Rooftop Units
Precedent™
3 - 10Tons — 60 Hz
PrecedentTM . . . The same Trane With its sleek compact cabinet, rounded
quality... with added flexibility. corners and beveled top, it may just be
Precedent is a flexible line of packaged the most aesthetically pleasing
units that covers a wide variety of packaged unit on the planet. And, of
applications. course, Precedent carries the Trane
Electromechanical controls are available reputation for excellence, quality, and
for simpler applications, and for the reliability.
more sophisticated, Reliatel™ From simple applications, to the most
microprocessor controls. In addition to complex, Precedent has the solution.
controls, Precedent offers many other
outstanding features and option choices.
Introduction 2
Features and Benefits 4
Application Considerations 10
Selection Procedure 11
Model Number Description 13
General Data 14
Performance Data 27
Cooling Performance 27
Fan Performance 36
Heat Performance 74
Controls 76
Electric Power 78
Dimension and Weights 86
Mechanical Specifications 95
RT-PRC006-EN 3
Features and
Benefits
4 RT-PRC006-EN
Features and
Benefits
Flexible Applications
Easy Access Low Voltage Terminal Board • Only two roof curbs for the 3-10 ton
Precedent line. . .simplifies curb
Precedent’s Low Voltage Terminal Board selection.
is external to the electrical control • Standard or High Efficiency Cooling.
cabinet. It is extremely easy to test • Electromechanical or ReliaTel
operation of all unit functions. This is microprocessor controls to meet either
another cost and time saving installation the simple or the more complex
feature. application.
• Low, medium or high gas heat
capacities.
• Airflow is outstanding. The Precedent
can replace an older machine with old
ductwork and, in many cases, improve
comfort through better air distribution.
• Belt or direct drive —standard or
oversized supply fan motors meet a
wide airflow range.
Low Voltage Connections • Precedent offers ultimate flexibility.
The wiring of the low voltage Options and components are not pre-
connections to the unit and the zone packaged at the factory. Units are built
sensors is as simple as 1-1, 2-2, and 3-3. to order in our standard “shortest in
This simplified system makes it easy for the industry”ship cycle time.
the installer to wire.
Single-Side Service
Single-side service is standard on all
Precedent units.
RT-PRC006-EN 5
Features and
Benefits
6 RT-PRC006-EN
Features and
Benefits
Convenience Outlet
RT-PRC006-EN 7
Features and
Benefits
8 RT-PRC006-EN
Features and
Benefits
Quality And Reliability Testing • We perform a 100% coil leak test at the
• All Precedent™ designs were factory. The evaporator and condenser
coils are leak tested at 200 psig and
rigorously rain tested at the factory to
ensure water integrity. pressure tested to 450 psig.
• Actual shipping tests were performed • All parts are inspected at the point of
to determine packaging requirements. final assembly. Sub-standard parts are
Units were test shipped around the identified and rejected immediately.
country to determine the best • The requirement for cycle testing of
packaging. heat exchangers is 10,000 cycles by
• Factory shake and drop tests were ANSI Z21.47. This is the standard
used as part of the package design required by both UL and AGA for cycle
process to help assure that the unit test requirments. Trane requires the
arrives at the job site in top condition. design to be tested to 2½ times this
current standard.
• Rigging tests include lifting a unit into
the air and letting it drop one foot, • Every unit receives a 100% unit run test
assuring that the lifting lugs and rails before leaving the production line to
hold up under stress. make sure it lives up to rigorous Trane
requirements.
VariTrac™
VariTrac
When Trane’s changeover VAV System
for light commercial applications is
coupled with Precedent, it provides the
latest in technological advances for
comfort management systems and can
allow thermostat control in every zone
served by VariTrac.
RT-PRC006-EN 9
Application
Considerations
10 RT-PRC006-EN
Selection
Procedures
RT-PRC006-EN 11
Selection
Procedure
MA' 72.2°F DB
RA’ conditions 65°F WB
OA
75°F db SA' 53°F DB
63°F wb MA'
SA 74°F DB RA'
Step 1: Determine the mixed/
entering air condition (MA’) SA' REHEAT SA
MA’ = (% outside air*outside air dry-bulb
temperature) + (% return air*return air
dry-bulb temperature)
MA’ = (0.40*68°F) + (0.60*75°F)
Chart C-1
MA’ = 72.20°F db
Note: Repeat for wet-bulb
temperature (wb).
Plot on psychrometric chart.
Note: Reheat temperature rise is based Step 5: Determine static pressure
MA’ on supply airflow and leaving evaporator drop add for reheat
72.2°F db coil temperature. Table PD-61 shows a static pressure drop
65°F wb of 0.09” wc 0.35”+ 0.09” = 0.5” wc
Step 4: Determine leaving unit
Step 2: Determine leaving unit temperature Table PD-54 indicates that a standard
temperature Reheat temperature (obtained in step 3) motor and field installed low static drive
Leaving Unit Temperature = SA’ + SA’ kit is needed for this airflow and static
Utilize theTOPSS™ program to 21°F db + 53°F = 74°F db pressure range.
determine the leaving unit temperature. SA=74°F
12 RT-PRC006-EN
Model
Number
Description
Y S C 036 A 3 R L A ** C 0 0 0 C 1 0 0 0 1 A 1
1 2 3 4,5,6 7 8 9 10 11 12,13 14 15 16 17 18 19 20 21 22 23 24 25
DIGIT 1 - Unit Function DIGIT 14 - Fresh Air Selection DIGIT 20 - Convenience Outlet
Y = DX Cooling, Gas Heat 0 = No Fresh Air 0 = No Convenience Outlet
A = Manual Outside Air Damper 0-50% A = Unpowered Convenience Outlet
DIGIT 2 - Efficiency B = Motorized Outside Air Damper 0-50% B = Powered Convenience Outlet
C = Economizer, Dry Bulb 0-100% (3 phase only)
S = Standard Efficiency
without Barometric Relief
H = High Efficiency
D = Economizer, Dry Bulb 0-100% DIGIT 21 - Communications Options
with Barometric Relief 0 = No Communications Interface
DIGIT 3 - Airflow E = Economizer, Reference Enthalpy 1 = Trane Communications Interface
C = Convertible 0-100% without Barometric Relief 2 = LonTalk® Communications Interface
F = Economizer, Reference Enthalpy 3 = Novar 2024 Controls
DIGITS 4,5,6 - Nominal Gross Cooling 0-100% with Barometric Relief 4 = Novar 3051 Controls
G = Economizer, Comparative Enthalpy
Capacity (MBh) 0-100% without Barometric Relief
036 = 3-Ton H = Economizer, Comparative Enthalpy DIGIT 22 - Refrigeration System Option
048 = 4-Ton 0-100% with Barometric Relief 0 = Standard Refrigeration System
060 = 5-Ton A = Thermal Expansion Valve (TXV)
072 = 6-Ton DIGIT 15 - Supply Fan/Drive Type/Motor B = Dehumidification (Hot Gas Reheat Coil)
090 = 7½-Ton, Single Compressor
092 = 7½-Ton, Dual Compressors 0 = Standard Drive
1 = Oversized Motor DIGIT 23 - Refrigeration Controls
102 = 8½-Ton
120 = 10-Ton 2 = Optional Belt Drive Motor 0 = No Refrigeration Control
1 = High Pressure Control
DIGIT 16 - Hinged Service AccessFilters 2 = Frostat
DIGIT 7 - Major Design Sequence 3 = Crankcase Heater
A = First 0 = Standard Panels/Standard Filters 4 = High Pressure Control and Frostat
A = Hinged Access Panels/Standard Filters 5 = High Pressure Control and Crankcase
B = Standard Panels/2” Pleated Filters Heater
DIGIT 8 - Unit Voltage C = Hinged Access Panels/2” Pleated Filters 6 = Frostat and Crankcase Heater
1 = 208-230/60/1
7 = High Pressure Control, Frostat and
3 = 208-230/60/3 DIGIT 17 - Condenser Coil Protection Crankcase Heater
4 = 460/60/3
W = 575/60/3 0 = Standard Coil
K = 380/60/3 1 = Standard Coil with Hail Guard DIGIT 24 - Smoke Detector
2 = Epoxy Coated Condenser Coil 0 = No Smoke Detector
3 = Epoxy Coated Condenser Coil with A = Return Air Smoke Detector
DIGIT 9 - Unit Controls Hail Guard
E = Electromechanical B = Supply Air Smoke Detector
R = ReliaTel™Microprocessor C = Supply and Return Air Smoke
DIGIT 18 - Through the Base Provisions Detectors
0 = No Through the Base Provisions
DIGIT 10 - Heating Capacity A = Through the Base Electric DIGIT 25 - Monitoring Controls
L = Low B = Through the Base Gas Piping
M = Medium 0 = No Monitoring Control
C = Through the Base Electric and Gas
H = High 1 = Clogged Filter Switch
Piping
2 = Fan Failure Switch
3 = DischargeAir Sensing Tube
DIGIT 11 - Minor Design Sequence DIGIT 19 - Disconnect/Circuit Breaker/ 4 = Clogged Filter Switch and Fan Fail
A = First Sequence Phase Monitor (3 phase only) Switch
0 = No Disconnect/NoCircuit Breaker/No 5 = Clogged Filter Switch and Discharge
DIGITS 12, 13 - Service Sequence Phase Monitor Air Sensing Tube
1 = Unit Mounted Non-Fused Disconnect 6 = Fan Fail Switch and Discharge Air
**= Factory Assigned
2 = Unit Mounted Circuit Breaker Sensing Tube
3 = Phase Monitor 7 = Clogged Filter and Fan Fail Switches
4 = Phase Monitor & Non-Fused and Discharge Air Sensing Tube
Disconnect Switch 8 = Novar Return Air Sensor
5 = Phase Monitor & Circuit Breaker
Example:
Model number YSC036A3RLA**C000C10001A10 describes a unit with the following characteristics: DX Cooling with natural gas heating, 3 ton nominal cooling capacity, 208-230/60/3 power supply,
ReliaTel™ controls, low heat model. 0-100% dry bulb economizer without barometric relief, standard direct drive motor, standard access panels, standard condenser coil with no coil protection,
through the base electric and gas access, non-fused disconnect, no convenience outlet or communications interface, standard refrigeration coil, high pressure control, return air smoke detector, and
clogged filter switch.
RT-PRC006-EN 13
General (3 - 4 Tons)
Data Standard Efficiency
14 RT-PRC006-EN
General (3 - 4 Tons)
Data Standard Efficiency
RT-PRC006-EN 15
General (5 - 6 Tons)
Data Standard Efficiency
16 RT-PRC006-EN
General (5 - 6 Tons)
Data Standard Efficiency
RT-PRC006-EN 17
General (7½ - 8½ Tons)
Data Standard Efficiency
18 RT-PRC006-EN
General (7½ - 8½ Tons)
Data Standard Efficiency
RT-PRC006-EN 19
General (10 Tons)
Data Standard Efficiency
20 RT-PRC006-EN
General (10 Tons)
Data Standard Efficiency
RT-PRC006-EN 21
General (3 - 4 Tons)
Data High Efficiency
22 RT-PRC006-EN
General (3 - 4 Tons)
Data High Efficiency
RT-PRC006-EN 23
General (5 - 6 Tons)
Data High Efficiency
24 RT-PRC006-EN
General (5 - 6 Tons)
Data High Efficiency
RT-PRC006-EN 25
General (7½ - 10 Tons)
Data High Efficiency
26 RT-PRC006-EN
Performance (3 Ton)
Data Standard Efficiency
Table PD-1 — Gross Cooling Capacities (MBH) 3-Ton Single/Three Phase YSC036A1, A3, A4, AW
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 34.6 29.0 38.6 22.3 40.6 14.7 31.2 27.3 36.6 21.1 39.5 13.8 28.2 25.6 33.4 19.6 37.8 12.9 25.1 24.1 29.6 18.2 35.5 11.9
80 35.6 35.0 38.8 27.3 41.0 20.2 32.6 32.6 36.8 26.6 39.8 19.5 30.0 30.0 33.5 25.2 38.0 18.5 27.3 27.3 29.9 23.5 35.6 17.5
1080
85 37.6 37.6 39.2 32.5 41.5 24.7 35.6 35.6 37.2 32.2 40.1 24.2 32.8 32.8 34.2 31.0 38.2 23.8 30.1 30.1 30.7 29.3 35.8 23.0
90 39.3 39.3 39.7 37.6 42.0 29.2 37.8 37.8 37.9 37.6 40.4 29.1 35.7 35.7 35.7 35.7 38.5 28.9 33.0 33.0 32.9 32.9 36.0 28.4
75 35.6 30.9 39.0 22.8 40.9 14.9 32.2 29.2 37.3 22.1 39.8 14.1 29.0 27.5 34.3 20.7 38.2 13.1 25.9 25.9 30.4 19.0 36.0 12.1
80 36.7 36.7 39.3 28.4 41.4 20.6 34.3 34.3 37.4 28.1 40.2 20.3 31.4 31.4 34.5 26.9 38.4 19.3 28.6 28.6 30.7 25.2 36.1 18.3
1200
85 38.7 38.7 39.7 33.9 41.9 25.3 37.0 37.0 37.9 34.0 40.5 25.0 34.5 34.5 35.3 33.2 38.7 24.8 31.5 31.5 31.7 31.6 36.3 24.2
90 40.2 40.2 40.4 39.2 42.3 30.1 38.8 38.8 38.8 38.8 40.9 30.2 37.1 37.1 37.0 37.0 39.1 30.3 34.6 34.6 34.6 34.6 36.6 30.0
75 36.4 32.6 39.4 23.5 41.1 15.1 33.2 31.0 37.7 23.0 40.1 14.3 29.8 29.3 34.9 21.8 38.5 13.4 26.8 26.8 30.9 20.0 36.3 12.4
80 37.7 37.7 39.7 29.4 41.6 20.9 35.7 35.7 37.9 29.3 40.4 21.2 32.7 32.7 35.2 28.5 38.7 19.9 29.8 29.8 31.4 26.8 36.5 19.0
1320
85 39.4 39.4 40.2 35.2 42.1 25.9 37.9 37.9 38.5 35.6 40.8 25.7 35.9 35.9 36.2 35.3 39.1 25.7 32.9 32.9 32.9 32.9 36.7 25.3
90 40.8 40.8 40.9 40.5 42.6 30.8 39.7 39.7 39.6 39.6 41.2 31.2 38.0 38.0 38.0 38.0 39.5 31.6 35.9 35.9 35.9 35.9 37.1 31.5
75 37.0 34.1 39.7 24.0 41.3 15.3 34.1 32.8 38.0 23.7 40.3 14.5 30.6 30.6 35.5 22.7 38.7 13.6 27.7 27.7 31.4 21.0 36.6 12.6
80 38.4 38.4 40.0 30.3 41.8 21.2 36.7 36.7 38.3 30.5 40.8 21.0 33.9 33.9 35.8 30.0 39.0 20.4 30.8 30.8 32.0 28.4 36.8 19.7
1440
85 40.0 40.0 40.6 36.3 42.4 26.4 38.7 38.7 39.0 37.0 41.2 26.7 36.8 36.8 36.8 36.8 39.4 26.6 34.2 34.2 34.2 34.2 37.0 26.4
90 41.4 41.4 41.4 41.4 42.9 31.6 40.3 40.3 40.3 40.3 41.5 32.1 38.7 38.7 38.7 38.7 39.9 32.7 36.7 36.7 36.7 36.7 37.6 33.0
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
RT-PRC006-EN 27
Performance (4 Ton)
Data Standard Efficiency
Table PD-2 — Gross Cooling Capacities (MBH) 4-Ton Single Phase YSC048A1
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 45.5 38.7 52.4 30.0 56.4 20.1 41.6 36.6 49.0 28.3 54.4 18.9 37.6 34.5 44.4 26.7 51.8 17.5 33.5 32.3 39.8 24.5 48.0 15.8
80 46.5 46.5 52.5 37.6 56.8 28.1 43.2 43.2 49.1 35.9 54.8 26.7 39.9 39.9 44.6 33.8 52.0 25.2 36.5 36.5 40.1 31.6 48.2 23.4
1440
85 50.3 50.3 53.0 45.1 57.4 34.9 47.0 47.0 49.7 43.7 55.0 33.9 43.6 43.6 45.3 41.6 52.2 32.8 40.2 40.2 41.0 39.5 48.3 31.0
90 53.3 53.3 53.8 52.5 57.7 41.1 50.8 50.8 50.8 50.8 55.5 41.0 47.5 47.5 47.5 47.5 52.5 40.1 44.0 44.0 44.0 44.0 48.6 38.6
75 46.8 41.3 53.1 31.3 56.9 20.5 42.7 39.1 50.1 29.7 55.0 19.2 38.7 37.0 45.4 27.5 52.4 17.9 34.4 34.4 40.8 25.4 48.9 16.3
80 48.7 48.7 53.4 39.5 57.5 28.9 45.2 45.2 50.3 38.2 55.4 27.8 41.8 41.8 45.7 36.0 52.7 26.3 38.2 38.2 41.1 33.9 49.1 24.7
1600
85 52.2 52.2 53.9 47.5 58.1 36.1 49.3 49.3 51.0 46.7 55.7 35.3 45.7 45.7 46.7 44.7 52.9 34.5 42.1 42.1 42.1 42.1 49.2 33.0
90 54.9 54.9 54.9 54.9 58.4 42.8 52.7 52.7 52.7 52.7 56.2 42.9 49.8 49.8 49.8 49.8 53.3 42.5 46.2 46.2 46.2 46.2 49.7 41.3
75 48.1 43.8 53.6 32.5 57.3 20.8 43.8 41.6 50.8 31.1 55.5 19.6 39.8 39.5 46.3 29.0 52.9 18.2 35.8 35.8 41.5 26.7 49.6 16.7
80 50.5 50.5 54.0 41.2 58.0 29.6 47.1 47.1 51.1 40.3 55.9 29.0 43.4 43.4 46.7 38.2 53.2 27.4 39.8 39.8 42.0 36.0 49.7 25.8
1760
85 53.6 53.6 54.8 49.8 58.6 37.1 51.1 51.1 52.0 49.4 56.3 36.6 47.7 47.7 48.1 47.9 53.5 36.1 43.9 43.9 43.9 43.9 49.9 34.9
90 56.1 56.1 56.1 56.1 59.0 44.2 54.2 54.2 54.1 54.1 56.9 44.8 51.5 51.5 51.5 51.5 54.1 44.7 48.2 48.2 48.2 48.2 50.5 43.9
75 49.1 46.3 54.2 33.5 57.7 21.2 44.9 44.0 51.5 32.4 55.9 20.0 40.7 40.7 47.1 30.4 53.3 18.6 37.0 37.0 42.2 28.1 50.1 17.0
80 51.9 51.9 54.6 42.7 58.4 30.1 48.8 48.8 51.8 42.2 56.3 30.2 45.0 45.0 47.7 40.4 53.7 28.5 41.2 41.2 42.9 38.2 50.3 26.9
1920
85 54.7 54.7 55.5 51.8 59.1 38.1 52.5 52.5 52.9 51.8 56.8 37.8 49.4 49.4 49.4 49.4 54.1 37.6 45.5 45.5 45.5 45.5 50.5 36.6
90 57.1 57.1 57.1 57.1 59.4 45.6 55.3 55.3 55.3 55.3 57.4 46.4 52.8 52.8 52.8 52.8 54.7 46.7 49.8 49.8 49.8 49.8 51.3 46.2
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-3 — Gross Cooling Capacities (MBH) 4-Ton Three Phase YSC048A3, A4, AW
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 44.8 38.6 51.4 29.8 56.1 20.1 41.0 36.6 48.2 28.2 53.7 18.9 37.3 34.7 44.2 26.4 50.8 17.6 33.4 32.7 39.6 25.2 47.1 16.0
80 46.0 46.0 51.6 37.4 56.5 27.9 42.9 42.9 48.3 35.8 54.0 26.6 39.7 39.7 44.4 34.0 51.0 25.2 36.4 36.4 40.0 32.0 47.2 23.6
1440 85 49.6 49.6 52.0 44.8 56.7 34.8 46.8 46.8 48.9 43.6 54.2 34.0 43.6 43.6 45.1 41.8 51.2 32.7 40.3 40.3 41.0 39.8 47.4 31.1
90 52.5 52.5 52.9 52.2 57.2 41.6 50.2 50.2 50.1 50.1 54.6 41.1 47.2 47.2 47.2 47.2 51.5 40.1 43.9 43.9 43.9 43.9 47.7 38.6
75 46.1 41.1 52.1 31.1 56.7 20.5 42.1 39.0 49.1 29.6 54.4 19.3 38.3 37.1 45.1 27.8 51.5 18.0 34.3 34.3 40.6 25.7 47.9 16.5
80 48.1 48.1 52.4 39.3 57.2 29.0 44.9 44.9 49.2 37.9 54.7 27.7 41.5 41.5 45.4 36.2 51.7 26.3 38.1 38.1 41.0 34.2 48.0 24.8
1600 85 51.4 51.4 53.0 47.3 57.7 36.7 48.7 48.7 50.0 46.4 55.0 35.5 45.6 45.6 46.3 44.8 51.9 34.6 42.1 42.1 42.1 42.1 48.2 33.0
90 54.2 54.2 54.2 54.2 58.0 43.5 51.9 51.9 51.9 51.9 55.4 43.2 49.1 49.1 49.1 49.1 52.3 42.5 45.9 45.9 45.9 45.9 48.7 41.3
75 47.2 43.5 52.8 32.3 57.3 20.9 43.3 41.5 49.8 30.9 54.9 19.7 39.1 39.1 45.8 29.1 52.0 18.3 35.6 35.6 41.3 27.1 48.5 16.8
80 49.7 49.7 53.1 41.0 57.8 30.1 46.7 46.7 50.1 40.0 55.3 28.8 43.3 43.3 46.2 38.3 52.3 27.4 39.7 39.7 41.8 36.3 48.7 25.9
1760 85 52.8 52.8 53.8 49.7 58.1 37.7 50.3 50.3 51.0 49.1 55.6 37.0 47.2 47.2 47.2 47.2 52.5 36.1 43.7 43.7 43.7 43.7 48.9 34.9
90 55.5 55.5 55.5 55.5 58.7 45.3 53.4 53.4 53.4 53.4 56.1 45.2 50.7 50.7 50.7 50.7 53.1 44.7 47.6 47.6 47.6 47.6 49.5 43.8
75 48.2 45.8 53.3 33.4 57.8 21.3 44.4 43.8 50.4 32.1 55.4 20.0 40.3 40.3 46.5 30.4 52.5 18.6 36.6 36.6 41.9 28.3 49.0 17.2
80 51.0 51.0 53.7 42.7 58.3 31.1 48.1 48.1 50.7 41.9 55.7 29.6 44.7 44.7 47.0 40.3 52.8 28.4 41.1 41.1 42.6 38.3 49.2 26.9
1920 85 53.9 53.9 54.6 51.8 58.6 38.7 51.6 51.6 51.9 51.5 56.2 38.4 48.6 48.6 48.6 48.6 53.1 37.7 45.2 45.2 45.2 45.2 49.4 36.6
90 56.6 56.6 56.6 56.6 59.3 47.0 54.6 54.6 54.5 54.5 56.8 47.1 52.0 52.0 52.0 52.0 53.8 46.9 49.0 49.0 49.0 49.0 50.3 46.1
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
28 RT-PRC006-EN
Performance (5 - 6Ton)
Data Standard Efficiency
Table PD-4 — Gross Cooling Capacities (MBH) 5-Ton Single/Three Phase YSC060A1,A3,A4,AW, AK
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 57.4 49.1 64.8 37.9 69.2 25.3 53.3 47.0 61.8 36.3 67.2 24.1 49.4 45.0 57.6 34.3 64.3 22.8 45.2 42.9 52.4 32.7 60.6 21.2
80 59.0 59.0 65.1 47.1 69.8 35.0 55.6 55.6 62.0 45.7 67.6 33.8 52.2 52.2 57.8 43.9 64.6 32.3 48.6 48.6 52.8 41.6 60.8 30.6
1800
85 63.1 63.1 65.7 56.2 70.2 42.9 60.3 60.3 62.7 55.3 68.0 42.3 56.8 56.8 58.9 53.6 64.9 41.3 52.9 52.9 54.0 51.4 61.0 39.9
90 66.4 66.4 66.9 65.2 70.8 51.0 64.1 64.1 64.1 64.1 68.5 50.8 61.1 61.1 61.1 61.1 65.4 50.1 57.5 57.5 57.5 57.5 61.5 49.0
75 59.0 52.2 65.7 39.4 69.8 25.7 54.9 50.1 62.8 37.9 67.8 24.6 50.7 48.0 58.9 36.1 64.9 23.2 46.5 45.9 53.5 33.8 61.3 21.6
80 61.3 61.3 66.0 49.2 70.2 35.6 58.1 58.1 63.1 48.2 68.1 34.8 54.4 54.4 59.2 46.6 65.3 33.7 50.6 50.6 54.0 44.3 61.5 32.0
2000
85 65.1 65.1 66.8 59.1 70.9 44.2 62.5 62.5 64.0 58.5 68.7 43.8 59.3 59.3 60.4 57.3 65.7 43.1 55.2 55.2 55.8 55.2 61.8 41.9
90 68.1 68.1 68.0 68.0 71.6 52.9 65.9 65.9 65.9 65.9 69.4 52.9 63.1 63.1 63.1 63.1 66.3 52.5 59.7 59.7 59.7 59.7 62.4 51.7
75 60.3 55.2 66.3 40.6 70.2 26.1 56.3 53.1 63.6 39.5 68.2 25.0 52.0 51.0 59.9 37.8 65.4 23.6 47.7 47.7 54.5 35.4 61.8 22.0
80 63.1 63.1 66.8 51.2 70.8 37.9 60.2 60.2 64.0 50.5 68.7 35.6 56.5 56.5 60.3 49.1 65.8 34.6 52.4 52.4 55.2 46.9 62.1 33.3
2200
85 66.5 66.5 67.7 61.6 71.5 45.4 64.2 64.2 65.0 61.3 69.4 45.2 61.2 61.2 61.7 60.5 66.4 44.7 57.3 57.3 57.3 57.3 62.5 43.8
90 69.4 69.4 69.3 69.3 72.2 54.6 67.3 67.3 67.3 67.3 70.1 54.9 64.6 64.6 64.6 64.6 67.1 54.8 61.2 61.2 61.2 61.2 63.2 54.2
75 61.5 58.0 66.9 41.8 70.6 26.5 57.6 56.0 64.2 40.8 68.6 25.4 53.0 53.0 60.6 39.3 65.9 24.0 49.1 49.1 55.4 37.1 62.2 22.4
80 64.5 64.5 67.5 53.0 71.2 38.8 61.8 61.8 64.7 52.5 69.1 36.4 58.3 58.3 61.1 51.4 66.3 35.5 53.9 53.9 56.3 49.5 62.5 34.3
2400
85 67.7 67.7 68.5 63.9 72.0 46.5 65.4 65.4 65.9 63.9 69.9 46.5 62.5 62.5 62.5 62.5 66.9 46.2 58.9 58.9 58.9 58.9 63.0 45.5
90 70.4 70.4 70.4 70.4 72.8 56.1 68.4 68.4 68.4 68.4 70.6 56.6 65.8 65.8 65.8 65.8 67.7 56.8 62.4 62.4 62.4 62.4 63.9 56.5
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-5 — Gross Cooling Capacities (MBH) 6-Ton Three Phase YSC072A3,A4,AW, AK
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 65.9 55.0 73.4 43.5 76.7 28.3 61.0 52.5 70.7 40.9 75.4 27.3 56.3 50.1 66.3 38.8 73.2 26.0 51.7 47.7 60.9 36.4 70.3 24.6
80 67.6 66.2 73.7 52.2 77.5 38.9 63.2 63.2 70.9 51.1 76.0 37.8 59.2 59.2 66.4 49.1 73.7 36.4 55.3 55.3 61.0 46.6 70.6 34.9
2160 85 71.4 71.4 74.2 61.9 78.6 47.4 68.5 68.5 71.4 61.3 76.5 46.6 64.4 64.4 67.3 59.7 74.0 46.0 60.4 60.4 62.2 57.3 70.8 45.0
90 74.6 74.6 75.3 71.3 79.3 55.7 72.4 72.4 72.8 71.3 77.2 55.5 69.5 69.5 69.5 69.5 74.6 55.4 65.7 65.7 65.6 65.6 71.2 54.8
75 67.7 58.3 74.0 43.8 77.1 28.7 62.9 55.9 71.7 42.6 75.9 27.7 57.9 53.4 67.9 40.8 73.7 26.4 53.2 51.0 62.4 38.3 70.9 25.0
80 69.7 69.7 74.6 54.1 78.0 39.5 66.2 66.2 72.0 53.6 76.6 39.2 61.8 61.8 68.0 52.0 74.3 37.9 57.8 57.8 62.6 49.6 71.3 36.3
2400 85 73.4 73.4 75.3 64.5 79.0 48.2 70.9 70.9 72.7 64.5 77.2 47.9 67.4 67.4 69.1 63.6 74.8 47.6 63.2 63.2 64.2 61.4 71.7 47.0
90 76.2 76.2 76.5 74.3 79.9 57.1 74.3 74.3 74.3 74.3 77.9 57.4 71.7 71.7 71.7 71.7 75.5 57.7 68.5 68.5 68.4 68.4 72.2 57.5
75 69.1 61.4 74.7 44.9 77.4 29.0 64.5 59.1 72.5 44.3 76.2 28.1 59.4 56.6 69.0 42.5 74.2 26.9 54.7 54.2 63.6 40.1 71.3 25.4
80 71.6 71.6 75.3 55.8 78.4 40.0 68.6 68.6 72.8 55.8 77.0 41.1 64.2 64.2 69.1 54.7 74.6 38.6 60.0 60.0 63.9 52.4 71.9 37.7
2640 85 74.8 74.8 76.1 66.8 79.4 49.1 72.7 72.7 73.8 67.3 77.8 49.3 69.7 69.7 70.5 66.9 75.4 49.1 65.7 65.7 66.1 65.4 72.3 48.7
90 77.4 77.4 77.5 76.8 80.3 58.4 75.8 75.8 75.8 75.8 78.5 59.0 73.4 73.4 73.3 73.3 76.2 59.7 70.5 70.5 70.5 70.5 73.0 59.8
75 70.2 64.1 75.2 45.8 77.6 29.4 66.1 62.3 73.1 45.4 76.5 28.5 60.9 59.7 69.8 44.2 74.5 27.3 56.2 56.2 64.7 41.9 71.7 25.8
80 72.9 72.9 75.9 57.4 78.7 40.4 70.3 70.3 73.6 57.8 77.3 41.8 66.5 66.5 70.1 57.1 75.2 41.1 62.0 62.0 65.2 55.2 72.1 38.5
2880 85 75.9 75.9 76.8 68.8 79.7 49.9 74.0 74.0 74.7 69.8 78.5 50.6 71.3 71.3 71.6 69.8 75.9 50.4 67.8 67.8 67.7 67.7 72.9 50.1
90 78.3 78.3 78.3 78.3 80.7 59.6 76.8 76.8 76.8 76.8 79.0 60.5 74.6 74.6 74.6 74.6 76.7 61.6 71.9 71.9 71.9 71.9 73.7 61.9
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
RT-PRC006-EN 29
Performance (7½Ton)
Data Standard Efficiency
Table PD-6 — Gross Cooling Capacities (MBH) 7½-Ton Single Compressor Three Phase YSC090A3,A4,AW, AK
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 87.4 73.8 96.2 56.7 98.8 36.7 80.6 70.3 93.3 54.3 98.8 35.6 73.5 66.6 86.9 51.2 96.8 33.9 66.6 63.1 78.4 48.2 92.8 31.8
80 89.6 88.9 96.6 68.7 100.0 49.9 83.4 83.4 93.5 68.3 99.9 50.2 77.6 77.6 87.2 65.3 97.4 48.2 71.6 71.6 78.9 61.5 92.9 46.0
2700 85 94.2 94.2 97.5 81.6 101.2 60.4 90.4 90.4 94.4 82.2 100.9 61.9 84.8 84.8 88.5 79.8 97.8 61.4 78.5 78.5 80.7 76.2 93.2 59.9
90 98.0 98.0 98.7 93.9 102.3 71.0 95.8 95.8 96.2 95.8 101.2 72.9 91.6 91.6 91.6 91.6 98.5 74.3 86.0 86.0 86.0 86.0 93.7 73.5
75 89.7 78.4 96.7 57.3 99.1 37.2 83.0 75.0 94.6 56.7 99.2 36.1 75.8 71.3 88.9 53.9 97.5 34.5 68.7 67.7 80.3 50.1 93.8 32.5
80 92.2 92.2 97.5 70.9 100.3 50.4 87.4 87.4 95.0 71.8 100.4 50.9 81.4 81.4 89.3 69.5 98.3 50.3 75.0 75.0 81.1 65.8 94.1 48.1
3000 85 96.5 96.5 98.5 84.4 101.5 61.2 93.8 93.8 96.1 86.6 101.6 63.4 88.9 88.9 91.0 85.5 98.8 63.7 82.5 82.5 83.7 82.1 94.4 63.1
90 99.5 99.5 99.9 97.0 102.6 72.3 98.2 98.2 98.2 98.2 101.9 75.0 94.9 94.9 94.9 94.9 99.7 77.4 90.1 90.1 90.0 90.0 95.3 77.7
75 91.5 82.5 97.7 59.0 99.3 37.7 85.2 79.6 95.5 58.8 99.5 36.6 78.0 76.0 90.5 56.5 98.0 35.1 70.5 70.5 82.1 52.8 94.5 33.2
80 94.4 94.4 98.1 72.8 100.5 55.0 90.7 90.7 96.2 74.8 100.8 51.6 84.7 84.7 91.1 73.5 98.9 51.5 78.0 78.0 83.2 70.0 95.0 50.1
3300 85 98.0 98.0 99.2 86.8 101.7 62.0 96.1 96.1 97.5 90.5 102.0 64.7 92.0 92.0 93.1 90.6 99.5 65.6 86.2 86.2 86.2 86.2 95.4 65.8
90 100.5 100.5 100.7 99.4 102.8 73.4 99.9 99.9 99.9 99.9 102.4 76.8 97.2 97.2 97.2 97.2 100.5 80.1 93.0 93.0 93.0 93.0 96.5 81.4
75 92.9 86.2 98.1 59.9 99.4 38.2 87.3 84.1 96.3 60.6 99.8 37.2 79.6 79.6 91.7 58.9 98.3 35.7 72.9 72.9 83.7 55.4 95.1 33.8
80 96.0 96.0 98.6 74.3 100.7 56.8 93.1 93.1 97.1 77.5 101.0 55.7 87.6 87.6 92.5 77.2 99.5 52.7 80.7 80.7 85.1 74.1 95.5 51.6
3600 85 99.0 99.0 99.7 88.7 101.8 62.7 97.8 97.8 98.6 93.7 102.3 65.8 94.4 94.4 94.4 94.4 100.0 67.3 89.1 89.1 89.1 89.1 96.3 68.3
90 101.1 101.1 101.1 101.1 103.0 74.4 101.0 101.0 101.0 101.0 102.8 78.4 98.9 98.9 98.9 98.9 101.2 82.4 95.1 95.1 95.1 95.1 97.5 84.6
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-7 — Gross Cooling Capacities (MBH) 7½-Ton Dual Compressors Three Phase YSC092A3,A4,AW
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 84.6 72.9 93.9 55.3 98.4 36.4 78.2 69.6 90.1 53.3 96.9 35.1 71.8 66.3 83.9 50.4 94.0 33.3 65.3 63.1 76.5 47.1 89.4 31.2
80 86.8 86.8 94.4 68.5 99.6 50.0 81.8 81.8 90.5 67.5 98.0 49.7 76.4 76.4 84.3 64.7 94.5 47.5 70.9 70.9 77.1 61.4 89.6 45.3
2700 85 92.2 92.2 95.4 81.7 100.8 61.3 88.4 88.4 91.5 81.5 99.0 62.4 83.2 83.2 85.8 79.3 94.9 60.9 77.6 77.6 79.0 76.1 89.9 59.3
90 96.3 96.3 96.9 94.4 102.0 72.8 93.6 93.6 93.6 93.6 99.3 73.4 89.6 89.6 89.6 89.6 95.8 74.0 84.5 84.5 84.5 84.5 90.6 73.0
75 86.8 77.5 94.7 57.0 98.9 37.1 80.5 74.4 91.5 55.8 97.6 35.7 74.0 71.1 85.6 53.1 94.8 34.0 67.1 67.1 78.2 49.8 90.5 31.9
80 90.1 90.1 95.6 71.2 100.2 50.8 85.4 85.4 92.0 71.1 98.7 50.7 79.9 79.9 86.3 68.9 95.5 49.6 74.1 74.1 79.1 65.7 90.8 47.4
3000 85 94.7 94.7 96.8 85.3 101.4 62.7 91.5 91.5 93.3 86.2 99.7 63.7 86.9 86.9 88.2 84.9 96.1 63.5 81.3 81.3 81.2 81.2 91.2 62.6
90 98.3 98.3 98.3 98.3 102.7 74.8 96.2 96.2 96.1 96.1 100.3 76.2 92.7 92.7 92.7 92.7 97.1 77.5 88.0 88.0 88.0 88.0 92.2 77.4
75 88.7 81.9 95.7 58.9 99.3 37.6 82.6 79.0 92.5 58.2 98.1 36.2 75.5 75.5 87.1 55.7 95.4 34.6 69.6 69.6 79.6 52.4 91.3 32.5
80 92.3 92.3 96.5 73.7 100.7 51.5 88.4 88.4 93.2 74.4 99.3 51.7 82.9 82.9 87.9 72.8 96.1 51.0 76.9 76.9 80.8 69.8 91.7 49.5
3300 85 96.5 96.5 97.8 88.4 102.0 63.9 93.8 93.8 94.8 90.3 100.0 65.0 89.8 89.8 89.8 89.8 96.9 65.8 84.4 84.4 84.4 84.4 92.3 65.5
90 99.7 99.7 99.7 99.7 103.3 76.5 98.0 98.0 98.0 98.0 101.1 78.5 94.9 94.9 94.9 94.9 98.1 80.6 90.7 90.7 90.7 90.7 93.5 81.3
75 90.2 85.7 96.4 60.6 99.7 38.1 84.6 83.6 93.3 60.0 98.5 36.8 77.9 77.9 88.2 58.1 96.0 35.2 71.8 71.8 80.9 55.0 92.0 33.2
80 94.0 94.0 97.2 75.8 101.0 52.1 90.7 90.7 94.3 77.4 99.7 52.6 85.6 85.6 89.2 76.6 96.6 52.0 79.5 79.5 82.3 73.8 92.5 51.5
3600 85 97.8 97.8 98.7 91.1 102.4 65.0 95.6 95.6 96.1 93.9 100.5 66.3 91.9 91.9 91.9 91.9 97.6 67.9 86.9 86.9 86.9 86.9 93.1 68.2
90 100.8 100.8 100.8 100.8 103.7 78.1 99.3 99.3 99.3 99.3 101.7 80.7 96.6 96.6 96.6 96.6 98.9 83.4 92.7 92.7 92.7 92.7 94.6 84.9
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
30 RT-PRC006-EN
Performance (8½ - 10 Ton)
Data Standard Efficiency
Table PD-8 — Gross Cooling Capacities (MBH) 8½ Ton Three Phase YSC102A3, A4, AW, AK
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 96.3 82.3 106.6 62.7 112.5 41.5 89.0 78.5 103.2 60.6 110.9 40.0 81.8 74.9 96.6 57.5 107.6 38.1 74.9 71.3 87.6 55.2 102.5 35.8
80 98.0 98.0 107.2 77.1 113.7 57.0 92.9 91.4 103.4 76.3 111.5 57.1 86.3 86.2 96.9 73.3 108.2 54.0 80.2 80.2 88.1 69.4 102.8 51.5
3060 85 103.9 103.9 108.1 91.7 114.8 69.6 100.1 100.1 104.3 91.7 112.4 70.0 94.3 94.3 98.3 89.5 108.6 68.9 87.6 87.6 89.9 85.7 103.1 67.1
90 108.6 108.6 109.6 105.7 116.0 82.4 105.9 105.9 105.9 105.9 113.2 83.0 101.6 101.6 101.9 100.2 109.3 83.4 95.6 95.6 95.6 95.5 103.6 82.3
75 98.7 87.2 107.8 65.9 113.0 42.0 91.8 83.8 104.7 63.7 111.8 40.7 84.2 80.0 98.7 60.5 108.6 38.9 76.3 76.3 89.6 58.6 103.7 36.5
80 101.6 100.0 108.5 80.1 114.6 58.1 96.9 96.5 105.0 80.1 112.8 57.8 90.3 90.3 99.1 77.9 109.3 56.3 83.8 83.8 90.3 74.0 104.0 53.8
3400 85 106.8 106.8 109.6 95.7 115.8 71.4 103.6 103.6 106.2 96.7 114.0 70.7 98.7 98.7 100.9 95.5 109.8 71.7 91.7 91.7 91.7 91.7 104.3 70.7
90 111.0 111.0 111.0 111.0 117.0 84.9 108.8 108.8 108.9 107.2 114.4 86.1 105.1 105.1 105.0 104.8 110.7 87.4 99.8 99.8 99.7 99.7 105.2 87.1
75 100.7 91.7 109.2 64.5 114.0 42.8 93.8 88.7 106.1 66.5 113.5 41.7 85.4 85.4 100.4 63.3 109.4 39.6 79.4 77.5 91.3 59.4 104.6 37.2
80 104.1 103.6 109.6 82.9 115.3 59.0 100.0 100.0 106.6 84.3 113.7 59.0 94.0 94.0 100.9 82.2 109.6 60.2 87.0 87.0 92.2 78.5 105.1 56.0
3740 85 108.9 108.9 110.9 99.2 116.6 73.0 106.7 106.7 108.3 102.4 114.8 74.4 102.0 102.0 102.0 102.0 110.8 74.3 95.6 95.6 96.4 93.7 105.5 73.9
90 112.8 112.8 112.8 112.8 117.8 87.2 111.8 111.8 111.8 111.2 116.0 90.0 107.7 107.7 107.7 107.7 111.9 90.9 102.9 102.9 102.9 102.9 106.6 91.4
75 102.3 95.8 110.2 66.1 114.6 43.5 95.2 95.2 106.7 68.3 113.1 42.2 88.2 88.2 101.6 65.9 110.1 40.3 81.6 80.6 92.7 62.1 105.3 38.1
80 106.2 106.2 110.5 85.3 115.9 59.8 102.8 102.8 107.4 86.8 114.3 60.0 97.4 97.4 102.4 86.2 111.0 58.6 89.9 89.9 94.1 82.9 105.9 58.2
4080 85 110.5 110.5 111.9 102.3 117.2 74.4 108.3 108.3 109.2 105.1 115.5 76.3 104.5 104.5 104.4 104.4 111.5 77.2 98.7 98.7 99.0 97.4 106.4 76.8
90 114.2 114.2 114.2 114.2 118.5 89.3 112.7 112.7 112.7 112.7 116.8 92.7 109.7 109.7 109.7 109.7 112.9 94.2 105.2 105.2 105.2 105.2 107.8 95.4
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-9— Gross Cooling Capacities (MBH) 10 Ton Three Phase YSC120A3, A4, AW, AK
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 108.6 95.7 120.5 71.5 126.0 46.0 100.1 91.3 115.5 68.8 123.6 43.3 91.0 86.5 107.2 64.9 119.3 41.0 82.2 82.0 96.5 60.1 113.1 37.9
80 112.8 112.8 121.2 89.2 127.5 65.7 106.3 106.3 116.1 88.1 124.8 62.8 98.5 98.5 108.2 84.5 120.1 60.5 90.5 90.5 97.8 79.7 113.6 57.4
3600
85 119.5 119.5 122.6 106.9 129.0 78.5 114.8 114.8 117.7 107.0 126.2 79.2 108.2 108.2 110.5 104.5 121.8 76.8 100.1 100.1 100.1 100.1 114.2 76.6
90 124.3 124.3 124.6 123.6 130.4 93.6 121.0 121.0 121.0 121.0 127.6 95.7 116.0 116.0 116.0 116.0 122.0 95.1 109.4 109.4 109.4 109.4 115.3 94.5
75 111.6 102.3 121.7 73.9 126.7 46.9 103.4 98.1 117.1 72.3 124.5 42.7 94.2 93.4 109.5 68.7 120.2 41.9 85.3 85.3 98.8 64.0 114.3 38.8
80 116.7 116.7 122.6 92.7 128.2 64.5 111.1 111.1 118.0 93.0 125.7 64.2 103.4 103.4 110.8 90.4 121.4 63.2 95.0 95.0 100.6 85.8 114.9 60.3
4000
85 122.3 122.3 124.2 111.4 129.7 80.2 118.5 118.5 120.0 113.1 127.1 81.6 112.8 112.8 113.6 112.1 122.6 82.1 105.1 105.1 105.1 105.1 115.6 80.4
90 126.9 126.9 126.4 126.4 131.3 96.0 123.7 123.7 123.7 123.7 128.7 99.0 119.3 119.3 119.3 119.3 124.1 100.7 113.4 113.4 113.4 113.4 117.1 100.0
75 114.1 108.4 122.5 75.8 127.3 47.7 106.5 104.9 118.4 75.8 124.9 45.4 97.1 97.1 111.3 72.3 121.3 40.2 88.6 88.6 100.9 67.7 115.1 39.7
80 119.5 119.5 123.8 96.1 128.9 65.5 114.7 114.7 119.5 97.3 126.3 69.2 107.7 107.7 112.9 95.9 122.2 64.9 99.0 99.0 103.1 91.7 115.8 63.2
4400
85 124.9 124.9 125.5 115.5 130.4 81.9 121.1 121.1 121.8 118.3 127.9 83.7 116.0 116.0 116.0 116.0 123.6 85.0 109.2 109.2 109.2 109.2 116.8 84.0
90 127.9 127.9 128.0 128.0 132.0 98.3 126.1 126.1 125.6 125.6 129.5 101.8 121.7 121.7 121.7 121.7 125.3 104.7 116.2 116.2 116.2 116.2 118.5 104.7
75 116.1 113.8 123.1 77.6 127.8 48.5 108.9 108.9 119.2 78.1 125.4 46.2 100.5 100.5 112.8 76.1 121.4 43.6 91.6 91.6 102.6 71.3 115.8 40.6
80 121.4 121.4 124.5 98.6 129.4 66.4 117.3 117.3 120.8 101.1 126.9 66.5 111.1 111.1 114.6 100.9 122.9 66.4 102.5 102.5 105.4 97.5 116.5 65.7
4800
85 126.0 126.0 126.4 118.6 130.9 83.4 122.9 122.9 123.2 122.6 128.5 85.6 118.4 118.4 118.4 118.4 124.3 87.5 112.1 112.1 112.1 112.1 117.8 87.3
90 129.1 129.1 129.1 129.1 132.5 100.4 127.2 127.2 126.9 126.9 130.2 104.4 124.0 124.0 123.7 123.7 126.2 108.0 118.2 118.2 118.2 118.2 119.7 108.9
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
RT-PRC006-EN 31
Performance (3 - 4 Tons)
Data High Efficiency
Table PD-10 — Gross Cooling Capacities (MBH) 3-on YHC036A1, A3, A4, AW
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 34.2 29.2 39.8 22.7 43.1 15.2 31.1 27.4 37.0 21.2 41.3 14.1 28.0 25.7 33.3 19.8 39.0 12.9 24.8 24.0 29.8 18.1 36.1 11.6
80 34.9 34.9 40.0 28.5 43.5 21.3 32.3 32.3 37.1 27.1 41.6 20.1 29.7 29.7 33.5 25.3 39.2 18.8 27.1 27.1 30.0 23.6 36.2 17.5
1080
85 37.9 37.9 40.3 34.3 44.0 26.5 35.3 35.3 37.5 33.0 41.9 25.6 32.6 32.6 34.0 31.3 39.5 24.6 30.0 30.0 30.6 29.6 36.4 23.2
90 40.5 40.5 40.9 40.0 44.5 31.7 38.4 38.4 38.4 38.4 42.3 31.0 35.7 35.7 35.7 35.7 39.7 30.3 32.9 32.9 32.9 32.9 36.7 29.0
75 35.3 31.2 40.4 23.7 43.5 15.5 32.0 29.4 37.8 22.4 41.8 14.4 28.8 27.7 34.1 20.6 39.5 13.2 25.5 25.5 30.5 18.8 36.7 11.9
80 36.7 36.7 40.7 30.0 44.0 21.9 33.9 33.9 38.0 28.9 42.1 20.9 31.2 31.2 34.4 27.1 39.8 19.7 28.5 28.5 30.8 25.3 36.9 18.4
1200
85 39.6 39.6 41.1 36.3 44.6 27.4 37.1 37.1 38.5 35.4 42.5 26.8 34.3 34.3 35.1 33.8 40.0 26.0 31.5 31.5 31.5 31.5 37.1 24.8
90 41.9 41.9 41.9 41.9 45.1 33.0 39.9 39.9 39.9 39.9 42.9 32.6 37.6 37.6 37.6 37.6 40.4 32.1 34.7 34.7 34.7 34.7 37.4 31.1
75 36.2 33.2 40.9 24.7 43.8 15.8 32.8 31.4 38.4 23.4 42.1 14.7 29.4 29.4 34.8 21.7 39.9 13.5 26.5 26.5 31.0 19.9 37.2 12.2
80 38.2 38.2 41.2 31.4 44.4 22.4 35.4 35.4 38.7 30.5 42.6 21.7 32.5 32.5 35.2 28.9 40.2 20.5 29.7 29.7 31.5 27.1 37.4 19.2
1320
85 40.8 40.8 41.8 38.1 45.0 28.3 38.7 38.7 39.4 37.6 43.1 28.0 35.9 35.9 36.2 36.2 40.5 27.2 32.9 32.9 32.9 32.9 37.6 26.2
90 42.9 42.9 42.9 42.9 45.6 34.2 41.1 41.1 41.1 41.1 43.4 34.0 38.9 38.9 38.9 38.9 41.0 33.8 36.3 36.3 36.3 36.3 38.1 33.1
75 37.1 35.1 41.3 25.5 44.1 16.1 33.6 33.3 38.9 24.4 42.4 15.0 30.4 30.4 35.5 22.8 40.2 13.8 27.5 27.5 31.5 21.0 37.5 12.5
80 39.4 39.4 41.7 32.6 44.7 22.9 36.8 36.8 39.3 32.1 42.9 22.3 33.8 33.8 35.9 30.6 40.6 21.4 30.8 30.8 32.1 28.8 37.8 20.1
1440
85 41.7 41.7 42.4 39.7 45.3 29.0 39.8 39.8 40.1 39.5 43.5 29.0 37.3 37.3 37.3 37.3 40.9 28.3 34.2 34.2 34.2 34.2 38.0 27.6
90 43.7 43.7 43.7 43.7 45.9 35.3 42.1 42.1 42.1 42.1 43.9 35.3 40.0 40.0 40.0 40.0 41.5 35.4 37.5 37.5 37.5 37.5 38.6 34.9
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-11— Gross Cooling Capacities (MBH) 4-Ton YHC048A1, A3, A4, AW
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 45.3 39.9 51.4 30.3 54.9 19.9 41.1 37.7 48.4 28.8 53.1 18.7 37.1 35.6 43.9 26.7 51.0 17.4 33.2 33.2 39.3 24.6 47.8 16.0
80 47.1 47.1 52.0 38.4 55.5 28.1 43.8 43.8 48.7 36.9 54.6 27.2 40.3 40.3 44.3 34.9 51.3 25.6 36.9 36.9 39.8 32.8 47.9 24.1
1440
85 50.5 50.5 52.5 46.3 56.2 34.5 47.8 47.8 49.4 45.2 54.9 34.9 44.3 44.3 45.3 43.3 51.6 33.6 40.9 40.9 40.9 40.9 48.1 32.2
90 53.1 53.1 53.5 53.5 56.9 41.4 51.2 51.2 51.2 51.2 54.6 41.4 48.4 48.4 48.4 48.4 52.0 41.2 45.0 45.0 45.0 45.0 48.6 40.2
75 46.7 42.7 52.7 31.9 55.2 20.2 42.4 40.5 49.4 30.3 54.4 19.3 38.2 38.2 45.0 28.4 51.6 17.8 34.7 34.7 40.2 26.2 48.6 16.4
80 49.2 49.2 52.8 40.4 55.9 28.2 46.0 46.0 49.8 39.4 55.2 28.4 42.3 42.3 45.6 37.5 51.9 26.9 38.7 38.7 40.9 35.3 48.7 25.4
1600
85 52.1 52.1 53.5 48.8 56.6 35.4 49.9 49.9 50.6 48.3 55.7 36.8 46.7 46.7 47.0 46.8 52.2 35.2 43.0 43.0 42.9 42.9 49.0 34.3
90 54.5 54.5 54.8 54.8 57.4 42.7 52.8 52.8 52.8 52.8 55.2 42.9 50.5 50.5 50.5 50.5 52.9 43.5 47.4 47.4 47.4 47.4 49.6 43.0
75 47.8 45.4 53.2 33.4 55.5 20.6 43.7 43.3 50.1 31.8 54.7 19.6 39.7 39.7 46.0 30.0 51.9 18.2 36.1 36.1 41.0 27.7 49.1 16.8
80 50.6 50.6 53.4 42.1 56.2 28.7 47.8 47.8 50.5 41.5 55.7 29.4 44.1 44.1 46.7 39.9 52.4 28.1 40.4 40.4 41.9 37.8 49.3 26.7
1760
85 53.1 53.1 54.2 50.9 57.0 36.2 51.4 51.4 51.6 51.0 56.2 38.0 48.6 48.6 48.6 48.6 52.8 36.7 44.9 44.9 44.9 44.9 49.7 36.3
90 55.1 55.1 55.7 55.7 57.7 43.8 53.9 53.9 53.9 53.9 55.6 44.3 51.9 51.9 51.9 51.9 53.5 45.6 49.2 49.2 49.2 49.2 50.5 45.7
75 48.8 48.1 53.6 34.4 55.7 20.9 45.0 45.0 50.6 33.2 55.0 20.0 41.0 41.0 46.8 31.5 52.3 18.5 37.3 37.3 41.7 29.3 49.6 17.2
80 51.7 51.7 53.9 43.5 56.4 31.7 49.3 49.3 51.2 43.5 56.0 30.1 45.8 45.8 47.6 42.3 52.8 28.9 41.8 41.8 42.8 40.2 49.8 27.9
1920
85 53.9 53.9 54.8 52.7 57.2 36.9 52.4 52.4 52.4 52.4 56.5 39.1 50.0 50.0 50.0 50.0 53.2 38.1 46.6 46.6 46.6 46.6 50.3 38.1
90 55.7 55.7 56.3 56.3 58.0 44.8 54.7 54.7 54.7 54.7 56.0 45.6 53.0 53.0 53.0 53.0 54.0 47.4 50.5 50.5 50.5 50.5 51.2 48.1
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
32 RT-PRC006-EN
Performance (5 Ton)
Data High Efficiency
Table PD-12 — Gross Cooling Capacities (MBH) 5-Ton Single Phase YHC060A1
AmbientTemperature (F)
85 95
105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 56.2 48.2 64.3 37.8 68.4 24.8 51.4 45.6 60.5 35.2 66.7 23.5 46.8 43.2 55.3 32.8 63.9 21.9 42.2 40.8 50.0 31.0 59.9 20.1
80 57.6 57.6 64.6 46.6 69.3 34.7 53.7 53.7 60.7 44.8 67.3 33.1 49.8 49.8 55.5 42.3 64.2 31.5 45.9 45.9 50.5 39.9 60.1 29.6
1800
85 62.2 62.2 65.2 55.8 70.1 42.6 58.4 58.4 61.4 54.5 68.0 42.2 54.5 54.5 56.5 52.0 64.6 40.9 50.6 50.6 51.6 49.7 60.3 39.0
90 65.8 65.8 66.3 64.9 70.9 50.8 63.0 63.0 63.0 63.0 68.2 52.0 59.3 59.3 59.2 59.2 65.0 49.9 55.3 55.3 55.3 55.3 60.7 48.5
75 57.8 51.4 65.2 38.8 69.6 25.4 52.9 48.8 61.8 37.0 67.3 23.9 48.2 46.3 56.5 34.6 64.6 22.4 43.3 43.3 51.2 32.1 60.9 20.7
80 60.3 60.3 65.6 48.8 69.8 35.2 56.2 56.2 62.1 47.6 68.0 34.6 52.1 52.1 56.9 45.1 65.0 32.9 48.1 48.1 51.7 42.7 61.2 31.1
2000
85 64.4 64.4 66.3 58.7 70.7 43.8 61.2 61.2 63.0 58.1 68.7 43.9 57.1 57.1 58.2 56.0 65.4 42.8 53.0 53.0 53.0 53.0 61.4 41.5
90 67.6 67.6 67.6 67.6 71.6 52.5 65.2 65.2 65.2 65.2 69.5 53.3 62.0 62.0 62.0 62.0 66.0 52.6 58.0 58.0 58.0 58.0 62.0 51.8
75 59.4 54.5 65.7 40.1 69.3 25.6 54.3 51.9 62.7 38.7 67.7 24.3 49.6 49.4 57.6 36.3 65.1 22.8 45.0 45.0 52.2 33.8 61.6 21.1
80 62.4 62.4 66.3 50.7 70.3 35.8 58.4 58.4 63.1 50.1 68.5 35.4 54.2 54.2 58.2 47.9 65.7 34.2 50.0 50.0 52.9 45.4 61.9 32.5
2200
85 66.0 66.0 67.3 61.2 71.2 44.8 63.3 63.3 64.2 61.3 69.4 45.3 59.4 59.4 59.9 59.8 66.1 44.6 55.2 55.2 55.2 55.2 62.2 43.7
90 68.9 68.9 68.9 68.9 72.2 54.0 66.9 66.9 66.9 66.9 70.2 55.4 64.0 64.0 64.0 64.0 66.8 55.1 60.4 60.4 60.4 60.4 63.0 54.6
75 60.6 57.4 66.1 41.5 69.7 26.0 55.6 54.9 63.4 40.3 68.1 24.7 50.8 50.8 58.5 38.0 65.5 23.2 46.5 46.5 53.0 35.5 62.1 21.5
80 64.0 64.0 67.0 52.5 70.6 38.5 60.4 60.4 63.9 52.4 69.0 36.1 56.1 56.1 59.2 50.5 66.1 35.8 51.8 51.8 54.0 48.1 62.5 33.8
2400
85 67.2 67.2 68.0 63.5 71.5 50.9 64.9 64.9 65.3 64.2 69.9 46.6 61.4 61.4 61.4 61.4 67.0 46.8 57.2 57.2 57.2 57.2 62.9 45.6
90 69.8 69.8 69.8 69.8 72.6 55.3 68.1 68.1 68.1 68.1 70.8 57.1 65.5 65.5 65.5 65.5 67.5 57.3 62.2 62.2 62.2 62.2 63.9 57.2
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-13 — Gross Cooling Capacities (MBH) 5-Ton Three Phase YHC060A3, A4, AW
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 56.6 49.0 64.4 37.5 67.7 24.7 52.0 46.8 60.9 35.7 66.2 23.3 47.0 44.2 55.9 33.3 63.6 21.8 42.3 41.7 50.0 30.7 59.8 20.0
1800 80 58.5 58.5 64.6 47.0 68.6 34.7 54.7 54.7 61.2 45.5 66.8 33.3 50.6 50.6 56.3 43.2 64.1 31.7 46.4 46.4 50.5 40.5 60.0 29.8
85 62.9 62.9 65.3 56.4 69.4 42.2 59.6 59.6 61.9 55.5 67.7 42.3 55.6 55.6 57.3 53.2 64.3 41.1 51.2 51.2 51.9 50.7 60.3 39.5
90 66.2 66.2 66.4 65.6 70.3 50.3 63.7 63.7 63.7 63.7 68.4 51.2 60.3 60.3 60.3 60.3 64.9 50.3 56.4 56.4 56.3 56.3 60.8 49.1
75 58.3 52.5 65.0 39.1 68.1 25.1 53.6 50.0 62.0 37.6 66.6 23.8 48.6 47.7 57.2 35.4 64.2 22.3 43.8 43.8 51.2 32.7 60.6 20.5
2000 80 61.1 61.1 65.6 49.2 69.0 34.6 57.3 57.3 62.4 48.4 67.5 34.8 53.2 53.2 57.8 46.2 64.7 33.2 48.7 48.7 52.0 43.6 60.9 31.4
85 64.9 64.9 66.4 59.2 69.9 43.1 62.1 62.1 63.4 59.1 67.8 43.0 58.4 58.4 59.2 57.5 64.9 43.9 54.0 54.0 54.0 54.0 61.2 42.0
90 67.7 67.7 67.7 67.7 70.8 51.7 65.7 65.7 65.7 65.7 68.6 52.2 62.8 62.8 62.8 62.8 65.9 52.9 59.0 59.0 59.0 59.0 61.9 52.3
75 59.9 55.8 65.8 40.7 68.4 25.5 55.2 53.4 62.9 39.5 67.0 24.2 50.0 50.0 58.3 37.3 64.6 22.7 45.6 45.6 52.4 34.7 61.2 21.0
2200 80 63.1 63.1 66.3 51.0 69.3 35.2 59.7 59.7 63.5 51.0 67.9 35.1 55.5 55.5 59.0 49.2 65.4 34.5 50.8 50.8 53.4 46.6 61.6 32.9
85 66.4 66.4 67.2 61.6 70.2 43.9 64.0 64.0 64.6 62.4 68.8 44.9 60.6 60.6 60.6 60.6 66.0 45.1 56.4 56.4 56.4 56.4 62.0 44.2
90 68.7 68.7 68.7 68.7 71.2 52.8 67.1 67.1 67.1 67.1 69.7 54.9 64.5 64.5 64.5 64.5 66.9 55.8 61.0 61.0 61.0 61.0 62.9 55.3
75 61.2 59.0 66.2 41.7 68.6 25.9 56.3 56.3 63.6 41.3 67.3 24.6 51.9 51.9 59.2 39.0 65.0 23.1 47.2 47.2 53.4 36.6 61.7 21.4
2400 80 64.5 64.5 67.0 53.1 69.6 35.6 61.6 61.6 64.2 53.3 68.2 35.7 57.5 57.5 60.1 52.1 65.8 35.5 52.8 52.8 54.7 49.6 62.1 34.3
85 67.3 67.3 68.1 64.0 70.5 44.7 65.4 65.4 65.6 65.2 69.1 46.0 62.4 62.4 62.3 62.3 66.6 46.8 58.4 58.4 58.4 58.4 62.6 46.2
90 69.4 69.4 69.5 69.5 71.5 53.9 68.1 68.1 68.1 68.1 70.1 56.3 65.7 65.7 65.7 65.7 67.6 58.0 62.5 62.5 62.5 62.5 63.7 57.9
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
RT-PRC006-EN 33
Performance (6 - 7½ Ton)
Data High Efficiency
Table PD-14 — Gross Cooling Capacities (MBH) 6-Ton Three Phase YHC072A3,A4,AW
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 67.3 56.6 73.6 42.5 74.5 27.6 61.6 53.5 71.8 41.9 75.1 26.6 55.8 50.4 66.8 38.7 74.1 25.3 49.8 47.2 59.9 36.3 71.3 23.5
80 68.7 68.2 73.8 51.7 75.4 37.0 63.6 63.6 72.0 52.1 76.0 38.1 58.9 58.9 66.9 49.7 74.7 36.4 54.1 54.1 60.2 46.5 71.5 34.5
2160 85 72.2 72.2 74.5 61.4 76.2 44.5 69.2 69.2 72.5 62.8 76.8 46.1 64.6 64.6 67.8 60.9 75.0 46.2 59.5 59.5 61.3 57.7 71.7 45.4
90 74.7 74.7 75.3 70.6 77.0 51.9 73.4 73.4 73.7 73.2 77.7 55.1 70.1 70.1 70.1 70.1 75.6 56.1 65.4 65.4 65.4 65.4 72.1 55.8
75 69.0 60.1 74.0 43.3 74.5 27.9 63.5 57.2 72.7 43.1 75.2 27.0 57.5 54.0 68.4 40.9 74.5 25.7 51.8 51.0 61.5 37.6 72.0 24.0
80 70.7 70.7 74.3 52.9 75.4 37.2 66.8 66.8 73.0 54.6 76.2 37.8 61.9 61.9 68.7 53.0 75.1 37.4 56.7 56.7 61.9 49.8 72.4 36.1
2400 85 73.8 73.8 75.0 63.0 76.2 44.9 71.9 71.9 73.8 66.0 77.1 47.0 67.9 67.9 69.7 65.4 75.5 47.5 62.7 62.7 63.6 62.4 72.6 47.7
90 75.6 75.6 75.9 72.4 77.0 52.5 75.2 75.2 75.1 75.1 78.0 56.3 72.8 72.8 72.7 72.7 76.4 58.2 68.8 68.8 68.8 68.8 73.2 59.0
75 70.3 63.2 74.2 43.9 74.6 28.3 65.2 60.8 73.2 44.5 75.4 27.4 59.2 57.7 69.6 42.9 74.7 26.2 53.2 53.2 62.9 39.8 72.5 24.6
80 72.3 72.3 74.5 53.9 75.4 37.4 69.5 69.5 73.8 56.7 76.3 38.2 64.6 64.6 70.0 56.1 75.6 38.5 59.2 59.2 63.5 53.0 73.0 37.7
2640 85 74.7 74.7 75.3 64.3 76.2 45.2 73.7 73.7 74.7 68.7 77.3 47.6 70.5 70.5 71.3 69.3 76.1 48.9 65.6 65.6 65.6 65.6 73.4 49.7
90 76.1 76.1 76.2 73.6 76.9 53.0 76.2 76.2 76.2 76.2 78.1 57.2 74.5 74.5 74.5 74.5 76.9 59.9 71.2 71.2 71.2 71.2 74.1 61.7
75 71.3 65.8 74.3 44.4 74.6 28.7 66.8 64.4 73.7 45.6 75.5 27.8 60.5 60.5 70.6 44.8 74.9 26.6 55.1 55.1 64.1 41.8 72.9 25.0
80 73.3 73.3 74.7 54.8 75.4 37.6 71.4 71.4 74.4 58.5 76.4 38.5 67.0 67.0 71.0 58.9 75.9 39.1 61.4 61.4 64.9 56.2 73.3 38.6
2880 85 75.1 75.1 75.5 65.3 76.2 45.6 74.8 74.8 75.4 70.8 77.4 48.2 72.4 72.4 72.4 72.4 76.4 49.9 68.2 68.2 68.1 68.1 74.0 51.5
90 76.3 76.3 76.3 74.5 76.9 53.5 76.9 76.9 76.9 76.9 78.2 58.0 75.7 75.7 75.7 75.7 77.2 61.3 72.9 72.9 72.9 72.9 74.8 64.1
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-15 — Gross Cooling Capacities (MBH) 7½-Ton Dual Compressors Three Phase YHC092A3,A4,AW
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 85.7 72.4 95.8 56.8 99.9 37.1 79.3 69.3 92.0 53.7 98.8 35.8 72.8 66.0 85.9 50.8 96.1 34.2 66.1 62.6 78.5 49.1 91.8 32.2
80 87.5 87.0 96.2 68.5 101.1 50.4 81.8 81.8 92.4 67.4 99.6 50.2 76.6 76.6 86.2 64.6 96.7 48.0 71.1 71.1 79.0 61.4 92.0 45.8
2700 85 92.8 92.8 97.0 81.6 102.3 61.3 88.5 88.5 93.1 81.1 100.3 61.3 83.4 83.4 87.1 78.6 97.0 60.9 77.9 77.9 80.3 75.4 92.3 59.4
90 97.2 97.2 98.3 94.2 103.5 72.4 94.3 94.3 94.3 94.3 101.1 73.1 90.0 90.0 90.0 90.0 97.8 73.7 84.9 84.9 84.9 84.9 92.9 72.7
75 87.9 77.0 96.6 57.3 100.4 37.6 81.5 73.7 93.5 56.1 99.4 36.4 74.9 70.5 87.8 53.4 96.9 34.8 67.4 67.4 80.5 50.2 92.8 32.8
80 90.5 90.5 97.4 71.2 101.6 51.1 85.6 85.6 94.0 71.0 100.4 50.9 80.2 80.2 88.2 68.7 97.3 49.8 74.5 74.5 81.0 65.5 93.2 47.9
3000 85 95.6 95.6 98.4 85.1 102.9 62.5 92.2 92.2 95.0 85.8 101.3 63.3 87.3 87.3 89.5 84.1 98.1 63.3 81.8 81.8 82.9 81.2 93.6 62.5
90 99.4 99.4 99.9 98.1 104.1 74.1 97.2 97.2 97.2 97.2 102.1 75.5 93.6 93.6 93.5 93.5 99.1 77.0 88.8 88.8 88.7 88.7 94.4 76.9
75 89.8 81.3 97.5 59.0 100.7 38.1 83.6 78.2 94.6 58.3 99.8 37.1 77.0 75.0 89.2 55.9 97.5 35.4 70.0 70.0 82.1 52.8 93.6 33.4
80 93.2 93.2 98.3 73.5 102.0 51.7 88.9 88.9 95.2 74.2 101.0 52.0 83.4 83.4 89.8 72.6 97.9 50.6 77.6 77.6 82.8 69.5 94.1 49.9
3300 85 97.6 97.6 99.4 88.0 103.3 67.9 94.9 94.9 96.5 90.0 101.9 64.8 90.5 90.5 91.7 89.4 99.0 67.3 85.2 85.2 85.1 85.1 94.7 65.2
90 100.9 100.9 100.9 100.9 104.6 75.6 99.2 99.2 99.2 99.2 102.8 77.7 96.1 96.1 96.1 96.1 100.1 80.0 91.8 91.8 91.8 91.8 95.7 80.7
75 91.5 85.3 98.2 60.6 101.0 38.6 85.5 82.6 95.4 60.2 100.2 37.5 78.5 78.5 90.5 58.3 98.0 35.9 72.4 72.4 83.4 55.2 94.3 34.0
80 95.2 95.2 99.0 75.4 102.3 56.8 91.5 91.5 96.3 77.2 101.5 52.7 86.3 86.3 91.3 76.3 98.4 51.4 80.4 80.4 84.4 73.4 94.7 51.4
3600 85 99.1 99.1 100.2 90.6 103.6 69.8 96.9 96.9 97.8 93.6 102.4 66.1 93.1 93.1 93.1 93.1 99.7 69.8 88.0 88.0 87.9 87.9 95.6 67.8
90 101.9 101.9 101.9 101.9 105.0 76.9 100.7 100.7 100.7 100.7 103.4 79.6 98.0 98.0 97.9 97.9 100.8 82.5 94.0 94.0 94.0 94.0 96.7 84.1
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
34 RT-PRC006-EN
Performance (8½ - 10 Ton)
Data High Efficiency
Table PD-16 — Gross Cooling Capacities (MBH) 8½-Ton Three Phase YHC102A3,A4,AW
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 94.0 81.8 105.7 62.8 110.8 40.9 86.3 77.8 100.7 59.7 109.7 39.3 79.0 74.2 92.4 56.0 105.5 37.1 71.8 70.5 84.0 53.1 99.6 34.6
80 96.9 96.9 106.2 77.6 112.0 56.0 90.6 90.6 101.1 75.9 110.1 55.4 84.5 84.5 92.9 72.2 106.1 53.2 78.3 78.3 84.7 68.5 99.8 50.6
3060 85 103.5 103.5 107.2 92.9 113.2 68.7 98.6 98.6 102.2 92.1 111.6 70.3 92.1 92.1 94.5 88.8 106.4 68.8 85.8 85.8 86.7 85.2 100.0 66.5
90 108.4 108.4 109.0 107.7 114.4 81.6 105.0 105.0 105.0 105.0 112.6 84.9 99.9 99.9 99.9 99.9 107.3 83.9 93.5 93.5 93.5 93.5 100.8 82.6
75 96.6 87.2 107.1 64.7 111.4 41.5 88.7 83.3 102.4 62.6 110.7 40.1 81.4 79.6 94.4 59.1 106.6 37.9 74.2 74.2 85.9 55.4 101.1 35.5
80 100.9 100.9 107.7 81.0 112.7 56.9 94.9 94.9 103.0 80.4 111.7 57.5 88.3 88.3 95.2 77.1 107.3 55.7 81.8 81.8 86.8 73.4 101.4 53.1
3400 85 106.6 106.6 108.9 97.4 114.0 70.2 102.6 102.6 104.4 97.8 112.8 72.9 96.5 96.5 97.6 95.6 108.0 72.4 89.9 89.9 89.8 89.8 101.8 70.8
90 110.8 110.8 110.8 110.8 115.3 83.8 108.1 108.1 108.1 108.1 114.0 88.5 103.8 103.8 103.8 103.8 108.9 88.3 97.8 97.8 97.8 97.8 102.8 87.9
75 98.9 92.5 107.4 65.9 112.0 42.2 91.2 88.7 103.7 65.4 111.1 40.7 83.5 83.5 96.3 62.2 107.5 38.7 76.9 76.9 87.5 58.4 102.2 36.2
80 103.7 103.7 108.8 84.0 113.3 57.7 98.7 98.7 104.5 84.5 112.4 58.7 91.7 91.7 97.3 81.9 108.3 57.6 85.0 85.0 88.8 78.2 102.6 55.5
3740 85 108.8 108.8 110.1 100.9 114.6 76.9 105.4 105.4 106.4 103.0 113.7 75.1 100.2 100.2 100.2 100.2 109.3 75.7 93.4 93.4 93.4 93.4 103.1 74.4
90 112.3 112.3 112.1 112.1 115.9 85.7 110.4 110.4 110.4 110.4 114.9 91.4 106.5 106.5 106.5 106.5 110.2 92.3 101.3 101.3 101.3 101.3 104.4 92.7
75 100.9 97.3 108.1 67.4 112.5 42.9 93.1 93.1 104.7 67.9 111.5 41.4 86.2 86.2 97.8 65.2 108.2 39.4 79.4 79.4 88.8 61.3 103.0 36.9
80 105.9 105.9 109.5 86.2 113.8 58.4 101.6 101.6 105.8 88.2 112.8 59.6 94.9 94.9 99.1 86.5 109.2 59.6 87.9 87.9 90.6 82.8 103.5 57.8
4080 85 110.2 110.2 110.9 103.4 115.1 79.5 107.6 107.6 107.6 107.6 114.1 76.6 103.0 103.0 103.0 103.0 109.9 77.6 96.6 96.6 96.6 96.6 104.2 77.7
90 112.9 112.9 112.9 112.9 116.5 87.5 112.2 112.2 112.2 112.2 115.4 93.4 108.6 108.6 108.6 108.6 111.3 95.9 103.9 103.9 103.9 103.9 105.8 97.0
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-17 — Gross Cooling Capacities (MBH) 10-Ton Three Phase YHC120A3,A4,AW
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 107.0 94.4 117.4 75.0 123.4 46.0 98.7 90.1 114.7 68.8 121.9 44.4 88.5 88.5 107.2 65.3 118.6 42.2 82.3 78.8 97.8 61.1 113.6 39.6
3600 80 110.9 108.6 119.9 88.2 125.0 62.5 104.5 104.1 115.2 87.5 123.4 62.3 97.7 97.7 107.8 84.3 119.4 60.8 90.6 90.6 98.5 80.1 114.3 58.3
85 117.6 117.6 120.9 105.0 126.6 76.7 113.1 113.1 116.5 105.8 124.9 78.1 106.9 106.9 107.0 107.0 120.9 78.1 99.9 99.9 100.0 100.0 114.8 76.5
90 122.5 122.5 122.4 122.4 128.2 91.1 119.6 119.6 119.6 117.1 126.4 94.1 115.0 115.0 114.7 114.6 121.6 94.3 109.0 109.0 109.0 109.0 115.8 94.3
75 109.8 100.5 119.4 71.9 122.5 46.5 99.7 99.7 116.1 71.5 121.7 45.0 92.5 92.5 110.1 69.1 119.4 43.0 85.6 83.4 100.9 65.0 114.6 40.5
4000 80 114.6 114.1 120.8 90.1 124.1 68.3 109.3 109.3 117.0 91.2 123.4 62.7 102.3 102.3 110.8 89.9 120.6 62.5 94.8 94.8 101.9 86.0 115.5 61.1
85 120.5 120.5 122.3 107.9 125.9 76.4 117.0 117.0 118.6 110.2 125.0 78.8 111.6 111.6 111.8 111.8 122.1 80.4 104.7 104.7 105.8 102.6 116.3 79.7
90 125.2 125.2 124.2 124.2 127.6 90.9 122.4 122.4 121.7 120.9 126.6 95.1 118.5 118.5 118.3 118.3 123.6 98.4 113.1 113.1 113.3 113.3 117.7 98.6
75 112.3 106.1 121.2 74.8 124.6 47.6 103.6 103.6 117.1 75.5 123.0 46.0 96.7 93.9 111.2 72.2 120.0 43.7 88.6 88.0 102.0 68.2 115.3 41.2
4400 80 117.6 117.6 122.5 94.7 126.3 64.2 113.0 113.0 118.4 95.8 124.7 64.4 106.3 106.3 112.2 94.9 121.5 64.3 98.8 98.8 103.5 91.1 116.1 62.8
85 122.4 122.4 124.3 113.8 128.0 79.6 119.6 119.6 119.6 119.6 126.4 81.8 115.1 115.1 115.5 111.7 122.7 83.0 109.1 109.1 108.8 107.4 117.2 83.2
90 126.0 126.0 127.1 125.0 129.6 95.2 124.3 124.3 124.2 124.2 128.0 99.4 120.9 120.9 120.9 120.9 123.9 101.2 116.1 116.1 116.1 116.1 118.8 103.3
75 113.4 113.4 121.8 76.2 125.0 48.4 107.6 104.0 118.5 77.0 123.5 46.9 99.6 98.2 112.7 75.4 120.5 44.8 91.6 91.6 103.7 71.6 115.9 41.9
4800 80 119.5 119.5 123.2 97.0 126.7 64.8 115.8 115.8 119.8 99.6 125.2 65.3 109.8 109.8 113.9 99.4 122.1 65.5 102.3 102.3 105.5 96.3 117.2 66.8
85 124.3 124.3 125.2 116.6 128.4 80.7 121.5 121.5 121.5 121.5 126.9 83.3 117.5 117.5 117.6 115.4 123.7 85.6 111.8 111.8 111.8 111.8 118.5 86.4
90 127.5 127.5 128.0 126.7 130.1 96.9 126.0 126.0 125.5 125.5 128.6 101.5 122.6 122.6 123.0 123.0 125.5 105.5 118.2 118.2 118.2 118.2 120.3 107.5
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
RT-PRC006-EN 35
Performance (3 - 5 Tons)
Data Standard Efficiency
Table PD-18 — Direct Drive Evaporator Fan Performance 3, 4 , and 5 Ton YSC036A, YSC048A, YSC060A — Low and
Medium Heat
External Static Pressure (Inches of Water) & Motor Power (Bhp)1
Standard Motor Oversized Motor2
High Speed Low Speed High Speed Low Speed
Unit
Tons Model No. CFM ESP BHP ESP BHP ESP BHP ESP BHP
960 0.81 0.36 0.61 0.28 0.96 0.39 0.89 0.35
1020 0.77 0.37 0.57 0.28 0.94 0.41 0.86 0.47
1080 0.73 0.38 0.50 0.29 0.91 0.43 0.82 0.39
1140 0.69 0.39 0.42 0.29 0.88 0.44 0.77 0.40
3 YSC036A**L,M 1200 0.66 0.40 0.34 0.30 0.84 0.45 0.74 0.41
Horizontal Airflow 1260 0.60 0.41 0.26 0.30 0.80 0.46 0.70 0.42
1320 0.55 0.42 0.14 0.31 0.75 0.48 0.65 0.44
1380 0.49 0.42 0.05 0.31 0.70 0.49 0.59 0.45
1440 0.44 0.43 — — 0.64 0.52 0.54 0.48
1280 0.88 0.53 0.76 0.47 1.15 0.67 0.94 0.56
1360 0.82 0.54 0.70 0.47 1.10 0.68 0.89 0.58
1440 0.75 0.54 0.63 0.48 1.05 0.70 0.83 0.60
1520 0.68 0.55 0.55 0.48 1.00 0.73 0.76 0.63
YSC048A**L,M 1600 0.61 0.55 0.46 0.49 0.95 0.75 0.69 0.64
4
Horizontal Airflow 1680 0.52 0.56 0.33 0.49 0.90 0.78 0.60 0.66
1760 0.42 0.56 0.18 0.50 0.85 0.82 0.45 0.68
1840 0.32 0.57 0.08 0.50 0.78 0.83 0.30 0.70
1920 0.22 0.57 — — 0.70 0.85 0.20 0.73
1600 0.85 0.78 0.77 0.64 1.15 0.90 1.00 0.85
1700 0.80 0.82 0.63 0.65 1.10 0.94 0.90 0.89
1800 0.75 0.85 0.51 0.65 1.00 0.98 0.80 0.91
1900 0.65 0.88 0.41 0.65 0.93 1.02 0.70 0.94
YSC060A**L,M3 2000 0.55 0.90 0.25 0.66 0.85 1.05 0.60 0.95
5
Horizontal Airflow 2100 0.45 0.93 0.09 0.66 0.75 1.10 0.45 0.96
2200 0.35 0.95 0.00 0.67 0.65 1.12 0.30 0.96
2300 0.25 0.97 — — 0.55 1.17 0.10 0.97
2400 0.15 1.00 — — 0.43 1.20 — —
960 0.81 0.36 0.61 0.28 0.96 0.39 0.89 0.35
1020 0.77 0.37 0.57 0.28 0.94 0.41 0.86 0.47
1080 0.73 0.38 0.50 0.29 0.91 0.43 0.82 0.39
1140 0.69 0.39 0.42 0.29 0.88 0.44 0.77 0.40
3 YSC036A**L,M 1200 0.66 0.40 0.34 0.30 0.84 0.45 0.74 0.41
Downflow Airflow 1260 0.60 0.41 0.26 0.30 0.80 0.46 0.70 0.42
1320 0.55 0.42 0.14 0.31 0.75 0.48 0.65 0.44
1380 0.49 0.42 0.05 0.31 0.70 0.49 0.59 0.45
1440 0.44 0.43 — — 0.64 0.52 0.54 0.48
1280 0.93 0.53 0.81 0.47 1.20 0.67 0.99 0.56
1360 0.87 0.54 0.75 0.47 1.15 0.68 0.94 0.58
1440 0.80 0.54 0.68 0.48 1.10 0.70 0.88 0.60
1520 0.73 0.55 0.60 0.48 1.05 0.73 0.81 0.63
YSC048A**L,M 1600 0.66 0.55 0.51 0.49 1.00 0.75 0.74 0.64
4
Downflow Airflow 1680 0.57 0.56 0.38 0.49 0.95 0.78 0.65 0.66
1760 0.47 0.56 0.23 0.50 0.90 0.82 0.50 0.68
1840 0.37 0.57 0.13 0.50 0.83 0.83 0.35 0.70
1920 0.27 0.57 — — 0.75 0.85 — —
1600 0.90 0.78 0.82 0.64 1.20 0.90 1.05 0.85
1700 0.85 0.82 0.68 0.65 1.15 0.94 0.95 0.89
1800 0.80 0.85 0.56 0.65 1.05 0.98 0.85 0.91
1900 0.70 0.88 0.46 0.65 0.98 1.02 0.75 0.94
YSC060A**L,M3 2000 0.60 0.90 0.30 0.66 0.90 1.05 0.65 0.95
5
Downflow Airflow 2100 0.50 0.93 0.14 0.66 0.80 1.10 0.50 0.96
2200 0.40 0.95 0.05 0.67 0.70 1.12 0.35 0.96
2300 0.30 0.97 — — 0.60 1.17 0.15 0.97
2400 0.20 1.00 — — 0.48 1.20 — —
Fan motor heat (MBH) = 3.72 x Fan Bhp + .24.
Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product’s warranty will not be affected.
NOTES:
1. Data includes pressure drop due to wet coil and filters.
2. 5 ton oversized motor performance is with 12x11 FC Centrifugal blower wheel.
3. YSC060AK* uses a 1.0 hp direct drive motor and 12x11 FC Centrifugal blower wheel. Refer to oversized motor column for the standard motor performance
data.
36 RT-PRC006-EN
Performance (3 - 5 Tons)
Data Standard Efficiency
Table PD-19 — Direct Drive Evaporator Fan Performance 3, 4 and 5 Ton YSC036A, YSC048A, YSC060A — High Heat
External Static Pressure (Inches of Water) & Motor Power (Bhp)1
Standard Motor Oversized Motor2
High Speed Low Speed High Speed Low Speed
Unit
Tons Model No. CFM ESP BHP ESP BHP ESP BHP ESP BHP
960 0.76 0.36 0.56 0.28 0.91 0.39 0.84 0.35
1020 0.72 0.37 0.52 0.28 0.89 0.41 0.81 0.47
1080 0.68 0.38 0.45 0.29 0.86 0.43 0.77 0.39
1140 0.64 0.39 0.37 0.29 0.83 0.44 0.72 0.40
YSC036A**H 1200 0.61 0.40 0.29 0.30 0.79 0.45 0.69 0.41
3
Horizontal Airflow 1260 0.55 0.41 0.21 0.30 0.75 0.46 0.65 0.42
1320 0.50 0.42 0.09 0.31 0.70 0.48 0.60 0.44
1380 0.44 0.42 0.00 0.31 0.65 0.49 0.54 0.45
1440 0.39 0.43 — — 0.59 0.52 0.49 0.48
1280 0.88 0.53 0.76 0.47 1.15 0.67 0.94 0.56
1360 0.82 0.54 0.70 0.47 1.10 0.68 0.89 0.58
1440 0.75 0.54 0.63 0.48 1.05 0.70 0.83 0.60
1520 0.68 0.55 0.55 0.48 1.00 0.73 0.76 0.63
4 YSC048A**H 1600 0.61 0.55 0.46 0.49 0.95 0.75 0.69 0.64
Horizontal Airflow 1680 0.52 0.56 0.33 0.49 0.90 0.78 0.60 0.66
1760 0.42 0.56 0.18 0.50 0.85 0.82 0.45 0.68
1840 0.32 0.57 0.08 0.50 0.78 0.83 0.30 0.70
1920 0.22 0.57 — — 0.70 0.85 0.20 0.73
1600 0.85 0.78 0.77 0.64 1.15 0.90 1.00 0.85
1700 0.80 0.82 0.63 0.65 1.10 0.94 0.90 0.89
1800 0.75 0.85 0.51 0.65 1.00 0.98 0.80 0.91
1900 0.65 0.88 0.41 0.65 0.93 1.02 0.70 0.94
YSC060A**H3 2000 0.55 0.90 0.25 0.66 0.85 1.05 0.60 0.95
5
Horizontal Airflow 2100 0.45 0.93 0.09 0.66 0.75 1.10 0.45 0.96
2200 0.35 0.95 0.00 0.67 0.65 1.12 0.30 0.96
2300 0.25 0.97 — — 0.55 1.17 0.10 0.97
2400 0.15 1.00 — — 0.43 1.20 — —
960 0.76 0.36 0.56 0.28 0.91 0.39 0.84 0.35
1020 0.72 0.37 0.52 0.28 0.89 0.41 0.81 0.47
1080 0.68 0.38 0.45 0.29 0.86 0.43 0.77 0.39
1140 0.64 0.39 0.37 0.29 0.83 0.44 0.72 0.40
YSC036A**H 1200 0.61 0.40 0.29 0.30 0.79 0.45 0.69 0.41
3
Downflow Airflow 1260 0.55 0.41 0.21 0.30 0.75 0.46 0.65 0.42
1320 0.50 0.42 0.09 0.31 0.70 0.48 0.60 0.44
1380 0.44 0.42 0.00 0.31 0.65 0.49 0.54 0.45
1440 0.39 0.43 — — 0.59 0.52 0.49 0.48
1280 0.93 0.53 0.81 0.47 1.20 0.67 0.99 0.56
1360 0.87 0.54 0.75 0.47 1.15 0.68 0.94 0.58
1440 0.80 0.54 0.68 0.48 1.10 0.70 0.88 0.60
1520 0.73 0.55 0.60 0.48 1.05 0.73 0.81 0.63
4 YSC048A**H 1600 0.66 0.55 0.51 0.49 1.00 0.75 0.74 0.64
Downflow Airflow 1680 0.57 0.56 0.38 0.49 0.95 0.78 0.65 0.66
1760 0.47 0.56 0.23 0.50 0.90 0.82 0.50 0.68
1840 0.37 0.57 0.13 0.50 0.83 0.83 0.35 0.70
1920 0.27 0.57 — — 0.75 0.85 — —
1600 0.90 0.78 0.82 0.64 1.20 0.90 1.05 0.85
1700 0.85 0.82 0.68 0.65 1.15 0.94 0.95 0.89
1800 0.80 0.85 0.56 0.65 1.05 0.98 0.85 0.91
1900 0.70 0.88 0.46 0.65 0.98 1.02 0.75 0.94
YSC060A**H3 2000 0.60 0.90 0.30 0.66 0.90 1.05 0.65 0.95
5
Downflow Airflow 2100 0.50 0.93 0.14 0.66 0.80 1.10 0.50 0.96
2200 0.40 0.95 0.00 0.67 0.70 1.12 0.35 0.96
2300 0.30 0.97 — — 0.60 1.17 0.15 0.97
2400 0.20 1.00 — — 0.48 1.20 — —
Fan motor heat (MBH) = 3.72 x Fan Bhp + .24.
Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product’s warranty will not be affected.
NOTES:
1. Data includes pressure drop due to wet coil and filters.
2. 5 ton oversized motor performance is with 12x11 FC Centrifugal blower wheel.
3. YSC060AK* uses a 1.0 hp direct drive motor and 12x11 FC Centrifugal blower wheel. Refer to oversized motor column for the standard motor performance data.
RT-PRC006-EN 37
Performance (3 Ton)
Data Standard Efficiency
Table PD-20 — Belt Drive Evaporator Fan Performance — 3-Ton — YSC036A3,A4,AW*L, M — Low and Medium Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
960 — — 570 0.14 634 0.18 690 0.22 741 0.27 791 0.31 836 0.36 879 0.41 922 0.46 961 0.52
1080 537 0.14 606 0.18 669 0.23 724 0.27 773 0.32 819 0.36 864 0.41 906 0.47 946 0.52 985 0.58
1200 581 0.18 645 0.22 705 0.27 759 0.33 807 0.38 851 0.42 894 0.48 935 0.53 973 0.59 1011 0.65
1320 627 0.23 686 0.28 742 0.33 795 0.39 842 0.44 885 0.50 927 0.55 966 0.61 1003 0.67 1040 0.73
1440 673 0.29 728 0.34 780 0.39 831 0.45 878 0.52 921 0.58 960 0.64 998 0.69 1034 0.76 1070 0.82
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop due to other motor failure. Our product’s warranty will not be affected.
options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK69 required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.
Table PD-21 — Belt Drive Evaporator Fan Performance — 3-Ton — YSC036A3,A4,AW*L, M — Low and Medium Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
960 552 0.13 631 0.17 699 0.22 759 0.27 811 0.33 858 0.38 902 0.44 943 0.49 980 0.54 1017 0.60
1080 598 0.17 675 0.22 739 0.27 798 0.33 850 0.38 898 0.44 941 0.50 982 0.57 1020 0.63 1056 0.69
1200 645 0.22 720 0.28 781 0.33 837 0.39 889 0.45 937 0.51 981 0.58 1021 0.65 1059 0.72 1095 0.79
1320 693 0.28 766 0.34 825 0.40 879 0.47 929 0.53 976 0.60 1020 0.67 1061 0.74 1099 0.81 1135 0.89
1440 743 0.35 811 0.42 871 0.49 922 0.55 970 0.62 1016 0.69 1059 0.77 1099 0.84 1138 0.92 1174 1.00
1-HP Standard
Motor & Field Supplied
High Static Drive (2)
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories motor failure. Our product’s warranty will not be affected.
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK69 required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave AK41 required.Field Supplied Belt may be necessary.
Table PD-21 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
960 1052 0.65 1086 0.71 1120 0.77 1152 0.83 1185 0.90
1080 1090 0.75 1123 0.81 1154 0.87 1185 0.93 1215 0.99
1200 1130 0.86 1162 0.92 1193 0.99 1224 1.05 1253 1.12
1320 1169 0.96 1203 1.04 1233 1.12 1263 1.19 1292 1.26
1440 1208 1.08 1241 1.16 1273 1.25 1303 1.33 1332 1.41
1-HP Standard Motor &
Field Supplied High Static Drive (2)
38 RT-PRC006-EN
Performance (3 Ton)
Data Standard Efficiency
Table PD-22— Belt Drive Evaporator Fan Performance — 3-Ton — YSC036A3,A4,AW*H — High Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
960 503 0.11 578 0.15 641 0.19 696 0.23 747 0.27 796 0.32 841 0.36 884 0.42 926 0.47 966 0.52
1080 548 0.15 616 0.19 678 0.23 731 0.28 780 0.32 826 0.37 870 0.42 912 0.47 952 0.53 991 0.59
1200 593 0.19 657 0.23 716 0.28 768 0.33 815 0.38 859 0.43 901 0.49 942 0.54 980 0.60 1017 0.66
1320 640 0.24 698 0.29 754 0.34 806 0.40 852 0.45 895 0.51 935 0.56 974 0.62 1012 0.68 1048 0.74
1440 688 0.31 742 0.35 794 0.41 844 0.47 890 0.53 931 0.59 970 0.65 1009 0.71 1045 0.77 1080 0.84
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories motor failure. Our product’s warranty will not be affected.
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK69 required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.
Table PD-23 — Belt Drive Evaporator Fan Performance — 3-Ton — YSC036A3,A4,AW*H — High Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
960 563 0.13 639 0.18 707 0.23 766 0.28 817 0.33 864 0.39 908 0.44 947 0.49 985 0.55 1020 0.60
1080 611 0.18 685 0.23 748 0.28 806 0.34 858 0.39 905 0.45 947 0.51 988 0.58 1026 0.64 1061 0.70
1200 660 0.23 732 0.29 792 0.34 847 0.40 899 0.46 945 0.53 989 0.59 1029 0.66 1066 0.73 1102 0.80
1320 711 0.29 781 0.36 838 0.42 890 0.48 940 0.55 986 0.61 1029 0.68 1070 0.76 1106 0.83 1142 0.90
1440 762 0.37 829 0.44 885 0.51 935 0.57 983 0.64 1028 0.71 1070 0.79 1111 0.86 1148 0.94 1183 1.02
1-HP Standard
Motor & Field Supplied
High Static Drive (2)
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories motor failure. Our product’s warranty will not be affected.
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK69 required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.
Table PD-23 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard 1-HP Standard Motor & Field
Motor & Drive Supplied High Static Drive (2)
960 1056 0.66 1090 0.71 1123 0.78 1156 0.84 1188 0.90
1080 1096 0.76 1128 0.82 1159 0.88 1190 0.94 1220 1.00
1200 1135 0.87 1168 0.93 1199 1.00 1229 1.07 1259 1.13
1320 1177 0.98 1209 1.06 1241 1.14 1270 1.21 1299 1.28
1440 1217 1.10 1250 1.18 1281 1.27 1311 1.35 1339 1.43
RT-PRC006-EN 39
Performance (4 Ton)
Data Standard Efficiency
Table PD-24 — Belt Drive Evaporator Fan Performance — 4-Ton — YSC048A3,A4,AW*L,M — Low and Medium Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1280 604 0.21 666 0.25 724 0.30 778 0.36 826 0.41 870 0.47 911 0.52 952 0.58 990 0.63 1026 0.69
1440 665 0.29 720 0.34 773 0.38 824 0.44 872 0.51 916 0.57 956 0.63 994 0.69 1030 0.75 1065 0.81
1600 726 0.38 777 0.44 826 0.49 873 0.54 919 0.61 961 0.68 1002 0.75 1039 0.82 1074 0.89 1109 0.95
1760 789 0.50 836 0.56 881 0.61 924 0.67 967 0.73 1008 0.81 1048 0.89 1085 0.97 1120 1.04 1154 1.12
1920 851 0.63 896 0.70 938 0.76 978 0.82 1018 0.88 1057 0.96 1095 1.04 1131 1.13 1167 1.21 1199 1.30
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standardfilters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories motor failure. Our product’s warranty will not be affected.
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.
Table PD-25 — Belt Drive Evaporator Fan Performance — 4-Ton — YSC048A3,A4,AW*L,, M — Low and Medium Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1280 669 0.25 744 0.31 805 0.37 860 0.44 911 0.50 959 0.56 1003 0.63 1045 0.70 1082 0.77 1119 0.85
1440 733 0.34 803 0.41 864 0.48 916 0.55 965 0.62 1011 0.69 1055 0.76 1096 0.83 1134 0.91 1171 0.99
1600 800 0.45 864 0.53 923 0.60 974 0.68 1021 0.75 1064 0.83 1106 0.91 1147 0.99 1185 1.07 1221 1.15
1760 868 0.58 926 0.67 982 0.75 1033 0.83 1079 0.92 1121 1.00 1161 1.08 1199 1.17 1237 1.26 1273 1.35
1920 937 0.74 989 0.83 1042 0.92 1092 1.01 1138 1.10 1179 1.19 1217 1.28 1254 1.38 1290 1.47 — —
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
NOTES:
Data includes pressure drop due to standard filters and wet coils. 1-HP Standard Motor & Field
No accessories or options are included in pressure drop data. Supplied High Static Drive (2)
Refer to Table PD-89 to determine additional static pressure drop
due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024. Table PD-25 — Continued
1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt
may be necessary. External Static Pressure (Inches of Water)
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt 1.10 1.20 1.30 1.40 1.50
may be necessary. CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Trane’s factory supplied motors, in commercial equipment, are definite purpose 1-HP Standard
motors, specifically designed and tested to operate reliably and continuously at Motor & Drive
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature 1280 1154 0.92 1187 1.00 1218 1.07 1248 1.14 1277 1.21
motor failure. Our product’s warranty will not be affected. 1440 1205 1.07 1237 1.15 1270 1.24 1300 1.32 1330 1.40
1600 1256 1.23 1290 1.33 1322 1.42 — — — —
1760 1307 1.43 — — — — — — — —
1920 — — — — — — — — — —
40 RT-PRC006-EN
Performance (4 Ton)
Data Standard Efficiency
Table PD-26 — Belt Drive Evaporator Fan Performance — 4-Ton — YSC048A3,A4,AW*H — High Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1280 618 0.22 678 0.26 735 0.31 788 0.37 835 0.42 879 0.48 920 0.53 960 0.59 997 0.65 1034 0.71
1440 680 0.30 735 0.35 787 0.40 838 0.46 884 0.52 926 0.59 966 0.64 1004 0.70 1040 0.77 1075 0.83
1600 744 0.40 794 0.45 842 0.50 888 0.56 933 0.64 975 0.71 1015 0.78 1051 0.84 1086 0.91 1120 0.97
1760 808 0.52 854 0.58 899 0.64 941 0.69 984 0.76 1024 0.84 1063 0.92 1099 1.00 1134 1.07 1167 1.14
1920 873 0.66 916 0.73 957 0.79 997 0.85 1037 0.92 1075 0.99 1112 1.08 1148 1.17 1183 1.25 1214 1.33
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories motor failure. Our product’s warranty will not be affected.
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.
Table PD-27 — Belt Drive Evaporator Fan Performance — 4-Ton — YSC048A3,A4,AW*H — High Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1280 686 0.27 758 0.33 817 0.39 871 0.45 922 0.51 968 0.58 1013 0.64 1053 0.72 1091 0.79 1127 0.86
1440 753 0.36 821 0.43 878 0.50 930 0.57 977 0.63 1022 0.70 1066 0.78 1107 0.85 1145 0.93 1180 1.01
1600 821 0.48 884 0.55 941 0.63 990 0.70 1035 0.78 1078 0.86 1120 0.93 1160 1.02 1197 1.10 1234 1.18
1760 891 0.62 949 0.70 1004 0.78 1052 0.87 1096 0.95 1137 1.03 1176 1.12 1214 1.20 1251 1.29 1287 1.38
1920 962 0.78 1015 0.87 1067 0.97 1115 1.06 1158 1.15 1198 1.24 1235 1.33 1271 1.42 — — — —
1-HP Standard
Motor & Field Supplied
High Static Drive (2)
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024. Table PD-27 — Continued
1. Field Supplied Fan Sheave AK61 required. Field Supplied
Belt may be necessary. External Static Pressure (Inches of Water)
2. Field Supplied Fan Sheave AK41 required. Field Supplied 1.10 1.20 1.30 1.40 1.50
Belt may be necessary. CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard
Motor & Drive
1280 1160 0.94 1194 1.01 1224 1.08 1254 1.15 1283 1.22
1440 1214 1.09 1247 1.18 1278 1.26 1308 1.34 1338 1.43
1600 1268 1.26 1300 1.35 1331 1.44 — — — —
1760 1321 1.47 — — — — — — — —
1920 — — — — — — — — — —
1-HP Standard Motor & Field
Supplied High Static Drive (2)
RT-PRC006-EN 41
Performance (5 Ton)
Data Standard Efficiency
Table PD-28 — Belt Drive Evaporator Fan Performance — 5-Ton — YSC060A3,A4,AW *L,M — Low and Medium Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1600 747 0.40 797 0.46 846 0.51 893 0.57 938 0.64 981 0.72 1020 0.79 1056 0.85 1091 0.92 1125 0.99
1800 828 0.56 873 0.62 917 0.68 960 0.74 1002 0.81 1042 0.89 1081 0.97 1118 1.05 1152 1.13 1185 1.20
2000 909 0.75 951 0.82 992 0.89 1031 0.95 1069 1.01 1107 1.09 1144 1.18 1179 1.27 1213 1.37 1246 1.45
2200 992 0.98 1031 1.06 1068 1.13 1104 1.20 1139 1.27 1175 1.35 1209 1.43 — — — — — —
2400 1075 1.26 1111 1.34 1145 1.42 1179 1.50 — — — — — — — — — — — —
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied
Belt may be necessary.
Table PD-29 — Belt Drive Evaporator Fan Performance — 5-Ton — YSC060A3,A4,AW*L,M — Low and Medium Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor
& Field Supplied
Low Static Drive (1) 1-HP Standard Motor & Drive
1600 825 0.48 889 0.56 946 0.64 996 0.71 1041 0.79 1084 0.87 1126 0.95 1166 1.03 1204 1.11 1240 1.20
1800 913 0.66 971 0.75 1025 0.84 1074 0.92 1117 1.01 1158 1.09 1197 1.18 1235 1.27 1272 1.36 1307 1.45
2000 1003 0.89 1054 0.98 1105 1.08 1153 1.18 1196 1.27 1235 1.37 1272 1.46 1308 1.50 — — — —
2200 1094 1.16 1140 1.26 1187 1.37 1232 1.48 — — — — — — — — — — — —
2400 1185 1.48 — — — — — — — — — — — — — — — — — —
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt may be necessary.
42 RT-PRC006-EN
Performance (5 Ton)
Data Standard Efficiency
Table PD-30 — Belt Drive Evaporator Fan Performance — 5-Ton — YSC060A3,A4,AW *H — High Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1600 764 0.42 814 0.47 862 0.53 909 0.60 953 0.67 994 0.74 1032 0.81 1069 0.88 1103 0.94 1136 1.01
1800 848 0.58 892 0.65 936 0.70 978 0.77 1020 0.84 1059 0.92 1098 1.01 1132 1.09 1166 1.16 1198 1.24
2000 932 0.79 973 0.86 1013 0.92 1051 0.98 1090 1.06 1127 1.14 1163 1.23 1197 1.32 1231 1.42 1262 1.50
2200 1017 1.03 1055 1.11 1091 1.18 1127 1.25 1162 1.32 1196 1.40 1231 1.49 — — — — — —
2400 1103 1.32 1138 1.41 1171 1.49 — — — — — — — — — — — — — —
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature motor
Refer to Table PD-89 to determine additional static pressure drop failure. Our product’s warranty will not be affected.
due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied
Belt may be necessary.
Table PD-31 — Belt Drive Evaporator Fan Performance — 5-Ton — YSC060A3,A4,AW *H— High Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor
& Field Supplied
Low Static Drive (1) 1-HP Standard Motor & Drive
1600 847 0.51 910 0.59 964 0.66 1011 0.74 1056 0.82 1098 0.89 1140 0.97 1179 1.06 1217 1.14 1252 1.23
1800 938 0.70 995 0.79 1047 0.87 1093 0.96 1135 1.05 1175 1.13 1213 1.22 1251 1.31 1287 1.40 1323 1.49
2000 1030 0.94 1082 1.03 1131 1.13 1176 1.23 1217 1.32 1255 1.42 1292 1.50 — — — — — —
2200 1123 1.23 1170 1.33 1216 1.44 — — — — — — — — — — — — — —
2400 — — — — — — — — — — — — — — — — — — — —
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt may be necessary.
RT-PRC006-EN 43
Performance (6 Ton)
Data Standard Efficiency
Table PD-32 — Belt Drive Evaporator Fan Performance — 6-Ton — YSC072A3,A4,AW *L,M — Low and Medium Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1920 — — — — 583 0.35 638 0.42 687 0.49 732 0.56 777 0.64 817 0.71 857 0.80 895 0.88
2160 — — 559 0.36 613 0.43 666 0.51 715 0.59 759 0.67 800 0.75 841 0.83 879 0.92 915 1.01
2400 — — 597 0.46 647 0.54 695 0.62 743 0.71 788 0.80 828 0.88 866 0.97 902 1.06 938 1.15
2640 585 0.49 636 0.59 684 0.66 728 0.75 772 0.84 815 0.94 856 1.03 894 1.13 930 1.23 963 1.32
2880 629 0.63 677 0.73 722 0.81 763 0.89 803 0.99 844 1.09 884 1.20 923 1.31 958 1.41 990 1.51
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.
Table PD-33 — Belt Drive Evaporator Fan Performance — 6-Ton — YSC072A3,A4,AW *H— High Heat — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor
& Field Supplied
Low Static Drive (1) 1-HP Standard Motor & Drive
1920 — — 559 0.32 618 0.39 668 0.46 715 0.53 759 0.61 802 0.69 842 0.77 881 0.85 917 0.93
2160 — — 600 0.42 654 0.49 705 0.57 749 0.65 791 0.73 831 0.81 870 0.90 907 0.99 943 1.08
2400 594 0.46 644 0.53 692 0.61 741 0.70 786 0.79 826 0.88 864 0.97 900 1.05 936 1.15 971 1.24
2640 643 0.60 691 0.67 734 0.76 778 0.85 822 0.95 862 1.05 899 1.14 935 1.24 967 1.33 1001 1.43
2880 693 0.76 737 0.84 778 0.93 818 1.03 858 1.13 898 1.24 935 1.35 970 1.45 1003 1.55 1034 1.66
2-HP Oversized
Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are
NOTES: definite purpose motors, specifically designed and tested to operate
Data includes pressure drop due to standard filters and wet coils. reliably and continuously at all cataloged conditions. Using the full
No accessories or options are included in pressure drop data. horsepower range of our fan motors as shown in our tabular data
Refer to Table PD-89 to determine additional static pressure drop will not result in nuisance tripping or premature motor failure. Our
due to other options/accessories product’s warranty will not be affected.
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.
Table PD-33 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & High Static Drive Kit
(or 2 HP oversized Motor& Drive)
1920 952 1.01 985 1.09 1019 1.17 1050 1.26 1080 1.34 1110 1.42 1139 1.51 1167 1.60 1192 1.68 1220 1.77
2160 977 1.17 1010 1.26 1043 1.36 1073 1.44 1103 1.53 1133 1.63 1161 1.72 1189 1.81 1216 1.91 1242 2.00
2400 1004 1.34 1037 1.44 1068 1.55 1099 1.65 1128 1.75 1156 1.85 1185 1.95 1212 2.05 1239 2.16 1265 2.26
2640 1033 1.54 1064 1.64 1095 1.75 1125 1.87 1153 1.97 1182 2.09 1210 2.20 — — — — — —
2880 1065 1.76 1096 1.88 1124 1.99 1153 2.10 1182 2.22 — – — — — — — — — —
2-HP Oversized Motor & Drive
44 RT-PRC006-EN
Performance (6 Ton)
Data Standard Efficiency
Table PD-34 — Belt Drive Evaporator Fan Performance — 6-Ton — YSC072AK *L — Low Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied 2-HP Standard Motor & Drive
Low Static Drive (1)
1920 - - - - 583 0.35 638 0.42 687 0.49 732 0.56 777 0.64 817 0.71 857 0.80 895 0.88
2160 - - 559 0.36 613 0.43 666 0.51 715 0.59 759 0.67 800 0.75 841 0.83 879 0.92 915 1.01
2400 - - 597 0.46 647 0.54 695 0.62 743 0.71 788 0.80 828 0.88 866 0.97 902 1.06 938 1.15
2640 585 0.49 636 0.59 684 0.66 728 0.75 772 0.84 815 0.94 856 1.03 894 1.13 930 1.23 963 1.32
2880 629 0.63 677 0.73 722 0.81 763 0.89 803 0.99 844 1.09 884 1.20 923 1.31 958 1.41 990 1.51
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are
NOTES: definite purpose motors, specifically designed and tested to operate
Data includes pressure drop due to standard filters and wet coils. reliably and continuously at all cataloged conditions. Using the full
No accessories or options are included in pressure drop data. horsepower range of our fan motors as shown in our tabular data
Refer to Table PD-89 to determine additional static pressure drop will not result in nuisance tripping or premature motor failure. Our
due to other options/accessories product’s warranty will not be affected.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.
Table PD-35 — Belt Drive Evaporator Fan Performance — 6-Ton — YSC072AK *H— High Heat — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Std. Motor & Field Supplied Low Static Drive 2 HP Standard Motor & Drive
1920 - - 559 0.32 618 0.39 668 0.46 715 0.53 759 0.61 802 0.69 842 0.77 881 0.85 917 0.93
2160 - - 600 0.42 654 0.49 705 0.57 749 0.65 791 0.73 831 0.81 870 0.90 907 0.99 943 1.08
2400 594 0.46 644 0.53 692 0.61 741 0.70 786 0.79 826 0.88 864 0.97 900 1.05 936 1.15 971 1.24
2640 643 0.60 691 0.67 734 0.76 778 0.85 822 0.95 862 1.05 899 1.14 935 1.24 967 1.33 1001 1.43
2880 693 0.76 737 0.84 778 0.93 818 1.03 858 1.13 898 1.24 935 1.35 970 1.45 1003 1.55 1034 1.66
2 HP Standard Motor
& High Static Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are
NOTES: definite purpose motors, specifically designed and tested to operate
Data includes pressure drop due to standard filters and wet coils. reliably and continuously at all cataloged conditions. Using the full
No accessories or options are included in pressure drop data. horsepower range of our fan motors as shown in our tabular data
Refer to Table PD-89 to determine additional static pressure drop will not result in nuisance tripping or premature motor failure. Our
due to other options/accessories product’s warranty will not be affected.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.
RT-PRC006-EN 45
Performance (6 Ton)
Data Standard Efficiency
Table PD-36 — Belt Drive Evaporator Fan Performance — 6-Ton — YSC072A3,A4,AW *L,M — Low and Medium Heat —Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1920 — — 576 0.32 636 0.40 687 0.46 733 0.54 778 0.62 821 0.70 864 0.78 906 0.86 946 0.95
2160 575 0.37 619 0.43 674 0.50 726 0.59 770 0.66 812 0.74 852 0.82 890 0.92 930 1.01 968 1.10
2400 629 0.49 669 0.55 713 0.62 763 0.71 809 0.81 849 0.89 887 0.97 923 1.06 959 1.16 994 1.27
2640 684 0.63 721 0.71 757 0.78 802 0.86 846 0.96 888 1.07 925 1.16 959 1.25 993 1.34 1027 1.45
2880 740 0.80 774 0.89 807 0.97 843 1.05 885 1.14 925 1.26 964 1.38 998 1.48 1030 1.57 1062 1.67
2-HP Oversized
Motor and Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at 1-HP Standard
1-HP Standard Motor
Motor &
& High
High Static
Static
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as Drive (or
(or 2-HP
2-HP Oversized
Oversized Motor)
Motor)
Drive
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
F1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000.
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.
Table PD-36 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard 1-HP Standard Motor & High Static Drive Kit
Motor & Drive (or 2 HP Oversized Motor & Drive)
1920 985 1.04 1020 1.13 1057 1.22 1090 1.31 1123 1.41 1155 1.50 1185 1.60 1213 1.69 1241 1.79 1268 1.88
2160 1005 1.19 1040 1.29 1075 1.38 1110 1.48 1143 1.59 1176 1.69 1206 1.80 1235 1.90 1264 2.00 — —
2400 1029 1.37 1063 1.47 1098 1.58 1130 1.68 1162 1.78 1194 1.89 1223 2.00 1254 2.11 — — — —
2540 1058 1.56 1090 1.68 1121 1.79 1152 1.90 1184 2.01 1214 2.13 1244 2.24 — — — — — —
2880 1093 1.78 1123 1.90 1152 2.02 1181 2.14 1211 2.27 — — — — — — — — — —
2-HP Oversized Motor & Drive
Table PD-37 — Belt Drive Evaporator Fan Performance — 6-Ton — YSC072A3,A4,AW *H — High Heat —Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1920 551 0.30 613 0.37 668 0.44 715 0.51 761 0.58 804 0.67 847 0.75 890 0.83 930 0.92 969 1.00
2160 608 0.41 661 0.48 714 0.56 760 0.64 802 0.72 842 0.80 882 0.90 920 0.99 958 1.08 996 1.17
2400 667 0.55 710 0.62 760 0.71 806 0.80 847 0.88 885 0.96 921 1.06 957 1.16 992 1.27 1027 1.37
2640 726 0.72 762 0.79 809 0.87 853 0.98 894 1.09 930 1.17 965 1.26 998 1.36 1031 1.47 1063 1.58
2880 786 0.91 818 0.99 857 1.08 900 1.18 939 1.30 976 1.41 1009 1.51 1042 1.61 1073 1.71 1103 1.82
2-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at 1-HP Standard Motor & High Static
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as Drive (or 2-HP Oversized Motor)
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.
Table PD-37 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & High Static Drive
Kit (or 2 HP Oversized Motor & Drive)
1920 1007 1.09 1044 1.19 1078 1.28 1111 1.37 1142 1.46 1172 1.56 1203 1.65 1230 1.75 1257 1.84 — —
2160 1032 1.26 1068 1.36 1102 1.46 1135 1.56 1167 1.66 1198 1.77 1229 1.88 1259 1.98 — — — —
2400 1061 1.47 1095 1.57 1128 1.67 1161 1.78 1191 1.88 1223 2.00 1254 2.11 1282 2.23 — — — —
2640 1095 1.70 1126 1.81 1157 1.92 1189 2.03 1219 2.15 1250 2.26 — — — — — — — —
2880 1133 1.94 1162 2.06 1191 2.19 1221 2.30 — — — — — — — — — — — —
2-HP Oversized Motor & Drive
46 RT-PRC006-EN
Performance (6 Ton)
Data Standard Efficiency
Table PD-38 — Belt Drive Evaporator Fan Performance — 6-Ton — YSC072AK *L — Low Heat —Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor & Low Static Drive 2 HP Standard Motor & Drive
1920 522 0.27 576 0.32 636 0.40 687 0.46 733 0.54 778 0.62 821 0.70 864 0.78 906 0.86 946 0.95
2160 575 0.37 619 0.43 674 0.50 726 0.59 770 0.66 812 0.74 852 0.82 890 0.92 930 1.01 968 1.10
2400 629 0.49 669 0.55 713 0.62 763 0.71 809 0.81 849 0.89 887 0.97 923 1.06 959 1.16 994 1.27
2640 684 0.63 721 0.71 757 0.78 802 0.86 846 0.96 888 1.07 925 1.16 959 1.25 993 1.34 1027 1.45
2880 740 0.80 774 0.89 807 0.97 843 1.05 885 1.14 925 1.26 964 1.38 998 1.48 1030 1.57 1062 1.67
2 HP Standard Motor
& High Static Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES:
motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils.
all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data.
shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop
motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000.
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.
Table PD-39 — Belt Drive Evaporator Fan Performance — 6-Ton — YSC072AK*H — High Heat —Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor & Field Supplied 2 HP Standard Motor & Drive
Low Static Drive (1)
1920 551 0.30 613 0.37 668 0.44 715 0.51 761 0.58 804 0.67 847 0.75 890 0.83 930 0.92 969 1.00
2160 608 0.41 661 0.48 714 0.56 760 0.64 802 0.72 842 0.80 882 0.90 920 0.99 958 1.08 996 1.17
2400 667 0.55 710 0.62 760 0.71 806 0.80 847 0.88 885 0.96 921 1.06 957 1.16 992 1.27 1027 1.37
2640 726 0.72 762 0.79 809 0.87 853 0.98 894 1.09 930 1.17 965 1.26 998 1.36 1031 1.47 1063 1.58
2880 786 0.91 818 0.99 857 1.08 900 1.18 939 1.30 976 1.41 1009 1.51 1042 1.61 1073 1.71 1103 1.82
2 HP Standard Motor & High Static Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.
RT-PRC006-EN 47
Performance (7½ Ton)
Data Standard Efficiency
Table PD-40 — Belt Drive Evaporator Fan Performance — 7½-Ton — YSC090,092A3,A4,AW, AK *L — Low Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied 2-HP Standard Motor & Drive
Low Static Drive (1)
2400 — — — — 676 0.59 726 0.67 773 0.77 815 0.85 854 0.94 891 1.03 928 1.12 963 1.22
2700 — — 682 0.68 727 0.76 770 0.85 814 0.95 856 1.06 895 1.16 931 1.25 965 1.35 998 1.45
3000 693 0.79 738 0.89 780 0.97 819 1.07 858 1.18 898 1.29 936 1.40 972 1.52 1006 1.63 1038 1.73
3300 753 1.03 795 1.14 834 1.23 871 1.33 906 1.45 942 1.56 978 1.69 1014 1.81 1048 1.94 1080 2.06
3600 814 1.31 853 1.44 890 1.55 925 1.65 958 1.76 991 1.88 1023 2.01 1057 2.14 1088 2.28 1121 2.41
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at 3-HP Oversized Motor
NOTES:
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. Field Supplied Motor Sheave 1VL40L x 7/8 and Fan Sheave AK71 required.
Table PD-41 — Belt Drive Evaporator Fan Performance — 7½-Ton — YSC090,092A3,A4,AW *M— Medium Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied 2-HP Standard Motor & Drive
Low Static Drive (1)
2400 — — 662 0.56 711 0.65 759 0.74 802 0.83 842 0.91 879 1.00 916 1.09 951 1.19 986 1.29
2700 676 0.67 721 0.75 764 0.84 809 0.94 851 1.04 891 1.14 927 1.24 961 1.34 994 1.44 1027 1.54
3000 741 0.89 783 0.98 822 1.08 861 1.19 901 1.30 939 1.41 975 1.52 1009 1.64 1041 1.74 1071 1.85
3300 807 1.17 846 1.26 882 1.37 917 1.48 953 1.60 989 1.72 1024 1.85 1058 1.97 1089 2.09 1119 2.21
3600 874 1.50 910 1.60 944 1.71 976 1.83 1008 1.95 1041 2.08 1074 2.22 1107 2.35 1138 2.49 1168 2.62
3-HP Oversized Motor
& Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at 2-HP Standard Motor & High Static
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as Drive (or 3-HP Oversized Motor)
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Motor Sheave 1VL40L x 7/8 and Fan Sheave AK71 required.
48 RT-PRC006-EN
Performance (7½ Ton)
Data Standard Efficiency
Table PD-42 — Belt Drive Evaporator Fan Performance — 7½-Ton — YSC090,092A3,A4,AW, AK *H — High Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied 2-HP Standard Motor & Drive
Low Static Drive (1)
2400 — — 697 0.62 745 0.71 790 0.80 830 0.89 869 0.98 906 1.07 941 1.16 976 1.26 1009 1.36
2700 717 0.74 760 0.83 804 0.93 847 1.03 887 1.13 922 1.23 958 1.33 991 1.43 1024 1.53 1055 1.64
3000 787 0.99 826 1.09 865 1.20 905 1.31 943 1.42 979 1.54 1012 1.64 1044 1.76 1075 1.87 1105 1.98
3300 858 1.30 894 1.41 929 1.52 965 1.64 1001 1.77 1036 1.89 1068 2.01 1099 2.13 1129 2.25 1157 2.37
3600 930 1.66 963 1.78 995 1.90 1028 2.03 1061 2.16 1093 2.30 1126 2.43 1157 2.57 1185 2.70 1212 2.83
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at 2-HP Standard Motor & High Static
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as Drive (or 3-HP Oversized Motor)
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Motor Sheave 1VL40L x 7/8 and Fan Sheave AK71 required.
Table PD-43 — Belt Drive Evaporator Fan Performance — 7½-Ton — YSC090,092A3,A4,AW, AK *L— Low Heat —Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied 2-HP Standard Motor & Drive
Low Static Drive (1)
2400 653 0.53 694 0.59 745 0.67 793 0.77 835 0.86 874 0.94 911 1.03 948 1.13 982 1.23 1017 1.34
2700 725 0.73 760 0.80 801 0.88 847 0.98 889 1.09 927 1.19 963 1.28 997 1.38 1030 1.48 1061 1.60
3000 798 0.98 830 1.06 862 1.15 902 1.24 943 1.35 981 1.48 1017 1.60 1050 1.70 1081 1.80 1111 1.90
3300 872 1.28 901 1.38 929 1.47 961 1.56 998 1.67 1036 1.80 1071 1.93 1104 2.07 1135 2.19 1164 2.30
3600 946 1.65 973 1.75 1000 1.85 1025 1.95 1057 2.06 1091 2.17 1125 2.31 1158 2.46 1189 2.61 1219 2.75
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as 2-HP Standard Motor & High Static
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Drive (or 3-HP Oversized Motor)
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Motor Sheave 1VL40L x 7/8 and Fan Sheave AK71 required.
RT-PRC006-EN 49
Performance (7½ Ton)
Data Standard Efficiency
Table PD-44 — Belt Drive Evaporator Fan Performance — 7½-Ton — YSC090,092A3,A4,AW *M — Medium Heat —Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied 2-HP Standard Motor & Drive
Low Static Drive (1)
2400 680 0.57 729 0.65 778 0.74 823 0.84 862 0.92 900 1.00 936 1.10 972 1.20 1006 1.31 1041 1.41
2700 756 0.79 795 0.87 841 0.97 884 1.08 923 1.18 959 1.27 992 1.36 1025 1.47 1057 1.58 1089 1.70
3000 833 1.07 865 1.16 906 1.25 946 1.36 985 1.49 1020 1.61 1052 1.71 1083 1.81 1114 1.91 1143 2.03
3300 910 1.41 938 1.50 972 1.60 1010 1.70 1047 1.84 1081 1.97 1114 2.11 1144 2.22 1173 2.33 1200 2.44
3600 988 1.81 1014 1.91 1042 2.01 1076 2.12 1110 2.25 1143 2.39 1175 2.54 1205 2.69 1234 2.82 1260 2.94
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at 2-HP Standard Motor & High
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as Static Drive (or 3-HP Oversized
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature Motor)
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Motor Sheave 1VL40L x 7/8 and Fan Sheave AK71 required.
Table PD-44 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor 2-HP Standard Motor & High Static Drive Kit
& Drive (or 3-HP Oversized Motor & Drive)
2400 1076 1.51 1110 1.62 1143 1.72 1176 1.83 1206 1.94 1238 2.05 1267 2.16 1297 2.28 1325 2.40 1353 2.52
2700 1120 1.82 1152 1.93 1183 2.05 1214 2.17 1243 2.28 1273 2.40 1302 2.52 1330 2.64 1357 2.76 1385 2.89
3000 1172 2.15 1201 2.29 1229 2.42 1257 2.55 1285 2.68 1312 2.80 1340 2.93 1367 3.06 1395 3.19 1421 3.33
3300 1227 2.56 1255 2.69 1281 2.83 1307 2.97 1333 3.11 1359 3.26 1384 3.40 — — — — — —
3600 1287 3.06 1312 3.18 1337 3.31 1361 3.45 — — — — — — — — — — — —
3-HP Oversized Motor & Drive
Table PD-45 — Belt Drive Evaporator Fan Performance — 7½-Ton — YSC090,092A3,A4,AW, AK *H— High Heat —Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied 2-HP Standard Motor & Drive
Low Static Drive (1)
2400 713 0.62 764 0.71 811 0.81 851 0.89 889 0.97 926 1.07 962 1.17 997 1.28 1031 1.38 1067 1.48
2700 790 0.86 837 0.96 880 1.07 919 1.17 955 1.26 989 1.36 1022 1.46 1054 1.57 1086 1.69 1117 1.80
3000 869 1.16 910 1.26 950 1.38 989 1.50 1023 1.62 1056 1.72 1086 1.82 1116 1.92 1146 2.04 1175 2.17
3300 949 1.53 985 1.63 1023 1.75 1058 1.88 1092 2.02 1124 2.15 1154 2.26 1182 2.37 1210 2.48 1237 2.60
3600 1029 1.97 1061 2.07 1096 2.19 1130 2.33 1162 2.48 1193 2.63 1222 2.77 1250 2.89 1276 3.01 1302 3.13
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at 2-HP Standard Motor & High Static
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as Drive (or 3-HP Oversized Motor)
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750..
1. Field Supplied Motor Sheave 1VL40L x 7/8 and Fan Sheave AK71 required.
50 RT-PRC006-EN
Performance (8½ Ton)
Data Standard Efficiency
Table PD-46 — Belt Drive Evaporator Fan Performance — 8½-Ton — YSC102A3,A4,AW, AK *L,M — Low and Medium Heat —DownflowAirflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied 2-HP Standard Motor & Drive
Low Static Drive (1)
2720 — — — — 608 0.59 649 0.70 689 0.82 728 0.94 764 1.06 798 1.19 829 1.33 859 1.46
3060 — — 615 0.65 654 0.75 692 0.87 728 0.99 764 1.13 799 1.26 833 1.39 864 1.53 894 1.68
3400 625 0.72 665 0.83 702 0.95 736 1.06 770 1.19 804 1.34 836 1.49 868 1.63 899 1.78 928 1.93
3740 681 0.93 716 1.05 752 1.18 784 1.31 815 1.44 846 1.58 876 1.74 906 1.90 935 2.06 963 2.22
4080 737 1.19 769 1.31 802 1.45 833 1.60 862 1.73 891 1.87 919 2.03 947 2.20 974 2.37 1001 2.55
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature motor
Refer to Table PD-89 to determine additional static pressure drop failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Table PD-47 — Belt Drive Evaporator Fan Performance — 8½-Ton — YSC102A3,A4,AW, AK *H— High Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied 2-HP Standard Motor & Drive
Low Static Drive (1)
2720 — — — — 619 0.62 661 0.74 700 0.85 738 0.97 773 1.09 807 1.23 838 1.36 868 1.51
3060 586 0.58 629 0.68 667 0.79 705 0.91 741 1.04 776 1.17 810 1.30 843 1.44 874 1.58 904 1.72
3400 642 0.76 681 0.88 717 1.00 751 1.12 785 1.25 817 1.40 849 1.55 881 1.69 911 1.84 940 1.99
3740 698 0.99 735 1.12 769 1.25 800 1.37 831 1.51 862 1.66 892 1.82 920 1.98 950 2.14 977 2.30
4080 756 1.26 789 1.40 821 1.54 851 1.68 879 1.82 908 1.97 936 2.13 964 2.30 991 2.48 1017 2.66
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
RT-PRC006-EN 51
Performance (8½ Ton)
Data Standard Efficiency
Table PD-48 — Belt Drive Evaporator Fan Performance — 8½-Ton — YSC102A3,A4,AW, AK *L,M — Low and Medium Heat —Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied 2-HP Standard Motor & Drive
Low Static Drive (1)
2720 607 0.59 655 0.69 697 0.80 744 0.93 791 1.07 834 1.21 871 1.34 904 1.46 933 1.58 962 1.70
3060 672 0.81 715 0.92 755 1.04 792 1.16 834 1.31 876 1.47 917 1.63 953 1.78 985 1.93 1013 2.06
3400 739 1.09 776 1.20 814 1.34 849 1.47 882 1.61 920 1.77 958 1.94 996 2.12 1030 2.29 1063 2.47
3740 807 1.43 839 1.54 875 1.69 907 1.83 938 1.98 969 2.13 1003 2.30 1037 2.49 1072 2.69 1106 2.88
4080 875 1.83 903 1.95 935 2.10 968 2.26 997 2.42 1025 2.58 1053 2.74 1084 2.93 1116 3.13 1148 3.34
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Table PD-49 — Belt Drive Evaporator Fan Performance — 8½-Ton — YSC102A3,A4,AW, AK *H— High Heat —Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied 2-HP Standard Motor & Drive
Low Static Drive (1)
2720 625 0.63 671 0.73 713 0.84 762 0.98 807 1.12 849 1.26 883 1.38 915 1.50 944 1.62 971 1.74
3060 692 0.86 734 0.98 772 1.10 811 1.23 854 1.38 896 1.54 934 1.70 969 1.85 997 1.99 1026 2.12
3400 760 1.15 799 1.28 834 1.41 868 1.55 903 1.70 942 1.87 980 2.04 1016 2.22 1049 2.39 1079 2.56
3740 828 1.50 863 1.64 898 1.79 929 1.94 960 2.08 993 2.25 1027 2.44 1062 2.63 1096 2.82 1127 3.02
4080 898 1.92 929 2.07 962 2.23 992 2.39 1020 2.55 1048 2.71 1078 2.89 1110 3.09 1142 3.30 — —
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
52 RT-PRC006-EN
Performance (10 Ton)
Data Standard Efficiency
Table PD-50 — Belt Drive Evaporator Fan Performance — 10-Ton — YSC120A3,A4,AW, AK *L,M — Low and Medium Heat — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Field Supplied
Low Static Drive (1)
3200 — — — — — — 727 1.00 763 1.14 798 1.28 832 1.42 863 1.56 895 1.71 924 1.86
3600 — — 717 1.03 751 1.15 784 1.28 816 1.42 848 1.57 879 1.73 910 1.89 940 2.05 968 2.20
4000 746 1.21 780 1.35 813 1.49 843 1.62 873 1.76 902 1.92 931 2.09 959 2.26 986 2.43 1014 2.61
4400 814 1.57 845 1.73 876 1.88 905 2.03 932 2.18 959 2.34 985 2.51 1012 2.69 1037 2.88 1063 3.07
4800 883 2.02 911 2.18 940 2.35 967 2.52 993 2.68 1018 2.84 1042 3.01 1067 3.20 1091 3.39 1115 3.59
3-HP Standard Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at 5-HP Oversized
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as Motor & Drive
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. Field Supplied Motor Sheave 1VM50 x 7/8”, Fan Sheave AK89 and Belt AX40 required.
Table PD-51— Belt Drive Evaporator Fan Performance — 10-Ton — YSC120A3,A4,AW, AK *H— High Heat — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Field Supplied
Low Static Drive (1)
3200 — — — — 723 0.99 759 1.12 793 1.26 827 1.40 860 1.55 891 1.69 921 1.84 949 2.00
3600 721 1.04 755 1.17 787 1.29 820 1.44 851 1.59 882 1.75 913 1.90 942 2.06 971 2.22 999 2.39
4000 793 1.40 824 1.54 854 1.67 883 1.82 913 1.98 941 2.15 969 2.32 997 2.50 1024 2.67 1050 2.85
4400 866 1.83 895 1.98 923 2.13 949 2.28 976 2.45 1003 2.63 1029 2.81 1054 3.00 1079 3.20 1104 3.39
4800 939 2.34 967 2.51 992 2.67 1017 2.84 1042 3.01 1066 3.19 1090 3.38 1114 3.58 1138 3.79 1161 4.00
3-HP Standard Motor & Drive 5-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. Field Supplied Motor Sheave 1VM50 x 7/8”, Fan Sheave AK89 and Belt AX40 required.
RT-PRC006-EN 53
Performance (10 Ton)
Data Standard Efficiency
Table PD-52 — Belt Drive Evaporator Fan Performance — 10-Ton — YSC120A3,A4,AW, AK *L,M — Low and Medium Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Field Supplied 3-HP Standard Motor & Drive
Low Static Drive (1)
3200 — — 761 1.10 798 1.22 834 1.35 875 1.51 916 1.68 955 1.85 991 2.01 1022 2.16 1050 2.31
3600 799 1.35 836 1.48 872 1.63 904 1.77 936 1.91 972 2.09 1009 2.28 1045 2.47 1079 2.66 1111 2.84
4000 881 1.81 913 1.96 947 2.12 977 2.28 1006 2.44 1035 2.60 1066 2.78 1100 2.99 1133 3.20 1165 3.41
4400 963 2.39 992 2.54 1023 2.71 1052 2.89 1079 3.06 1106 3.23 1132 3.41 1160 3.61 1189 3.82 1219 4.05
4800 1045 3.07 1072 3.23 1099 3.41 1127 3.61 1154 3.80 1179 3.98 1203 4.17 1227 4.36 1251 4.56 1278 4.80
5-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature motor
Refer to Table PD-89 to determine additional static pressure drop failure. Our product’s warranty will not be affected.
due to other options/accessories
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. Field Supplied Motor Sheave 1VM50 x 7/8”, Fan Sheave AK89 and Belt AX40 required.
Table PD-52 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Drive 5-HP Oversized Motor & Drive
3200 1077 2.45 1103 2.60 1126 2.73 1150 2.87 1171 3.01 1193 3.15 1214 3.29 1233 3.42 1253 3.56 1274 3.71
3600 1140 3.02 1165 3.18 1190 3.34 1214 3.51 1235 3.66 1257 3.82 1279 3.98 1298 4.13 1317 4.28 1338 4.45
4000 1196 3.62 1225 3.83 1252 4.03 1276 4.22 1299 4.40 1321 4.58 1342 4.76 1363 4.94 1383 5.11 1401 5.28
4400 1250 4.28 1280 4.52 1307 4.75 1334 4.98 1359 5.20 1384 5.43 1405 5.62 — — — — — —
4800 1305 5.03 1334 5.28 1361 5.54 — — — — — — — — — — — — — —
Table PD-53 — Belt Drive Evaporator Fan Performance — 10-Ton — YSC120A3,A4,AW, AK *H— High Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Field Supplied 3-HP Standard Motor & Drive
Low Static Drive (1)
3200 768 1.12 805 1.25 842 1.38 884 1.54 924 1.71 962 1.88 998 2.04 1028 2.19 1055 2.34 1082 2.48
3600 856 1.56 888 1.70 921 1.84 955 2.00 992 2.19 1028 2.37 1063 2.57 1096 2.75 1126 2.93 1153 3.10
4000 943 2.10 973 2.26 1002 2.41 1031 2.58 1062 2.76 1096 2.96 1129 3.17 1161 3.38 1192 3.59 1222 3.81
4400 1031 2.76 1060 2.94 1086 3.11 1113 3.28 1139 3.45 1167 3.66 1198 3.89 1228 4.11 1257 4.34 1287 4.58
4800 1119 3.45 1146 3.74 1171 3.93 1195 4.11 1219 4.30 1243 4.50 1270 4.72 1297 4.96 1325 5.21 1353 5.46
5-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
NOTES: Trane’s factory supplied motors, in commercial equipment, are definite purpose
Data includes pressure drop due to standard filters and wet coils. motors, specifically designed and tested to operate reliably and continuously at
No accessories or options are included in pressure drop data. all cataloged conditions. Using the full horsepower range of our fan motors as
Refer to Table PD-89 to determine additional static pressure drop shown in our tabular data will not result in nuisance tripping or premature
due to other options/accessories motor failure. Our product’s warranty will not be affected.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. Field Supplied Motor Sheave 1VM50 x 7/8”, Fan Sheave AK89 and Belt AX40 required.
54 RT-PRC006-EN
Performance (3 - 5 Tons)
Data High Efficiency
Table PD-54— Direct Drive Evaporator Fan Performance 3, 4 And 5 Ton YHC036A**L,M, YHC048A**L,M, YHC060A**L,M
— Low and Medium Heat
External Static Pressure (Inches of Water) & Motor Power (Bhp)1
Standard Motor Oversized Motor2
Unit High Speed Low Speed High Speed Low Speed
Tons Model No. CFM ESP BHP ESP BHP ESP BHP ESP BHP
960 0.74 0.36 0.56 0.28 0.89 0.38 0.82 0.35
1020 0.69 0.37 0.49 0.28 0.85 0.39 0.77 0.36
1080 0.65 0.38 0.44 0.29 0.82 0.41 0.74 0.38
1140 0.61 0.39 0.37 0.29 0.77 0.43 0.69 0.40
3 YHC036A**L,M 1200 0.55 0.40 0.29 0.30 0.74 0.44 0.65 0.41
Horizontal Airflow 1260 0.51 0.41 0.19 0.30 0.70 0.45 0.61 0.42
1320 0.46 0.42 0.10 0.31 0.67 0.47 0.57 0.44
1380 0.41 0.43 0.00 0.31 0.64 0.48 0.52 0.45
1440 0.34 0.44 — — 0.57 0.51 0.45 0.48
1280 0.85 0.53 0.74 0.47 1.11 0.67 0.90 0.56
1360 0.78 0.54 0.66 0.47 1.06 0.68 0.85 0.58
1440 0.71 0.54 0.60 0.48 1.01 0.70 0.80 0.60
1520 0.64 0.55 0.51 0.48 0.96 0.73 0.72 0.63
YHC048A**L,M 1600 0.55 0.55 0.39 0.49 0.89 0.75 0.63 0.64
4
Horizontal Airflow 1680 0.46 0.56 0.27 0.49 0.84 0.78 0.54 0.66
1760 0.37 0.56 0.12 0.50 0.79 0.82 0.37 0.68
1840 0.26 0.57 0.00 0.50 0.70 0.83 0.24 0.70
1920 0.16 0.57 — — 0.62 0.85 0.13 0.73
1600 0.99 0.78 0.89 0.64 1.32 0.90 1.18 0.85
1700 0.92 0.80 0.76 0.65 1.24 0.94 1.08 0.89
1800 0.87 0.85 0.65 0.65 1.16 0.98 0.97 0.91
1900 0.77 0.88 0.56 0.65 1.15 1.02 0.87 0.94
YHC060A**L,M 2000 0.69 0.90 0.40 0.66 0.98 1.05 0.76 0.95
5
Horizontal Airflow 2100 0.59 0.93 0.25 0.66 0.89 1.10 0.63 0.96
2200 0.46 0.94 0.10 0.67 0.78 1.12 0.42 0.96
2300 0.37 0.95 — — 0.68 1.17 0.18 0.97
2400 0.26 0.97 — — 0.55 1.20 — —
960 0.74 0.36 0.56 0.28 0.89 0.38 0.82 0.35
1020 0.69 0.37 0.49 0.28 0.85 0.39 0.77 0.36
1080 0.65 0.38 0.44 0.29 0.82 0.41 0.74 0.38
1140 0.61 0.39 0.37 0.29 0.77 0.43 0.69 0.40
3 YHC036A**L,M 1200 0.55 0.40 0.29 0.30 0.74 0.44 0.65 0.41
Downflow Airflow 1260 0.51 0.41 0.19 0.30 0.70 0.45 0.61 0.42
1320 0.46 0.42 0.10 0.31 0.67 0.47 0.57 0.44
1380 0.41 0.43 0.00 0.31 0.64 0.48 0.52 0.45
1440 0.34 0.44 — — 0.57 0.51 0.45 0.48
1280 0.90 0.53 0.79 0.47 1.16 0.67 0.95 0.56
1360 0.83 0.54 0.71 0.47 1.11 0.68 0.90 0.58
1440 0.76 0.54 0.65 0.48 1.06 0.70 0.85 0.60
1520 0.69 0.55 0.56 0.48 1.01 0.73 0.77 0.63
YHC048A**L,M 1600 0.60 0.55 0.44 0.49 0.94 0.75 0.68 0.64
4
Downflow Airflow 1680 0.51 0.56 0.32 0.49 0.89 0.78 0.59 0.66
1760 0.42 0.56 0.17 0.50 0.84 0.82 0.42 0.68
1840 0.31 0.57 0.05 0.50 0.75 0.83 0.29 0.70
1920 0.21 0.57 – — 0.67 0.85 — —
1600 1.04 0.78 0.94 0.64 1.37 0.90 1.23 0.85
1700 0.97 0.80 0.81 0.65 1.29 0.94 1.13 0.89
1800 0.92 0.85 0.70 0.65 1.21 0.98 1.02 0.91
1900 0.82 0.88 0.61 0.65 1.20 1.02 0.92 0.94
YHC060A**L,M 2000 0.74 0.90 0.45 0.66 1.03 1.05 0.81 0.95
5
Downflow Airflow 2100 0.64 0.93 0.30 0.66 0.94 1.10 0.68 0.96
2200 0.51 0.94 0.15 0.67 0.83 1.12 0.47 0.96
2300 0.42 0.95 — — 0.73 1.17 0.23 0.97
2400 0.31 0.97 — — 0.60 1.20 — —
Fan motor heat (MBH) = 3.72 x Fan Bhp + .24.
Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
NOTES:
1. Data includes pressure drop due to wet coil and filters.
RT-PRC006-EN 55
Performance (3 - 5 Tons)
Data High Efficiency
Table PD-55 — Direct Drive Evaporator Fan Performance 3, 4 And 5 Ton YHC036A**H, YHC048A**H, YHC060A**H
— High Heat
External Static Pressure (Inches of Water) & Motor Power (Bhp)1
Standard Motor Oversized Motor2
Unit High Speed Low Speed High Speed Low Speed
Tons Model No. CFM ESP BHP ESP BHP ESP BHP ESP BHP
960 0.74 0.36 0.56 0.28 0.89 0.38 0.82 0.35
1020 0.69 0.37 0.49 0.28 0.85 0.39 0.77 0.36
1080 0.65 0.38 0.44 0.29 0.82 0.41 0.74 0.38
1140 0.61 0.39 0.37 0.29 0.77 0.43 0.69 0.40
YHC036A**H 1200 0.55 0.40 0.29 0.30 0.74 0.44 0.65 0.41
3
Horizontal Airflow 1260 0.51 0.41 0.19 0.30 0.70 0.45 0.61 0.42
1320 0.46 0.42 0.10 0.31 0.67 0.47 0.57 0.44
1380 0.41 0.43 0.00 0.31 0.64 0.48 0.52 0.45
1440 0.34 0.44 — — 0.57 0.51 0.45 0.48
1280 0.85 0.53 0.74 0.47 1.11 0.67 0.90 0.56
1360 0.78 0.54 0.66 0.47 1.06 0.68 0.85 0.58
1440 0.71 0.54 0.60 0.48 1.01 0.70 0.80 0.60
1520 0.64 0.55 0.51 0.48 0.96 0.73 0.72 0.63
4 YHC048A**H 1600 0.55 0.55 0.39 0.49 0.89 0.75 0.63 0.64
Horizontal Airflow 1680 0.46 0.56 0.27 0.49 0.84 0.78 0.54 0.66
1760 0.37 0.56 0.12 0.50 0.79 0.82 0.37 0.68
1840 0.26 0.57 0.00 0.50 0.70 0.83 0.24 0.70
1920 0.16 0.57 — — 0.62 0.85 0.13 0.73
1600 0.94 0.78 0.84 0.64 1.27 0.90 1.13 0.85
1700 0.87 0.80 0.71 0.65 1.19 0.94 1.03 0.89
1800 0.82 0.85 0.60 0.65 1.11 0.98 0.92 0.91
1900 0.72 0.88 0.51 0.65 1.10 1.02 0.82 0.94
YHC060A**H 2000 0.64 0.90 0.35 0.66 0.93 1.05 0.71 0.95
5
Horizontal Airflow 2100 0.54 0.93 0.20 0.66 0.84 1.10 0.58 0.96
2200 0.41 0.94 0.05 0.67 0.73 1.12 0.37 0.96
2300 0.32 0.95 — — 0.63 1.17 0.13 0.97
2400 0.21 0.97 — — 0.50 1.20 — —
960 0.74 0.36 0.56 0.28 0.89 0.38 0.82 0.35
1020 0.69 0.37 0.49 0.28 0.85 0.39 0.77 0.36
1080 0.65 0.38 0.44 0.29 0.82 0.41 0.74 0.38
1140 0.61 0.39 0.37 0.29 0.77 0.43 0.69 0.40
YHC036A**H 1200 0.55 0.40 0.29 0.30 0.74 0.44 0.65 0.41
3
Downflow Airflow 1260 0.51 0.41 0.19 0.30 0.70 0.45 0.61 0.42
1320 0.46 0.42 0.10 0.31 0.67 0.47 0.57 0.44
1380 0.41 0.43 0.00 0.31 0.64 0.48 0.52 0.45
1440 0.34 0.44 — — 0.57 0.51 — —
1280 0.90 0.53 0.79 0.47 1.16 0.67 0.95 0.56
1360 0.83 0.54 0.71 0.47 1.11 0.68 0.90 0.58
1440 0.76 0.54 0.65 0.48 1.06 0.70 0.85 0.60
1520 0.69 0.55 0.56 0.48 1.01 0.73 0.77 0.63
4 YHC048A**H 1600 0.60 0.55 0.44 0.49 0.94 0.75 0.68 0.64
Downflow Airflow 1680 0.51 0.56 0.32 0.49 0.89 0.78 0.59 0.66
1760 0.42 0.56 0.17 0.50 0.84 0.82 0.42 0.68
1840 0.31 0.57 0.05 0.50 0.75 0.83 0.29 0.70
1920 0.21 0.57 — — 0.67 0.85 — —
1600 0.99 0.78 0.89 0.64 1.32 0.90 1.18 0.85
1700 0.92 0.80 0.76 0.65 1.24 0.94 1.08 0.89
1800 0.87 0.85 0.65 0.65 1.16 0.98 0.97 0.91
1900 0.77 0.88 0.56 0.65 1.15 1.02 0.87 0.94
YHC060A**H 2000 0.69 0.90 0.40 0.66 0.98 1.05 0.76 0.95
5
Downflow Airflow 2100 0.59 0.93 0.25 0.66 0.89 1.10 0.63 0.96
2200 0.46 0.94 0.10 0.67 0.78 1.12 0.42 0.96
2300 0.37 0.95 0.00 0.68 0.68 1.17 0.18 0.97
2400 0.26 0.97 — — 0.55 1.20 — —
Fan motor heat (MBH) = 3.72 x Fan Bhp + .24.
Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
NOTES:
1. Data includes pressure drop due to wet coil and filters.
2. 5 Ton oversized motor peformance is with 12 x 11 FC Centrifugal blower fan.
56 RT-PRC006-EN
Performance (3 Ton)
Data High Efficiency
Table PD-56 — Evaporator Fan Performance — 3 Ton — YHC036A3,A4,AW*L, M — Low and Medium Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
960 — — 570 0.14 634 0.18 690 0.22 741 0.27 791 0.31 836 0.36 879 0.41 922 0.46 961 0.52
1080 537 0.14 606 0.18 669 0.23 724 0.27 773 0.32 819 0.36 864 0.41 906 0.47 946 0.52 985 0.58
1200 581 0.18 645 0.22 705 0.27 759 0.33 807 0.38 851 0.42 894 0.48 935 0.53 973 0.59 1011 0.65
1320 627 0.23 686 0.28 742 0.33 795 0.39 842 0.44 885 0.50 927 0.55 966 0.61 1003 0.67 1040 0.73
1440 673 0.29 728 0.34 780 0.39 831 0.45 878 0.52 921 0.58 960 0.64 998 0.69 1034 0.76 1070 0.82
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK69 required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.
Table PD-57 — Evaporator Fan Performance — 3 Ton — YHC036A3,A4,AW*L, M — Low and Medium Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
960 552 0.13 631 0.17 699 0.22 759 0.27 811 0.33 858 0.38 902 0.44 943 0.49 980 0.54 1017 0.60
1080 598 0.17 675 0.22 739 0.27 798 0.33 850 0.38 898 0.44 941 0.50 982 0.57 1020 0.63 1056 0.69
1200 645 0.22 720 0.28 781 0.33 837 0.39 889 0.45 937 0.51 981 0.58 1021 0.65 1059 0.72 1095 0.79
1320 693 0.28 766 0.34 825 0.40 879 0.47 929 0.53 976 0.60 1020 0.67 1061 0.74 1099 0.81 1135 0.89
1440 743 0.35 811 0.42 871 0.49 922 0.55 970 0.62 1016 0.69 1059 0.77 1099 0.84 1138 0.92 1174 1.00
1-HP Standard
Motor & Field Supplied
High Static Drive (2)
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK69 required. Field Supplied Belt
may be necessary. Table PD-57 — Continued
2. Field Supplied Fan Sheave AK41 required.Field Supplied Belt
may be necessary. External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
960 1052 0.65 1086 0.71 1120 0.77 1152 0.83 1185 0.90
1080 1090 0.75 1123 0.81 1154 0.87 1185 0.93 1215 0.99
1200 1130 0.86 1162 0.92 1193 0.99 1224 1.05 1253 1.12
1320 1169 0.96 1203 1.04 1233 1.12 1263 1.19 1292 1.26
1440 1208 1.08 1241 1.16 1273 1.25 1303 1.33 1332 1.41
1-HP Standard Motor &
Field Supplied High Static Drive (2)
RT-PRC006-EN 57
Performance (3 Ton)
Data High Efficiency
Table PD-58— Belt Drive Evaporator Fan Performance — 3 Ton — YHC036A3,A4,AW*H — High Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
960 503 0.11 578 0.15 641 0.19 696 0.23 747 0.27 796 0.32 841 0.36 884 0.42 926 0.47 966 0.52
1080 548 0.15 616 0.19 678 0.23 731 0.28 780 0.32 826 0.37 870 0.42 912 0.47 952 0.53 991 0.59
1200 593 0.19 657 0.23 716 0.28 768 0.33 815 0.38 859 0.43 901 0.49 942 0.54 980 0.60 1017 0.66
1320 640 0.24 698 0.29 754 0.34 806 0.40 852 0.45 895 0.51 935 0.56 974 0.62 1012 0.68 1048 0.74
1440 688 0.31 742 0.35 794 0.41 844 0.47 890 0.53 931 0.59 970 0.65 1009 0.71 1045 0.77 1080 0.84
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite
NOTES: purpose motors, specifically designed and tested to operate reliably and
Data includes pressure drop due to standard filters and wet coils. continuously at all cataloged conditions. Using the full horsepower range of
No accessories or options are included in pressure drop data. our fan motors as shown in our tabular data will not result in nuisance
Refer to Table PD-89 to determine additional static pressure drop tripping or premature motor failure. Our product’s warranty will not be
due to other options/accessories affected.
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK69 required. Field Supplied Belt
may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt
may be necessary.
Table PD-58— Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
960 1005 0.58 1041 0.64 1076 0.70 1110 0.76 1142 0.82
1080 1029 0.65 1064 0.71 1099 0.77 1133 0.83 1166 0.90
1200 1053 0.72 1089 0.78 1123 0.85 1156 0.91 1189 0.98
1320 1082 0.80 1116 0.87 1150 0.93 1182 1.00 1214 1.07
1440 1113 0.90 1146 0.97 1178 1.04 1209 1.11 1240 1.18
1-HP Standard Motor &
Field Supplied High Static Drive (2)
Table PD-59 — Belt Drive Evaporator Fan Performance — 3 Ton — YHC036A3,A4,AW*H — High Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
960 563 0.13 639 0.18 707 0.23 766 0.28 817 0.33 864 0.39 908 0.44 947 0.49 985 0.55 1020 0.60
1080 611 0.18 685 0.23 748 0.28 806 0.34 858 0.39 905 0.45 947 0.51 988 0.58 1026 0.64 1061 0.70
1200 660 0.23 732 0.29 792 0.34 847 0.40 899 0.46 945 0.53 989 0.59 1029 0.66 1066 0.73 1102 0.80
1320 711 0.29 781 0.36 838 0.42 890 0.48 940 0.55 986 0.61 1029 0.68 1070 0.76 1106 0.83 1142 0.90
1440 762 0.37 829 0.44 885 0.51 935 0.57 983 0.64 1028 0.71 1070 0.79 1111 0.86 1148 0.94 1183 1.02
1-HP Standard
Motor & Field Supplied
High Static Drive (2)
For Standard Evaporator Fan Speed (RPM), reference Table PD-85. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-88 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK69 required. Field Supplied Belt
may be necessary. Table PD-59 — Continued
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt
may be necessary. External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard 1-HP Standard Motor & Field
Motor & Drive Supplied High Static Drive (2)
960 1056 0.66 1090 0.71 1123 0.78 1156 0.84 1188 0.90
1080 1096 0.76 1128 0.82 1159 0.88 1190 0.94 1220 1.00
1200 1135 0.87 1168 0.93 1199 1.00 1229 1.07 1259 1.13
1320 1177 0.98 1209 1.06 1241 1.14 1270 1.21 1299 1.28
1440 1217 1.10 1250 1.18 1281 1.27 1311 1.35 1339 1.43
58 RT-PRC006-EN
Performance (4 Ton)
Data High Efficiency
Table PD-60 — Belt Drive Evaporator Fan Performance — 4 Ton — YHC048A3,A4,AW*L,M — Low and Medium Heat — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1280 614 0.22 675 0.26 733 0.31 787 0.37 834 0.42 878 0.48 919 0.53 959 0.59 997 0.65 1034 0.71
1440 676 0.30 731 0.34 784 0.39 835 0.46 883 0.52 925 0.58 965 0.64 1003 0.70 1039 0.76 1075 0.83
1600 739 0.40 789 0.45 838 0.50 885 0.56 931 0.63 973 0.70 1012 0.77 1049 0.84 1085 0.91 1118 0.97
1760 803 0.51 850 0.57 894 0.63 938 0.69 981 0.76 1021 0.83 1061 0.92 1097 0.99 1131 1.07 1164 1.14
1920 867 0.65 911 0.72 952 0.78 993 0.84 1033 0.91 1071 0.99 1110 1.07 1145 1.16 1180 1.25 1213 1.33
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessoriesdue to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt
may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt
may be necessary. Table PD-60 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
1280 1069 0.77 1104 0.83 1138 0.90 1170 0.97 1203 1.04
1440 1109 0.89 1141 0.96 1175 1.03 1205 1.10 1236 1.17
1600 1151 1.04 1183 1.11 1215 1.19 1246 1.26 1275 1.33
1760 1197 1.21 1227 1.29 1258 1.36 1287 1.44 — —
1920 1243 1.41 1274 1.49 — — — — — —
Table PD-61— Belt Drive Evaporator Fan Performance — 4 Ton — YHC048A3,A4,AW*L,M — Low and Medium Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor &
Field Supplied Low Static Drive (1) 1-HP Standard Motor & Drive
1280 681 0.26 755 0.32 816 0.38 870 0.45 921 0.51 968 0.58 1013 0.65 1053 0.72 1091 0.79 1127 0.86
1440 748 0.36 817 0.43 876 0.49 927 0.56 976 0.63 1022 0.70 1065 0.78 1106 0.85 1144 0.93 1180 1.01
1600 816 0.47 879 0.55 937 0.62 987 0.70 1033 0.78 1076 0.85 1119 0.93 1158 1.01 1197 1.10 1233 1.18
1760 885 0.61 943 0.69 999 0.78 1049 0.86 1093 0.94 1135 1.03 1174 1.11 1213 1.20 1250 1.29 1286 1.38
1920 956 0.77 1009 0.86 1062 0.96 1110 1.05 1154 1.14 1195 1.23 1232 1.32 1269 1.41 1304 1.50 — —
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024. 1-HP Standard Motor & Field
1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt Supplied High Static Drive (2)
may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt
may be necessary. Table PD-61 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard
Motor & Drive
1280 1162 0.94 1193 1.01 1225 1.09 1255 1.16 1284 1.23
1440 1214 1.09 1247 1.18 1278 1.26 1309 1.35 1337 1.43
1600 1268 1.27 1300 1.35 1332 1.45 — — — —
1760 1320 1.47 — — — — — — — —
1920 — — — — — — — — — —
1-HP Standard Motor & Field Supplied High Static Drive (2)
RT-PRC006-EN 59
Performance (4 Ton)
Data High Efficiency
Table PD-62 — Belt Drive Evaporator Fan Performance — 4 Ton — YHC048A3,A4,AW*H — High Heat — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1280 627 0.23 688 0.27 745 0.32 797 0.38 844 0.43 887 0.49 928 0.54 967 0.60 1006 0.66 1042 0.72
1440 691 0.31 746 0.36 798 0.41 848 0.47 894 0.54 936 0.60 975 0.66 1012 0.72 1049 0.78 1085 0.85
1600 756 0.41 806 0.47 854 0.52 901 0.58 945 0.66 987 0.73 1025 0.79 1061 0.86 1096 0.93 1129 1.00
1760 822 0.54 868 0.60 912 0.65 955 0.71 997 0.79 1038 0.87 1076 0.95 1111 1.02 1145 1.10 1178 1.17
1920 889 0.69 931 0.75 972 0.81 1012 0.88 1051 0.95 1090 1.03 1127 1.11 1162 1.20 1196 1.29 1228 1.37
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt
may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt
may be necessary.
Table PD-62 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
1280 1077 0.78 1112 0.85 1145 0.91 1178 0.98 1210 1.05
1440 1118 0.91 1150 0.98 1183 1.05 1214 1.12 1244 1.19
1600 1162 1.06 1193 1.13 1225 1.21 1255 1.28 1285 1.36
1760 1208 1.24 1239 1.32 1268 1.39 1297 1.47 — —
1920 1258 1.45 — — — — — — — —
Table PD-63 — Belt Drive Evaporator Fan Performance — 4 Ton — YHC048A3,A4,AW*H — High Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor &
Field Supplied Low Static Drive (1) 1-HP Standard Motor & Drive
1280 698 0.28 769 0.34 828 0.40 881 0.46 932 0.52 978 0.59 1021 0.66 1061 0.73 1099 0.81 1134 0.88
1440 767 0.37 834 0.44 890 0.51 941 0.58 988 0.65 1034 0.72 1077 0.80 1116 0.87 1153 0.95 1190 1.03
1600 837 0.50 899 0.57 955 0.65 1003 0.72 1048 0.80 1091 0.88 1132 0.96 1171 1.04 1209 1.12 1245 1.21
1760 908 0.64 966 0.73 1020 0.81 1067 0.89 1110 0.98 1151 1.06 1190 1.15 1228 1.23 1264 1.32 1300 1.41
1920 981 0.82 1035 0.91 1085 1.00 1133 1.09 1174 1.18 1213 1.27 1250 1.37 1286 1.46 — — — —
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt
1-HP Standard Motor & Field
may be necessary. Supplied High Static Drive (2)
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt
may be necessary.
Table PD-63 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard
Motor & Drive
1280 1169 0.96 1201 1.03 1231 1.10 1262 1.17 1290 1.24
1440 1222 1.11 1256 1.20 1286 1.28 1317 1.37 1346 1.45
1600 1278 1.29 1311 1.38 1342 1.48 — — — —
1760 — — — — — — — — — —
1920 — — — — — — — — —
1-HP Standard Motor & Field Supplied High Static Drive (2)
60 RT-PRC006-EN
Performance (5 Ton)
Data High Efficiency
Table PD-64 — Belt Drive Evaporator Fan Performance — 5 Ton — YHC060A3,A4,AW*L,M — Low and Medium Heat — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1600 704 0.36 757 0.41 806 0.47 853 0.52 899 0.58 942 0.65 984 0.72 1021 0.79 1058 0.85 1092 0.92
1800 777 0.49 828 0.56 872 0.62 915 0.67 957 0.73 998 0.80 1038 0.88 1076 0.96 1112 1.04 1146 1.11
2000 851 0.66 900 0.73 942 0.80 981 0.87 1019 0.93 1057 0.99 1094 1.07 1130 1.15 1165 1.24 1199 1.33
2200 927 0.86 973 0.94 1012 1.02 1049 1.09 1084 1.17 1119 1.23 1153 1.30 1188 1.38 1220 1.46 — —
2400 1003 1.10 1045 1.19 1084 1.28 1119 1.36 1152 1.44 — — — — — — — — — —
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
NOTES: Trane’s factory supplied motors, in commercial equipment, are definite purpose
Data includes pressure drop due to standard filters and wet coils. motors, specifically designed and tested to operate reliably and continuously at
No accessories or options are included in pressure drop data. all cataloged conditions. Using the full horsepower range of our fan motors as
Refer to Table PD-89 to determine additional static pressure drop shown in our tabular data will not result in nuisance tripping or premature
due to other options/accessories motor failure. Our product’s warranty will not be affected.
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt
may be necessary.
Table PD-65 — Belt Drive Evaporator Fan Performance — 5 Ton — YHC060A3,A4,AW*L,M — Low and Medium Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor &
Field Supplied Low Static Drive (1) 1-HP Standard Motor & Drive
1600 775 0.42 837 0.50 898 0.57 952 0.65 1000 0.72 1044 0.79 1086 0.87 1127 0.95 1166 1.03 1203 1.11
1800 856 0.58 912 0.66 967 0.74 1020 0.83 1069 0.91 1112 1.00 1152 1.08 1189 1.16 1227 1.25 1263 1.34
2000 939 0.77 990 0.86 1040 0.96 1089 1.05 1136 1.14 1180 1.24 1219 1.33 1256 1.42 1292 1.50 — —
2200 1023 1.01 1070 1.11 1115 1.21 1160 1.31 1205 1.41 — — — — — — — — — —
2400 1108 1.29 1151 1.39 1193 1.50 — — — — — — — — — — — — — —
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt
may be necessary.
RT-PRC006-EN 61
Performance (5 Ton)
Data High Efficiency
Table PD-66 — Belt Drive Evaporator Fan Performance — 5 Ton — YHC060A3,A4,AW*H — High Heat — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1600 723 0.38 774 0.43 822 0.48 869 0.54 914 0.60 957 0.68 997 0.75 1035 0.81 1070 0.88 1104 0.94
1800 801 0.52 847 0.58 891 0.64 933 0.70 975 0.76 1015 0.83 1054 0.91 1091 0.99 1126 1.07 1160 1.15
2000 878 0.70 922 0.77 962 0.84 1001 0.90 1039 0.96 1076 1.03 1113 1.11 1149 1.20 1183 1.28 1217 1.38
2200 957 0.91 999 0.99 1036 1.07 1072 1.14 1107 1.21 1142 1.28 1176 1.35 1209 1.43 — — — —
2400 1036 1.17 1076 1.26 1111 1.34 1144 1.42 1177 1.50 — — — — — — — — — —
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt
may be necessary.
Table PD-67 — Belt Drive Evaporator Fan Performance — 5 Ton — YHC060A3,A4,AW*H — High Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & 1-HP Standard Motor & Drive
Field Supplied High Static Drive (1)
1600 796 0.45 858 0.52 917 0.60 969 0.67 1015 0.75 1059 0.82 1100 0.90 1141 0.98 1178 1.06 1216 1.14
1800 881 0.61 935 0.70 991 0.78 1042 0.87 1087 0.95 1129 1.03 1168 1.12 1206 1.20 1244 1.29 1279 1.38
2000 967 0.82 1016 0.91 1066 1.01 1115 1.10 1160 1.19 1201 1.28 1239 1.38 1275 1.47 — — — —
2200 1054 1.07 1099 1.17 1144 1.27 1189 1.38 1233 1.48 — — — — — — — — — —
2400 1141 1.37 1183 1.48 — — — — — — — — — — — — — — — —
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt
may be necessary.
62 RT-PRC006-EN
Performance (6 Ton)
Data High Efficiency
Table PD-68— Belt Drive Evaporator Fan Performance — 6 Ton — YHC072A3,A4,AW*L,M — Low and Medium Heat — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1920 — — — — 597 0.37 652 0.44 700 0.51 745 0.58 788 0.66 829 0.74 869 0.82 906 0.91
2160 — — 575 0.38 629 0.46 683 0.54 730 0.62 774 0.70 815 0.78 854 0.86 893 0.95 929 1.04
2400 561 0.41 615 0.49 664 0.57 714 0.65 762 0.74 805 0.83 844 0.92 882 1.01 918 1.10 954 1.20
2640 606 0.53 657 0.62 703 0.70 747 0.79 792 0.88 835 0.98 875 1.08 912 1.18 947 1.27 980 1.37
2880 651 0.67 699 0.77 743 0.85 785 0.94 825 1.05 867 1.15 906 1.26 943 1.37 978 1.47 1010 1.58
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at 2-HP Oversized
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as Motor & Drive
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.
Table PD-69 — Belt Drive Evaporator Fan Performance — 6 Ton — YHC072A3,A4,AW*H — High Heat — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1920 — — 574 0.34 631 0.41 681 0.48 727 0.55 771 0.63 814 0.71 853 0.79 892 0.87 928 0.95
2160 562 0.36 616 0.44 671 0.52 719 0.60 763 0.68 805 0.76 845 0.84 884 0.93 921 1.02 957 1.11
2400 612 0.48 662 0.56 711 0.65 759 0.74 802 0.83 842 0.91 879 1.00 916 1.09 951 1.19 986 1.29
2640 663 0.63 709 0.71 754 0.80 798 0.90 842 1.00 881 1.10 917 1.19 951 1.29 986 1.39 1018 1.49
2880 715 0.80 758 0.88 799 0.98 840 1.08 880 1.19 920 1.30 955 1.41 990 1.51 1022 1.62 1053 1.72
2-HP Oversized
Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose 1-HP Standard Motor & High Static
NOTES: motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
Drive Kit (or 2-HP Oversized Motor)
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.
RT-PRC006-EN 63
Performance (6 Ton)
Data High Efficiency
Table PD-70 — Belt Drive Evaporator Fan Performance — 6 Ton — YHC072A3,A4,AW*L,M — Low and Medium Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1920 — — 591 0.34 649 0.42 699 0.48 745 0.56 789 0.64 834 0.72 877 0.81 918 0.89 957 0.97
2160 587 0.38 633 0.44 690 0.52 740 0.61 784 0.68 825 0.76 865 0.85 904 0.95 943 1.04 981 1.13
2400 643 0.51 682 0.58 732 0.65 781 0.75 825 0.84 864 0.92 902 1.01 938 1.11 974 1.21 1010 1.32
2640 700 0.66 736 0.74 775 0.81 822 0.90 866 1.01 906 1.11 942 1.20 976 1.29 1009 1.40 1042 1.51
2880 756 0.84 790 0.93 823 1.01 864 1.09 907 1.20 947 1.32 983 1.43 1017 1.53 1048 1.62 1080 1.73
2-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at 1-HP Standard Motor & High Static
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as Drive (or 2-HP Oversized Motor)
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.
2. Field Supplied Fan Sheave AK54 and Belt AX30 required.
Table PD-70 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard 1-HP Standard Motor & High Static
Motor & Drive Drive Kit(or 2 HP Oversized Motor & Drive)
1920 996 1.06 1033 1.16 1067 1.25 1102 1.35 1134 1.44 1165 1.53 1195 1.63 1223 1.72 1251 1.82 1277 1.91
2160 1018 1.23 1054 1.32 1090 1.42 1123 1.52 1156 1.63 1188 1.73 1218 1.84 1247 1.94 1276 2.05 1304 2.16
2400 1044 1.42 1079 1.52 1112 1.62 1145 1.73 1177 1.83 1208 1.94 1240 2.06 1268 2.17 1298 2.29 — —
2640 1075 1.62 1107 1.74 1139 1.85 1170 1.96 1201 2.08 1232 2.19 — — — — 2-HP Oversized Motor
2880 1111 1.85 1140 1.97 1169 2.09 1200 2.22 — — — — — — — — & FieldSupplied High
2-HP Oversized Motor & Drive Static Drive (2)
Table PD-71 — Belt Drive Evaporator Fan Performance — 6 Ton — YHC072A3,A4,AW*H — High Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1920 565 0.31 627 0.39 680 0.46 727 0.52 772 0.61 816 0.69 859 0.77 902 0.86 942 0.94 981 1.03
2160 621 0.43 677 0.50 729 0.59 774 0.66 816 0.74 856 0.83 895 0.93 934 1.02 973 1.11 1009 1.21
2400 680 0.57 729 0.65 778 0.74 823 0.84 862 0.92 900 1.00 936 1.10 972 1.20 1006 1.31 1041 1.41
2640 741 0.75 782 0.82 828 0.92 872 1.03 911 1.13 947 1.21 981 1.31 1014 1.41 1048 1.53 1079 1.64
2880 802 0.95 837 1.04 880 1.13 921 1.24 960 1.36 995 1.47 1028 1.56 1060 1.66 1091 1.77 1122 1.89
2-HP Oversized
Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose 1-HP Standard Motor & High Static
NOTES: motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
Drive Kit (or 2-HP Oversized Motor)
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.
2. Field Supplied Fan Sheave AK54 and Belt AX30 required.
Table PD-71 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & High Static Drive Kit
(or 2 HP Oversized Motor & Drive)
1920 1018 1.12 1054 1.21 1089 1.31 1122 1.40 1154 1.50 1184 1.59 1212 1.69 1241 1.78 1268 1.88 1293 1.97
2160 1045 1.30 1081 1.40 1114 1.50 1149 1.61 1181 1.71 1211 1.81 1241 1.92 1270 2.03 1298 2.13 1324 2.24
2400 1076 1.51 1110 1.62 1143 1.72 1176 1.83 1206 1.94 1238 2.05 1267 2.16 1297 2.28 — — — —
2640 1111 1.75 1144 1.87 1174 1.98 1205 2.09 1236 2.21 — — — — — — — — — —
2880 1151 2.02 1180 2.14 1209 2.27 — — — — — — — — — — — — — —
2-HP Oversized Motor & Drive 2-HP Oversized Motor & Field
Supplied High Static Drive (2)
64 RT-PRC006-EN
Performance (7½ Ton)
Data High Efficiency
Table PD-72 — Belt Drive Evaporator Fan Performance — 7½-Ton — YHC092A3,A4,AW *L,M — Low and Medium Heat —DownflowAirflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied
Low Static Drive (1)
2400 — — — — — — 613 0.58 656 0.68 696 0.79 732 0.91 765 1.03 798 1.16 829 1.30
2700 — — — — 605 0.58 647 0.69 687 0.81 726 0.93 762 1.05 796 1.18 828 1.32 857 1.45
3000 — — 606 0.62 645 0.72 684 0.83 721 0.96 758 1.09 792 1.22 826 1.36 858 1.49 888 1.64
3300 609 0.66 650 0.77 688 0.89 723 1.00 758 1.13 792 1.27 825 1.41 857 1.56 888 1.70 918 1.85
3600 658 0.84 695 0.96 731 1.08 764 1.20 796 1.33 828 1.47 859 1.63 890 1.79 920 1.94 949 2.10
2-HP Standard Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Table PD-72 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2400 858 1.43 888 1.57 917 1.71 945 1.85 971 1.99 998 2.14 1023 2.28 1048 2.44 1072 2.59 1095 2.75
2700 886 1.60 915 1.75 942 1.90 969 2.05 995 2.21 1020 2.36 1045 2.51 1069 2.67 1093 2.83 1117 3.00
3000 916 1.79 944 1.94 970 2.10 995 2.26 1020 2.43 1044 2.59 1069 2.76 1092 2.93 1116 3.10 1139 3.27
3300 947 2.01 974 2.16 1000 2.33 1026 2.50 1050 2.67 1073 2.84 1097 3.02 1119 3.20 1141 3.38 — —
3600 976 2.25 1004 2.42 1030 2.58 1056 2.76 1080 2.94 1103 3.12 1126 3.30 — — — — — —
3-HP Oversized Motor & Drive
Table PD-73 — Belt Drive Evaporator Fan Performance — 7½-Ton — YHC092A3,A4,AW *H — High Heat —DownflowAirflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied
Low Static Drive (1)
2400 — — — — — — 623 0.60 664 0.70 703 0.82 739 0.93 773 1.06 804 1.19 835 1.32
2700 — — — — 617 0.61 658 0.73 698 0.84 736 0.96 771 1.08 804 1.21 835 1.35 865 1.49
3000 — — 619 0.65 658 0.75 696 0.87 733 1.00 770 1.13 804 1.26 837 1.40 868 1.54 897 1.69
3300 625 0.70 666 0.82 702 0.93 737 1.05 771 1.19 805 1.33 838 1.47 870 1.62 900 1.76 929 1.91
3600 675 0.89 713 1.02 747 1.14 779 1.26 811 1.40 843 1.55 874 1.70 904 1.86 934 2.02 962 2.17
2-HP Standard Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Table PD-73 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2400 864 1.46 895 1.60 923 1.74 951 1.88 977 2.02 1003 2.17 1028 2.32 1053 2.47 1078 2.63 1100 2.78
2700 894 1.64 921 1.79 948 1.94 974 2.09 1001 2.24 1027 2.40 1052 2.56 1076 2.72 1100 2.88 1124 3.05
3000 925 1.83 952 1.99 978 2.15 1004 2.32 1029 2.48 1052 2.65 1076 2.82 1100 2.99 1123 3.15 1146 3.33
3300 958 2.06 984 2.22 1010 2.39 1035 2.56 1059 2.73 1082 2.91 1105 3.09 1128 3.28 — — — —
3600 990 2.33 1017 2.50 1043 2.66 1067 2.84 1091 3.02 1114 3.20 1137 3.39 — — — — — —
3-HP Oversized Motor & Drive
RT-PRC006-EN 65
Performance (7½ Ton)
Data High Efficiency
Table PD-74 — Belt Drive Evaporator Fan Performance — 7½-Ton — YHC092A3,A4,AW *L,M — Low and Medium Heat —Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied
Low Static Drive (1)
2400 — — 599 0.52 650 0.62 703 0.75 751 0.87 789 0.98 823 1.08 855 1.19 885 1.29 912 1.39
2700 604 0.58 651 0.68 694 0.79 741 0.91 789 1.06 832 1.19 868 1.32 900 1.44 931 1.56 959 1.68
3000 661 0.77 705 0.88 744 1.00 783 1.12 826 1.26 869 1.42 909 1.58 945 1.73 976 1.86 1004 1.99
3300 719 1.00 758 1.11 797 1.25 832 1.37 867 1.51 907 1.68 946 1.85 983 2.02 1017 2.18 1048 2.34
3600 779 1.28 813 1.39 850 1.54 883 1.68 915 1.82 948 1.97 984 2.15 1020 2.33 1055 2.52 1088 2.71
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Table PD-74 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2400 939 1.50 965 1.60 990 1.71 1014 1.81 1039 1.92 1063 2.03 1085 2.14 1108 2.25 1131 2.36 1154 2.49
2700 985 1.79 1010 1.91 1034 2.03 1058 2.14 1081 2.26 1104 2.38 1126 2.50 1148 2.62 1169 2.74 1190 2.86
3000 1031 2.12 1056 2.25 1081 2.39 1104 2.51 1127 2.65 1148 2.77 1169 2.90 1190 3.03 1210 3.16 1231 3.30
3300 1077 2.50 1102 2.64 1127 2.78 1151 2.93 1174 3.07 1194 3.21 1216 3.36 — — — — — —
3600 1120 2.89 1146 3.06 1172 3.22 1195 3.38 — — — — — — — — — — — —
3-HP Oversized Motor & Drive
Table PD-75 — Belt Drive Evaporator Fan Performance — 7½-Ton — YHC092A3,A4,AW *H — High Heat —Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied
Low Static Drive (1)
2400 — — 613 0.54 666 0.66 718 0.78 762 0.90 799 1.01 833 1.11 864 1.22 893 1.32 920 1.42
2700 621 0.61 667 0.72 710 0.83 759 0.97 804 1.10 846 1.24 880 1.36 911 1.48 941 1.60 968 1.72
3000 680 0.81 723 0.93 761 1.05 802 1.18 845 1.33 888 1.49 925 1.64 959 1.79 988 1.92 1016 2.05
3300 740 1.06 780 1.19 816 1.31 850 1.45 889 1.60 928 1.77 966 1.94 1002 2.11 1036 2.28 1063 2.42
3600 800 1.35 837 1.49 872 1.63 904 1.77 935 1.91 971 2.08 1007 2.27 1043 2.45 1077 2.64 1108 2.83
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. Field Supplied Fan Sheave AK79 and Belt AX38 required..
Table PD-75 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2400 946 1.53 972 1.64 997 1.74 1022 1.84 1045 1.95 1069 2.06 1092 2.17 1115 2.28 1137 2.40 1160 2.52
2700 994 1.84 1019 1.95 1043 2.07 1066 2.18 1089 2.30 1112 2.42 1134 2.54 1155 2.66 1177 2.78 1197 2.90
3000 1043 2.18 1067 2.31 1091 2.44 1114 2.57 1137 2.70 1158 2.83 1178 2.96 1200 3.09 1220 3.22 1240 3.35
3300 1090 2.57 1116 2.72 1140 2.86 1162 3.00 1185 3.15 1206 3.29 1227 3.43 — — — — — —
3600 137 3.00 1163 3.17 1188 3.33 — — — — — — — — — — — — — —
3-HP Oversized Motor & Drive
66 RT-PRC006-EN
Performance (8½ Ton)
Data High Efficiency
Table PD-76— Belt Drive Evaporator Fan Performance — 8½-Ton — YHC102A3,A4,AW *L — Low Heat — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied
Low Static Drive (1)
2720 — — — — 621 0.62 662 0.74 703 0.86 741 0.98 777 1.11 810 1.24 841 1.38 871 1.52
3060 587 0.58 630 0.69 668 0.79 707 0.92 743 1.05 779 1.18 814 1.32 846 1.45 878 1.60 907 1.75
3400 643 0.77 683 0.89 718 1.00 753 1.13 787 1.26 820 1.41 853 1.56 884 1.71 915 1.86 944 2.02
3740 699 0.99 736 1.12 770 1.25 802 1.38 833 1.52 864 1.67 894 1.83 925 2.00 953 2.16 982 2.33
4080 757 1.26 790 1.40 823 1.55 853 1.69 882 1.83 910 1.98 938 2.15 967 2.32 994 2.50 1021 2.68
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Table PD-76 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2720 900 1.67 927 1.82 954 1.97 980 2.12 1006 2.28 1032 2.44 1057 2.60 1082 2.76 1105 2.92 1129 3.09
3060 936 1.90 962 2.06 989 2.22 1014 2.39 1039 2.56 1062 2.73 1085 2.90 1109 3.07 1133 3.25 1155 3.43
3400 973 2.17 999 2.34 1025 2.51 1050 2.68 1074 2.86 1097 3.04 1120 3.22 1142 3.41 — — — —
3740 1010 2.50 1036 2.66 1062 2.84 1087 3.01 1110 3.19 1134 3.39 — — — — — — — —
4080 1047 2.86 1073 3.04 1098 3.22 1123 3.40 — — — — — — — — — — — —
3-HP Oversized Motor & Drive
Table PD-77 — Belt Drive Evaporator Fan Performance — 8½-Ton — YHC102A3,A4,AW *M— Medium Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied
Low Static Drive (1)
2720 — — — — 623 0.63 664 0.75 704 0.87 742 0.99 778 1.11 811 1.24 842 1.38 872 1.53
3060 589 0.58 632 0.69 670 0.80 709 0.92 745 1.06 781 1.19 815 1.32 848 1.46 880 1.60 909 1.75
3400 645 0.77 685 0.89 721 1.01 755 1.13 789 1.27 822 1.42 854 1.57 886 1.72 916 1.87 945 2.02
3740 702 1.00 739 1.14 772 1.26 804 1.39 836 1.53 867 1.69 897 1.85 926 2.01 956 2.18 984 2.34
4080 759 1.27 793 1.42 826 1.56 856 1.70 884 1.84 913 2.00 941 2.16 969 2.34 996 2.52 1024 2.70
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Table PD-77 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2720 900 1.67 928 1.82 955 1.98 982 2.14 1008 2.29 1033 2.45 1057 2.60 1083 2.77 1107 2.94 1129 3.10
3060 936 1.91 964 2.07 989 2.23 1015 2.39 1039 2.56 1063 2.73 1088 2.92 1111 3.09 1134 3.26 1157 3.44
3400 974 2.18 1001 2.35 1027 2.52 1051 2.69 1075 2.87 1098 3.05 1121 3.23 1144 3.42 — — — —
3740 1011 2.50 1038 2.68 1064 2.85 1089 3.03 1113 3.22 1135 3.40 — — — — — — — —
4080 1050 2.87 1076 3.05 1101 3.24 1126 3.43 — — — — — — — — — — — —
3-HP Oversized Motor & Drive
RT-PRC006-EN 67
Performance (8½ Ton)
Data High Efficiency
Table PD-78 — Belt Drive Evaporator Fan Performance — 8½-Ton — YHC102A3,A4,AW *H — High Heat — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied
Low Static Drive (1)
2720 — — 590 0.55 633 0.66 674 0.77 713 0.89 750 1.01 786 1.14 818 1.28 850 1.42 879 1.56
3060 602 0.62 643 0.72 682 0.83 719 0.96 756 1.09 791 1.23 825 1.36 857 1.50 889 1.65 917 1.80
3400 660 0.82 698 0.94 733 1.05 767 1.18 801 1.32 834 1.48 866 1.62 897 1.77 927 1.92 956 2.08
3740 718 1.06 754 1.19 787 1.32 818 1.45 849 1.60 880 1.76 910 1.92 939 2.08 968 2.24 996 2.41
4080 777 1.35 811 1.49 841 1.63 870 1.77 899 1.92 928 2.08 956 2.26 983 2.43 1011 2.61 1037 2.79
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Table PD-78 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2720 907 1.71 934 1.86 960 2.01 987 2.17 1014 2.33 1039 2.48 1063 2.64 1088 2.81 1112 2.97 1134 3.13
3060 945 1.95 971 2.11 997 2.28 1022 2.45 1047 2.62 1070 2.79 1094 2.96 1117 3.14 1141 3.31 — —
3400 985 2.24 1010 2.40 1036 2.58 1060 2.76 1084 2.93 1106 3.11 1130 3.31 — — — — — —
3740 1023 2.58 1049 2.75 1075 2.93 1099 3.11 1122 3.29 — — — — — — — — — —
4080 1063 2.96 1089 3.15 1114 3.34 — — — — — — — — — — — — — —
3-HP Oversized Motor & Drive
Table PD-79 — Belt Drive Evaporator Fan Performance — 8½-Ton — YHC102A3,A4,AW *L— Low Heat —Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied
Low Static Drive (1)
2720 622 0.62 669 0.73 711 0.84 760 0.97 807 1.12 849 1.26 884 1.38 915 1.50 944 1.62 972 1.74
3060 688 0.85 732 0.97 770 1.09 809 1.22 853 1.38 895 1.54 934 1.70 968 1.85 998 1.99 1026 2.13
3400 756 1.14 795 1.27 832 1.40 866 1.54 901 1.69 941 1.86 979 2.04 1015 2.22 1049 2.40 1079 2.56
3740 824 1.49 859 1.62 895 1.78 926 1.92 957 2.07 990 2.24 1025 2.42 1061 2.62 1095 2.82 1127 3.02
4080 893 1.90 925 2.05 958 2.21 988 2.37 1017 2.53 1046 2.70 1075 2.88 1108 3.08 1140 3.29 — —
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Table PD-79 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2720 998 1.86 1024 1.98 1047 2.10 1071 2.22 1094 2.33 1115 2.45 1138 2.57 1159 2.69 1181 2.82 1201 2.94
3060 1053 2.26 1078 2.39 1102 2.53 1125 2.66 1146 2.79 1169 2.93 1190 3.06 1210 3.19 1230 3.32 1250 3.45
3400 1106 2.71 1131 2.86 1156 3.02 1179 3.16 1201 3.31 1223 3.45 — — — — — — — —
3740 1158 3.21 1185 3.39 — — — — — — — — — — — — — — — —
4080 — — — — — — — — — — — — — — — — — — — —
3-HP Oversized Motor & Drive
68 RT-PRC006-EN
Performance (8½ Ton)
Data High Efficiency
Table PD-80 — Belt Drive Evaporator Fan Performance — 8½-Ton — YHC102A3,A4,AW *M — Medium Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied
Low Static Drive (1)
2720 625 0.62 671 0.73 714 0.84 763 0.98 809 1.13 851 1.27 885 1.39 917 1.51 946 1.63 974 1.75
3060 691 0.86 734 0.98 772 1.10 812 1.23 856 1.39 897 1.55 936 1.71 970 1.86 1001 2.00 1028 2.14
3400 759 1.15 798 1.28 835 1.41 868 1.55 904 1.70 943 1.87 982 2.05 1019 2.23 1052 2.41 1082 2.57
3740 827 1.50 863 1.64 898 1.79 930 1.94 960 2.09 994 2.26 1029 2.44 1064 2.64 1098 2.84 1130 3.03
4080 897 1.92 929 2.07 962 2.23 992 2.39 1021 2.55 1049 2.72 1079 2.90 1112 3.10 1144 3.31 — —
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Table PD-80 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2720 1000 1.87 1025 1.99 1048 2.10 1072 2.22 1095 2.34 1117 2.46 1139 2.58 1161 2.70 1182 2.82 1203 2.95
3060 1054 2.27 1080 2.41 1103 2.53 1126 2.67 1149 2.80 1170 2.93 1192 3.07 1211 3.20 1231 3.33 — —
3400 1108 2.73 1134 2.88 1158 3.03 1181 3.17 1204 3.33 — — — — — — — — — —
3740 1160 3.23 1187 3.41 — — — — — — — — — — — — — — — —
4080 — — — — — — — — — — — — — — — — — — — —
3-HP Oversized Motor & Drive
Table PD-81 — Belt Drive Evaporator Fan Performance — 8½-Ton — YHC102A3,A4,AW *H— High Heat —Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied 2-HP Standard Motor & Drive
Low Static Drive (1)
2720 640 0.66 684 0.77 729 0.89 778 1.03 823 1.17 863 1.31 896 1.43 926 1.55 955 1.67 982 1.79
3060 709 0.91 750 1.03 788 1.15 829 1.29 872 1.45 913 1.61 950 1.77 983 1.92 1011 2.05 1038 2.19
3400 778 1.21 817 1.35 851 1.48 885 1.62 924 1.78 963 1.96 1000 2.14 1035 2.30 1067 2.49 1095 2.65
3740 848 1.58 885 1.73 917 1.88 948 2.03 979 2.18 1014 2.36 1050 2.56 1084 2.76 1118 2.96 1148 3.15
4080 919 2.02 952 2.18 984 2.35 1012 2.50 1041 2.67 1070 2.84 1102 3.04 1135 3.25 — — — —
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Table PD-81 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2720 1007 1.90 1032 2.02 1056 2.14 1079 2.26 1101 2.38 1124 2.50 1146 2.62 1167 2.74 1189 2.86 1209 2.98
3060 1064 2.32 1090 2.46 1113 2.59 1135 2.72 1157 2.85 1178 2.98 1199 3.12 1220 3.26 1240 3.39 — —
3400 1121 2.80 1146 2.95 1170 3.10 1193 3.25 1215 3.40 — — — — — — — — — —
3740 1177 3.34 — — — — — — — — — — — — — — — — — —
4080 — — — — — — — — — — — — — — — — — — — —
3-HP Oversized Motor & Drive
RT-PRC006-EN 69
Performance (10 Ton)
Data High Efficiency
Table PD-82— Belt Drive Evaporator Fan Performance — 10-Ton — YHC120A3,A4,AW *L,M — Low and Medium Heat — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Field Supplied
Low Static Drive (1)
3200 — — — — — — 743 1.06 779 1.20 814 1.35 847 1.49 879 1.63 910 1.78 938 1.93
3600 — — 735 1.10 768 1.22 802 1.36 834 1.50 866 1.66 897 1.82 927 1.98 957 2.14 985 2.30
4000 767 1.29 802 1.44 833 1.58 863 1.71 892 1.87 922 2.04 951 2.21 979 2.39 1006 2.56 1034 2.74
4400 837 1.69 869 1.85 899 2.00 926 2.15 953 2.31 980 2.48 1007 2.66 1033 2.85 1059 3.04 1085 3.24
4800 908 2.16 937 2.33 965 2.50 991 2.67 1017 2.83 1041 3.00 1066 3.19 1090 3.38 1115 3.59 1139 3.80
3-HP Standard Motor & Drive 5-HP Oversized
Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
NOTES:
Trane’s factory supplied motors, in commercial equipment, are definite purpose
Data includes pressure drop due to standard filters and wet coils.
motors, specifically designed and tested to operate reliably and continuously at
No accessories or options are included in pressure drop data.
all cataloged conditions. Using the full horsepower range of our fan motors as
Refer to Table PD-89 to determine additional static pressure drop
shown in our tabular data will not result in nuisance tripping or premature
due to other options/accessories
motor failure. Our product’s warranty will not be affected.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. Field Supplied Motor Sheave 1VM50 x 7/8 inch, Fan Sheave AK89, and Belt AX40 required.
Table PD-83— Belt Drive Evaporator Fan Performance — 10-Ton — YHC120A3,A4,AW *H— High Heat —Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Field Supplied 3-HP Standard Motor
Low Static Drive (1) & Drive
3200 — — — — 739 1.05 774 1.19 809 1.33 843 1.47 874 1.61 905 1.76 935 1.92 963 2.08
3600 738 1.11 772 1.23 805 1.37 838 1.52 869 1.68 900 1.84 930 2.00 960 2.16 988 2.32 1016 2.49
4000 813 1.49 844 1.63 873 1.77 903 1.93 932 2.10 961 2.27 989 2.45 1017 2.63 1043 2.80 1070 2.98
4400 889 1.95 917 2.10 944 2.25 971 2.42 998 2.59 1024 2.78 1050 2.97 1076 3.17 1101 3.37 1126 3.56
4800 964 2.50 991 2.66 1016 2.83 1040 3.00 1065 3.18 1090 3.38 1114 3.58 1138 3.79 1161 4.00 1184 4.22
5-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. Field Supplied Motor Sheave 1VM50 x 7/8 inch, Fan Sheave AK89, and Belt AX40 required
Table PD-83 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Drive
3200 989 2.24 1015 2.41 1039 2.58 1064 2.76 1087 2.93 1111 3.12 1133 3.30 1156 3.48 1179 3.68 1200 3.85
3600 1042 2.66 1067 2.84 1091 3.02 1115 3.21 1138 3.40 1160 3.59 1181 3.78 1203 3.98 1224 4.19 1244 4.39
4000 1095 3.17 1120 3.35 1145 3.54 1167 3.73 1190 3.93 1212 4.14 1233 4.35 1253 4.55 1273 4.76 1293 4.97
4400 1150 3.75 1174 3.95 1197 4.15 1221 4.36 1243 4.56 1265 4.77 1285 4.97 1306 5.20 1326 5.42 1345 5.65
4800 1208 4.42 1231 4.64 1253 4.86 1275 5.07 1297 5.29 1317 5.50 1338 5.72 — — — — — —
5-HP Oversized Motor & Drive
70 RT-PRC006-EN
Performance (10 Ton)
Data High Efficiency
Table PD-84 — Belt Drive Evaporator Fan Performance — 10-Ton — YHC120A3,A4,AW *L,M — Low and Medium Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Field Supplied
Low Static Drive (1)
3200 — — 777 1.15 814 1.28 853 1.42 895 1.59 936 1.76 973 1.93 1008 2.09 1037 2.24 1064 2.38
3600 819 1.42 857 1.57 890 1.71 922 1.85 957 2.02 994 2.20 1032 2.39 1067 2.58 1099 2.77 1131 2.96
4000 902 1.91 936 2.07 968 2.23 998 2.39 1027 2.55 1058 2.73 1091 2.93 1124 3.14 1158 3.36 1189 3.57
4400 986 2.50 1016 2.68 1047 2.86 1075 3.03 1101 3.20 1128 3.39 1155 3.58 1186 3.80 1217 4.03 1246 4.25
4800 1070 3.22 1098 3.40 1127 3.60 1153 3.79 1178 3.98 1203 4.17 1227 4.37 1251 4.57 1279 4.80 1307 5.05
3-HP Standard Motor 5-HP Oversized Motor & Drive
& Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Trane’s factory supplied motors, in commercial equipment, are definite purpose
NOTES: motors, specifically designed and tested to operate reliably and continuously at
Data includes pressure drop due to standard filters and wet coils. all cataloged conditions. Using the full horsepower range of our fan motors as
No accessories or options are included in pressure drop data. shown in our tabular data will not result in nuisance tripping or premature
Refer to Table PD-89 to determine additional static pressure drop motor failure. Our product’s warranty will not be affected.
due to other options/accessories
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. Field Supplied Motor Sheave 1VM50 x 7/8 inch, Fan Sheave AK89, and Belt AX40 required.
Table PD-85 — Belt Drive Evaporator Fan Performance — 10-Ton — YHC120A3,A4,AW *H— High Heat —Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Field Supplied 3-HP Standard Motor & Drive
Low Static Drive (1)
3200 785 1.18 821 1.31 861 1.46 903 1.62 944 1.80 981 1.96 1014 2.12 1043 2.27 1070 2.41 1095 2.55
3600 874 1.64 907 1.78 939 1.93 977 2.11 1014 2.30 1050 2.49 1084 2.69 1115 2.87 1144 3.05 1169 3.21
4000 964 2.21 994 2.37 1023 2.53 1053 2.71 1087 2.91 1121 3.12 1154 3.33 1185 3.55 1215 3.76 1242 3.96
4400 1055 2.91 1082 3.08 1109 3.25 1135 3.43 1164 3.64 1194 3.86 1225 4.09 1255 4.32 1284 4.56 1312 4.79
4800 1146 3.74 1171 3.92 1196 4.11 1220 4.31 1244 4.51 1271 4.73 1298 4.97 1327 5.22 1354 5.47 1382 5.74
5-HP Oversized Motor & Drive
Trane’s factory supplied motors, in commercial equipment, are definite purpose
For Standard Evaporator Fan Speed (RPM), reference Table PD-86.
motors, specifically designed and tested to operate reliably and continuously at
NOTES:
all cataloged conditions. Using the full horsepower range of our fan motors as
Data includes pressure drop due to standard filters and wet coils.
shown in our tabular data will not result in nuisance tripping or premature
No accessories or options are included in pressure drop data.
motor failure. Our product’s warranty will not be affected.
Refer to Table PD-89 to determine additional static pressure drop
due to other options/accessories
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. Field Supplied Motor Sheave 1VM50 x 7/8 inch, Fan Sheave AK89, and Belt AX40 required
RT-PRC006-EN 71
Performance
Data
Table PD-87— Standard Motor & High Static Drive Accessory Sheave/Fan Speed (Rpm)
Unit 6Turns 5Turns 4Turns 3Turns 2Turns 1Turn
Tons Model No. Open Open Open Open Open Open Closed
6 Y#C072A3,A4,AW N/A 831 895 959 1022 1086 1150
6 YSC072AK N/A 958 1022 1086 1150 1214 1278
7½ YSC090,092A N/A 958 1022 1086 1150 1214 1278
Factory set at 3 turns open.
72 RT-PRC006-EN
Performance
Data
Table PD-89 — Static Pressure Drops Through Accessories (Inches Water Column)
Economizer with OA/RA Dampers2
Unit Standard Through 2” Pleated 100% OA 100% RA 100% OA 100% RA
Tons Model No CFM Filters1 Reheat Coil (WC) Filters Downflow Horizontal
960 0.03 — 0.05 0.05 0.01 0.05 0.00
YSC036A 1200 0.04 — 0.07 0.07 0.02 0.07 0.01
1440 0.06 — 0.10 0.10 0.03 0.10 0.01
3 960 0.02 .03 0.04 0.05 0.01 0.05 0.00
YHC036A 1200 0.03 .04 0.05 0.07 0.02 0.07 0.01
1440 0.04 .06 0.07 0.10 0.03 0.10 0.01
1280 0.04 — 0.06 0.08 0.03 0.08 0.01
YSC048A 1600 0.05 — 0.09 0.12 0.04 0.12 0.01
4 1920 0.08 — 0.12 0.17 0.06 0.17 0.02
1280 0.04 .05 0.06 0.08 0.03 0.08 0.01
YHC048A 1600 0.05 .07 0.09 0.12 0.04 0.12 0.01
1920 0.08 .09 0.12 0.17 0.06 0.17 0.02
1600 0.10 — 0.15 0.12 0.04 0.12 0.01
YSC060A 2000 0.15 — 0.22 0.18 0.07 0.18 0.02
2400 0.22 — 0.29 0.26 0.10 0.26 0.04
5 1600 0.04 0.07 0.07 0.12 0.04 0.12 0.01
YHC060A 2000 0.06 0.10 0.10 0.18 0.07 0.18 0.02
2400 0.09 0.14 0.14 0.26 0.10 0.26 0.04
1920 0.04 — 0.07 0.10 0.01 0.06 0.02
6 Y#C072A 2400 0.06 — 0.09 0.11 0.02 0.08 0.02
2880 0.09 — 0.12 0.13 0.04 0.10 0.04
2400 0.06 — 0.09 0.11 0.02 0.08 0.02
YSC090, 092A 3000 0.10 — 0.13 0.14 0.05 0.12 0.05
7½ 3600 0.14 — 0.18 0.21 0.07 0.25 0.08
2400 0.04 .10 0.06 0.11 0.02 0.08 0.02
YHC092A 3000 0.06 .14 0.09 0.14 0.05 0.12 0.05
3600 0.09 .19 0.13 0.21 0.07 0.25 0.08
2720 0.05 — 0.08 0.12 0.03 0.09 0.04
YSC102A 3400 0.08 — 0.11 0.19 0.06 0.18 0.06
8½ 4080 0.12 — 0.16 0.30 0.07 0.31 0.09
2720 0.05 .12 0.08 0.12 0.03 0.09 0.04
YHC102A 3400 0.08 .17 0.11 0.19 0.06 0.18 0.06
4080 0.12 .23 0.16 0.30 0.07 0.31 0.09
3200 0.07 — 0.10 0.17 0.05 0.14 0.05
YSC120A 4000 0.11 — 0.15 0.26 0.07 0.30 0.08
10 4800 0.16 — 0.20 0.34 0.09 0.35 0.10
3200 — 0.15 0.10 0.17 0.05 0.14 0.05
YHC120A 4000 — 0.22 0.15 0.26 0.07 0.30 0.08
4800 0.16 0.31 0.20 0.34 0.09 0.35 0.10
Notes:
1. Tested with standard filters (3-5 tons 1”, 6-10 tons 2”) . Difference in pressure drop should be considered when utilizing optional 2” pleated filters.
2. OA = Outside Air and RA = Return Air.
RT-PRC006-EN 73
Performance
Data
-12
Table PD-90— Outdoor Sound Power Level - dB (ref. 10 Watts)
Unit Octave Center Frequency Overall
Tons Model No. 63. 125 250 500 1000 2000 4000 8000 dBA
3 Y*C036A 86 83 81 80 78 74 69 68 83
YSC048A1 92 87 84 83 81 76 72 69 86
4 YSC048A3,A4,AW 90 84 78 77 76 72 70 68 82
YHC048A 92 86 83 82 81 75 72 69 85
YSC060A 94 87 83 82 79 75 73 69 84
5 YHC060A 94 87 82 81 78 74 72 69 84
YSC072A 90 94 90 87 83 78 74 67 88
6 YHC072A 91 95 90 87 84 79 75 68 89
YSC090A 92 95 91 88 84 80 75 68 90
7½ YSC092A 89 93 88 85 81 76 72 66 87
YHC092A 92 96 92 89 85 80 76 69 91
YSC102A 88 92 87 84 80 75 72 65 86
8½ YHC102A 91 95 90 87 84 79 75 68 89
YSC120A 91 88 84 82 81 76 73 67 86
10
YHC120A 94 89 87 85 84 78 75 69 88
Note:
Tests follow ARI270-95.
74 RT-PRC006-EN
Performance
Data
RT-PRC006-EN 75
Zone
Controls
ReliaTel™ Controlled Units Integrated ComfortTM System — Programmable Night Setback — Auto
Sensor(s) available with optional or manual changeover with seven-day
Zone Sensors are the building temperature adjustment and override programming. Keyboard selection of
occupant’s comfort control devices for buttons to provide
Precedent™ units with the Micro control: central control
through aTrane
Manual Changeover — Heat, Cool or Off Integrated
System Switch. Fan Auto or Off Switch. ComfortTM system.
One temperature
setpoint lever.
76 RT-PRC006-EN
Zone
Controls
Electromechanically Controlled
Units
Conventional Thermostats are the
building occupant’s comfort control
devices for electromechanically
controlled units.
Manual Changeover — One Heat, One
CoolThermostat.
Heat, Cool or Off
System Switch.
Fan Auto or On 70 80
60
Switch. Set Point
90
Dial. Adjustable TM
Heat Anticipator. 60
90
70
80
HEAT 50 60 70 80 50 60 70 80
COOL
50 60 70 80
TM
FAN
AUTO ON OFF AUTO
RT-PRC006-EN 77
Electrical
Data (Standard Efficiency)
78 RT-PRC006-EN
Electrical
Data (High Efficiency)
RT-PRC006-EN 79
Electrical
Data
80 RT-PRC006-EN
Electrical
Data
RT-PRC006-EN 81
Electrical
Data (Standard Efficiency)
Table ED-5 — Electrical Characteristics — Compressor Motor And Condenser Motor — Standard Efficiency
Compressor Motor Condenser Fan Motors
Unit Amps Amps
Tons Model No. No. Volts Phase HP2 RPM RLA LRA No. Phase HP FLA LRA
YSC036A1 1 208-230 1 3.1 3450 17.2 104.0 1 1 .20 1.5 2.5
3 YSC036A3 1 208-230 3 3.1 3450 11.3 74.0 1 1 .20 1.5 2.5
YSC036A4 1 460 3 3.1 3450 6.0 37.6 1 1 .20 0.6 1.3
YSC036AW 1 575 3 3.1 3450 4.9 30.4 1 1 .20 0.5 1.2
YSC048A1 1 208-230 1 3.9 3450 22.7 131.0 1 1 .33 2.0 6.6
YSC048A3 1 208-230 3 3.9 3450 14.6 91.0 1 1 .33 2.0 6.6
4 YSC048A4 1 460 3 3.9 3450 7.9 46.0 1 1 .33 1.2 2.5
YSC048AW 1 575 3 3.9 3450 6.1 37.0 1 1 .33 0.7 1.5
YSC060A1 1 208-230 1 5.1 3450 31.3 144.0 1 1 .33 2.0 6.6
YSC060A3 1 208-230 3 5.1 3450 18.6 128.0 1 1 .33 2.0 6.6
5
YSC060A4 1 460 3 5.1 3450 9.5 63.0 1 1 .33 1.2 2.5
YSC060AW 1 575 3 5.1 3450 7.5 49.0 1 1 .33 0.7 1.5
YSC060AK 1 380 3 5.1 3450 11.4 64 1 1 .40 1.1 4.3
YSC072A3 1 208-230 3 6 3450 19.0 156 1 1 .70 3.85 9.30
6 YSC072A4 1 460 3 6 3450 10.1 75 1 1 .70 2.50 5.80
YSC072AW 1 575 3 6 3450 7.7 54 1 1 .70 1.54 3.60
YSC072AK 1 380 3 6 3450 12.2 70 1 1 .75 2.5 7.7
YSC090A3 1 208-230 3 7.5 3450 26.0 181.5 1 1 .70 3.85 9.30
YSC090A4 1 460 3 7.5 3450 13.6 95.0 1 1 .70 2.50 5.80
YSC090AW 1 575 3 7.5 3450 10.9 69.0 1 1 .70 1.54 3.60
YSC090AK 1 380 3 7.5 3450 16.4 106.3 1 1 .75 2.5 7.7
7½ YSC092A3 2 208-230 3 4/2.8 3450 14.7/10.3 91/77 1 1 .70 3.85 9.30
YSC092A4 2 460 3 4/2.8 3450 7.6/5.4 50/39 1 1 .70 2.50 5.80
YSC092AW 2 575 3 4/2.8 3450 5.8/4.2 37/31 1 1 .70 1.54 3.60
YSC102A3 2 208-230 3 5.1/2.8 3450 18.6/10.3 128/77 1 1 .75 4.0 9.4
8½ YSC102A4 2 460 3 5.1/2.8 3450 10.0/5.4 63/39 1 1 .75 2.8 6.8
YSC102AW 2 575 3 5.1/2.8 3450 8.2/4.2 49/31 1 1 .75 2.4 6.2
YSC102AK 1 380 3 5.1/2.8 3450 12.1/6.6 64/39 1 1 7.5 2.5 7.7
YSC120A3 2 208-230 3 5.1/3.9 3450 18.6/14.7 128/91 1 1 .75 4.0 9.4
10 YSC120A4 2 460 3 5.1/3.9 3450 9.5/7.4 63/46 1 1 .75 2.8 6.8
YSC120AW 2 575 3 5.1/3.9 3450 7.8/5.8 49/37 1 1 .75 2.4 6.2
YSC120AK 1 380 3 5.1/3.9 3450 11.5/9.0 64/54 1 1 .75 2.5 7.7
82 RT-PRC006-EN
Electrical
Data (High Efficiency)
Table ED-6 — Electrical Characteristics — Compressor Motor And Condenser Motor — High Efficiency
Compressor Motor Condenser Fan Motors
Unit Amps1 Amps
Tons Model No. No. Volts Phase HP2 RPM RLA LRA No. Phase HP2 FLA LRA
YHC036A1 1 208-230 1 2.8 3450 16.1 88.0 1 1 .20 1.5 2.5
YHC036A3 1 208-230 3 2.8 3450 10.7 77.0 1 1 .20 1.5 2.5
3 YHC036A4 1 460 3 2.8 3450 5.8 39.0 1 1 .20 0.6 1.3
YHC036AW 1 575 3 2.8 3450 4.4 31.0 1 1 .20 0.5 1.2
YHC048A1 1 208-230 1 3.5 3450 19.0 109.0 1 1 .33 2.0 6.6
YHC048A3 1 208-230 3 3.5 3450 12.5 88.0 1 1 .33 2.0 6.6
4 YHC048A4 1 460 3 3.5 3450 6.5 44.0 1 1 .33 1.2 2.5
YHC048AW 1 575 3 3.5 3450 4.9 34.0 1 1 .33 0.7 1.5
YHC060A1 1 208-230 1 4.5 3450 25.0 169.0 1 1 .33 2.0 6.6
YHC060A3 1 208-230 3 4.5 3450 17.4 124.0 1 1 .33 2.0 6.6
5 YHC060A4 1 460 3 4.5 3450 7.8 59.6 1 1 .33 1.2 2.5
YHC060AW 1 575 3 4.5 3450 6.2 49.4 1 1 .33 0.9 1.5
YHC072A3 1 208-230 3 5.7 3450 20.7 156 1 1 .70 3.85 9.30
6 YHC072A4 1 460 3 5.7 3450 10 75 1 1 .70 2.50 5.80
YHC072AW 1 575 3 5.7 3450 8.2 54 1 1 .70 1.54 3.60
YHC092A3 2 208-230 3 3.5/3.3 3450 12.4/12.4 88/88 1 1 .70 3.85 9.30
7½ YHC092A4 2 460 3 3.5/3.3 3450 6.4/5.8 44/44 1 1 .70 2.50 5.80
YHC092AW 2 575 3 3.5/3.3 3450 4.8/4.8 34/34 1 1 .70 1.54 3.60
YHC102A3 2 208-230 3 3.9/3.5 3450 14.7/12.4 91/88 1 1 .75 4.0 9.4
8½ YHC102A4 2 460 3 3.9/3.5 3450 7.1/6.4 50/44 1 1 .75 2.8 6.8
YHC102AW 2 575 3 3.9/3.5 3450 5.4/4.8 37/34 1 1 .75 2.4 6.2
YHC120A3 2 208-230 3 4.8/3.5 3450 17.3/12.4 124/88 1 1 .75 4.0 9.4
10 YHC120A4 2 460 3 4.8/3.5 3450 9.0/6.4 59.6/44 1 1 .75 2.8 6.8
YHC120AW 2 575 3 4.8/3.5 3450 7.1/4.8 49.4/34 1 1 .75 2.4 6.2
Notes:
1. Amp draw for each motor; multiply value by numbers of motors to determine total amps.
2. HP for each compressor.
RT-PRC006-EN 83
Electrical
Data
84 RT-PRC006-EN
Jobsite
Connections
ROOFTOP Thermostats
UNIT A— 4 Wires, 24-volts
RT-PRC006-EN 85
Dimensional
Data (3 - 5 Tons)
1775
1775
86 RT-PRC006-EN
Dimensional
Data (3 - 5 Tons)
RT-PRC006-EN 87
Dimensional
Data (3 - 5 Tons)
88 RT-PRC006-EN
Dimensional
Data (6 - 10 Tons)
RT-PRC006-EN 89
Dimensional
Data (6 - 10 Tons)
90 RT-PRC006-EN
Dimensional
Data (6 - 10 Tons)
857
857
RT-PRC006-EN 91
Dimensional (3 - 5 Tons) Options/
Data Accessories
92 RT-PRC006-EN
Dimensional (6 -10 Tons) Options/
Data Accessories
RT-PRC006-EN 93
Weights
Table W-1 — Maximum Unit And Corner Weights (Lbs) And Center Of Gravity Dimensions (In.)
Unit Maximum Weights (Lbs)2 Corner Weights (Lbs)1 Center of Gravity (In.)
Tons Model No. Shipping Net A B C D Length Width
YSC036A 572 480 151 124 96 109 32 19
3
YHC036A 589 497 158 128 101 110 32 19
YSC048A 597 505 159 130 108 109 33 19
4
YHC048A 631 539 166 133 114 126 32 20
YSC060A 614 522 169 134 105 114 32 18
5
YHC060A 666 574 179 140 119 136 32 20
YSC072A 878 735 249 193 132 161 39 21
6
YHC072A 915 772 249 198 141 184 39 22
YSC090A 963 820 273 208 146 193 38 22
7½ YSC092A 965 822 277 222 147 175 40 21
YHC092A 1066 923 306 243 165 210 39 22
YSC102A 1042 899 297 243 165 194 40 21
8½
YHC102A 1100 957 310 252 175 220 40 22
YSC120A 1063 958 317 261 177 202 41 21
10
YHC120A 1203 1060 342 277 197 245 40 22
NOTES:
1. Corner weights are given for information only.
2. Weights are approximate.
94 RT-PRC006-EN
Mechanical
Specifications
RT-PRC006-EN 95
Mechanical
Specifications
96 RT-PRC006-EN
Mechanical
Specifications
Through the Base Electrical with Circuit Reference or Comparative Enthalpy Control Options
Breaker Reference or Comparative Enthalpy
This option is a factory-installed thermal option shall be available when a factory- Trane Communication Interface
magnetic, molded case, HACR Circuit installed Downflow Economizer is This factory or field-installed option shall
Breaker with provisions for through the ordered.This option is available for micro be provided to interface microprocessor
base electrical connections.The circuit controlled units. controlled units with theTrane Integrated
breaker will be installed in a water tight ComfortTM systems.
High Pressure Cutout
enclosure in the unit with access through This factory-installed option is offered for LonTalk® Communication Interface
a swinging door. Factory wiring will be units that do not have High Pressure This factory or field-installed option shall
provided from the switch to the unit high cutout as standard. All 3-phase models be provided to allow the unit to
voltage terminal block.The circuit breaker with scroll compressors include High communicate as a Tracer™LCI-R device
will provide overcurrent protection, be Pressure Cutout as standard. or directly with generic LonTalk Network
sized per NEC and UL guidelines, and be Building Automation System Controls.
agency recognized by UL/CSA. Hinged Access Doors
Sheet metal hinges are available factory- Zone Sensor
Powered or Unpowered Convenience installed on the Filter/Evaporator Access Field-installed, this accessory shall be
Outlet Door, Indoor Fan/Heat Exchanger Door, provided to interface with the Micro
This factory-installed option is a GFCI, and the Compressor/Control Access equipped units and shall be available in
120v/15amp, 2 plug, convenience outlet, Door. either manual, automatic programmable
either powered or unpowered. When the with night setback, with system
convenience outlet is powered, a service Supply and/or Return Air Smoke malfunction lights or remote sensor
receptacle disconnect will be available. Detector options.
The convenience outlet is powered from With this option installed, if smoke is
the line side of the disconnect or circuit detected, all unit operation will be shut Thermostats
breaker, and therefore will not be down. Reset will be manual at the unit. Two stage heating and cooling operation
affected by the position of the disconnect Return Air Smoke Detectors require or one stage heating and cooling shall be
or circuit breaker.This option can only be minimum allowable airflow when used available, for field installation, in either
ordered when theThrough the Base with certain models. See the Installation, manual or automatic changeover.
Electrical with either the Disconnect Operation, and Maintenance (IOM) Automatic programmable electronic with
Switch, or Circuit Breaker, option is manual for the models affected and the night set back shall also be available.
ordered. minimum allowable airflow required.This Novar Unit Controls
option is available for micro controlled Optional Novar rooftop unit controls shall
Phase Monitor units.
Phase monitor shall provide 100% be factory installed and tested. The
protection for motors and compressors Black Epoxy Coated Condenser Coil Novar electronic thermostat module will
against problems caused by phase loss, The coil provides corrosion protection to interface to the unit microprocesser and
phase imbalance, and phase reversal. condenser coils for seacoast application. will control the unit to the desired stage of
Phase monitor is equipped with an LED The protection is a factory applied cooling or heating.
that provides an ON or FAULT indicator. thermoset vinyl coating, bonded to Novar Return Air Sensor
normal aluminum fin stock.The uniform This option, when used in conjunction
Through the Base Gas Piping thickness of the bonded vinyl layer
The unit shall include a standard though with Novar Controls, will contain a factory
exhibits excellent corrosion protection in provided and wired zone temperature
the base gas provision. This factory- salt spray tests performed in accordance
installed option shall have all piping sensor located in the return air stream.
with ASTM B117.
necessary including, black steel, manual Enthalpy Control
gas shut-off valve, elbows, and union.The Dehumidification Option Replaces the dry bulb control with a wet
manual shut-off valve shall include a 1/8" The dehumidification (hot gas reheat) bulb changeover controller which has a
NPT pressure tap.This assembly will option shall be a factory-installed option fully adjustable setpoint. Enthalpy control
require minor field labor to install. that provides increased dehumidification. offers a higher level of comfort control,
The option shall consist of a hot-gas along with energy savings potential, than
Fan Failure/Clogged Filter Switches reheat coil located on the leaving air side
These factory or field-installed options the standard dry bulb control. This is due
of the evaporator coil prepiped and to the additional wet bulb sensing
allow for individual fan failure and dirty circuited.
filter indication in microprocessor capability.This option shall be available
controlled units.The fan failure switch will The option shall be equipped with for microprocessor controlled units. It can
disable all unit functions and “flash” the crankcase heater(s), low pressure be field-installed or factory-installed with
Service LED on the zone sensor.The dirty switch(es), Frostat™, and a thermostatic the factory-installed economizer.
filter switch will light the Service LED on expansion valve(s) (TXV) as standard.
the zone sensor and will allow continued
unit operation.
RT-PRC006-EN 97
Mechanical
Specifications
98 RT-PRC006-EN
RT-PRC006-EN 99
*High Efficiency Units only