TDS DLSF Series
TDS DLSF Series
Technical Data
Electrical Specifications DLSF-XXA-24V DLSF-XXA-230V DLSF-XXA-385V DLSF-XXA-480V
Max Continuous
30 VAC / 38 VDC 230 VAC 385 VAC 480 VAC
Operating Voltage Uc:
Voltage Protection Level, UP < 80 V < 700 V < 1200 V < 1500 V
Protection status indication: LED indicators for POWER and PROTECTION OK.
Surge Filter, 1Ph, 30 VAC, 8 A, 8 kA+8 kA 8/20 µs L-L, Power & Status
DLSF-8A-24V 12 – 24 VAC/DC 8A
Indication, Alarm Contacts
Surge Filter, 1Ph, 30 VAC, 16 A, 8 kA+8 kA 8/20 µs L-L, Power & Status
DLSF-16A-24V 12 – 24 VAC/DC 16 A
Indication, Alarm Contacts
Surge Filter, 1Ph, 30 VAC, 20 A, 8 kA+8 kA 8/20 µs L-L, Power & Status
DLSF-20A-24V 12 – 24 VAC/DC 20 A
Indication, Alarm Contacts
Surge Filter, 1Ph, 230 VAC, 8 A, 25 kA+25 kA 8/20 µs L-L, Power & Status 100 – 120 VAC
DLSF-8A-230V 8A
Indication, Alarm Contacts (50-60 Hz)
Surge Filter, 1Ph, 230 VAC, 16 A, 25 kA+25 kA 8/20 µs L-L, Power & Status 100 – 120 VAC
DLSF-16A-230V 16 A
Indication, Alarm Contacts (50-60 Hz)
Surge Filter, 1Ph, 230 VAC, 20 A, 25 kA+25 kA 8/20µs L-L, Power & Status 100 – 120 VAC
DLSF-20A-230V 20 A
Indication, Alarm Contacts (50-60 Hz)
Surge Filter, 1Ph, 385 VAC, 8 A, 25 kA+25 kA 8/20 µs L-L, Power & Status 200 – 240 VAC
DLSF-8A-385V 8A
Indication, Alarm Contacts (50-60 Hz)
Surge Filter, 1Ph, 385 VAC, 16 A, 25 kA+25 kA 8/20 µs L-L, Power & Status 200 – 240 VAC
DLSF-16A-385V 16 A
Indication, Alarm Contacts (50-60 Hz)
Surge Filter, 1Ph, 385 VAC, 20 A, 25 kA+25 kA 8/20 µs L-L, Power & Status 200 – 240 VAC
DLSF-20A-385V 20 A
Indication, Alarm Contacts (50-60 Hz)
Surge Filter, 1Ph, 480 VAC, 8 A, 25 kA+25 kA 8/20 µs L-L, Power & Status 220 – 277 VAC
DLSF-8A-480V 8A
Indication, Alarm Contacts (50-60 Hz)
Surge Filter, 1Ph, 480 VAC, 16 A, 25 kA+25 kA 8/20 µs L-L, Power & Status 220 – 277 VAC
DLSF-16A-480V 16 A
Indication, Alarm Contacts (50-60 Hz)
Surge Filter, 1Ph, 480 VAC, 20 A, 25 kA+25 kA 8/20 µs L-L, Power & Status 220 – 277 VAC
DLSF-20A-480V 20 A
Indication, Alarm Contacts (50-60 Hz)
65 67.5 0.8Nm
0.1 - 4mm2
Installation Details
All installation work must be carried out by licensed electrical personnel in accordance with local
standards and regulations.
The power must be disconnected. Ensure no dangerous voltages exist prior to commencing
installation work.
LINE
(exposed)
L1 L2
Alarm
Contacts
☺
POWER
STATUS
ALARM
CONTACTS
E1 E2
EQUIPMENT
(protected)