26 05 29 71-A Iec (16071)
26 05 29 71-A Iec (16071)
26 05 29 71-A Iec (16071)
1. General
A. Furnish and install vibration control devices, materials, and related items. Perform
all work as shown on the Drawings and as specified herein to provide complete
vibration isolation systems in proper working order.
A. Provide vibration isolators of the appropriate sizes and proper loading to meet the
specified requirements.
B. Supply and install any incidental materials needed to meet the requirements stated
herein, even if not expressly specified or shown on the Drawings, without claim for
additional payment.
1.6. Submittals
B. Submission of samples may be requested for each type of vibration isolation device.
2. Products
3.1. Application
A. Unit Substations:
1) Unit substations within the fab building construction and office penthouse shall
be mounted on unit DNP isolators. The entire unit substation assembly,
consisting of transformers and switchgear, shall be mounted on unit DNP
isolators.
2) Electrical connections to unit substations shall be made using single wire
armoured (SWA) cable.
3.2. Installation
B. Isolation Mounts:
1) All mounts shall be aligned squarely above or below mounting points for the
supported equipment.
2) If a housekeeping pad is provided, the isolators shall bear on the housekeeping
pad and the isolator base plate shall rest entirely on the pad.
A. Should any electrical equipment cause excessive noise or vibration, the Subcontractor
shall be responsible for remedial work required to reduce noise and vibration levels.
Excessive is defined as exceeding the manufacturer’s specifications for the unit in
question.
End of Section