Ymc2 Bas SC Eq Rev2.11
Ymc2 Bas SC Eq Rev2.11
Ymc2 Bas SC Eq Rev2.11
Rev 2.11
December 8, 2021
SC-EQ Software Version 4.2.0.20
BACnet
Long Name Short Name IP SI Object & N2 Metasys MODBUS MODBUS MODBUS
(BACnet Object Description) (BACnet Object Name) Notes Units Units Enum Set Instance Address Address Scale Data Type LON Profile Name LON SNVT Type
Remote Leaving Chilled Liquid Setpoint REM LEAVING CHL TEMP SP °F °C AV1 ADF 1 0001 X10 Signed nviCoolSetPt SNVT_temp_p
Remote Input Current Limit Setpoint REMOTE INPUT CURRENT SP % % AV2 ADF 2 0002 X10 Signed nviCapacityLimit SNVT_lev_percent
Remote Heating Setpoint REM HEATING SP °F °C AV3 ADF 3 0003 X10 Signed nviHeatSetPt SNVT_temp_p
AV4 ADF 4 0004 X10 Signed
Remote Run/Stop [0=Stop, 1=Run] REM RUN STOP CMD 0=Stop, 1=Run BV1 BD 1 0061 N/A Signed nviChillerEnable SNVT_switch
BV2 BD 2 0062 N/A Signed
BV3 BD 3 0063 N/A Signed
BV4 BD 4 0064 N/A Signed
Units Units None None 0=IP (English), 1=SI (Metric) MV65001 ADI 201 65001 X1 Unsigned
Leaving Chilled Liquid Temperature LEAVING CH LIQ TEMP °F °C AV5 ADF 5 0005 X10 Signed nvoLvgCHWTemp SNVT_temp_p
Entering Chilled Liquid Temperature ENTERING CH LIQ TEMP °F °C AV6 ADF 6 0006 X10 Signed nvoEntCHWTemp SNVT_temp_p
Leaving Condenser Liquid Temperature LEAVING COND WATER TEMP °F °C AV7 ADF 7 0007 X10 Signed nvoLvgCNDTemp SNVT_temp_p
Entering Condenser Liquid Temperature ENTERING COND WATER TEMP °F °C AV8 ADF 8 0008 X10 Signed nvoEntCNDTemp SNVT_temp_p
Evaporator Pressure EVAPORATOR PRESSURE PSIG kPaG AV9 ADF 9 0009 X10 Signed nvoEvapPress SNVT_press
Condenser Pressure CONDENSER PRESSURE PSIG kPaG AV10 ADF 10 0010 X10 Signed nvoCondPress SNVT_press
Discharge Temperature DISCHARGE TEMP °F °C AV11 ADF 11 0011 X10 Signed nvoDischTemp SNVT_temp_p
Enable point when Evaporator Refrigerant
Evaporator Refrigerant Temperature EVAP REFRIGERANT TEMP Temperature Sensor is Enabled °F °C AV12 ADF 12 0012 X10 Signed nvoEvapRefTemp SNVT_temp_p
VSD Phase A Output Current (RMS) VSD PHASE A OUTPUT CURRENT Amps Amps AV13 ADF 13 0013 X10 Signed nvoVSDCurrent_A SNVT_amp
VSD Phase B Output Current (RMS) VSD PHASE B OUTPUT CURRENT Amps Amps AV14 ADF 14 0014 X10 Signed nvoVSDCurrent_B SNVT_amp
VSD Phase C Output Current (RMS) VSD PHASE C OUTPUT CURRENT Amps Amps AV15 ADF 15 0015 X10 Signed nvoVSDCurrent_C SNVT_amp
AV16 ADF 16 0016 X1 Signed
VSD L1 Input Current (RMS) VSD RMS INPUT CURRENT L1 Amps Amps AV17 ADF 17 0017 X10 Signed nvoInputCur_L1 SNVT_amp
VSD L2 Input Current (RMS) VSD RMS INPUT CURRENT L2 Amps Amps AV18 ADF 18 0018 X10 Signed nvoInputCur_L2 SNVT_amp
VSD L3 Input Current (RMS) VSD RMS INPUT CURRENT L3 Amps Amps AV19 ADF 19 0019 X10 Signed nvoInputCur_L3 SNVT_amp
Leaving Chilled Liquid Setpoint - Selected LEAVING CH LIQ TEMP ACT SP °F °C AV20 ADF 20 0020 X10 Signed nvoActiveSetpt SNVT_temp_p
Active Input Current Limit INPUT CURRENT LMT ACTIVE % % AV21 ADF 21 0021 X10 Signed nvoActInptCurLmt SNVT_lev_percent
Evaporator Saturation Temperature EVAP SATURATION TEMP °F °C AV22 ADF 22 0022 X10 Signed nvoEvapSatTemp SNVT_temp_p
Condenser Saturation Temperature COND SATURATION TEMP °F °C AV23 ADF 23 0023 X10 Signed nvoCondSatTemp SNVT_temp_p
Input % Full Load Amps INPUT CURRENT PCT FLA % % AV24 ADF 24 0024 X10 Signed nvoPctInputCurr SNVT_lev_percent
Condenser Refrigerant Level COND REFRIGERANT LEVEL % % AV25 ADF 25 0025 X10 Signed nvoRefLvlPos SNVT_lev_percent
Operating Hours OPERATING HOURS Hr Hr AV26 ADF 26 0026 X1 Unsigned nvoRunHours SNVT_time_hours
Number Of Starts NUMBER OF STARTS None None AV27 ADF 27 0027 X1 Unsigned nvoSystemStarts SNVT_count
Hot Gas Bypass Command HOT GAS BYPASS VLV CMD Enable point when Hot Gas Bypass is Enabled % % AV28 ADF 28 0028 X1 Signed nvoHtGasBypasCmd SNVT_lev_percent
Motor % Full Load Amps MOTOR CURRENT PCT FLA % % AV29 ADF 29 0029 X10 Signed nvoPctMotorCurr SNVT_lev_percent
Motor Run [0=Off, 1=On] COMPR MOTOR STATUS 0=Off, 1=On BV5 BD 5 0065 N/A Signed nvoOnOff SNVT_switch
Chilled Liquid Pump [0=Off, 1=On] CH LIQ PUMP STAT 0=Off, 1=On BV6 BD 6 0066 N/A Signed nvoCHPump SNVT_switch
VSD Cooling System [0=Off, 1=On] VSD COOLING SYS STAT 0=Off, 1=On BV7 BD 7 0067 N/A Signed nvoCoolSysStat SNVT_switch
Run Permissive [0=Off, 1=On] RUN PERMISSIVE 0=Off, 1=On BV8 BD 8 0068 N/A Signed nvoRunPermissive SNVT_switch
Chilled Liquid Flow Switch [0=Open, 1=Closed] CH LIQ FLOW SWITCH STAT 0=Open, 1=Closed BV9 BD 9 0069 N/A Signed nvoCHFlowSwitch SNVT_switch
Condenser Liquid Flow Switch [0=Open, 1=Closed] CND FLOW SWITCH STAT 0=Open, 1=Closed BV10 BD 10 0070 N/A Signed nvoCNDFlowSwitch SNVT_switch
Condenser Level Control Valve Mode [0=Auto,1=Manual] COND REF LEVEL CNTRL MODE 0=Auto, 1=Manual BV11 BD 11 0071 N/A Signed nvoRefLvlCtlMode SNVT_switch
Condenser Liquid Pump [0=Off, 1=On] CND LIQ PUMP STAT 0=Off, 1=On BV12 BD 12 0072 N/A Signed nvoCNDLPump SNVT_switch
BV13 BD 13 0073 N/A Signed
BV14 BD 14 0074 N/A Signed
BV15 BD 15 0075 N/A Signed
BV16 BD 16 0076 N/A Signed
BV17 BD 17 0077 N/A Signed
BV18 BD 18 0078 N/A Signed
BV19 BD 19 0079 N/A Signed
BV20 BD 20 0080 N/A Signed
BV21 BD 21 0081 N/A Signed
BV22 BD 22 0082 N/A Signed
BV23 BD 23 0083 N/A Signed
BV24 BD 24 0084 N/A Signed
Unit Operation Code UNIT OPERATION CODE See SC.1 on Status Codes MV1 N/A N/A N/A Unsigned N/A N/A
Unit Operation Code AV UNIT OPERATION CODE AV None None See SC.1 on Status Codes AV401 ADI 1 0030 X1 Unsigned nvoOperCode SNVT_count
Unit Safety Fault Code UNIT SAFETY FAULT CODE See SC.2 on Status Codes MV2 N/A N/A N/A Unsigned N/A N/A
Unit Safety Fault Code AV UNIT SAFETY FAULT CODE AV None None See SC.2 on Status Codes AV402 ADI 2 0031 X1 Unsigned nvoSafetyCode SNVT_count
Unit Cycling Fault Code UNIT CYCLING FAULT CODE See SC.3 on Status Codes MV3 N/A N/A N/A Unsigned N/A N/A
Unit Cycling Fault Code AV UNIT CYCLING FAULT CODE AV None None See SC.3 on Status Codes AV403 ADI 3 0032 X1 Unsigned nvoCyclingFault SNVT_count
Unit Warning Code UNIT WARNING CODE See SC.4 on Status Codes MV4 N/A N/A N/A Unsigned N/A N/A
YMC2 SC-EQ BAS Points List
Rev 2.11
December 8, 2021
SC-EQ Software Version 4.2.0.20
BACnet
Long Name Short Name IP SI Object & N2 Metasys MODBUS MODBUS MODBUS
(BACnet Object Description) (BACnet Object Name) Notes Units Units Enum Set Instance Address Address Scale Data Type LON Profile Name LON SNVT Type
Unit Warning Code AV UNIT WARNING CODE AV None None See SC.4 on Status Codes AV404 ADI 4 0033 X1 Unsigned nvoWarnFault SNVT_count
0=Local
1=ISN (BAS)
2=Analog
3=Digital
4=Modem
Unit Control Source UNIT CONTROL SOURCE 5=Remote MV5 N/A N/A N/A Unsigned N/A N/A
0=Local
1=ISN (BAS)
2=Analog
3=Digital
4=Modem
Unit Control Source AV UNIT CONTROL SOURCE AV None None 5=Remote AV405 ADI 5 0034 X1 Unsigned nvoUnitCtrlSrce SNVT_count
Unit Modified Run Code UNIT MODIFIED RUN CODE See SC.12 on Status Codes MV6 N/A N/A N/A Unsigned N/A N/A
Unit Modified Run Code AV UNIT MODIFIED RUN CODE AV None None See SC.12 on Status Codes AV406 ADI 6 0035 X1 Unsigned nvoModRunFault SNVT_count
Unit Start Inhibit Code UNIT START INHIBIT CODE See SC.13 on Status Codes MV7 N/A N/A N/A Unsigned N/A N/A
Unit Start Inhibit Code AV UNIT START INHIBIT CODE AV None None See SC.13 on Status Codes AV407 ADI 7 0036 X1 Unsigned nvoInhibitFault SNVT_count
Unit Internal Fault Code UNIT INTERNAL FAULT CODE See SC.14 on Status Codes MV8 N/A N/A N/A Unsigned N/A N/A
Unit Internal Fault Code AV UNIT INTERNAL FAULT CODE AV None None See SC.14 on Status Codes AV408 ADI 8 0037 X1 Unsigned nvoInternalFault SNVT_count
MV9 ADI 9 0038 X1 Unsigned
MV10 ADI 10 0039 X1 Unsigned
0 = [Unused]
1 = Probing or Capacity Control
2 = Stall Reacting
3 = Stall Waiting
4 = Surge Reacting
5 = Surge Waiting
6 = Sensor Override
7 = [Unused]
VGD Control State VGD CONTROL STATE (Mod A Chillers only) None None 8 = PRV Position Override AV30 ADF 30 0040 X1 Unsigned nvoVGDCntrlState SNVT_count
VGD Stall Count VGD STALL COUNT (Mod A Chillers only) None None AV31 ADF 31 0041 X1 Unsigned nvoVGDStallCnt SNVT_count
Active Anti-Surge Minimum Frequency ACTIVE ANTI SURGE MIN FREQ Hz Hz AV32 ADF 32 0042 X1 Signed nvoAntiSurMinFq SNVT_freq_hz
AV33 ADF 33 0043 X1 Signed
VSD Output Voltage VSD OUTPUT VOLTAGE Volts Volts AV34 ADF 34 0044 X10 Signed nvoVSDOutputVolt SNVT_volt
VSD Input Power VSD INPUT POWER kW kW AV35 ADF 35 0045 X1 Signed nvoVSDInputPower SNVT_power_kilo
VSD Input Kilowatt Hours VSD INPUT KWH kWh kWh AV36 ADF 36 0046 X1 Unsigned nvoVSDKWH SNVT_elec_kwh
VSD DC Bus Voltage VSD DC BUS VOLTAGE Volts Volts AV37 ADF 37 0047 X1 Signed nvoVSDDCBusVolt SNVT_volt
VSD L1 Input Voltage (RMS) VSD INPUT VOLTAGE L1 Volts Volts AV38 ADF 38 0048 X1 Signed nvoInputVoltL1 SNVT_volt
Surge Count SURGE COUNT None None AV39 ADF 39 0049 X1 Unsigned nvoSurgeCount SNVT_count
VSD Output Frequency VSD OUTPUT FREQUENCY Hz Hz AV40 ADF 40 0050 X1 Signed nvoVSDOutFreq SNVT_freq_hz
VSD L2 Input Voltage (RMS) VSD INPUT VOLTAGE L2 Volts Volts AV41 ADF 41 0051 X1 Signed nvoInputVoltL2 SNVT_volt
VSD L3 Input Voltage (RMS) VSD INPUT VOLTAGE L3 Volts Volts AV42 ADF 42 0052 X1 Signed nvoInputVoltL3 SNVT_volt
Condenser Level Control Valve Command COND LVL CTRL VLV CMD % % AV43 ADF 43 0053 X1 Signed nvoCondLvlCtlVlv SNVT_lev_percent
BV25 BD 25 0085 N/A Signed
MBC Levitation Mode [0=Off, 1=On] MBC LEVITATION MODE 0=Off, 1=On BV26 BD 26 0086 N/A Signed nvoLevitateMode SNVT_switch
MBC Rotation Mode [0=Off, 1=On] MBC ROTATION MODE 0=Off, 1=On BV27 BD 27 0087 N/A Signed nvoRotateMode SNVT_switch
BV28 BD 28 0088 N/A Signed
BV29 BD 29 0089 N/A Signed
AV44 ADF 44 0101 N/A Signed
AV45 ADF 45 0102 N/A Signed
AV46 ADF 46 0103 N/A Signed
AV47 ADF 47 0104 N/A Signed
BV30 BD 30 0161 N/A Signed
BV31 BD 31 0162 N/A Signed
BV32 BD 32 0163 N/A Signed
BV33 BD 33 0164 N/A Signed
Motor Housing Temp MOTOR HOUSING TEMP °F °C AV48 ADF 48 0105 X10 Signed nvoMtrHsgTmp SNVT_temp_p
AV106 ADF 49 0106 X10 Signed
Motor Cooling Valve Command MOTOR COOLING VALVE CMD (Mod A FAB comp & Mod B chillers) % % AV107 ADF 50 0107 X10 Signed nvoMtrCoolVlvCmd SNVT_lev_percent
VSD Internal Ambient Temperature 2 VSD INTERNAL AMBIENT TEMP 2 °F °C AV108 ADF 51 0108 X10 Signed nvoVSDInterTmp2 SNVT_temp_p
Average Motor Winding Temperature MTR WINDING AVG TEMP °F °C AV109 ADF 52 0109 X10 Signed nvoAvgMWindTemp SNVT_temp_p
VSD Internal Ambient Temperature 1 VSD INTERNAL AMBIENT TEMP 1 °F °C AV110 ADF 53 0110 X10 Signed nvoVSDInterTmp1 SNVT_temp_p
VGD Position VGD POSITION % % AV111 ADF 54 0111 X10 Signed nvoVGDPosition SNVT_lev_percent
Pre Rotation Vanes (PRV) Position PRE ROTATION VANES POS (Mod A chiller FAA comp only) % % AV112 ADF 55 0112 X10 Signed nvoPRVPosition SNVT_lev_percent
Condenser Active Level Setpoint COND REFRIGERANT LEVEL SP % % AV113 ADF 56 0113 X10 Signed nvoRefLvlSP SNVT_lev_percent
Drop Leg Refrigerant Temperature DROP LEG REFRIG TEMP °F °C AV114 ADF 57 0114 X10 Signed nvoDropLegTemp SNVT_temp_p
VSD L1 Voltage Total Harmonic Distortion VSD L1 VOLTAGE THD % % AV115 ADF 58 0115 X10 Signed nvoVSDL1VoltTHD SNVT_lev_percent
VSD L2 Voltage Total Harmonic Distortion VSD L2 VOLTAGE THD % % AV116 ADF 59 0116 X10 Signed nvoVSDL2VoltTHD SNVT_lev_percent
YMC2 SC-EQ BAS Points List
Rev 2.11
December 8, 2021
SC-EQ Software Version 4.2.0.20
BACnet
Long Name Short Name IP SI Object & N2 Metasys MODBUS MODBUS MODBUS
(BACnet Object Description) (BACnet Object Name) Notes Units Units Enum Set Instance Address Address Scale Data Type LON Profile Name LON SNVT Type
VSD L3 Voltage Total Harmonic Distortion VSD L3 VOLTAGE THD % % AV117 ADF 60 0117 X10 Signed nvoVSDL3VoltTHD SNVT_lev_percent
VSD L1 Input Current Total Demand Distortion VSD L1 INPUT CURRENT TDD % % AV118 ADF 61 0118 X10 Signed nvoVSDL1CurrTDD SNVT_lev_percent
VSD L2 Input Current Total Demand Distortion VSD L2 INPUT CURRENT TDD % % AV119 ADF 62 0119 X10 Signed nvoVSDL2CurrTDD SNVT_lev_percent
VSD L3 Input Current Total Demand Distortion VSD L3 INPUT CURRENT TDD % % AV120 ADF 63 0120 X10 Signed nvoVSDL3CurrTDD SNVT_lev_percent
Input Kilowatt Hours = (Input Kilowatt Hours
Offset x 10,000) + Input Kilowatt Hours Low
Input Kilowatt Hours Low INPUT KWH LO kWh Lo = kWh % 10000 (integer modulus) None None AV121 ADF 64 0121 X1 Unsigned nvoKWHLo SNVT_elec_kwh
Input Kilowatt Hours = (Input Kilowatt Hours
Offset x 10,000) + Input Kilowatt Hours Low
Input Kilowatt Hours Offset INPUT KWH OFFSET kWh Offset = kWh / 10000 (integer divide) None None AV122 ADF 65 0122 X1 Unsigned nvoKWHOffset SNVT_elec_kwh
Operating Hours = (Operating Hours Offset x
10,000) + Operating Hours Low
Operating Hours Low OPERATING HOURS LO Hours Lo = Hours % 10000 (integer modulus) None None AV123 ADF 66 0123 X1 Unsigned nvoOpHrLo SNVT_time_hour
Operating Hours = (Operating Hours Offset x
10,000) + Operating Hours Low
Operating Hours Offset OPERATING HOURS OFFSET Hours Offset = Hours / 10000 (integer divide) None None AV124 ADF 67 0124 X1 Unsigned nvoOpHrOffset SNVT_time_hour
MBC Motor Speed MBC MOTOR SPEED Hz Hz AV125 ADF 68 0125 X1 Signed nvoMotorSpeedHz SNVT_freq_hz
MBC Landing Counter MBC LANDING COUNTER (Mod A chillers only) None None AV126 ADF 69 0126 X1 Unsigned nvoLandingCountr SNVT_count
Active Minimum PRV Position ACTIVE MIN PRV POS (Mod A chiller FAA comp only) % % AV127 ADF 70 0127 X1 Signed nvoAntiSurMinPos SNVT_lev_percent
AV128 ADF 71 0128 X1 Signed
AV129 ADF 72 0129 X1 Signed
BV105 BD 34 0165 N/A Signed
BV106 BD 35 0166 N/A Signed
BV107 BD 36 0167 N/A Signed
BV108 BD 37 0168 N/A Signed
BV109 BD 38 0169 N/A Signed
BV110 BD 39 0170 N/A Signed
BV111 BD 40 0171 N/A Signed
BV112 BD 41 0172 N/A Signed
BV113 BD 42 0173 N/A Signed
BV114 BD 43 0174 N/A Signed
BV115 BD 44 0175 N/A Signed
BV116 BD 45 0176 N/A Signed
BV117 BD 46 0177 N/A Signed
BV118 BD 47 0178 N/A Signed
BV119 BD 48 0179 N/A Signed
BV120 BD 49 0180 N/A Signed
BV121 BD 50 0181 N/A Signed
BV122 BD 51 0182 N/A Signed
BV123 BD 52 0183 N/A Signed
BV124 BD 53 0184 N/A Signed
MV101 /AV411 ADI 11 0130 X1 Signed
MV102 /AV412 ADI 12 0131 X1 Signed
MV103 /AV413 ADI 13 0132 X1 Signed
MV104 /AV414 ADI 14 0133 X1 Signed
MV105 /AV415 ADI 15 0134 X1 Signed
MV106 /AV416 ADI 16 0135 X1 Signed
MV107 /AV417 ADI 17 0136 X1 Signed
MV108 /AV418 ADI 18 0137 X1 Signed
MV109 /AV419 ADI 19 0138 X1 Signed
MV110 /AV420 ADI 20 0139 X1 Signed
AV130 ADF 73 0140 X1 Signed
AV131 ADF 74 0141 X1 Signed
AV132 ADF 75 0142 X1 Signed
AV133 ADF 76 0143 X1 Signed
AV134 ADF 77 0144 X10 Signed
AV135 ADF 78 0145 X1 Signed
AV136 ADF 79 0146 X1 Signed
UPS Battery Voltage UPS BATTERY VOLTAGE Mod B Chillers only Volts Volts AV137 ADF 80 0147 X10 Signed nvoUPSBattVolt SNVT_volt
VSD Phase A Rectifier Baseplate Temperature VSD PH A REC BASEPLATE TEMP °F °C AV138 ADF 81 0148 X10 Signed nvoVSDRecBaseAT SNVT_temp_p
VSD Phase B Rectifier Baseplate Temperature VSD PH B REC BASEPLATE TEMP °F °C AV139 ADF 82 0149 X10 Signed nvoVSDRecBaseBT SNVT_temp_p
VSD Phase C Rectifier Baseplate Temperature VSD PH C REC BASEPLATE TEMP °F °C AV140 ADF 83 0150 X10 Signed nvoVSDRecBaseCT SNVT_temp_p
VSD Phase A Inverter Baseplate Temperature VSD PH A INV BASEPLATE TEMP °F °C AV141 ADF 84 0151 X10 Signed nvoVSDInvBaseAT SNVT_temp_p
VSD Phase B Inverter Baseplate Temperature VSD PH B INV BASEPLATE TEMP °F °C AV142 ADF 85 0152 X10 Signed nvoVSDInvBaseBT SNVT_temp_p
VSD Phase C Inverter Baseplate Temperature VSD PH C INV BASEPLATE TEMP °F °C AV143 ADF 86 0153 X10 Signed nvoVSDInvBaseCT SNVT_temp_p
BV125 BD 54 0185 N/A Signed
BV126 BD 55 0186 N/A Signed
YMC2 SC-EQ BAS Points List
Rev 2.11
December 8, 2021
SC-EQ Software Version 4.2.0.20
BACnet
Long Name Short Name IP SI Object & N2 Metasys MODBUS MODBUS MODBUS
(BACnet Object Description) (BACnet Object Name) Notes Units Units Enum Set Instance Address Address Scale Data Type LON Profile Name LON SNVT Type
BV127 BD 56 0187 N/A Signed
BV128 BD 57 0188 N/A Signed
BV129 BD 58 0189 N/A Signed
Evaporator Small Temp Difference EVAP SMALL TEMP DIFF °F (diff) °C (diff) AV144 ADF 87 0190 X10 Signed nvoEvapSmTmpDiff SNVT_temp_p
Condenser Small Temp Difference COND SMALL TEMP DIFF °F (diff) °C (diff) AV145 ADF 88 0191 X10 Signed nvoCondSmTmpDiff SNVT_temp_p
Discharge Superheat DISCHARGE SUPERHEAT °F (diff) °C (diff) AV146 ADF 89 0192 X10 Signed nvoDschSuperheat SNVT_temp_p
Subcooler Effectiveness SUBCOOLLER EFFECTIVENESS None None AV147 ADF 90 0193 X10 Signed nvoSubcoolerEff SNVT_count_f
Subcooling Temperature SUBCOOLING TEMP °F (diff) °C (diff) AV148 ADF 91 0194 X10 Signed nvoSubcoolingTmp SNVT_temp_p
Delta P / P DELTA P DIV P None None AV149 ADF 92 0195 X10 Signed nvoDeltaPdivP SNVT_count_f
Head Pressure HEAD PRESSURE PSID kPaD AV150 ADF 93 0196 X10 Signed nvoHeadPress SNVT_press
Run/Stop Control Source [0=Local, 1=BAS, 2=Hardwire] RUN STOP CTRL SOURCE 0=Local, 1=BAS, 2=Hardwire MV10 N/A N/A N/A Unsigned N/A N/A
Run/Stop Control Source AV [0=Local, 1=BAS, 2=Hardwire] RUN STOP CTRL SOURCE AV None None 0=Local, 1=BAS, 2=Hardwire AV421 ADI 21 0197 X1 Unsigned nvoRunStopSrce SNVT_count
0=Local
1=BAS
2=0-10 Volts
3=4-20 mA
Cooling Setp Control Source [0=Local, 1=BAS, 2=0-10 Volts, 3=4-20
COOL
mA,SETP
4=PWM]
CTRL SOURCE 4=PWM MV11 N/A N/A N/A Unsigned N/A N/A
0=Local
1=BAS
2=0-10 Volts
3=4-20 mA
Cooling Setp Control Source AV [0=Local, 1=BAS, 2=0-10 Volts, 3=4-20
COOL SETP
mA, 4=PWM]
CTRL SOURCE AV None None 4=PWM AV422 ADI 22 0198 X1 Unsigned nvoCoolSetpSrce SNVT_count
0=Local
1=BAS
2=0-10 Volts
3=4-20 mA
Heating Setp Control Source [0=Local, 1=BAS, 2=0-10 Volts, 3=4-20
HEAT
mA,
SETP
4=PWM]
CTRL SOURCE 4=PWM MV12 N/A N/A N/A Unsigned N/A N/A
0=Local
1=BAS
2=0-10 Volts
3=4-20 mA
Heating Setp Control Source AV [0=Local, 1=BAS, 2=0-10 Volts, 3=4-20
HEAT SETP
mA, 4=PWM]
CTRL SOURCE AV None None 4=PWM AV423 ADI 23 0199 X1 Unsigned nvoHeatSetpSrce SNVT_count
0=Local
1=BAS
2=0-10 Volts
3=4-20 mA
Current Limit Control Source [0=Local, 1=BAS, 2=0-10 Volts, 3=4-20
CURRmA,
LIM4=PWM]
CTRL SOURCE 4=PWM MV13 N/A N/A N/A Unsigned N/A N/A
0=Local
1=BAS
2=0-10 Volts
3=4-20 mA
Current Limit Control Source AV [0=Local, 1=BAS, 2=0-10 Volts, 3=4-20
CURR LIM
mA,CTRL
4=PWM]
SOURCE AV None None 4=PWM AV424 ADI 24 0200 X1 Unsigned nvoCurrLimSrce SNVT_count
YMC2 SC-EQ BAS Status Codes
Rev 2.11
December 8, 2021
SC-EQ Software Version 4.2.0.20
YMC2 Operation Code SC.1 YMC2 Safety Fault Code SC.2 YMC2 Safety Fault Code SC.2 YMC2 Safety Fault Code SC.2
*NOTE: for BACnet MSV values add 1 to number *NOTE: for BACnet MSV values add 1 to number *NOTE: for BACnet MSV values add 1 to number *NOTE: for BACnet MSV values add 1 to number
Code SC.1 Code SC.2 Code SC.2 Code SC.2
0 Unit Stopped - Ready To Start 0 No Safety Faults Present 65 N/A 130 MBC - DSP INTEGRITY
1 Unit Stopped - Local Shutdown 1 EVAPORATOR - LOW PRESSURE 66 VSD - MOTOR CURRENT IMBALANCE 131 MBC - FLASH MEMORY CLEAR
2 Unit Stopped - Remote Shutdown 2 EVAPORATOR - TRANSDUCER OR LEAVING LIQUID PROBE 67 CONDENSER - HIGH PRESSURE - STOPPED 132 MBC - FLASH MEMORY WRITE
3 Unit Stopped - Warning Active 3 EVAPORATOR - TRANSDUCER OR TEMPERATURE SENSOR 68 MBC - DSP UNAUTHORIZED ROTATION 133 MBC - EEPROM
4 Unit Stopped - Cycling Shutdown 4 CONDENSER - HIGH PRESSURE SWITCH OPEN 69 MBC - SPV UNAUTHORIZED ROTATION 134 MBC - FLASH MEMORY FULL
5 Unit Stopped - Safety Shutdown 5 CONDENSER - HIGH PRESSURE 70 MBC - AMP COMMUNICATION 135 MBC - INTERNAL FAULT 11
6 Unit Start Inhibit 6 CONDENSER - PRESSURE TRANSDUCER OUT OF RANGE 71 MBC - AMP WATCHDOG 136 MBC - INTERNAL FAULT 12
7 Unit Starting 7 AUXILIARY SAFETY - CONTACTS CLOSED 72 N/A 137 MBC - INTERNAL FAULT 13
8 Unit Running - No Abnormal Condition 8 DISCHARGE - LOW TEMPERATURE 73 MBC - LOW RADIAL OSCILLATOR VOLTAGE 138 MBC - INTERNAL FAULT 14
9 Unit Running - Warning Active 9 DISCHARGE - HIGH TEMPERATURE 74 N/A 139 MBC - DSP WATCHDOG
10 Unit Running - Soft Shutdown 10 MBC - OVERSPEED FAULT 75 MBC - LOW AXIAL OSCILLATOR VOLTAGE 140 MBC - DATA ACQUISITION FAULT
11 Unit Coastdown 11 MBC - WATCHDOG 76 MBC - ROTOR CONTRACTION 141 MBC - HIGH BEARING Z1 TEMPERATURE
12 Unit Running - Modified Run 12 MBC - POWER SUPPLY FAULT 77 MBC - HIGH INPUT VOLTAGE 142 MBC - HIGH BEARING Z2 TEMPERATURE
13 Unit Stopped - Internal Shutdown 13 MBC - HIGH HEATSINK TEMPERATURE 78 N/A 143 MBC - CABLE FAULT
14 N/A 14 MBC - HIGH DC BUS VOLTAGE 79 MBC - INTERNAL FAULT 144 MBC - SPEED SIGNAL FAULT
15 Unit Running - Active Low Lift - No Abnormal Condition 15 MBC - AMPLIFIER FUSE 80 VGD ACTUATOR FAULT 145 MBC - OVERSPEED FAULT
16 Unit Running - Active Low Lift - Warning Active 16 MBC - SPEED SENSOR FAULT 81 VGD POSITIONING FAULT 146 MBC - ROTOR ELONGATION
17 Unit Running - Active Low Lift - Modified Run 17 MBC - HIGH BEARING J TEMPERATURE 82 MBC - POWER FAIL LANDING 147 MBC - HIGH BEARING CURRENT
18 Unit Running - Passive Low Lift - No Abnormal Condition 18 MBC - HIGH BEARING H1 TEMPERATURE 83 MBC - HIGH ROTOR ELONGATION RATE 148 MBC - OSCILLATOR FAULT
19 Unit Running - Passive Low Lift - Warning Active 19 MBC - HIGH BEARING H2 TEMPERATURE 84 N/A 149 MBC - POWER SUPPLY FAULT
20 Unit Running - Passive Low Lift - Modified Run 20 MBC - HIGH BEARING K TEMPERATURE 85 N/A 150 MBC - UNAUTHORIZED ROTATION
21 Unit Running - Cooling - No Abnormal Condition 21 CONTROL PANEL - POWER FAILURE 86 N/A 151 MBC - FAULT CODE X
22 Unit Running - Cooling - Warning Active 22 CONTROL PANEL - LOSS OF CONTROL VOLTAGE 87 N/A 152 MBC - NO LEVITATION
23 Unit Running - Cooling - Modified Run 23 UPS - BATTERY NOT CONNECTED 88 N/A 153 MBC - STARTUP FAILURE
24 Unit Running - Heating - No Abnormal Condition 24 UPS - INVERTER LOW BATTERY VOLTAGE 89 N/A 154 MBC - EXCESSIVE SHUTDOWNS
25 Unit Running - Heating - Warning Active 25 MBC - GROUND FAULT 90 N/A 155 SAFETY STOP
26 Unit Running - Heating - Modified Run 26 MBC - LOW GATE VOLTAGE 91 N/A 156 MBC - INITIALIZATION FAILURE
27 Unit Running - Cooling & Heating - No Abnormal Condition 27 MBC - HIGH GATE VOLTAGE 92 N/A 157 MBC - CUSTOMER SERIAL LINK DISABLED
28 Unit Running - Cooling & Heating - Warning Active 28 MBC - POWER FAIL LANDING 93 N/A 158 MOTOR - HIGH HOUSING TEMPERATURE
29 Unit Running - Cooling & Heating - Modified Run 29 MBC - HIGH AMPLIFIER TEMPERATURE 94 VSD - HIGH HX APPROACH TEMPERATURE 159 SALES ORDER - INVALID COMPRESSOR MODEL
30 VSD - 105% MOTOR CURRENT OVERLOAD 95 VSD - LOGIC BOARD PLUG 160 VSD - LINE VOLTAGE PHASE ROTATION
31 MBC - HIGH AMPLIFIER VOLTAGE 96 VSD - INPUT CURRENT OVERLOAD 161 VSD - PHASE LOCKED LOOP
32 MBC - FAULT CONTACTS OPEN 97 VSD - HIGH PHASE A INPUT BASEPLATE TEMPERATURE 162 VSD - LOGIC BOARD HARDWARE
33 MBC - NOT LEVITATED 98 VSD - HIGH PHASE B INPUT BASEPLATE TEMPERATURE 163 ISOLATION VALVES - NOT OPENED
34 N/A 99 VSD - HIGH PHASE C INPUT BASEPLATE TEMPERATURE
35 VSD - PRECHARGE LOCKOUT 100 VSD - HIGH PHASE A MOTOR BASEPLATE TEMPERATURE
36 VSD - HIGH MOTOR HARMONICS 101 VSD - HIGH PHASE B MOTOR BASEPLATE TEMPERATURE
37 VSD - CAPACITOR FAULT 102 VSD - HIGH PHASE C MOTOR BASEPLATE TEMPERATURE
38 VSD - ELECTRICAL SIGNATURE BOARD 103 VSD - DC BUS PRE-REGULATION LOCKOUT
39 VSD - BASEPLATE TEMPERATURE IMBALANCE 104 VSD - GROUND FAULT
40 VSD - HIGH CONVERTER HEATSINK TEMPERATURE 105 VSD - PHASE A MOTOR DCCT
41 VSD - INVALID SOFTWARE 106 VSD - PHASE B MOTOR DCCT
42 HARMONIC FILTER - HIGH BASEPLATE TEMPERATURE 107 VSD - PHASE C MOTOR DCCT
43 HARMONIC FILTER - HIGH TOTAL DEMAND DISTORTION 108 VSD - PHASE A INPUT DCCT
44 N/A 109 VSD - PHASE B INPUT DCCT
45 N/A 110 VSD - PHASE C INPUT DCCT
46 N/A 111 VSD - HIGH TOTAL DEMAND DISTORTION
47 N/A 112 VSD - HIGH INTERNAL AMBIENT TEMPERATURE
48 N/A 113 VSD - DC BUS LOCKOUT - DO NOT CYCLE POWER
49 N/A 114 VSD - INPUT DCCT OFFSET LOCKOUT
50 N/A 115 VSD - OUTPUT PHASE ROTATION
51 EVAPORATOR - LOW PRESSURE 116 VSD - HIGH PHASE A INPUT CURRENT
52 EVAPORATOR - LOW PRESSURE - SMART FREEZE 117 VSD - HIGH PHASE B INPUT CURRENT
53 SURGE PROTECTION - EXCESS SURGE 118 VSD - HIGH PHASE C INPUT CURRENT
54 SYSTEM - STARTUP FAILURE 119 VSD - HIGH PHASE A MOTOR CURRENT
55 N/A 120 VSD - HIGH PHASE B MOTOR CURRENT
56 N/A 121 VSD - HIGH PHASE C MOTOR CURRENT
57 N/A 122 VSD - MOTOR CURRENT THD FAULT
58 N/A 123 VSD - HIGH INPUT CURRENT TDD
59 N/A 124 VSD - RECTIFIER PROGRAM FAULT
60 MOTOR - LOW WINDING TEMPERATURE 125 VSD - INVERTER PROGRAM FAULT
61 MOTOR - HIGH WINDING TEMPERATURE 126 MBC - DSP INITIALIZATION
62 MOTOR - HIGH ROTOR TEMPERATURE 127 MBC - HIGH AMPLIFIER TEMPERATURE
63 N/A 128 MBC - HIGH DC/DC TEMPERATURE
64 N/A 129 MBC - DSP COMMUNICATION
YMC2 SC-EQ BAS Status Codes
Rev 2.11
December 8, 2021
SC-EQ Software Version 4.2.0.20
YMC2 Cycling Fault Code SC.3 YMC2 Cycling Fault Code SC.3 YMC2 Cycling Fault Code SC.3
*NOTE: for BACnet MSV values add 1 to number *NOTE: for BACnet MSV values add 1 to number *NOTE: for BACnet MSV values add 1 to number
Code SC.3 Code SC.3 Code SC.3
0 No Cycling Faults Present 65 HARMONIC FILTER - LOGIC BOARD POWER SUPPLY 130 EXPANSION I/O - SERIAL COMMUNICATIONS
1 MULTIUNIT CYCLING - CONTACTS OPEN 66 HARMONIC FILTER - PRECHARGE - LOW DC BUS VOLTAGE 2 131 N/A
2 SYSTEM CYCLING - CONTACTS OPEN 67 HARMONIC FILTER - PRECHARGE - LOW DC BUS VOLTAGE 1 132 VSD - HIGH PHASE A INPUT CURRENT
3 SYSTEM - STARTUP FAILURE 68 HARMONIC FILTER - LOW DC BUS VOLTAGE 133 VSD - HIGH PHASE B INPUT CURRENT
4 N/A 69 HARMONIC FILTER - DC BUS VOLTAGE IMBALANCE 134 VSD - HIGH PHASE C INPUT CURRENT
5 CONTROL PANEL - POWER FAILURE 70 HARMONIC FILTER - INPUT CURRENT OVERLOAD 135 VSD - HIGH PHASE A MOTOR CURRENT
6 LEAVING CHILLED LIQUID - LOW TEMPERATURE 71 HARMONIC FILTER - RUN SIGNAL 136 VSD - HIGH PHASE B MOTOR CURRENT
7 CHILLED LIQUID - FLOW SWITCH OPEN 72 HARMONIC FILTER - DC CURRENT TRANSFORMER 1 137 VSD - HIGH PHASE C MOTOR CURRENT
8 CONDENSER - FLOW SWITCH OPEN 73 HARMONIC FILTER - DC CURRENT TRANSFORMER 2 138 VSD - PHASE A INPUT GATE DRIVER
9 LEAVING CONDENSER LIQUID - HIGH TEMPERATURE 74 N/A 139 VSD - PHASE B INPUT GATE DRIVER
10 AMBIENT DEW POINT - LOW TEMPERATURE 75 N/A 140 VSD - PHASE C INPUT GATE DRIVER
11 REFRIGERANT TYPE NOT SET 76 N/A 141 VSD - PHASE A MOTOR GATE DRIVER
12 CONTROL PANEL - SCHEDULE 77 N/A 142 VSD - PHASE B MOTOR GATE DRIVER
13 N/A 78 N/A 143 VSD - PHASE C MOTOR GATE DRIVER
14 N/A 79 N/A 144 VSD - LOW PHASE A INPUT BASEPLATE TEMPERATURE
15 N/A 80 N/A 145 VSD - LOW PHASE B INPUT BASEPLATE TEMPERATURE
16 N/A 81 N/A 146 VSD - LOW PHASE C INPUT BASEPLATE TEMPERATURE
17 VSD - INITIALIZATION FAILURE 82 N/A 147 VSD - LOW PHASE A MOTOR BASEPLATE TEMPERATURE
18 VSD SHUTDOWN - REQUESTING FAULT DATA... 83 N/A 148 VSD - LOW PHASE B MOTOR BASEPLATE TEMPERATURE
19 VGD ACTUATOR - SERIAL COMMUNICATIONS 84 N/A 149 VSD - LOW PHASE C MOTOR BASEPLATE TEMPERATURE
20 UPS - LINE LOW BATTERY VOLTAGE 85 N/A 150 VSD – LINE VOLTAGE PHASE ROTATION
21 UPS - NOT CHARGING 86 N/A 151 VSD - DC BUS PRE-REGULATION
22 N/A 87 N/A 152 VSD - LOGIC BOARD PROCESSOR
23 N/A 88 N/A 153 VSD – PHASE LOCKED LOOP
24 N/A 89 N/A 154 VSD - NOT RUNNING
25 VSD - SINGLE PHASE INPUT POWER 90 N/A 155 VSD - PHASE A INPUT DCCT OFFSET
26 VSD - HIGH DC BUS VOLTAGE 91 N/A 156 VSD - PHASE B INPUT DCCT OFFSET
27 VSD - LOGIC BOARD POWER SUPPLY 92 N/A 157 VSD - PHASE C INPUT DCCT OFFSET
28 VSD - LOW DC BUS VOLTAGE 93 N/A 158 VSD - PRECHARGE - LOW DC BUS VOLTAGE 2
29 VSD - 105% MOTOR CURRENT OVERLOAD 94 N/A 159 VSD - INVALID SETPOINTS
30 VSD - HIGH INTERNAL AMBIENT TEMPERATURE 95 N/A 160 CONDENSER - FREEZE THREAT - FLOW SWITCH OPEN
31 VSD - DC BUS VOLTAGE IMBALANCE 96 N/A 161 ISOLATION VALVES - NOT CLOSED
32 VSD - BASEPLATE TEMPERATURE IMBALANCE 97 N/A
33 VSD - LOW CONVERTER HEATSINK TEMPERATURE 98 N/A
34 VSD - PRECHARGE - DC BUS VOLTAGE IMBALANCE 99 N/A
35 VSD - INVALID VSD MODEL 100 VSD - SERIAL COMMUNICATIONS
36 N/A 101 MBC - V13 POSITION
37 VSD - PRECHARGE - LOW DC BUS VOLTAGE 1 102 MBC - W13 POSITION
38 N/A 103 MBC - V24 POSITION
39 VSD - RUN SIGNAL 104 MBC - W24 POSITION
40 VSD - SERIAL RECEIVE 105 MBC - Z12 POSITION
41 VSD - FAULT CONTACTS OPEN 106 MBC - V13 LOW FREQUENCY DISPLACEMENT
42 MBC - LOW DC BUS VOLTAGE 107 MBC - W13 LOW FREQUENCY DISPLACEMENT
43 MBC - BEARING CALIBRATION REQUIRED 108 MBC - V24 LOW FREQUENCY DISPLACEMENT
44 MBC - J RADIAL POSITION 109 MBC - W24 LOW FREQUENCY DISPLACEMENT
45 MBC - K RADIAL POSITION 110 MBC - Z12 LOW FREQUENCY DISPLACEMENT
46 MBC - H AXIAL POSITION 111 MBC - VW13 VIBRATION
47 MBC - CALIBRATION FAULT 112 MBC - VW24 VIBRATION
48 MBC - LOW BEARING J TEMPERATURE 113 MBC - Z12 VIBRATION
49 MBC - LOW BEARING H1 TEMPERATURE 114 MBC - HIGH AMPLIFIER TEMPERATURE
50 MBC - LOW BEARING H2 TEMPERATURE 115 MBC - HIGH DC/DC TEMPERATURE
51 MBC - LOW BEARING K TEMPERATURE 116 MBC - SERIAL COMMUNICATIONS
52 MBC - LOW HEATSINK TEMPERATURE 117 MBC - SPEED SIGNAL FAULT
53 N/A 118 MBC SHUTDOWN - REQUESTING FAULT DATA...
54 N/A 119 MBC - FAULT CONTACTS OPEN
55 N/A 120 MBC - STARTUP FAILURE
56 N/A 121 MBC - UNKNOWN PARAMETER FILE
57 N/A 122 MBC - LOW INPUT VOLTAGE
58 N/A 123 N/A
59 N/A 124 N/A
60 HARMONIC FILTER - HIGH DC BUS VOLTAGE 125 N/A
61 HARMONIC FILTER - HIGH PHASE C CURRENT 126 N/A
62 HARMONIC FILTER - HIGH PHASE B CURRENT 127 EVAPORATOR - LOW PRESSURE - SMART FREEZE
63 HARMONIC FILTER - HIGH PHASE A CURRENT 128 EVAPORATOR - LOW PRESSURE
64 HARMONIC FILTER - PHASE LOCKED LOOP 129 CONTROL PANEL - LOSS OF CONTROL VOLTAGE
YMC2 SC-EQ BAS Status Codes
Rev 2.11
December 8, 2021
SC-EQ Software Version 4.2.0.20
YMC2 Warning Code SC.4 YMC2 Warning Code SC.4 YMC2 Start Inhibit Code SC.13
*NOTE: for BACnet MSV values add 1 to number *NOTE: for BACnet MSV values add 1 to number *NOTE: for BACnet MSV values add 1 to number
Code SC.4 Code SC.4 Code SC.13
0 No Warnings Present 65 WARNING - MBC - ROTATION MODE OFF 0 No Start Inhibits Present
1 WARNING - REAL TIME CLOCK FAILURE 66 WARNING - MOTOR - HIGH CURRENT LIMIT 1 ANTI-RECYCLE
2 WARNING - SETPOINT OVERRIDE 67 WARNING - MOTOR - HIGH HOUSING TEMPERATURE 2 N/A
3 WARNING - CONDENSER OR EVAPORATOR XDCR ERROR 68 WARNING - VSD - DC BUS ACTIVE 3 VGD STROKE NOT CALIBRATED
4 WARNING - EVAPORATOR - LOW PRESSURE LIMIT 69 WARNING - LIQUID LEVEL SETPOINT NOT ACHIEVED 4 VGD FEEDBACK NOT CALIBRATED
5 WARNING - CONDENSER - HIGH PRESSURE LIMIT 70 WARNING - LOSS OF SUBCOOLER LIQUID SEAL 5 MBC - BEARING CALIBRATION IN PROGRESS
6 WARNING - QUARTERLY SERVICE REQUIRED - CONTACT JCI 71 WARNING - CONDENSER - FREEZE THREAT FROM LOW PRESSURE 6 MBC - BEARING CLEARANCE CHECK IN PROGRESS
7 WARNING - YEARLY SERVICE REQUIRED - CONTACT JCI 7 VSD - INITIALIZATION IN PROGRESS
8 WARNING - 3 YEAR SERVICE REQUIRED - CONTACT JCI 8 N/A
9 WARNING - CONDENSER - HIGH SMALL TEMP DIFFERENCE 9 N/A
10 WARNING - MBC - LOW AMPLIFIER RESISTANCE 10 PRV NOT CALIBRATED
11 WARNING - MBC - HIGH AMPLIFIER RESISTANCE 11 N/A
12 WARNING - MBC - LOW AMPLIFIER CURRENT 12 VGD NOT CALIBRATED
13 WARNING - MBC - HIGH AMPLIFIER CURRENT 13 LINE VOLTAGE NOT SET
14 WARNING - MBC - POSITION SENSOR ERROR 14 LINE FREQUENCY NOT SET
15 WARNING - MBC - J BEARING SENSOR DISABLED 15 MBC - INITIALIZATION IN PROGRESS
16 WARNING - MBC - K BEARING SENSOR DISABLED
17 WARNING - MBC - H BEARING SENSOR DISABLED
18 N/A
19 N/A
20 WARNING – UPS – NOT CHARGING YMC2 Modified Run Code SC.12
21 WARNING – UPS – LINE LOW BATTERY VOLTAGE *NOTE: for BACnet MSV values add 1 to number
22 WARNING – UPS – BATTERY NOT CONNECTED Code SC.12
23 WARNING – UPS – CHECK BATTERY CONNECTION 0 No Modified Run Conditions Present
24 WARNING – UPS – BATTERY TEST FAILED 1 VSD - DC BUS ACTIVE
25 WARNING - SALES ORDER - INVALID SERIAL NUMBER 2 MOTOR - HIGH CURRENT LIMIT
26 N/A 3 N/A
27 N/A 4 VSD - INPUT PULLDOWN LIMIT
28 N/A 5 VSD - HIGH INPUT CURRENT LIMIT
29 WARNING - SURGE PROTECTION - EXCESS SURGE LIMIT
30 WARNING - EXCESS SURGE DETECTED
31 N/A
32 N/A
33 N/A YMC2 Internal Fault Code SC.14
34 WARNING - CONDENSER OR VGD SENSOR FAILURE *NOTE: for BACnet MSV values add 1 to number
35 WARNING - HARMONIC FILTER - INVALID MODEL Code SC.14
36 WARNING - HARMONIC FILTER - OPERATION INHIBITED 0 No Internal Faults Present
37 WARNING - HARMONIC FILTER - DATA LOSS 1 INTERNAL ERROR - NO TIMER HANDLES AVAILABLE
38 WARNING - HARMONIC FILTER - INPUT FREQUENCY RANGE 2 WATCHDOG - SOFTWARE REBOOT
39 WARNING - HARMONIC FILTER - NOT RUNNING 3 INTERNAL ERROR - CANNOT CREATE TASK
40 WARNING - MOTOR - HIGH WINDING TEMPERATURE 4 INTERNAL ERROR - CANNOT REGISTER CONTROL
41 WARNING - MOTOR - HIGH ROTOR TEMPERATURE 5 INTERNAL ERROR - INVALID BRAM
42 N/A
43 N/A
44 WARNING - VSD - INPUT VOLTAGE IMBALANCE
45 WARNING - VSD - HIGH HX APPROACH TEMPERATURE
46 N/A
47 N/A
48 WARNING - MBC - LANDING COUNTER HIGH
49 N/A
50 N/A
51 N/A
52 N/A
53 N/A
54 N/A
55 WARNING – MBC – CHECKSUM CENTERING
56 WARNING – MBC – DSP WATCHDOG
57 WARNING – MBC – AMP WATCHDOG
58 WARNING – MBC – INTERNAL ALARM
59 WARNING – MBC – HIGH RADIAL OSCILLATOR VOLTAGE
60 WARNING – MBC – HIGH AXIAL OSCILLATOR VOLTAGE
61 N/A
62 N/A
63 N/A
64 N/A