3. Battery connection
a. While dispatching the equipment from factory, the battery connections
are kept open to reduce internal discharge.
b. Check battery voltage across terminals K20 –J13 and K21 – J13.
c. Voltage in both the cases should be more than 11 V dc. If battery
voltage is less than 11V DC, charge the batteries externally with
external battery charger till voltage across each battery is 12 V dc each
or replace the batteries with new set.
d. After ensuring both battery voltages are more than 11V, check and
firmly connect the 2 pin Green color Male-Female connectors F26 & F27
as per schematic diagram. This will connect the two 12V batteries in
series.
e. Check the voltage across battery terminals to be around 24V
f. Switch ON the MCB: D10-24 MCB for battery
a. Insert 24 pin female socket inside the LV cabinet from bottom thru cut
out provided.
b. Fix the floating gland plate (on the cable) to cover the cut out by inserting
4 nos. M6 threaded welded studs on the floating gland plates through the
4 nos. holes provided at the four corners of the cut out and fix with 4nos.
M6 nuts & the M40 nut on the floating gland plate.
c. Connect 24 pin male plug to 24 pin female socket in the LV
Page 2 of 6
OVR – Three phase mechanically ganged reclosers
Operator’s quick reference guide for OVR-15, OVR-27 & OVR-38
Page 3 of 6
OVR – Three phase mechanically ganged reclosers
Operator’s quick reference guide for OVR-15, OVR-27 & OVR-38
1. Recloser needs auxiliary power for general application. This power is generally derived from the distribution feeder itself
with the help of control transformer or fed from substation auxiliary source. In case of temporary unavailability of auxiliary
power (few hrs. in a day), the recloser is feed via internal battery bank of the LV cabinet.
2. If battery bank is healthy and in fully charge condition i.e. ≥ 24 Vdc, for the power outage can be of < 24Hrs. without any
special attention required.
3. If power outage is for more than 24 Hrs OR typically > 10 CO operations after power failure, then it is considered as long
power outage requiring special attention of batteries.
4. During long outages, the batteries might get drained to such a level that it might go into deep discharge stage i.e. battery
bank voltage goes below 18 V.
5. In this situation recloser will not be able to recharge the batteries automatically and external charging may be required.
Such situation might also damage batteries permanently and thus required to be replaced.
6. To avoid such situation, in case of power outage more than 24 Hrs. switch OFF the battery MCB D10-24. After the power is
resume, switch ON the battery MCB D10-24
7. If power outage is more than a month, then charge the batteries on regular interval externally to keep ensure the battery
bank voltage more than 21 VDC.
Page 4 of 6
OVR – Three phase mechanically ganged reclosers
Operator’s quick reference guide for OVR-15, OVR-27 & OVR-38
E. Trouble shooting
(Please read this table in conjunction with the approved/ as built wiring diagram)
ACU/RER615 No LEDs
does not power (RED/GREEN)
up even after glowing on ACU
main Aux. MCB Switch ON the MCB for ACU (
2 No LEDs on relay HMI MCB for ACU is OFF
is ON & Aux MCBs D10-31 & D10-24)
Supply is glow and LCD screen
available for of RER615 does not
more than 60s light up
The wiring of the 52a/b aux. limit Check, secure and correct the
Wrong recloser
switch may be loose or wrong wiring of 52a/b aux. limit switch
ON/OFF status on
(52a/b aux. limit switch is as per approved /as built
SLD of RER615 HMI
mounted in HV unit) schematic
Page 5 of 6
OVR – Three phase mechanically ganged reclosers
Operator’s quick reference guide for OVR-15, OVR-27 & OVR-38
The data and illustrations are not binding. We reserve the right to modify the contents of this document without prior notice following technical and product developments.
© Copyright 2021 ABB. All rights reserved
— — — —
ABB India Limited ABB SAU ABB de México S.A. de C.V. ABB Inc.
Plot 34 & 79, Norberto Lopez 3600 Av. Central 310 Parque 655 Century Point
MIDC Estate, Satpur, El Jagüel, Buenos Aires Logístico Lake Mary, Florida
Nashik, MH 422007, India B1805ABT, Argentina San Luis Potosí 32746, USA
Phone: +91 253-2201-200 Phone: +54 11 5984 3560 78395, México Phone: +1 407 732 2000
Fax: +91 253-2351-260 Email: [email protected] Phone: +52 55 8525 9486 Email:
Email: [email protected] Email: [email protected] [email protected]
new.abb.com/medium-voltage
Page 6 of 6