Wind Load On Structures
Wind Load On Structures
The structure illustrated in Figure below is to be located in the center of Adama city on flat and
horizontal area with which its site surrounded by buildings of similar height. It is an apartment
building with internal wall partitions. Wind from the east and west is transmitted from clad faces
to the north and south masonry walls.
Solution:
𝑉𝑏 is the basic wind velocity defined as a function of wind direction and time of year at 10𝑚
above ground of terrain category II and shall be calculated from expression:
The fundamental value of the basic wind velocity 𝑉𝑏,0 is the characteristic 10 minutes
mean wind velocity irrespective of wind direction and time of year at 10𝑚 above ground
level in open country terrain with low vegetation such as grass and isolated obstacles with
separations of at least 20 obstacle heights (terrain category II). The value of the basic
wind velocity 𝑉𝑏,0 may be given in the National Annex. The recommended value
is 𝑉𝑏,0 = 22𝑚⁄𝑠𝑒𝑐 .
The value of the directional factor 𝐶𝑑𝑖𝑟 for various wind directions may be found in the
National Annex. The recommended value is 1.0.
The value of the season factor 𝐶𝑠𝑒𝑎𝑠𝑜𝑛 may be given in the National Annex. The
recommended value is 1.0.
1
𝑞𝑏 = 2 ∗ 𝜌 ∗ 𝑉𝑏2
Where 𝜌 is the air density which depends on the altitude, temperature and barometric pressure to
be expected in the region during wind storms. The values for 𝜌 may be given in the National
Annex. The recommended value is 𝜌 = 1.25𝑘𝑔⁄𝑚3 .
1 1
⇒ 𝑞𝑏 = 2 ∗ 𝜌 ∗ 𝑉𝑏2 == 2 ∗ 1.25𝑘𝑔⁄𝑚3 ∗ (22𝑚⁄𝑠𝑒𝑐 )2 = 302.5𝑁⁄𝑚2 = 0. 3025𝑘𝑁⁄𝑚2
Step 3: Determination of peak velocity pressure 𝑞𝑝 (𝑧) (refer ES EN 1991-1-4:2015 section 4.5)
𝑞𝑝 depends on the wind climate, the terrain roughness and orography and the reference height.
1
𝑞𝑝 (𝑧) = [1 + 7 ∗ 𝑙𝑣 (𝑧)] ∗ 2 ∗ 𝜌 ∗ 𝑉𝑚2 (𝑧)
The reference height 𝒁𝒆 for walls of rectangular plan buildings (zone D windward) depends on
the aspect ratio ℎ/𝑏 and are always the upper heights of the different parts of the walls.
A building whose height 𝒉 is greater than 𝒃 but less than 𝟐𝒃 may be considered to be two parts
comprising: a lower part extending upwards from the ground by a height equal to 𝑏 (𝒁𝒆𝟏 = 𝒃 =
𝟏𝟐𝒎) and an upper part consisting of the remainder (𝒁𝒆𝟐 = 𝒉 − 𝒃 = 𝟐𝟎 − 𝟏𝟐 = 𝟖𝒎).
Figure: Reference height 𝒁𝒆 depending on ℎ and 𝑏 and corresponding velocity pressure profile
(Source: Adopted from ES EN 1991-1-4:2015)
Note: With the reference height calculated as the distance from the ground to the top of the part.
The rules for the velocity pressure distribution for leeward wall (zone E) and side walls (zones
A, B, C) may be given in the National Annex or be defined for the individual project.
The recommended procedure is to take the reference height as the height of the building (𝒁𝒆 =
𝒉).
The reference height 𝒛𝒊 for the internal pressures should be equal to the reference height 𝒛𝒆 for
the external pressures on the faces which contribute by their openings to the creation of the
internal pressure.
𝑘𝑙
𝑙𝑣 (𝑧) = 𝐶 𝑓𝑜𝑟 𝑧𝑚𝑖𝑛 ≤ 𝑧 ≤ 𝑧𝑚𝑎𝑥
0 (𝑧)∗𝑙𝑛(𝑧⁄𝑧0 )
𝑘𝑙
𝑙𝑣 (𝑧) = 𝑙𝑣 (𝑧𝑚𝑖𝑛 ) = 𝐶 (𝑧 )∗𝑙𝑛(𝑧
𝑓𝑜𝑟 𝑧 ≤ 𝑧𝑚𝑖𝑛
0 𝑚𝑖𝑛 𝑚𝑖𝑛 ⁄𝑧0 )
In this example, the building is located on flat and horizontal terrain. For flat terrain where
orographic factor 𝐶0 (𝑧) = 1.0. The building site is surrounded by buildings of similar height.
The height of building 𝑧 is 20𝑚. Area in which at least 15% of the surface is covered with
buildings and their average height exceeds 15𝑚, the terrain category is terrain category IV.
Where:
𝑘𝑙 is the turbulence factor. The value of 𝑘𝑙 may be given in the National Annex. The
recommended value is 𝑘𝑙 = 1.0.
𝑧0 is the roughness length = 1.0𝑚 for terrain category IV given in Table 4.1 of ES EN 1991-1-
4:2015
𝒛𝒎𝒊𝒏 is the minimum height = 10𝑚 for terrain category IV given in Table 4.1 of ES EN 1991-1-
4:2015
𝑘𝑙 1.0
∴ 𝑙𝑣 (𝑧 = 12𝑚) = 𝐶 (𝑧)∗𝑙𝑛(𝑧 ⁄𝑧0 )
= 1.0∗𝑙𝑛(12⁄1) = 0.40243
0
𝑘𝑙 1.0
∴ 𝑙𝑣 (𝑧 = 20𝑚) = 𝐶 = 1.0∗𝑙𝑛(20⁄1) = 0.3338
0 (𝑧)∗𝑙𝑛(𝑧⁄𝑧0 )
The mean wind velocity 𝑉𝑚 (𝑧) at a height z above the terrain depends on the terrain roughness
and orography and on the basic wind velocity 𝑉𝑏 and should be determined using expression:
Where:
The terrain roughness factor 𝒄𝒓 (𝒛) accounts for the variability of the mean wind velocity at the
site of the structure due to the height above ground level and the ground roughness of the
terrain upwind of the structure in the wind direction considered.
𝑧
𝑐𝑟 (𝑧) = 𝑘𝑟 ∗ 𝑙𝑛 (𝑧 ) 𝑓𝑜𝑟 𝑧𝑚𝑖𝑛 ≤ 𝑧 ≤ 𝑧𝑚𝑎𝑥
0
𝑧𝑚𝑖𝑛
𝑐𝑟 (𝑧) = 𝑐𝑟 (𝑧𝑚𝑖𝑛 ) = 𝑘𝑟 ∗ 𝑙𝑛 ( ) 𝑓𝑜𝑟 𝑧 ≤ 𝑧𝑚𝑖𝑛
𝑧0
Where 𝒌𝒓 the terrain factor depending on the roughness length is 𝑧0 calculated using
0.07
𝑧0 1.0 0.07
𝑘𝑟 = 0.19 ∗ (𝑧 ) = 0.19 ∗ (0.05) = 0.23433
0,𝐼𝐼
𝑧 12
∴ 𝑐𝑟 (𝑧 = 12𝑚) = 𝑘𝑟 ∗ 𝑙𝑛 (𝑧 ) = 0.23433 ∗ 𝑙𝑛 (1.0) = 0.5823
0
𝑧 20
𝑐𝑟 (𝑧 = 20𝑚) = 𝑘𝑟 ∗ 𝑙𝑛 (𝑧 ) = 0.23433 ∗ 𝑙𝑛 (1.0) = 0.702
0
1 1
⇒ 𝑞𝑝 (𝑧 = 12𝑚) = [1 + 7 ∗ 𝑙𝑣 (𝑧 = 12𝑚)] ∗ 2 ∗ 𝜌 ∗ 𝑉𝑚2 (𝑧 = 12𝑚) = [1 + 7 ∗ 0.40243] ∗ 2 ∗
1 1
⇒ 𝑞𝑝 (𝑧 = 20𝑚) = [1 + 7 ∗ 𝑙𝑣 (𝑧 = 20𝑚)] ∗ 2 ∗ 𝜌 ∗ 𝑉𝑚2 (𝑧 = 20𝑚) = [1 + 7 ∗ 0.3338] ∗ 2 ∗
𝑞𝑝 (𝑧) 0.5
𝐶𝑒 (𝑧) is the exposure factor given by: 𝐶𝑒 (𝑧) = = 0.3025 = 1.653
𝑞𝑏
Or For flat terrain where orographic factor 𝐶0 (𝑧) = 1.0 the exposure factor is given by:
2
𝑧
𝐶𝑒 (𝑧) = (𝑘𝑟 ∗ 𝑙𝑛 (𝑧 )) [1 + 7 ∗ 𝑙𝑣 (𝑧)] = (0.702)2 [1 + 7 ∗ 0.3338] = 1.6443
0
Although the exposure factor 𝐶𝑒 (𝑧) is given in the graphical form as a function of height above
terrain and a function of terrain category.
Figure: Illustrations of the exposure factor 𝐶𝑒 (𝑧) for 𝐶0 = 1.0, 𝑘𝑙 = 1.0 (Source: Adopted from
ES EN 1991-1-4:2015)
Step 4: Determination of external pressure coefficient 𝐶𝑝𝑒 for vertical walls as per ES EN 1991-
1-4:2015 section 7.2.2
The external pressure coefficients 𝑪𝒑𝒆 for buildings and parts of buildings depend on the size of
the loaded area 𝐴 which is the area of the structure that produces the wind action in the section to
be calculated. The external pressure coefficients are given for the various zones (zone A, B, C, D
and E) of the vertical walls of a rectangular building for loaded areas 𝐴 of 1𝑚2 and 10𝑚2 for the
appropriate building configurations as 𝑐𝑝𝑒,1 for local coefficients and 𝑐𝑝𝑒,10 for overall
coefficients respectively.
For 1𝑚2 < 𝐴 < 10𝑚2 ; 𝑐𝑝𝑒 = 𝑐𝑝𝑒,1 − (𝑐𝑝𝑒,1 − 𝑐𝑝𝑒,10 ) 𝑙𝑜𝑔10 𝐴
𝑏 = 12𝑚
𝑒 = 𝐿𝑒𝑠𝑠𝑒𝑟 𝑜𝑓 { ∴ 𝒆 = 𝟏𝟐𝒎 and 𝑑 = 10𝑚 → 𝑒 = 12𝑚 ≥ 𝑑 = 10𝑚
2ℎ = 2 ∗ 20 = 40𝑚
Zones Width 𝑏(𝑚) Height ℎ(𝑚) Area (𝑚2 ) ℎ ⁄𝑑 𝐶𝑝𝑒 from Table 7.1
A 𝑒⁄5 = 12⁄5 = 2.4 20 48 20⁄10 = 2 𝐶𝑝𝑒 = 𝐶𝑝𝑒,10 = −1.2
B 𝑑 − 𝑒⁄5 = 10 − 2.4 = 7.6 20 152 20⁄10 = 2 𝐶𝑝𝑒 = 𝐶𝑝𝑒,10 = −0.8
D 12 20 240 20⁄10 = 2 𝐶𝑝𝑒 = 𝐶𝑝𝑒,10 = +0.8
E 12 20 240 20⁄10 = 2 𝐶𝑝𝑒 = 𝐶𝑝𝑒,10 = −0.55
Table 7.1: Recommended values of external pressure coefficients for vertical walls of
rectangular plan buildings (Source: Adopted from ES EN 1991-1-4:2015)
Internal pressure arises due to opening such as windows, doors and vents in the cladding. The
calculation of the internal pressures 𝑪𝒑𝒊 in ES EN 1991-1-4 depends on the fact whether a
building has dominant faces (i.e. non-uniformly distributed openings) or not (i.e. uniformly
distributed openings). A face of a building should be regarded as dominant when the area of
openings at that face is at least twice the area of openings and leakages in the remaining faces of
the building considered. Within this example it is not possible to estimate the permeability and
opening ratio of the building. Where it is not possible to estimate µ for a particular case, then 𝑪𝒑𝒊
should be taken as the more onerous of +𝟎. 𝟐 and − 𝟎. 𝟑. In this case 𝑪𝒑𝒊 is unfavorable when
𝑪𝒑𝒊 is taken to +𝟎. 𝟐.
Based on this, we should have to consider the worst condition for each walls. Example, for
windward wall, the external wind load is pressure and the internal wind load should be suction to
obtain the largest value. For leeward, left and right walls, the external wind load is suction and
the internal wind load should be pressure to obtain the largest value.
A positive wind load stands for pressure whereas a negative wind load indicates suction on the
surface. This definition applies for the external wind action as well as for the internal wind
action.
The wind pressure acting on the external surfaces 𝑾𝒆 should be obtained from expression:
𝑊𝑒 = 𝑞𝑝 (𝑧𝑒 ) ∗ 𝐶𝑝𝑒
Where: 𝑞𝑝 (𝑧𝑒 ) is the peak velocity pressure (see ES EN 1991-1-4:2015 section 4.5)
𝑧𝑒 is the reference height for the external pressure given in ES EN 1991-1-4:2015 section 7
𝐶𝑝𝑒 is the pressure coefficient for the external pressure (see ES EN 1991-1-4:2015 section 7).
Maximum external pressure on Zone D occurs on the upper part. Assume mean height of
openings equal to mean height of this part, 𝑧𝑖 = 20𝑚.
The net wind force 𝑭𝒘 acting on a structure or a structural component may be determined
directly by using expression:
𝐹𝑤 = 𝐶𝑠 𝐶𝑑 𝑞𝑝 (𝑧)[𝐶𝑝𝑒 + 𝐶𝑝𝑖 ] ∗ 𝐴𝑟𝑒𝑓
Lower part Upper part Lower part Upper part Lower part Upper part
A 48 0.5 0.5 −1.4 −0.70 −0.70 −33.60 −33.60
The building shown in figure is to be built in a sloped terrain in Adama around Ali Birra square.
The details of the terrain and the position of the building are shown in the figure. The building is
meant for an industrial purpose inside of which has no partition walls. Six windows of 2.5𝑚 ∗
2.75𝑚 size are provided in each of the longer sides. Two windows of 2.0𝑚 ∗ 2.75𝑚 size and
one door of 2.5𝑚 ∗ 3𝑚 are provided in each of the shorter sides of the building.
Calculate the wind load acting on the middle and edge truss in the roof truss assembly. The
trusses are spanning in the short direction of the building at 3𝑚 centers. The shape of the roof
truss is also shown in the figure.
1.6
tan 𝛼 =
6.0
1.6
𝛼 = 𝑡𝑎𝑛−1 ( ) = 15°
6.0
Solution:
𝑉𝑏 is the basic wind velocity defined as a function of wind direction and time of year at 10𝑚
above ground of terrain category II and shall be calculated from expression:
The value of the basic wind velocity 𝑉𝑏,0 may be given in the National Annex. The
recommended value is 𝑉𝑏,0 = 22𝑚⁄𝑠𝑒𝑐 .
The value of the directional factor 𝐶𝑑𝑖𝑟 for various wind directions may be found in the
National Annex. The recommended value is 1.0.
The value of the season factor 𝐶𝑠𝑒𝑎𝑠𝑜𝑛 may be given in the National Annex. The
recommended value is 1.0.
1
𝑞𝑏 = 2 ∗ 𝜌 ∗ 𝑉𝑏2
Where 𝜌 is the air density which depends on the altitude, temperature and barometric pressure to
be expected in the region during wind storms. The values for 𝜌 may be given in the National
Annex. The recommended value is 𝜌 = 1.25𝑘𝑔⁄𝑚3 .
1 1
⇒ 𝑞𝑏 = 2 ∗ 𝜌 ∗ 𝑉𝑏2 == 2 ∗ 1.25𝑘𝑔⁄𝑚3 ∗ (22𝑚⁄𝑠𝑒𝑐 )2 = 302.5𝑁⁄𝑚2 = 0. 3025𝑘𝑁⁄𝑚2
Step 3: Determination of peak velocity pressure 𝑞𝑝 (𝑧) (refer ES EN 1991-1-4:2015 section 4.5)
𝑞𝑝 depends on the wind climate, the terrain roughness and orography and the reference height.
1
𝑞𝑝 (𝑧) = [1 + 7 ∗ 𝑙𝑣 (𝑧)] ∗ 2 ∗ 𝜌 ∗ 𝑉𝑚2 (𝑧)
𝑘𝑙
𝑙𝑣 (𝑧) = 𝐶 𝑓𝑜𝑟 𝑧𝑚𝑖𝑛 ≤ 𝑧 ≤ 𝑧𝑚𝑎𝑥
0 (𝑧)∗𝑙𝑛(𝑧⁄𝑧0 )
𝑘𝑙
𝑙𝑣 (𝑧) = 𝑙𝑣 (𝑧𝑚𝑖𝑛 ) = 𝐶 (𝑧 )∗𝑙𝑛(𝑧
𝑓𝑜𝑟 𝑧 ≤ 𝑧𝑚𝑖𝑛
0 𝑚𝑖𝑛 𝑚𝑖𝑛 ⁄𝑧0 )
In our problem, Adama can be considered as a sub urban area and therefore the terrain category
falls as category III.
Where:
𝑘𝑙 is the turbulence factor. The value of 𝑘𝑙 may be given in the National Annex. The
recommended value is 𝑘𝑙 = 1.0.
𝑧0 is the roughness length = 0.3𝑚 for terrain category III given in Table 4.1 of ES EN 1991-1-
4:2015
𝒛𝒎𝒊𝒏 is the minimum height = 5.0𝑚 for terrain category IV given in Table 4.1 of ES EN 1991-
1-4:2015
Table A.2: Values of the effective length 𝐿𝑒 (Source: Adopted from ES EN 1991-1-4:2015)
𝐿𝑒 = 𝐿𝑢 𝐿𝑒 = 𝐻 ⁄0.3
𝐿𝑒 is the effective length of the upwind slope (Table A.2) (𝐹𝑜𝑟 0.05 < 𝜙 < 0.3; 𝐿𝑒 = 𝐿𝑢 =
500𝑚)
𝐿𝑢 is the actual length of the upwind slope in the wind direction = 500𝑚
𝑥 is the horizontal distance of the site from the top of the crest = 200𝑚
𝑧 is the vertical distance from the ground level of the site = 6.1𝑚
𝑥⁄ = −200⁄ 𝑧 6.1⁄
𝐿𝑢 500 = −0.4 𝑎𝑛𝑑 ⁄𝐿𝑒 = 500 = 0.0122 ≈ 0.1
𝑘𝑙 1.0
∴ 𝑙𝑣 (𝑧 = 6.1𝑚) = 𝐶 = 1.036∗𝑙𝑛(6.1⁄0.3) = 0.32
0 (𝑧)∗𝑙𝑛(𝑧⁄𝑧0 )
The mean wind velocity 𝑉𝑚 (𝑧) at a height z above the terrain depends on the terrain roughness
and orography and on the basic wind velocity 𝑉𝑏 and should be determined using expression:
Where:
𝑧
𝑐𝑟 (𝑧) = 𝑘𝑟 ∗ 𝑙𝑛 (𝑧 ) 𝑓𝑜𝑟 𝑧𝑚𝑖𝑛 ≤ 𝑧 ≤ 𝑧𝑚𝑎𝑥
0
𝑧𝑚𝑖𝑛
𝑐𝑟 (𝑧) = 𝑐𝑟 (𝑧𝑚𝑖𝑛 ) = 𝑘𝑟 ∗ 𝑙𝑛 ( ) 𝑓𝑜𝑟 𝑧 ≤ 𝑧𝑚𝑖𝑛
𝑧0
Where 𝒌𝒓 the terrain factor depending on the roughness length is 𝑧0 calculated using
0.07
𝑧0 0.3 0.07
𝑘𝑟 = 0.19 ∗ (𝑧 ) = 0.19 ∗ (0.05) = 0.2154
0,𝐼𝐼
𝑧 6.1
∴ 𝑐𝑟 (𝑧 = 6.1𝑚) = 𝑘𝑟 ∗ 𝑙𝑛 (𝑧 ) = 0.2154 ∗ 𝑙𝑛 (0.3) = 0.6488
0
1
⇒ 𝑞𝑝 (𝑧 = 6.1𝑚) = [1 + 7 ∗ 𝑙𝑣 (𝑧 = 6.1𝑚)] ∗ 2 ∗ 𝜌 ∗ 𝑉𝑚2 (𝑧 = 6.1𝑚)
1
= [1 + 7 ∗ 0.32] ∗ ∗ 1.25𝑘𝑔⁄𝑚3 ∗ (14.79𝑚 ⁄𝑠𝑒𝑐 )2 = 442.8𝑁⁄𝑚2 ≈ 0.443𝑘𝑁⁄𝑚2
2
Step 4: Determination of external pressure coefficient 𝐶𝑝𝑒 for duopitch roof as per ES EN 1991-
1-4:2015 section 7.2.5
The external pressure coefficients 𝑪𝒑𝒆 for buildings and parts of buildings depend on the size of
the loaded area 𝐴 which is the area of the structure that produces the wind action in the section to
be calculated. The external pressure coefficients are given for the various zones (zone F, G, H, I
and J) of the vertical walls of a rectangular building for loaded areas 𝐴 of 1𝑚2 and 10𝑚2 for the
appropriate building configurations as 𝑐𝑝𝑒,1 for local coefficients and 𝑐𝑝𝑒,10 for overall
coefficients respectively.
For 1𝑚2 < 𝐴 < 10𝑚2 ; 𝑐𝑝𝑒 = 𝑐𝑝𝑒,1 − (𝑐𝑝𝑒,1 − 𝑐𝑝𝑒,10 ) 𝑙𝑜𝑔10 𝐴
𝑏 = 30𝑚
𝑒 = 𝐿𝑒𝑠𝑠𝑒𝑟 𝑜𝑓 {
2ℎ = 2 ∗ 6.1 = 12.2𝑚
∴ 𝒆 = 𝟏𝟐. 𝟐𝒎
𝑏 = 12𝑚
𝑒 = 𝐿𝑒𝑠𝑠𝑒𝑟 𝑜𝑓 {
2ℎ = 2 ∗ 6.1 = 12.2𝑚
∴ 𝒆 = 𝟏𝟐𝒎
Zones Width 𝑏(𝑚) Height ℎ(𝑚) Area (𝑚2 ) 𝐶𝑝𝑒 from Table 7.4a
G 𝑒⁄10 = 12.2⁄10 = 1.22 𝑏 − 2𝑒⁄4 = 30 − 2.44 = 23.9 29.158 𝐶𝑝𝑒 = 𝐶𝑝𝑒,10 = −0.8
For 1𝑚2 < 𝐴 = 3.721𝑚2 < 10𝑚2 ; 𝑐𝑝𝑒 = 𝑐𝑝𝑒,1 − (𝑐𝑝𝑒,1 − 𝑐𝑝𝑒,10 ) 𝑙𝑜𝑔10 𝐴
𝑐𝑝𝑒 = 𝑐𝑝𝑒,1 − (𝑐𝑝𝑒,1 − 𝑐𝑝𝑒,10 ) 𝑙𝑜𝑔10 𝐴 = −2.0 − [−2.0 − (−0.9)] 𝑙𝑜𝑔10 3.721 = −1.3723
External pressure coefficient 𝐶𝑝𝑒 of duopitch roof for wind direction 𝜃 = 90°
Zones Width 𝑏(𝑚) Height ℎ(𝑚) Area (𝑚2 ) 𝐶𝑝𝑒 from Table 7.4b
For zone F;
For 1𝑚2 < 𝐴 = 3.6𝑚2 < 10𝑚2 ; 𝑐𝑝𝑒 = 𝑐𝑝𝑒,1 − (𝑐𝑝𝑒,1 − 𝑐𝑝𝑒,10 ) 𝑙𝑜𝑔10 𝐴
𝑐𝑝𝑒 = 𝑐𝑝𝑒,1 − (𝑐𝑝𝑒,1 − 𝑐𝑝𝑒,10 ) 𝑙𝑜𝑔10 𝐴 = −2.0 − [−2.0 − (−1.3)] 𝑙𝑜𝑔10 3.6 = −1.61
Internal pressure arises due to opening such as windows, doors and vents in the cladding. The
calculation of the internal pressures 𝑪𝒑𝒊 in ES EN 1991-1-4 depends on the fact whether a
building has dominant faces (i.e. non-uniformly distributed openings) or not (i.e. uniformly
distributed openings). A face of a building should be regarded as dominant when the area of
openings at that face is at least twice the area of openings and leakages in the remaining faces of
the building considered.
∑ 𝑎𝑟𝑒𝑎 𝑜𝑓 𝑜𝑝𝑒𝑛𝑖𝑛𝑔𝑠 𝑎𝑡 𝑤𝑖𝑛𝑑 𝑝𝑎𝑟𝑎𝑙𝑙𝑒𝑙 𝑠𝑖𝑑𝑒𝑠 = 4 ∗ 2.0𝑚 ∗ 2.75𝑚 + 2 ∗ 2.5𝑚 ∗ 3.0𝑚 = 37𝑚𝑚2
∑ 𝑎𝑟𝑒𝑎 𝑜𝑓 𝑜𝑝𝑒𝑛𝑖𝑛𝑔𝑠 𝑤ℎ𝑒𝑟𝑒 𝐶𝑝𝑒 𝑖𝑠 𝑛𝑒𝑔𝑎𝑡𝑖𝑣𝑒 (𝑎𝑡 𝑙𝑒𝑒𝑤𝑎𝑟𝑑 𝑎𝑛𝑑 𝑤𝑖𝑛𝑑 𝑝𝑎𝑟𝑎𝑙𝑙𝑒𝑙 𝑠𝑖𝑑𝑒𝑠) 𝑜𝑟 0.0
= 41.25 + 37 = 78.25𝑚𝑚2
∑ 𝑎𝑟𝑒𝑎 𝑜𝑓 𝑎𝑙𝑙 𝑜𝑝𝑒𝑛𝑖𝑛𝑔𝑠(𝑎𝑡 𝑤𝑖𝑛𝑑𝑤𝑎𝑟𝑑, 𝑙𝑒𝑒𝑤𝑎𝑟𝑑 𝑎𝑛𝑑 𝑤𝑖𝑛𝑑 𝑝𝑎𝑟𝑎𝑙𝑙𝑒𝑙 𝑠𝑖𝑑𝑒𝑠) = 2 ∗ 41.25 +
37 = 119.5𝑚𝑚2
78.25 ℎ 6.1
µ = 119.5 = 0.6548 𝑎𝑛𝑑 = = 0.50833
𝑑 12
1.0 0.1
∑ 𝑎𝑟𝑒𝑎 𝑜𝑓 𝑜𝑝𝑒𝑛𝑖𝑛𝑔𝑠 𝑤ℎ𝑒𝑟𝑒 𝐶𝑝𝑒 𝑖𝑠 𝑛𝑒𝑔𝑎𝑡𝑖𝑣𝑒 (𝑎𝑡 𝑙𝑒𝑒𝑤𝑎𝑟𝑑 𝑎𝑛𝑑 𝑤𝑖𝑛𝑑 𝑝𝑎𝑟𝑎𝑙𝑙𝑒𝑙 𝑠𝑖𝑑𝑒𝑠) 𝑜𝑟 0.0
∑ 𝑎𝑟𝑒𝑎 𝑜𝑓 𝑎𝑙𝑙 𝑜𝑝𝑒𝑛𝑖𝑛𝑔𝑠(𝑎𝑡 𝑤𝑖𝑛𝑑𝑤𝑎𝑟𝑑, 𝑙𝑒𝑒𝑤𝑎𝑟𝑑 𝑎𝑛𝑑 𝑤𝑖𝑛𝑑 𝑝𝑎𝑟𝑎𝑙𝑙𝑒𝑙 𝑠𝑖𝑑𝑒𝑠) = 2 ∗ 18.5 +
82.5 = 119.5𝑚𝑚2
101 ℎ 6.1
µ = 119.5 = 0.8452 𝑎𝑛𝑑 = = 0.50833
𝑑 12
0.25 −0.23
0.50833 𝑪𝒑𝒊
1.0 −0.35
Zones F G H I J
Area (𝑚2 ) 3.721 29.158 143.4 143.4 36.6
𝐶𝑝𝑒 (−𝑣𝑒) −1.3723 −0.8 −0.3 −0.4 −1.0
𝐶𝑝𝑒 (+𝑣𝑒) +0.2 +0.2 +0.2 +0.0 +0.0
𝐶𝑝𝑖 +0.146 +0.146 +0.146 +0.146 +0.146
𝐶𝑝𝑒 (+𝑣𝑒) + 𝐶𝑝𝑖 +0.346 +0.346 +0.346 +0.146 +0.146
𝐶𝑝𝑒 (−𝑣𝑒) + 𝐶𝑝𝑖 −1.2263 −0.654 −0.154 −0.254 −0.854
Summary the 𝐶𝑝𝑒 and 𝐶𝑝𝑖 values for wind direction 𝜽 = 𝟗𝟎°
Zones F G H I
The net wind force 𝑭𝒘 acting on a structure or a structural component may be determined
directly by using expression:
𝐹𝑤 = 𝐶𝑠 𝐶𝑑 𝑞𝑝 (𝑧)[𝐶𝑝𝑒 + 𝐶𝑝𝑖 ] ∗ 𝐴𝑟𝑒𝑓
Thus, the analysis result indicates that the wind direction 𝜽 = 𝟗𝟎° gives the critical values.
The net wind pressure acts on the roof covering which is supported by purlins. Purlins are
supported at each and every joint of the principal rafter of the truss. Load transfer path is:
Wind Pressure → Roof Covering → Purlins → Truss.
1.6𝑚
6.0𝑚
Wind Load on structures Page 29
Department of Civil Engineering Structural Design
6.21𝑚
Center-to-center spacing between purlins = = 1.5525𝑚
4
Load transferred to the purlin from different zones the roof covering
Figure: Wind pressure distribution on EGA sheet for zone F and G of roof