SMART Current Driver KFD2-SCD2-Ex2.

LK

Features Assembly

• 2-channel isolated barrier


• 24 V DC supply (Power Rail)
Front view
• Current output up to 700 Ω load Removable terminals
blue
• HART I/P and valve positioner
• Line fault detection (LFD)
• Accuracy 0.05 % 1 2 3

• Terminal blocks with test sockets


4 5 6

• Up to SIL2 acc. to IEC 61508 KFD2-SCD2-Ex2.LK

Function LED red:


LB and SC CHK1 CHK2 PWR
LED green:
Power supply

This isolated barrier is used for intrinsic safety applications. It


drives SMART I/P converters, electrical valves, and
positioners in hazardous areas. Switch S1, S2:
Digital signals are superimposed on the analog values at the HART communication 7 8 9
10 11 12
13 14 15
field or control side and are transferred bi-directionally.
Current transferred across the DC/DC converter is repeated at Removable terminals
terminals 1, 2 and 4, 5. green
An open and shorted field circuit presents a high input
impedance to the control side to allow line fault detection by
control system.
If the loop resistance for the digital communication is too low,
an internal resistor of 250 Ω between terminals 8, 9 and 11, 12
is available, which may be used as the HART communication
resistor.
Sockets for the connection of a HART communicator are
integrated into the terminals of the device.
A unique collective error messaging feature is available when
used with the Power Rail system. 2

Connection
122397_eng.xml

KFD2-SCD2-Ex2.LK

1+ 7-
mA
HART
HART

8+
I

I
Date of issue 2015-06-03

9+
2- 250 Ω

4+ 10-
mA
HART
HART

11+
I

II
P

12+
Release date 2015-06-03 16:51

5- 250 Ω

14+
15-
24 V DC

Zone 0, 1, 2 ERR 24 V DC
Div. 1, 2 Power Rail

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
1
Technical data KFD2-SCD2-Ex2.LK

General specifications
Signal type Analog output
Supply
Connection Power Rail or terminals 14+, 15-
Rated voltage Un 20 ... 35 V DC
Ripple within the supply tolerance
Power loss 1.4 W at 20 mA into 10 V (equivalent to 500 Ω) load
Power consumption 1.8 W at 20 mA
Input
Connection terminals 7-, 8+, (9+); 10-, 11+, (12+)
Voltage drop approx. 4 V or internal resistance 200 Ω at 20 mA
Input resistance > 100 kΩ, when wiring resistance in the field > 16 V (equivalent to 800 Ω at 20 mA)
Current 4 ... 20 mA limited to approx. 25 mA
Output
Connection terminals 1+, 2-; 4+, 5-
Current 4 ... 20 mA
Load 100 ... 700 Ω
Voltage ≥ 14 V at 20 mA
Transfer characteristics
Deviation
After calibration at 20 °C (68 °F): ≤ 10 µA incl. non-linearity, calibration, hysteresis, supply and load changes
Influence of ambient temperature ≤ 1 µA/K
Rise time < 100 µs , 10 ... 90 % step change
Electrical isolation
Input/power supply functional insulation, rated insulation voltage 50 V AC
Input/input functional insulation, rated insulation voltage 50 V AC
Directive conformity
Electromagnetic compatibility
Directive 2004/108/EC EN 61326-1:2006
Conformity
Electromagnetic compatibility NE 21:2011
Degree of protection IEC 60529:2001
Protection against electrical shock UL 61010-1:2004
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protection IP20
Mass approx. 150 g
Dimensions 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 in) , housing type B2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection
with Ex-areas
EC-Type Examination Certificate BAS 00 ATEX 7240 , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protection ¬ II (1)G [Ex ia Ga] IIC , ¬ II (1)D [Ex ia Da] IIIC , ¬ I (M1) [Ex ia Ma] I
Output [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Voltage Uo 25.2 V
Current Io 93 mA
122397_eng.xml

Power Po 585 mW
Supply
Maximum safe voltage Um 250 V rms (Attention! The rated voltage can be lower.)
Input
Maximum safe voltage Um 250 V rms (Attention! The rated voltage can be lower.)
Date of issue 2015-06-03

Statement of conformity TÜV 99 ATEX 1499 X , observe statement of conformity


Group, category, type of protection, ¬ II 3G Ex nA II T4 [device in zone 2]
temperature class
Electrical isolation
Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Output/power supply safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Release date 2015-06-03 16:51

Directive conformity
Directive 94/9/EC EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
UL approval
Control drawing 116-0173 (cULus)
IECEx approval IECEx BAS 04.0014
Approved for [Zone 0] [Ex ia] IIC, [Ex iaD], [Ex ia] I

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
2
Technical data KFD2-SCD2-Ex2.LK

General information
Supplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of
Conformity and instructions have to be observed where applicable. For information see www.pepperl-
fuchs.com.
122397_eng.xml
Date of issue 2015-06-03
Release date 2015-06-03 16:51

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
3
Technical data KFD2-SCD2-Ex2.LK

Additional information

Lead monitoring, input characteristics


During lead breakage (> 16 V) in the field the input resistance is > 100 kΩ, the field current is < 1 mA and the red LED is flashing.
During short circuit (< 50 Ω) in the field the input resistance is approx. 20 kΩ, the input current and the field current are
approx. 1 mA and the red LED is flashing.
The voltage drop at the current input (terminals 7-, 8+ and 10-, 11+) is lower than 4 V. Thus, it corresponds to an input resistance
of 200 Ω at 20 mA. The AC input impedance corresponds to the load impedance of the unit.

Adjustment SMART function


When using positioners, which do not meet the HART standard, set the switches to the 1 position (without SMART function)
(see adjustment table).

Switch Position Function S1 S2


Channel 1 Channel 2 1 1
S1.1 S2.1 0 SMART
0 0
S1.2 S2.2 0
All other switch settings non SMART S1.1 S1.2 S2.1 S2.2

If you are using field devices with high input impedance and a control system with low output impedance, check
wheather HART transparency is working correctly.
If necessary, deactivate HART transparency via the DIP switches. If the impedances are combined as described
above, you can for example use the device KCD2-SCD-Ex1 alternatively.

Accessories

Power feed module KFD2-EB2


The power feed module is used to supply the devices with 24 V DC via the Power Rail. The fuse-protected power feed module
can supply up to 150 individual devices depending on the power consumption of the devices. Collective error messages received
from the Power Rail activate a galvanically-isolated mechanical contact.

Power Rail UPR-03


The Power Rail UPR-03 is a complete unit consisting of the electrical insert and an aluminium profile rail 35 mm x 15 mm. To
make electrical contact, the devices are simply engaged.

Profile Rail K-DUCT with Power Rail


The profile rail K-DUCT is an aluminum profile rail with Power Rail insert and two integral cable ducts for system and field cables.
Due to this assembly no additional cable guides are necessary.

Power Rail and Profile Rail must not be fed via the device terminals of the individual devices!
122397_eng.xml
Date of issue 2015-06-03
Release date 2015-06-03 16:51

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091