LEC OM032xx
LEC OM032xx
LEC-OM03203
Product name
Model / Series
LEC-GEN1
Contents
1. Safety Instructions................................................................. 4
2. Outlines of Product................................................................ 7
2. 1 Features................................................................................................................ 7
2. 2 How to Order ...................................................................................................... 7
2. 3 Structure of the product ................................................................................ 8
2. 4 Procedure (How to start the actuator) ................................................... 9
(1) Checking the content of the package ................................................ 9
(2) Mounting the unit ....................................................................................... 9
(3) Initial setting of the connect controller ............................................. 9
(4) Setting the unit........................................................................................... 9
(5) Unit wiring / Connection ......................................................................... 9
(6) Power supply ............................................................................................. 10
(7) Operation .................................................................................................... 10
3. Specifications .............................................................................11
3. 1 Specifications.................................................................................................... 11
3. 2 Details of parts................................................................................................. 13
3.3 Outside dimension diagram............................................................................ 14
(1) Screw mount type (LEC-GEN1) ...................................................... 14
(2) DIN rail mount type (LEC-GEN1D)................................................. 14
3.4 How to install...................................................................................................... 15
(1) How to install............................................................................................. 15
(2) Installation location ................................................................................. 15
-1-
6.1 Power supply connector................................................................................. 23
6.2 Power line ............................................................................................................ 23
6. 3 Wiring of the shutdown circuit .................................................................... 24
【Shutdown circuit Example】 ...................................................................... 26
10. Mode.............................................................................................33
10. 1 Outline............................................................................................................... 33
10. 2 Step data input mode .................................................................................. 33
10. 3 Numerical data input mode ........................................................................ 33
10. 4 Data writing mode ......................................................................................... 35
-3-
LEC Series/ Gateway unit
1. Safety Instructions
These safety instructions are intended to prevent hazardous situations and/or equipment damage. These
instructions are categorized into three groups, "Caution", "Warning" and "Danger" depending on the level of
hazard and damage, and the degree of emergency. They are all important notes for safety and must be
followed in addition to International Standards (ISO/IEC), Japan Industrial Standards (JIS)*1) and
other safety regulations*2).
*1) ISO 4414: Pneumatic fluid power -- General rules relating to systems
ISO 4413: Hydraulic fluid power -- General rules relating to systems
IEC 60204-1: Safety of machinery -- Electrical equipment of machines (Part 1: General requirements)
ISO 10218-1992: Manipulating industrial robots -- Safety
JIS B 8370: Pneumatic fluid power - General rules relating to systems
JIS B 8361: Hydraulic fluid power - General rules relating to systems
JIS B 9960-1: Safety of machinery - Electrical equipments of machines (Part 1: General requirements)
JIS B 8433-1993: Manipulating industrial robots - Safety, etc/
*2) Labor Safety and Sanitation Law, etc.
Caution indicates a hazard with a low level of risk which, if not avoided, could result in minor or
Caution moderate injury.
Warning indicates a hazard with a medium level of risk which, if not avoided, could result in death or
Warning serious injury.
Danger Danger indicates a hazard with a high level of risk which, if not avoided, will result in death or
serious injury.
Warning
(1) The compatibility of the product is the responsibility of the person who designs the
equipment or decides its specifications.
Since the product specified here is used under various operating conditions, its compatibility with
specific equipment must be decided by the person who designs the equipment or decides its
specifications based on necessary analysis and test results.
The expected performance and safety assurance of the equipment will be the responsibility of the
person who has determined its compatibility with the product.
This person should also continuously review all specifications of the product referring to its latest
catalog information, with a view to giving due consideration to any possibility of equipment failure
when configuring the equipment.
(2) Only personnel with appropriate training should operate machinery and equipment.
The product specified here may become unsafe if handled incorrectly.
The assembly, operation and maintenance of machines or equipment must be performed by an
operator who is appropriately trained and experienced.
(3) Do not service or attempt to remove product and machinery/equipment until safety is
confirmed.
1. The inspection and maintenance of machinery/equipment should only be performed after measures
to prevent dropping of driven objects or run-away of machinery/equipment have been confirmed.
2. When the product is to be removed, confirm that the safety measures as mentioned above are
implemented and the power from any appropriate source is cut, and read and understand the
specific product precautions of all relevant products carefully.
3.Before machinery/equipment is restarted, take measures to prevent unexpected operation and malfunction.
-4-
Warning
(4) Contact SMC beforehand and take special consideration of safety measures if the product is
to be used in any of the following conditions.
1. Conditions and environments outside of the given specifications, or use outdoors or in a location
exposed to direct sunlight.
2. Installation on equipment in conjunction with atomic energy, railways, air navigation, space,
shipping, vehicles, military, medical treatment, combustion and recreation, or equipment in contact
with food and beverages, emergency stop circuits, clutch and brake circuits in press applications,
safety equipment or other applications unsuitable for the standard specifications described in the
product catalog.
3. An application which could have negative effects on people, property, or animals requiring special
safety analysis.
Use in an interlock circuit, which requires the provision of double interlock for possible failure by using
a mechanical protective function, and periodical checks to confirm proper operation. Check the
product regularly in order to confirm normal operation.
-5-
LEC-G Series/Gateway unit
Safety Instructions
Caution
The product is provided for use in manufacturing industries.
The product herein described is basically provided for peaceful use in manufacturing industries.
If considering using the product in other industries, consult SMC beforehand and exchange
specifications or a contract if necessary.
If anything is unclear, contact your nearest sales branch.
(2) For any failure or damage reported within the warranty period which is clearly our
responsibility, a replacement product or necessary parts will be provided.
This limited warranty applies only to SMC product independently, and not to any other damage
incurred due to the failure of the product.
(3) Prior to using SMC products, please read and understand the warranty terms and disclaimers
noted in the specified catalog for the particular products.
[Compliance Requirements]
When the product is exported, strictly follow the laws required by the Ministry of Economy, Trade and
Industry (Foreign Exchange and Foreign Trade Control Law).
-6-
2. Outlines of Product
2. 1 Features
The gateway unit (GW unit, hereafter) is the unit to connect the electric actuator controller (LEC
series) to Ethernet IP. One unit can control up to 12 same type of controllers.
Caution
When setting up the device or when failure occurs, please refer to the operation manual of the
controller, the actuator, and the teaching box as well as this operation manual.
* Keep this operation manual accessible so it can be referred to when necessary.
2. 2 How to Order
How to order is shown below.
L E C -G E N 1 □
DIN rail
Electric equipment
Controller Nil Not mountable.
D Mountable
Applicable
EN1 EtherNetIP
Unit types
G Gateway unit
-7-
2. 3 Structure of the product
PLC
Teaching box
LEC-T1-3□G□
HUB
EtherNet/IP
●Controller setting Kit
Gateway unit LEC-W2
LEC-GEN1□
Motor controller
LEC Series ・
Electric actuator
LE Series
-8-
2. 4 Procedure (How to start the actuator)
Install, wire, set and operate the gateway unit referring to the procedure below when the product is
used for the first time.
(*)
These items are included if you ordered by the part number for a set of controller and actuator.
Connector
-9-
(6) Power supply
Supply power 24V DC.
Caution
Supply power first to the controller (LEC), then to the gateway unit.
If power is supplied to the gateway unit and then to the controller (LEC), reset the data link after
supplying power to the controller (LEC).
(Refer to 11.4 Gateway unit control flag for the details of data link reset.)
If the condition is normal, LED on the front of the gateway unit turns on as the table below when power
is supplied.
If LED [ALM] on the front panel of the gateway unit shows red, an alarm conditions has occured.
(7) Operation
Refer to section 11. Memory map for the assignment of the memory. Read the operation manual of
LEC series as well.
- 10 -
3. Specifications
3. 1 Specifications
Basic specifications of the product.
Item Specifications
Rated voltage 24 VDC±10%
Current consumption 200mA or less (When teaching box is not connected)
300mA or less (When teaching box is connected)
Applicable controller Electric actuator controller (LEC series)
Product to be connected Max. 12pcs.
When conformity to UL is required, the electric actuator and controller should be used with a UL1310
Class 2 power supply.
【EtherNet type】
Item Specifications
Fieldbus EtherNet (IEEEE802.3)
Media 100BASE-TX
Communication speed 10/100Mbps (Automatically selected)
Maximum length of cable 100m (328ft)
Fieldbus protocol EtherNet/IP TM
Occupied area (inputs /outputs) 2048 point(256byte)/2048 point(256byte)
IP address setting DHCP server. Arbitrary address
Device information Vendor ID: 7
Device type: 0 (Generic device)
Product code: 154
Product name: LEC-GEN1
- 11 -
【Controller IF communication spec.】
Item Specifications
Serial RS485 (Modbus protocol compliant)
communication
Communication 115.2k or 230.4kbps (Select 115.2kbps when the teaching box is connected)
speed
Cable length The cable for the teaching box (3m) and the electric actuator controller (5m x
12)
makes 63m of cable length. This is the maximum cable length.
・・・
3m
5m 5m 5m 5m
【Conditions of environment】
Item Specifications
Applicable ambient temperature 0~40℃(No freezing)
Applicable ambient humidity 90%RH or less (No condensation)
Atmosphere No corrosive gas, flammable gas, oil mist, or particles.
Storage temperature -10~60℃(No freezing)
Storage humidity 90%RH or less (No condensation)
Vibration 4.9m/s2 (0.5G) or less
Enclosure IP20
200g (screw mount type)
Mass
220g (DIN rail mount type)
- 12 -
3. 2 Details of parts
Details of parts of the gateway unit
(2)
(3)
①
(4)
(5)
(6)
(7)
- 13 -
3.3 Outside dimension diagram
The outside view of this product is as shown in the diagram below:
(1) Screw mount type (LEC-GEN1)
- 14 -
3.4 How to install
(1) How to install
There are two types of controllers; screw mount type and DIN rail mount type.
The followings are the descriptions on how to install each type:
[1] Screw mount type (LEC-GEN1) [2] DIN rail mount type (LEC-GEN1D)
(Installation with two M4 screws) (Installation with the DIN rail)
DIN rail is locked.
Screw direction
DIN rail
Screw direction
Caution
Install the gateway unit on a flat surface. Excessive pressure applied to the housing will damage the
gateway unit.
- 15 -
4. Initial Setting
4. 1 Gateway unit Communication speed switch (B RATE)
The transmission rate of motor controller LEC are set. Table below shows the setting of switches.
Communication speed of
B RATE
controller IF
F
: Not used
9
8 230.4 kbps
7
: Not used
1
0 115.2 kbps
Caution1: Set the controller IF communication speed at 115.2kbps to use the teaching box (LEC-T1-□).
Caution2: Turn off the power supply in order to change the switch setting
- 16 -
4. 3 Setting of controller (LEC)
Initial parameter setting is necessary for the controller (LEC) which is connected to the gateway unit.
Set the following by directly connecting the teaching box (LEC-T1-□) or the setting software to the
controller (LEC) before connecting the gateway unit.
Check the operation manual of the controller (LEC) and the teaching box (LEC-T1-□) when setting
the controller (LEC).
4. 3. 1 ID setting
ID setting is necessary when connecting two or more controllers (LEC) to the gateway unit.
Assign ID to each controller (LEC) in serial number so that the numbers do not overlap. The setting
range of ID is between 1 to 12.
[Example of ID change procedure using the ACT Controller Setting software (LEC-W2)]
Start the setting software in Normal mode.
Open the parameter window.
(1) Set the controller ID.
(Letters are changed to blue)
- 17 -
(2) Set the controller so that the communication speed can be changed.
Change "Parameter protect" setting so that "Communication speed" parameter can be changed.
View the parameters of the controller.
Select "Basic" Tab - Item "Parameter protect" to "3: Common + Extend + Step"
The changed data is sent by clicking the download button, and the parameter protect set value text
changes from blue to black.
(3) Select the "Motor" Tab of the parameter window to change item "Comm speed" to "115200" for when
using Teaching box or "230400" for when using ACT Controller software.
The changed data is sent by clicking the download button, and "Communication speed" set value is
changed from blue to black.
- 18 -
(4) Change item "Parameter protect" using “Basic” tab of the display of (2) to "1: Common + Step data"
and click download.
(5) Close the ACT Controller software (LEC-W2) and turn OFF the controller (LEC) power supply. The
changed communication speed will be valid from the next time the controller (LEC) is turned on.
Caution
The communication speed of the gateway unit and the controller (LEC) must match.
If the communication speed does not match, the gateway unit and the controller (LEC) cannot
communicate.
Set the controller IF communication speed to 115,2kbps when using the teaching box (LEC-T1-)
The defaults setting of communication speed in the setting software (LEC-W2) is 38.6kbps.
After changing the communication speed, set the ACT Controller software (LEC-W2)
communication speed to 115.2kbps for Teaching box or 230.4kbps for the ACT controller software.
Do not change any parameters other than "ID setting"/"Communication speed setting".
Otherwise, malfunction can result.
Change "ID setting" / "Communication speed setting" to use the controller (LEC) stand-alone.
- 19 -
4. 4 Setting of EtherNet/IP using RSLogix5000TM
・Comnection Parameters
Instance Size
Input 100 256
Output 150 256
Configuration 1 0
- 20 -
5. External connection
5. 1 CN4: Power supply connector
Connect the power supply. The gateway unit and the controller (LEC) should have the common 0V line.
Gateway
Unit
Power supply
(24 VDC)
Power supply line
CN4
Gateway
Unit
PLC
EtherNet line.
CN3 HUB
CN1
Terminating Resistor
(120Ω 1/4W)
- 21 -
* Refer to section 7. CN1: Controller IF communication connector (CONT)
Caution
Do not pull out the cable between the gateway unit and the cable, or cut off the power
supply to the controller (LEC). Communication is interrupted.
Gateway unit
(2) Connecting PC
Gateway unit
Conversion unit モニタ
現在 位 置 120.3 mm 動 作中
USB cable
設定 位置 速度
1 テ スト 100 500
2 テ スト 200 1000
(A-miniB type)
3 テ スト 50 200
CN2CN2
Communication cable
PC
Caution
Do not start the setting software during data link.
Otherwise, communication error (data link error) is generated with the gateway unit.
- 22 -
6. CN4: Power supply connector
6.1 Power supply connector
Specifications of the communication connector in accessory
3 C 24V Power supply + terminal Power supply terminal of the Gateway unit
Caution
(1) 0V line of the gateway unit and the motor controller (LEC) have to be common.
(2) When conformity to UL is required, the electric actuator and controller should be used with a
UL1310 Class 2 power supply.
Peeled wire
length
8mm
Caution
Do not connect multiple wires to one terminal.
- 23 -
Caution
(1) The earthling should be the dedicated grounding point. It should be a functional ground with less
than 100 Ω resistance.
(2) The ground point should be near this gateway unit to make the wire length shorter.
Switch to change
the communication
(CN2SW)
Teaching Shutdown
RY
box circuit
CN4
CN2
EMG +
EMG-
24V
Internal
circuit
0V
Gateway unit
- 24 -
Caution
Turn on the communication switch (CN2SW) before install / removal of the teaching box to
/ from the gateway unit.
If EMG+ and EMG- terminals are connected to the controller (LEC) or a shutdown circuit and the
communication switch is turned off when the teaching box is not connected, connected controller
(LEC) or the shutdown circuit receives stop signal (Open between EMG+ and EMG-) and operation
stops
- 25 -
【Shutdown circuit Example】
Shutdown circuit with gateway Check the circuit referring the controller (LEC) operation manual.
Stop
Switch
Gateway
EMG + Surge suppressor
Ry
Unit
EMG -
Caution
When the stop signal is input, the controller (LEC) is stopped with max deceleration speed, and servo
motor is turned off.
- 26 -
7. CN1: Controller IF communication connector (CONT)
7. 1 Connection
One unit can control up to 12 pcs. of controllers (LEC).
The example of link connection which consists of telecommunication cable LEC-CG 1-1 and cable
LEC-CG 2-1 between branches is shown below.
3 LEC-CG2-□
b) M12 4pin b) M12 4pin
male connector male connector
2 LEC-CGD 2 LEC-CGD 4
5
c) M12 4pin
female connector
1 LEC-CG1-□
b) M12 4pin b) M12 4pin
male connector male connector
1 LEC-CG1-□ 1 LEC-CG1-□
a) RJ45 male connector with a shield(8P) a) RJ45 male connector with a shield(8P)
1 Communication cable cable LEC-CG1-□ Cable to connect the gateway unit CN1 and the branch
L 0.5m
1 1m
2 Branch connector LEC-CGD The junction cable to connect the gateway and the controller.
K 0.3m
L 0.5m
1 1m
Recommended connector
120Ω 1/4W
5 RJ-45 connector dust cover Dust adhere when the RJ-45 connector is not connected with the
dust.
- 27 -
Recommended connector
No Description Part number
a) RJ45 male connector with a shield(8P) TM21P-88P [HIROSE ELECTRIC CO., LTD.]
b) M12 4pinmale connector HR24-8DJ4PE550A(73) [HIROSE ELECTRIC CO., LTD.]
XS2G-D4** [OMRON Corporation]
c) M12 4pin female connector HR24-8DP4S300(73) [HIROSE ELECTRIC CO., LTD.]
XS2C-D4** [OMRON Corporation]
- 28 -
7. 2 Wiring diagram
For you reference, the example of wiring of the gateway unit CN1 is shown below.
The communication line from the gateway unit CN1 branches to each controller (LEC) by the branch
connector. It is recommended to connect the terminating resistor (120Ω 1/4W) to the branch connector
at the terminal.
When connecting the cable, the shield of the cable becomes same potential as 0V of the controller
power supply.
When using it, do not contact it to conductive parts of switchboard, other instruments, wiring, etc.
N.C. 2 1 1 1 1
SD+ 3 2 2 2 2
SD- 4 3 3 3 3
N.C. 5 4 4 4 4
N.C. 6
N.C. 7 1 2 3 4 1 2 3 4
N.C. 8
Shield
- 29 -
8. CN2: TB/PC connector
8. 1 How to use
This connector is for setting the controller (LEC) which is connected to the gateway unit by the teaching
box or the set software.
When the communication switch (CN2SW) is turned off, the communication from EtherNet/IP to the
controller is disconnected, and the signal line of CN2 and CN1 is connected. From now on, the setting of
each controller is possible.
The following is the setting procedure of the controller (LEC) when the teaching box or PC setting
software us connected to the gateway unit.
Caution
Do not start the setting software during data link (CN2SW turn on).
Otherwise, communication error (data link error) is generated with the gateway unit.
Use the teaching box and the setting software after finishing startup process of the gateway
unit (After ALM lamp green blinks). (CN2SW turn off etc.)
The gateway unit communicates with controller (LEC) as startup processing immediately
after turning on of the power supply.
At this time, if the teaching box or the setting software communicate to controller (LEC),
communication error is generated.
- 30 -
9. LED display
9. 1 LED display
- 31 -
9. 2 Controller IF communication status and LED display
- 32 -
10. Mode
10. 1 Outline
This unit has 3 types of operation mode. These modes can be switched by mode change[OUT: 250.0,
250.1] Current mode can be checked by mode return[IN: 250.0, 250.1]
Refer to “11.4(1) Return of the mode” for “Return of the Mode”.
Please confirm the setting method of "Mode change" and "Mode return" by "Gateway control flag" and
"Gateway unit state flag".
- 33 -
●Operation commanded by numerical data input mode (ID=1)
1 3 6
Operation command [OUT: 2]
2
Data (Position, speed) [OUT: 3~19])
4
Sending [IN: 19.1]
Operation
5
- 34 -
10. 4 Data writing mode
This is the mode that the step data of the controller(LEC) can be changed through the gateway unit.
After changing it, the changed step data is reflected by commanding to drive the changed step data.
And the same functions as step data input mode are available in this mode.
The driving and the return to origin etc. are commanded by using the memory which corresponds to
parallel IO of LEC controller.
Refer to the manual of controller (LEC) for detail of the function and the operation of parallel IO.
- 35 -
11. Memory map
11.1 Memory assignment
2 3
3 2 Current
4 +/-2147483647 0.01mm
position
4 1
5 0
6 H Current Numerical data
2 0 to 65500 mm/s
7 L speed input
8 H Current
2 0 to 300 %
9 L Force
10 3
11 2 Target
4 +/-2147483647 0.01mm
12 1 position
13 0
・Please refer the operation manual of the step motor controller (LECP6) and the servo motor controller
(LECA6) to check the detail of each signal.
- 36 -
Corresp
Bit/Byte Model/ Corresponding
onding Address Data name Value range Unit
No. Size mode
ID
14 - Alarm 0 to 255 -
18
Controller IF status flag(ID=1) All modes
19
ID2 20 to 39 Same as ID1
ID3 40 to 59 Same as ID1
ID4 60 to 79 Same as ID1
ID5 80 to 99 Same as ID1
ID6 100 to 119 Same as ID1
ID7 120 to 139 Same as ID1
ID8 140 to 159 Same as ID1
ID9 160 to 179 Same as ID1
ID10 180 to 199 Same as ID1
ID11 200 to 219 Same as ID1
ID12 220 to 239 Same as ID1
- 240 to 249 Unused
- 250 to 253 Gateway unit status flag All modes
- 254,255 Unused
- 37 -
● Higher level device --> Gateway unit [OUT]
Corresp
Bit/Byte Model/ Corresponding
onding Address Data name Value range Unit
No. Size mode
ID
0 IN0 bit 0,1 -
1 IN1 bit 0,1 -
2 IN2 bit 0,1 -
3 IN3 bit 0,1 -
0
4 IN4 bit 0,1 -
5 IN5 bit 0,1 -
6 - bit 0 -
7 - bit 0 -
All mode
0 HOLD bit 0,1 -
1 SVON bit 0,1 -
2 DRIVE bit 0,1 -
3 RESET bit 0,1 -
1
4 SETUP bit 0,1 -
5 - bit 0 -
6 - bit 0 -
7 - bit 0 -
ID1 0: no send Numerical data
Start flag
2 - 1 1: send - input
Step data No 0 to 63 Data writing
1: Absolute
2: Relative
3 - Operation 1 -
0: (Only data
writing mode)
4 H
Speed 2 0 to 65500 mm/s
5 L Numerical data
6 3 input
7 2
Position 4 +/-2147483647 0.01mm
8 1 Data writing
9 0
10 H
Acceleration 2 0 to 65500 mm/s2
11 L
12 H
Deceleration 2 0 to 65500 mm/s2
13 L
・Please refer the operation manual of the step motor controller (LECP6) and the servo motor controller
(LECA6) to check the detail of each signal.
- 38 -
Corresp
Bit/Byte Model/ Corresponding
onding Address Data name Value range Unit
No. Size mode
ID
14 - Pushing force 1 0 to 30 10%
15 - Trigger LV 1 0 to 30 10%
- 39 -
11.2 Controller IF flag(IN Data)
[ID=1]
bit
I_Address 7 6 5 4 3 2 1 0
- - - - - - Abnormal
18 Connect station
station
- - - - - - Sending
19 Sending
completed
Start flag
Sending
Sending completed
Sending command
bit
I_Address 7 6 5 4 3 2 1 0
Commu
250 Initial ALARM READY - - Return of the mode
nicating
251
Return of the read numerical data
252
253 Return of the final station number
- 40 -
(1) Return of the mode
Current mode is displayed
Address250 Mode name
bit1 Bit0
0 0 Step data input mode
0 1 Numerical data input mode
1 0 Data writing mode
(2) READY
1 (ON) appears when the gateway is activated.
(3) ALARM
1 (ON) appears when one or more abnormal station are present, and the alarm is generated. 0 (OFF)
appears when alarm is not generated.
(4) Initial
0 (OFF) appears during processing the initial for check the connect station. 1 (ON) appears when the
processing of the initial is completed.
(6) Return of the read numerical data (Valid only in numerical data input mode)
ON (1) appears in ID bit if numerical data can be read. OFF (0) appears when the data can not be read.
The command to read numerical data is given by [OUT: 251.]{OUT: 252.}.
bit
I_Address 7 6 5 4 3 2 1 0
251 ID8 ID7 ID6 ID5 ID4 ID3 ID2 ID1
252 - - - - ID12 ID11 ID10 ID9
- 41 -
11.4 Gateway unit control flag(OUT Data)
bit
Address 7 6 5 4 3 2 1 0
250 Stop - Restart Reset - - Mode command
251 ID8 ID7 ID6 ID5 ID4 ID3 ID2 ID1
252 - - - - ID12 ID11 ID10 ID9
253 - - - - Setting the final station number
(2) Reset
Communication to the abnormal station restart when 0 (OFF) is changed to 1 (ON). But, it is invalid
when Stop[OUT: 250.7.] is 1 (ON) or CN2SW is ON.
(3) Restart
Initial processing is executed again when 0 OFF) is changed to 1 (ON). But, it is invalid when Stop
[OUT: 250.7.] is 1 (ON) or CN2SW is ON.
(4) Stop
All communications to the connected motor controller (LEC) are stopped when 0 (OFF) is changed to 1
(ON). Communication restart by chancing to 0 (OFF) from 1 (ON).
- 42 -
12. Precautions for controlling the controller (LEC)
12. 1 Communication delay between the gateway unit unit and the controller(LEC)
There is communication delay between the gateway unit and the controller (LEC). Please refer to the
procedure below for the control procedure taking the delay into consideration
For details of each signal, please refer to the operation manual of each motor controller (LEC) to be
connected.
- 43 -
12. 2. Guideline of the Response delay between the Gateway and the Motor Control Unit
The gateway unit communicates with the motor controller (LEC) to read the controller status and
commands the controller. The time for the communication causes delay in the response.
Please take this into consideration when selecting the PLC program.
Motor controller
(LEC)
Motor controller
(LEC)
Response delay depends on the number of the connected motor controllers (LEC) and rewrite
frequency.
Ex. 1) Response time guideline when four controllers are connected in step data input mode.
4 pcs. × approx. 30ms = Approx. 120ms + α
[α:Communication time to rewrite the remote I/O and the register]
Ex. 2) Response time guideline when twelve controllers are connected in step data input mode.
12 pcs. × approx. 30ms = Approx. 360ms + α
[α:Communication time to rewrite the remote I/O and the register]
Ex. 3) Response time guideline when 12 controllers are connected in numerical data input mode (6
controllers are valid for reading numerical data).
12 pcs. × approx. 30ms + 6pcs. x approx. 30ms = Approx. 540ms + α
[α:Communication time to rewrite the remote I/O and the register]
※This response time does not include the response time of Ethernet IP and motor controller (LEC), and
processing time of PLC.
- 44 -
13. Wiring of cables/Common precautions
Warning
1. Adjusting, mounting or wiring change should never be done before shutting off the power
supply to the product.
Electrical shock, malfunction and damaged can result.
2. Never disassemble the cable. Use only specified cables.
3. Never connect or disconnect the cable or connector with power on.
Caution
1. Wire the connector securely. Do not apply any voltage to the terminals other than those
specified in the product Manual.
2. Wire the connector securely.
Check for correct connector wiring and polarity.
3. Take appropriate measures against noise.
Noise in a signal line may cause malfunction. As a countermeasure, separate high voltage and low
voltage cables, and shorten wiring lengths, etc.
4. Do not route wires and cables together with power or high voltage cables.
The product can malfunction due to interference of noise and surge voltage from power and high
voltage cables to the signal line. Route the wires of the product separately from power or high
voltage cables.
5. Take care that actuator movement does not catch cables.
6. Operate with cables secured. Avoid bending cables at sharp angles where they enter the product.
7. Avoid twisting, folding, rotating or applying an external force to the cable.
Risk of electric shock, wire break, contact failure and lost of control for the product can happen.
8. Fix the motor cable protruding from the product in place before using.
The motor and lock cables are not robotic type cables and can be damaged when moved.Therefore
do not place it in a flexible moving tube.
9. The cable connecting the actuator and controller (LEC) is superior in bending resistance, but
should not be placed into a flexible moving tube with a radius smaller than the specified
value.
( Min. 50 mm)
- 45 -
14. Electric actuators/Common precautions
14.1 Design and selection
Warning
1. Be sure to read the Operation Manual.
Handling or usage/operation other than that specified in the Operation Manual may lead to
breakage and operation failure of the product.
Any damage attributed to the use beyond the specifications is not guaranteed.
2. There is a possibility of dangerous sudden action by the product if sliding parts of machinery
are twisted due to external forces, etc.
In such cases, human injury may occur, such as by catching hands or feet in the machinery, or damage to the
machinery itself may occur. Design the machinery should be designed to avoid such dangers.
3. A protective cover is recommended to minimize the risk of personal injury.
If a driven object and moving parts of the product are in close proximity, personal injury may occur.
Design the system to avoid contact with the human body.
4. Securely tighten all stationary parts and connected parts so that they will not become loose.
When the product operates with high frequency or is installed where there is a lot of vibration,
ensure that all parts remain secure.
5. Consider a possible loss of power source.
Take measures to prevent injury and equipment damage even in the case of a power source failure.
6. Consider behavior of emergency stop of whole system.
Design the system so that human injury and/or damage to machinery and equipment will not be
caused, when it is stopped by a safety device for abnormal conditions such as a power outage or a
manual emergency stop of whole system.
7. Consider the action when operation is restarted after an emergency stop or abnormal stop of
whole system.
Design the system so that human injury or equipment damage will not occur upon restart of
operation of whole system.
8. Disassembly and modification prohibited
Do not modify or reconstruct (including additional machining) the product. An injury or failure can result.
9. Do not use stop signal,"EMG" of the controller and stop switch on the teaching box as the
emergency stop of system.
The stop signal, "EMG" of controller and the stop switch on the teaching box are for decelerating
and stopping the actuator.
Design the system with an emergency stop circuit which is applied relevant safety standard separately.
10. When using it for vertical application, it is necessary to build in a safety device.
The rod may fall due to the weight of work. The safety device should not interfere with normal
operation of the machine.
Caution
1. Operate within the limits of the maximum usable stroke.
The product will be damaged if it is used with the stroke which is over the maximum stroke. Refer to
the specifications of the product.
2. When the product repeatedly cycles with partial strokes, operate it at a full stroke at least
once a day or every 1000 strokes.
Otherwise, lubrication can run out.
- 46 -
3. Do not use the product in applications where excessive external force or impact force is
applied to it.
The product can be damaged. Each component that includes motor is made with accurate
tolerance. So even slightly deformed or miss-alignment of component may lead operation failure of
the product.
4. Refer to a common auto switch /matter (Best Pneumatics No 2) when an auto switch is built
in and used.
5. Return to origin cannot return while operating.
It cannot be done during positioning operation, pushing operation and pushing.
6. When conformity to UL is required, the electric actuator and controller should be used
with a UL1310 Class 2 power supply.
14.2 Mounting
Warning
1. Install and operate the product only after reading the Operation Manual carefully and
understanding its contents. Keep the manual in a safe place future reference.
2. Observe the tightening torque for screws.
Tighten the screws to the recommended torque for mounting the product.
3. Do not make any alterations to this product.
Alterations made to this product may lead to a loss of durability and damage to the product, which
can lead to human injury and damage to other equipment and machinery.
4. When using external guide, the guide axis should be parallel to the actuator axis.
There will be damage/excessive wear on the lead screw if the external guide is not parallel.
5. When an external guide is used, connect the moving parts of the product and the load in
such a way that there is no interference at any point within the stroke.
Do not scratch or dent the sliding parts of the product tube or piston rod etc., by striking or grasping
them with other objects. Components are manufactured to precise tolerances, so that even a slight
deformation may cause faulty operation.
6. Prevent the seizure of rotating parts.
Prevent the seizure of rotating parts (pins, etc.) by applying grease.
7. Do not use the product until you verify that the equipment can be operated properly.
After mounting or repair, connect the power supply to the product and perform appropriate functional
inspections to check it is mounted properly.
8. At the overhang mounted impeller fixation
There is a possibility that the power at the bending moment damages the actuator when moving it at
high speed.
The support metal fittings that suppress the vibration of the main body of the actuator are installed.
Lower and use speed for the state that the actuator doesn't vibrate.
9. When attaching work piece, do not apply strong impact or large moment.
If an external force over the allowable moment is applied, it may cause looseness in the guide unit,
an increase in sliding resistance or other problems.
10. Maintenance space.
Allow sufficient space for maintenance and inspection.
- 47 -
14.3 Handling
Warning
1. Do not touch the motor while in operation.
The surface temperature of the motor can increase to approx. 90oC to 100oC due to operating
conditions. Energizing alone may also cause this temperature increase. As it may cause burns, do
not touch the motor when in operation.
2. If abnormal heating, smoking or fire, etc., occurs in the product, immediately shut off the
power supply.
3. Immediately stop operation if abnormal operation noise or vibration occurs.
If abnormal operation noise or vibration occurs, the product may have been mounted incorrectly.
Unless operation of the product is stopped for inspection, the product can be seriously damaged.
4. Never touch the rotating part of the motor or moving part of the actuator while in operation.
5. When installing, adjusting, inspecting or performing maintenance on the product, controller and
related equipment, be sure to shut off the power supply to each of them. Then, lock it so that no one
other than the person working can turn the power on, or implement measures such as a safety plug.
6. In the case of the actuator that has a servo motor (24VDC), the “motor phase detection step"
is done by inputting the servo on signal just after the controller power is turned on. The
“motor phase detection step” operates the table/rod to the maximum distance of the lead
screw. (The motor rotates in the reverse direction if the table hits an obstacle such as the end
stop damper.) Take the “motor phase detection step” into consideration for the installation
and operation of this actuator.
Caution
1. Keep the controller and product combined as delivered for use.
The product is set in parameters for shipment. If it is combined with a different parameter, failure can result.
2. Check the product for the following points before operation.
a) Damage to electric driving line and signal lines
b) Looseness of the connector to each power line and signal line
c) Looseness of the actuator/cylinder and controller/driver mounting
d) Abnormal operation
e) Emergency stop of the total system
3. When more than one person is performing work, decide on the procedures, signals,
measures and resolution for abnormal conditions before beginning the work. Also,
designate a person to supervise work other than those performing work.
4. Actual speed of the product will be changed by the workload.
Before selecting a product, check the catalog for the instructions regarding selection and
specifications.
5. Do not apply a load, impact or resistance in addition to a transferred load during return to origin.
In the case of the return to origin by pushing force, additional force will cause displacement of the
origin position since it is based on detected motor torque.
6. Do not remove the name plate.
7. Operation test should be done by low speed. Start operation by predefined speed after
confirming there is no trouble.
[Earth]
Warning
1. Please give the earth of the actuator.
2. Please make it to the earth of the exclusive use. The earth construction is D seed.
(Below earth resistance 100Ω)
3. Please shorten the distance until the actuator and earth.
- 48 -
[Unpackaging]
Caution
1. Check the received product is as ordered.
If a different product is installed from the one ordered, injury or damage can result.
- 49 -
14.5 Maintenance
Warning
1. Do not disassemble or repair the product.
Fire or electric shock can result.
2. Before modifying or checking the wiring, the voltage should be checked with a tester 5
minutes after the power supply is turned off.
Electrical shock can result.
Caution
1. Maintenance should be performed according to the procedure indicated in the Operating
Manual.
Incorrect handling can cause injury, damage or malfunction of equipment and machinery.
2. Removal of product.
When equipment is serviced, first confirm that measures are in place to prevent dropping of work
pieces and run-away of equipment, etc, and then cut the power supply to the system. When
machinery is restarted, check that operation is normal with actuators in the proper positions.
[Lubrication]
Caution
1. The product has been lubricated for life at manufacturer, and does not require lubrication in
service.
Contact SMC if lubrication will be applied.
1. Do not use the lock as a safety lock or a control that requires a locking force.
The lock used for the product with a lock is designed to prevent dropping of work piece.
2. For vertical mounting, use the product with a lock.
If the product is not equipped with a lock, the product will move and drop the work piece when
the power is removed.
3. "Measures against drops” means preventing a work piece from dropping due to its
weight when the product operation is stopped and the power supply is turned off.
4. Do not apply an impact load or strong vibration while the lock is activated.
If an external impact load or strong vibration is applied to the product, the lock will lose it’s
holding force and damage to the sliding part of the lock or reduced lifetime can result. The
same situations will happen when the lock slips due to a force over the thurst of the product, as
this accelerates the wear to the lock.
5. Do not apply liquid or oil and grease to the lock or its surrounding.
When liquid or oil and grease is applied to the sliding part of the lock, its holding force will
reduce significantly.
6. Take measures against drops and check that safety is assured before mounting,
adjustment and inspection of the product.
If the lock is released with the product mounted vertically, a work piece can drop due to its weight.
- 50 -
15. Gateway unit and its peripheral devices /Specific product precautions
15.1 Design and selection
Warning
1. Be sure to apply the specified voltage.
Otherwise, a malfunction and breakage of the gateway unit may be caused.
If the applied voltage is lower than the specified, it is possible that the load cannot be moved due to
an internal voltage drop. Please check the operating voltage before use.
2. Do not operate beyond the specifications.
It may cause a fire, malfunction or actuator damage can result. Please check the specifications before
use.
3. Install an emergency stop circuit.
Please install an emergency stop outside of the enclosure so that it can stop the system operation
immediately and intercept the power supply.
4. In order to prevent danger and damage due to the breakdown and the malfunction of this
product, which may occur at a certain probability, a backup system should be established
previously by giving a multiple-layered structure or a fail-safe design to the equipment, etc.
5. If a fire or danger against the personnel is expected due to an abnormal heat generation,
ignition, smoking of the product, etc., cut off the power supply for this product and the
system immediately.
6. Use UL1310 compliant Class 2 power supply unit for direct current.
15.2 Handling
Warning
1. The inside of the gateway unit and its connector should not be touched.
It may cause an electric shock or damage to the controller.
2. Do not perform the operation or setting of this equipment with wet hands.
It may cause an electric shock.
3. Product with damage or the one lacking of any components should not be used.
It may cause an electric shock, fire, or injury.
4. Use only the specified combination between the controller and electric actuator.
It may cause damage to the controller or the actuator.
5. Be careful not to be caught or hit by the workpiece while the actuator is moving.
It may cause an injury.
6. Do not connect the power supply or power on the product before confirming the area where
the work moves is safe.
The movement of the work may cause accident.
7. Do not touch the product when it is energized and for some time after power has been
disconnected, as it is very hot.
It may lead to a burn due to the high temperature.
8. Check the voltage using a tester for more than 5 minute after power-off in case of installation,
wiring and maintenance.
There is a possibility of getting electric shock, fire and injury.
- 51 -
9. Do not use in an area where dust, powder dust, water or oil is in the air.
It will cause failure or malfunction.
10. Do not use in an area where a magnetic field is generated.
It will cause failure or malfunction.
11. Do not install in the environment of flammable gas, corrosive gas and explosive gas.
It could lead to fire, explosion and corrosion.
12. Radiant heat from strong heat supplys such as a furnace, direct sunlight, etc. should not be
applied to the product.
It will cause failure of the gateway unit or its peripheral devices.
13. Do not use the product in an environment subject to a temperature cycle.
It will cause failure of the gateway unit or its peripheral devices.
14. Do not use in a place where surges are generated.
When there are units that generate a large amount of surge around the product (e.g., solenoid type
lifters, high frequency induction furnaces, motors, etc.), this may cause deterioration or damage to
the product’s' internal circuit. Avoid supplys of surge generation and crossed lines.
15. The product is not immune to lightening strikes. Take measures against lightening strikes in
the system.
16. Do not install this product in an environment under the effect of vibrations and impacts.
It will cause failure or malfunction.
17. If this product is used with a relay or solenoid valve, they should be the surge absorbing
element built-in type.
15.3 Mounting
Warning
1. The gateway unit and its peripheral devices should be installed on a fire-proof material.
A direct installation on or near a flammable material may cause fire.
2. Do not install this product in a place subject to vibrations and impacts.
It may cause an electric shock, fire, or injury.
3. Take measure so that the operating temperature of this gateway unit and its peripheral
devices are within the range of the specifications. Also, this controller should be installed
with 50mm or larger spaces between each side of it and the other structures or components.
It may cause a malfunction of the controller and its peripheral devices and a fire.
4. Do not mount this gateway unit and its peripheral devices together with a large-sized
electromagnetic contactor or no-fuse breaker, which generates vibration, on the same panel.
Mount them on different panels, or keep the controller and its peripheral devices away from
such a vibration supply.
5. This gateway unit and its peripheral devices should be installed on a flat surface.
If the mounting surface is distorted or not flat, an unacceptable force may be added to the housing,
etc. to cause troubles.
- 52 -
15.4 Electrical wiring
1. Do not apply any excessive force to cables by repeated bending, tensioning or placing a
heavy object on the cables.
It may cause an electric shock, fire, or breaking of wire.
2. Connect wires and cables correctly.
Incorrect wiring could break he gateway unit or its peripheral devices depending on the seriousness.
3. Do not connect wires while the power is supplied.
It can break the gateway unit or its peripheral devices could be damaged to cause a malfunction.
4. Do not carry this product by holding its cables.
It may cause an injury or damage to the product.
5. Do not connect power cable or high-voltage cable in the same wiring route as the unit.
Te wires to the gateway unit or its peripheral devices can be interrupted with noise or induced surge
voltage from power lines or high-voltage lines and malfunction could be caused.
Separate the wiring of the gateway unit and its peripheral device from that of power line and high
voltage line.
6. Verify the insulation of wiring.
Insulation failure (interference with other circuit, poor insulation between terminals and etc.) could
introduce excessive voltage or current to the gateway unit or its peripheral devices and damage
them.
15.5 Power supply
Caution
1. Use a power supply that has low noise between lines and between power and ground.
In cases where noise is high, an isolation transformer should be used.
2. To prevent surges from lightning, an appropriate measure should be taken. Ground the surge
absorber for lightning separately from the grounding of the gateway unit and its peripheral
devices.
15.6. Grounding
1. Be sure to carry out grounding in order to ensure the noise tolerance of the gateway unit.
It may cause an electric shock or fire.
2. Dedicated grounding should be used.
Grounding should be to a D-class ground (Ground resistance of 100 Ω or less.)
3. Grounding should be performed near the unit as much as possible to shorten the grounding
distance.
4. In the unlikely event that malfunction is caused by the ground, it may be disconnected.
- 53 -
15.7 Maintenace
1. Perform a maintenance check periodically
Confirm wiring and screws are not loose.
Loose screws or wires may cause unintentional malfunction.
2. Conduct an appropriate functional inspection after completing the maintenance.
In case of any abnormities (in the case that the actuator does no move, etc.), stop the operation of
the system. Otherwise, an unexpected malfunction may occur and it will become impossible to
secure the safety.
3. Do not disassemble, modify or repair this gateway unit and the peripheral equipment.
4. Do not put anything conductive or flammable inside of this gateway unit.
It may cause a fire and explosion.
5. Do not conduct an insulation resistance test and withstand voltage test on this product.
6. Ensure sufficient space for maintenance activities. Provide space required for
maintenance.
Design the system that allows required space for maintenance.
7. Do not used solvents such as benzene, thinner etc. to clean the gateway unit.
They could damage the surface of the body and erase the markings on the body.
Use a soft cloth to remove stains.
For heavy stains, use a cloth soaked with diluted neutral detergent and fully squeezed, then wipe up
the stains again with a dry cloth.
- 54 -
Revision history
No.LEC-OM03201
Feb/2012 1st printing
No.LEC-OM03202
Mar/2012 Revision
No.LEC-OM03803
Apr/2012 Revision
Addition to notes about UL recognition
URL http://www.smcworld.com
Note: Specifications are subject to change without prior notice and any obligation on the part of the manufacturer.