COPPERBELT UNIVERSITY SCHOOL OF ENGINEERING ELECTRICAL DEPARTMENT Email: [email protected] Earth Fault Protection Dr. Zulu Esau 2 3.6 Protection for Earth Faults ▪ When a fault involving ground occurs, a residue current flows to earth ▪ This current is completely unaffected by the load current ▪ Thus, sensitive protection against earth faults which only responds to residual component can be obtained (using earth fault relay) ▪ Lower settings of earth fault relays are possible, limited only by presence of unbalance leakage or capacitance currents to earth and/or equipment design
Dr. Zulu Esau 3
3.6 Protection for Earth Faults ▪ Residual component is extracted by connecting the CT as shown in diagram ▪ In (a), the earth fault relay is connected in the neutral line. ▪ In practice, phase fault relays are connected to the CT output lines while the earth fault relay is inserted between the star point and the OC relay group Figs. (b) & (c) ▪ Typically, earth fault relays are set around 30-40% of the full load current Dr. Zulu Esau 4 3.7 Effective Setting of E/F Relays ▪ Static, digital and numerical relays have very low variations in burden. ▪ Therefore, primary setting of EF relay is the relay setting multiplied by CT ratio ▪ For electromechanical relays, the EF element is similar to phase OC elements. ▪ Thus, because of its lower setting, it will have similar VA consumption at setting but will impose a higher burden at nominal or rated current. ▪ The ‘effective setting’ is the vector sum of the relay setting current and the total exciting current. See table in next slide Dr. Zulu Esau 5 3.7 Effective Setting of E/F Relays
Dr. Zulu Esau 6
3.8 Grading of E/F Relays ▪ The time grading of earth-fault relays can be arranged in the same manner as for phase fault relays ▪ The time/primary current characteristic for electromechanical relays cannot be kept proportionate to the relay characteristic with anything like the accuracy that is possible for phase fault relays ▪ The ratio error of the current transformers at relay setting current may be very high ▪ Time grading of electromechanical earth-fault relays is not such a simple matter as the procedure adopted for phase relays ▪ Either the above factors must be considered with the errors calculated for each current level, making the process much more tedious, or longer grading margins must be allowed. However, for other types of relay, the procedure adopted for phase fault relays can be used
Dr. Zulu Esau 7
3.8 Sensitive E/F Protection ▪ It is common to earth HV systems through an impedance that limits the earth-fault current. ▪ Further, in some countries, the resistivity of the earth path may be very high due to the nature of the ground itself (e.g. desert or rock). ▪ A fault to earth not involving earth conductors may result in the flow of only a small current, insufficient to operate a normal protection system. ▪ A similar difficulty also arises in the case of broken line conductors, which, after falling on to hedges or dry metalled roads, remain energised because of the low leakage current, and therefore present a danger to life. Dr. Zulu Esau 8 3.8 Sensitive E/F Protection ▪ To overcome the problem, it is necessary to provide an earth-fault protection system with a setting that is considerably lower than the normal line protection. ▪ This presents no difficulty to a modern digital or numerical relay. ▪ However, older electromechanical or static relays may present difficulties due to the high effective burden they may present to the CT.
Dr. Zulu Esau 9
3.8 Sensitive E/F Protection ▪ The required sensitivity cannot normally be provided by means of conventional CT’s. ▪ A core balance current transformer (CBCT) will normally be used. ▪ The CBCT is a current transformer mounted around all three phase (and neutral if present) conductors so that the CT secondary current is proportional to the residual (i.e. earth) current. ▪ Such a CT can be made to have any convenient ratio suitable for operating a sensitive earth-fault relay element. ▪ Earth fault settings down to 10% of the current rating of the circuit to be protected can be obtained. Care must be taken to position a CBCT correctly in a cable circuit. If the cable sheath is earthed, the earth connection from the cable gland/sheath junction must be taken through the CBCT primary to ensure that phase sheath faults are detected. Dr. Zulu Esau 10 3.8 Sensitive E/F Protection ▪ With the incorrect method, the fault current in the sheath is not seen as an unbalance current and hence relay operation does not occur. ▪ The normal residual current that may flow during healthy conditions limits the application of non-directional sensitive earth-fault protection. ▪ Such residual effects can occur due to unbalanced leakage or capacitance in the system.
Dr. Zulu Esau 11
3.8 Directional E/F Protection ▪ Directional earth-fault overcurrent may need to be applied in the following situations: 1. for earth-fault protection where the overcurrent protection is by directional relays 2. in insulated-earth networks 3. in Petersen coil earthed networks 4. where the sensitivity of sensitive earth-fault protection is insufficient – use of a directional earth-fault relay may provide greater sensitivity ▪ The relay elements previously described as phase fault elements respond to the flow of earth fault current, and it is important that their directional response be correct for this condition. ▪ If a special earth fault element is provided as described in earlier Sections (which will normally be the case), a related directional element is needed.
Dr. Zulu Esau 12
3.8.1 Relay Connection ▪ The polarizing quantity is the residual voltage of the system. This is the vector sum of the individual phase voltages. ▪ If the secondary windings of a three- phase, five limb voltage transformer is connected in broken delta, the voltage developed across its terminals will be the vector sum of the phase to ground voltages and hence the residual voltage of the system. ▪ The primary star point of the VT must be earthed. ▪ Three limb VT is not suitable, as there is no path for the residual magnetic flux.