.5 78.5 90.5 58.3 98.0 35.9 72.4 72.4 83.4 55.2 94.3 34.0
80 95.2 95.2 99.0 75.4 102.3 56.8 91.5 91.5 96.3 77.2 101.5 52.7 86.3 86.3 91.3 76.3 98.4 51.4 80.4 80.4 84.4 73.4 94.7 51.4
3600 85 99.1 99.1 100.2 90.6 103.6 69.8 96.9 96.9 97.8 93.6 102.4 66.1 93.1 93.1 93.1 93.1 99.7 69.8 88.0 88.0 87.9 87.9 95.6 67.8
90 101.9 101.9 101.9 101.9 105.0 76.9 100.7 100.7 100.7 100.7 103.4 79.6 98.0 98.0 97.9 97.9 100.8 82.5 94.0 94.0 94.0 94.0 96.7 84.1
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

34 RT-PRC006-EN
Performance (8½ - 10 Ton)
Data High Efficiency

Table PD-16 — Gross Cooling Capacities (MBH) 8½-Ton Three Phase YHC102A3,A4,AW
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 94.0 81.8 105.7 62.8 110.8 40.9 86.3 77.8 100.7 59.7 109.7 39.3 79.0 74.2 92.4 56.0 105.5 37.1 71.8 70.5 84.0 53.1 99.6 34.6
80 96.9 96.9 106.2 77.6 112.0 56.0 90.6 90.6 101.1 75.9 110.1 55.4 84.5 84.5 92.9 72.2 106.1 53.2 78.3 78.3 84.7 68.5 99.8 50.6
3060 85 103.5 103.5 107.2 92.9 113.2 68.7 98.6 98.6 102.2 92.1 111.6 70.3 92.1 92.1 94.5 88.8 106.4 68.8 85.8 85.8 86.7 85.2 100.0 66.5
90 108.4 108.4 109.0 107.7 114.4 81.6 105.0 105.0 105.0 105.0 112.6 84.9 99.9 99.9 99.9 99.9 107.3 83.9 93.5 93.5 93.5 93.5 100.8 82.6
75 96.6 87.2 107.1 64.7 111.4 41.5 88.7 83.3 102.4 62.6 110.7 40.1 81.4 79.6 94.4 59.1 106.6 37.9 74.2 74.2 85.9 55.4 101.1 35.5
80 100.9 100.9 107.7 81.0 112.7 56.9 94.9 94.9 103.0 80.4 111.7 57.5 88.3 88.3 95.2 77.1 107.3 55.7 81.8 81.8 86.8 73.4 101.4 53.1
3400 85 106.6 106.6 108.9 97.4 114.0 70.2 102.6 102.6 104.4 97.8 112.8 72.9 96.5 96.5 97.6 95.6 108.0 72.4 89.9 89.9 89.8 89.8 101.8 70.8
90 110.8 110.8 110.8 110.8 115.3 83.8 108.1 108.1 108.1 108.1 114.0 88.5 103.8 103.8 103.8 103.8 108.9 88.3 97.8 97.8 97.8 97.8 102.8 87.9
75 98.9 92.5 107.4 65.9 112.0 42.2 91.2 88.7 103.7 65.4 111.1 40.7 83.5 83.5 96.3 62.2 107.5 38.7 76.9 76.9 87.5 58.4 102.2 36.2
80 103.7 103.7 108.8 84.0 113.3 57.7 98.7 98.7 104.5 84.5 112.4 58.7 91.7 91.7 97.3 81.9 108.3 57.6 85.0 85.0 88.8 78.2 102.6 55.5
3740 85 108.8 108.8 110.1 100.9 114.6 76.9 105.4 105.4 106.4 103.0 113.7 75.1 100.2 100.2 100.2 100.2 109.3 75.7 93.4 93.4 93.4 93.4 103.1 74.4
90 112.3 112.3 112.1 112.1 115.9 85.7 110.4 110.4 110.4 110.4 114.9 91.4 106.5 106.5 106.5 106.5 110.2 92.3 101.3 101.3 101.3 101.3 104.4 92.7
75 100.9 97.3 108.1 67.4 112.5 42.9 93.1 93.1 104.7 67.9 111.5 41.4 86.2 86.2 97.8 65.2 108.2 39.4 79.4 79.4 88.8 61.3 103.0 36.9
80 105.9 105.9 109.5 86.2 113.8 58.4 101.6 101.6 105.8 88.2 112.8 59.6 94.9 94.9 99.1 86.5 109.2 59.6 87.9 87.9 90.6 82.8 103.5 57.8
4080 85 110.2 110.2 110.9 103.4 115.1 79.5 107.6 107.6 107.6 107.6 114.1 76.6 103.0 103.0 103.0 103.0 109.9 77.6 96.6 96.6 96.6 96.6 104.2 77.7
90 112.9 112.9 112.9 112.9 116.5 87.5 112.2 112.2 112.2 112.2 115.4 93.4 108.6 108.6 108.6 108.6 111.3 95.9 103.9 103.9 103.9 103.9 105.8 97.0
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table PD-17 — Gross Cooling Capacities (MBH) 10-Ton Three Phase YHC120A3,A4,AW
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 107.0 94.4 117.4 75.0 123.4 46.0 98.7 90.1 114.7 68.8 121.9 44.4 88.5 88.5 107.2 65.3 118.6 42.2 82.3 78.8 97.8 61.1 113.6 39.6
3600 80 110.9 108.6 119.9 88.2 125.0 62.5 104.5 104.1 115.2 87.5 123.4 62.3 97.7 97.7 107.8 84.3 119.4 60.8 90.6 90.6 98.5 80.1 114.3 58.3
85 117.6 117.6 120.9 105.0 126.6 76.7 113.1 113.1 116.5 105.8 124.9 78.1 106.9 106.9 107.0 107.0 120.9 78.1 99.9 99.9 100.0 100.0 114.8 76.5
90 122.5 122.5 122.4 122.4 128.2 91.1 119.6 119.6 119.6 117.1 126.4 94.1 115.0 115.0 114.7 114.6 121.6 94.3 109.0 109.0 109.0 109.0 115.8 94.3
75 109.8 100.5 119.4 71.9 122.5 46.5 99.7 99.7 116.1 71.5 121.7 45.0 92.5 92.5 110.1 69.1 119.4 43.0 85.6 83.4 100.9 65.0 114.6 40.5
4000 80 114.6 114.1 120.8 90.1 124.1 68.3 109.3 109.3 117.0 91.2 123.4 62.7 102.3 102.3 110.8 89.9 120.6 62.5 94.8 94.8 101.9 86.0 115.5 61.1
85 120.5 120.5 122.3 107.9 125.9 76.4 117.0 117.0 118.6 110.2 125.0 78.8 111.6 111.6 111.8 111.8 122.1 80.4 104.7 104.7 105.8 102.6 116.3 79.7
90 125.2 125.2 124.2 124.2 127.6 90.9 122.4 122.4 121.7 120.9 126.6 95.1 118.5 118.5 118.3 118.3 123.6 98.4 113.1 113.1 113.3 113.3 117.7 98.6
75 112.3 106.1 121.2 74.8 124.6 47.6 103.6 103.6 117.1 75.5 123.0 46.0 96.7 93.9 111.2 72.2 120.0 43.7 88.6 88.0 102.0 68.2 115.3 41.2
4400 80 117.6 117.6 122.5 94.7 126.3 64.2 113.0 113.0 118.4 95.8 124.7 64.4 106.3 106.3 112.2 94.9 121.5 64.3 98.8 98.8 103.5 91.1 116.1 62.8
85 122.4 122.4 124.3 113.8 128.0 79.6 119.6 119.6 119.6 119.6 126.4 81.8 115.1 115.1 115.5 111.7 122.7 83.0 109.1 109.1 108.8 107.4 117.2 83.2
90 126.0 126.0 127.1 125.0 129.6 95.2 124.3 124.3 124.2 124.2 128.0 99.4 120.9 120.9 120.9 120.9 123.9 101.2 116.1 116.1 116.1 116.1 118.8 103.3
75 113.4 113.4 121.8 76.2 125.0 48.4 107.6 104.0 118.5 77.0 123.5 46.9 99.6 98.2 112.7 75.4 120.5 44.8 91.6 91.6 103.7 71.6 115.9 41.9
4800 80 119.5 119.5 123.2 97.0 126.7 64.8 115.8 115.8 119.8 99.6 125.2 65.3 109.8 109.8 113.9 99.4 122.1 65.5 102.3 102.3 105.5 96.3 117.2 66.8
85 124.3 124.3 125.2 116.6 128.4 80.7 121.5 121.5 121.5 121.5 126.9 83.3 117.5 117.5 117.6 115.4 123.7 85.6 111.8 111.8 111.8 111.8 118.5 86.4
90 127.5 127.5 128.0 126.7 130.1 96.9 126.0 126.0 125.5 125.5 128.6 101.5 122.6 122.6 123.0 123.0 125.5 105.5 118.2 118.2 118.2 118.2 120.3 107.5
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

RT-PRC006-EN 35
Performance (3 - 5 Tons)
Data Standard Efficiency

Table PD-18 — Direct Drive Evaporator Fan Performance 3, 4 , and 5 Ton YSC036A, YSC048A, YSC060A — Low and
Medium Heat
External Static Pressure (Inches of Water) & Motor Power (Bhp)1
Standard Motor Oversized Motor2
High Speed Low Speed High Speed Low Speed
Unit
Tons Model No. CFM ESP BHP ESP BHP ESP BHP ESP BHP
960 0.81 0.36 0.61 0.28 0.96 0.39 0.89 0.35
1020 0.77 0.37 0.57 0.28 0.94 0.41 0.86 0.47
1080 0.73 0.38 0.50 0.29 0.91 0.43 0.82 0.39
1140 0.69 0.39 0.42 0.29 0.88 0.44 0.77 0.40
3 YSC036A**L,M 1200 0.66 0.40 0.34 0.30 0.84 0.45 0.74 0.41
Horizontal Airflow 1260 0.60 0.41 0.26 0.30 0.80 0.46 0.70 0.42
1320 0.55 0.42 0.14 0.31 0.75 0.48 0.65 0.44
1380 0.49 0.42 0.05 0.31 0.70 0.49 0.59 0.45
1440 0.44 0.43 — — 0.64 0.52 0.54 0.48
1280 0.88 0.53 0.76 0.47 1.15 0.67 0.94 0.56
1360 0.82 0.54 0.70 0.47 1.10 0.68 0.89 0.58
1440 0.75 0.54 0.63 0.48 1.05 0.70 0.83 0.60
1520 0.68 0.55 0.55 0.48 1.00 0.73 0.76 0.63
YSC048A**L,M 1600 0.61 0.55 0.46 0.49 0.95 0.75 0.69 0.64
4
Horizontal Airflow 1680 0.52 0.56 0.33 0.49 0.90 0.78 0.60 0.66
1760 0.42 0.56 0.18 0.50 0.85 0.82 0.45 0.68
1840 0.32 0.57 0.08 0.50 0.78 0.83 0.30 0.70
1920 0.22 0.57 — — 0.70 0.85 0.20 0.73
1600 0.85 0.78 0.77 0.64 1.15 0.90 1.00 0.85
1700 0.80 0.82 0.63 0.65 1.10 0.94 0.90 0.89
1800 0.75 0.85 0.51 0.65 1.00 0.98 0.80 0.91
1900 0.65 0.88 0.41 0.65 0.93 1.02 0.70 0.94
YSC060A**L,M3 2000 0.55 0.90 0.25 0.66 0.85 1.05 0.60 0.95
5
Horizontal Airflow 2100 0.45 0.93 0.09 0.66 0.75 1.10 0.45 0.96
2200 0.35 0.95 0.00 0.67 0.65 1.12 0.30 0.96
2300 0.25 0.97 — — 0.55 1.17 0.10 0.97
2400 0.15 1.00 — — 0.43 1.20 — —
960 0.81 0.36 0.61 0.28 0.96 0.39 0.89 0.35
1020 0.77 0.37 0.57 0.28 0.94 0.41 0.86 0.47
1080 0.73 0.38 0.50 0.29 0.91 0.43 0.82 0.39
1140 0.69 0.39 0.42 0.29 0.88 0.44 0.77 0.40
3 YSC036A**L,M 1200 0.66 0.40 0.34 0.30 0.84 0.45 0.74 0.41
Downflow Airflow 1260 0.60 0.41 0.26 0.30 0.80 0.46 0.70 0.42
1320 0.55 0.42 0.14 0.31 0.75 0.48 0.65 0.44
1380 0.49 0.42 0.05 0.31 0.70 0.49 0.59 0.45
1440 0.44 0.43 — — 0.64 0.52 0.54 0.48
1280 0.93 0.53 0.81 0.47 1.20 0.67 0.99 0.56
1360 0.87 0.54 0.75 0.47 1.15 0.68 0.94 0.58
1440 0.80 0.54 0.68 0.48 1.10 0.70 0.88 0.60
1520 0.73 0.55 0.60 0.48 1.05 0.73 0.81 0.63
YSC048A**L,M 1600 0.66 0.55 0.51 0.49 1.00 0.75 0.74 0.64
4
Downflow Airflow 1680 0.57 0.56 0.38 0.49 0.95 0.78 0.65 0.66
1760 0.47 0.56 0.23 0.50 0.90 0.82 0.50 0.68
1840 0.37 0.57 0.13 0.50 0.83 0.83 0.35 0.70
1920 0.27 0.57 — — 0.75 0.85 — —
1600 0.90 0.78 0.82 0.64 1.20 0.90 1.05 0.85
1700 0.85 0.82 0.68 0.65 1.15 0.94 0.95 0.89
1800 0.80 0.85 0.56 0.65 1.05 0.98 0.85 0.91
1900 0.70 0.88 0.46 0.65 0.98 1.02 0.75 0.94
YSC060A**L,M3 2000 0.60 0.90 0.30 0.66 0.90 1.05 0.65 0.95
5
Downflow Airflow 2100 0.50 0.93 0.14 0.66 0.80 1.10 0.50 0.96
2200 0.40 0.95 0.05 0.67 0.70 1.12 0.35 0.96
2300 0.30 0.97 — — 0.60 1.17 0.15 0.97
2400 0.20 1.00 — — 0.48 1.20 — —
Fan motor heat (MBH) = 3.72 x Fan Bhp + .24.
Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product’s warranty will not be affected.
NOTES:
1. Data includes pressure drop due to wet coil and filters.
2. 5 ton oversized motor performance is with 12x11 FC Centrifugal blower wheel.
3. YSC060AK* uses a 1.0 hp direct drive motor and 12x11 FC Centrifugal blower wheel. Refer to oversized motor column for the standard motor performance
data.
36 RT-PRC006-EN
Performance (3 - 5 Tons)
Data Standard Efficiency

Table PD-19 — Direct Drive Evaporator Fan Performance 3, 4 and 5 Ton YSC036A, YSC048A, YSC060A — High Heat
External Static Pressure (Inches of Water) & Motor Power (Bhp)1
Standard Motor Oversized Motor2
High Speed Low Speed High Speed Low Speed
Unit
Tons Model No. CFM ESP BHP ESP BHP ESP BHP ESP BHP
960 0.76 0.36 0.56 0.28 0.91 0.39 0.84 0.35
1020 0.72 0.37 0.52 0.28 0.89 0.41 0.81 0.47
1080 0.68 0.38 0.45 0.29 0.86 0.43 0.77 0.39
1140 0.64 0.39 0.37 0.29 0.83 0.44 0.72 0.40
YSC036A**H 1200 0.61 0.40 0.29 0.30 0.79 0.45 0.69 0.41
3
Horizontal Airflow 1260 0.55 0.41 0.21 0.30 0.75 0.46 0.65 0.42
1320 0.50 0.42 0.09 0.31 0.70 0.48 0.60 0.44
1380 0.44 0.42 0.00 0.31 0.65 0.49 0.54 0.45
1440 0.39 0.43 — — 0.59 0.52 0.49 0.48
1280 0.88 0.53 0.76 0.47 1.15 0.67 0.94 0.56
1360 0.82 0.54 0.70 0.47 1.10 0.68 0.89 0.58
1440 0.75 0.54 0.63 0.48 1.05 0.70 0.83 0.60
1520 0.68 0.55 0.55 0.48 1.00 0.73 0.76 0.63
4 YSC048A**H 1600 0.61 0.55 0.46 0.49 0.95 0.75 0.69 0.64
Horizontal Airflow 1680 0.52 0.56 0.33 0.49 0.90 0.78 0.60 0.66
1760 0.42 0.56 0.18 0.50 0.85 0.82 0.45 0.68
1840 0.32 0.57 0.08 0.50 0.78 0.83 0.30 0.70
1920 0.22 0.57 — — 0.70 0.85 0.20 0.73
1600 0.85 0.78 0.77 0.64 1.15 0.90 1.00 0.85
1700 0.80 0.82 0.63 0.65 1.10 0.94 0.90 0.89
1800 0.75 0.85 0.51 0.65 1.00 0.98 0.80 0.91
1900 0.65 0.88 0.41 0.65 0.93 1.02 0.70 0.94
YSC060A**H3 2000 0.55 0.90 0.25 0.66 0.85 1.05 0.60 0.95
5
Horizontal Airflow 2100 0.45 0.93 0.09 0.66 0.75 1.10 0.45 0.96
2200 0.35 0.95 0.00 0.67 0.65 1.12 0.30 0.96
2300 0.25 0.97 — — 0.55 1.17 0.10 0.97
2400 0.15 1.00 — — 0.43 1.20 — —
960 0.76 0.36 0.56 0.28 0.91 0.39 0.84 0.35
1020 0.72 0.37 0.52 0.28 0.89 0.41 0.81 0.47
1080 0.68 0.38 0.45 0.29 0.86 0.43 0.77 0.39
1140 0.64 0.39 0.37 0.29 0.83 0.44 0.72 0.40
YSC036A**H 1200 0.61 0.40 0.29 0.30 0.79 0.45 0.69 0.41
3
Downflow Airflow 1260 0.55 0.41 0.21 0.30 0.75 0.46 0.65 0.42
1320 0.50 0.42 0.09 0.31 0.70 0.48 0.60 0.44
1380 0.44 0.42 0.00 0.31 0.65 0.49 0.54 0.45
1440 0.39 0.43 — — 0.59 0.52 0.49 0.48
1280 0.93 0.53 0.81 0.47 1.20 0.67 0.99 0.56
1360 0.87 0.54 0.75 0.47 1.15 0.68 0.94 0.58
1440 0.80 0.54 0.68 0.48 1.10 0.70 0.88 0.60
1520 0.73 0.55 0.60 0.48 1.05 0.73 0.81 0.63
4 YSC048A**H 1600 0.66 0.55 0.51 0.49 1.00 0.75 0.74 0.64
Downflow Airflow 1680 0.57 0.56 0.38 0.49 0.95 0.78 0.65 0.66
1760 0.47 0.56 0.23 0.50 0.90 0.82 0.50 0.68
1840 0.37 0.57 0.13 0.50 0.83 0.83 0.35 0.70
1920 0.27 0.57 — — 0.75 0.85 — —
1600 0.90 0.78 0.82 0.64 1.20 0.90 1.05 0.85
1700 0.85 0.82 0.68 0.65 1.15 0.94 0.95 0.89
1800 0.80 0.85 0.56 0.65 1.05 0.98 0.85 0.91
1900 0.70 0.88 0.46 0.65 0.98 1.02 0.75 0.94
YSC060A**H3 2000 0.60 0.90 0.30 0.66 0.90 1.05 0.65 0.95
5
Downflow Airflow 2100 0.50 0.93 0.14 0.66 0.80 1.10 0.50 0.96
2200 0.40 0.95 0.00 0.67 0.70 1.12 0.35 0.96
2300 0.30 0.97 — — 0.60 1.17 0.15 0.97
2400 0.20 1.00 — — 0.48 1.20 — —
Fan motor heat (MBH) = 3.72 x Fan Bhp + .24.
Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product’s warranty will not be affected.
NOTES:
1. Data includes pressure drop due to wet coil and filters.
2. 5 ton oversized motor performance is with 12x11 FC Centrifugal blower wheel.
3. YSC060AK* uses a 1.0 hp direct drive motor and 12x11 FC Centrifugal blower wheel. Refer to oversized motor column for the standard motor performance data.

RT-PRC006-EN 37
Performance (3 Ton)
Data Standard Efficiency

Table PD-20 — Belt Drive Evaporator Fan Performance — 3-Ton — YSC036A3,A4,AW*L, M — Low and Medium Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
960 — — 570 0.14 634 0.18 690 0.22 741 0.27 791 0.31 836 0.36 879 0.41 922 0.46 961 0.52
1080 537 0.14 606 0.18 669 0.23 724 0.27 773 0.32 819 0.36 864 0.41 906 0.47 946 0.52 985 0.58
1200 581 0.18 645 0.22 705 0.27 759 0.33 807 0.38 851 0.42 894 0.48 935 0.53 973 0.59 1011 0.65
1320 627 0.23 686 0.28 742 0.33 795 0.39 842 0.44 885 0.50 927 0.55 966 0.61 1003 0.67 1040 0.73
1440 673 0.29 728 0.34 780 0.39 831 0.45 878 0.52 921 0.58 960 0.64 998 0.69 1034 0.76 1070 0.82
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop due to other motor failure. Our product’s warranty will not be affected.
options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK69 required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.

Table PD-20 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
960 1000 0.57 1037 0.63 1072 0.69 1106 0.75 1139 0.81
1080 1022 0.64 1058 0.70 1093 0.76 1127 0.82 1161 0.89
1200 1047 0.71 1083 0.77 1117 0.83 1150 0.90 1183 0.97
1320 1075 0.79 1108 0.85 1141 0.92 1174 0.99 1206 1.06
1440 1104 0.88 1137 0.95 1170 1.02 1201 1.09 1231 1.16

1-HP Standard Motor &


Field Supplied High Static Drive (2)

Table PD-21 — Belt Drive Evaporator Fan Performance — 3-Ton — YSC036A3,A4,AW*L, M — Low and Medium Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
960 552 0.13 631 0.17 699 0.22 759 0.27 811 0.33 858 0.38 902 0.44 943 0.49 980 0.54 1017 0.60
1080 598 0.17 675 0.22 739 0.27 798 0.33 850 0.38 898 0.44 941 0.50 982 0.57 1020 0.63 1056 0.69
1200 645 0.22 720 0.28 781 0.33 837 0.39 889 0.45 937 0.51 981 0.58 1021 0.65 1059 0.72 1095 0.79
1320 693 0.28 766 0.34 825 0.40 879 0.47 929 0.53 976 0.60 1020 0.67 1061 0.74 1099 0.81 1135 0.89
1440 743 0.35 811 0.42 871 0.49 922 0.55 970 0.62 1016 0.69 1059 0.77 1099 0.84 1138 0.92 1174 1.00
1-HP Standard
Motor & Field Supplied
High Static Drive (2)
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories motor failure. Our product’s warranty will not be affected.
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK69 required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave AK41 required.Field Supplied Belt may be necessary.
Table PD-21 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
960 1052 0.65 1086 0.71 1120 0.77 1152 0.83 1185 0.90
1080 1090 0.75 1123 0.81 1154 0.87 1185 0.93 1215 0.99
1200 1130 0.86 1162 0.92 1193 0.99 1224 1.05 1253 1.12
1320 1169 0.96 1203 1.04 1233 1.12 1263 1.19 1292 1.26
1440 1208 1.08 1241 1.16 1273 1.25 1303 1.33 1332 1.41
1-HP Standard Motor &
Field Supplied High Static Drive (2)

38 RT-PRC006-EN
Performance (3 Ton)
Data Standard Efficiency

Table PD-22— Belt Drive Evaporator Fan Performance — 3-Ton — YSC036A3,A4,AW*H — High Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
960 503 0.11 578 0.15 641 0.19 696 0.23 747 0.27 796 0.32 841 0.36 884 0.42 926 0.47 966 0.52
1080 548 0.15 616 0.19 678 0.23 731 0.28 780 0.32 826 0.37 870 0.42 912 0.47 952 0.53 991 0.59
1200 593 0.19 657 0.23 716 0.28 768 0.33 815 0.38 859 0.43 901 0.49 942 0.54 980 0.60 1017 0.66
1320 640 0.24 698 0.29 754 0.34 806 0.40 852 0.45 895 0.51 935 0.56 974 0.62 1012 0.68 1048 0.74
1440 688 0.31 742 0.35 794 0.41 844 0.47 890 0.53 931 0.59 970 0.65 1009 0.71 1045 0.77 1080 0.84

For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories motor failure. Our product’s warranty will not be affected.
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK69 required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.

Table PD-22 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
960 1005 0.58 1041 0.64 1076 0.70 1110 0.76 1142 0.82
1080 1029 0.65 1064 0.71 1099 0.77 1133 0.83 1166 0.90
1200 1053 0.72 1089 0.78 1123 0.85 1156 0.91 1189 0.98
1320 1082 0.80 1116 0.87 1150 0.93 1182 1.00 1214 1.07
1440 1113 0.90 1146 0.97 1178 1.04 1209 1.11 1240 1.18
1-HP Standard Motor &
Field Supplied High Static Drive (2)

Table PD-23 — Belt Drive Evaporator Fan Performance — 3-Ton — YSC036A3,A4,AW*H — High Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
960 563 0.13 639 0.18 707 0.23 766 0.28 817 0.33 864 0.39 908 0.44 947 0.49 985 0.55 1020 0.60
1080 611 0.18 685 0.23 748 0.28 806 0.34 858 0.39 905 0.45 947 0.51 988 0.58 1026 0.64 1061 0.70
1200 660 0.23 732 0.29 792 0.34 847 0.40 899 0.46 945 0.53 989 0.59 1029 0.66 1066 0.73 1102 0.80
1320 711 0.29 781 0.36 838 0.42 890 0.48 940 0.55 986 0.61 1029 0.68 1070 0.76 1106 0.83 1142 0.90
1440 762 0.37 829 0.44 885 0.51 935 0.57 983 0.64 1028 0.71 1070 0.79 1111 0.86 1148 0.94 1183 1.02
1-HP Standard
Motor & Field Supplied
High Static Drive (2)
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories motor failure. Our product’s warranty will not be affected.
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK69 required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.
Table PD-23 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard 1-HP Standard Motor & Field
Motor & Drive Supplied High Static Drive (2)
960 1056 0.66 1090 0.71 1123 0.78 1156 0.84 1188 0.90
1080 1096 0.76 1128 0.82 1159 0.88 1190 0.94 1220 1.00
1200 1135 0.87 1168 0.93 1199 1.00 1229 1.07 1259 1.13
1320 1177 0.98 1209 1.06 1241 1.14 1270 1.21 1299 1.28
1440 1217 1.10 1250 1.18 1281 1.27 1311 1.35 1339 1.43

RT-PRC006-EN 39
Performance (4 Ton)
Data Standard Efficiency

Table PD-24 — Belt Drive Evaporator Fan Performance — 4-Ton — YSC048A3,A4,AW*L,M — Low and Medium Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1280 604 0.21 666 0.25 724 0.30 778 0.36 826 0.41 870 0.47 911 0.52 952 0.58 990 0.63 1026 0.69
1440 665 0.29 720 0.34 773 0.38 824 0.44 872 0.51 916 0.57 956 0.63 994 0.69 1030 0.75 1065 0.81
1600 726 0.38 777 0.44 826 0.49 873 0.54 919 0.61 961 0.68 1002 0.75 1039 0.82 1074 0.89 1109 0.95
1760 789 0.50 836 0.56 881 0.61 924 0.67 967 0.73 1008 0.81 1048 0.89 1085 0.97 1120 1.04 1154 1.12
1920 851 0.63 896 0.70 938 0.76 978 0.82 1018 0.88 1057 0.96 1095 1.04 1131 1.13 1167 1.21 1199 1.30

For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standardfilters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories motor failure. Our product’s warranty will not be affected.
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.

Table PD-24 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
1280 1062 0.76 1097 0.82 1130 0.88 1163 0.95 1195 1.02
1440 1100 0.88 1133 0.94 1166 1.01 1198 1.08 1228 1.15
1600 1141 1.02 1173 1.09 1205 1.16 1235 1.23 1265 1.31
1760 1185 1.19 1215 1.26 1246 1.33 1275 1.41 1304 1.49
1920 1230 1.37 1260 1.45 — — — — — —

1-HP Standard Motor & Field


Supplied High Static Drive (2)

Table PD-25 — Belt Drive Evaporator Fan Performance — 4-Ton — YSC048A3,A4,AW*L,, M — Low and Medium Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1280 669 0.25 744 0.31 805 0.37 860 0.44 911 0.50 959 0.56 1003 0.63 1045 0.70 1082 0.77 1119 0.85
1440 733 0.34 803 0.41 864 0.48 916 0.55 965 0.62 1011 0.69 1055 0.76 1096 0.83 1134 0.91 1171 0.99
1600 800 0.45 864 0.53 923 0.60 974 0.68 1021 0.75 1064 0.83 1106 0.91 1147 0.99 1185 1.07 1221 1.15
1760 868 0.58 926 0.67 982 0.75 1033 0.83 1079 0.92 1121 1.00 1161 1.08 1199 1.17 1237 1.26 1273 1.35
1920 937 0.74 989 0.83 1042 0.92 1092 1.01 1138 1.10 1179 1.19 1217 1.28 1254 1.38 1290 1.47 — —
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
NOTES:
Data includes pressure drop due to standard filters and wet coils. 1-HP Standard Motor & Field
No accessories or options are included in pressure drop data. Supplied High Static Drive (2)
Refer to Table PD-89 to determine additional static pressure drop
due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024. Table PD-25 — Continued
1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt
may be necessary. External Static Pressure (Inches of Water)
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt 1.10 1.20 1.30 1.40 1.50
may be necessary. CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Trane’s factory supplied motors, in commercial equipment, are definite purpose 1-HP Standard
motors, specifically designed and tested to operate reliably and continuously at Motor & Drive
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature 1280 1154 0.92 1187 1.00 1218 1.07 1248 1.14 1277 1.21
motor failure. Our product’s warranty will not be affected. 1440 1205 1.07 1237 1.15 1270 1.24 1300 1.32 1330 1.40
1600 1256 1.23 1290 1.33 1322 1.42 — — — —
1760 1307 1.43 — — — — — — — —
1920 — — — — — — — — — —

1-HP Standard Motor & Field


Supplied High Static Drive (2)

40 RT-PRC006-EN
Performance (4 Ton)
Data Standard Efficiency

Table PD-26 — Belt Drive Evaporator Fan Performance — 4-Ton — YSC048A3,A4,AW*H — High Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1280 618 0.22 678 0.26 735 0.31 788 0.37 835 0.42 879 0.48 920 0.53 960 0.59 997 0.65 1034 0.71
1440 680 0.30 735 0.35 787 0.40 838 0.46 884 0.52 926 0.59 966 0.64 1004 0.70 1040 0.77 1075 0.83
1600 744 0.40 794 0.45 842 0.50 888 0.56 933 0.64 975 0.71 1015 0.78 1051 0.84 1086 0.91 1120 0.97
1760 808 0.52 854 0.58 899 0.64 941 0.69 984 0.76 1024 0.84 1063 0.92 1099 1.00 1134 1.07 1167 1.14
1920 873 0.66 916 0.73 957 0.79 997 0.85 1037 0.92 1075 0.99 1112 1.08 1148 1.17 1183 1.25 1214 1.33
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories motor failure. Our product’s warranty will not be affected.
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.

Table PD-26 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
1280 1069 0.77 1104 0.83 1137 0.90 1169 0.96 1202 1.04
1440 1109 0.89 1142 0.96 1174 1.03 1205 1.10 1236 1.17
1600 1153 1.04 1184 1.11 1214 1.18 1244 1.26 1275 1.33
1760 1197 1.22 1228 1.29 1258 1.36 1287 1.44 — —
1920 1245 1.41 1274 1.49 — — — — — —
1-HP Standard Motor &
Field Supplied High Static Drive (2)

Table PD-27 — Belt Drive Evaporator Fan Performance — 4-Ton — YSC048A3,A4,AW*H — High Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1280 686 0.27 758 0.33 817 0.39 871 0.45 922 0.51 968 0.58 1013 0.64 1053 0.72 1091 0.79 1127 0.86
1440 753 0.36 821 0.43 878 0.50 930 0.57 977 0.63 1022 0.70 1066 0.78 1107 0.85 1145 0.93 1180 1.01
1600 821 0.48 884 0.55 941 0.63 990 0.70 1035 0.78 1078 0.86 1120 0.93 1160 1.02 1197 1.10 1234 1.18
1760 891 0.62 949 0.70 1004 0.78 1052 0.87 1096 0.95 1137 1.03 1176 1.12 1214 1.20 1251 1.29 1287 1.38
1920 962 0.78 1015 0.87 1067 0.97 1115 1.06 1158 1.15 1198 1.24 1235 1.33 1271 1.42 — — — —
1-HP Standard
Motor & Field Supplied
High Static Drive (2)
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024. Table PD-27 — Continued
1. Field Supplied Fan Sheave AK61 required. Field Supplied
Belt may be necessary. External Static Pressure (Inches of Water)
2. Field Supplied Fan Sheave AK41 required. Field Supplied 1.10 1.20 1.30 1.40 1.50
Belt may be necessary. CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard
Motor & Drive

1280 1160 0.94 1194 1.01 1224 1.08 1254 1.15 1283 1.22
1440 1214 1.09 1247 1.18 1278 1.26 1308 1.34 1338 1.43
1600 1268 1.26 1300 1.35 1331 1.44 — — — —
1760 1321 1.47 — — — — — — — —
1920 — — — — — — — — — —
1-HP Standard Motor & Field
Supplied High Static Drive (2)

RT-PRC006-EN 41
Performance (5 Ton)
Data Standard Efficiency

Table PD-28 — Belt Drive Evaporator Fan Performance — 5-Ton — YSC060A3,A4,AW *L,M — Low and Medium Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1600 747 0.40 797 0.46 846 0.51 893 0.57 938 0.64 981 0.72 1020 0.79 1056 0.85 1091 0.92 1125 0.99
1800 828 0.56 873 0.62 917 0.68 960 0.74 1002 0.81 1042 0.89 1081 0.97 1118 1.05 1152 1.13 1185 1.20
2000 909 0.75 951 0.82 992 0.89 1031 0.95 1069 1.01 1107 1.09 1144 1.18 1179 1.27 1213 1.37 1246 1.45
2200 992 0.98 1031 1.06 1068 1.13 1104 1.20 1139 1.27 1175 1.35 1209 1.43 — — — — — —
2400 1075 1.26 1111 1.34 1145 1.42 1179 1.50 — — — — — — — — — — — —

For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied
Belt may be necessary.

Table PD-28 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
1600 1158 1.05 1190 1.13 1221 1.20 1251 1.27 1281 1.35
1800 1216 1.28 1246 1.35 1276 1.43 — — — —
2000 — — — — — — — — — —
2200 — — — — — — — — — —
2400 — — — — — — — — — —

Table PD-29 — Belt Drive Evaporator Fan Performance — 5-Ton — YSC060A3,A4,AW*L,M — Low and Medium Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor
& Field Supplied
Low Static Drive (1) 1-HP Standard Motor & Drive
1600 825 0.48 889 0.56 946 0.64 996 0.71 1041 0.79 1084 0.87 1126 0.95 1166 1.03 1204 1.11 1240 1.20
1800 913 0.66 971 0.75 1025 0.84 1074 0.92 1117 1.01 1158 1.09 1197 1.18 1235 1.27 1272 1.36 1307 1.45
2000 1003 0.89 1054 0.98 1105 1.08 1153 1.18 1196 1.27 1235 1.37 1272 1.46 1308 1.50 — — — —
2200 1094 1.16 1140 1.26 1187 1.37 1232 1.48 — — — — — — — — — — — —
2400 1185 1.48 — — — — — — — — — — — — — — — — — —
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt may be necessary.

Table PD-29 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard
Motor & Drive

1600 1274 1.28 1307 1.37 1338 1.46 — —


1800 — — — — — — — —
2000 — — — — — — — —
2200 — — — — — — — —
2400 — — — — — — — —

42 RT-PRC006-EN
Performance (5 Ton)
Data Standard Efficiency

Table PD-30 — Belt Drive Evaporator Fan Performance — 5-Ton — YSC060A3,A4,AW *H — High Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1600 764 0.42 814 0.47 862 0.53 909 0.60 953 0.67 994 0.74 1032 0.81 1069 0.88 1103 0.94 1136 1.01
1800 848 0.58 892 0.65 936 0.70 978 0.77 1020 0.84 1059 0.92 1098 1.01 1132 1.09 1166 1.16 1198 1.24
2000 932 0.79 973 0.86 1013 0.92 1051 0.98 1090 1.06 1127 1.14 1163 1.23 1197 1.32 1231 1.42 1262 1.50
2200 1017 1.03 1055 1.11 1091 1.18 1127 1.25 1162 1.32 1196 1.40 1231 1.49 — — — — — —
2400 1103 1.32 1138 1.41 1171 1.49 — — — — — — — — — — — — — —
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature motor
Refer to Table PD-89 to determine additional static pressure drop failure. Our product’s warranty will not be affected.
due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied
Belt may be necessary.

Table PD-30 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
1600 1168 1.08 1201 1.15 1231 1.22 1261 1.30 1290 1.37
1800 1229 1.31 1259 1.39 1288 1.46 — — — —
2000 — — — — — — — — — —
2200 — — — — — — — — — —
2400 — — — — — — — — — —

Table PD-31 — Belt Drive Evaporator Fan Performance — 5-Ton — YSC060A3,A4,AW *H— High Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor
& Field Supplied
Low Static Drive (1) 1-HP Standard Motor & Drive
1600 847 0.51 910 0.59 964 0.66 1011 0.74 1056 0.82 1098 0.89 1140 0.97 1179 1.06 1217 1.14 1252 1.23
1800 938 0.70 995 0.79 1047 0.87 1093 0.96 1135 1.05 1175 1.13 1213 1.22 1251 1.31 1287 1.40 1323 1.49
2000 1030 0.94 1082 1.03 1131 1.13 1176 1.23 1217 1.32 1255 1.42 1292 1.50 — — — — — —
2200 1123 1.23 1170 1.33 1216 1.44 — — — — — — — — — — — — — —
2400 — — — — — — — — — — — — — — — — — — — —

For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt may be necessary.

Table PD-31 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40
CFM RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard
Motor & Drive

1600 1285 1.31 1317 1.40 1348 1.49 — —


1800 — — — — — — — —
2000 — — — — — — — —
2200 — — — — — — — —
2400 — — — — — — — —

RT-PRC006-EN 43
Performance (6 Ton)
Data Standard Efficiency

Table PD-32 — Belt Drive Evaporator Fan Performance — 6-Ton — YSC072A3,A4,AW *L,M — Low and Medium Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1920 — — — — 583 0.35 638 0.42 687 0.49 732 0.56 777 0.64 817 0.71 857 0.80 895 0.88
2160 — — 559 0.36 613 0.43 666 0.51 715 0.59 759 0.67 800 0.75 841 0.83 879 0.92 915 1.01
2400 — — 597 0.46 647 0.54 695 0.62 743 0.71 788 0.80 828 0.88 866 0.97 902 1.06 938 1.15
2640 585 0.49 636 0.59 684 0.66 728 0.75 772 0.84 815 0.94 856 1.03 894 1.13 930 1.23 963 1.32
2880 629 0.63 677 0.73 722 0.81 763 0.89 803 0.99 844 1.09 884 1.20 923 1.31 958 1.41 990 1.51
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.

Table PD-32 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1 HP Standard Motor & Drive 1HP Standard Motor & High Static Drive Kit
(or 2 HP Oversized Motor & Drive)
1920 931 0.96 965 1.04 999 1.12 1030 1.20 1062 1.29 1092 1.37 1120 1.45 1150 1.54 1177 1.63 1204 1.71
2160 951 1.10 984 1.19 1018 1.29 1049 1.37 1080 1.46 1110 1.55 1139 1.65 1168 1.74 1196 1.84 1222 1.93
2400 973 1.25 1006 1.35 1039 1.45 1070 1.55 1100 1.65 1129 1.76 1158 1.86 1186 1.96 1213 2.06 1241 2.16
2540 996 1.42 1029 1.52 1060 1.63 1091 1.74 1121 1.85 1150 1.96 1178 2.07 1206 2.18 1233 2.30 — —
2880 1023 1.62 1054 1.72 1085 1.83 1114 1.95 1143 2.06 1172 2.18 1200 2.30 — — — — — —
2 HP Oversized Motor & Drive

Table PD-33 — Belt Drive Evaporator Fan Performance — 6-Ton — YSC072A3,A4,AW *H— High Heat — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor
& Field Supplied
Low Static Drive (1) 1-HP Standard Motor & Drive
1920 — — 559 0.32 618 0.39 668 0.46 715 0.53 759 0.61 802 0.69 842 0.77 881 0.85 917 0.93
2160 — — 600 0.42 654 0.49 705 0.57 749 0.65 791 0.73 831 0.81 870 0.90 907 0.99 943 1.08
2400 594 0.46 644 0.53 692 0.61 741 0.70 786 0.79 826 0.88 864 0.97 900 1.05 936 1.15 971 1.24
2640 643 0.60 691 0.67 734 0.76 778 0.85 822 0.95 862 1.05 899 1.14 935 1.24 967 1.33 1001 1.43
2880 693 0.76 737 0.84 778 0.93 818 1.03 858 1.13 898 1.24 935 1.35 970 1.45 1003 1.55 1034 1.66
2-HP Oversized
Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are
NOTES: definite purpose motors, specifically designed and tested to operate
Data includes pressure drop due to standard filters and wet coils. reliably and continuously at all cataloged conditions. Using the full
No accessories or options are included in pressure drop data. horsepower range of our fan motors as shown in our tabular data
Refer to Table PD-89 to determine additional static pressure drop will not result in nuisance tripping or premature motor failure. Our
due to other options/accessories product’s warranty will not be affected.
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.
Table PD-33 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & High Static Drive Kit
(or 2 HP oversized Motor& Drive)
1920 952 1.01 985 1.09 1019 1.17 1050 1.26 1080 1.34 1110 1.42 1139 1.51 1167 1.60 1192 1.68 1220 1.77
2160 977 1.17 1010 1.26 1043 1.36 1073 1.44 1103 1.53 1133 1.63 1161 1.72 1189 1.81 1216 1.91 1242 2.00
2400 1004 1.34 1037 1.44 1068 1.55 1099 1.65 1128 1.75 1156 1.85 1185 1.95 1212 2.05 1239 2.16 1265 2.26
2640 1033 1.54 1064 1.64 1095 1.75 1125 1.87 1153 1.97 1182 2.09 1210 2.20 — — — — — —
2880 1065 1.76 1096 1.88 1124 1.99 1153 2.10 1182 2.22 — – — — — — — — — —
2-HP Oversized Motor & Drive

44 RT-PRC006-EN
Performance (6 Ton)
Data Standard Efficiency

Table PD-34 — Belt Drive Evaporator Fan Performance — 6-Ton — YSC072AK *L — Low Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied 2-HP Standard Motor & Drive
Low Static Drive (1)
1920 - - - - 583 0.35 638 0.42 687 0.49 732 0.56 777 0.64 817 0.71 857 0.80 895 0.88
2160 - - 559 0.36 613 0.43 666 0.51 715 0.59 759 0.67 800 0.75 841 0.83 879 0.92 915 1.01
2400 - - 597 0.46 647 0.54 695 0.62 743 0.71 788 0.80 828 0.88 866 0.97 902 1.06 938 1.15
2640 585 0.49 636 0.59 684 0.66 728 0.75 772 0.84 815 0.94 856 1.03 894 1.13 930 1.23 963 1.32
2880 629 0.63 677 0.73 722 0.81 763 0.89 803 0.99 844 1.09 884 1.20 923 1.31 958 1.41 990 1.51
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are
NOTES: definite purpose motors, specifically designed and tested to operate
Data includes pressure drop due to standard filters and wet coils. reliably and continuously at all cataloged conditions. Using the full
No accessories or options are included in pressure drop data. horsepower range of our fan motors as shown in our tabular data
Refer to Table PD-89 to determine additional static pressure drop will not result in nuisance tripping or premature motor failure. Our
due to other options/accessories product’s warranty will not be affected.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.

Table PD-34 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor & Drive 2 HP Standard Motor & High Static Drive)
1920 931 0.96 965 1.04 999 1.12 1030 1.20 1062 1.29 1092 1.37 1120 1.45 1150 1.54 1177 1.63 1204 1.71
2160 951 1.10 984 1.19 1018 1.29 1049 1.37 1080 1.46 1110 1.55 1139 1.65 1168 1.74 1196 1.84 1222 1.93
2400 973 1.25 1006 1.35 1039 1.45 1070 1.55 1100 1.65 1129 1.76 1158 1.86 1186 1.96 1213 2.06 1241 2.16
2640 996 1.42 1029 1.52 1060 1.63 1091 1.74 1121 1.85 1150 1.96 1178 2.07 1206 2.18 1233 2.30 - -
2880 1023 1.62 1054 1.72 1085 1.83 1114 1.95 1143 2.06 1172 2.18 1200 2.30 - - - - - -
2 HP Standard Motor & High Static Drive

Table PD-35 — Belt Drive Evaporator Fan Performance — 6-Ton — YSC072AK *H— High Heat — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Std. Motor & Field Supplied Low Static Drive 2 HP Standard Motor & Drive
1920 - - 559 0.32 618 0.39 668 0.46 715 0.53 759 0.61 802 0.69 842 0.77 881 0.85 917 0.93
2160 - - 600 0.42 654 0.49 705 0.57 749 0.65 791 0.73 831 0.81 870 0.90 907 0.99 943 1.08
2400 594 0.46 644 0.53 692 0.61 741 0.70 786 0.79 826 0.88 864 0.97 900 1.05 936 1.15 971 1.24
2640 643 0.60 691 0.67 734 0.76 778 0.85 822 0.95 862 1.05 899 1.14 935 1.24 967 1.33 1001 1.43
2880 693 0.76 737 0.84 778 0.93 818 1.03 858 1.13 898 1.24 935 1.35 970 1.45 1003 1.55 1034 1.66
2 HP Standard Motor
& High Static Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are
NOTES: definite purpose motors, specifically designed and tested to operate
Data includes pressure drop due to standard filters and wet coils. reliably and continuously at all cataloged conditions. Using the full
No accessories or options are included in pressure drop data. horsepower range of our fan motors as shown in our tabular data
Refer to Table PD-89 to determine additional static pressure drop will not result in nuisance tripping or premature motor failure. Our
due to other options/accessories product’s warranty will not be affected.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.

Table PD-35 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor & Drive 2-HP Standard Motor & High Static Drive
1920 952 1.01 985 1.09 1019 1.17 1050 1.26 1080 1.34 1110 1.42 1139 1.51 1167 1.60 1192 1.68 1220 1.77
2160 977 1.17 1010 1.26 1043 1.36 1073 1.44 1103 1.53 1133 1.63 1161 1.72 1189 1.81 1216 1.91 1242 2.00
2400 1004 1.34 1037 1.44 1068 1.55 1099 1.65 1128 1.75 1156 1.85 1185 1.95 1212 2.05 1239 2.16 1265 2.26
2640 1033 1.54 1064 1.64 1095 1.75 1125 1.87 1153 1.97 1182 2.09 1210 2.20 - - - - - -
2880 1065 1.76 1096 1.88 1124 1.99 1153 2.10 1182 2.22 - - - - - - - - - -

RT-PRC006-EN 45
Performance (6 Ton)
Data Standard Efficiency

Table PD-36 — Belt Drive Evaporator Fan Performance — 6-Ton — YSC072A3,A4,AW *L,M — Low and Medium Heat —Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1920 — — 576 0.32 636 0.40 687 0.46 733 0.54 778 0.62 821 0.70 864 0.78 906 0.86 946 0.95
2160 575 0.37 619 0.43 674 0.50 726 0.59 770 0.66 812 0.74 852 0.82 890 0.92 930 1.01 968 1.10
2400 629 0.49 669 0.55 713 0.62 763 0.71 809 0.81 849 0.89 887 0.97 923 1.06 959 1.16 994 1.27
2640 684 0.63 721 0.71 757 0.78 802 0.86 846 0.96 888 1.07 925 1.16 959 1.25 993 1.34 1027 1.45
2880 740 0.80 774 0.89 807 0.97 843 1.05 885 1.14 925 1.26 964 1.38 998 1.48 1030 1.57 1062 1.67
2-HP Oversized
Motor and Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at 1-HP Standard
1-HP Standard Motor
Motor &
& High
High Static
Static
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as Drive (or
(or 2-HP
2-HP Oversized
Oversized Motor)
Motor)
Drive
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
F1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000.
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.
Table PD-36 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard 1-HP Standard Motor & High Static Drive Kit
Motor & Drive (or 2 HP Oversized Motor & Drive)
1920 985 1.04 1020 1.13 1057 1.22 1090 1.31 1123 1.41 1155 1.50 1185 1.60 1213 1.69 1241 1.79 1268 1.88
2160 1005 1.19 1040 1.29 1075 1.38 1110 1.48 1143 1.59 1176 1.69 1206 1.80 1235 1.90 1264 2.00 — —
2400 1029 1.37 1063 1.47 1098 1.58 1130 1.68 1162 1.78 1194 1.89 1223 2.00 1254 2.11 — — — —
2540 1058 1.56 1090 1.68 1121 1.79 1152 1.90 1184 2.01 1214 2.13 1244 2.24 — — — — — —
2880 1093 1.78 1123 1.90 1152 2.02 1181 2.14 1211 2.27 — — — — — — — — — —
2-HP Oversized Motor & Drive

Table PD-37 — Belt Drive Evaporator Fan Performance — 6-Ton — YSC072A3,A4,AW *H — High Heat —Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1920 551 0.30 613 0.37 668 0.44 715 0.51 761 0.58 804 0.67 847 0.75 890 0.83 930 0.92 969 1.00
2160 608 0.41 661 0.48 714 0.56 760 0.64 802 0.72 842 0.80 882 0.90 920 0.99 958 1.08 996 1.17
2400 667 0.55 710 0.62 760 0.71 806 0.80 847 0.88 885 0.96 921 1.06 957 1.16 992 1.27 1027 1.37
2640 726 0.72 762 0.79 809 0.87 853 0.98 894 1.09 930 1.17 965 1.26 998 1.36 1031 1.47 1063 1.58
2880 786 0.91 818 0.99 857 1.08 900 1.18 939 1.30 976 1.41 1009 1.51 1042 1.61 1073 1.71 1103 1.82
2-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at 1-HP Standard Motor & High Static
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as Drive (or 2-HP Oversized Motor)
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.
Table PD-37 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & High Static Drive
Kit (or 2 HP Oversized Motor & Drive)
1920 1007 1.09 1044 1.19 1078 1.28 1111 1.37 1142 1.46 1172 1.56 1203 1.65 1230 1.75 1257 1.84 — —
2160 1032 1.26 1068 1.36 1102 1.46 1135 1.56 1167 1.66 1198 1.77 1229 1.88 1259 1.98 — — — —
2400 1061 1.47 1095 1.57 1128 1.67 1161 1.78 1191 1.88 1223 2.00 1254 2.11 1282 2.23 — — — —
2640 1095 1.70 1126 1.81 1157 1.92 1189 2.03 1219 2.15 1250 2.26 — — — — — — — —
2880 1133 1.94 1162 2.06 1191 2.19 1221 2.30 — — — — — — — — — — — —
2-HP Oversized Motor & Drive

46 RT-PRC006-EN
Performance (6 Ton)
Data Standard Efficiency

Table PD-38 — Belt Drive Evaporator Fan Performance — 6-Ton — YSC072AK *L — Low Heat —Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor & Low Static Drive 2 HP Standard Motor & Drive
1920 522 0.27 576 0.32 636 0.40 687 0.46 733 0.54 778 0.62 821 0.70 864 0.78 906 0.86 946 0.95
2160 575 0.37 619 0.43 674 0.50 726 0.59 770 0.66 812 0.74 852 0.82 890 0.92 930 1.01 968 1.10
2400 629 0.49 669 0.55 713 0.62 763 0.71 809 0.81 849 0.89 887 0.97 923 1.06 959 1.16 994 1.27
2640 684 0.63 721 0.71 757 0.78 802 0.86 846 0.96 888 1.07 925 1.16 959 1.25 993 1.34 1027 1.45
2880 740 0.80 774 0.89 807 0.97 843 1.05 885 1.14 925 1.26 964 1.38 998 1.48 1030 1.57 1062 1.67
2 HP Standard Motor
& High Static Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES:
motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils.
all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data.
shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop
motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000.
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.

Table PD-38 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard 2 HP Standard Motor & High Static Drive Kit
Motor & Drive
1920 985 1.04 1020 1.13 1057 1.22 1090 1.31 1123 1.41 1155 1.50 1185 1.60 1213 1.69 1241 1.79 1268 1.88
2160 1005 1.19 1040 1.29 1075 1.38 1110 1.48 1143 1.59 1176 1.69 1206 1.80 1235 1.90 1264 2.00 - -
2400 1029 1.37 1063 1.47 1098 1.58 1130 1.68 1162 1.78 1194 1.89 1223 2.00 1254 2.11 - - - -
2640 1058 1.56 1090 1.68 1121 1.79 1152 1.90 1184 2.01 1214 2.13 1244 2.24 - - - - - -
2880 1093 1.78 1123 1.90 1152 2.02 1181 2.14 1211 2.27 - - - - - - - - - -

Table PD-39 — Belt Drive Evaporator Fan Performance — 6-Ton — YSC072AK*H — High Heat —Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor & Field Supplied 2 HP Standard Motor & Drive
Low Static Drive (1)
1920 551 0.30 613 0.37 668 0.44 715 0.51 761 0.58 804 0.67 847 0.75 890 0.83 930 0.92 969 1.00
2160 608 0.41 661 0.48 714 0.56 760 0.64 802 0.72 842 0.80 882 0.90 920 0.99 958 1.08 996 1.17
2400 667 0.55 710 0.62 760 0.71 806 0.80 847 0.88 885 0.96 921 1.06 957 1.16 992 1.27 1027 1.37
2640 726 0.72 762 0.79 809 0.87 853 0.98 894 1.09 930 1.17 965 1.26 998 1.36 1031 1.47 1063 1.58
2880 786 0.91 818 0.99 857 1.08 900 1.18 939 1.30 976 1.41 1009 1.51 1042 1.61 1073 1.71 1103 1.82
2 HP Standard Motor & High Static Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.

Table PD-39 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor & High Static Drive
1920 1007 1.09 1044 1.19 1078 1.28 1111 1.37 1142 1.46 1172 1.56 1203 1.65 1230 1.75 1257 1.84 - -
2160 1032 1.26 1068 1.36 1102 1.46 1135 1.56 1167 1.66 1198 1.77 1229 1.88 1259 1.98 - - - -
2400 1061 1.47 1095 1.57 1128 1.67 1161 1.78 1191 1.88 1223 2.00 1254 2.11 1282 2.23 - - - -
2640 1095 1.70 1126 1.81 1157 1.92 1189 2.03 1219 2.15 1250 2.26 - - - - - - - -
2880 1133 1.94 1162 2.06 1191 2.19 1221 2.30 - - - - - - - - - - - -

RT-PRC006-EN 47
Performance (7½ Ton)
Data Standard Efficiency

Table PD-40 — Belt Drive Evaporator Fan Performance — 7½-Ton — YSC090,092A3,A4,AW, AK *L — Low Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied 2-HP Standard Motor & Drive
Low Static Drive (1)
2400 — — — — 676 0.59 726 0.67 773 0.77 815 0.85 854 0.94 891 1.03 928 1.12 963 1.22
2700 — — 682 0.68 727 0.76 770 0.85 814 0.95 856 1.06 895 1.16 931 1.25 965 1.35 998 1.45
3000 693 0.79 738 0.89 780 0.97 819 1.07 858 1.18 898 1.29 936 1.40 972 1.52 1006 1.63 1038 1.73
3300 753 1.03 795 1.14 834 1.23 871 1.33 906 1.45 942 1.56 978 1.69 1014 1.81 1048 1.94 1080 2.06
3600 814 1.31 853 1.44 890 1.55 925 1.65 958 1.76 991 1.88 1023 2.01 1057 2.14 1088 2.28 1121 2.41

For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at 3-HP Oversized Motor
NOTES:
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. Field Supplied Motor Sheave 1VL40L x 7/8 and Fan Sheave AK71 required.

Table PD-40 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2- HP Standard Motor & Drive 2-HP Standard Motor & High Static Drive
Kit (or 3-HP Oversized Motor & Drive)
2400 996 1.32 1028 1.42 1061 1.52 1092 1.63 1122 1.73 1151 1.83 1180 1.93 1207 2.03 1235 2.14 1261 2.24
2700 1031 1.56 1062 1.66 1093 1.78 1123 1.89 1153 2.00 1181 2.12 1209 2.23 1236 2.35 1262 2.47 1288 2.58
3000 1070 1.85 1099 1.95 1128 2.07 1158 2.19 1185 2.31 1213 2.43 1240 2.55 1267 2.68 1293 2.81 1319 2.94
3300 1110 2.18 1139 2.29 1167 2.42 1195 2.54 1222 2.66 1248 2.79 1274 2.92 1301 3.05 1325 3.18 1351 3.33
3600 1151 2.55 1181 2.68 1208 2.81 1236 2.95 1261 3.07 1287 3.21 1311 3.33 — — — — — —
3-HP Oversized Motor & Drive

Table PD-41 — Belt Drive Evaporator Fan Performance — 7½-Ton — YSC090,092A3,A4,AW *M— Medium Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied 2-HP Standard Motor & Drive
Low Static Drive (1)
2400 — — 662 0.56 711 0.65 759 0.74 802 0.83 842 0.91 879 1.00 916 1.09 951 1.19 986 1.29
2700 676 0.67 721 0.75 764 0.84 809 0.94 851 1.04 891 1.14 927 1.24 961 1.34 994 1.44 1027 1.54
3000 741 0.89 783 0.98 822 1.08 861 1.19 901 1.30 939 1.41 975 1.52 1009 1.64 1041 1.74 1071 1.85
3300 807 1.17 846 1.26 882 1.37 917 1.48 953 1.60 989 1.72 1024 1.85 1058 1.97 1089 2.09 1119 2.21
3600 874 1.50 910 1.60 944 1.71 976 1.83 1008 1.95 1041 2.08 1074 2.22 1107 2.35 1138 2.49 1168 2.62
3-HP Oversized Motor
& Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at 2-HP Standard Motor & High Static
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as Drive (or 3-HP Oversized Motor)
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Motor Sheave 1VL40L x 7/8 and Fan Sheave AK71 required.

Table PD-41 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & High Static Drive Kit
2-HP Standard Motor & Drive (or 3-HP Oversized Motor & Drive)
2400 1019 1.39 1051 1.49 1083 1.60 1113 1.70 1141 1.80 1171 1.90 1199 2.01 1225 2.10 1252 2.20 1278 2.31
2700 1058 1.65 1089 1.76 1120 1.87 1149 1.99 1178 2.10 1205 2.21 1232 2.33 1259 2.45 1284 2.56 1310 2.68
3000 1101 1.96 1131 2.08 1160 2.20 1187 2.31 1215 2.44 1243 2.57 1269 2.69 1295 2.82 1321 2.95 1346 3.08
3300 1147 2.33 1176 2.45 1204 2.58 1230 2.70 1256 2.82 1282 2.96 1308 3.09 1333 3.23 1358 3.36 — —
3600 1196 2.75 1223 2.88 1250 3.02 1276 3.15 1301 3.28 1325 3.41 — — — — — — — —
3-HP Oversized Motor & Drive

48 RT-PRC006-EN
Performance (7½ Ton)
Data Standard Efficiency

Table PD-42 — Belt Drive Evaporator Fan Performance — 7½-Ton — YSC090,092A3,A4,AW, AK *H — High Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied 2-HP Standard Motor & Drive
Low Static Drive (1)
2400 — — 697 0.62 745 0.71 790 0.80 830 0.89 869 0.98 906 1.07 941 1.16 976 1.26 1009 1.36
2700 717 0.74 760 0.83 804 0.93 847 1.03 887 1.13 922 1.23 958 1.33 991 1.43 1024 1.53 1055 1.64
3000 787 0.99 826 1.09 865 1.20 905 1.31 943 1.42 979 1.54 1012 1.64 1044 1.76 1075 1.87 1105 1.98
3300 858 1.30 894 1.41 929 1.52 965 1.64 1001 1.77 1036 1.89 1068 2.01 1099 2.13 1129 2.25 1157 2.37
3600 930 1.66 963 1.78 995 1.90 1028 2.03 1061 2.16 1093 2.30 1126 2.43 1157 2.57 1185 2.70 1212 2.83
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at 2-HP Standard Motor & High Static
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as Drive (or 3-HP Oversized Motor)
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Motor Sheave 1VL40L x 7/8 and Fan Sheave AK71 required.

Table PD-42 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive 2-HP Standard Motor & High Static Drive Kit (or 3-HP Oversized Motor & Drive)
2400 1042 1.46 1073 1.56 1104 1.67 1134 1.77 1163 1.87 1190 1.97 1218 2.08 1244 2.18 1271 2.28 1296 2.38
2700 1086 1.75 1117 1.86 1146 1.97 1174 2.09 1203 2.21 1230 2.32 1255 2.44 1282 2.55 1308 2.67 1333 2.78
3000 1134 2.09 1163 2.21 1191 2.33 1218 2.45 1245 2.58 1272 2.70 1298 2.83 1323 2.96 1348 3.09 1372 3.22
3300 1185 2.49 1212 2.61 1238 2.74 1265 2.87 1292 3.01 1316 3.13 1341 3.27 1366 3.41 — — — —
3600 1239 2.96 1265 3.09 1290 3.22 1316 3.36 — — — — — — — — — — — —
3-HP Oversized Motor & Drive

Table PD-43 — Belt Drive Evaporator Fan Performance — 7½-Ton — YSC090,092A3,A4,AW, AK *L— Low Heat —Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied 2-HP Standard Motor & Drive
Low Static Drive (1)
2400 653 0.53 694 0.59 745 0.67 793 0.77 835 0.86 874 0.94 911 1.03 948 1.13 982 1.23 1017 1.34
2700 725 0.73 760 0.80 801 0.88 847 0.98 889 1.09 927 1.19 963 1.28 997 1.38 1030 1.48 1061 1.60
3000 798 0.98 830 1.06 862 1.15 902 1.24 943 1.35 981 1.48 1017 1.60 1050 1.70 1081 1.80 1111 1.90
3300 872 1.28 901 1.38 929 1.47 961 1.56 998 1.67 1036 1.80 1071 1.93 1104 2.07 1135 2.19 1164 2.30
3600 946 1.65 973 1.75 1000 1.85 1025 1.95 1057 2.06 1091 2.17 1125 2.31 1158 2.46 1189 2.61 1219 2.75
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as 2-HP Standard Motor & High Static
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Drive (or 3-HP Oversized Motor)
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Motor Sheave 1VL40L x 7/8 and Fan Sheave AK71 required.

Table PD-43 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive 2-HP Standard Motor & High Static Drive Kit (or 3-HP Oversized Motor & Drive)
2400 1053 1.44 1087 1.55 1121 1.65 1153 1.76 1185 1.86 1217 1.98 1246 2.08 1277 2.20 1306 2.32 1334 2.44
2700 1093 1.71 1124 1.83 1156 1.95 1187 2.06 1218 2.18 1248 2.30 1277 2.42 1306 2.53 1333 2.65 1361 2.78
3000 1141 2.02 1170 2.15 1198 2.28 1227 2.41 1255 2.54 1283 2.67 1311 2.79 1339 2.93 1365 3.05 1391 3.18
3300 1192 2.41 1220 2.52 1247 2.65 1272 2.78 1299 2.92 1325 3.07 1350 3.21 1376 3.36 — — — —
3600 1246 2.87 1272 2.99 1298 3.11 1323 3.24 1348 3.37 — — — — — — — — — —
3-HP Oversized Motor & Drive

RT-PRC006-EN 49
Performance (7½ Ton)
Data Standard Efficiency

Table PD-44 — Belt Drive Evaporator Fan Performance — 7½-Ton — YSC090,092A3,A4,AW *M — Medium Heat —Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied 2-HP Standard Motor & Drive
Low Static Drive (1)
2400 680 0.57 729 0.65 778 0.74 823 0.84 862 0.92 900 1.00 936 1.10 972 1.20 1006 1.31 1041 1.41
2700 756 0.79 795 0.87 841 0.97 884 1.08 923 1.18 959 1.27 992 1.36 1025 1.47 1057 1.58 1089 1.70
3000 833 1.07 865 1.16 906 1.25 946 1.36 985 1.49 1020 1.61 1052 1.71 1083 1.81 1114 1.91 1143 2.03
3300 910 1.41 938 1.50 972 1.60 1010 1.70 1047 1.84 1081 1.97 1114 2.11 1144 2.22 1173 2.33 1200 2.44
3600 988 1.81 1014 1.91 1042 2.01 1076 2.12 1110 2.25 1143 2.39 1175 2.54 1205 2.69 1234 2.82 1260 2.94
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at 2-HP Standard Motor & High
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as Static Drive (or 3-HP Oversized
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Motor)
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Motor Sheave 1VL40L x 7/8 and Fan Sheave AK71 required.
Table PD-44 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor 2-HP Standard Motor & High Static Drive Kit
& Drive (or 3-HP Oversized Motor & Drive)
2400 1076 1.51 1110 1.62 1143 1.72 1176 1.83 1206 1.94 1238 2.05 1267 2.16 1297 2.28 1325 2.40 1353 2.52
2700 1120 1.82 1152 1.93 1183 2.05 1214 2.17 1243 2.28 1273 2.40 1302 2.52 1330 2.64 1357 2.76 1385 2.89
3000 1172 2.15 1201 2.29 1229 2.42 1257 2.55 1285 2.68 1312 2.80 1340 2.93 1367 3.06 1395 3.19 1421 3.33
3300 1227 2.56 1255 2.69 1281 2.83 1307 2.97 1333 3.11 1359 3.26 1384 3.40 — — — — — —
3600 1287 3.06 1312 3.18 1337 3.31 1361 3.45 — — — — — — — — — — — —
3-HP Oversized Motor & Drive

Table PD-45 — Belt Drive Evaporator Fan Performance — 7½-Ton — YSC090,092A3,A4,AW, AK *H— High Heat —Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied 2-HP Standard Motor & Drive
Low Static Drive (1)
2400 713 0.62 764 0.71 811 0.81 851 0.89 889 0.97 926 1.07 962 1.17 997 1.28 1031 1.38 1067 1.48
2700 790 0.86 837 0.96 880 1.07 919 1.17 955 1.26 989 1.36 1022 1.46 1054 1.57 1086 1.69 1117 1.80
3000 869 1.16 910 1.26 950 1.38 989 1.50 1023 1.62 1056 1.72 1086 1.82 1116 1.92 1146 2.04 1175 2.17
3300 949 1.53 985 1.63 1023 1.75 1058 1.88 1092 2.02 1124 2.15 1154 2.26 1182 2.37 1210 2.48 1237 2.60
3600 1029 1.97 1061 2.07 1096 2.19 1130 2.33 1162 2.48 1193 2.63 1222 2.77 1250 2.89 1276 3.01 1302 3.13
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at 2-HP Standard Motor & High Static
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as Drive (or 3-HP Oversized Motor)
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750..
1. Field Supplied Motor Sheave 1VL40L x 7/8 and Fan Sheave AK71 required.

Table PD-45 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard 2-HP Standard Motor & High Static Drive Kit
Motor & Drive (or 3-HP Oversized Motor & Drive)
2400 1101 1.59 1134 1.69 1166 1.80 1197 1.90 1229 2.02 1259 2.13 1287 2.25 1317 2.37 1344 2.48 1373 2.61
2700 1148 1.92 1180 2.04 1210 2.15 1241 2.27 1269 2.39 1299 2.51 1326 2.62 1354 2.74 1383 2.88 1409 3.00
3000 1204 2.30 1232 2.43 1260 2.56 1287 2.69 1316 2.82 1344 2.95 1370 3.07 1397 3.20 1423 3.34 — —
3300 1264 2.74 1290 2.87 1316 3.02 1342 3.16 1367 3.30 1393 3.45 — — — — — — — —
3600 1327 3.26 1352 3.39 — — — — — — — — — — — — — — — —
3-HP Oversized Motor & Drive

50 RT-PRC006-EN
Performance (8½ Ton)
Data Standard Efficiency

Table PD-46 — Belt Drive Evaporator Fan Performance — 8½-Ton — YSC102A3,A4,AW, AK *L,M — Low and Medium Heat —DownflowAirflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied 2-HP Standard Motor & Drive
Low Static Drive (1)
2720 — — — — 608 0.59 649 0.70 689 0.82 728 0.94 764 1.06 798 1.19 829 1.33 859 1.46
3060 — — 615 0.65 654 0.75 692 0.87 728 0.99 764 1.13 799 1.26 833 1.39 864 1.53 894 1.68
3400 625 0.72 665 0.83 702 0.95 736 1.06 770 1.19 804 1.34 836 1.49 868 1.63 899 1.78 928 1.93
3740 681 0.93 716 1.05 752 1.18 784 1.31 815 1.44 846 1.58 876 1.74 906 1.90 935 2.06 963 2.22
4080 737 1.19 769 1.31 802 1.45 833 1.60 862 1.73 891 1.87 919 2.03 947 2.20 974 2.37 1001 2.55
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature motor
Refer to Table PD-89 to determine additional static pressure drop failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.

Table PD-46 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
2720 888 1.61 916 1.76 943 1.91 970 2.07 996 2.22 1021 2.37 1046 2.53 1071 2.69 1096 2.86 1119 3.02
3060 922 1.82 949 1.98 976 2.14 1001 2.31 1026 2.47 1051 2.65 1074 2.81 1098 2.99 1120 3.16 1144 3.34
3400 957 2.08 984 2.24 1011 2.41 1035 2.58 1060 2.75 1083 2.93 1106 3.11 1128 3.29 — — — —
3740 992 2.39 1018 2.55 1045 2.72 1070 2.90 1095 3.08 1117 3.25 1140 3.44 — — — — — —
4080 1028 2.73 1053 2.90 1079 3.07 1104 3.26 1128 3.44 — — — — — — — — — —

Table PD-47 — Belt Drive Evaporator Fan Performance — 8½-Ton — YSC102A3,A4,AW, AK *H— High Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied 2-HP Standard Motor & Drive
Low Static Drive (1)
2720 — — — — 619 0.62 661 0.74 700 0.85 738 0.97 773 1.09 807 1.23 838 1.36 868 1.51
3060 586 0.58 629 0.68 667 0.79 705 0.91 741 1.04 776 1.17 810 1.30 843 1.44 874 1.58 904 1.72
3400 642 0.76 681 0.88 717 1.00 751 1.12 785 1.25 817 1.40 849 1.55 881 1.69 911 1.84 940 1.99
3740 698 0.99 735 1.12 769 1.25 800 1.37 831 1.51 862 1.66 892 1.82 920 1.98 950 2.14 977 2.30
4080 756 1.26 789 1.40 821 1.54 851 1.68 879 1.82 908 1.97 936 2.13 964 2.30 991 2.48 1017 2.66
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.

Table PD-47 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
2720 896 1.65 923 1.80 950 1.95 977 2.11 1003 2.26 1029 2.42 1053 2.57 1078 2.74 1102 2.90 1124 3.06
3060 932 1.88 959 2.04 985 2.20 1010 2.36 1034 2.53 1058 2.70 1082 2.87 1105 3.05 1129 3.22 1151 3.39
3400 969 2.15 996 2.31 1020 2.48 1045 2.65 1070 2.83 1093 3.00 1116 3.19 1138 3.37 — — — —
3740 1005 2.47 1032 2.64 1058 2.81 1083 2.99 1106 3.16 1129 3.35 — — — — — — — —
4080 1044 2.83 1069 3.01 1095 3.19 1119 3.37 — — — — — — — — — — — —

RT-PRC006-EN 51
Performance (8½ Ton)
Data Standard Efficiency

Table PD-48 — Belt Drive Evaporator Fan Performance — 8½-Ton — YSC102A3,A4,AW, AK *L,M — Low and Medium Heat —Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied 2-HP Standard Motor & Drive
Low Static Drive (1)
2720 607 0.59 655 0.69 697 0.80 744 0.93 791 1.07 834 1.21 871 1.34 904 1.46 933 1.58 962 1.70
3060 672 0.81 715 0.92 755 1.04 792 1.16 834 1.31 876 1.47 917 1.63 953 1.78 985 1.93 1013 2.06
3400 739 1.09 776 1.20 814 1.34 849 1.47 882 1.61 920 1.77 958 1.94 996 2.12 1030 2.29 1063 2.47
3740 807 1.43 839 1.54 875 1.69 907 1.83 938 1.98 969 2.13 1003 2.30 1037 2.49 1072 2.69 1106 2.88
4080 875 1.83 903 1.95 935 2.10 968 2.26 997 2.42 1025 2.58 1053 2.74 1084 2.93 1116 3.13 1148 3.34
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.

Table PD-48 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
2720 988 1.81 1013 1.93 1037 2.05 1061 2.17 1084 2.28 1106 2.40 1128 2.52 1150 2.64 1172 2.76 1192 2.88
3060 1040 2.19 1065 2.33 1090 2.46 1113 2.59 1136 2.72 1158 2.86 1179 2.99 1199 3.12 1220 3.25 1239 3.38
3400 1091 2.62 1117 2.78 1141 2.92 1165 3.07 1188 3.22 1210 3.37 — — — — — — — —
3740 1137 3.07 1166 3.27 1193 3.44 — — — — — — — — — — — — — —
4080 — — — — — — — — — — — — — — — — — — — —

Table PD-49 — Belt Drive Evaporator Fan Performance — 8½-Ton — YSC102A3,A4,AW, AK *H— High Heat —Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied 2-HP Standard Motor & Drive
Low Static Drive (1)
2720 625 0.63 671 0.73 713 0.84 762 0.98 807 1.12 849 1.26 883 1.38 915 1.50 944 1.62 971 1.74
3060 692 0.86 734 0.98 772 1.10 811 1.23 854 1.38 896 1.54 934 1.70 969 1.85 997 1.99 1026 2.12
3400 760 1.15 799 1.28 834 1.41 868 1.55 903 1.70 942 1.87 980 2.04 1016 2.22 1049 2.39 1079 2.56
3740 828 1.50 863 1.64 898 1.79 929 1.94 960 2.08 993 2.25 1027 2.44 1062 2.63 1096 2.82 1127 3.02
4080 898 1.92 929 2.07 962 2.23 992 2.39 1020 2.55 1048 2.71 1078 2.89 1110 3.09 1142 3.30 — —
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.

Table PD-49 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
2720 998 1.86 1022 1.97 1046 2.09 1069 2.21 1092 2.33 1115 2.45 1136 2.56 1158 2.69 1179 2.80 1200 2.93
3060 1052 2.26 1077 2.39 1101 2.52 1124 2.66 1146 2.79 1167 2.92 1188 3.05 1209 3.18 1229 3.31 1249 3.45
3400 1106 2.71 1131 2.86 1155 3.01 1179 3.16 1202 3.31 1222 3.45 — — — — — — — —
3740 1157 3.21 1185 3.39 — — — — — — — — — — — — — — — —
4080 — — — — — — — — — — — — — — — — — — — —

52 RT-PRC006-EN
Performance (10 Ton)
Data Standard Efficiency

Table PD-50 — Belt Drive Evaporator Fan Performance — 10-Ton — YSC120A3,A4,AW, AK *L,M — Low and Medium Heat — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Field Supplied
Low Static Drive (1)
3200 — — — — — — 727 1.00 763 1.14 798 1.28 832 1.42 863 1.56 895 1.71 924 1.86
3600 — — 717 1.03 751 1.15 784 1.28 816 1.42 848 1.57 879 1.73 910 1.89 940 2.05 968 2.20
4000 746 1.21 780 1.35 813 1.49 843 1.62 873 1.76 902 1.92 931 2.09 959 2.26 986 2.43 1014 2.61
4400 814 1.57 845 1.73 876 1.88 905 2.03 932 2.18 959 2.34 985 2.51 1012 2.69 1037 2.88 1063 3.07
4800 883 2.02 911 2.18 940 2.35 967 2.52 993 2.68 1018 2.84 1042 3.01 1067 3.20 1091 3.39 1115 3.59
3-HP Standard Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at 5-HP Oversized
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as Motor & Drive
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. Field Supplied Motor Sheave 1VM50 x 7/8”, Fan Sheave AK89 and Belt AX40 required.

Table PD-50 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Drive
3200 952 2.01 979 2.18 1004 2.34 1029 2.51 1053 2.68 1078 2.86 1101 3.04 1124 3.23 1146 3.41 1169 3.59
3600 996 2.37 1023 2.53 1049 2.71 1073 2.88 1097 3.07 1120 3.25 1142 3.43 1164 3.63 1186 3.83 1207 4.02
4000 1041 2.79 1067 2.96 1092 3.14 1117 3.33 1141 3.51 1164 3.70 1186 3.90 1208 4.10 1228 4.30 1249 4.51
4400 1088 3.26 1113 3.45 1137 3.64 1162 3.84 1185 4.04 1207 4.23 1229 4.43 1252 4.65 1273 4.85 1293 5.06
4800 1139 3.80 1161 4.00 1185 4.22 1208 4.43 1230 4.63 1253 4.85 1275 5.06 1295 5.27 1317 5.49 1337 5.71
5-HP Oversized Motor & Drive

Table PD-51— Belt Drive Evaporator Fan Performance — 10-Ton — YSC120A3,A4,AW, AK *H— High Heat — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Field Supplied
Low Static Drive (1)
3200 — — — — 723 0.99 759 1.12 793 1.26 827 1.40 860 1.55 891 1.69 921 1.84 949 2.00
3600 721 1.04 755 1.17 787 1.29 820 1.44 851 1.59 882 1.75 913 1.90 942 2.06 971 2.22 999 2.39
4000 793 1.40 824 1.54 854 1.67 883 1.82 913 1.98 941 2.15 969 2.32 997 2.50 1024 2.67 1050 2.85
4400 866 1.83 895 1.98 923 2.13 949 2.28 976 2.45 1003 2.63 1029 2.81 1054 3.00 1079 3.20 1104 3.39
4800 939 2.34 967 2.51 992 2.67 1017 2.84 1042 3.01 1066 3.19 1090 3.38 1114 3.58 1138 3.79 1161 4.00
3-HP Standard Motor & Drive 5-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. Field Supplied Motor Sheave 1VM50 x 7/8”, Fan Sheave AK89 and Belt AX40 required.

Table PD-51 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Drive
3200 976 2.16 1001 2.32 1027 2.49 1051 2.66 1075 2.84 1098 3.02 1120 3.19 1143 3.38 1166 3.57 1189 3.75
3600 1025 2.55 1052 2.73 1076 2.90 1100 3.09 1122 3.27 1145 3.46 1167 3.66 1188 3.85 1210 4.05 1230 4.25
4000 1076 3.03 1101 3.20 1126 3.40 1149 3.58 1172 3.77 1194 3.97 1216 4.18 1236 4.38 1257 4.59 1277 4.80
4400 1129 3.58 1153 3.77 1176 3.97 1200 4.17 1222 4.37 1244 4.57 1266 4.78 1286 4.99 1307 5.21 1326 5.43
4800 1184 4.21 1207 4.42 1229 4.63 1252 4.84 1274 5.06 1295 5.27 1315 5.48 1336 5.70 — — — —
5-HP Oversized Motor & Drive

RT-PRC006-EN 53
Performance (10 Ton)
Data Standard Efficiency

Table PD-52 — Belt Drive Evaporator Fan Performance — 10-Ton — YSC120A3,A4,AW, AK *L,M — Low and Medium Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Field Supplied 3-HP Standard Motor & Drive
Low Static Drive (1)
3200 — — 761 1.10 798 1.22 834 1.35 875 1.51 916 1.68 955 1.85 991 2.01 1022 2.16 1050 2.31
3600 799 1.35 836 1.48 872 1.63 904 1.77 936 1.91 972 2.09 1009 2.28 1045 2.47 1079 2.66 1111 2.84
4000 881 1.81 913 1.96 947 2.12 977 2.28 1006 2.44 1035 2.60 1066 2.78 1100 2.99 1133 3.20 1165 3.41
4400 963 2.39 992 2.54 1023 2.71 1052 2.89 1079 3.06 1106 3.23 1132 3.41 1160 3.61 1189 3.82 1219 4.05
4800 1045 3.07 1072 3.23 1099 3.41 1127 3.61 1154 3.80 1179 3.98 1203 4.17 1227 4.36 1251 4.56 1278 4.80
5-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature motor
Refer to Table PD-89 to determine additional static pressure drop failure. Our product’s warranty will not be affected.
due to other options/accessories
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. Field Supplied Motor Sheave 1VM50 x 7/8”, Fan Sheave AK89 and Belt AX40 required.
Table PD-52 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Drive 5-HP Oversized Motor & Drive
3200 1077 2.45 1103 2.60 1126 2.73 1150 2.87 1171 3.01 1193 3.15 1214 3.29 1233 3.42 1253 3.56 1274 3.71
3600 1140 3.02 1165 3.18 1190 3.34 1214 3.51 1235 3.66 1257 3.82 1279 3.98 1298 4.13 1317 4.28 1338 4.45
4000 1196 3.62 1225 3.83 1252 4.03 1276 4.22 1299 4.40 1321 4.58 1342 4.76 1363 4.94 1383 5.11 1401 5.28
4400 1250 4.28 1280 4.52 1307 4.75 1334 4.98 1359 5.20 1384 5.43 1405 5.62 — — — — — —
4800 1305 5.03 1334 5.28 1361 5.54 — — — — — — — — — — — — — —

Table PD-53 — Belt Drive Evaporator Fan Performance — 10-Ton — YSC120A3,A4,AW, AK *H— High Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Field Supplied 3-HP Standard Motor & Drive
Low Static Drive (1)
3200 768 1.12 805 1.25 842 1.38 884 1.54 924 1.71 962 1.88 998 2.04 1028 2.19 1055 2.34 1082 2.48
3600 856 1.56 888 1.70 921 1.84 955 2.00 992 2.19 1028 2.37 1063 2.57 1096 2.75 1126 2.93 1153 3.10
4000 943 2.10 973 2.26 1002 2.41 1031 2.58 1062 2.76 1096 2.96 1129 3.17 1161 3.38 1192 3.59 1222 3.81
4400 1031 2.76 1060 2.94 1086 3.11 1113 3.28 1139 3.45 1167 3.66 1198 3.89 1228 4.11 1257 4.34 1287 4.58
4800 1119 3.45 1146 3.74 1171 3.93 1195 4.11 1219 4.30 1243 4.50 1270 4.72 1297 4.96 1325 5.21 1353 5.46
5-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
NOTES: Trane’s factory supplied motors, in commercial equipment, are definite purpose
Data includes pressure drop due to standard filters and wet coils. motors, specifically designed and tested to operate reliably and continuously at
No accessories or options are included in pressure drop data. all cataloged conditions. Using the full horsepower range of our fan motors as
Refer to Table PD-89 to determine additional static pressure drop shown in our tabular data will not result in nuisance tripping or premature
due to other options/accessories motor failure. Our product’s warranty will not be affected.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. Field Supplied Motor Sheave 1VM50 x 7/8”, Fan Sheave AK89 and Belt AX40 required.

Table PD-53 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Drive 5-HP Oversized Motor & Drive
3200 1107 2.62 1131 2.76 1154 2.90 1176 3.04 1197 3.17 1218 3.32 1238 3.46 1257 3.59 1276 3.73 1296 3.87
3600 1178 3.27 1202 3.42 1224 3.58 1247 3.74 1268 3.90 1288 4.05 1308 4.21 1328 4.37 1346 4.52 1366 4.69
4000 1249 4.01 1273 4.19 1296 4.38 1318 4.56 1339 4.73 1361 4.91 1380 5.08 1399 5.26 1418 5.44 — —
4400 1315 4.81 1340 5.03 1366 5.26 1389 5.48 1410 5.67 — — — — — — — — — —
4800 1379 5.71 — — — — — — — — — — — — — — — — — —

54 RT-PRC006-EN
Performance (3 - 5 Tons)
Data High Efficiency

Table PD-54— Direct Drive Evaporator Fan Performance 3, 4 And 5 Ton YHC036A**L,M, YHC048A**L,M, YHC060A**L,M
— Low and Medium Heat
External Static Pressure (Inches of Water) & Motor Power (Bhp)1
Standard Motor Oversized Motor2
Unit High Speed Low Speed High Speed Low Speed
Tons Model No. CFM ESP BHP ESP BHP ESP BHP ESP BHP
960 0.74 0.36 0.56 0.28 0.89 0.38 0.82 0.35
1020 0.69 0.37 0.49 0.28 0.85 0.39 0.77 0.36
1080 0.65 0.38 0.44 0.29 0.82 0.41 0.74 0.38
1140 0.61 0.39 0.37 0.29 0.77 0.43 0.69 0.40
3 YHC036A**L,M 1200 0.55 0.40 0.29 0.30 0.74 0.44 0.65 0.41
Horizontal Airflow 1260 0.51 0.41 0.19 0.30 0.70 0.45 0.61 0.42
1320 0.46 0.42 0.10 0.31 0.67 0.47 0.57 0.44
1380 0.41 0.43 0.00 0.31 0.64 0.48 0.52 0.45
1440 0.34 0.44 — — 0.57 0.51 0.45 0.48
1280 0.85 0.53 0.74 0.47 1.11 0.67 0.90 0.56
1360 0.78 0.54 0.66 0.47 1.06 0.68 0.85 0.58
1440 0.71 0.54 0.60 0.48 1.01 0.70 0.80 0.60
1520 0.64 0.55 0.51 0.48 0.96 0.73 0.72 0.63
YHC048A**L,M 1600 0.55 0.55 0.39 0.49 0.89 0.75 0.63 0.64
4
Horizontal Airflow 1680 0.46 0.56 0.27 0.49 0.84 0.78 0.54 0.66
1760 0.37 0.56 0.12 0.50 0.79 0.82 0.37 0.68
1840 0.26 0.57 0.00 0.50 0.70 0.83 0.24 0.70
1920 0.16 0.57 — — 0.62 0.85 0.13 0.73
1600 0.99 0.78 0.89 0.64 1.32 0.90 1.18 0.85
1700 0.92 0.80 0.76 0.65 1.24 0.94 1.08 0.89
1800 0.87 0.85 0.65 0.65 1.16 0.98 0.97 0.91
1900 0.77 0.88 0.56 0.65 1.15 1.02 0.87 0.94
YHC060A**L,M 2000 0.69 0.90 0.40 0.66 0.98 1.05 0.76 0.95
5
Horizontal Airflow 2100 0.59 0.93 0.25 0.66 0.89 1.10 0.63 0.96
2200 0.46 0.94 0.10 0.67 0.78 1.12 0.42 0.96
2300 0.37 0.95 — — 0.68 1.17 0.18 0.97
2400 0.26 0.97 — — 0.55 1.20 — —
960 0.74 0.36 0.56 0.28 0.89 0.38 0.82 0.35
1020 0.69 0.37 0.49 0.28 0.85 0.39 0.77 0.36
1080 0.65 0.38 0.44 0.29 0.82 0.41 0.74 0.38
1140 0.61 0.39 0.37 0.29 0.77 0.43 0.69 0.40
3 YHC036A**L,M 1200 0.55 0.40 0.29 0.30 0.74 0.44 0.65 0.41
Downflow Airflow 1260 0.51 0.41 0.19 0.30 0.70 0.45 0.61 0.42
1320 0.46 0.42 0.10 0.31 0.67 0.47 0.57 0.44
1380 0.41 0.43 0.00 0.31 0.64 0.48 0.52 0.45
1440 0.34 0.44 — — 0.57 0.51 0.45 0.48
1280 0.90 0.53 0.79 0.47 1.16 0.67 0.95 0.56
1360 0.83 0.54 0.71 0.47 1.11 0.68 0.90 0.58
1440 0.76 0.54 0.65 0.48 1.06 0.70 0.85 0.60
1520 0.69 0.55 0.56 0.48 1.01 0.73 0.77 0.63
YHC048A**L,M 1600 0.60 0.55 0.44 0.49 0.94 0.75 0.68 0.64
4
Downflow Airflow 1680 0.51 0.56 0.32 0.49 0.89 0.78 0.59 0.66
1760 0.42 0.56 0.17 0.50 0.84 0.82 0.42 0.68
1840 0.31 0.57 0.05 0.50 0.75 0.83 0.29 0.70
1920 0.21 0.57 – — 0.67 0.85 — —
1600 1.04 0.78 0.94 0.64 1.37 0.90 1.23 0.85
1700 0.97 0.80 0.81 0.65 1.29 0.94 1.13 0.89
1800 0.92 0.85 0.70 0.65 1.21 0.98 1.02 0.91
1900 0.82 0.88 0.61 0.65 1.20 1.02 0.92 0.94
YHC060A**L,M 2000 0.74 0.90 0.45 0.66 1.03 1.05 0.81 0.95
5
Downflow Airflow 2100 0.64 0.93 0.30 0.66 0.94 1.10 0.68 0.96
2200 0.51 0.94 0.15 0.67 0.83 1.12 0.47 0.96
2300 0.42 0.95 — — 0.73 1.17 0.23 0.97
2400 0.31 0.97 — — 0.60 1.20 — —
Fan motor heat (MBH) = 3.72 x Fan Bhp + .24.
Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
NOTES:
1. Data includes pressure drop due to wet coil and filters.

RT-PRC006-EN 55
Performance (3 - 5 Tons)
Data High Efficiency

Table PD-55 — Direct Drive Evaporator Fan Performance 3, 4 And 5 Ton YHC036A**H, YHC048A**H, YHC060A**H
— High Heat
External Static Pressure (Inches of Water) & Motor Power (Bhp)1
Standard Motor Oversized Motor2
Unit High Speed Low Speed High Speed Low Speed
Tons Model No. CFM ESP BHP ESP BHP ESP BHP ESP BHP
960 0.74 0.36 0.56 0.28 0.89 0.38 0.82 0.35
1020 0.69 0.37 0.49 0.28 0.85 0.39 0.77 0.36
1080 0.65 0.38 0.44 0.29 0.82 0.41 0.74 0.38
1140 0.61 0.39 0.37 0.29 0.77 0.43 0.69 0.40
YHC036A**H 1200 0.55 0.40 0.29 0.30 0.74 0.44 0.65 0.41
3
Horizontal Airflow 1260 0.51 0.41 0.19 0.30 0.70 0.45 0.61 0.42
1320 0.46 0.42 0.10 0.31 0.67 0.47 0.57 0.44
1380 0.41 0.43 0.00 0.31 0.64 0.48 0.52 0.45
1440 0.34 0.44 — — 0.57 0.51 0.45 0.48
1280 0.85 0.53 0.74 0.47 1.11 0.67 0.90 0.56
1360 0.78 0.54 0.66 0.47 1.06 0.68 0.85 0.58
1440 0.71 0.54 0.60 0.48 1.01 0.70 0.80 0.60
1520 0.64 0.55 0.51 0.48 0.96 0.73 0.72 0.63
4 YHC048A**H 1600 0.55 0.55 0.39 0.49 0.89 0.75 0.63 0.64
Horizontal Airflow 1680 0.46 0.56 0.27 0.49 0.84 0.78 0.54 0.66
1760 0.37 0.56 0.12 0.50 0.79 0.82 0.37 0.68
1840 0.26 0.57 0.00 0.50 0.70 0.83 0.24 0.70
1920 0.16 0.57 — — 0.62 0.85 0.13 0.73
1600 0.94 0.78 0.84 0.64 1.27 0.90 1.13 0.85
1700 0.87 0.80 0.71 0.65 1.19 0.94 1.03 0.89
1800 0.82 0.85 0.60 0.65 1.11 0.98 0.92 0.91
1900 0.72 0.88 0.51 0.65 1.10 1.02 0.82 0.94
YHC060A**H 2000 0.64 0.90 0.35 0.66 0.93 1.05 0.71 0.95
5
Horizontal Airflow 2100 0.54 0.93 0.20 0.66 0.84 1.10 0.58 0.96
2200 0.41 0.94 0.05 0.67 0.73 1.12 0.37 0.96
2300 0.32 0.95 — — 0.63 1.17 0.13 0.97
2400 0.21 0.97 — — 0.50 1.20 — —
960 0.74 0.36 0.56 0.28 0.89 0.38 0.82 0.35
1020 0.69 0.37 0.49 0.28 0.85 0.39 0.77 0.36
1080 0.65 0.38 0.44 0.29 0.82 0.41 0.74 0.38
1140 0.61 0.39 0.37 0.29 0.77 0.43 0.69 0.40
YHC036A**H 1200 0.55 0.40 0.29 0.30 0.74 0.44 0.65 0.41
3
Downflow Airflow 1260 0.51 0.41 0.19 0.30 0.70 0.45 0.61 0.42
1320 0.46 0.42 0.10 0.31 0.67 0.47 0.57 0.44
1380 0.41 0.43 0.00 0.31 0.64 0.48 0.52 0.45
1440 0.34 0.44 — — 0.57 0.51 — —
1280 0.90 0.53 0.79 0.47 1.16 0.67 0.95 0.56
1360 0.83 0.54 0.71 0.47 1.11 0.68 0.90 0.58
1440 0.76 0.54 0.65 0.48 1.06 0.70 0.85 0.60
1520 0.69 0.55 0.56 0.48 1.01 0.73 0.77 0.63
4 YHC048A**H 1600 0.60 0.55 0.44 0.49 0.94 0.75 0.68 0.64
Downflow Airflow 1680 0.51 0.56 0.32 0.49 0.89 0.78 0.59 0.66
1760 0.42 0.56 0.17 0.50 0.84 0.82 0.42 0.68
1840 0.31 0.57 0.05 0.50 0.75 0.83 0.29 0.70
1920 0.21 0.57 — — 0.67 0.85 — —
1600 0.99 0.78 0.89 0.64 1.32 0.90 1.18 0.85
1700 0.92 0.80 0.76 0.65 1.24 0.94 1.08 0.89
1800 0.87 0.85 0.65 0.65 1.16 0.98 0.97 0.91
1900 0.77 0.88 0.56 0.65 1.15 1.02 0.87 0.94
YHC060A**H 2000 0.69 0.90 0.40 0.66 0.98 1.05 0.76 0.95
5
Downflow Airflow 2100 0.59 0.93 0.25 0.66 0.89 1.10 0.63 0.96
2200 0.46 0.94 0.10 0.67 0.78 1.12 0.42 0.96
2300 0.37 0.95 0.00 0.68 0.68 1.17 0.18 0.97
2400 0.26 0.97 — — 0.55 1.20 — —
Fan motor heat (MBH) = 3.72 x Fan Bhp + .24.
Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
NOTES:
1. Data includes pressure drop due to wet coil and filters.
2. 5 Ton oversized motor peformance is with 12 x 11 FC Centrifugal blower fan.

56 RT-PRC006-EN
Performance (3 Ton)
Data High Efficiency

Table PD-56 — Evaporator Fan Performance — 3 Ton — YHC036A3,A4,AW*L, M — Low and Medium Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
960 — — 570 0.14 634 0.18 690 0.22 741 0.27 791 0.31 836 0.36 879 0.41 922 0.46 961 0.52
1080 537 0.14 606 0.18 669 0.23 724 0.27 773 0.32 819 0.36 864 0.41 906 0.47 946 0.52 985 0.58
1200 581 0.18 645 0.22 705 0.27 759 0.33 807 0.38 851 0.42 894 0.48 935 0.53 973 0.59 1011 0.65
1320 627 0.23 686 0.28 742 0.33 795 0.39 842 0.44 885 0.50 927 0.55 966 0.61 1003 0.67 1040 0.73
1440 673 0.29 728 0.34 780 0.39 831 0.45 878 0.52 921 0.58 960 0.64 998 0.69 1034 0.76 1070 0.82

For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK69 required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.

Table PD-56 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
960 1000 0.57 1037 0.63 1072 0.69 1106 0.75 1139 0.81
1080 1022 0.64 1058 0.70 1093 0.76 1127 0.82 1161 0.89
1200 1047 0.71 1083 0.77 1117 0.83 1150 0.90 1183 0.97
1320 1075 0.79 1108 0.85 1141 0.92 1174 0.99 1206 1.06
1440 1104 0.88 1137 0.95 1170 1.02 1201 1.09 1231 1.16

1-HP Standard Motor &


Field Supplied High Static Drive (2)

Table PD-57 — Evaporator Fan Performance — 3 Ton — YHC036A3,A4,AW*L, M — Low and Medium Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
960 552 0.13 631 0.17 699 0.22 759 0.27 811 0.33 858 0.38 902 0.44 943 0.49 980 0.54 1017 0.60
1080 598 0.17 675 0.22 739 0.27 798 0.33 850 0.38 898 0.44 941 0.50 982 0.57 1020 0.63 1056 0.69
1200 645 0.22 720 0.28 781 0.33 837 0.39 889 0.45 937 0.51 981 0.58 1021 0.65 1059 0.72 1095 0.79
1320 693 0.28 766 0.34 825 0.40 879 0.47 929 0.53 976 0.60 1020 0.67 1061 0.74 1099 0.81 1135 0.89
1440 743 0.35 811 0.42 871 0.49 922 0.55 970 0.62 1016 0.69 1059 0.77 1099 0.84 1138 0.92 1174 1.00
1-HP Standard
Motor & Field Supplied
High Static Drive (2)
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK69 required. Field Supplied Belt
may be necessary. Table PD-57 — Continued
2. Field Supplied Fan Sheave AK41 required.Field Supplied Belt
may be necessary. External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
960 1052 0.65 1086 0.71 1120 0.77 1152 0.83 1185 0.90
1080 1090 0.75 1123 0.81 1154 0.87 1185 0.93 1215 0.99
1200 1130 0.86 1162 0.92 1193 0.99 1224 1.05 1253 1.12
1320 1169 0.96 1203 1.04 1233 1.12 1263 1.19 1292 1.26
1440 1208 1.08 1241 1.16 1273 1.25 1303 1.33 1332 1.41
1-HP Standard Motor &
Field Supplied High Static Drive (2)

RT-PRC006-EN 57
Performance (3 Ton)
Data High Efficiency

Table PD-58— Belt Drive Evaporator Fan Performance — 3 Ton — YHC036A3,A4,AW*H — High Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
960 503 0.11 578 0.15 641 0.19 696 0.23 747 0.27 796 0.32 841 0.36 884 0.42 926 0.47 966 0.52
1080 548 0.15 616 0.19 678 0.23 731 0.28 780 0.32 826 0.37 870 0.42 912 0.47 952 0.53 991 0.59
1200 593 0.19 657 0.23 716 0.28 768 0.33 815 0.38 859 0.43 901 0.49 942 0.54 980 0.60 1017 0.66
1320 640 0.24 698 0.29 754 0.34 806 0.40 852 0.45 895 0.51 935 0.56 974 0.62 1012 0.68 1048 0.74
1440 688 0.31 742 0.35 794 0.41 844 0.47 890 0.53 931 0.59 970 0.65 1009 0.71 1045 0.77 1080 0.84
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite
NOTES: purpose motors, specifically designed and tested to operate reliably and
Data includes pressure drop due to standard filters and wet coils. continuously at all cataloged conditions. Using the full horsepower range of
No accessories or options are included in pressure drop data. our fan motors as shown in our tabular data will not result in nuisance
Refer to Table PD-89 to determine additional static pressure drop tripping or premature motor failure. Our product’s warranty will not be
due to other options/accessories affected.
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK69 required. Field Supplied Belt
may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt
may be necessary.
Table PD-58— Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
960 1005 0.58 1041 0.64 1076 0.70 1110 0.76 1142 0.82
1080 1029 0.65 1064 0.71 1099 0.77 1133 0.83 1166 0.90
1200 1053 0.72 1089 0.78 1123 0.85 1156 0.91 1189 0.98
1320 1082 0.80 1116 0.87 1150 0.93 1182 1.00 1214 1.07
1440 1113 0.90 1146 0.97 1178 1.04 1209 1.11 1240 1.18
1-HP Standard Motor &
Field Supplied High Static Drive (2)

Table PD-59 — Belt Drive Evaporator Fan Performance — 3 Ton — YHC036A3,A4,AW*H — High Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
960 563 0.13 639 0.18 707 0.23 766 0.28 817 0.33 864 0.39 908 0.44 947 0.49 985 0.55 1020 0.60
1080 611 0.18 685 0.23 748 0.28 806 0.34 858 0.39 905 0.45 947 0.51 988 0.58 1026 0.64 1061 0.70
1200 660 0.23 732 0.29 792 0.34 847 0.40 899 0.46 945 0.53 989 0.59 1029 0.66 1066 0.73 1102 0.80
1320 711 0.29 781 0.36 838 0.42 890 0.48 940 0.55 986 0.61 1029 0.68 1070 0.76 1106 0.83 1142 0.90
1440 762 0.37 829 0.44 885 0.51 935 0.57 983 0.64 1028 0.71 1070 0.79 1111 0.86 1148 0.94 1183 1.02
1-HP Standard
Motor & Field Supplied
High Static Drive (2)
For Standard Evaporator Fan Speed (RPM), reference Table PD-85. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-88 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK69 required. Field Supplied Belt
may be necessary. Table PD-59 — Continued
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt
may be necessary. External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard 1-HP Standard Motor & Field
Motor & Drive Supplied High Static Drive (2)
960 1056 0.66 1090 0.71 1123 0.78 1156 0.84 1188 0.90
1080 1096 0.76 1128 0.82 1159 0.88 1190 0.94 1220 1.00
1200 1135 0.87 1168 0.93 1199 1.00 1229 1.07 1259 1.13
1320 1177 0.98 1209 1.06 1241 1.14 1270 1.21 1299 1.28
1440 1217 1.10 1250 1.18 1281 1.27 1311 1.35 1339 1.43

58 RT-PRC006-EN
Performance (4 Ton)
Data High Efficiency

Table PD-60 — Belt Drive Evaporator Fan Performance — 4 Ton — YHC048A3,A4,AW*L,M — Low and Medium Heat — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1280 614 0.22 675 0.26 733 0.31 787 0.37 834 0.42 878 0.48 919 0.53 959 0.59 997 0.65 1034 0.71
1440 676 0.30 731 0.34 784 0.39 835 0.46 883 0.52 925 0.58 965 0.64 1003 0.70 1039 0.76 1075 0.83
1600 739 0.40 789 0.45 838 0.50 885 0.56 931 0.63 973 0.70 1012 0.77 1049 0.84 1085 0.91 1118 0.97
1760 803 0.51 850 0.57 894 0.63 938 0.69 981 0.76 1021 0.83 1061 0.92 1097 0.99 1131 1.07 1164 1.14
1920 867 0.65 911 0.72 952 0.78 993 0.84 1033 0.91 1071 0.99 1110 1.07 1145 1.16 1180 1.25 1213 1.33

For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessoriesdue to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt
may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt
may be necessary. Table PD-60 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
1280 1069 0.77 1104 0.83 1138 0.90 1170 0.97 1203 1.04
1440 1109 0.89 1141 0.96 1175 1.03 1205 1.10 1236 1.17
1600 1151 1.04 1183 1.11 1215 1.19 1246 1.26 1275 1.33
1760 1197 1.21 1227 1.29 1258 1.36 1287 1.44 — —
1920 1243 1.41 1274 1.49 — — — — — —

1-HP Standard Motor & Field


Supplied High Static Drive (2)

Table PD-61— Belt Drive Evaporator Fan Performance — 4 Ton — YHC048A3,A4,AW*L,M — Low and Medium Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor &
Field Supplied Low Static Drive (1) 1-HP Standard Motor & Drive
1280 681 0.26 755 0.32 816 0.38 870 0.45 921 0.51 968 0.58 1013 0.65 1053 0.72 1091 0.79 1127 0.86
1440 748 0.36 817 0.43 876 0.49 927 0.56 976 0.63 1022 0.70 1065 0.78 1106 0.85 1144 0.93 1180 1.01
1600 816 0.47 879 0.55 937 0.62 987 0.70 1033 0.78 1076 0.85 1119 0.93 1158 1.01 1197 1.10 1233 1.18
1760 885 0.61 943 0.69 999 0.78 1049 0.86 1093 0.94 1135 1.03 1174 1.11 1213 1.20 1250 1.29 1286 1.38
1920 956 0.77 1009 0.86 1062 0.96 1110 1.05 1154 1.14 1195 1.23 1232 1.32 1269 1.41 1304 1.50 — —

For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024. 1-HP Standard Motor & Field
1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt Supplied High Static Drive (2)
may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt
may be necessary. Table PD-61 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard
Motor & Drive
1280 1162 0.94 1193 1.01 1225 1.09 1255 1.16 1284 1.23
1440 1214 1.09 1247 1.18 1278 1.26 1309 1.35 1337 1.43
1600 1268 1.27 1300 1.35 1332 1.45 — — — —
1760 1320 1.47 — — — — — — — —
1920 — — — — — — — — — —
1-HP Standard Motor & Field Supplied High Static Drive (2)

RT-PRC006-EN 59
Performance (4 Ton)
Data High Efficiency

Table PD-62 — Belt Drive Evaporator Fan Performance — 4 Ton — YHC048A3,A4,AW*H — High Heat — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1280 627 0.23 688 0.27 745 0.32 797 0.38 844 0.43 887 0.49 928 0.54 967 0.60 1006 0.66 1042 0.72
1440 691 0.31 746 0.36 798 0.41 848 0.47 894 0.54 936 0.60 975 0.66 1012 0.72 1049 0.78 1085 0.85
1600 756 0.41 806 0.47 854 0.52 901 0.58 945 0.66 987 0.73 1025 0.79 1061 0.86 1096 0.93 1129 1.00
1760 822 0.54 868 0.60 912 0.65 955 0.71 997 0.79 1038 0.87 1076 0.95 1111 1.02 1145 1.10 1178 1.17
1920 889 0.69 931 0.75 972 0.81 1012 0.88 1051 0.95 1090 1.03 1127 1.11 1162 1.20 1196 1.29 1228 1.37
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt
may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt
may be necessary.
Table PD-62 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
1280 1077 0.78 1112 0.85 1145 0.91 1178 0.98 1210 1.05
1440 1118 0.91 1150 0.98 1183 1.05 1214 1.12 1244 1.19
1600 1162 1.06 1193 1.13 1225 1.21 1255 1.28 1285 1.36
1760 1208 1.24 1239 1.32 1268 1.39 1297 1.47 — —
1920 1258 1.45 — — — — — — — —

1-HP Standard Motor & Field


Supplied High Static Drive (2)

Table PD-63 — Belt Drive Evaporator Fan Performance — 4 Ton — YHC048A3,A4,AW*H — High Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor &
Field Supplied Low Static Drive (1) 1-HP Standard Motor & Drive
1280 698 0.28 769 0.34 828 0.40 881 0.46 932 0.52 978 0.59 1021 0.66 1061 0.73 1099 0.81 1134 0.88
1440 767 0.37 834 0.44 890 0.51 941 0.58 988 0.65 1034 0.72 1077 0.80 1116 0.87 1153 0.95 1190 1.03
1600 837 0.50 899 0.57 955 0.65 1003 0.72 1048 0.80 1091 0.88 1132 0.96 1171 1.04 1209 1.12 1245 1.21
1760 908 0.64 966 0.73 1020 0.81 1067 0.89 1110 0.98 1151 1.06 1190 1.15 1228 1.23 1264 1.32 1300 1.41
1920 981 0.82 1035 0.91 1085 1.00 1133 1.09 1174 1.18 1213 1.27 1250 1.37 1286 1.46 — — — —
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt
1-HP Standard Motor & Field
may be necessary. Supplied High Static Drive (2)
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt
may be necessary.
Table PD-63 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard
Motor & Drive
1280 1169 0.96 1201 1.03 1231 1.10 1262 1.17 1290 1.24
1440 1222 1.11 1256 1.20 1286 1.28 1317 1.37 1346 1.45
1600 1278 1.29 1311 1.38 1342 1.48 — — — —
1760 — — — — — — — — — —
1920 — — — — — — — — —
1-HP Standard Motor & Field Supplied High Static Drive (2)

60 RT-PRC006-EN
Performance (5 Ton)
Data High Efficiency

Table PD-64 — Belt Drive Evaporator Fan Performance — 5 Ton — YHC060A3,A4,AW*L,M — Low and Medium Heat — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1600 704 0.36 757 0.41 806 0.47 853 0.52 899 0.58 942 0.65 984 0.72 1021 0.79 1058 0.85 1092 0.92
1800 777 0.49 828 0.56 872 0.62 915 0.67 957 0.73 998 0.80 1038 0.88 1076 0.96 1112 1.04 1146 1.11
2000 851 0.66 900 0.73 942 0.80 981 0.87 1019 0.93 1057 0.99 1094 1.07 1130 1.15 1165 1.24 1199 1.33
2200 927 0.86 973 0.94 1012 1.02 1049 1.09 1084 1.17 1119 1.23 1153 1.30 1188 1.38 1220 1.46 — —
2400 1003 1.10 1045 1.19 1084 1.28 1119 1.36 1152 1.44 — — — — — — — — — —
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
NOTES: Trane’s factory supplied motors, in commercial equipment, are definite purpose
Data includes pressure drop due to standard filters and wet coils. motors, specifically designed and tested to operate reliably and continuously at
No accessories or options are included in pressure drop data. all cataloged conditions. Using the full horsepower range of our fan motors as
Refer to Table PD-89 to determine additional static pressure drop shown in our tabular data will not result in nuisance tripping or premature
due to other options/accessories motor failure. Our product’s warranty will not be affected.
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt
may be necessary.

Table PD-64 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
1600 1125 0.98 1158 1.06 1190 1.13 1220 1.20 1250 1.27
1800 1178 1.19 1209 1.26 1239 1.33 1269 1.41 1296 1.48
2000 1232 1.42 1263 1.50 — — — — — —
2200 — — — — — — — — — —
2400 — — — — — — — — — —

Table PD-65 — Belt Drive Evaporator Fan Performance — 5 Ton — YHC060A3,A4,AW*L,M — Low and Medium Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor &
Field Supplied Low Static Drive (1) 1-HP Standard Motor & Drive
1600 775 0.42 837 0.50 898 0.57 952 0.65 1000 0.72 1044 0.79 1086 0.87 1127 0.95 1166 1.03 1203 1.11
1800 856 0.58 912 0.66 967 0.74 1020 0.83 1069 0.91 1112 1.00 1152 1.08 1189 1.16 1227 1.25 1263 1.34
2000 939 0.77 990 0.86 1040 0.96 1089 1.05 1136 1.14 1180 1.24 1219 1.33 1256 1.42 1292 1.50 — —
2200 1023 1.01 1070 1.11 1115 1.21 1160 1.31 1205 1.41 — — — — — — — — — —
2400 1108 1.29 1151 1.39 1193 1.50 — — — — — — — — — — — — — —
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt
may be necessary.

Table PD-65 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40
CFM RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard
Motor & Drive
1600 1239 1.19 1272 1.28 1304 1.37 1336 1.46
1800 1299 1.43 — — — — — —
2000 — — — — — — — —
2200 — — — — — — — —
2400 — — — — — — — —

RT-PRC006-EN 61
Performance (5 Ton)
Data High Efficiency

Table PD-66 — Belt Drive Evaporator Fan Performance — 5 Ton — YHC060A3,A4,AW*H — High Heat — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1600 723 0.38 774 0.43 822 0.48 869 0.54 914 0.60 957 0.68 997 0.75 1035 0.81 1070 0.88 1104 0.94
1800 801 0.52 847 0.58 891 0.64 933 0.70 975 0.76 1015 0.83 1054 0.91 1091 0.99 1126 1.07 1160 1.15
2000 878 0.70 922 0.77 962 0.84 1001 0.90 1039 0.96 1076 1.03 1113 1.11 1149 1.20 1183 1.28 1217 1.38
2200 957 0.91 999 0.99 1036 1.07 1072 1.14 1107 1.21 1142 1.28 1176 1.35 1209 1.43 — — — —
2400 1036 1.17 1076 1.26 1111 1.34 1144 1.42 1177 1.50 — — — — — — — — — —

For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt
may be necessary.

Table PD-66 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
1600 1137 1.01 1168 1.08 1199 1.15 1230 1.22 1260 1.29
1800 1191 1.22 1222 1.29 1252 1.37 1281 1.44 1310 1.50
1000 1248 1.46 — — — — — — — —
2200 — — — — — — — — — —
2400 — — — — — — — — — —

Table PD-67 — Belt Drive Evaporator Fan Performance — 5 Ton — YHC060A3,A4,AW*H — High Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & 1-HP Standard Motor & Drive
Field Supplied High Static Drive (1)
1600 796 0.45 858 0.52 917 0.60 969 0.67 1015 0.75 1059 0.82 1100 0.90 1141 0.98 1178 1.06 1216 1.14
1800 881 0.61 935 0.70 991 0.78 1042 0.87 1087 0.95 1129 1.03 1168 1.12 1206 1.20 1244 1.29 1279 1.38
2000 967 0.82 1016 0.91 1066 1.01 1115 1.10 1160 1.19 1201 1.28 1239 1.38 1275 1.47 — — — —
2200 1054 1.07 1099 1.17 1144 1.27 1189 1.38 1233 1.48 — — — — — — — — — —
2400 1141 1.37 1183 1.48 — — — — — — — — — — — — — — — —
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt
may be necessary.

Table PD-67 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
1600 1251 1.22 1283 1.31 1315 1.40 1345 1.49
1800 1313 1.47 — — — — — —
2000 — — — — — — — —
2200 — — — — — — — —
2400 — — — — — — — —

62 RT-PRC006-EN
Performance (6 Ton)
Data High Efficiency

Table PD-68— Belt Drive Evaporator Fan Performance — 6 Ton — YHC072A3,A4,AW*L,M — Low and Medium Heat — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1920 — — — — 597 0.37 652 0.44 700 0.51 745 0.58 788 0.66 829 0.74 869 0.82 906 0.91
2160 — — 575 0.38 629 0.46 683 0.54 730 0.62 774 0.70 815 0.78 854 0.86 893 0.95 929 1.04
2400 561 0.41 615 0.49 664 0.57 714 0.65 762 0.74 805 0.83 844 0.92 882 1.01 918 1.10 954 1.20
2640 606 0.53 657 0.62 703 0.70 747 0.79 792 0.88 835 0.98 875 1.08 912 1.18 947 1.27 980 1.37
2880 651 0.67 699 0.77 743 0.85 785 0.94 825 1.05 867 1.15 906 1.26 943 1.37 978 1.47 1010 1.58
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at 2-HP Oversized
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as Motor & Drive
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.

Table PD-68 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard 1-HP Standard Motor & High Static Drive Kit
Motor & Drive (or 2 HP Oversized Motor & Drive)
1920 941 0.99 977 1.07 1009 1.15 1041 1.23 1073 1.32 1103 1.40 1132 1.49 1159 1.57 1187 1.66 1213 1.75
2160 964 1.13 997 1.23 1031 1.32 1061 1.41 1093 1.50 1123 1.60 1151 1.69 1179 1.78 1207 1.87 1234 1.97
2400 988 1.29 1020 1.39 1054 1.50 1085 1.60 1114 1.70 1143 1.80 1171 1.90 1200 2.01 1227 2.11 1254 2.21
2640 1014 1.47 1046 1.58 1077 1.69 1107 1.80 1138 1.91 1166 2.02 1193 2.13 1222 2.25 — — — —
2880 1042 1.68 1073 1.79 1103 1.90 1132 2.02 1162 2.14 1190 2.26 — — — — — — — —
2-HP Oversized Motor & Drive

Table PD-69 — Belt Drive Evaporator Fan Performance — 6 Ton — YHC072A3,A4,AW*H — High Heat — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1920 — — 574 0.34 631 0.41 681 0.48 727 0.55 771 0.63 814 0.71 853 0.79 892 0.87 928 0.95
2160 562 0.36 616 0.44 671 0.52 719 0.60 763 0.68 805 0.76 845 0.84 884 0.93 921 1.02 957 1.11
2400 612 0.48 662 0.56 711 0.65 759 0.74 802 0.83 842 0.91 879 1.00 916 1.09 951 1.19 986 1.29
2640 663 0.63 709 0.71 754 0.80 798 0.90 842 1.00 881 1.10 917 1.19 951 1.29 986 1.39 1018 1.49
2880 715 0.80 758 0.88 799 0.98 840 1.08 880 1.19 920 1.30 955 1.41 990 1.51 1022 1.62 1053 1.72
2-HP Oversized
Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose 1-HP Standard Motor & High Static
NOTES: motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
Drive Kit (or 2-HP Oversized Motor)
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.

Table PD-69 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard 1-HP Standard Motor & High Static Drive Kit
Motor & Drive (or 2 HP Oversized Motor & Drive)
1920 963 1.04 997 1.12 1028 1.20 1061 1.28 1090 1.36 1119 1.45 1149 1.54 1177 1.63 1203 1.71 1229 1.80
2160 990 1.21 1023 1.30 1055 1.39 1086 1.48 1115 1.57 1144 1.66 1173 1.76 1200 1.85 1227 1.95 1253 2.04
2400 1019 1.39 1051 1.49 1083 1.60 1113 1.70 1141 1.80 1171 1.90 1199 2.01 1225 2.10 1252 2.20 — —
2640 1050 1.59 1081 1.70 1111 1.81 1141 1.93 1170 2.04 1198 2.15 1226 2.27 — — — — — —
2880 1084 1.83 1114 1.94 1143 2.06 1172 2.18 1199 2.30 — — — — — — — — — —

2-HP Oversized Motor & Drive

RT-PRC006-EN 63
Performance (6 Ton)
Data High Efficiency

Table PD-70 — Belt Drive Evaporator Fan Performance — 6 Ton — YHC072A3,A4,AW*L,M — Low and Medium Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1920 — — 591 0.34 649 0.42 699 0.48 745 0.56 789 0.64 834 0.72 877 0.81 918 0.89 957 0.97
2160 587 0.38 633 0.44 690 0.52 740 0.61 784 0.68 825 0.76 865 0.85 904 0.95 943 1.04 981 1.13
2400 643 0.51 682 0.58 732 0.65 781 0.75 825 0.84 864 0.92 902 1.01 938 1.11 974 1.21 1010 1.32
2640 700 0.66 736 0.74 775 0.81 822 0.90 866 1.01 906 1.11 942 1.20 976 1.29 1009 1.40 1042 1.51
2880 756 0.84 790 0.93 823 1.01 864 1.09 907 1.20 947 1.32 983 1.43 1017 1.53 1048 1.62 1080 1.73
2-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at 1-HP Standard Motor & High Static
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as Drive (or 2-HP Oversized Motor)
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.
2. Field Supplied Fan Sheave AK54 and Belt AX30 required.
Table PD-70 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard 1-HP Standard Motor & High Static
Motor & Drive Drive Kit(or 2 HP Oversized Motor & Drive)
1920 996 1.06 1033 1.16 1067 1.25 1102 1.35 1134 1.44 1165 1.53 1195 1.63 1223 1.72 1251 1.82 1277 1.91
2160 1018 1.23 1054 1.32 1090 1.42 1123 1.52 1156 1.63 1188 1.73 1218 1.84 1247 1.94 1276 2.05 1304 2.16
2400 1044 1.42 1079 1.52 1112 1.62 1145 1.73 1177 1.83 1208 1.94 1240 2.06 1268 2.17 1298 2.29 — —
2640 1075 1.62 1107 1.74 1139 1.85 1170 1.96 1201 2.08 1232 2.19 — — — — 2-HP Oversized Motor
2880 1111 1.85 1140 1.97 1169 2.09 1200 2.22 — — — — — — — — & FieldSupplied High
2-HP Oversized Motor & Drive Static Drive (2)
Table PD-71 — Belt Drive Evaporator Fan Performance — 6 Ton — YHC072A3,A4,AW*H — High Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1920 565 0.31 627 0.39 680 0.46 727 0.52 772 0.61 816 0.69 859 0.77 902 0.86 942 0.94 981 1.03
2160 621 0.43 677 0.50 729 0.59 774 0.66 816 0.74 856 0.83 895 0.93 934 1.02 973 1.11 1009 1.21
2400 680 0.57 729 0.65 778 0.74 823 0.84 862 0.92 900 1.00 936 1.10 972 1.20 1006 1.31 1041 1.41
2640 741 0.75 782 0.82 828 0.92 872 1.03 911 1.13 947 1.21 981 1.31 1014 1.41 1048 1.53 1079 1.64
2880 802 0.95 837 1.04 880 1.13 921 1.24 960 1.36 995 1.47 1028 1.56 1060 1.66 1091 1.77 1122 1.89
2-HP Oversized
Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose 1-HP Standard Motor & High Static
NOTES: motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
Drive Kit (or 2-HP Oversized Motor)
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.
2. Field Supplied Fan Sheave AK54 and Belt AX30 required.
Table PD-71 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & High Static Drive Kit
(or 2 HP Oversized Motor & Drive)
1920 1018 1.12 1054 1.21 1089 1.31 1122 1.40 1154 1.50 1184 1.59 1212 1.69 1241 1.78 1268 1.88 1293 1.97
2160 1045 1.30 1081 1.40 1114 1.50 1149 1.61 1181 1.71 1211 1.81 1241 1.92 1270 2.03 1298 2.13 1324 2.24
2400 1076 1.51 1110 1.62 1143 1.72 1176 1.83 1206 1.94 1238 2.05 1267 2.16 1297 2.28 — — — —
2640 1111 1.75 1144 1.87 1174 1.98 1205 2.09 1236 2.21 — — — — — — — — — —
2880 1151 2.02 1180 2.14 1209 2.27 — — — — — — — — — — — — — —
2-HP Oversized Motor & Drive 2-HP Oversized Motor & Field
Supplied High Static Drive (2)
64 RT-PRC006-EN
Performance (7½ Ton)
Data High Efficiency

Table PD-72 — Belt Drive Evaporator Fan Performance — 7½-Ton — YHC092A3,A4,AW *L,M — Low and Medium Heat —DownflowAirflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied
Low Static Drive (1)
2400 — — — — — — 613 0.58 656 0.68 696 0.79 732 0.91 765 1.03 798 1.16 829 1.30
2700 — — — — 605 0.58 647 0.69 687 0.81 726 0.93 762 1.05 796 1.18 828 1.32 857 1.45
3000 — — 606 0.62 645 0.72 684 0.83 721 0.96 758 1.09 792 1.22 826 1.36 858 1.49 888 1.64
3300 609 0.66 650 0.77 688 0.89 723 1.00 758 1.13 792 1.27 825 1.41 857 1.56 888 1.70 918 1.85
3600 658 0.84 695 0.96 731 1.08 764 1.20 796 1.33 828 1.47 859 1.63 890 1.79 920 1.94 949 2.10
2-HP Standard Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Table PD-72 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2400 858 1.43 888 1.57 917 1.71 945 1.85 971 1.99 998 2.14 1023 2.28 1048 2.44 1072 2.59 1095 2.75
2700 886 1.60 915 1.75 942 1.90 969 2.05 995 2.21 1020 2.36 1045 2.51 1069 2.67 1093 2.83 1117 3.00
3000 916 1.79 944 1.94 970 2.10 995 2.26 1020 2.43 1044 2.59 1069 2.76 1092 2.93 1116 3.10 1139 3.27
3300 947 2.01 974 2.16 1000 2.33 1026 2.50 1050 2.67 1073 2.84 1097 3.02 1119 3.20 1141 3.38 — —
3600 976 2.25 1004 2.42 1030 2.58 1056 2.76 1080 2.94 1103 3.12 1126 3.30 — — — — — —
3-HP Oversized Motor & Drive

Table PD-73 — Belt Drive Evaporator Fan Performance — 7½-Ton — YHC092A3,A4,AW *H — High Heat —DownflowAirflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied
Low Static Drive (1)
2400 — — — — — — 623 0.60 664 0.70 703 0.82 739 0.93 773 1.06 804 1.19 835 1.32
2700 — — — — 617 0.61 658 0.73 698 0.84 736 0.96 771 1.08 804 1.21 835 1.35 865 1.49
3000 — — 619 0.65 658 0.75 696 0.87 733 1.00 770 1.13 804 1.26 837 1.40 868 1.54 897 1.69
3300 625 0.70 666 0.82 702 0.93 737 1.05 771 1.19 805 1.33 838 1.47 870 1.62 900 1.76 929 1.91
3600 675 0.89 713 1.02 747 1.14 779 1.26 811 1.40 843 1.55 874 1.70 904 1.86 934 2.02 962 2.17
2-HP Standard Motor & Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Table PD-73 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2400 864 1.46 895 1.60 923 1.74 951 1.88 977 2.02 1003 2.17 1028 2.32 1053 2.47 1078 2.63 1100 2.78
2700 894 1.64 921 1.79 948 1.94 974 2.09 1001 2.24 1027 2.40 1052 2.56 1076 2.72 1100 2.88 1124 3.05
3000 925 1.83 952 1.99 978 2.15 1004 2.32 1029 2.48 1052 2.65 1076 2.82 1100 2.99 1123 3.15 1146 3.33
3300 958 2.06 984 2.22 1010 2.39 1035 2.56 1059 2.73 1082 2.91 1105 3.09 1128 3.28 — — — —
3600 990 2.33 1017 2.50 1043 2.66 1067 2.84 1091 3.02 1114 3.20 1137 3.39 — — — — — —
3-HP Oversized Motor & Drive

RT-PRC006-EN 65
Performance (7½ Ton)
Data High Efficiency

Table PD-74 — Belt Drive Evaporator Fan Performance — 7½-Ton — YHC092A3,A4,AW *L,M — Low and Medium Heat —Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied
Low Static Drive (1)
2400 — — 599 0.52 650 0.62 703 0.75 751 0.87 789 0.98 823 1.08 855 1.19 885 1.29 912 1.39
2700 604 0.58 651 0.68 694 0.79 741 0.91 789 1.06 832 1.19 868 1.32 900 1.44 931 1.56 959 1.68
3000 661 0.77 705 0.88 744 1.00 783 1.12 826 1.26 869 1.42 909 1.58 945 1.73 976 1.86 1004 1.99
3300 719 1.00 758 1.11 797 1.25 832 1.37 867 1.51 907 1.68 946 1.85 983 2.02 1017 2.18 1048 2.34
3600 779 1.28 813 1.39 850 1.54 883 1.68 915 1.82 948 1.97 984 2.15 1020 2.33 1055 2.52 1088 2.71
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Table PD-74 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2400 939 1.50 965 1.60 990 1.71 1014 1.81 1039 1.92 1063 2.03 1085 2.14 1108 2.25 1131 2.36 1154 2.49
2700 985 1.79 1010 1.91 1034 2.03 1058 2.14 1081 2.26 1104 2.38 1126 2.50 1148 2.62 1169 2.74 1190 2.86
3000 1031 2.12 1056 2.25 1081 2.39 1104 2.51 1127 2.65 1148 2.77 1169 2.90 1190 3.03 1210 3.16 1231 3.30
3300 1077 2.50 1102 2.64 1127 2.78 1151 2.93 1174 3.07 1194 3.21 1216 3.36 — — — — — —
3600 1120 2.89 1146 3.06 1172 3.22 1195 3.38 — — — — — — — — — — — —
3-HP Oversized Motor & Drive

Table PD-75 — Belt Drive Evaporator Fan Performance — 7½-Ton — YHC092A3,A4,AW *H — High Heat —Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied
Low Static Drive (1)
2400 — — 613 0.54 666 0.66 718 0.78 762 0.90 799 1.01 833 1.11 864 1.22 893 1.32 920 1.42
2700 621 0.61 667 0.72 710 0.83 759 0.97 804 1.10 846 1.24 880 1.36 911 1.48 941 1.60 968 1.72
3000 680 0.81 723 0.93 761 1.05 802 1.18 845 1.33 888 1.49 925 1.64 959 1.79 988 1.92 1016 2.05
3300 740 1.06 780 1.19 816 1.31 850 1.45 889 1.60 928 1.77 966 1.94 1002 2.11 1036 2.28 1063 2.42
3600 800 1.35 837 1.49 872 1.63 904 1.77 935 1.91 971 2.08 1007 2.27 1043 2.45 1077 2.64 1108 2.83
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. Field Supplied Fan Sheave AK79 and Belt AX38 required..
Table PD-75 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2400 946 1.53 972 1.64 997 1.74 1022 1.84 1045 1.95 1069 2.06 1092 2.17 1115 2.28 1137 2.40 1160 2.52
2700 994 1.84 1019 1.95 1043 2.07 1066 2.18 1089 2.30 1112 2.42 1134 2.54 1155 2.66 1177 2.78 1197 2.90
3000 1043 2.18 1067 2.31 1091 2.44 1114 2.57 1137 2.70 1158 2.83 1178 2.96 1200 3.09 1220 3.22 1240 3.35
3300 1090 2.57 1116 2.72 1140 2.86 1162 3.00 1185 3.15 1206 3.29 1227 3.43 — — — — — —
3600 137 3.00 1163 3.17 1188 3.33 — — — — — — — — — — — — — —
3-HP Oversized Motor & Drive

66 RT-PRC006-EN
Performance (8½ Ton)
Data High Efficiency

Table PD-76— Belt Drive Evaporator Fan Performance — 8½-Ton — YHC102A3,A4,AW *L — Low Heat — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied
Low Static Drive (1)
2720 — — — — 621 0.62 662 0.74 703 0.86 741 0.98 777 1.11 810 1.24 841 1.38 871 1.52
3060 587 0.58 630 0.69 668 0.79 707 0.92 743 1.05 779 1.18 814 1.32 846 1.45 878 1.60 907 1.75
3400 643 0.77 683 0.89 718 1.00 753 1.13 787 1.26 820 1.41 853 1.56 884 1.71 915 1.86 944 2.02
3740 699 0.99 736 1.12 770 1.25 802 1.38 833 1.52 864 1.67 894 1.83 925 2.00 953 2.16 982 2.33
4080 757 1.26 790 1.40 823 1.55 853 1.69 882 1.83 910 1.98 938 2.15 967 2.32 994 2.50 1021 2.68
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Table PD-76 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2720 900 1.67 927 1.82 954 1.97 980 2.12 1006 2.28 1032 2.44 1057 2.60 1082 2.76 1105 2.92 1129 3.09
3060 936 1.90 962 2.06 989 2.22 1014 2.39 1039 2.56 1062 2.73 1085 2.90 1109 3.07 1133 3.25 1155 3.43
3400 973 2.17 999 2.34 1025 2.51 1050 2.68 1074 2.86 1097 3.04 1120 3.22 1142 3.41 — — — —
3740 1010 2.50 1036 2.66 1062 2.84 1087 3.01 1110 3.19 1134 3.39 — — — — — — — —
4080 1047 2.86 1073 3.04 1098 3.22 1123 3.40 — — — — — — — — — — — —
3-HP Oversized Motor & Drive

Table PD-77 — Belt Drive Evaporator Fan Performance — 8½-Ton — YHC102A3,A4,AW *M— Medium Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied
Low Static Drive (1)
2720 — — — — 623 0.63 664 0.75 704 0.87 742 0.99 778 1.11 811 1.24 842 1.38 872 1.53
3060 589 0.58 632 0.69 670 0.80 709 0.92 745 1.06 781 1.19 815 1.32 848 1.46 880 1.60 909 1.75
3400 645 0.77 685 0.89 721 1.01 755 1.13 789 1.27 822 1.42 854 1.57 886 1.72 916 1.87 945 2.02
3740 702 1.00 739 1.14 772 1.26 804 1.39 836 1.53 867 1.69 897 1.85 926 2.01 956 2.18 984 2.34
4080 759 1.27 793 1.42 826 1.56 856 1.70 884 1.84 913 2.00 941 2.16 969 2.34 996 2.52 1024 2.70
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Table PD-77 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2720 900 1.67 928 1.82 955 1.98 982 2.14 1008 2.29 1033 2.45 1057 2.60 1083 2.77 1107 2.94 1129 3.10
3060 936 1.91 964 2.07 989 2.23 1015 2.39 1039 2.56 1063 2.73 1088 2.92 1111 3.09 1134 3.26 1157 3.44
3400 974 2.18 1001 2.35 1027 2.52 1051 2.69 1075 2.87 1098 3.05 1121 3.23 1144 3.42 — — — —
3740 1011 2.50 1038 2.68 1064 2.85 1089 3.03 1113 3.22 1135 3.40 — — — — — — — —
4080 1050 2.87 1076 3.05 1101 3.24 1126 3.43 — — — — — — — — — — — —
3-HP Oversized Motor & Drive

RT-PRC006-EN 67
Performance (8½ Ton)
Data High Efficiency

Table PD-78 — Belt Drive Evaporator Fan Performance — 8½-Ton — YHC102A3,A4,AW *H — High Heat — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied
Low Static Drive (1)
2720 — — 590 0.55 633 0.66 674 0.77 713 0.89 750 1.01 786 1.14 818 1.28 850 1.42 879 1.56
3060 602 0.62 643 0.72 682 0.83 719 0.96 756 1.09 791 1.23 825 1.36 857 1.50 889 1.65 917 1.80
3400 660 0.82 698 0.94 733 1.05 767 1.18 801 1.32 834 1.48 866 1.62 897 1.77 927 1.92 956 2.08
3740 718 1.06 754 1.19 787 1.32 818 1.45 849 1.60 880 1.76 910 1.92 939 2.08 968 2.24 996 2.41
4080 777 1.35 811 1.49 841 1.63 870 1.77 899 1.92 928 2.08 956 2.26 983 2.43 1011 2.61 1037 2.79
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Table PD-78 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2720 907 1.71 934 1.86 960 2.01 987 2.17 1014 2.33 1039 2.48 1063 2.64 1088 2.81 1112 2.97 1134 3.13
3060 945 1.95 971 2.11 997 2.28 1022 2.45 1047 2.62 1070 2.79 1094 2.96 1117 3.14 1141 3.31 — —
3400 985 2.24 1010 2.40 1036 2.58 1060 2.76 1084 2.93 1106 3.11 1130 3.31 — — — — — —
3740 1023 2.58 1049 2.75 1075 2.93 1099 3.11 1122 3.29 — — — — — — — — — —
4080 1063 2.96 1089 3.15 1114 3.34 — — — — — — — — — — — — — —
3-HP Oversized Motor & Drive

Table PD-79 — Belt Drive Evaporator Fan Performance — 8½-Ton — YHC102A3,A4,AW *L— Low Heat —Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied
Low Static Drive (1)
2720 622 0.62 669 0.73 711 0.84 760 0.97 807 1.12 849 1.26 884 1.38 915 1.50 944 1.62 972 1.74
3060 688 0.85 732 0.97 770 1.09 809 1.22 853 1.38 895 1.54 934 1.70 968 1.85 998 1.99 1026 2.13
3400 756 1.14 795 1.27 832 1.40 866 1.54 901 1.69 941 1.86 979 2.04 1015 2.22 1049 2.40 1079 2.56
3740 824 1.49 859 1.62 895 1.78 926 1.92 957 2.07 990 2.24 1025 2.42 1061 2.62 1095 2.82 1127 3.02
4080 893 1.90 925 2.05 958 2.21 988 2.37 1017 2.53 1046 2.70 1075 2.88 1108 3.08 1140 3.29 — —
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Table PD-79 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2720 998 1.86 1024 1.98 1047 2.10 1071 2.22 1094 2.33 1115 2.45 1138 2.57 1159 2.69 1181 2.82 1201 2.94
3060 1053 2.26 1078 2.39 1102 2.53 1125 2.66 1146 2.79 1169 2.93 1190 3.06 1210 3.19 1230 3.32 1250 3.45
3400 1106 2.71 1131 2.86 1156 3.02 1179 3.16 1201 3.31 1223 3.45 — — — — — — — —
3740 1158 3.21 1185 3.39 — — — — — — — — — — — — — — — —
4080 — — — — — — — — — — — — — — — — — — — —
3-HP Oversized Motor & Drive

68 RT-PRC006-EN
Performance (8½ Ton)
Data High Efficiency

Table PD-80 — Belt Drive Evaporator Fan Performance — 8½-Ton — YHC102A3,A4,AW *M — Medium Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied
Low Static Drive (1)
2720 625 0.62 671 0.73 714 0.84 763 0.98 809 1.13 851 1.27 885 1.39 917 1.51 946 1.63 974 1.75
3060 691 0.86 734 0.98 772 1.10 812 1.23 856 1.39 897 1.55 936 1.71 970 1.86 1001 2.00 1028 2.14
3400 759 1.15 798 1.28 835 1.41 868 1.55 904 1.70 943 1.87 982 2.05 1019 2.23 1052 2.41 1082 2.57
3740 827 1.50 863 1.64 898 1.79 930 1.94 960 2.09 994 2.26 1029 2.44 1064 2.64 1098 2.84 1130 3.03
4080 897 1.92 929 2.07 962 2.23 992 2.39 1021 2.55 1049 2.72 1079 2.90 1112 3.10 1144 3.31 — —
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Table PD-80 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2720 1000 1.87 1025 1.99 1048 2.10 1072 2.22 1095 2.34 1117 2.46 1139 2.58 1161 2.70 1182 2.82 1203 2.95
3060 1054 2.27 1080 2.41 1103 2.53 1126 2.67 1149 2.80 1170 2.93 1192 3.07 1211 3.20 1231 3.33 — —
3400 1108 2.73 1134 2.88 1158 3.03 1181 3.17 1204 3.33 — — — — — — — — — —
3740 1160 3.23 1187 3.41 — — — — — — — — — — — — — — — —
4080 — — — — — — — — — — — — — — — — — — — —
3-HP Oversized Motor & Drive

Table PD-81 — Belt Drive Evaporator Fan Performance — 8½-Ton — YHC102A3,A4,AW *H— High Heat —Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied 2-HP Standard Motor & Drive
Low Static Drive (1)
2720 640 0.66 684 0.77 729 0.89 778 1.03 823 1.17 863 1.31 896 1.43 926 1.55 955 1.67 982 1.79
3060 709 0.91 750 1.03 788 1.15 829 1.29 872 1.45 913 1.61 950 1.77 983 1.92 1011 2.05 1038 2.19
3400 778 1.21 817 1.35 851 1.48 885 1.62 924 1.78 963 1.96 1000 2.14 1035 2.30 1067 2.49 1095 2.65
3740 848 1.58 885 1.73 917 1.88 948 2.03 979 2.18 1014 2.36 1050 2.56 1084 2.76 1118 2.96 1148 3.15
4080 919 2.02 952 2.18 984 2.35 1012 2.50 1041 2.67 1070 2.84 1102 3.04 1135 3.25 — — — —
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Table PD-81 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2720 1007 1.90 1032 2.02 1056 2.14 1079 2.26 1101 2.38 1124 2.50 1146 2.62 1167 2.74 1189 2.86 1209 2.98
3060 1064 2.32 1090 2.46 1113 2.59 1135 2.72 1157 2.85 1178 2.98 1199 3.12 1220 3.26 1240 3.39 — —
3400 1121 2.80 1146 2.95 1170 3.10 1193 3.25 1215 3.40 — — — — — — — — — —
3740 1177 3.34 — — — — — — — — — — — — — — — — — —
4080 — — — — — — — — — — — — — — — — — — — —
3-HP Oversized Motor & Drive

RT-PRC006-EN 69
Performance (10 Ton)
Data High Efficiency

Table PD-82— Belt Drive Evaporator Fan Performance — 10-Ton — YHC120A3,A4,AW *L,M — Low and Medium Heat — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Field Supplied
Low Static Drive (1)
3200 — — — — — — 743 1.06 779 1.20 814 1.35 847 1.49 879 1.63 910 1.78 938 1.93
3600 — — 735 1.10 768 1.22 802 1.36 834 1.50 866 1.66 897 1.82 927 1.98 957 2.14 985 2.30
4000 767 1.29 802 1.44 833 1.58 863 1.71 892 1.87 922 2.04 951 2.21 979 2.39 1006 2.56 1034 2.74
4400 837 1.69 869 1.85 899 2.00 926 2.15 953 2.31 980 2.48 1007 2.66 1033 2.85 1059 3.04 1085 3.24
4800 908 2.16 937 2.33 965 2.50 991 2.67 1017 2.83 1041 3.00 1066 3.19 1090 3.38 1115 3.59 1139 3.80
3-HP Standard Motor & Drive 5-HP Oversized
Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
NOTES:
Trane’s factory supplied motors, in commercial equipment, are definite purpose
Data includes pressure drop due to standard filters and wet coils.
motors, specifically designed and tested to operate reliably and continuously at
No accessories or options are included in pressure drop data.
all cataloged conditions. Using the full horsepower range of our fan motors as
Refer to Table PD-89 to determine additional static pressure drop
shown in our tabular data will not result in nuisance tripping or premature
due to other options/accessories
motor failure. Our product’s warranty will not be affected.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. Field Supplied Motor Sheave 1VM50 x 7/8 inch, Fan Sheave AK89, and Belt AX40 required.

Table PD-82 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Drive
3200 966 2.10 992 2.26 1018 2.43 1042 2.60 1066 2.78 1091 2.96 1114 3.15 1136 3.33 1159 3.51 1182 3.70
3600 1013 2.47 1039 2.64 1065 2.82 1089 3.00 1113 3.19 1135 3.38 1157 3.56 1179 3.76 1201 3.97 1221 4.16
4000 1060 2.92 1086 3.10 1111 3.28 1135 3.47 1159 3.66 1182 3.86 1203 4.05 1224 4.26 1246 4.47 1266 4.68
4400 1110 3.43 1134 3.62 1159 3.82 1183 4.02 1205 4.22 1229 4.43 1251 4.64 1272 4.84 1292 5.05 1313 5.27
4800 1162 4.01 1185 4.22 1209 4.44 1231 4.64 1253 4.86 1276 5.07 1298 5.30 1319 5.51 1338 5.73 — —
5-HP Oversized Motor & Drive

Table PD-83— Belt Drive Evaporator Fan Performance — 10-Ton — YHC120A3,A4,AW *H— High Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Field Supplied 3-HP Standard Motor
Low Static Drive (1) & Drive
3200 — — — — 739 1.05 774 1.19 809 1.33 843 1.47 874 1.61 905 1.76 935 1.92 963 2.08
3600 738 1.11 772 1.23 805 1.37 838 1.52 869 1.68 900 1.84 930 2.00 960 2.16 988 2.32 1016 2.49
4000 813 1.49 844 1.63 873 1.77 903 1.93 932 2.10 961 2.27 989 2.45 1017 2.63 1043 2.80 1070 2.98
4400 889 1.95 917 2.10 944 2.25 971 2.42 998 2.59 1024 2.78 1050 2.97 1076 3.17 1101 3.37 1126 3.56
4800 964 2.50 991 2.66 1016 2.83 1040 3.00 1065 3.18 1090 3.38 1114 3.58 1138 3.79 1161 4.00 1184 4.22
5-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. Field Supplied Motor Sheave 1VM50 x 7/8 inch, Fan Sheave AK89, and Belt AX40 required
Table PD-83 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Drive
3200 989 2.24 1015 2.41 1039 2.58 1064 2.76 1087 2.93 1111 3.12 1133 3.30 1156 3.48 1179 3.68 1200 3.85
3600 1042 2.66 1067 2.84 1091 3.02 1115 3.21 1138 3.40 1160 3.59 1181 3.78 1203 3.98 1224 4.19 1244 4.39
4000 1095 3.17 1120 3.35 1145 3.54 1167 3.73 1190 3.93 1212 4.14 1233 4.35 1253 4.55 1273 4.76 1293 4.97
4400 1150 3.75 1174 3.95 1197 4.15 1221 4.36 1243 4.56 1265 4.77 1285 4.97 1306 5.20 1326 5.42 1345 5.65
4800 1208 4.42 1231 4.64 1253 4.86 1275 5.07 1297 5.29 1317 5.50 1338 5.72 — — — — — —
5-HP Oversized Motor & Drive

70 RT-PRC006-EN
Performance (10 Ton)
Data High Efficiency

Table PD-84 — Belt Drive Evaporator Fan Performance — 10-Ton — YHC120A3,A4,AW *L,M — Low and Medium Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Field Supplied
Low Static Drive (1)
3200 — — 777 1.15 814 1.28 853 1.42 895 1.59 936 1.76 973 1.93 1008 2.09 1037 2.24 1064 2.38
3600 819 1.42 857 1.57 890 1.71 922 1.85 957 2.02 994 2.20 1032 2.39 1067 2.58 1099 2.77 1131 2.96
4000 902 1.91 936 2.07 968 2.23 998 2.39 1027 2.55 1058 2.73 1091 2.93 1124 3.14 1158 3.36 1189 3.57
4400 986 2.50 1016 2.68 1047 2.86 1075 3.03 1101 3.20 1128 3.39 1155 3.58 1186 3.80 1217 4.03 1246 4.25
4800 1070 3.22 1098 3.40 1127 3.60 1153 3.79 1178 3.98 1203 4.17 1227 4.37 1251 4.57 1279 4.80 1307 5.05
3-HP Standard Motor 5-HP Oversized Motor & Drive
& Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. Field Supplied Motor Sheave 1VM50 x 7/8 inch, Fan Sheave AK89, and Belt AX40 required.

Table PD-84 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Drive
3200 1090 2.53 1115 2.67 1139 2.81 1161 2.95 1183 3.09 1205 3.23 1225 3.37 1246 3.51 1265 3.65 1284 3.78
3600 1157 3.13 1181 3.29 1205 3.45 1228 3.61 1250 3.77 1272 3.93 1293 4.09 1312 4.24 1331 4.40 1351 4.56
4000 1218 3.78 1246 3.99 1271 4.18 1294 4.36 1317 4.55 1338 4.72 1360 4.91 1379 5.07 1398 5.25 1418 5.43
4400 1276 4.49 1304 4.73 1333 4.97 1359 5.20 1383 5.42 1405 5.62 — — — — — — — —
4800 1336 5.30 1363 5.56 — — — — — — — — — — — — — — — —
5-HP Oversized Motor & Drive

Table PD-85 — Belt Drive Evaporator Fan Performance — 10-Ton — YHC120A3,A4,AW *H— High Heat —Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Field Supplied 3-HP Standard Motor & Drive
Low Static Drive (1)
3200 785 1.18 821 1.31 861 1.46 903 1.62 944 1.80 981 1.96 1014 2.12 1043 2.27 1070 2.41 1095 2.55
3600 874 1.64 907 1.78 939 1.93 977 2.11 1014 2.30 1050 2.49 1084 2.69 1115 2.87 1144 3.05 1169 3.21
4000 964 2.21 994 2.37 1023 2.53 1053 2.71 1087 2.91 1121 3.12 1154 3.33 1185 3.55 1215 3.76 1242 3.96
4400 1055 2.91 1082 3.08 1109 3.25 1135 3.43 1164 3.64 1194 3.86 1225 4.09 1255 4.32 1284 4.56 1312 4.79
4800 1146 3.74 1171 3.92 1196 4.11 1220 4.31 1244 4.51 1271 4.73 1298 4.97 1327 5.22 1354 5.47 1382 5.74
5-HP Oversized Motor & Drive
Trane’s factory supplied motors, in commercial equipment, are definite purpose
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
motors, specifically designed and tested to operate reliably and continuously at
NOTES:
all cataloged conditions. Using the full horsepower range of our fan motors as
Data includes pressure drop due to standard filters and wet coils.
shown in our tabular data will not result in nuisance tripping or premature
No accessories or options are included in pressure drop data.
motor failure. Our product’s warranty will not be affected.
Refer to Table PD-89 to determine additional static pressure drop
due to other options/accessories
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. Field Supplied Motor Sheave 1VM50 x 7/8 inch, Fan Sheave AK89, and Belt AX40 required

Table PD-85 — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Drive
3200 1120 2.70 1143 2.84 1166 2.98 1188 3.12 1208 3.25 1229 3.39 1249 3.53 1269 3.67 1289 3.82 1308 3.96
3600 1194 3.37 1217 3.53 1240 3.69 1262 3.85 1282 4.01 1303 4.17 1322 4.32 1341 4.48 1361 4.64 1378 4.79
4000 1269 4.16 1292 4.34 1314 4.52 1335 4.70 1356 4.88 1377 5.06 1397 5.24 1415 5.41 — — — —
4400 1339 5.02 1365 5.25 1388 5.47 1410 5.67 — — — — — — — — — — — —
4800 — — — — — — — — — — — — — — — — — — — —
5-HP Oversized Motor & Drive

RT-PRC006-EN 71
Performance
Data

Table PD-86— Standard Motor & Sheave/Fan Speed (Rpm)


Unit 6Turns 5Turns 4Turns 3Turns 2Turns 1Turn
Tons Model No. Open Open Open Open Open Open Closed
3 Y#C036A NA 745 819 894 968 1043 1117
4 Y#C048A NA 833 916 1000 1083 1167 1250
5 Y#C060A NA 897 987 1077 1166 1256 1346
6 Y#C072A N/A 723 779 835 890 946 1002
7½ Y#C090,092A N/A 835 891 946 1002 1057 1113
8½ Y#C102A N/A 787 847 908 968 1029 1089
10 Y#C120A N/A 908 969 1029 1090 1150 1211
Factory set at 3 turns open.

Table PD-87— Standard Motor & High Static Drive Accessory Sheave/Fan Speed (Rpm)
Unit 6Turns 5Turns 4Turns 3Turns 2Turns 1Turn
Tons Model No. Open Open Open Open Open Open Closed
6 Y#C072A3,A4,AW N/A 831 895 959 1022 1086 1150
6 YSC072AK N/A 958 1022 1086 1150 1214 1278
7½ YSC090,092A N/A 958 1022 1086 1150 1214 1278
Factory set at 3 turns open.

Table PD-88 — Oversized Motor & Drive Sheave/Fan Speed (Rpm)


Unit 6Turns 5Turns 4Turns 3Turns 2Turns 1Turn
Tons Model No. Open Open Open Open Open Open Closed
6 Y#C072A3, A4, AW N/A 958 1022 1086 1150 1214 1278
7½ Y#C090,092A N/A 1068 1150 1232 1315 1397 1479
8½ Y#C102A N/A 958 1022 1086 1150 1214 1278
10 Y#C120A 1050 1135 1200 1275 1350 1425 N/A
Factory set at 3 turns open.

# Indicates both standard and high efficiency units.


*Indicates both ReliaTel and Electromechanical controls.

72 RT-PRC006-EN
Performance
Data

Table PD-89 — Static Pressure Drops Through Accessories (Inches Water Column)
Economizer with OA/RA Dampers2
Unit Standard Through 2” Pleated 100% OA 100% RA 100% OA 100% RA
Tons Model No CFM Filters1 Reheat Coil (WC) Filters Downflow Horizontal
960 0.03 — 0.05 0.05 0.01 0.05 0.00
YSC036A 1200 0.04 — 0.07 0.07 0.02 0.07 0.01
1440 0.06 — 0.10 0.10 0.03 0.10 0.01
3 960 0.02 .03 0.04 0.05 0.01 0.05 0.00
YHC036A 1200 0.03 .04 0.05 0.07 0.02 0.07 0.01
1440 0.04 .06 0.07 0.10 0.03 0.10 0.01
1280 0.04 — 0.06 0.08 0.03 0.08 0.01
YSC048A 1600 0.05 — 0.09 0.12 0.04 0.12 0.01
4 1920 0.08 — 0.12 0.17 0.06 0.17 0.02
1280 0.04 .05 0.06 0.08 0.03 0.08 0.01
YHC048A 1600 0.05 .07 0.09 0.12 0.04 0.12 0.01
1920 0.08 .09 0.12 0.17 0.06 0.17 0.02
1600 0.10 — 0.15 0.12 0.04 0.12 0.01
YSC060A 2000 0.15 — 0.22 0.18 0.07 0.18 0.02
2400 0.22 — 0.29 0.26 0.10 0.26 0.04
5 1600 0.04 0.07 0.07 0.12 0.04 0.12 0.01
YHC060A 2000 0.06 0.10 0.10 0.18 0.07 0.18 0.02
2400 0.09 0.14 0.14 0.26 0.10 0.26 0.04
1920 0.04 — 0.07 0.10 0.01 0.06 0.02
6 Y#C072A 2400 0.06 — 0.09 0.11 0.02 0.08 0.02
2880 0.09 — 0.12 0.13 0.04 0.10 0.04
2400 0.06 — 0.09 0.11 0.02 0.08 0.02
YSC090, 092A 3000 0.10 — 0.13 0.14 0.05 0.12 0.05
7½ 3600 0.14 — 0.18 0.21 0.07 0.25 0.08
2400 0.04 .10 0.06 0.11 0.02 0.08 0.02
YHC092A 3000 0.06 .14 0.09 0.14 0.05 0.12 0.05
3600 0.09 .19 0.13 0.21 0.07 0.25 0.08
2720 0.05 — 0.08 0.12 0.03 0.09 0.04
YSC102A 3400 0.08 — 0.11 0.19 0.06 0.18 0.06
8½ 4080 0.12 — 0.16 0.30 0.07 0.31 0.09
2720 0.05 .12 0.08 0.12 0.03 0.09 0.04
YHC102A 3400 0.08 .17 0.11 0.19 0.06 0.18 0.06
4080 0.12 .23 0.16 0.30 0.07 0.31 0.09
3200 0.07 — 0.10 0.17 0.05 0.14 0.05
YSC120A 4000 0.11 — 0.15 0.26 0.07 0.30 0.08
10 4800 0.16 — 0.20 0.34 0.09 0.35 0.10
3200 — 0.15 0.10 0.17 0.05 0.14 0.05
YHC120A 4000 — 0.22 0.15 0.26 0.07 0.30 0.08
4800 0.16 0.31 0.20 0.34 0.09 0.35 0.10
Notes:
1. Tested with standard filters (3-5 tons 1”, 6-10 tons 2”) . Difference in pressure drop should be considered when utilizing optional 2” pleated filters.
2. OA = Outside Air and RA = Return Air.

RT-PRC006-EN 73
Performance
Data

-12
Table PD-90— Outdoor Sound Power Level - dB (ref. 10 Watts)
Unit Octave Center Frequency Overall
Tons Model No. 63. 125 250 500 1000 2000 4000 8000 dBA
3 Y*C036A 86 83 81 80 78 74 69 68 83
YSC048A1 92 87 84 83 81 76 72 69 86
4 YSC048A3,A4,AW 90 84 78 77 76 72 70 68 82
YHC048A 92 86 83 82 81 75 72 69 85
YSC060A 94 87 83 82 79 75 73 69 84
5 YHC060A 94 87 82 81 78 74 72 69 84
YSC072A 90 94 90 87 83 78 74 67 88
6 YHC072A 91 95 90 87 84 79 75 68 89
YSC090A 92 95 91 88 84 80 75 68 90
7½ YSC092A 89 93 88 85 81 76 72 66 87
YHC092A 92 96 92 89 85 80 76 69 91
YSC102A 88 92 87 84 80 75 72 65 86
8½ YHC102A 91 95 90 87 84 79 75 68 89
YSC120A 91 88 84 82 81 76 73 67 86
10
YHC120A 94 89 87 85 84 78 75 69 88
Note:
Tests follow ARI270-95.

Table PD-91 — Gas-Fired Heating Capacities


Unit Heating Heating Air Temp.
Tons Efficiency Model No. Input MBH Output MBH Rise, F
Y*C036A1*L 60.0 47.0 25-55
Y*C036A3, A4, AW*L 60.0 48.0 25-56
Standard and Y*C036A1*M 80.0 63.0 35-65
3
High Efficiency Y*C036A3, A4, AW*M 80.0 64.0 35-65
Y*C036A1*H 120.0 95.0 55-85
Y*C036A3, A4, AW*H 120.0 96.0 55-85
Y*C048A1*L, 60.0 47.0 15-45
Y*C048A3, A4, AW *L 60.0 48.0 15-45
Standard and Y*C048A1*M 80.0 63.0 20-50
4
High Efficiency Y*C048A3, A4, AW*M 80.0 64.0 20-50
Y*C048A1*H 120.0 95.0 40-70
Y*C048A3, A4, AW *H 120.0 96.0 40-70
YSC060A1*L 60.0 47.0 10-40
YSC060A3, A4, AW, AK*L 60.0 48.0 10-40
YSC060A1*M 80.0 63.0 15-45
Standard Eff. YSC060A3 A4, AW*M 80.0 64.0 15-45
YSC060A1*H 130.0 103.0 35-65
YSC060A3, A4, AW, AK*H 130.0 104.0 35-65
5
YHC060A1*L 60.0 47.0 10-40
YHC060A3, A4, AW, AK*L 60.0 48.0 10-40
High Eff.
YHC060A1*M 80.0 63.0 15-45
YHC060A3,A4,AW*M 80.0 64.0 15-45
YHC060A1*H 130.0 103.0 35-65
YHC060A3, A4, AW, AK*H 130.0 104.0 35-65
Y*C072A1, A3, A4, AW, AK*L 80.0 64.8 15-45
Standard and
6 High Efficiency Y*C072A1, A3, A4, AW*M 120.0 97.2 20-50
Y*C072A1, A3, A4, AW, AK*H 150.0 121.5 25-55
Y*C090,092A1, A3, A4, AW, AK*L 120.0 97.2 20-50
Standard and
7½ Y*C090,092A1, A3, A4, AW*M 150.0 121.5 25-55
High Efficiency
Y*C090,092A1, A3, A4, AW, AK*H 200.0 162.0 35-65
Y*C102A1, A3, A4, AW, AK*L 120.0 97.2 15-45
Standard and
8½ Y*C102A1, A3, A4, AW*M 150.0 121.5 20-50
High Efficiency
Y*C102A1, A3, A4, AW, AK*H 200.0 162.0 35-65
Y*C120A1, A3, A4, AW, AK*L 150.0 121.5 20-50
Standard and
10 High Efficiency Y*C120A1, A3, A4, AW*M 200.0 162.0 25-55
Y*C120A1, A3, A4, AW, AK*H 250.0 202.5 35-65
Ratings shown are for elevations up to 2,000 ft. For higher elevations, reduce ratings at a rate of 4% per 1,000 ft. elevation.

74 RT-PRC006-EN
Performance
Data

Table PD-92— Hot Gas Reheat Temperature Rise3


SCFM Leaving Evaporator Dry Bulb [F]
Tons SCFM 35 40 45 50 55 60 65
960 17.6 17.3 17.0 16.6 16.2 15.8 15.5
1080 16.7 16.4 16.1 15.7 15.4 15.0 14.6
3 1200 15.8 15.5 15.2 14.9 14.5 14.1 13.8
1320 14.9 14.6 14.3 14.0 13.6 13.3 12.9
1440 14.0 13.8 13.5 13.1 12.8 12.4 12.0
Tons SCFM 35 40 45 50 55 60 65
1280 19.0 18.7 18.4 18.1 17.9 17.5 17.2
1440 17.9 17.7 17.4 17.1 16.9 16.5 16.2
4 1600 16.9 16.6 16.4 16.1 15.8 15.5 15.2
1760 15.9 15.6 15.4 15.1 14.8 14.5 14.2
1920 14.8 14.6 14.4 14.1 13.8 13.5 13.2
Tons SCFM 35 40 45 50 55 60 65
1600 20.3 20.1 19.9 19.7 19.5 19.3 19.0
1800 19.1 18.9 18.7 18.5 18.4 18.1 17.8
5 2000 17.9 17.8 17.6 17.4 17.2 16.9 16.6
2200 16.8 16.6 16.4 16.2 16.0 15.7 15.4
2400 15.6 15.4 15.2 15.1 14.9 14.6 14.3
Tons SCFM 35 40 45 50 55 60 65
2400 16.7 17.3 18.0 18.7 19.3 20.1 20.9
2700 14.9 15.5 16.1 16.7 17.3 18.0 18.7
7½ 3000 13.1 13.7 14.2 14.7 15.2 15.9 16.5
3300 11.4 11.8 12.3 12.7 13.1 13.7 14.3
3600 9.6 10.0 10.3 10.7 11.1 11.6 12.2
Tons SCFM 35 40 45 50 55 60 65
2720 16.6 17.4 18.2 18.9 19.7 20.3 21.0
3060 14.7 15.3 15.9 16.6 17.2 17.7 18.1
8½ 3400 12.7 13.2 13.7 14.2 14.7 15.0 15.3
3740 10.7 11.1 11.4 11.8 12.2 12.3 12.5
4080 8.7 9.0 9.2 9.4 9.6 9.7 9.7
Tons SCFM 35 40 45 50 55 60 65
3200 18.7 19.5 20.3 21.2 22.0 22.7 23.4
3600 16.2 17.2 18.1 19.1 20.1 20.8 21.6
10 4000 13.8 14.9 15.9 17.0 18.1 19.0 19.8
4400 11.3 12.5 13.7 14.9 16.1 17.1 18.1
4800 8.9 10.2 11.5 12.9 14.2 15.3 16.3
NOTES:
1. Temperature rise does not account for indoor fan heat.
2. 70 deg OD Ambient Temperature.
3. For units with the Dehumidification (Hot Gas Reheat) option.

RT-PRC006-EN 75
Zone
Controls

ReliaTel™ Controlled Units Integrated ComfortTM System — Programmable Night Setback — Auto
Sensor(s) available with optional or manual changeover with seven-day
Zone Sensors are the building temperature adjustment and override programming. Keyboard selection of
occupant’s comfort control devices for buttons to provide
Precedent™ units with the Micro control: central control
through aTrane
Manual Changeover — Heat, Cool or Off Integrated
System Switch. Fan Auto or Off Switch. ComfortTM system.
One temperature
setpoint lever.

Heat, Cool, Fan, Auto, or On. All


programmable sensors have System On,
Dual Thermistor Remote Zone Sensor Heat, Cool, Service LED/indicators as
This sensor will allow the customer to standard. Night Setback Sensors have
reduce the total number of remote one (1) Occupied, one (1) Un-occupied,
sensors to obtain space temperature and two (2) Override programs per day.
averaging. This sensor should be utilized
with ReliaTel controls. Humidity Sensor — Field installed,
wall-mounted or duct-mounted humidity
Manual/Automatic Changeover — sensor is used to control activation of the
Auto, Heat, Cool or Off System Switch. Digital Display Zone Sensor
The Digital LCD (Liquid Crystal Display) hot gas reheat
Fan Auto or Off Switch.Two temperature dehumidification
setpoint levers. zone sensor has the look and functionality
of standard zone option.The
Optional Status humidity sensor
Indication LED sensors.This sensor
includes a digital can be set for
lights, System On, humidity levels
Heat, Cool, or display of set point
adjustment and between 40% and
Service. 60% relative
space temperature
in F (Fahrenheit) or C humidity by
(Celsius). Includes adjusting the
FAN and SYSTEM ReliaTel Options
buttons (supports Module.
the service functions
of the standard CO2 Sensing —The CO2 sensor shall
sensor). E-squared have the ability to to monitor space
memory stores last occupancy levels within the building by
programmed set points. Requires 24 VAC measuring the parts per million of CO2
(Volts AC).This sensor should be utilized (Carbon Dioxide) in the air. As the CO2
with ReliaTel™ controls. levels increase,
Remote Sensor — Sensor(s) available
for all zone sensors to provide remote the outside air
sensing capabilities. damper
modulates to
meet the CO2
space ventilation
requirements.
The CO2
accessory shall
be available as
field installed.

76 RT-PRC006-EN
Zone
Controls

Electromechanically Controlled
Units
Conventional Thermostats are the
building occupant’s comfort control
devices for electromechanically
controlled units.
Manual Changeover — One Heat, One
CoolThermostat.
Heat, Cool or Off
System Switch.
Fan Auto or On 70 80
60
Switch. Set Point

90
Dial. Adjustable TM

Heat Anticipator. 60

90
70
80

Automatic Changeover — One Heat,


Two CoolThermostat. Off, Auto System
Switch. Auto/On Fan Switch.

HEAT 50 60 70 80 50 60 70 80
COOL

50 60 70 80

TM

FAN
AUTO ON OFF AUTO

Programmable Electronic Night Setback


Thermostat — Heating setback and
cooling setup with 7-day, 5-1-1
programming capability. Available in two
heating/
cooling or
one heating/
cooling
versions with
automatic
changeover.

RT-PRC006-EN 77
Electrical
Data (Standard Efficiency)

Table ED-1 — Unit Wiring - Standard Efficiency


Standard Indoor Fan Motor Oversize Indoor Fan Motor Optional Belt Drive Indoor Fan Motor
Unit Minimum Maximum Fuse Minimum Maximum Fuse Minimum Maximum Fuse
Unit Operating Circuit Size or Maximum Circuit Size or Maximum Circuit Size or Maximum
Tons Model No. Voltage Range Ampacity Circuit Breaker1 Ampacity Circuit Breaker 1
Ampacity Circuit Breaker1
YSC036A1 187-253 25.3 40 27.7 40 — —
3 YSC036A3 187-253 17.9 25 20.3 30 20.6 30
YSC036A4 414-506 9.2 15 10.4 15 10.6 15
YSC036AW 517-633 7.7 15 8.3 15 8.3 15
YSC048A1 187-253 34.0 50 36.1 50 — —
YSC048A3 187-253 23.9 35 26.0 40 25.3 35
4 YSC048A4 414-506 12.8 20 14.4 20 13.6 20
YSC048AW 517-633 9.8 15 10.6 15 10.0 15
YSC060A1 187-253 47.3 60 49.0 60 — —
YSC060A3 187-253 31.5 50 33.6 50 30.3 45
5 YSC060A4 414-506 16.0 25 16.3 25 15.6 25
YSC060AW 517-633 12.2 15 12.8 20 11.8 15
YSC060AK 342-418 19.6 30 — — — —
YSC072A3 187-253 32.7 50 34.0 50 — —
6 YSC072A4 414-506 17.6 25 18.2 25 — —
YSC072AW 517-633 12.8 20 13.6 20 — —
YSC072AK 342-418 23.2 35 — — — —
YSC090A3 187-253 42.7 60 45.8 60 — —
YSC090A4 414-506 22.6 35 24.1 35 — —
YSC090AW 517-633 17.6 25 18.8 25 — —
YSC090AK 342-418 28.9 40 29.9 45 — —

YSC092A3 187-253 38.9 50 42.0 50 — —
YSC092A4 414-506 20.5 25 22.0 25 — —
YSC092AW 517-633 15.5 20 16.7 20 — —
YSC102A3 187-253 45.1 60 48.2 60 — —
8½ YSC102A4 414-506 24.0 30 25.5 35 — —
YSC102AW 517-633 19.5 25 20.7 25 — —
YSC102AK 342-418 29.6 40 31.1 40 — —
YSC120A3 187-253 52.6 60 56.6 60 — —
10 YSC120A4 414-506 26.9 35 28.9 35 — —
YSC120AW 517-633 21.8 25 23.5 30 — —
YSC120AK 342-418 32.8 40 35.6 45 — —
NOTES:
1. HACR breaker per NEC.

#Indicates both standard and high efficiency airflow.

78 RT-PRC006-EN
Electrical
Data (High Efficiency)

Table ED-2 — Unit Wiring - High Efficiency


Standard Indoor Fan Motor Oversize Indoor Fan Motor Belt Drive Indoor Fan Motor
Unit Minimum Maximum Fuse Minimum Maximum Fuse Minimum Maximum Fuse
Unit Operating Circuit Size or Maximum Circuit Size or Maximum Circuit Size or Maximum
Tons Model No. Voltage Range Ampacity Circuit Breaker1 Ampacity Circuit Breaker1 Ampacity Circuit Breaker1
YHC036A1 187-253 23.9 40 26.3 40 — —
3 YHC036A3 187-253 17.2 25 19.6 30 19.9 30
YHC036A4 414-506 9.0 15 10.2 15 10.4 15
YHC036AW 517-633 7.1 15 7.7 15 7.7 15
YHC048A1 187-253 29.4 45 31.5 50 — —
YHC048A3 187-253 21.2 30 23.3 35 22.6 35
4 YHC048A4 414-506 11.0 15 12.6 15 11.8 15
YHC048AW 517-633 8.3 15 9.1 15 8.5 15
YHC060A1 187-253 39.5 60 41.2 60 — —
YHC060A3 187-253 30.0 45 31.7 45 28.8 45
5 YHC060A4 414-506 14.7 20 15.0 20 14.3 20
YHC060AW 517-633 11.8 15 12.4 15 11.4 15
YHC072A3 187-253 34.8 50 36.1 50 — —
6 YHC072A4 414-506 17.5 25 18.1 25 — —
YHC072AW 517-633 13.5 20 14.3 20 — —
YHC092A3 187-253 38.1 50 41.2 50 — —
7½ YHC092A4 414-506 19.4 25 20.9 25 — —
YHC092AW 517-633 14.8 15 16.0 20 — —
YHC102A3 187-253 42.3 50 45.4 60 — —
8½ YHC102A4 414-506 21.4 25 22.9 30 — —
YHC102AW 517-633 16.6 20 17.8 20 — —
YHC120A3 187-253 48.6 60 52.6 60 — —
10 YHC120A4 414-506 25.3 30 27.3 35 — —
YHC120AW 517-633 19.9 25 21.6 25 — —
NOTES:
1. HACR breaker per NEC.

RT-PRC006-EN 79
Electrical
Data

Table ED-3 — Electrical Characteristics — Evaporator Fan Motors — Direct Drive


Standard Evaporator Fan Motor Oversized Evaporator Fan Motor
Unit Amps Amps
Tons Model No. No. Volts Phase HP FLA LRA No. Volts Phase HP FLA LRA
Y#C036A1 1 208-230 1 .33 2.30 3.90 1 208-230 1 .50 4.70 9.80
3 Y#C036A3 1 208-230 1 .33 2.30 3.90 1 208-230 1 .50 4.70 9.80
Y#C036A4 1 460 1 .33 1.10 2.00 1 460 1 .50 2.30 5.20
Y#C036AW 1 575 1 .33 1.10 1.80 1 460 1 .50 1.70 3.60
Y#C048A1 1 208-230 1 .60 3.60 6.60 1 208-230 1 .80 5.70 13.60
Y#C048A3 1 208-230 1 .60 3.60 6.60 1 208-230 1 .80 5.70 13.60
4
Y#C048A4 1 460 1 .60 1.70 2.80 1 460 1 .80 3.30 7.20
Y#C048AW 1 575 1 .60 1.50 2.40 1 575 1 .80 2.30 5.80
Y#C060A1 1 208-230 1 .90 6.20 14.0 1 208-230 1 1.00 7.90 16.40
Y#C060A3 1 208-230 1 .90 6.20 14.0 1 208-230 1 1.00 7.90 16.40
5 Y#C060A4 1 460 1 .90 2.90 6.60 1 460 1 1.00 3.20 8.20
Y#C060AW 1 575 1 .90 2.10 4.90 1 575 1 1.00 2.70 5.00
YSC060AK 1 380 1 1.00 4.30 8.30 N/A N/A N/A N/A N/A N/A

80 RT-PRC006-EN
Electrical
Data

Table ED-4 — Electrical Characteristics — Evaporator Fan Motors — Belt Drive


Standard Evaporator Fan Motor Oversized Evaporator Fan Motor
Unit Amps Amps
Tons Model No. No. Volts Phase HP FLA LRA No. Volts Phase HP FLA LRA
3 Y#C036A3 1 208-230 3 1.0 5.0 32.2 — — — — — —
Y#C036A4 1 460 3 1.0 2.5 16.1 — — — — — —
Y#C036AW 1 575 3 1.0 1.7 13.2 — — — — — —
Y#C048A3 1 208-230 3 1.0 5.0 32.2 — — — — — —
4 Y#C048A4 1 460 3 1.0 2.5 16.1 — — — — — —
Y#C048AW 1 575 3 1.0 1.7 13.2 — — — — — —
Y#C060A3 1 208-230 3 1.0 5.0 32.2 — — — — — —
5 Y#C060A4 1 460 3 1.0 2.5 16.1 — — — — — —
Y#C060AW 1 575 3 1.0 1.7 13.2 — — — — — —
YSC060AK 1 380 1 1.0 4.3 8.3 — — — — — —
Y#C072A3 1 208-230 3 1.00 5.00 32.20 1 208-230 3 2.00 6.30 48.00
6 Y#C072A4 1 460 3 1.00 2.50 16.10 1 460 3 2.00 3.10 24.00
Y#C072AW 1 575 3 1.00 1.70 13.20 1 575 3 2.00 2.50 18.20
YSC072AK 1 380 3 2.0 4.9 35.0 — — — — — —
YSC090A3 1 208-230 3 2.00 6.30 48.00 1 208-230 3 3.00 9.40 83.00
YSC090A4 1 460 3 2.00 3.10 24.00 1 460 3 3.00 4.60 42.00
YSC090AW 1 575 3 2.00 2.50 18.20 1 575 3 3.00 3.70 31.00
YSC090AK 1 380 3 2.0 4.9 3.50 1 3.80 3 3.0 6.4 51.1
7½ Y#C092A3 1 208-230 3 2.00 6.30 48.00 1 208-230 3 3.00 9.40 83.00
Y#C092A4 1 460 3 2.00 3.10 24.00 1 460 3 3.00 4.60 42.00
Y#C092AW 1 575 3 2.00 2.50 18.20 1 575 3 3.00 3.70 31.00
Y#C102A3 1 208-230 3 2.00 6.30 48.00 1 208-230 3 3.00 9.40 83.00
8½ Y#C102A4 1 460 3 2.00 3.10 24.00 1 460 3 3.00 4.60 42.00
Y#C102AW 1 575 3 2.00 2.50 18.20 1 575 3 3.00 3.70 31.00
YSC102AK 1 380 3 2.0 4.9 35.0 1 380 3 3.0 6.4 51.1
Y#C120A3 1 208-230 3 3.00 9.40 83.00 1 208-230 3 5.00 13.40 112.00
10 Y#C120A4 1 460 3 3.00 4.60 42.00 1 460 3 5.00 6.60 56.00
Y#C120AW 1 575 3 3.00 3.70 31.00 1 575 3 5.00 5.40 41.00
YSC120AK 1 380 3 3.0 6.4 51.1 1 380 3 5.0 10.8 66.5

RT-PRC006-EN 81
Electrical
Data (Standard Efficiency)

Table ED-5 — Electrical Characteristics — Compressor Motor And Condenser Motor — Standard Efficiency
Compressor Motor Condenser Fan Motors
Unit Amps Amps
Tons Model No. No. Volts Phase HP2 RPM RLA LRA No. Phase HP FLA LRA
YSC036A1 1 208-230 1 3.1 3450 17.2 104.0 1 1 .20 1.5 2.5
3 YSC036A3 1 208-230 3 3.1 3450 11.3 74.0 1 1 .20 1.5 2.5
YSC036A4 1 460 3 3.1 3450 6.0 37.6 1 1 .20 0.6 1.3
YSC036AW 1 575 3 3.1 3450 4.9 30.4 1 1 .20 0.5 1.2
YSC048A1 1 208-230 1 3.9 3450 22.7 131.0 1 1 .33 2.0 6.6
YSC048A3 1 208-230 3 3.9 3450 14.6 91.0 1 1 .33 2.0 6.6
4 YSC048A4 1 460 3 3.9 3450 7.9 46.0 1 1 .33 1.2 2.5
YSC048AW 1 575 3 3.9 3450 6.1 37.0 1 1 .33 0.7 1.5
YSC060A1 1 208-230 1 5.1 3450 31.3 144.0 1 1 .33 2.0 6.6
YSC060A3 1 208-230 3 5.1 3450 18.6 128.0 1 1 .33 2.0 6.6
5
YSC060A4 1 460 3 5.1 3450 9.5 63.0 1 1 .33 1.2 2.5
YSC060AW 1 575 3 5.1 3450 7.5 49.0 1 1 .33 0.7 1.5
YSC060AK 1 380 3 5.1 3450 11.4 64 1 1 .40 1.1 4.3
YSC072A3 1 208-230 3 6 3450 19.0 156 1 1 .70 3.85 9.30
6 YSC072A4 1 460 3 6 3450 10.1 75 1 1 .70 2.50 5.80
YSC072AW 1 575 3 6 3450 7.7 54 1 1 .70 1.54 3.60
YSC072AK 1 380 3 6 3450 12.2 70 1 1 .75 2.5 7.7
YSC090A3 1 208-230 3 7.5 3450 26.0 181.5 1 1 .70 3.85 9.30
YSC090A4 1 460 3 7.5 3450 13.6 95.0 1 1 .70 2.50 5.80
YSC090AW 1 575 3 7.5 3450 10.9 69.0 1 1 .70 1.54 3.60
YSC090AK 1 380 3 7.5 3450 16.4 106.3 1 1 .75 2.5 7.7
7½ YSC092A3 2 208-230 3 4/2.8 3450 14.7/10.3 91/77 1 1 .70 3.85 9.30
YSC092A4 2 460 3 4/2.8 3450 7.6/5.4 50/39 1 1 .70 2.50 5.80
YSC092AW 2 575 3 4/2.8 3450 5.8/4.2 37/31 1 1 .70 1.54 3.60
YSC102A3 2 208-230 3 5.1/2.8 3450 18.6/10.3 128/77 1 1 .75 4.0 9.4
8½ YSC102A4 2 460 3 5.1/2.8 3450 10.0/5.4 63/39 1 1 .75 2.8 6.8
YSC102AW 2 575 3 5.1/2.8 3450 8.2/4.2 49/31 1 1 .75 2.4 6.2
YSC102AK 1 380 3 5.1/2.8 3450 12.1/6.6 64/39 1 1 7.5 2.5 7.7
YSC120A3 2 208-230 3 5.1/3.9 3450 18.6/14.7 128/91 1 1 .75 4.0 9.4
10 YSC120A4 2 460 3 5.1/3.9 3450 9.5/7.4 63/46 1 1 .75 2.8 6.8
YSC120AW 2 575 3 5.1/3.9 3450 7.8/5.8 49/37 1 1 .75 2.4 6.2
YSC120AK 1 380 3 5.1/3.9 3450 11.5/9.0 64/54 1 1 .75 2.5 7.7

82 RT-PRC006-EN
Electrical
Data (High Efficiency)

Table ED-6 — Electrical Characteristics — Compressor Motor And Condenser Motor — High Efficiency
Compressor Motor Condenser Fan Motors
Unit Amps1 Amps
Tons Model No. No. Volts Phase HP2 RPM RLA LRA No. Phase HP2 FLA LRA
YHC036A1 1 208-230 1 2.8 3450 16.1 88.0 1 1 .20 1.5 2.5
YHC036A3 1 208-230 3 2.8 3450 10.7 77.0 1 1 .20 1.5 2.5
3 YHC036A4 1 460 3 2.8 3450 5.8 39.0 1 1 .20 0.6 1.3
YHC036AW 1 575 3 2.8 3450 4.4 31.0 1 1 .20 0.5 1.2
YHC048A1 1 208-230 1 3.5 3450 19.0 109.0 1 1 .33 2.0 6.6
YHC048A3 1 208-230 3 3.5 3450 12.5 88.0 1 1 .33 2.0 6.6
4 YHC048A4 1 460 3 3.5 3450 6.5 44.0 1 1 .33 1.2 2.5
YHC048AW 1 575 3 3.5 3450 4.9 34.0 1 1 .33 0.7 1.5
YHC060A1 1 208-230 1 4.5 3450 25.0 169.0 1 1 .33 2.0 6.6
YHC060A3 1 208-230 3 4.5 3450 17.4 124.0 1 1 .33 2.0 6.6
5 YHC060A4 1 460 3 4.5 3450 7.8 59.6 1 1 .33 1.2 2.5
YHC060AW 1 575 3 4.5 3450 6.2 49.4 1 1 .33 0.9 1.5
YHC072A3 1 208-230 3 5.7 3450 20.7 156 1 1 .70 3.85 9.30
6 YHC072A4 1 460 3 5.7 3450 10 75 1 1 .70 2.50 5.80
YHC072AW 1 575 3 5.7 3450 8.2 54 1 1 .70 1.54 3.60
YHC092A3 2 208-230 3 3.5/3.3 3450 12.4/12.4 88/88 1 1 .70 3.85 9.30
7½ YHC092A4 2 460 3 3.5/3.3 3450 6.4/5.8 44/44 1 1 .70 2.50 5.80
YHC092AW 2 575 3 3.5/3.3 3450 4.8/4.8 34/34 1 1 .70 1.54 3.60
YHC102A3 2 208-230 3 3.9/3.5 3450 14.7/12.4 91/88 1 1 .75 4.0 9.4
8½ YHC102A4 2 460 3 3.9/3.5 3450 7.1/6.4 50/44 1 1 .75 2.8 6.8
YHC102AW 2 575 3 3.9/3.5 3450 5.4/4.8 37/34 1 1 .75 2.4 6.2
YHC120A3 2 208-230 3 4.8/3.5 3450 17.3/12.4 124/88 1 1 .75 4.0 9.4
10 YHC120A4 2 460 3 4.8/3.5 3450 9.0/6.4 59.6/44 1 1 .75 2.8 6.8
YHC120AW 2 575 3 4.8/3.5 3450 7.1/4.8 49.4/34 1 1 .75 2.4 6.2
Notes:
1. Amp draw for each motor; multiply value by numbers of motors to determine total amps.
2. HP for each compressor.

RT-PRC006-EN 83
Electrical
Data

Table ED-7 — Electrical Characteristics — Inducer Motor


Unit
Model No. Stages HP RPM Volts Phase LRA
Y*C036-060A 1 1/35 3000 208-230 1 0.6
Y*C072A*L,M
Y*C090,092,102A*L 1 1/35 3000/3000 208-230 1 0.6
Y*072A*H
Y*090, 092,102A*M,H 2 1/15 3500 208-230 1 0.42
Y*120A*L,M,H

Table ED-8— Electrical Characteristics — Power Exhaust


Accessory
Tons Model No. Volts Phase HP RPM1 FLA LRA
6-10 BAYPWRX026 208-230 1 0.87 1075 5.7 16.3
6-10 BAYPWRX027 460 1 0.87 1075 3.3 6.8
6-10 BAYPWRX028 575 1 0.87 1075 2.3 5.4
Note:
1. Two speed.

84 RT-PRC006-EN
Jobsite
Connections

Typical Number Of Wires

DISCONNECT Zone Sensors


SWITCH A— Manual Changeover ........................................ 4
(BY OTHERS) Manual/Auto Changeover .............................. 5
Manual/Auto Changeover with
B Status Indication LED’s ............................ 10
Programmable Night Setback
ZONE SENSOR OR A with Status Indication LED’s ..................... 7
THERMOSTAT

ROOFTOP Thermostats
UNIT A— 4 Wires, 24-volts

B— 3 Power Wires + 1 Ground Wire (three phase)


2 Power Wires + 1 Ground Wire (single phase)

For specific wiring information, see the installation instructions.


All wiring except power wires is low voltage.
All customer supplied wiring to be copper and must conform to applicable electrical codes (such as NEC or CEC) and local electrical codes. Wiring shown dotted is to be furnished
and installed by the customer.

RT-PRC006-EN 85
Dimensional
Data (3 - 5 Tons)

All dimensions are in inches/millimeters.

3, 4, and 5 Ton Standard Efficiency — Low and Medium Heat


3 and 4 Ton High Efficiency — Low and Medium Heat

1775

3, 4, and 5 Ton Standard Efficiency —High Heat


3 and 4 Ton High Efficiency — High Heat
5 Ton — High Efficiency — Low, Medium, and High Heat

1775

86 RT-PRC006-EN
Dimensional
Data (3 - 5 Tons)

All dimensions are in inches/millimeters.

3-5 Tons — Downflow Airflow Supply and Return;


Through the Base Utilities

3-5 Tons — Horizontal Airflow Supply and


Return

3-5 Tons — Unit Clearance and Roof


Opening

RT-PRC006-EN 87
Dimensional
Data (3 - 5 Tons)

All dimensions are in inches/millimeters.


37 1/8”
928 MM

3-5 Tons— Roof Curb

3-5 Tons — Downflow Duct Connections —


Field Fabricated

88 RT-PRC006-EN
Dimensional
Data (6 - 10 Tons)

All dimensions are in inches/millimeters.

6 Ton Standard and High


Efficiency
7½ Ton Standard Efficiency

7½ Ton High Efficiency


8½ and 10 Ton Standard and High Efficiency

RT-PRC006-EN 89
Dimensional
Data (6 - 10 Tons)

All dimensions are in inches/millimeters.

6-10 Tons — Downflow Airflow Supply and Return;


Through the Base Utilities

6-10 Tons — Horizontal Airflow Supply and Return Return


Supply

6-10 Tons — Unit Clearance and Roof


Opening

90 RT-PRC006-EN
Dimensional
Data (6 - 10 Tons)

All dimensions are in inches/millimeters.

6-10 Tons — Roof Curb

857

857

ALL FLANGES 1 1/4” (31 MM)

6-10 Tons — Downflow Duct


Connections — Field Fabricated

RT-PRC006-EN 91
Dimensional (3 - 5 Tons) Options/
Data Accessories

3-5 Tons — Economizer, Manual, or Motorized Damper


Hood 3-5 Tons — Barometric Relief Damper Hood

3-5 Tons — Height of Gas Pipe required


from Inside Base of Unit to Gas Shut off
assembly (Factory Provided)

3-5 Tons — Swing Diameter for Hinged Door(s) Option

92 RT-PRC006-EN
Dimensional (6 -10 Tons) Options/
Data Accessories

6-10 Tons — Economizer and Barometric


Relief Damper Hoods 6-10 Tons — Power Exhaust

6-10 Tons — Height of Gas Pipe required


from Inside Base of Unit to Gas Shut off
assembly (Factory Provided)

6-10 Tons — Swing Diameter for Hinged


Door(s) Option

RT-PRC006-EN 93
Weights

Table W-1 — Maximum Unit And Corner Weights (Lbs) And Center Of Gravity Dimensions (In.)
Unit Maximum Weights (Lbs)2 Corner Weights (Lbs)1 Center of Gravity (In.)
Tons Model No. Shipping Net A B C D Length Width
YSC036A 572 480 151 124 96 109 32 19
3
YHC036A 589 497 158 128 101 110 32 19
YSC048A 597 505 159 130 108 109 33 19
4
YHC048A 631 539 166 133 114 126 32 20
YSC060A 614 522 169 134 105 114 32 18
5
YHC060A 666 574 179 140 119 136 32 20
YSC072A 878 735 249 193 132 161 39 21
6
YHC072A 915 772 249 198 141 184 39 22
YSC090A 963 820 273 208 146 193 38 22
7½ YSC092A 965 822 277 222 147 175 40 21
YHC092A 1066 923 306 243 165 210 39 22
YSC102A 1042 899 297 243 165 194 40 21

YHC102A 1100 957 310 252 175 220 40 22
YSC120A 1063 958 317 261 177 202 41 21
10
YHC120A 1203 1060 342 277 197 245 40 22
NOTES:
1. Corner weights are given for information only.
2. Weights are approximate.

Table W-2 — Factory-installed Options Net Weights (Lbs)1,2


Net Weight
Accessory 3-5Tons 6-10Tons
Economizer 26 36
Barometric Relief 7 10
Powered Exhaust — 80
Motorized Outside Air Damper 20 30
Manual Outside Air Damper 16 26
Roof Curb 70 115
Oversized Motor 5 8
Belt Drive Motor 31 —
Smoke Detector, Return 7 7
Smoke Detector, Supply 5 5
Coil Guards 12 20
Hinged Doors 10 12
Powered Convenience Outlet 38 38
Through the Base Electrical 8 13
Through the Base Gas 5 5
Unit Mounted Circuit Breaker 5 5
Unit Mounted Disconnect 5 5
Novar Control 8 8
Dehumidification (Hot Gas Reheat) Coil 15 25
NOTES:
1.Weights for options not listed are < 5 lbs.
2.Net weight should be added to unit weight when ordering factory-installed accessories.

94 RT-PRC006-EN
Mechanical
Specifications

General UnitTop Evaporator and Condenser Coils


Units shall be convertible airflow. The top cover shall be one piece Internally finned, 5/16” copper tubes
Operating range shall be between 115°F construction or, where seams exist, it mechanically bonded to a configured
and 0°F cooling as standard from the shall be double-hemmed and gasket- aluminum plate fin shall be standard.
factory for units with microprocessor sealed. The ribbed top adds extra Coils shall be leak tested at the factory
controls. Operating range for units with strength and prevents water from to ensure pressure integrity. The
electromechanical controls shall be pooling on unit top. evaporator coil and condenser coil
between 115°F and 40°F. Cooling Filters shall be leak tested to 200 psig and
performance shall be rated in One inch, throwaway filters shall be pressure tested to 450 psig. The
accordance with DOE and/or ARI testing standard on all 3-5 ton units. The filter condenser coil shall have a patent
procedures. All units shall be factory rack can be converted to two inch pending 1 +1+ 1 hybrid design with
assembled, internally wired, fully capability. Two inch filters shall be factory slight gaps for ease of cleaning. A
charged with R-22, and 100 percent run- supplied on all 6-10 ton units. Optional removeable, reversible, double-sloped
tested before leaving the factory. Wiring two inch pleated filters shall be available. condensate drain pan is standard.
internal to the unit shall be colored and Provision for through the base
numbered for simplified identification. Compressors condensate drain is standard.
Units (except 380/60/3) shall be UL listed All 3 ton standard units shall have direct-
drive, hermetic, reciprocating type Gas Heating Section
and labeled, classified in accordance to
compressors.The reciprocating type The heating section shall have a
ANSIZ21.47 for gas fired central furnaces
compressors have a centrifugal oil pump progressive tubular heat exchanger
and UL 1995/CAN/CSA No. 236-M90 for
providing positive lubrication to moving design using stainless steel burners
central cooling air conditioners.
parts. Motor shall be suction gas-cooled and corrosion resistant steel
Canadian units shall be CSA certified.
and shall have a voltage utilization range throughout. An induced draft
Casing of plus or minus 10 percent of unit combustion blower shall be used to
Unit casing shall be constructed of zinc nameplate voltage. Crankcase heater, pull the combustion products through
coated, heavy gauge, galvanized steel. internal temperature, and current- the firing tubes. The heater shall use a
Exterior surfaces shall be cleaned, sensitive motor overloads shall be direct spark ignition (DSI) system. On
phosphatized, and finished with a included for maximum protection. initial call for heat, the combustion
weather-resistant baked enamel finish. Compressors shall have internal spring blower shall purge the heat exchanger
Unit’s surface shall be tested 1000 hours isolation and sound muffling to minimize for 20 seconds before ignition After
in a salt spray test in compliance with vibration transmission and noise. Low three unsuccessful ignition attempts, the
ASTM B117. Cabinet construction shall pressure switches shall be standard. entire heating system shall be locked
allow for all maintenance on one side of out until manually reset at the
the unit. Service panels shall have lifting 3 ton high efficiency and 4-10 ton thermostat/zone sensor. Units shall be
handles and be removed and reinstalled standard and high efficiency units shall suitable for use with natural gas or
by removing only a single fastener while have direct-drive, hermetic, scroll type propane (field-installed kit) and also
providing a water and air tight seal. All compressors with centrifugal type oil comply with the California requirement
exposed vertical panels and top covers pumps. Motor shall be suction gas-cooled for low NOx emissions.
in the indoor air section shall be and shall have a voltage utilization range
of plus or minus 10 percent of unit Outdoor Fans
insulated with a cleanable foil faced, fire-
nameplate voltage. Internal overloads The outdoor fans shall be direct-drive,
retardent permanent, odorless glass
shall be provided with the scroll statically and dynamically balanced,
fiber material. The base of the unit shall
compressors. Crankcase heaters shall be draw-through in the vertical discharge
be insulated with 1/2 inch, 1 pound
included on 7½ ton standard efficiency position. The fan motor shall be
density foil-faced, closed-cell material. All
units. permanently lubricated and shall have
insulation edges shall be either captured
built-in thermal overload protection.
or sealed. The unit’s base pan shall have Refrigerant Circuits
no penetrations within the perimeter of Each refrigerant circuit offers a choice of
the curb other than the raised 11/8 inch independent fixed orifice expansion
high downflow supply/return openings device or thermal expansion valve.
to provide an added water integrity Service pressure ports, and refrigerant
precaution, if the condensate drain backs line filter driers shall be factory-installed
up. The base of the unit shall have as standard. An area shall be provided
provisions for forklift and crane lifting, for replacement suction line driers.
with forklift capabilities on three sides of
the unit.

RT-PRC006-EN 95
Mechanical
Specifications

Indoor Fan Accessories/Options Oversized Motors


All 3-5 ton 3-phase units offer a choice of Factory or field-installed direct drive
direct-drive, FC, centrifugal fans or belt Roof Curb oversized motors shall be available for
driven, FC centrifugal fans with The roof curb shall be designed to mate high static applications.
adjustable motor sheaves. 3-5 ton direct with the unit’s downflow supply and
return openings and provide support and Powered Exhaust
drive oversized motors shall be available The field installed powered exhaust,
for high static operations. All 6-10 ton a watertight installation when installed
properly.The roof curb design shall allow available for 6-10 ton units, shall provide
units shall have belt drive motors with an exhaust of return air, when using an
adjustable idler-arm assembly for quick- field-fabricated rectangular supply/return
ductwork to be connected directly to the economizer, to maintain better bulding
adjustment to fan belts and motor pressurization.
sheaves. All motors shall be thermally curb. Curb design shall comply with
protected. All indoor fan motors meet the NRCA requirements. Curb shall be Discharge Air Sensing
U.S. Energy Policy Act of 1992 (EPACT). shipped knocked down for field assembly This factory or field option provides true
and shall include wood nailer strips. discharge air sensing in heating models.
Controls This sensor is a status indicator readable
Unit shall be completely factory wired Economizer
This accessory shall be either field or throughTracer™ orTracker™. This option
with necessary controls and contactor is available for microprocessor controlled
pressure lugs or terminal block for power factory-installed and is available with or
without barometric relief.The assembly units.
wiring. Units shall provide an external
location for mounting a fused disconnect includes fully modulating 0-100 percent Coil Guards
device. motor and dampers, minimum position Hail protection quality coil guards shall be
setting, preset linkage, wiring harness either factory or field-installed for
A choice of micro-processor controls or with plug, spring return actuators and condenser coil protection.
electromechanical controls shall be fixed dry bulb control. Optional solid state
available. Through the Base Electrical Access
enthalpy and differential enthalpy control An electrical service entrance shall be
Microprocessor controls provide for all 24 shall be either factory or field-installed. factory provided allowing electrical
volt control functions. With the The factory-installed economizer arrives access for both control and main power
microprocessor controls, the resident in the shipping position and shall be connections inside the curb and through
control algorithms shall make all heating, moved to the operating position by the the base of the unit. Option will allow for
cooling, and/or ventilating decisions in installing contractor. field installation of liquid-tight conduit and
response to electronic signals from Remote Potentiometer an external field-installed disconnect
sensors measuring indoor and outdoor Field-installed, the minimum position switch.
temperatures.The control algorithm setting of economizer shall be adjusted
maintains accurate temperature control, Through the Base Electrical with
with this accessory. Disconnect Switch
minimizes drift from set point, and
provides better building comfort. A Motorized Outside Air Dampers Factory-installed 3-pole, molded case
centralized Micro-processor shall provide Factory or field-installed manually set disconnect switch with provisions for
anti-short cycle timing and time delay outdoor air dampers shall provide up to through the base electrical connections
between compressors to provide a 50 percent outside air. Once set, outdoor are available.The disconnect switch will
higher level of machine protection. air dampers shall open to set position be installed in the unit in a water tight
when indoor fan starts.The damper shall enclosure with access through a swinging
24-volt electromechanical control circuit close to the full closed position when door. Factory wiring will be provided from
shall include control transformer and indoor fan shuts down. the switch to the unit high voltage
contactor pressure lugs for power wiring. terminal block.The switch will be UL/CSA
Unit shall have single point power entry Manual Outside Air Damper
Factory or field-installed rain hood and agency recognized. Note:The disconnect
as standard. switch will be sized per NEC and UL
screen shall provide up to 50 percent
outside air. guidelines but will not be used in place of
unit overcurrent protection.

96 RT-PRC006-EN
Mechanical
Specifications

Through the Base Electrical with Circuit Reference or Comparative Enthalpy Control Options
Breaker Reference or Comparative Enthalpy
This option is a factory-installed thermal option shall be available when a factory- Trane Communication Interface
magnetic, molded case, HACR Circuit installed Downflow Economizer is This factory or field-installed option shall
Breaker with provisions for through the ordered.This option is available for micro be provided to interface microprocessor
base electrical connections.The circuit controlled units. controlled units with theTrane Integrated
breaker will be installed in a water tight ComfortTM systems.
High Pressure Cutout
enclosure in the unit with access through This factory-installed option is offered for LonTalk® Communication Interface
a swinging door. Factory wiring will be units that do not have High Pressure This factory or field-installed option shall
provided from the switch to the unit high cutout as standard. All 3-phase models be provided to allow the unit to
voltage terminal block.The circuit breaker with scroll compressors include High communicate as a Tracer™LCI-R device
will provide overcurrent protection, be Pressure Cutout as standard. or directly with generic LonTalk Network
sized per NEC and UL guidelines, and be Building Automation System Controls.
agency recognized by UL/CSA. Hinged Access Doors
Sheet metal hinges are available factory- Zone Sensor
Powered or Unpowered Convenience installed on the Filter/Evaporator Access Field-installed, this accessory shall be
Outlet Door, Indoor Fan/Heat Exchanger Door, provided to interface with the Micro
This factory-installed option is a GFCI, and the Compressor/Control Access equipped units and shall be available in
120v/15amp, 2 plug, convenience outlet, Door. either manual, automatic programmable
either powered or unpowered. When the with night setback, with system
convenience outlet is powered, a service Supply and/or Return Air Smoke malfunction lights or remote sensor
receptacle disconnect will be available. Detector options.
The convenience outlet is powered from With this option installed, if smoke is
the line side of the disconnect or circuit detected, all unit operation will be shut Thermostats
breaker, and therefore will not be down. Reset will be manual at the unit. Two stage heating and cooling operation
affected by the position of the disconnect Return Air Smoke Detectors require or one stage heating and cooling shall be
or circuit breaker.This option can only be minimum allowable airflow when used available, for field installation, in either
ordered when theThrough the Base with certain models. See the Installation, manual or automatic changeover.
Electrical with either the Disconnect Operation, and Maintenance (IOM) Automatic programmable electronic with
Switch, or Circuit Breaker, option is manual for the models affected and the night set back shall also be available.
ordered. minimum allowable airflow required.This Novar Unit Controls
option is available for micro controlled Optional Novar rooftop unit controls shall
Phase Monitor units.
Phase monitor shall provide 100% be factory installed and tested. The
protection for motors and compressors Black Epoxy Coated Condenser Coil Novar electronic thermostat module will
against problems caused by phase loss, The coil provides corrosion protection to interface to the unit microprocesser and
phase imbalance, and phase reversal. condenser coils for seacoast application. will control the unit to the desired stage of
Phase monitor is equipped with an LED The protection is a factory applied cooling or heating.
that provides an ON or FAULT indicator. thermoset vinyl coating, bonded to Novar Return Air Sensor
normal aluminum fin stock.The uniform This option, when used in conjunction
Through the Base Gas Piping thickness of the bonded vinyl layer
The unit shall include a standard though with Novar Controls, will contain a factory
exhibits excellent corrosion protection in provided and wired zone temperature
the base gas provision. This factory- salt spray tests performed in accordance
installed option shall have all piping sensor located in the return air stream.
with ASTM B117.
necessary including, black steel, manual Enthalpy Control
gas shut-off valve, elbows, and union.The Dehumidification Option Replaces the dry bulb control with a wet
manual shut-off valve shall include a 1/8" The dehumidification (hot gas reheat) bulb changeover controller which has a
NPT pressure tap.This assembly will option shall be a factory-installed option fully adjustable setpoint. Enthalpy control
require minor field labor to install. that provides increased dehumidification. offers a higher level of comfort control,
The option shall consist of a hot-gas along with energy savings potential, than
Fan Failure/Clogged Filter Switches reheat coil located on the leaving air side
These factory or field-installed options the standard dry bulb control. This is due
of the evaporator coil prepiped and to the additional wet bulb sensing
allow for individual fan failure and dirty circuited.
filter indication in microprocessor capability.This option shall be available
controlled units.The fan failure switch will The option shall be equipped with for microprocessor controlled units. It can
disable all unit functions and “flash” the crankcase heater(s), low pressure be field-installed or factory-installed with
Service LED on the zone sensor.The dirty switch(es), Frostat™, and a thermostatic the factory-installed economizer.
filter switch will light the Service LED on expansion valve(s) (TXV) as standard.
the zone sensor and will allow continued
unit operation.

RT-PRC006-EN 97
Mechanical
Specifications

Differential Enthalpy Digital Display Zone Sensor


Replaces the standard dry bulb control The Digital LCD (Liquid Crystal Display)
with two enthalpy sensors that compare zone sensor has the look and functionality
total heat content of the indoor air and of standard zone sensors.This sensor
outdoor air to determine the most includes a digital display of set point
efficient air source.This control option adjustment and space temperature in F
offers the highest level of comfort control, (Fahrenheit) or C (Celsius). Includes FAN
plus energy efficiency, available.This and SYSTEM buttons (supports the
option shall be available for service functions of the standard sensor).
microprocessor controlled units. It can be E-squared memory stores last
field-installed or factory-installed with the programmed set points. Requires 24 VAC
factory-installed economizer. (Volts AC).This sensor should be utilized
Low Ambient Cooling with ReliaTel™ controls.
All microprocessor units shall have Dual Thermistor Remote Zone Sensor
cooling capabilities down to 0°F as This sensor will allow the customer to
standard. Electromechanical models reduce the total number of remote
have cooling capabilites to 40°F as built, sensors to obtain space temperature
or to 0°F by adding the optional low averaging.This sensor should be utilized
ambient (frostat) control. with ReliaTel controls.
Thermal Expansion Valve Humidity Sensor
All units shall have a short orifice Field installed, wall-mounted humidity
refrigerate control metering device. For sensor is used to control activation of the
more exact refrigerant flow, when using hot gas reheat dehumidification option.
unit in low airflow applications, aThermal The humidity sensor can be set for
Expansion Valve option shall be available. humidity levels between 40% and 60%
CO2 Sensing relative humidity by adjusting the ReliaTel
The CO2 sensor shall have the ability to Options Module.
monitor space occupancy levels within Humidity Sensor
the building by measuring the parts per Field installed, duct-mounted humidity
million of CO2 (Carbon Dioxide) in the air. sensor is used to control activation of the
As the CO2 levels increase, the outside air hot gas reheat dehumidification option.
damper modulates to meet the CO2 The humidity sensor can be set for
space ventilation requirements.The CO2 humidity levels between 40% and 60%
accessory shall be available as field relative humidity by adjusting the ReliaTel
installed. Options Module.
Ventilation Override Accessory
With the Ventilation Override Accessory
installed, the unit can be set to transition
up to 3 different pre-programmed
sequences for Smoke Purge,
Pressurization, and Exhaust.The
transition occurs when a binary input on
the RTOM is closed (shorted).This would
typically be a hard wired relay output
from a smoke detector or fire control
panel. The ventilation override accessory
shall be available as field installed.

98 RT-PRC006-EN
RT-PRC006-EN 99
*High Efficiency Units only

Literature Order Number RT-PRC006-EN


File Number PL-UN-RT-YSC/YHC3-10TONS-PRC006-EN-2-04
Supersedes PL-UN-RT-YSC/YHC3-10TONS-PRC006-EN-12-03
Trane
A business of American Standard Companies Stocking Location 05-03 Webb/Mason 2-04 Electronic Only
www.trane.com
For more information contact your local dealer
(distributor), local district office, or e-mail us at Trane has a policy of continuous product and product data improvement and reserves the right to change
[email protected] design and specifications without notice.