E5 J Temperature Controller: Operation Manual
E5 J Temperature Controller: Operation Manual
Operation Manual
Cat. No. Z103-E3-1
Notice:
OMRON products are manufactured for use according to proper procedures by a qualified operator
and only for the purposes described in this manual.
The following conventions are used to indicate and classify precautions in this manual. Always heed
the information provided with them. Failure to heed precautions can result in injury to people or dam-
age to the product.
! DANGER Indicates information that, if not heeded, is likely to result in loss of life or serious
injury.
! WARNING Indicates information that, if not heeded, could possibly result in loss of life or
serious injury.
! Caution Indicates information that, if not heeded, could result in relatively serious or mi-
nor injury, damage to the product, or faulty operation.
Visual Aids
The following headings appear in the left column of the manual to help you locate different types of
information.
Note Indicates information of particular interest for efficient and convenient operation
of the product.
1, 2, 3... 1. Indicates lists of one sort or another, such as procedures, checklists, etc.
OMRON, 1998
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any
form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permis-
sion of OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is
constantly striving to improve its high-quality products, the information contained in this manual is subject to change
without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no
responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the informa-
tion contained in this publication.
v
TABLE OF CONTENTS
SECTION 1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1-1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1-2 Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1-3 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
SECTION 2
Sensor and Mode Settings . . . . . . . . . . . . . . . . . . . . . . . . 9
2-1 Disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2-2 Output Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2-3 Internal Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
SECTION 3
Settings Before Operation . . . . . . . . . . . . . . . . . . . . . . . . . 17
3-1 Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3-2 Setting Flowchart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3-3 List of Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3-4 Parameters on Display Level 0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3-5 Parameters on Display Level 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
SECTION 4
Fuzzy Self-tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4-1 Fuzzy Self-tuning Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
4-2 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4-3 Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
SECTION 5
Installation and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
5-1 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5-2 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5-3 Terminal Arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
SECTION 6
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
6-1 Error Display and Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
6-2 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
SECTION 7
Event Input Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
7-1 Event Input Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
SECTION 8
Heater Burnout Detection . . . . . . . . . . . . . . . . . . . . . . . . . 49
8-1 Heater Burnout Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
8-2 Heater Burnout Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
8-3 Wiring the Current Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
8-4 Heater Burnout Alarm Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
SECTION 9
Engineering Level Settings . . . . . . . . . . . . . . . . . . . . . . . . 55
9-1 Engineering Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
9-2 Engineering Level Parameter List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
9-3 Engineering Level Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
vii
TABLE OF CONTENTS
SECTION 10
Auto-tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
10-1 Starting Auto-tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
10-2 Conditions that Prevent Auto-tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
10-3 Force-ending Auto-tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
10-4 Changing Parameters during Auto-tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Appendices
A Dimensions/Mounting Holes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
viii
About this Manual:
This manual describes the installation and operation of the Thermac E5J Temperature Controller and
includes the sections described below.
Please read this manual carefully and be sure you understand the information provided before attempting
to install and operate the Thermac E5J Temperature Controller.
Section 1 describes the specifications and basic features of the Thermac E5J Temperature Controller.
Section 2 describes the sensor and mode settings of the Thermac E5J Temperature Controller that are
necessary before turning on the Thermac E5J Temperature Controller.
Section 3 describes the settings of the Thermac E5J Temperature Controller that are necessary before
operating the Thermac E5J Temperature Controller.
Section 4 provides the procedures required to adjust all PID constants using fuzzy self-tuning according
to the characteristics of the device for ideal temperature control.
Section 5 describes the installation and wiring of the Thermac E5J Temperature Controller.
Section 6 describes the troubleshooting of the Thermac E5J Temperature Controller.
Section 7 describes how the event input function of the Thermac E5J Temperature Controller works.
Section 8 describes the basic features of heater burnout detection and necessary steps that should be
taken at the time of heater burnout, as well as the method of obtaining heater burnout alarm values.
Section 9 describes the parameters that can be changed on the engineering level. These parameters
should be changed only when the values set before shipping do not suit the application. After these pa-
rameters are changed on the engineering level, record the contents of the changes for your future refer-
ence.
Section 10 describes how to execute auto-tuning.
The Appendix provides the dimensions and mounting specifications for the various Thermac E5J Tem-
perature Controller Units.
! WARNING Failure to read and understand the information provided in this manual may result in
personal injury or death, damage to the product, or product failure. Please read each
section in its entirety and be sure you understand the information provided in the section
and related sections before attempting any of the procedures or operations given.
ix
SECTION 1
Introduction
This section describes the specifications and basic features of the Thermac E5J Temperature Controller.
1-1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1-2 Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1-3 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1-3-1 Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1-3-2 Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1
Models Section 1-2
1-1 Features
The basic features of the Thermac E5J Temperature Controller are outlined
below.
Fuzzy Self-tuning When using a conventional temperature controller for ideal temperature control,
it is necessary to adjust the PID constants of the temperature controller accord-
ing to the controlled device. The Thermac E5J Temperature Controller incor-
porates a fuzzy self-tuning function, thus allowing ideal temperature control
without any adjustment of the PID constants. The user needs only to set the
E5J to the desired temperature for ideal temperature control.
Auto-tuning Auto-tuning is also available. It is useful when appropriate results are not
obtained through fuzzy self-tuning. (Refer to Section 10 Auto-tuning.)
Event Input Function It is possible to select a set point out of a maximum of two set values on the
E5CJ-B and four set values on the E5AJ-B via their event input terminals
from the PCs connected to these Temperature Controllers. The control opera-
tion of the E5AJ-B via can be stopped with an event input signal.
Watertight Construction The E5J can be used in places where water is sprayed onto the E5J, be-
cause the front panel of the E5J assures IP54 when the E5J is panel-
mounted (except for front panel of the E5CJ, which assures IP50). If greater wa-
tertightness is required, use the Y92A-N, a dedicated watertight cover (sold
separately).
Advanced PID The E5J incorporates an advanced PID function, which is also incorporated by
the Thermac X Temperature Controller. The advanced PID function prevents
temperature overshooting the moment the Temperature Controller starts oper-
ating, assures a short startup time, and performs ideal temperature control by
quickly responding to external disturbances.
Output Units The E53-R Relay Unit, E53-Q, E53-Q3, and E53-Q4 Voltage Output Units for
driving SSRs, and E53-C3, E53-C3D, E53-V34, and E53-V35 Linear Output
Unit can be connected to any E5J Temperature Controller (except the E5CJ)
with ease according to the desired output configuration and application.
1-2 Models
The thermocouples and platinum resistance thermometers listed in the follow-
ing table can be connected to any Thermac E5J Temperature Controller.
2
Models Section 1-2
96 X 96mm
Alarm 2 relay output points with heater burnout alarm (see note 1)
Event input 2 points (set point selection, RUN/STOP) (see note 2)
Control output Replaceable Output Unit (sold separately)
Model Communications function --- E5AJ-A2HB
RS-232C E5AJ-A2H01
RS-422 E5AJ-A2H02
RS-485 E5AJ-A2H03
Communications Board add-on model E5AJ-A2HM
Note 1. No heater burnout alarm is output if the E53-C3 Current Output Unit is used
with the E5AJ.
2. The event input function is not incorporated by models that have a commu-
nications function.
48 X 96mm
Alarm 2 relay output points with heater burnout alarm (see note 1)
Event input 2 points (set point selection, RUN/STOP) (see note 2)
Control output Replaceable Output Unit (sold separately)
Model Communications function --- E5EJ-A2HB
RS-232C E5EJ-A2H01
RS-422 E5EJ-A2H02
RS-485 E5EJ-A2H03
Communications Board add-on model E5EJ-A2HM
Note 1. No heater burnout alarm is output if the Linear Output Unit is used with the
E5EJ.
2. The event input function is not incorporated by models that have a commu-
nications function.
3
Specifications Section 1-3
48 X 48mm
1-3 Specifications
1-3-1 Ratings
E5J
Item Specification
Supply voltage 100 to 240 VAC, 50 or 60 Hz 24 V AC/DC,
50 or 60 Hz
Operating voltage range 85 to 110% of supply voltage
Power consumption E5AJ 10 VA (at 100 VAC) to 10 VA (at 24 VAC)
14 VA (at 240 VAC) 6 W (at 24 VDC)
C)
E5EJ 10 VA (at 100 VAC) to
14 VA (at 240 VAC)
E5CJ 10 VA (at 100 VAC) to
12 VA (at 240 VAC)
Input Thermocouples (K, J, T, L, U, and N) and platinum
resistance thermometers (JPt100 and Pt100)
CT input Dedicated CT (E54-CT1 or E54-CT3)
Control output E5AJ/E5EJ Replaceable Output Unit (sold separately)
E5CJ Relay output SPST-NO, 3 A at 250 VAC (resistive load)
Voltage output 20 mA at 12 VDC (with short-circuit protection)
Current output 4 to 20 mA DC with a load of 600 Ω max. and a
resolution of approx. 2600
Control mode ON/OFF or advanced PID with fuzzy self-tuning and
auto-tuning
Alarm output E5AJ/E5EJ 2 SPST-NO relay output points, 3 A at 250 VAC
(resistive load)
E5CJ 2 SPST-NO relay output points (with the same common),
1 A at 250 VAC (resistive load)
Setting method Digital setting with Up Key and Down Key
4
Specifications Section 1-3
Item Specification
Indication method E5AJ All digital indication (PV: Red, 15 mm; SV: Green,
10.5 mm)
E5EJ All digital indication (PV: Red, 14 mm; SV: Green,
9.5 mm)
E5CJ All digital indication (PV: Red, 12 mm, SV: Green 8.0
mm)
Event input Contact input: ON: 1 kΩ max. OFF: 100 kΩ min.
No-contact input: ON: residual voltage of 3 V max; OFF:
current leakage of 1 mA max.
Other function • Key protect
• Cooling operation/Heating operation
• Heater burnout alarm
Model with event input (E5J-B)
• Set point selection (set point x 2)
• RUN/STOP (E5AJ-B and E5EJ-B only)
Ambient operating temperature –10°C to 55°C (with no condensation)
Ambient operating humidity 35 to 85%
Storage temperature –25°C to 65°C (with no condensation)
5
Specifications Section 1-3
1-3-2 Characteristics
E5J
Item Specification
Indication accuracy ±0.5% or ±1°C whichever is larger ± 1 digit max.
Thermocouple K, T, or N at a temperature of –100°C; thermocouple U at ± 2°C ± 1
digit max.
Hysteresis (for ON/OFF control) 0.1 to 999.9°C/° F (in units of 0.1°C/°F)
Proportional band 0.1 to 999.9°C/°F (in units of 0.1°C/°F)
Integral time 0 to 3999 s (in units of 1 s)
Derivative time 0 to 3999 s (in units of 1 s)
Control period Relay or voltage output:1 to 99 s (in units of 1 s)
Manual reset value (I = 0) 0.0 to 100.0% (in units of 0.1%)
Alarm setting range With K, J, L, or N input: –1999 to 9999° C/°F (in units of 1°C/°F)
With JPt100, Pt100, T, or U input: –199.9 to 999.9° C/°F (in units of 0.1°C/°F)
Sampling period 500 ms
Output refresh period 500 ms
Display refresh period 500 ms
Insulation resistance 20 MΩ min. at 500 VDC (measured with an Output Unit)
Dielectric strength 2000 VAC, 50/60 Hz for 1 min. between charged terminals different from each other
in polarity
Vibration Malfunction 10 to 55 Hz, 9.8 m/s2 (1G) 10 min. in X, Y, and Z directions
resistance
i Destruction 10 to 55 Hz, 19.6 m/s2 (2G) 2 hr. in X, Y, and Z directions
Shock resistance Malfunction 196 m/s2 (20G) 3 times each in 3-axis 6 directions (98 m/s2 (10G) for the relay)
Destruction 294 m/s2 (30G) 3 times each in 3-axis 6 directions
Weight E5AJ Approx. 360 g; mounting bracket: approx. 65 g
E5EJ Approx. 280 g; mounting bracket: approx. 65 g
E5CJ Approx. 170 g; adapter: approx. 10 g
Enclosure rating Front panel: E5AJ/E5EJ: IEC standard IP54
E5CJ: IEC standard IP50 (see note 1)
Rear case: IEC standard IP20
Terminals: IEC standard IP00
Memory Protection Non-volatile memory
EMC Emission Enclosure: EN55011 Group 1 class A
Emission AC Mains: EN55011 Group 1 class A
Immunity ESD: EN61000-4-2: 4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Immunity RF-interference: ENV50140: 10 V/m (amplitude modulated,
80 MHz to 1 GHz) (level 3)
10 V/m (pulse modulated,
900 MHz)
Immunity Conducted Disturbance: ENV50141: 10 V (0.15 to 80 MHz) (level 3)
Immunity Burst: EN61000-4-4: 2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
Approved standards UL1092, CSA C22.2 No. 142
Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC1010-1) (see note 2)
Conforms to VDE0106/part 100 (Finger Protection), when the separately-ordered
terminal cover is mounted.
Note 1. The model numbers of the exclusive watertight covers conforming to IP66,
NEMA4 are as follows:
For E5AJ: Y92A-96N; For E5CJ: Y92A-48N; For E5EJ: Y92A-49N
2. Basic insulation is between the input and output.
6
Specifications Section 1-3
Note 1. Use the K2CU-FA-GS (with gate input terminals) for the detection of
three-phase heater burnout.
2. The heater burnout alarm is always OFF if the alarm is set to 0.0 A and al-
ways ON if the alarm is set to 50.0 A.
3. No heater burnout detection or heater current value measurement is pos-
sible if the control output is ON for less than 190 ms.
Model with Refer to the E5AJ/E5EJ Communications Manual (Z102) for details.
Communications Function
Item Specification
Interface RS-232C, RS-422, RS-485
Communications method Half duplex
Synchronization method Start-stop synchronization
(non-synchronization)
Communications speed 1200, 2400, 4800, 9600, and 19200 bps
Communications Writing to Set point, alarm value, heater burnout alarm
item Thermac J value, proportional band, derivative time,
integral time, and input shift value
Reading from Process value, set point, alarm value, heater
Thermac J burnout alarm value, heater current value,
proportional band, derivative time, integral
time, output value, input shift and error code
7
SECTION 2
Sensor and Mode Settings
This section describes the sensor and mode settings of the Thermac E5J Temperature Controller that are necessary before
turning on the Thermac E5J Temperature Controller.
2-1 Disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2-2 Output Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2-3 Internal Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2-3-1 Internal Switch Positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2-3-2 Input Type Selector Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2-3-3 Alarm Mode Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2-3-4 Standby Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2-3-5 Function Selector Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2-3-6 Key Protection Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
9
Output Units Section 2-2
2-1 Disassembly
Before turning on the E5J, set its sensor type and control mode with the inter-
nal selectors. Refer to the following illustrations for disassembling the E5J to
access the internal switch settings.
Hook
After setting the internal switches, insert the internal mechanism into the case
until the front panel snaps with the hook.
Bracket
Output Unit
Socket
After mounting the Output Unit, be sure to secure it with the mounting bracket
provided with the Output Unit.
If the E53-C3, E53-C3D, E53-V34, and E53-V35 Linear Output Unit is used for
control output, no heater burnout alarm is available.
Each Voltage Output Unit is used for driving an SSR as shown in the following
illustrations.
10
Internal Switch Settings Section 2-3
+ +
LOAD SSR INPUT
– –
+ +
PROTECT ALL
Key protection
switch OFF
INPUT SP FUNCTION
Input type Function selector
selector
E5EJ
ALM2
Top view Alarm mode selector 2
PROTECT
Key protection ALL
switch
OFF
ALM1
Alarm mode SP
selector 1
INPUT FUNCTION
Input type selector Function selector
11
Internal Switch Settings Section 2-3
E5CJ
Top view ALM2
Alarm mode selector 2 Bottom view
ALM1 PROTECT
Alarm mode selector 1 Key protection
switch SP
INPUT
OFF
Input type selector
ALL
FUNCTION
Function selector
Note The E5CJ with no alarm does not incorporate ALM1 or ALM2.
INPUT
Note The resistance of the JPt100 at a temperature of 100°C is 139.16 Ω and that of
the Pt100 at a temperature of 100°C is 138.50 Ω.
1, 2, 3... 1. To use Fahrenheit, set function selector 4 to ON, which is usually set to OFF.
2. Insert the internal mechanism into the case.
3. Turn on the E5J so that d-u will be displayed on the process value display.
Then press the Up Key so that f will be displayed on the set value display.
4. Turn off the power in two seconds.
5. Draw the internal mechanism from the case and set function selector 4 to
OFF and turn on the E5J.
12
Internal Switch Settings Section 2-3
ALM2 ALM1
If the alarm mode switch is set to 1 to 7, the alarm value is set with the deviation
width from the set point as shown in the following diagram.
Alarm value
10°C/°F
If the alarm mode switch is set to 8 or 9, the alarm value is set with the absolute
value from 0°C/°F as shown in the following diagram.
Alarm value
110°C/°F
0°C/°F
13
Internal Switch Settings Section 2-3
Alarm point
Alarm output
It is possible to change the alarm hysteresis (set to 0.2°C before shipping) on the
engineering level.
2-3-5 Function Selector Settings
All the function selector pins are factory-set to OFF.
ON
OFF
To set these pins to
FUNCTION ON, use a small flat-
blade screwdriver.
14
Internal Switch Settings Section 2-3
SP OFF ALL
PROTECT
Mode Protection
SP Prohibits all set value changes except the set point. The Level
Key is not available. The Down Key and Up Key are available
only for set point setting.
OFF All keys are available.
ALL Prohibits all set value changes. The Level Key, Down Key, and
Up Key are not available.
15
SECTION 3
Settings Before Operation
This section describes the settings of the Thermac E5J Temperature Controller that are necessary before operating the
Thermac E5J Temperature Controller.
3-1 Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3-2 Setting Flowchart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3-3 List of Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3-4 Parameters on Display Level 0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3-5 Parameters on Display Level 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
17
Nomenclature Section 3-1
3-1 Nomenclature
The following is the front panel of the E5AJ-A2HB. The front panels of the E5EJ
and E5CJ are similar to the front panel of the E5AJ-A2HB.
Process Value (PV) display
Displays not only the process
value but also indicates the pa-
Stop indicator rameter being displayed on the
Lit when the E5J is not operating. SV display and error messages. Set Value (SV) display
The E5CJ does not incorporate this Displays the set temperature
indicator. and other parameters.
Note Refer to the E5AJ/E5EJ Communications Manual for the operation of E5J
models incorporating a communications function.
18
Setting Flowchart Section 3-2
Display Level 0 Parameters that are changed frequently are ranked as display level 0 parame-
ters.
Display level 1 Parameters that are not changed frequently are ranked as display level 1 pa-
rameters.
Engineering Level Parameters that are changed with only a few applications are ranked as engi-
neering level parameters.
OFF ON
Level Key
Press for 1 s min.
Display level 0 Display level 1
Level Key
Press for 1 s min.
19
List of Parameters Section 3-3
SP-0 Set point 0 Set point lower limit 0 For models incorporating an
to set point upper event input function.
limit (°C/°F)
SP-1 Set point 1 Set point lower limit 0 For models incorporating an
to set point upper event input function.
limit (°C/°F)
SP-2 Set point 2 Set point lower limit 0 For models incorporating an
to set point upper event input 2 function.
limit (°C/°F) Displayed and can be set if
the default value is changed
on the engineering level.
SP-3 Set point 3 Set point lower limit 0 For models incorporating an
to set point upper event input 2 function.
limit (°C/°F) Displayed and can be set if
the default value is changed
on the engineering level.
in-S Input shift value –199.9 to 999.9 °C/°F 0.0 Displayed and can be set if
the default value is changed
on the engineering level.
20
List of Parameters Section 3-3
oFr Manual reset value 0.0 to 100.0 % 50.0 Displayed and can be set if
the integral time is set to 0
when the E5J is in
advanced PID operation.
Note The value in the parentheses is the E5J--F setting before shipping.
21
Parameters on Display Level 0 Section 3-4
(Alarm 1 setting)
(Alarm 2 setting)
Set Point Setting (°C or °F) It is possible to alter the present set point (SP0 or SP1).
al1 and al2 (°C or °F) The alarm mode is factory-set to the upper limit alarm (deviation). It is possible to
change the alarm mode with the alarm mode selector. Refer to 2-3-3 Alarm
Mode Setting. The alarm value can be set with the deviation width or absolute
value according to the alarm mode.
Deviation alarm Absolute value alarm
Upper and lower limit alarm, upper limit Absolute value upper limit alarm and
alarm, lower limit alarm and upper and absolute value lower limit alarm.
lower limit range alarm.
Set with the deviation width from Set with the absolute value from 0°C/°F.
the set point
Alarm value
Alarm value 110°C/°F
10°C/°F
0°C/°F
Set point (SP) 100°C/°F
22
Parameters on Display Level 1 Section 3-5
(Hysteresis setting)
Displays if I is 0.
(Manual reset value
setting)
23
Parameters on Display Level 1 Section 3-5
o Output Value Display The output value is displayed within a range of 0.0% to 100.0%.
cp Control Period Setting It is possible to set the control period within a range of 1 to 99 s. The control peri-
od is the period required by the E5J to turn ON and OFF its relay output or volt-
age output. The ON period increases in proportion to the output value. If the con-
trol period is short, smooth control operation will be possible although a short
control period shortens the life of the relay if relay output is used. Therefore, the
control period should not be less than 20 s if relay output is used. The following
are output examples with an output value of 50.0 %.
5s 10 s
ON ON
OFF OFF
hys Hysteresis Setting (°C It is possible to set the hysteresis for the E5J in ON/OFF control operation with-
or °F) in a range of 0.1° to 999.9°C/°F.
Hysteresis
Heating
control ON
(Reverse) OFF
Low temperature Set point High temperature
Hysteresis
Cooling
ON
control
(Normal) OFF
Low temperature Set point High temperature
sp0, sp1, sp2, and sp3 It is possible to set sp-0 (set point 0), sp-1 (set point 1), sp-2 (set point 2), and sp-3
(E5J-B Only) (set point 3) all in Celsius or Fahrenheit regardless of the set point presently se-
lected. To select the set point, open or short-circuit terminals EV1 and EV2. Re-
fer to Section 7 Event Input Function for details.
in-s Input Shift Value It is possible to set the input shift value within a range of –199.9° to 999.9°C/°F.
When an input shift value is set, the process value will be the input value added
with the shift value.
Example Input Input shift value Process value
100°C 0 (no compensation) 100°C
10.0 (compensation value) 110°C
–10.0 (compensation value) 90°C
After the input shift value is set, the it is effective even if the input shift value dis-
play is turned off on the engineering level.
ct Heater Current Value It is possible to set the heater current value within a range of 0.0 to 55.0 A. If the
Display (E5J-H Only) current value exceeds 55.0 A, ffff will be displayed on the set value display.
The heater current will be processed and displayed if the control output is ON.
hb Heater Burnout Alarm It is possible to set the heater burnout alarm value within a range of 0.0 to 50.0 A,
Value Setting (E5J-H which will be used to detect heater burnout. If the heater burnout alarm value is
Only) set to 0.0 A, the heater burnout alarm output will be always OFF. If the heater
burnout alarm value is set to 50.0 A, the heater burnout alarm output will be al-
ways ON. Refer to Section 8 Heater Burnout Detection for details.
When the E5J is in advanced PID with fuzzy self-tuning mode, the following
parameters (p, i, d, ofr) will not be displayed (i.e., there is no need to set the
following parameters). The fuzzy self-tuning always adjusts the PID constants to
the most suitable values according to the characteristics of the controlled de-
vice.
24
Parameters on Display Level 1 Section 3-5
p Proportional Band Setting It is possible to set the proportional band within a range of 0.1 to 999.9°C/°F.
i Integral Time Setting It is possible to set the integral time within a range of 0 to 3999 s.
d Derivative Time Setting It is possible to set the derivative time within a range of 0 to 3999 s.
ofr Manual Reset Value It is possible to set the necessary output value when the E5J is in constant op-
Setting eration within a range of 0.0% to 100.0%. The E5J will be balanced with a devi-
ation between the set point and process value in P or PD control mode. This
deviation is called offset. The offset can be removed by changing the manual
reset value.
25
SECTION 4
Fuzzy Self-tuning
This section provides the procedures required to adjust all PID constants using fuzzy self-tuning according to the characteris-
tics of the device for ideal temperature control.
27
Fuzzy Self-tuning Operation Section 4-1
Set point
Max. tempera- P X 1.27
ture slope R
In step response tuning, control is completely imposed step-
Tuning at startup wise to measure the maximum temperature slope (R) and
dead time (L), and the most ideal PID constants for the de-
vice are obtained from R and L.
Dead time L
Note Be sure to turn on the power supply to the load either before or simultaneously
with the start of Temperature Controller operation. When using the E5AJ-A2HB
or E5EJ-A2HB, you can change the RUN/STOP setting to RUN via event input
2 after supplying power to the load.
Dead time will be measured from the time the Temperature Controller starts
operating. If a load such as a heater is turned on after the Temperature Control-
ler is turned on, dead time longer than the actual value will be measured and
inappropriate PID constants will be obtained. If an extremely large amount of
dead time is measured, the control amount will be set to 0% for a short period of
time before being returned to 100%, and the constants will then be retuned.
Retuning is performed only for large amounts of dead time, so be sure to follow
the precaution given above when starting operation.
28
Fuzzy Self-tuning Operation Section 4-1
SRT Startup Condition SRT will be ON if the following conditions are satisfied simultaneously when the
Temperature Controller is turned on or the set point is changed.
At the time the Temperature Controller At the time set point is changed
starts operating
1) The set point at the time the 1) The new set point is different from
Temperature Controller starts operating the set point used at the time SRT
is different from the set point used at was executed last (see note).
the time SRT was last executed (see 2) The set point changing range is
note). larger than the present
2) The difference between the set point proportional band value (P) x 1.27
and the process value at the time the + 4.
Temperature Controller starts operating 3) The process value is in stable
is larger than the present proportional condition before the set point is
band value (P) x 1.27 + 4. changed.
3) The process value at the time the 4) A larger set point value is set in
Temperature Controller starts operating reverse operation and a smaller
is smaller than the set point in reverse set point is set in normal operation.
operation and larger than the set point
in normal operation.
Note The last SRT-executed set point is set to 0 before shipping and when changing
from advanced PID control to advanced PID control with fuzzy self-tuning.
Imposition Completion In order to prevent overshooting, the step controlled amount must be imposed
Condition of Step Control continuously only while the present deviation is the same as or greater than the
Amount
value obtained from the proportional band (P)1.27. The step control will not be
applied when the deviation becomes smaller than this value.
PID Constant Refreshing If the step control amount is applied before the maximum temperature slope (R)
Conditions is obtained, SRT will not renew any PID constant. If the proportional band ob-
tained from the R and L values that were measured before the imposition had
been completed is larger than the present proportional band, the PID constants
will be renewed because the measured value is in the direction towards the suit-
able proportional band value, and the set point at that time will be the SRT-
executed set point.
DT at the Time of Operation If there is overshooting at the time the Temperature Controller restarts operating
Start and Set Value Change after SRT has been executed, DT adjusts the PID constants so that the set point
response waveform will be as close as possible to the most ideal response wa-
veform after it is deemed that there has been a characteristics change in the con-
trol system.
Set point
Stability judge-
ment time
The set point response waveform
at the time the Temperature Con-
Measurement of troller restarts operation will be
set point response closer to the most ideal response
waveform
waveform.
PID before tuning PID after tuning
29
Fuzzy Self-tuning Operation Section 4-1
DT at the Time of External After the process value reaches the set point and becomes stable, if the process
Disturbance Response value is disturbed and the disturbance exceeds the stable range, the distur-
bance is regarded as external disturbance At the time of disturbance, DT mea-
sures the external disturbance waveform and adjusts the PID constants so that
the external disturbance waveform will be as close as possible to the most ideal
external disturbance response waveform.
Stable range
External disturbance (set to 15.0°C before shipping)
External disturbance
Set point
Stability judge-
ment time
The external disturbance response waveform is approaching to
Measurement of the most ideal response waveform even if the same kind of
external disturbance
response waveform external disturbance reoccurs. The waveform will not, however,
change if the most ideal PID constants are already set.
Startup Conditions of DT DT is used to monitor the control waveform if there is external disturbance or
SRT does not work at the time the Temperature Controller starts operating or at
the time of set point change. If the measured waveform is not an ideal waveform,
DT will be ON. If either one of the following conditions is satisfied, the control
waveform will be monitored.
1, 2, 3... 1. SRT Startup conditions 3 and 4 on page 29 are satisfied but neither 1 nor 2 is
satisfied.
2. There has been an external disturbance exceeding the stable range after
the process value was in stable condition.
Extreme value
Stable range
Set point (set to 15.0°C before shipping)
Measurement of
hunting waveform
Startup Conditions of HT HT will be ON when there is hunting with four or more maximum temperature
values while SRT is not being executed.
Note If the periodic temperature changes of the application exceed the stable range
(set to 15.0°C at the factory) due to continuous external disturbance (i.e., the
temperature is affected by an external disturbance before stabilizing after a pre-
vious external disturbance (refer to figure A below)), the user should change the
stable range to a value greater than the temperature changing range, otherwise
30
Troubleshooting Section 4-2
HT may change the PID constants even though the PID constants are ideal for
the control system. Refer to 9-1 Engineering Level for details.
External disturbance
External disturbance
T1<T2
T1 T2
4-2 Troubleshooting
Fuzzy self-tuning may not exhibit its full capability due to the characteristics and
conditions of the controlled object.
Refer to the following table for troubleshooting when Unit operation is not
smooth.
31
Terminology Section 4-3
4-3 Terminology
If the measured value continuously coincides with the set point, it can be said
that the measured value is stable. The measured value will not continuously
coincide perfectly with the set point if there is noise inference. It is, however, pos-
sible to make the measured value stay within a permissible range called the
stable range. Even if the temperature is within the stable range, the Temperature
Controller may respond to external disturbance or hunting. Therefore, it cannot
be said that the temperature is stable unless the temperature stays within the
stage range continuously for a certain time. This time is called stability judge-
ment time. Like PID constants, stability judgement time is adjusted with fuzzy
self-tuning according to the characteristics of the object to be controlled. Fuzzy
32
Terminology Section 4-3
self-tuning will not be activated if the temperature is stable because the Temper-
ature Controller deems that temperature control is smooth.
Stable range
Set point
Stable range
Stable Stable
4-3-2 Hunting
If the PID constants are not suitable to the controlled device, the measured value
will fluctuate and will not coincide with the set point, this phenomenon is called
hunting. Hunting is also called cycling.
Set point
4-3-5 Interference
If devices, such as heaters, controlled by different temperature controllers are
physically close to one another, the heaters are mutually influenced and the tem-
perature of each heater are affected. This phenomenon is called interference. If
there is serious interference, it will be difficult for each temperature controller to
control the device, and special controlled methods taking this interference into
consideration will be required.
33
Terminology Section 4-3
4-3-6 Startup
Startup means that the Temperature Controller starts operating. The following
conditions are required to operate the Temperature Controller.
• The Temperature Controller must be turned ON.
• No sensor error has occurred.
• If a model with event input 2 is used, event input 2 must be set to RUN.
Event input 2 is set to RUN before shipping.
The Temperature Controller will not start operating until all the above conditions
are satisfied.
34
SECTION 5
Installation and Wiring
This section describes the installation and wiring of the Thermac E5J Temperature Controller.
5-1 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5-1-1 Dimensions and Mounting Holes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5-1-2 Mounting Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5-2 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5-2-1 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5-3 Terminal Arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
35
Installation Section 5-1
5-1 Installation
Install the E5J in the following places.
É
É
Mounting bracket
É
Panel
É
Watertight packing É
E5CJ Open a square hole in the panel to which the E5CJ is to be mounted, mount the
E5CJ, attach the adapter provided with the E5CJ as shown in the following il-
lustration to reduce the space between the E5CJ and panel, and secure the
É
adapter with the tightening screw.
Panel É
É
Adapter
É
É Mounting screw
36
Wiring Section 5-2
5-2 Wiring
Refer to the terminal arrangements to wire the E5J. Before wiring, observe the
following.
1, 2, 3... 1. When connecting extension wires to the thermocouple, use proper compen-
sating lead wires.
2. When connecting extension wires to the platinum resistance thermometer,
use three low-resistance wires of equal resistance.
3. The power supply must not be influenced by noise. If necessary use a noise
filter.
4. All the wires connected to the input circuitry must be separated from the
wires connected to the power supply or output circuitry.
5. Use shielded wires where static inductance noise is present.
6. Twist the input wires evenly and closely if there is any electromagnetic in-
ductance noise.
5-2-1 Connection
With Solderless Terminals Use solderless terminals for M3.5 screws. The terminal screws are M3.5 x 8 self-
up screws.
Solder-dipped Leads It is possible to connect solder-dipped leads to the terminals with ease. The
ÉÉÉ
length of each bare lead wire should be 6 to 8 mm.
ÉÉÉ 6 to 8
37
Terminal Arrangement Section 5-3
38
Terminal Arrangement Section 5-3
2. Only the heater burnout alarm will be output from the alarm output 1 termi-
nals if alarm mode switch 1 is set to 0. Only the temperature alarm will be
output if the heater burnout alarm value is set to 0.0 A.
E5CJ Standard Model
Control output (OUT)
+
10
See note 1. 12 VDC
Voltage Output Unit
– (20 mA max.)
Event input 1 (EV1) Exter- 9
nally selects the set point. +
10 Current Output Unit
open
4 to 20 mA DC
–
short-circuit 9 (with a load of 600 Ω max.)
100 to 240 VAC, 50 or 60 Hz, 12 VA
or 5 10 Relay Output Unit
14 + 3 A (resistive load)
24 VAC, 50 or 60 HZ, 10 VA at 250 VAC
24 VDC 6 W 4 9
(Heater burnout alarm 13 –
See note 2. and temperature alarm) A
3 8
Alarm (ALM1) 12
output 1 – B
2 7
Alarm output 2 11
+ B
1 6
1 A (resistive load)
at 250 VAC
Use the E54-CT1 with a hole
CT diameter of 5.8 mm or E54-CT3 with a hole
diameter of 12 mm (both sold separately).
Note 1. The event input terminals and voltage output and current output terminals
are not insulated.
2. Only the heater burnout alarm will be output from the alarm output 1 termi-
nals if alarm mode switch 1 is set to 0. Only the temperature alarm will be
output if the heater burnout alarm value is set to 0.0 A.
3. A simple model with no alarm does not incorporate any event input or alarm
output. A simple model with an alarm function does not incorporate any
event input.
39
SECTION 6
Troubleshooting
This section describes the troubleshooting of the Thermac E5J Temperature Controller.
41
Troubleshooting Section 6-2
Note If the input is within the possible controlling range but exceeding the possible
display range (–1999 to 9999), (((( will be displayed if the value is smaller than
–1999 and )))) will be displayed if the value is larger than 9999, at which time, the
control output and alarm output will work normally.
6-2 Troubleshooting
Refer to the following table for troubleshooting.
42
Troubleshooting Section 6-2
43
SECTION 7
Event Input Function
This section describes how the event input function of the Thermac E5J Temperature Controller works.
45
Event Input Function Section 7-1
EV1
Short-circuit
COM
Set point 1
(SP1)
Displays the set point
currently selected.
SP2 and SP3 can be displayed
Set point 2 only when the set point selec-
(SP2) tion is selected with the event
input 2 selection (set to RUN/
STOP before shipping) on the
Set point 3 engineering level. Refer to Sec-
(SP3) tion 9 Engineering Level Set-
tings for details.
The set point on display level 0 and that on display level 1 are synchronized. In
the above example, if the set point on display level 0 is changed from 200°C to
250°C, the set point 1 value on display level 1 will also change to 250°C.
46
Event Input Function Section 7-1
+24 V
Internal circuitry
470 Ω
3 kΩ
EV* Flow current:
7 mA approx.
VF = 1.2 VF = 0.6
COM
0V
COM COM
ON: A resistance of 1 kΩ max. ON: A residual voltage of 3 V max.
OFF: A resistance of 100 kΩ min. OFF: A current leakage of 1 mA max.
The following table lists the event input terminal numbers for each model.
Model E5AJ/E5EJ E5CJ
Input terminal
EV1 20 14
EV2 19 ---
COM 17 13
47
SECTION 8
Heater Burnout Detection
This section describes the basic features of heater burnout detection and necessary steps that should be taken at the time of
heater burnout, as well as the method of obtaining heater burnout alarm values.
49
Heater Burnout Procedures Section 8-2
50
Heater Burnout Alarm Value Section 8-4
To heater
AC power supply
CT
CT
To the CT input terminals of the
E5J
If the difference between the normal heater current value and heater burnout
current value is comparatively small, heater burnout detection will not be stable.
For stable detection, the difference must be 1.0 A minimum if the heater current
consumption is less than 10.0 A and it must be 2.5 A minimum if the heater cur-
rent consumption is 10.0 A or more.
The heater burnout alarm value can be set within a range of 0.0 to 50.0 A. If the
alarm value is set to 0.0 A or 50.0 A, no heater burnout detection is possible. The
alarm output is always OFF if the alarm value is set to 0.0 A and always ON if the
alarm value is set to 50.0 A.
51
Heater Burnout Alarm Value Section 8-4
The normal heater current value should be 50.0 A max. The heater current value
can, however, display up to 55.0 A. If the current value exceeds 55.0 A, CT input
overflow will result and ffff will be displayed.
CT input
overflow
200 VAC
Normal heater
current value
CT
200 VAC
Heater burnout
current value CT
Disconnect
Example 2 In this example, 400-W, 1700-W, and 2000-W heaters at 200 VAC are con-
nected in parallel and the difference between the normal current value and heat-
er burnout current value is less than 2.5 A.
1, 2, 3... 1. Obtain the normal current value and heater burnout current value in ad-
vance as follows:
Normal current = (400 + 1700 + 2000) 200 = 20.5 A
Heater burnout current = 20.5 – 400 200 = 18.5 A
Normal current – heater burnout current = 20.5 – 18.5 = 2.0 A (Stable detec-
tion is not possible because the value is not 2.5 A or more.)
2. For stable hater burnout detection, in such a case, increase the number of
turns of the wire passing through the CT as if apparent current value in-
52
Heater Burnout Alarm Value Section 8-4
Heater wire
3. Obtain the heater burnout alarm value using the method in example 1.
Apparent normal current = (400 + 1700 + 2000) 200 x 2 = 41.0 A
Normal heater
current value
53
SECTION 9
Engineering Level Settings
This section describes the parameters that can be changed on the engineering level. These parameters should be changed only
when the values set before shipping do not suit the application. After these parameters are changed on the engineering level,
record the contents of the changes for your future reference.
55
Engineering Level Parameter List Section 9-2
15.0
ALFA Alpha 0.00 to 1.00 0.65
SL-L Set point lower limit Set range lower limit to –200 (–300)
value set point upper limit
value (see note 1).
(°C/°F)
56
Engineering Level Parameter List Section 9-2
57
Engineering Level Parameters Section 9-3
(°C/°F selection)
(Alpha setting)
58
Engineering Level Parameters Section 9-3
rdu °C/°F Selection To change the temperature display unit from °C to °F, press the Up Key so that f
will be displayed in the set value display.
SV SV
c: °C
f: °F
sbit Stop Bit Use this parameter to change the stop bit length.
s.t-b Stable Range (°C/°F) This parameter is used to decide conditions under which fuzzy self-tuning oper-
ates and can be set within a range of 0.1 to 999.9. If the absolute value of the
deviation (the difference between the process value and set point) is within the
stable range, temperature control operation is deemed smooth and fuzzy self-
tuning will not start.
Stable
Set point range
Stable
Fuzzy self-tuning
alfa (α) PID Control Type By adjusting internal parameter α of advanced PID within a range of 0.00 to 1.00,
PID control such as derivative preceding PID or proportional preceding PID (I-
PD) control will be possible.
α = 0.00 (Derivative preceding PID)
Set point
α = 0.65
α = 1.00
(Proportional preceding PID)
To increase the set point response speed, decrease the value of parameter α. If
the value of parameter α is decreased, however, the overshooting value will in-
crease.
59
Engineering Level Parameters Section 9-3
ret Automatic Return of By setting automatic return of display mode, the display will return to the normal
Display Mode (Return Time) operation display (on level 0 displaying the process value or set point) if no key is
operated for the time set with this parameter. The return time can be set within a
range of 0 to 99 s. If the return time is set to 0 s, this function will not work. The
return time is set to 0 s before shipping.
rest Standby Sequence It is possible to select the restart conditions of the standby sequence of the alarm
Reset Method attached with standby sequence. If this parameter is set to 0, the standby se-
quence will restart when the set point, alarm value, or input shift value is
changed or the moment the E5J starts operating including the moment the
E5J is turned on. If this parameter is set to 1, the standby sequence will restart
only the moment the E5J is turned on. The following timing chart is an example
of a lower limit alarm attached with standby sequence.
Alarm point
Set value
change
ins Input Shift Display It is possible to select to display or not to display the input shift function on display
level 1 with this parameter.
alh1 Alarm 1 Hysteresis It is possible to adjust alarm sensitivity with both these parameters within a range
and alh2 Alarm 2 of 0.1 to 999.9. Change the alarm sensitivity of the E5J if the alarm output chat-
Hysteresis ters.
The alarm output will be OFF when the process value is within the alarm hystere-
sis range when the E5J restarts (e.g., when the E5J is turned on).
sll Set Point Lower Limit It is possible to limit the set point changeable range with both these parameters.
Value (°C/°F) and slh Set For example, if the set point lower limit value is set to 0°C and the set point upper
Point Upper Limit Value limit value is set to 400°C, the set point can be changed only between 0°C and
(°C/°F)
400°C.
60
Engineering Level Parameters Section 9-3
eu2 Event Input 2 Type It is possible to select the function of event input 2. If 0 (set point value selection)
Selection is selected, sp2 and sp3 will be displayed on display level 1 and if 1 is selected
RUN/STOP will be selected. When 0 is selected, the set point can be selected
from the following.
EV1 20
EV2 19
COM 17
61
SECTION 10
Auto-tuning
This section describes how to execute auto-tuning.
63
Changing Parameters during Auto-tuning Section 10-4
1, 2, 3... 1. Turn ON pin 3 of the function selector switch to select the advanced PID con-
trol mode (refer to Section 2-3-5).
2. Press the Level Key and the Display Key simultaneously for 1 s or longer to
start auto-tuning.
Auto-tuning SP1
SP0
Set point
Auto-tuning started.
Scale changes disabled here.
64
Appendix A
Dimensions/Mounting Holes
E5AJ
Dimensions
96 x 96 12 98 91 x 91
112
Mounting Holes
+0.8
92 0
92 +0.8
0
92 +0.8
0
120 min.
65
Dimensions/Mounting Holes Appendix A
E5EJ
Dimensions
48 12 98
44
96 112 91
Mounting Holes
+0.6
45 0
+1
(48 x units – 2.5) 0
+0.8 +0.8
92 0
92 0
120 min.
E5CJ
Dimensions
48 x 48 9.5 100
44.8 x 44.8
58
66
Dimensions/Mounting Holes Appendix A
Mounting Holes
+0.6
45 0 +1
(48 x units – 2.5) 0
+0.6
45 0 +0.6
45 0
60 min.
Terminal Covers
112
58
67
Dimensions/Mounting Holes Appendix A
112
68
Index
A E
engineering level
advanced PID alarm hysteresis, 60
function, 2 automatic return of display mode, 60
setting, 14 communications, 59
setting with fuzzy self-tuning, 14 data bit length, 59
input shift display, 60
alarm mode parameters, 19
changing, 22 parameters table, 56
setting. See settings parity check, 59
standby sequence. See settings PID control type, 59
selecting temperature display, 59
auto-tuning settings, 56
force-ending, 64 stable range, 59
parameters, 64 standby sequence reset, 60
preventing, 64 stop bit, 59
starting, 64
event input 2, 33
automatic return of display mode. See engineering level selecting, 61
event input function, 2
parameters, 24
selecting RUN/STOP, 46
C
selecting set point, 46
signal input method, 47
external disturbance, definition, 32
communications function, specifications, 7
D
features, 28
function, 2
69
Index
I set point
See also event input function
adjusting changeable range, 60
installation
setting type, 22
mounting, 36
precautions, 36 settings
integral time range, 25 advanced PID control, 14
alarm mode selection, 13
interference, definition, 33 functions. See functions
internal switches, sensor type and control mode, 10 fuzzy self-tuning, 14
internal switches, 11, 12
key protection switch, 15
K-M
selecting input type, 12
selecting output unit, 10
sensor type and control mode, 10
key protection switch, setting, 15
specifications
manual reset value, 25 general, table, 5
models, 2 operating characteristics, table, 6
Communications Boards, 4 output unit, table, 6
communications function, limitations, 3, 4
standard, 3 SRT. See step response tuning
P
T
parameters
engineering level, 19 terminal arrangement, 38
levels, 19
setting, 19 Terminal Covers, 67
tables, 20 troubleshooting, 30
PID, setting constants, 32 controller and sensor error, 43
table, 42
proportional band range, 25
R W
return time, 60 watertight cover, 2
RUN, selection, 46
wiring
current transformer, 51
precautions, 37
S terminal arrangement, 38, 39
using solder-dipped leads, 37
self-diagnostic function, 42 using solderless terminals, 37
70
Revision History
Operation Manual
A manual revision code appears as a suffix to the catalog number on the front cover of the manual.
Revision
code
The following table outlines the changes made to the manual during each revision. Page numbers refer to the
previous version for manuals designated as E1 revisions.
71
Revision History
72