100% found this document useful (1 vote)
78 views6 pages

ZMG310

Uploaded by

stupard1989
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
78 views6 pages

ZMG310

Uploaded by

stupard1989
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

Electricity Meters IEC/MID

INDUSTRIAL+COMMERCIAL
Landis+Gyr Dialog

ZMG310AR/CR
TECHNICAL DATA

IEC-specific data

Current
Base Current Ib 5 – 10 – 20 – 40 A

Maximal Current Imax


metrological 40 – 60 – 80 – 100 – 125 A
thermal 125 A
with aluminium wires 80 A

Short Circuit ≤ 10 ms 10’000 A

Measurement Accuracy
Accuracy ZMG310xR
active energy to IEC 62053-21 class 1
reactive energy to IEC 62053-23 class 2

Measurement Behaviour
Starting Current ZMG310xR
according to IEC 0.4% Ib
typical 0.3% Ib
The startup of the meter is controlled by the
starting power and not by the starting current.

Starting Power in M-Circuit single phase


nominal voltage x starting current

General
MID-specific data
Voltage Current (for Class B)
Nominal Voltage Un ZMG310xR Minimum Current Imin 0.25, 0.5, 0.75, 1.0 A
3 x 220/380 to 240/415 V
Transitional Current Itr 0.5, 1.0, 1.5, 2.0 A
Voltage Range 70% to 125% Un
Maximum Current Imax 125 A
with aluminium wires 80 A
Frequency
Nominal Frequency fn 50 or 60 Hz Measurement Accuracy
tolerance ± 2% ZMG300xR; to EN 50470-3 Class B

Measurement Behaviour
Starting Current Ist 0.02, 0.04, 0.06, 0.08 A

H 71 0200 0376 f en – ZMG310AR/CR – Technical Data © Landis+Gyr AG


1/6
General Fast Transient Surge Test to IEC 61000-4-5
current and voltage circuits 4 kV
Operating Behaviour auxiliary circuits > 40 V 1 kV
Voltage Failure (Power Down)
bridging time according to IEC 0.5 s Insulation Strength
data storage after another 0.2 s Insulation Strength 4 kV @ 50 Hz during 1 min
switch off after approx. 1 s
Impulse Voltage 1.2/50µs to IEC 62052-11
Voltage Restoration (Power Up) current and voltage circuits 10 kV
function standby 3 phases after 4 s auxiliary circuits > 40 V 6 kV
function standby 1 phase after 5 s
detection of Protection Class according to IEC 60050-131 2
energy direction + phase voltage after 4 to 5 s
Calendar Clock
Power Consumption Accuracy < 5 ppm
Power Consumption per Phase in Voltage Circuit
phase voltage 240 V Calendar Type
active power (typical) 0.8 W Gregorian or Persian (Jalaali)
apparent power (typical) 5 VA
Backup Time (Power Reserve)
Power Consumption per Phase in Current Circuit with supercap > 21 days
phase current 10 A loading time for max. backup time 300 h
apparent power (typical) 0.03 VA with battery 1
(calendar clock, display, readout) 10 years
battery type UM3-R6-AA
Environmental Influences
with battery 2 (calendar clock only) 10 years
Temperature Range to IEC 62052-11
battery type CR2032
operation –40 °C to +70 °C
storage –40 °C to +85 °C
Display
Temperature Coefficent Characteristics
range –25 °C to +70 °C type LCD liquid crystal display
average value (typical) ± 0.012% per K digit size in value field 9 mm
at cosϕ=1 (from 0.05 Ib to Imax) ± 0.02% per K number of digits in value field up to 8
at cosϕ=0.5 (from 0.1 Ib to Imax) ± 0.03% per K digit size in index field 6 mm
number of digits in index field up to 7
Impermeability according to IEC 60529 IP53
Inputs and Outputs
Electromagnetic Compatibility Control Inputs
Electrostatic Discharges to IEC 61000-4-2 control voltage Us 100 to 240 V AC
contact discharge 15 kV input current < 2 mA ohmic at 230 V AC

Electromagnetic RF Fields to IEC 61000-4-3 Output Contacts


80 MHz – 2 GHz 10 and 30 V/m type solid state relay
voltage 12 to 240 V AC/DC
Radio Interference Suppression max. current 100 mA
according to IEC/CISPR 22 class B max. switching frequency (pulse length 20 ms) 25 Hz

Fast Transient Burst Test to IEC 61000-4-4


Optical Test Output Active and Reactive Energy
current and voltage circuits not under load 4 kV
type red LED
current and voltage circuits under load
number 2
according to IEC 62053-21/22/23 2 kV
meter constant selectable
auxiliary circuits > 40 V 1 kV

© Landis+Gyr AG H 71 0200 0376 f en – ZMG310AR/CR – Technical Data


2/6
Communication Interfaces Weight and Dimensions
Optical Interface according to IEC 62056-21 Weight approx. 1.5 kg
type serial, asynchronous, half duplex
max. bit rate 19’200 bps External Dimensions
protocols IEC 62056-21 and dlms width 177 mm
height (with short terminal cover) 244 mm
RS232-Interface to DIN 61393 / DIN 66259 height (with standard terminal cover) 281.5 mm
type serial, asymmetric, depth 75 mm
asynchronous, bidirectional
operating mode intelligent or transparent Suspension Triangle
nominal voltage ±9 V DC height (suspension eyelet open) 206 mm
maximum voltage ±15 V DC height (suspension eyelet covered) 190 mm
minimum voltage ±5 V DC width 150 mm
max. bit rate 38’400 bps
protocols IEC 62056-21 and dlms Terminal Cover
max. conductor lenght depending on short no free space
environment and connecting cable 30 m standard 40 mm free space
insulation resistance long 60 mm free space
to meter 4 kVAC / 50 Hz, 1 min ZxB-type 80 mm 80 mm free space
creep distance ≥ 6.2 mm ZxB-type 110 mm 110 mm free space
ADP1 adapter
RS485 interface according to ISO-8482
RCR/FTY adapter
type serial, symmetrical, half duplex
nominal voltage range –7 to +12 V DC
Connections
binary 1 state difference voltage < –0.2 V
binary 0 state difference voltage > 0.2 V Phase Connections
max. bit rate 38’400 bps type cage type terminals
max. number of slaves 32 cross section 9 x 9 mm
protocols IEC 62056-21 and dlms min conductor cross section 2.5 mm2
max. conductor lenght depending on max. cross section cable 35 mm2 (up to 125 A)
environment and connecting cable ≤ 1000 m max. cross section strand 25 mm2 (up to 80 A)
insulation resistance screw head Pozidrive Combi No. 2
to meter 4 kVAC / 50 Hz, 1 min screw dimension M6 x 14
creep distance ≥ 6.2 mm screw head diameter ≤ 6.6 mm
tightening torque 3 to 5 Nm
CS Interface to IEC 62056-21 / DIN 66258
type serial, bidirectional, current interface RS232 Interface
nominal voltage without load 24 V DC type designation .02/.42
max. voltage without load 30 V DC type RJ 12
binary 1 state 10–30 mA pin assignment
binary 0 state ≤ 2 mA
max. bit rate 9600 bps 1 6 1 CTS
protocols IEC 62056-21 and dlms 2 TxD
insulation resistance 3 GND
to meter 4 kVAC / 50 Hz, 1 min 4 DTR
5 RxD
creep distance ≥ 6.2 mm
6 DSR

H 71 0200 0376 f en – ZMG310AR/CR – Technical Data © Landis+Gyr AG


3/6
RS485 Interface
type designation .03/.43
type RJ 12
pin assignment

1 6 1 c (ground)
2 a (data a)
3 b (data b)
4 b
5 a
6 c

CS Interface
type designation .40/.42/.43
type screw type terminals

+ -

Other Connections
type screw type terminals
max. current of voltage outputs 1A
max. voltage of control inputs 300 V

Material
Housing
The meter housing is made of polycarbonate which
is partly glass-fibre reinforced.

© Landis+Gyr AG H 71 0200 0376 f en – ZMG310AR/CR – Technical Data


4/6
Meter Dimensions (Standard Terminal Cover)
6.2 75

206

281.5
190
26
40
150
177 75

Terminal Dimensions

9 5
9

19.75 14.5 14.5 14.5 14.5 14.5 14.5 12.6 13.5

Terminal Layout

Communication
Control inputs and interfaces RS232/485
output contacts with/without CS

Voltage outputs

U1 U2 U3 N

optical
separation
of phases

L1 L2 L3 N

Phase connections

H 71 0200 0376 f en – ZMG310AR/CR – Technical Data © Landis+Gyr AG


5/6
Type Designation ZMG 3 10 CR 4.26 0 b .43

Network Type
ZFG 3-phase 3 wire network (F-connection)
ZMG 3-phase 4 wire network (M-connection)

Connection Type
3 Direct connection
4 Transformer connection
Accuracy Class
10 Class 1 (IEC), B (MID) ZMG310/410..
05 Class 0.5 (IEC), C (MID) ZMG405..
Measured Quantities
AR Active energy meter
CR Combi meter for active and reactive energy
Tariff Functions; Control Inputs/Output Contacts
1.xx Energy rates, externally controlled
2.xx Energy rates, internally controlled with time switch
3.xx Energy and demand rates, externally controlled
4.xx Energy and demand rates, internally controlled with time switch

x.00 no inputs/output contacts


x.26 2 control inputs/6 output contacts
x.44 4 control inputs/4 output contacts
Special Functions
0 none
Further Functions
0 none
3 with software events
4 with hard- and software events
7 with load profile
a with load profile and software events
b with load profile and hard- and software events
Interfaces
00 none
02 with RS232
03 with RS485
40 with CS
42 with CS and RS232
43 with CS and RS485

Data subject to change without notice.

Landis+Gyr AG
Feldstrasse 1
CH-6301 Zug
Switzerland
Phone: +41 41 935 60 00
www.landisgyr.com

© Landis+Gyr AG H 71 0200 0376 f en – ZMG310AR/CR – Technical Data