3.2 Earth Fault - Overcurrent Protection

Download as pdf or txt
Download as pdf or txt
You are on page 1of 13

EE 531 PROTECTION

DR. ZULU ESAU


COPPERBELT UNIVERSITY
SCHOOL OF ENGINEERING
ELECTRICAL DEPARTMENT
Email: [email protected]
Earth Fault
Protection
Dr. Zulu Esau 2
3.6 Protection for Earth Faults
▪ When a fault involving ground occurs, a
residue current flows to earth
▪ This current is completely unaffected by the
load current
▪ Thus, sensitive protection against earth faults
which only responds to residual component
can be obtained (using earth fault relay)
▪ Lower settings of earth fault relays are
possible, limited only by presence of
unbalance leakage or capacitance currents to
earth and/or equipment design

Dr. Zulu Esau 3


3.6 Protection for Earth Faults
▪ Residual component is
extracted by connecting the CT
as shown in diagram
▪ In (a), the earth fault relay is
connected in the neutral line.
▪ In practice, phase fault relays
are connected to the CT output
lines while the earth fault relay
is inserted between the star
point and the OC relay group
Figs. (b) & (c)
▪ Typically, earth fault relays are
set around 30-40% of the full
load current
Dr. Zulu Esau 4
3.7 Effective Setting of E/F Relays
▪ Static, digital and numerical relays have very
low variations in burden.
▪ Therefore, primary setting of EF relay is the
relay setting multiplied by CT ratio
▪ For electromechanical relays, the EF element is
similar to phase OC elements.
▪ Thus, because of its lower setting, it will have
similar VA consumption at setting but will
impose a higher burden at nominal or rated
current.
▪ The ‘effective setting’ is the vector sum of the
relay setting current and the total exciting
current. See table in next slide
Dr. Zulu Esau 5
3.7 Effective Setting of E/F Relays

Dr. Zulu Esau 6


3.8 Grading of E/F Relays
▪ The time grading of earth-fault relays can be arranged in
the same manner as for phase fault relays
▪ The time/primary current characteristic for
electromechanical relays cannot be kept proportionate to
the relay characteristic with anything like the accuracy
that is possible for phase fault relays
▪ The ratio error of the current transformers at relay setting
current may be very high
▪ Time grading of electromechanical earth-fault relays is
not such a simple matter as the procedure adopted for
phase relays
▪ Either the above factors must be considered with the
errors calculated for each current level, making the
process much more tedious, or longer grading margins
must be allowed. However, for other types of relay, the
procedure adopted for phase fault relays can be used

Dr. Zulu Esau 7


3.8 Sensitive E/F Protection
▪ It is common to earth HV systems through an
impedance that limits the earth-fault current.
▪ Further, in some countries, the resistivity of the
earth path may be very high due to the nature of
the ground itself (e.g. desert or rock).
▪ A fault to earth not involving earth conductors
may result in the flow of only a small current,
insufficient to operate a normal protection
system.
▪ A similar difficulty also arises in the case of
broken line conductors, which, after falling on to
hedges or dry metalled roads, remain energised
because of the low leakage current, and
therefore present a danger to life.
Dr. Zulu Esau 8
3.8 Sensitive E/F Protection
▪ To overcome the problem, it is necessary to
provide an earth-fault protection system with
a setting that is considerably lower than the
normal line protection.
▪ This presents no difficulty to a modern digital
or numerical relay.
▪ However, older electromechanical or static
relays may present difficulties due to the high
effective burden they may present to the CT.

Dr. Zulu Esau 9


3.8 Sensitive E/F Protection
▪ The required sensitivity cannot normally be provided by means of
conventional CT’s.
▪ A core balance current transformer (CBCT) will normally be
used.
▪ The CBCT is a current transformer mounted around all three
phase (and neutral if present) conductors so that the CT secondary
current is proportional to the residual (i.e. earth) current.
▪ Such a CT can be made to have any convenient ratio suitable for
operating a sensitive earth-fault relay element.
▪ Earth fault settings down to 10% of the current rating of the
circuit to be protected can be obtained. Care must be taken to
position a CBCT correctly in a cable circuit. If the cable sheath is
earthed, the earth connection from the cable gland/sheath junction
must be taken through the CBCT primary to ensure that phase
sheath faults are detected.
Dr. Zulu Esau 10
3.8 Sensitive E/F Protection
▪ With the incorrect method, the fault
current in the sheath is not seen as an
unbalance current and hence relay
operation does not occur.
▪ The normal residual current that may
flow during healthy conditions limits
the application of non-directional
sensitive earth-fault protection.
▪ Such residual effects can occur due to
unbalanced leakage or capacitance in
the system.

Dr. Zulu Esau 11


3.8 Directional E/F Protection
▪ Directional earth-fault overcurrent may need to be applied in the
following situations:
1. for earth-fault protection where the overcurrent protection is by
directional relays
2. in insulated-earth networks
3. in Petersen coil earthed networks
4. where the sensitivity of sensitive earth-fault protection is
insufficient – use of a directional earth-fault relay may provide
greater sensitivity
▪ The relay elements previously described as phase fault elements
respond to the flow of earth fault current, and it is important that
their directional response be correct for this condition.
▪ If a special earth fault element is provided as described in earlier
Sections (which will normally be the case), a related directional
element is needed.

Dr. Zulu Esau 12


3.8.1 Relay Connection
▪ The polarizing quantity is the residual
voltage of the system. This is the
vector sum of the individual phase
voltages.
▪ If the secondary windings of a three-
phase, five limb voltage transformer is
connected in broken delta, the voltage
developed across its terminals will be
the vector sum of the phase to ground
voltages and hence the residual
voltage of the system.
▪ The primary star point of the VT must
be earthed.
▪ Three limb VT is not suitable, as there
is no path for the residual magnetic
flux.

Dr. Zulu Esau 13

You might also like