A Hybrid Overload Current Limiting and S
A Hybrid Overload Current Limiting and S
Cem Koseoglu*, Necmi Altin **, Fevzi Zengin*, Hasan Kelebek*, and Ibrahim Sefa**
‡
Cem Koseoglu, 34785, İstanbul, Turkey, Tel: +90 (262) 751 16 00 /8311, [email protected]
Abstract- In this study, a current limiting technique which combines an analog comparator circuit and a digital current limiting
algorithm is proposed for voltage mode – controlled inverters. Thus, providing smooth output voltage waveform feature of
digital current limiting technique and very fast response feature of the analog technique are combined. A three-phase 10kVA
voltage mode – controlled inverter has been used to test the performance of the proposed method. Besides, the digital and the
analog current limiting techniques have been tested separately to highlight and compare the performance of the proposed
hybrid method. It is seen from experimental tests that the proposed technique provides fast response and a successful current
limiting performance at short circuit and overcurrent conditions. In addition, the proposed method improves the reliability and
fault tolerance capability of the inverter significantly. Moreover, the proposed current limiting algorithm adds fault clearing
capability function to the inverter.
Keywords Overcurrent protection; overload; short circuit protection; current limiter; fault-tolerant inverter; voltage source
inverter (VSI).
Nomenclature
VSI Voltage Source Inverter Inverter Output Reference Voltage
UPS Uninterruptible Power Supply Digital Current Limiter Input Signal
Measured DC Bus Voltage Digital Current Limiter Output Signal
Measured Inverter Output Voltage Positive Alternance Analog Current Limit Peak Value
Measured Inverter Output Current Negative Alternance Analog Current Limit Peak
Digital Current Limiter Parameter Value
Analog Current Limiter Measured Current
Digital Current Limit Value
1. Introduction
are the major reason of power circuitry damages. It is
The voltage source inverters (VSIs) which are
reported that about 38% of the faults in a power circuitry of
employing several semiconductor power switches, such as the VSI is due to failures of switching devices [2]. Therefore,
IGBTs and MOSFETs are commonly used in industrial designing a proper protection and fault detection system for
applications including the Uninterruptible Power Supplies
these inverter circuits is very important requirement to obtain
(UPSs), Distributed Generation (DG) systems, and motor
a high-reliability inverter especially for high power systems
drives [2 – 8]. Among the other causes, power switch faults
[2].
INTERNATIONAL JOURNAL of RENEWABLE ENERGY RESEARCH
C. Koseoglu et al., Vol.10, No.1, March, 2020
408
INTERNATIONAL JOURNAL of RENEWABLE ENERGY RESEARCH
C. Koseoglu et al., Vol.10, No.1, March, 2020
409
INTERNATIONAL JOURNAL of RENEWABLE ENERGY RESEARCH
C. Koseoglu et al., Vol.10, No.1, March, 2020
the current limiting capacity and makes fault current limiting this case at the first short circuit instant, digital technique
more difficult. Therefore, the current limiting effect of the may not detect this fast current and destruction of the IGBT
filter inductor which limits di/dt of the device current in short is possible.
circuit conditions should be investigated.
410
INTERNATIONAL JOURNAL of RENEWABLE ENERGY RESEARCH
C. Koseoglu et al., Vol.10, No.1, March, 2020
In this study a hybrid current limiting method is mode from the constant voltage mode to constant current
proposed. This method combines the analog and digital mode, and IGBT current is limited successfully. After the
current limiting methods discussed earlier. In previous first cycle, the nonlinear load capacitors are charged. Then
sections, both methods are discussed and either method has the current decreases and system reaches to its steady state.
some disadvantages. By incorporating these two methods At the steady state, waveforms become periodical as seen in
together, better current limitation action can be achieved. Fig. 7. The digital current limiting algorithm can be applied
to single- or three-phase inverters. Here, all three phases of
In digital current limiting technique, the system operates
the three-phase inverter are controlled separately. From Fig.
in constant voltage mode if the current is below the digital
7 and 8, it is seen that digital current limiting technique
current limit. If the current is higher than digital current limit,
provides smooth output voltage waveforms at current
the system operates in constant current mode. The algorithm
limiting duration.
performs these transitions automatically. The digital
technique has advantage of generating smooth voltage Table 1. Parameters of the inverter used in experimental
waveform during current limiting. But for fast changing studies.
currents, the digital technique may not be able to catch the
faults and limit the fault currents. The analog current limiting Symbol Value
technique can detect and limit these currents. Unfortunately, Output Power, Pout 10 kVA
the analog technique cannot produce smooth waveforms
during current limiting stage when compared to digital Output Voltage, Vout 230 V
technique. Filter Inductor, Lf 900 µH
The analog and digital current limiting techniques are Filter Capacitor, Cf 20 µF
employed together to gain advantages of each technique. The Switching Frequency, fsw 10 kHz
reference value for the analog current limiting technique
should be set a higher value than the digital current limiting
algorithm. In this way, the analog current limiting technique
stops the current if the digital technique is insufficient. The
analog comparator circuit works at the first instant of the
excessive current and then the digital current limiting takes
over the control and provides a smooth current limiting
waveform.
The inverter and switching devices are immediately
protected from the high fault currents by the analog control
technique when the digital control is insufficient and fast
changing currents are handled. During the current limitation Fig. 7. Performance of the digital current limiting
transients, sensitive loads are not affected from inverter algorithm for nonlinear load.
voltage distortion because of the smooth current limiting
action of the digital technique. In addition, combinational use
of the digital current limiting technique yields higher RMS
voltage value than the analog technique during the current
limiting transients, which is also better for the sensitive
loads.
In the experimental part effect of both techniques will be
discussed separately, and then combination of the two
techniques will be discussed.
4. Experimental Tests and Results Fig. 8. Performance of the digital current limiting
algorithm for three-phase nonlinear load.
Proposed hybrid current limiting technique is
implemented and tested with the three-phase 10kVA inverter. Fig. 9 shows the current limiting response of the analog
Parameters of the inverter used in experimental tests are current limiting technique. The analog current limiting
given in Table 1. An uncontrolled rectifier with a filter technique successfully limits the overcurrent, but it has much
capacitor at its output is defined as a standard nonlinear test more ripple content compared to digital limiting technique.
load. For testing excessive currents, this standard load shall Besides, the resultant current oscillations cause audible noise
be used. in inverter filter inductances. For some applications, the
distorted inverter voltage may affect sensitive loads. If the
First inverter is tested with the standard nonlinear load. inverter supplies sensitive loads and nonlinear loads at the
In Fig. 7 and Fig. 8, the results obtained from these tests same time, every transient state caused by overcurrent can
when the digital current limiting technique is employed are disturb sensitive loads. Therefore, use of the analog current
given for single-phase and three-phase, respectively. At the limiting alone is not a good solution. In addition to that,
first instant, the algorithm is changed the inverter operation analog technique charges nonlinear load capacitance in a
411
INTERNATIONAL JOURNAL of RENEWABLE ENERGY RESEARCH
C. Koseoglu et al., Vol.10, No.1, March, 2020
(b)
(c)
Fig. 9. Inverter response while the only analog current
limiting is active, a) The linear load condition, b)
Detailed look of linear load response, c) Nonlinear load
condition.
Fig. 12. Current limitation transient with nonlinear load.
412
INTERNATIONAL JOURNAL of RENEWABLE ENERGY RESEARCH
C. Koseoglu et al., Vol.10, No.1, March, 2020
Fig. 13. The limitation of short circuit current. Fig. 17. Changing the current limiting set value during
the phase-to-phase short circuit.
limiting technique can stop the current at defined levels and
ensures the peak current value never exceeds the upper
analog limit. As it is clearly seen in Fig. 12, the proposed
hybrid current liming technique provides a smooth voltage
waveform at overcurrent conditions and gives fast current
limiting capability even at peak voltage short circuits.
Another important overcurrent topic is the short-circuit
conditions. The proposed technique can stop overcurrent
caused by different types of short-circuits without any
Fig. 14. The fault current when the short-circuit occurs modification on algorithm and analog circuit. In Fig. 13, the
at the peak of the inverter output voltage. phase-to-neutral short-circuit test result is given. Before the
short-circuit instant, the inverter operates at constant voltage
mode. When the short circuit occurs, the inverter switches to
constant current mode and output current becomes a square–
wave. At the short-circuit condition, the inverter output
voltage is nearly zero. It is clearly seen from Fig. 13 that the
proposed technique can successfully limit the short circuit. In
Fig. 14, the short-circuit duration is zoomed in. The short-
circuit condition occurring at the peak value of the output
voltage can be accepted as a worst case. It is seen that the
proposed hybrid technique can overcome short-circuit events
event at the worst case.
Fig. 15. The effect of short-circuit current set value. The fault current level which will occur at the short-
circuit instants can be controlled by changing
parameter in the digital current limiting algorithm. Fig. 15
shows the effect of this set value. The set value is decreased
at the short-circuit condition and obtained response is
depicted in the figure. As seen from the figure, the fault-
current is kept at this set value. The heat generated in the
semiconductor because of the conduction losses can be
minimized by changing the short-circuit current limit level.
Usually, cooling fans are supplied by the inverter output
voltage. Therefore, fans do not work at short-circuit
conditions. Decreasing the short circuit current may be a
solution for these kinds of semiconductor heating problems.
Fig. 16. The limitation of phase-to-phase short-circuit
current.
413
INTERNATIONAL JOURNAL of RENEWABLE ENERGY RESEARCH
C. Koseoglu et al., Vol.10, No.1, March, 2020
Acknowledgements
Fig. 19. Transition to normal operation from phase-to-
neutral short-circuit. This work was supported by the Scientific and
Technological Research Council of Turkey (TUBITAK)
By using proposed operation method longer short circuit under Grant 3161102.
currents can be supplied. In this way, the circuit breakers at
the load side can isolate the short–circuited load by removing References
the fault from the system. Thus, inverter shall continue to
supply critical loads with minimum power outage. [1] C. Koseoglu, N. Altin, F. Zengin, H. Kelebek, I. Sefa, “A
In this application, each phase of the three-phase inverter Hybrid Overload Current Limiting and Short Circuit
is controlled independently, and each phase has its own Protection Scheme: A Case Study on UPS Inverter”,
analog current limiting circuit. Thus, the inverter is capable International Conference on Renewable Energy Research
of being overcome phase-to-phase short-circuit faults. Fig. and Applications ICRERA, Oct. 2019. (Conference
16 and Fig. 17 show the waveforms obtained for phase-to- Paper, in press)
phase short-circuit fault conditions obtained with the [2] I. Lizama, R. Alvarez, S. Bernet, and M. Wagner, “A new
proposed hybrid current limiting technique. Similarly, at method for fast short circuit protection of IGBTs,” Proc.
phase-to-phase short circuits, the short circuit current can be 40th Annu. Conf. IEEE Ind. Electron. Soc., pp. 1072–
adjusted by using parameters. In Fig. 17, adjusting the 1076, Oct. 2014. (Conference Paper)
short-circuit current limit value during the fault is seen.
[3] B. Wei, A. Marzàbal, J. Perez, R. Pinyol, J. M. Guerrero
In Fig. 18 and Fig. 19, transition to normal operation and J. C. Vásquez, "Overload and short-circuit protection
(when the short-circuit is isolated) from phase-to-phase strategy for voltage source inverter-based UPS," IEEE
short-circuit and phase-to-neutral short circuit conditions are Transactions on Power Electronics, vol. 34, no. 11, pp.
given, respectively. When the short-circuit is removed, the 11371-11382, Nov. 2019. (Article)
inverter quickly switches to constant voltage mode from
[4] N. Altin, and I. Sefa, “dSPACE based adaptive neuro-
constant current mode. These transitions are carried out
fuzzy controller of grid interactive inverter”, Energy
automatically according to control rule of the digital current
Conversion and Management, vol. 56, pp. 130-139, 2012.
limiting algorithm. If inverter voltage regulation algorithm
(Article)
uses an integrator, the value stored in the integrator should be
considered after removal of the short circuit, and windup [5] I. Sefa, N. Altin and S. Ozdemir, "An implementation of
schemes should be employed. grid interactive inverter with reactive power support
capability for renewable energy sources," 2011
5. Conclusion International Conference on Power Engineering, Energy
and Electrical Drives, Malaga, 2011, pp. 1-6. (Conference
A hybrid overload and short circuit protection technique Paper)
for a voltage–controlled inverter is proposed in this study.
[6] Y. Wang, C. Lee, P. Kuo, and Y. Lin, “Overcurrent
The proposed technique combines the analog current limiting
protection design, failure mode and effect analysis of an
technique and the digital current limiting algorithm. Thus,
electric vehicle inverter,” Proc. IEEE Int. Conf. Ind.
providing smooth output voltage waveform feature of the
Technol., pp. 1287–1292, Mar. 2016. (Conference Paper)
digital technique and fast response feature of the analog
technique are combined. By selecting the proper current [7] B. Lu and S. K. Sharma, “A literature review of IGBT
limiting value according to the current carrying capability of fault diagnostic and protection methods for power
the switcing devices, the fault current can be kept inside inverters,” IEEE Trans. Ind. Appl., vol. 45, no. 5, pp.
SOA for any conditions with the proposed technique. 1770–1777, Jul. 2009. (Article)
Proposed hybrid current limiting technique is tested with [8] I. Sefa, S. Ozdemir, H. Komurcugil and N. Altin, "An
10kVA inverter with linear and nonlinear loads, at phase-to- enhanced Lyapunov-function based control scheme for
neutral and phase-to-phase short-circuit conditions. three-phase grid-tied VSI with LCL filter," IEEE
Experimental results validate that the proposed technique Transactions on Sustainable Energy, vol. 10, no. 2, pp.
provides fast and stable response, prevents destruction of 504-513, April 2019. (Article)
semiconductors during fault instants. and improves system
[9] D. Liu, A. Hu, G. Wang and J. Guo, "Triple-loop-
reliability significantly. Besides, it allows to use lower filter
controlled overload or short circuit current limiter and
414
INTERNATIONAL JOURNAL of RENEWABLE ENERGY RESEARCH
C. Koseoglu et al., Vol.10, No.1, March, 2020
415