Temperature Controller TC244CX, TC344CX

Features :
4+4 digits, 7 segment LED dual display
Auto tune/ Self tune PID
PID/ ON - OFF control
TC/ RTD input
Two set points
Field selectable control output (Relay or SSR)
Dwell timer
72 x 72mm 96 x 96mm IDM applicable
Auxiliary output: Relay
Certifications:

Display 4+4 digits, 7 Segment LED dual display


Height of display White display: 16.7mm, Green display : 9mm
AT: Auto Tune OUT 1: ON
LED indication
S:Dwell timer OUT 2: ON
Keys 3 keys of digital setting

Inputs Thermocouple (J, K, T, R, S)/ RTD (PT100)


Resolution
For TC inputs : 0.25% of F.S. ±1°
Indication accuracy For R & S inputs : 0.5% of F.S. ±1° (30 min of warm up time)
For RTD inputs : 0.1% of F.S. ±1° (F.S. = Full scale)
Temperature unit °C/°F selectable
0.2 to 10.0 sec
Sampling time 250 ms

Control output

Relay contact (SPDT) Main Output: NO :10A 250 VAC/ 24 VDC


NO/ NC : 5A/5A 250 VAC/ 24V DC
SSR drive (Voltage pulse) 12 VDC, 50 mA
Auxiliary output
Relay contact (SPDT) Alarm Output: NO :10A 250 VAC/ 24VDC
NO/ NC : 5A/5A 250 VAC/ 24 VDC

1) PID Control with auto tuning


Control action 2) ON-OFF control
3) Heat cool with auto tuning
Proportional band (P) 1.0 to 400.0°C
Integral time (I) 0 to 9999 sec
Derivative time (D) 0 to 9999 sec
Cycle time 0.1 to 99.9 sec
Hysteresis width 0.1 to 99.9°
Manual reset value -19.9 to 19.9°
Heat-cool
Control action PID
Proportional band-cool 0.0 to 400.0°
Cycle time-cool 0.1 to 99.9 sec
Dead band SPLL to SPHL (Programmable)
Settings for alarm output
Modes Deviation, Absolute
Hysteresis 0.1 to 99.9°

www.selec.com 1
Temperature Controller TC244CX, TC344CX

Supply voltage 90 to 270V AC / DC (50 / 60Hz)


Power consumption 5 VA max @ 230V AC

Temperature Operating : 0°C to 50°C; Storage : -20°C to 75°C


Humidity (non - condensing) 95% RH

Mounting Panel
Weight TC244CX - 164 gms ; TC344CX - 217 gms

Cross-wiring old v/s new


TC244CX TC344CX
OLD NEW
OLD NEW

Terminal connections Independent downloader module (IDM)


TC244CX TC344CX

Download
Device

Dimensions (All are in mm)

Front bezel Side view Panel Cutout

MODELS DIM A B C D E F G
TC244CX 76 76 44 67 4.5 69 69
TC344CX 99 99 39 90.5 3.5 92 92

Ordering information
Output 1
Product Code Output 2 Supply Voltage
Relay SSR
TC244CX RELAY (5A) SSR (12V DC) RELAY (5A) 90 to 270V AC / DC
TC344CX RELAY (5A) SSR (12V DC) RELAY (5A) 90 to 270V AC / DC