7sj600 Catalog Sip E6
7sj600 Catalog Sip E6
7sj600 Catalog Sip E6
SIPROTEC 7SJ600
Numerical Overcurrent, Motor and Overload Protection Relay
Function overview
Feeder protection
• Overcurrent-time protection
• Earth-fault protection
• Overload protection
• Negative-sequence protection
• Cold load pickup
• Auto-reclosure
• Trip circuit supervision
LSP2001-afpen.tif
Motor protection
• Starting time supervision
• Locked rotor
Control functions
• Commands for control of a circuit- 5
Fig. 5/19 SIPROTEC 7SJ600 breaker
numerical overcurrent, motor and overload protection relay • Control via keyboard,
DIGSI 4 or SCADA system
Measuring functions
• Operational measured values I
Description
Monitoring functions
The SIPROTEC 7SJ600 is a numerical • Fault event logging with time stamp
overcurrent relay which, in addition to its (buffered)
primary use in radial distribution networks • 8 oscillographic fault records
and motor protection, can also be em-
• Continuous self-monitoring
ployed as backup for feeder, transformer
and generator differential protection. Communication
The SIPROTEC 7SJ600 provides definite- • Via personal computer and DIGSI 3 or
time and inverse-time overcurrent protec- DIGSI 4 (≥ 4.3)
tion along with overload and negative- • Via RS232 – RS485 converter
sequence protection for a very comprehen- • Via modem
sive relay package. In this way, equipment • IEC 60870-5-103 protocol, 2 kV-isolated
such as motors can be protected against
• RS485 interface
asymmetric and excessive loading. Asym-
metric short-circuits with currents that can Hardware
be smaller than the largest possible load •3 current transformers
currents or phase interruptions are reliably
•3 binary inputs
detected.
•3 output relays
•1 live status contact
Application
Inverse-time characteristics
In addition, invese-time overcurrent
protection characteristics (IDMTL)
LSP2002-afpen.tif
can be activated.
Fig. 5/21
Rear view of flush-mounting housing
Protection functions
Switch-onto-fault protection
If switched onto a fault, instantaneous trip-
ping can be effected. If the internal control
function is used (local or via serial inter-
face), the manual closing function is avail-
able without any additional wiring. If the
control switch is connected to a circuit-
breaker bypassing the internal control
function, manual detection using a binary
input is implemented.
Busbar protection
(Reverse interlocking)
Binary inputs can be used to block any of
the six current stages. Parameters are as-
signed to decide whether the input circuit
is to operate in open-circuit or closed-cir-
5
cuit mode. In this case, reverse interlocking
provides high-speed busbar protection in
radial or ring power systems that are
opened at one point. The reverse inter-
locking principle is used, for example,
in medium-voltage power systems and
in switchgear for power plants, where a
high-voltage system transformer feeds
a busbar section with several medium-
voltage outgoing feeders. Fig. 5/25 Reverse interlocking
Connection diagrams
Fig. 5/29
Fig. 5/30
Connection of 2 CTs only for isolated or
Sensitive earth-fault protection
resonant-earthed (grounded) power systems
(3 -times increased sensitivity)
Technical data
Technical data
EMC tests for interference immunity; type tests Mechanical stress tests
Standards IEC 60255-6; IEC 60255-22 Vibration, shock and seismic vibration
(product standard) During operation
EN 50082-2 (generic standard),
DIN VDE 0435 Part 303 Standards Acc. to IEC 60255-2-1 and
IEC 60068-2
High-frequency test 2.5 kV (peak), 1 MHz, τ = 15 μs,
IEC 60255-22-1, class III 400 surges/s, duration 2 s Vibration Sinusoidal 10 to 60 Hz: ± 0.035 mm
IEC 60255-21-1, class1 amplitude, 60 to 150 Hz: 0.5 g
Electrostatic discharge 4 kV/6 kV contact discharge, IEC 60068-2-6 acceleration
IEC 60255-22-2, class III 8 kV air discharge, both polarities, Sweep rate 1 octave/min
and IEC 61000-4-2, class III 150 pF, Ri=330 Ω 20 cycles in 3 orthogonal axes
Irradiation with radio-frequency Shock Half-sine, acceleration 5 g, duration
field IEC 60255-21-2, class 1 11 ms, 3 shocks in each direction
Non-modulated, 10 V/m, 27 to 500 MHz of 3 orthogonal axes
IEC 60255-22-3 (report) class III
Amplitude modulated, 10 V/m, 80 to 1000 MHz, Seismic vibration Sinusoidal
IEC 61000-4-3, class III 80 % AM, 1 kHz IEC 60255-21-3, class 1, 1 to 8 Hz: ± 3.5 mm amplitude
Pulse modulated, 10 V/m, 900 MHz, repetition IEC 60068-3-3 (horizontal axis)
5 IEC 61000-4-3, class III frequency, 200 Hz, duty cycle 50 % 1 to 8 Hz: ± 1.5 mm amplitude
(vertical axis)
Fast transient interference/bursts 2 kV, 5/50 ns, 5 kHz, burst length 8 to 35 Hz: 1 g acceleration
IEC 60255-22-4 and 15 ms, repetition rate 300 ms, both (horizontal axis)
IEC 61000-4-4, class III polarities, Ri = 50 Ω, duration 1 min 8 to 35 Hz: 0.5 g acceleration
Conducted disturbances induced by 10 V, 150 kHz to 80 MHz, (vertical axis)
radio-frequency fields, 80 % AM, 1 kHz Sweep rate 1 octave/min
amplitude modulated 1 cycle in 3 orthogonal axes
IEC 601000-4-6, class III During transport
Power frequency magnetic field 30 A/m continuous, 50 Hz Vibration Sinusoidal
IEC 61000-4-8, class IV 300 A/m for 3 s, 50 Hz IEC 60255-21-1, class 2 5 to 8 Hz: ± 7.5 mm amplitude;
IEC 60255-6 0.5 mT; 50 Hz IEC 60068-2-6 8 to 150 Hz: 2 g acceleration
Oscillatory surge withstand 2.5 to 3 kV (peak), 1 MHz to Sweep rate 1 octave/min
capability ANSI/IEEE C37.90.1 1.5 MHz, decaying oscillation, 50 shots 20 cycles in 3 orthogonal axes
(common mode) per s, duration 2 s, Ri = 150 Ω Shock Half-sine, acceleration 15 g ,
to 200 Ω IEC 60255-21-2, class 1 duration 11 ms, 3 shocks in each
Fast transient surge withstand 4 to 5 kV, 10/150 ns, 50 surges IEC 60068-2-27 direction of 3 orthogonal axes
capability ANSI/IEEE C37.90.1 per s, both polarities, duration 2 s, Continuous shock Half-sine, acceleration 10 g
(commom mode) Ri = 80 Ω IEC 60255-21-2, class 1 duration 16 ms, 1000 shocks in each
Radiated electromagnetic interfer- 10 to 20 V/m, 25 to 1000 MHz, IEC 60068-2-29 direction of 3 orthogonal axes
ence, ANSI/IEEE C37.90.2 amplitude and pulse-modulated
High-frequency test 2.5 kV (peak, alternating polarity), Climatic stress tests
Document 17C (SEC) 102 100 kHz, 1 MHz, 10 MHz and
50 MHz, decaying oscillation, Temperatures
Ri = 50 Ω Recommended temperature
EMC tests for interference emission; type tests during operation –5 °C to +55 °C / +23 °F to +131 °F
> 55 °C decreased display contrast
Standard EN 50081-* (generic standard)
Permissible temperature
Conducted interference voltage, aux. 150 kHz to 30 MHz
during operation –20 °C to +70 °C / –4 °F to +158 °F
voltage CISPR 22, EN 55022,
during storage –25 °C to +55 °C / –13 °F to +131 °F
DIN VDE 0878 Part 22,
during transport –25 °C to +70 °C / –13 °F to +158 °F
limit value class B
(Storage and transport with
Interference field strength 30 to 1000 MHz standard works packaging)
CISPR 11, EN 55011, DIN VDE
Humidity
0875 Part 11, limit value class A
Mean value per year ≤ 75 % relative
humidity, on 30 days per year
95 % relative humidity,
condensation not permissible
Technical data
Functions Tolerances
Definite-time overcurrent protection (ANSI 50, 50N) Pickup values 5%
Delay time for 2 ≤ I/Ip ≤ 20 5 % of theoretical value ± 2 %
Setting range/steps and 0.5 ≤ I/IN ≤ 24 current tolerance, at least 30 ms
Overcurrent pickup phase I> I/IN = 0.1 to 25 (steps 0.1), or ∞
earth IE> = 0.05 to 25 (steps 0.01), or ∞ Influencing variables
phase I>> I/IN = 0.1 to 25 (steps 0.1), or ∞ Auxiliary voltage, range: ≤1%
earth IE>> = 0.05 to 25 (steps 0.01), or ∞ 0.8 ≤ Vaux/VauxN ≤ 1.2
phase I>>> I/IN = 0.3 to 12.5 (steps 0.1), or ∞ Temperature, range: ≤ 0.5 %/10 K
-5 °C ≤ Θamb ≤ 40 °C
Delay times T for I>, IE>, I>> 0 s to 60 s (steps 0.01 s) +23 °F ≤ Θamb ≤ 104 °F
and IE>> Frequency, range: ≤ 8 % referred to theoretical time
The set times are pure delay times 0.95 ≤ f/fN ≤ 1.05 value
Pickup times I>, I>>, IE>, IE>> Negative-sequence overcurrent protection (ANSI 46)
At 2 x setting value, without Approx. 35 ms
meas. repetition Setting range/steps
At 2 x setting value, with meas. Approx. 50 ms Tripping stage 8 % to 80 % of IN
repetition I2> in steps of 1 % 8 % to 80 % of IN
Pickup times for I>>> at 2 x I2>> in steps of 1 %
Approx. 20 ms Time delays T(I2>), T(I2>>) 0.00 s to 60.00 s
setting value
in steps of 0.01s 5
Reset times I>, I>>, IE>, IE> Approx. 35 ms Lower function limit At least one phase current ≥ 0.1 x IN
I>>> Approx. 65 ms
Pickup times At fN = 50 Hz 60 Hz
Reset ratios Approx. 0.95 Tripping stage I2>, tripping Approx. 60 ms 75 ms
Overshot time Approx. 25 ms stage I2>>
But with currents I/IN>1.5 Approx. 200 ms 310 ms
Tolerances
(overcurrent case) or
Pickup values I>, I>>, I>>>, 5 % of setting value
negative-sequence current
IE>, IE>>
< (set value +0.1 x IN)
Delay times T 1 % of setting value or 10 ms
Reset times At fN = 50 Hz 60 Hz
Influencing variables
Tripping stage I2>, Approx. 35 ms 42 ms
Auxiliary voltage, range: ≤1%
tripping stage I2>>
0.8 ≤ Vaux /VauxN ≤ 1.2
Temperature, range: ≤ 0.5 %/10 K Reset ratios
0 °C ≤ Θamb ≤ 40 °C Tripping stage I2>, Approx. 0.95 to 0.01 x IN
Frequency, range: ≤ 1.5 % tripping stage I2>>
0.98 ≤ f/fN ≤ 1.02 Tolerances
Frequency, range: ≤ 2.5 % Pickup values I2>, I2>>
0.95 ≤ f/fN ≤ 1.05 with current I/IN ≤ 1.5 ± 1 % of IN ± 5 % of set value
Harmonics with current I/IN > 1.5 ± 5 % of IN ± 5 % of set value
Up to 10 % of 3rd harmonic ≤1% Stage delay times ± 1 % or 10 ms
Up to 10 % of 5th harmonic ≤1%
Influence variables
Inverse-time overcurrent protection (ANSI 51/51N) Auxiliary DC voltage, range: ≤1%
Setting range/steps 0.8 ≤Vaux /VauxN ≤ 1.2
Overcurrent pickup phase Ip I/IN = 0.1 to 4 (steps 0.1) Temperature, range: ≤ 0.5 %/10 K
earth IEp = 0.05 to 4 (steps 0.01) –5 °C ≤ Θamb ≤ +40 °C
+23 °F ≤ Θamb ≤ +104 °F
Time multiplier for Ip, IEp (IEC charac.) 0.05 to 3.2 s
Frequency,
Tp (steps 0.01 s)
range: 0.98 ≤ f/fN ≤ 1.02 ≤ 2 % of IN
(ANSI charac.) 0.5 to 15 s
range: 0.95 ≤ f/fN ≤ 1.05 ≤ 5 % of IN
(steps 0.1 s)
Auto-reclosure (option) (ANSI 79)
Overcurrent pickup phase I>> I/IN = 0.1 to 25 (steps 0.1), or ∞
phase I>>> = 0.3 to 12.5 (steps 0.1), or ∞ Number of possible shots 1 up to 9
earth IE>> = 0.05 to 25 Auto-reclose modes 3-pole
(steps 0.01), or ∞ Dead times for 1st to 3rd shot 0.05 s to 1800 s (steps 0.01 s)
Delay time T for I>>, IE>> 0 s to 60 s (steps 0.01 s) for 4th and any further 0.05 s to 1800 s (steps 0.01 s)
shot
Tripping time characteristics acc. to IEC
Reclaim time after successful AR 0.05 s to 320 s (steps 0.01 s)
Pickup threshold Approx. 1.1 x Ip
Drop-out threshold Approx. 1.03 x Ip Lock-out time after 0.05 s to 320 s (steps 0.01 s)
Drop-out time Approx. 35 ms unsuccessful AR
Tripping time characteristics acc. to ANSI / IEEE Reclaim time after manual close 0.50 s to 320 s (steps 0.01 s)
Pickup threshold Approx. 1.06 x Ip Duration of RECLOSE command 0.01s to 60 s (steps 0.01 s)
Drop-out threshold, Approx. 1.03 x Ip Control
alternatively: disk emulation
Number of devices 1
Evaluation of breaker control None
Technical data
Unit design
For panel surface mounting, terminals on the side B
Terminal connection on top and bottom D
For panel flush mounting/cubicle mounting E
Languages 5
English, German, Spanish, French, Russian 0
Auto-reclosure (option)
Without 0
With 1
Control
Without A
With B
UL-Listing
Without UL-listing 0
With UL-listing 1
Converter, full-duplex,
fiber-optic cable RS485 with built-in power supply unit
Auxiliary voltage 24 to 250 V DC and 110/230 V AC 7XV5650- 0BA00
LSP2289-afp.eps
Sample order
7SJ600, 1 A, 60 - 125 V, flush mounting, ARC 7SJ6001-4EA00-1DA0
1) Rated current can be selected by
means of jumpers.
Converter V.24 -RS485, 230 V AC 7XV5700-0AA00
Manual, English C53000-G1176-C106-7
2) Transition between the two auxiliary
voltage ranges can be selected by or visit www.siemens.com/siprotec
means of jumpers.
3) Only when position 16 is not “1” (with UL-listing).
4) Possible versions see part 13.
* RS485 bus system up to 115 kbaud
RS485 bus cable and adaptor 7XV5103-oAAoo;
see part 13.
Connection diagram
Fig. 5/32
Connection diagram according to IEC standard