0% found this document useful (0 votes)
173 views

4010 Programming Manual 574 052

Uploaded by

thujaplicata1
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
173 views

4010 Programming Manual 574 052

Uploaded by

thujaplicata1
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 212

4010 Fire Alarm

Front Panel
Installing, Operating
and Programming
Instructions
574-052
Rev. S
Copyright and Copyright © 2006-2010 SimplexGrinnell LP. All rights reserved.
Trademarks
Information in this document is subject to change without notice. No part of this document
may be reproduced or transmitted in any form or by any means, electronic or mechanical, for
any purpose, without the express written consent of SimplexGrinnell LP.
Simplex and the Simplex logo are trademarks of Tyco International Ltd, and its affiliates and
are used under license.
Walk Test™ is protected by US Patent No. 4,725,818.
MAPNET addressable communications is protected by US Patent No.4,796,025.
IDNet™ is patent pending.
TrueAlarm® Analog Detection is protected by US Patent No. 5,155,468.
TrueAlarm® Detector Base is protected by US Patent No. 5,173, 683.
This product is protected by US Patents 5,966,002; 6,034,601; and 6,281,789.

Cautions and Warnings READ AND SAVE THESE INSTRUCTIONS- Follow the instructions in this installation man-
ual. These instructions must be followed to avoid damage to this product and associated equip-
ment. Product operation and reliability depend upon proper installation.

DO NOT INSTALL ANY SIMPLEX® PRODUCT THAT APPEARS DAMAGED- Upon


unpacking your Simplex product, inspect the contents of the carton for shipping damage. If
damage is apparent, immediately file a claim with the carrier and notify an authorized Simplex
product supplier.

ELECTRICAL HAZARD - Disconnect electrical field power when making any internal adjust-
ments or repairs. All repairs should be performed by a representative or authorized agent of
your local Simplex product supplier.

FCC RULES AND REGULATIONS – PART 15 - This equipment has been tested and found to
comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful interference when the
equipment is operated in a commercial environment. This equipment generates, uses, and can
radiate radio frequency energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. Operation of this equipment
in a residential area is likely to cause harmful interference in which case the user will be
required to correct the interference at his own expense.
Codes and Standards The 4010 is listed for the following listing categories.

UL 864 Listings for Type of System:


UL 864 Power-Limited Fire Alarm Control Unit
Local (formerly NFPA 72A)
Requires the sounding of an alarm via listed notification appliance(s)
Auxiliary (formerly NFPA 72B)
Requires 4010-9809City Circuit Module
Remote Station - protected premise (formerly NFPA 72C)
Requires 4010-98094010-9809 City Circuit Module or the 4010-9810 or -9816 DACT
Proprietary - protected premise (formerly NFPA 72D)
Requires 4010-9817 (with 4010-9818 or 4010-9819) or 4010-9821 Network Interface Modules
Central Station - protected premise (formerly NFPA 71)
Requires 4010-9810 or -9816 DACT
Suppression Release Service
4010-98094010-9809 or the 4010-9810 or -9816 DACT

When controlling Halon 1301 per NFPA 12A, either an uninterruptible power supply, listed
for fire protective signaling use, or an appropriately rated standby battery must be provided as
a standby power source.
UL 864 Listings for Type of Service:

Automatic, Manual, Waterflow, and Sprinkler Supervisory

UL 864 Listings for Type of Signaling:

Coded, Non-Coded, March-Time and DACT


Requires the 4010-9810 or -9816 DACT

Factory Mutual Approved:

Same as UL above
ULC-S527 Listed:
• Local
• Remote Station
• Suppression Releasing Service

Local Approvals:

• CSFM *
• MEA
• City of Chicago (pending)
*This product has been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listing No. 7170-
0026:226 for allowable values and/or conditions for use concerning material presented in this
document.
Codes and Standards The installer should also be familiar with the following relevant codes as well as any other
applicable local codes and standards, when installing a fire alarm system.

• NFPA 72 National Fire Alarm Code

• NFPA 11 Standard for Low-Expansion Foam and Combined Agent Systems

• NFPA 11A Standard for Medium- and High-Expansion Foam Systems

• NFPA 12 Standard on Carbon Dioxide Extinguishing Systems

• NFPA 12B Standard on Halon 1211

• NFPA 13 Standard for the Installation of Sprinkler Systems

• NFPA 17 Standard for Dry Chemical Extinguishing Systems

• NFPA 70 National Electrical Code

• NFPA 101 Life Safety Code

• ULC S524 Standard for Installation of Fire Alarm Systems (Canadian Systems)

• C22.1 Canadian Electrical Code


Table of Contents
Chapter 1 .
4010 FACP Overview ............................................. 1-1
Introduction..................................................................................... 1-1
In This Chapter............................................................................... 1-1
Related Documentation ........................................................................1-2
Base System Module ............................................................................1-3
Overview ........................................................................................ 1-3
SFI/O .............................................................................................. 1-3
Power Supply - Base System......................................................... 1-4
Default Settings .............................................................................. 1-4
Environmental Specifications ......................................................... 1-4
Optional System Modules .....................................................................1-5
Overview ........................................................................................ 1-5
Optional Modules with Dedicated Hardware Slots ......................... 1-5
Optional Modules for Expansion Slots ........................................... 1-6
Remote Optional Modules.............................................................. 1-7
Other Compatible Equipment ......................................................... 1-7
User Interface .......................................................................................1-9
Overview ........................................................................................ 1-9
Operator Key Definitions ................................................................ 1-9
Menu Navigation Key Definitions ................................................. 1-10
Passcodes, Access Levels, and Logging In and Out ..........................1-11
Overview ...................................................................................... 1-11
Passcodes and Access Levels..................................................... 1-11
Logging In and Out....................................................................... 1-12
Menu Structure ...................................................................................1-13

Chapter 2.
Back Box Mounting ............................................... 2-1
Introduction..................................................................................... 2-1
In This Chapter............................................................................... 2-1
Before You Begin ..................................................................................2-2
Unpacking the System ................................................................... 2-2
Installation Guidelines .................................................................... 2-2
Standards and Codes..................................................................... 2-2
Removing the Chassis and Cutting Conduit Openings .........................2-3
Overview ........................................................................................ 2-3
Step 1. Removing the Chassis ....................................................... 2-3
Step 2. Cutting Conduit Entrances ................................................. 2-3
Mounting the Back Box .........................................................................2-4
Surface Mounting the Back Box ..................................................... 2-4
Semi-Flush Mounting the Back Box ............................................... 2-4
Re-Installing the Chassis ......................................................................2-5
....................................................................................................... 2-5
Door-Mounted Annunciator Setup ........................................................2-6
Introduction..................................................................................... 2-6
Location of Switches ...................................................................... 2-6
Remove Metal PCB Cover ............................................................. 2-6
Set N2 Baud Rate Switch (SW1).................................................... 2-6
Setting Card Address (SW2) .......................................................... 2-7
Setting LED Color Switches (SW4, SW5, SW6) ............................ 2-7
Programming LEDs ........................................................................ 2-9
Chapter 3.
Wiring ..................................................................... 3-1
Introduction .................................................................................... 3-1
In This Chapter .............................................................................. 3-1
Overview .............................................................................................. 3-2
Power Limited Versus Non-Power Limited Systems ..................... 3-2
Locations of Terminal Connections ............................................... 3-3
NAC Wiring .......................................................................................... 3-4
Overview........................................................................................ 3-4
Terminal Connections.................................................................... 3-4
IDNet Wiring ......................................................................................... 3-5
Overview........................................................................................ 3-5
Terminal Connections.................................................................... 3-5
AC Power and Battery Wiring .............................................................. 3-6
AC Power....................................................................................... 3-6
Installing and Connecting Batteries ............................................... 3-7
Auxiliary Relays .................................................................................... 3-9
System Power-Up and Checkout ....................................................... 3-10
Connecting AC and Battery Power .............................................. 3-10
Power-Up..................................................................................... 3-10
Before Checkout .......................................................................... 3-11
Checkout (Acceptance Testing)................................................... 3-12
Periodic Testing and Maintenance ..................................................... 3-13
Overview...................................................................................... 3-13
Battery Testing Information.......................................................... 3-13

Chapter 4 .
Quick CFIG............................................................. 4-1
Introduction .................................................................................... 4-1
In This Chapter .............................................................................. 4-1
Cautions and Warnings ........................................................................ 4-2
Reconfiguring All Hardware ................................................................. 4-3
Overview........................................................................................ 4-3
Procedure ...................................................................................... 4-3
Auto Detecting New Hardware ............................................................. 4-4
Overview........................................................................................ 4-4
Procedure ...................................................................................... 4-4
Restoring Factory CFIG ....................................................................... 4-5
Overview........................................................................................ 4-5
Procedure ...................................................................................... 4-5
Accepting Default Settings for System Options ................................... 4-6
Overview........................................................................................ 4-6
Procedure ...................................................................................... 4-6
Editing Settings for System Options ..................................................... 4-7
Overview........................................................................................ 4-7
Procedure ...................................................................................... 4-7
Save CFIG Option ................................................................................ 4-9
Chapter 5 .
Configuring Cards................................................. 5-1
Introduction .................................................................................... 5-1
In This Chapter .............................................................................. 5-1
Card Addresses ................................................................................... 5-2
Adding, Deleting, or Modifying 4010 Cards .......................................... 5-3
Overview........................................................................................ 5-3
Adding a Card................................................................................ 5-3
Deleting a Card.............................................................................. 5-4
Modifying a Card............................................................................ 5-5

Chapter 6 .
Configuring Points ................................................ 6-1
Introduction .................................................................................... 6-1
In This Chapter .............................................................................. 6-1
The Configure Points Menu ................................................................. 6-2
Configuring TrueAlarm Points .............................................................. 6-3
Overview........................................................................................ 6-3
Adding an IDNet Point ................................................................... 6-3
Editing a TrueAlarm Point.............................................................. 6-3
Deleting a TrueAlarm Point............................................................ 6-5
Configuring ZAM/IAM/RIAM Points ...................................................... 6-6
Overview........................................................................................ 6-6
Adding a ZAM/IAM/RIAM Point ..................................................... 6-6
Editing a ZAM/IAM/RIAM Point...................................................... 6-6
Deleting a ZAM/IAM/RIAM Point ................................................... 6-8
Configuring Programmable Relay and NAC Points ............................. 6-9
Overview........................................................................................ 6-9
Procedure ...................................................................................... 6-9
Configuring Digital and Analog Pseudo Points .................................. 6-11
Overview...................................................................................... 6-11
Configuring Digital Pseudo Points ............................................... 6-11
Configuring Analog Pseudo Points .............................................. 6-12
Configuring 24-Point Programmable I/O Points ................................. 6-14
Configuring 24-Point Input Points ................................................ 6-14
Configuring 24-Point Output Points ............................................. 6-15
Configuring List Points ....................................................................... 6-17
Overview...................................................................................... 6-17
Configure a List............................................................................ 6-17
Adding a Point to a List................................................................ 6-18
Deleting a Point from a List.......................................................... 6-18
Deleting All Points from a List...................................................... 6-18
Configuring User-Defined Programmable Switches and LEDs .......... 6-19
Overview...................................................................................... 6-19
Configuring a User-Defined Switch or LED ................................. 6-19
Edit a Mode of a User-Defined SW/LED...................................... 6-20
Chapter 7.
System Options..................................................... 7-1
Introduction .................................................................................... 7-1
In This Chapter .............................................................................. 7-1
System Options Menu .......................................................................... 7-2
Introduction .................................................................................... 7-2
Time/Date Format ................................................................................ 7-3
Overview........................................................................................ 7-3
Setting the Time Format ................................................................ 7-3
Active Status Reminder ........................................................................ 7-4
Overview........................................................................................ 7-4
Setting the Active Status Reminder ............................................... 7-4
Silence/Reset Inhibit ............................................................................ 7-5
Overview........................................................................................ 7-5
Setting the Silence/Reset Inhibit.................................................... 7-5
Alarm Cut-Out Timer ............................................................................ 7-6
Overview........................................................................................ 7-6
Setting the Alarm Cut-out Timer .................................................... 7-6
Door Drop on Alarm ............................................................................. 7-7
Overview........................................................................................ 7-7
Setting the Door Drop on Alarm Timer .......................................... 7-7
Door Drop on AC Loss ......................................................................... 7-8
Overview........................................................................................ 7-8
Setting the Door Drop on AC Loss Timer ...................................... 7-8
Audible and Visible NAC Operation ..................................................... 7-9
Overview........................................................................................ 7-9
Setting the Audible or Visual NAC Operation ................................ 7-9
TrueAlert Non-Addressable Horn Operation ...................................... 7-10
Overview...................................................................................... 7-10
Setting the TrueAlert Non-Addressable Horn Option................... 7-10
Depleted Battery Cut-Out ................................................................... 7-11
Overview...................................................................................... 7-11
Setting the Depleted Battery Cut-Out .......................................... 7-11
Stagger Starting AHUs ....................................................................... 7-12
Overview...................................................................................... 7-12
Setting the Stagger Start AHU Delay Timer ................................ 7-12
Enabling the City Circuit ..................................................................... 7-13
Overview...................................................................................... 7-13
Setting the Enable City Circuit Option ......................................... 7-13
Expansion Power ............................................................................... 7-14
Overview...................................................................................... 7-14
Setting the Expansion Power Option ........................................... 7-14
Single Station ..................................................................................... 7-15
Overview...................................................................................... 7-15
Setting the Single Station Option................................................. 7-15
Display 1st Alarm ............................................................................... 7-15
Overview...................................................................................... 7-15
Immediate AC Fail .............................................................................. 7-15
Overview...................................................................................... 7-15
Wheelock ........................................................................................... 7-16
Overview...................................................................................... 7-16
Recurring Trouble Filter ..................................................................... 7-16
Overview...................................................................................... 7-16
Chapter 8.
Custom Control ..................................................... 8-1
Introduction .................................................................................... 8-1
In This Chapter .............................................................................. 8-1
Overview .............................................................................................. 8-2
SMPL Opcodes and Operators ............................................................ 8-3
Input Opcodes ............................................................................... 8-3
Input and Relational Operators...................................................... 8-4
Output Opcodes............................................................................. 8-5
Custom Control Example ..................................................................... 8-6
Output Opcodes............................................................................. 8-6
Custom Control Programming .............................................................. 8-7
To Start Custom Control Programming ......................................... 8-7
Custom Control Menu Navigation.................................................. 8-7
Equation Level ............................................................................... 8-8
Custom Control Level .................................................................... 8-8
Equations....................................................................................... 8-9
Input Side (IF) ................................................................................ 8-9
Field 1 ............................................................................................ 8-9
Field 2 .......................................................................................... 8-14
Fields 3 and 4 .............................................................................. 8-15
Output Side (THEN)..................................................................... 8-22
Application-Specific Examples ........................................................... 8-24
Overview...................................................................................... 8-24
Day/Night Programming Example ............................................... 8-24
TrueAlarm Heat Utility Monitoring Example................................. 8-24
City Circuit Alarm-Output Programming Example ....................... 8-24
AHJ City Circuit Reset Operation Example ................................. 8-24

Chapter 9.
Saving a CFIG........................................................ 9-1
Introduction .................................................................................... 9-1
In This Chapter .............................................................................. 9-1
Viewing CFIG Properties ...................................................................... 9-2
Overview........................................................................................ 9-2
Procedure ...................................................................................... 9-2
Continue, Restore CFIG, and Save CFIG ............................................ 9-3
Continue ........................................................................................ 9-3
Restore CFIG................................................................................. 9-3
Save CFIG ..................................................................................... 9-3

Chapter 10.
Diagnostics and Troubleshooting ..................... 10-1
Introduction .................................................................................. 10-1
Before Calling Technical Support ................................................ 10-1
In This Chapter ............................................................................ 10-1
Diagnostics ......................................................................................... 10-2
Overview...................................................................................... 10-2
Running Diagnostics.................................................................... 10-2
N2 Comm Diagnostics ................................................................. 10-3
IDNet Diagnostics ........................................................................ 10-3
IDNet Earth Fault Search Diagnostics ......................................... 10-4
Network Diagnostics .................................................................... 10-4
Walk Test ........................................................................................... 10-6
Overview...................................................................................... 10-6
Using Walk Test........................................................................... 10-6
TrueTest ............................................................................................. 10-8
Overview...................................................................................... 10-8
Using TrueTest ............................................................................ 10-9
Crash Codes .................................................................................... 10-10

Chapter 11 .
Operation ............................................................. 11-1
Introduction .................................................................................. 11-1
In This Chapter ............................................................................ 11-1
Handling Abnormal Conditions ........................................................... 11-2
Normal Operation ........................................................................ 11-2
Abnormal Conditions ................................................................... 11-2
Silencing Alarms .......................................................................... 11-3
Viewing and Clearing Historical Logs ................................................. 11-5
Overview...................................................................................... 11-5
Viewing and Controlling Points .......................................................... 11-7
Overview...................................................................................... 11-7
Controlling/Viewing Points ........................................................... 11-7
Disabling Points in Alarm............................................................. 11-9
Editing Custom Labels ..................................................................... 11-10
User Control Functions .................................................................... 11-12
Overview.................................................................................... 11-12
Using the Function Options ....................................................... 11-12
Setting the Time and Date ............................................................... 11-13

Appendix A.
Device and Point Types........................................ A-1
Introduction .................................................................................... A-1
In This Chapter .............................................................................. A-1
Hardware Device Types .......................................................................A-2
Overview........................................................................................ A-2
TrueAlarm Hardware Device Types............................................... A-2
Monitor Hardware Device Types ................................................... A-3
4009A Hardware Device Types ..................................................... A-3
Software Point Types ...........................................................................A-4
Monitor Point Types....................................................................... A-4
TrueAlert Non-Addressable Point Types ....................................... A-8

Appendix B.
Hardware and Pseudo Points .............................. B-1
Introduction .................................................................................... B-1
In This Chapter .............................................................................. B-1
Hardware Points ...................................................................................B-2
Overview........................................................................................ B-2
General Card Status Point Information.......................................... B-2
Master Controller Card .................................................................. B-2
Master Controller Card Status Points ............................................ B-2
Master Controller Points ................................................................ B-2
NAC Card ...................................................................................... B-3
NAC Card Status Points ................................................................ B-4
NAC Card Points ........................................................................... B-4
Power Supply Card Status Points.................................................. B-5
Power Supply Points...................................................................... B-5
IDNet Card Status Points............................................................... B-6
IDNet Points................................................................................... B-7
RS-232 or Modem Card................................................................. B-7
RS-232/Modem Card Status Points............................................... B-8
RS-232/Modem Points................................................................... B-8
DACT Card .................................................................................... B-8
DACT Card Status Points .............................................................. B-9
SDACT Points................................................................................ B-9
Network Card................................................................................. B-9
Network Card
Status Points................................................................................ B-10
Network Points............................................................................. B-10
24 I/O Status Points..................................................................... B-11
24 I/O Points ................................................................................ B-11
LCD Card..................................................................................... B-11
LCD Card Status Points............................................................... B-12
LCD Points................................................................................... B-12
Pseudo Points ....................................................................................B-13
Overview...................................................................................... B-13
Digital Pseudo Points................................................................... B-13
4010 System Digital Pseudos...................................................... B-14
Analog Pseudo Points ................................................................. B-17
4010 System Analog Pseudos..................................................... B-18
4010 User Analog Pseudos ......................................................... B-18
List Pseudo Points ....................................................................... B-19
4010 System Lists ....................................................................... B-19
4010 User Lists............................................................................ B-20

Appendix C.
Glossary................................................................. C-1
Introduction .................................................................................... C-1
Glossary......................................................................................... C-1

Appendix D.
Suppression Release............................................ D-1
Introduction .................................................................................... D-1
In this Chapter ............................................................................... D-1
Overview ..............................................................................................D-2
General Capabilities ...................................................................... D-2
Applying Suppression Label to Front Cover .................................. D-3
Flow Charts.................................................................................... D-4
Flow Charts.................................................................................... D-5
Wiring Suppression Devices ................................................................D-6
Wiring Initiating Devices ................................................................ D-6
Wiring Notification Appliances ....................................................... D-6
Wiring Manual Release and Abort Switches.................................. D-6
Wiring Releasing Peripheral .......................................................... D-6
Programming Device and Point Types for Suppression Devices .........D-7
Overview........................................................................................ D-7
Assigning a Point's Hazard Area ................................................... D-8
Assigning a Point's Hazard Area ................................................... D-9
Programming Suppression Release Options .....................................D-10
Step 1. Enable Suppression Release System Options............... D-10
Step 2. Set Audible Output Option.............................................. D-11
Step 3. Set Options for Hazard Area .......................................... D-11
Step 4. Set Detector Delay ......................................................... D-11
Step 5. Set Manual Delay ........................................................... D-12
Step 6. Set Cutout Timer ............................................................ D-12
Step 7. Set Release Abort Operation ......................................... D-13
Step 7. Set Release Abort Operation ......................................... D-14
Chapter 1.
4010 FACP Overview

Introduction The 4010 is a single-channel, addressable, modular Fire Alarm Control Panel (FACP) that
monitors and controls up to 250 IDNet addressable devices. The Standard Function Input/
Output (SFI/O) card, power supply, and cabinet provide a complete fire alarm control panel for
most applications. Optional modules mount to the chassis to provide additional inputs and
outputs, network communication, and additional power. Additionally, the 4010 can
automatically control supplementary equipment such as fire doors and fans during an alarm
condition using its auxiliary relay outputs.

The 4010 provides audible and visible indications during trouble, supervisory, or alarm (fire)
conditions. Should any of these conditions occur, the system activates the applicable
notification appliance(s), LEDs, and the panel tone-alert. The indications continue until
someone appropriately acknowledges the condition.

This publication describes how to install, configure, operate, program, and test the 4010 Fire
Alarm Control Panel (FACP).

In This Chapter This chapter discusses the following topics:

Topic See Page #

Related Documentation 1-2

Base System Module 1-3

Optional System Modules 1-5

User Interface 1-9

Passcodes, Access Levels, and Logging In and Out 1-11

Menu Structure 1-13

1-1
Related Documentation

The following table lists publications that provide specific information concerning field
wiring, replacement parts, optional modules, and application information.

Table 1-1. Related Documentation

Publication Title Part Number

4010-9806 Class A Module - Installation Instructions 574-055

4010-9809 City Circuit Card - Installation Instructions 574-056

4010Fire Alarm Expansion Power Supplies Installation Instructions 574-057

4010Fire Alarm RS232 Interface and Service Modem Cards 574-058


Installation Instructions

4010-9820 Battery Meter Module - Installation Instructions 574-165

4010-9814 Suppression Kit - Installation Instructions 574-166

4010 Fire Alarm DACT Modules - Installation Instructions 574-167

4010 Fire Alarm 4120 Network Interface Cards Installation 574-168


Instructions

Fire Alarm - Parts List 574-424

4098 Detectors, Sensors, and Bases - Application Manual 574-709

4010 Fire Alarm - Field Wiring Diagrams 842-058

2-Wire Detector Compatibility chart 579-832 Rev. G

1-2
Base System Module

Overview The 4010 Base System includes the SFI/O card, power supply, and cabinet.

SFI/O The SFI/O contains all connections for optional modules as well as N2 annunciator
communication, IDNet, NAC, Auxiliary Power, Programmable Auxiliary Relay, PC
Programmer (service port), and expansion power connections.

The User Interface provides a 2x40 LCD screen, LEDs, operational and programming keys, all
of which are visible with the cabinet door closed. See “User Interface” later in this chapter for
additional information about the user interface.

Figure 1-1. 4010 SFI/O with User Interface

Continued on next page

1-3
Base System Module, Continued

Power Supply - Base Base System:


System
• 120 VAC, 60Hz or 220/240 VAC, 50/60 Hz

• 24 VDC (unregulated) 4 A alarm power (both special application and 24V regulated)

• 24 VDC, 1/2 A auxiliary power

• Battery Charger for 25 Ah Batteries, 24-hour recharge at 120 VAC (for larger battery
capacity, use the 4081-9301, -9302, -9303, or -9304 External Battery Cabinet w/Charger)

Note: The 4010 back box can accommodate up to 25Ah batteries.

Default Settings All switches and potentiometers are set at the factory before shipping. Although the settings
should be accurate, you can change the settings on the following components as indicated.

• LCD Adjustment (R143) - If necessary, use a small flat head screwdriver, turn the R143
Potentiometer located below TB1 to adjust the contrast on the LCD for the 4010.

• Baud Rate Setting (SW2) - Baud rate settings for the 4010 communications are shown in
Table 1-2. If you receive a communications trouble at the panel, verify that SW2 is set
correctly.

Table 1-2: SW2 Switch Settings

Baud Rate SW2-1 SW2-2

OFF LINE ON ON

9,600 OFF ON

19,200 ON OFF

19,200 OFF OFF

Important: You must set all cards to the same baud rate in order for the 4010 to operate
properly. If you have a 4010 with a Network or DACT card, you must set the SW2 dip switch
to the 9600 baud rate. It is recommended that you use the 19,200 option when uploading/
downloading information to a PC.

Environmental Temperature:
Specifications The 4010 operates normally with ambient temperatures from 32° F to 120° F (0° C to 49° C),
inclusive.

Humidity:
The 4010 operates normally under non-condensing humidity conditions up to 85% relative
humidity @ 86° F (30° C).

1-4
Optional System Modules

Overview The following is a list of optional modules for the 4010. Refer to the individual instructions
that accompany each module for more information. Those instructions and their part numbers
are listed in the "Related Documentation" section of this chapter. Refer to the label inside the
door of the 4010 for the placement of optional modules.

Note: Certain modules are mutually exclusive. For example:


• One DACT or one City Circuit Card is allowed.
• One 4120 Network Card or one DACT is allowed.
• One Dual RS232 Card or one RS232/Modem is allowed.
• One Battery Meter Module or one 24 VDC Extender Terminal Block.

Optional Modules with The 4010 has five dedicated mounting locations to support the following modules.
Dedicated Hardware
Slots 4010-9806 Class A Adapter Card for NACs

The four NACs found on the SFI/O board are Class B (Style Y). To support Class A (Style Z)
you must install an adapter card that mounts to the SFI/O board. Each adapter card supports
two NACs.

4010-9809 City Circuit Card

The city circuit card connects to the SFI/O with a ribbon harness to provide UL-listed
connections to either Remote Station (reverse polarity) or Public Service Fire Communications
Center (local energy) receiving units (selectable). The card has two circuits -- Circuit 1 reports
only alarm events and Circuit 2 can be configured to report Trouble events or Trouble and
Supervisory events. In the event of a CPU failure, a city card configured for a Trouble Output
sends a trouble to the city circuit. The card is mounted to the right of the SFI/O at the top of
the chassis.

Newer versions of the 4010 FACP (Version 2.01 or later) provide the ability to reset the City
Circuit in any of the following situations:

• The device(s) in alarm is physically removed.

• ·No other devices are in an alarm state.

• ·System Reset is performed.

Enabling City Circuit reset is done via Custom Control. Refer to "Application-Specific
Examples" at the end of Chapter 8 for specific information. Be sure to consult the AHJ before
enabling the City Circuit Reset option.

4010-9813 Expansion Power Supply Special Application

When more than 4 A of Notification or AUX power is required, an expansion power supply
may be added. The expansion power supply provides filtered 24 VDC power (4 A Special
Applications, 2A 24V Regulated) for notification and auxiliary use. The expansion power sup-
ply is mounted to the right of the SFI/O at the bottom of the chassis.

Continued on next page

1-5
Optional System Modules, Continued

Optional Modules with


Dedicated Hardware
Slots 4010-9820 Battery Meter Module

The 4010-9820 Battery Meter Module provides an indication of the charge/discharge state of
the FACP's batteries (internal or external), and provides a constant reading of the current and
voltage of the monitored batteries. This module mounts to the right of the city module.

Optional Modules for The 4010 has a maximum of two expansion slots available to support the following cards.
Expansion Slots
4010-9810 and -9816 DACT Cards. Two versions of the DACT are offered:

4010-9810 - Event Reporting DACT - Five categories of status changes are supported with this
card. The Central Station is notified of Alarm, Trouble, Supervisory or Waterflow status
changes. AC Fail trouble is delayed for 6 to 12 hours before reporting to the Central Station.
In the event of a CPU failure, the card sends a "CPU Trouble" message to the Central Station.

4010-9816 - Per Point Reporting DACT - Specific information is available about which point
in the system experiences a status change. The report sent to the Central Station includes the
specific point address along with the point status. The DACT supervises the system CPU via
N2 communication. In the event of a CPU failure, the DACT sends a "CPU Trouble" message
to the Central Station.

4010-9811 Dual RS-232 Card

The Dual RS-232 Card is connected to the N2 communication lines. The 4010 can vector
messages to RS232 ports by category. The RS-232 ports may be configured as follows:

• ·Two serial printers (80 or 40 column).

• ·One serial printer and one CRT/Keyboard (command line interface).

The RS-232 ports on the option card are electrically isolated from earth, allowing connection
of an AC powered printer or CRT/keyboard.

Note: Only the 80-column printer can be used to print 4010 system reports.

4010-9812 RS-232/Service Modem Card

This card is similar to the above dual RS-232 card except that one port is a dedicated Service
Modem port (command line interface). The second port may be programmed for use with a
serial printer or left unused. Event vectoring by category is supported on the modem and
RS-232 ports.

1-6
Optional System Modules, Continued

Optional Modules for 4010-9817, -9818, -9819, and -9821 4120 Network Cards
Expansion Slots
A 4120 Network card can be added to the 4010. This card communicates with the system CPU
via N2 communication. The 4010 system can be a node on a 4120 Network, though it has
limited functionality. Points on the 4010 may be declared as Public. No points on other nodes
may be declared as External to the 4010. Set Host and Remote Download functions are fully
supported.

Remote Optional The following optional modules mount remotely from the FACP.
Modules
4606-9101 LCD Remote Annunciator

The 4606 LCD annunciator for the 4010 provides remote area annunciation of the panel's
status. The pass-key protected user interface provides a 2x40 LCD screen, indicating LEDs,
and operator membrane keys.

4605-8401 24-Point I/O

The 24-Point I/O Card is capable of using any combination of 24 programmable inputs or
outputs to control LEDs, lamps, and relays, and to monitor contact closure inputs. The outputs
can be ON continuous or flashed, at a slow or fast rate. Inputs may be unsupervised,
supervised for opens, supervised for open and shorts, depending upon how the switch is wired
externally.

Other Compatible The 4010 is compatible with the following equipment, provided all equipment meets the
Equipment applicable agency listings for the intended use.

• 4003 Voice Control Panel (VCP). Since the 4010AutoPulse Z-28Triton RPA does not
contain hardwired monitor points, the alarm/trouble output from the 4003 is connected to
a Zone Adapter Module (ZAM). One of the NACs on the 4010AutoPulse Z-28Triton RPA
can be used to activate the 4003.
• 4009A and 4009R IDNet NAC Extender.
• The 4010 is compatible with the 4098 smoke/heat sensors and bases listed in Table 1-3.

Table 1-3: Compatible Sensors and Bases

PID Description

4098-9710 Quickconnect, TrueAlarm, Photo Smoke Sensor

4098-9713 Quickconnect, TrueAlarm, Photo Smoke Sensor with


sounder.

4098-9714 TrueAlarm, Photo Smoke Sensor (requires


separate base)

4098-9717 TrueAlarm, Ion Smoke Sensor (requires separate base)

4098-9733 TrueAlarm Heat Sensor (requires separate base)

4098-9789, -9791 to -9793 Sensor Bases

• Power supplies that are power-limited and listed for fire-protective signaling use can be
used with the 4010 when wired according to power-limited guidelines.

1-7
Optional System Modules, Continued

• The 4010 is compatible with the 4120 network. In order to use the 4010 as a node on the
network, you must have

• 4100 master software at Rev. 8.01 or higher and GCC/NPU at Rev. 2.03 or higher.

• 4120 network firmware at Rev. 3.01 or greater. (Rev. 3.02.99 or later is


recommended.)

• 4010 network firmware at Rev. 3.03.99 or later.

1-8
User Interface

Overview The user interface of the 4010 system consists of control keys, LEDs, a 2-line by 40-character
backlit LCD, and a tone-alert mounted in the control panel. The purposes of the Operator and
Menu keys are listed in the following section.

SYSTEM IS NORMAL
LCD
10:09:33am Wed 27-Nov-01

LEDs

Operator Keys

Menu Navigation
Keys

Figure 1-2. Operator Interface, Showing High-Level Status Screen

Operator Key Definitions The following information defines the operator (rectangular) keys on the panel.

ALARM Alarm Acknowledge <ALARM ACK>


ACK
The <ALARM ACK> key is used to acknowledge any unacknowledged fire alarms in the
system and to scroll through the alarms in the active Alarm List.

SUPV Supervisory Acknowledge <SUPV ACK>


ACK
The <SUPV ACK> key is used to acknowledge any unacknowledged supervisories in the
system and to scroll through the supervisory conditions in the active Supervisory List.

TROUBLE Trouble Acknowledge <TROUBLE ACK>


ACK
The <TROUBLE ACK> key is used to acknowledge any unacknowledged troubles in the
system and to scroll through the troubles in the active Trouble List.

Alarm Silence <ALARM SILENCE>


ALARM
SILENCE The <ALARM SILENCE> key is used to silence any silenceable output types (generally all
non-visible notification appliances).

System Reset <SYSTEM RESET>


SYSTEM
RESET The <SYSTEM RESET> key allows you to reset all alarm notification appliances and con-
trols, remove alarms from the Alarm List, silence all silenceable outputs, reset detectors, and
return the system to a normal state (provided that no alarms are present). The display will indi-
cate that a reset is in progress and whether or not a reset completes successfully.

Continued on next page

1-9
User Interface, Continued

Menu Navigation Key The following information defines the menu navigation (round) keys on the 4010 panel. These
Definitions keys perform access level dependent functions defined in the "Passcodes, Access Levels, and
Logging In and Out" section of this chapter.

Menu <Menu>

The <Menu> key always brings you to the top of the main menu structure unless you are in
Programming or Quick-CFIG menus (see the Menu Structure at the back of this chapter).

Function <Function>

The Function Menu is displayed when the <Function> key is pressed at the High-Level Status
screen. Use the < Previous> and <‚ Next> keys to scroll through the functions list. The
function key provides access to commonly used control and display "functions," and is also
used for list editing.

Disable/Enable <Disable/Enable>

The <Disable/Enable> key allows the operator to quickly disable or enable any point that is
currently displayed (passcode protected). A confirmation screen is displayed requesting
<Enter> be pressed before performing the actual enable or disable.

Exit/Clear <Exit/Clear>

The <Exit/Clear> key is used to back out of menus or displays to get to the top-level menu
structure (refer to the "Menu Structure" at the end of this chapter). Where possible, the <Exit/
Clear> key will back out one level at a time. There are cases, however, that the <Exit/Clear>
key will return the operator directly to the top level.

Enter <Enter>

The <Enter> key is used to confirm selections. When pressed, this key provides additional
information about the point shown on the display. In a programming screen, pressing <Enter>
indicates that the information on the display is correct and can be entered. The <Enter> key is
used in various other places within the menu structure, always for this same type of operation.

Right and Left Arrow

The right and left arrows are used in screens with multiple choices. The keys advance the
focus (square brackets [ ] ) from field-to-field.

Previous and Next

The Previous and Next keys allow you to move from screen-to-screen within any displayable
object having multiple screens. This would include scrolling through an historical log, the
point database, a list of points, or other similar activities. The <‚ Next> key selects the next
display screen in sequence, and the < Previous> key selects the previous screen. These keys
are also used to view additional information about abnormal points or in viewing Historical
Logs.

1-10
Passcodes, Access Levels, and Logging In and Out

Overview Certain operator functions of the 4010 are passcode protected at different levels. This section
describes logging in and out at specific access levels.

Passcodes and Access All operations in the 4010 are protected at a preset level with designated passcodes to access
Levels these operations. Table 1-4 shows the basic operations and menu choices for specific access
levels. The default passcodes are listed for Levels 2 through 4. Refer to the Menu Structure
later in this chapter for a complete quick-reference of the main 4010 FACP menus.

Table 1-4: Access Levels and Operations

Access Level Operations

Ack
1 Silence
System Reset

All Level 1 Operations, plus:


2 Set Time/Date
Passcode = 2000 Point Control
Enable/Disable Points

All Level 1 & 2 Operations, plus:


Clear Logs
Clear Verification Tallies
Programming
3
- Edit/Clear Point Label
Passcode = 3000
- Restore/Save CFIG
TrueTest
Walk Test
Reports

All Level 1,2, & 3 Operations, plus:


Quick CFIG
Run Diagnostics
Upload/Download
Programming
4
- Edit Cards·
Passcode = 4000
- Edit SMPL Program
-·System Options
Restart Panel
-·Warm Start
-·Cold Start

Continued on next page

1-11
Passcodes, Access Levels, and Logging In and Out, Continued

Logging In and Out To execute any of the functions protected at Level 2 or above, you must Login to the FACP
using a passcode. After completing a task at a certain access level you should then Logout to
return the access level to Level 1. When logged in at Level 2 or above and you do not press
any front panel keys for more than ten minutes, the 4010 defaults to access level 1.

All passcodes consist of a four-digit number. Logging in at a Level 4 causes a Service Mode
trouble. Note that this trouble can only be cleared by restarting the panel.

To Login, perform Steps 1 through 7 on an 4010 that is at the High-Level Status screen (refer
to Figure 1-2 for an example of this screen). When moving from one digit to the next, an
asterisk (*) appears in the place of an entered number for security purposes. See Table 1-4 in
the previous section for the default passcodes.

1 Obtain the appropriate passcode information for the appropriate level.

2 Press <MENU>.

3 Press and hold <NEXT> until [Login/Logout] is displayed, and then press <ENTER>.

4 Press and hold <NEXT> until [Login] is displayed, and then press <ENTER>.

5 Press <NEXT> to scroll through the numbers on the display until the appropriate number
is displayed.

6 Press the right arrow to move the focus brackets [ ] to the next digit in the passcode.
Repeat Steps 5 & 6 until all numbers are entered.

7 When the passcode is correct, press <ENTER> to Login.

A **Login Accepted** screen indicating your current access level is displayed briefly upon a
successful Login attempt. If you did not enter the appropriate Login passcode, a **Login is
Invalid** screen appears.

To Logout, perform Steps 1 through 4 above except for Step 4 where you need to wait until
[Logout] is displayed.

1-12
Menu Structure

Refer to Figure 1-3 to review the 4010 menu structure.

Figure 1-3. 4010 Menu Structure

1-13
Chapter 2.
Back Box Mounting

Introduction This chapter contains instructions and guidelines for installing the 4010 FACP back box.

In This Chapter This chapter discusses the following topics:

Topic See Page #

Before You Begin 2-2

Removing the Chassis and Cutting Conduit Openings 2-3

Mounting the Back Box 2-4

Re-Installing the Chassis 2-5

Door-Mounted Annunciator Setup 2-6

2-1
Before You Begin

Unpacking the System • Carefully unpack the system and inspect it for shipping damage.

• Then select a location for the control panel in a clean, dry, vibration-free area with
a moderate temperature (see the “Environmental Specifications” section in Chapter 1)

Installation Guidelines Before installing the 4010, review the following guidelines:

• Install the FACP in a readily accessible area with sufficient room to easily install and
maintain the control panel.

• Locate the top of the cabinet approximately five feet above the floor with the door hinge
on the left-hand side.

• Count the number of conductors needed for all devices and cut the appropriate knockouts.
Pay careful attention to the routing for Power-Limited and Non-Power Limited wiring.
You must maintain a 1/4-inch separation between these two types of wiring. All terminal
connections are Power-Limited except those to the AC power, Battery, and City Circuit,
and contacts when switching Non-Power Limited sources.

• Review the precautions and warnings at the front of this publication.

• All wiring must comply with the National and/or Local codes for fire alarm systems. All
wiring must test free of grounds.

• Leave sufficient room for batteries in the bottom of the back box (see the label inside the
4010 back box for more information).

• Enclosure must be level and plumb when installed.

Standards and Codes When installing the 4010, you should be familiar with the following standards:

• NEC Article 300 Wiring Methods

• NEC Article 760 Fire Protective Signaling Systems

• Applicable Local and State Building Codes

• Requirements of the Local Authority Having Jurisdiction (AHJ)

2-2
Removing the Chassis and Cutting Conduit Openings

Overview The 4010 ships from the factory completely assembled in the back box, or as a single piece
electronics assembly that is shipped separately from the back box, retainer, and door. The
system electronics (SFI/O and power supply) are mounted to a steel chassis. Refer to the 526-
407 label inside the back box for additional information.

Step 1. Removing the Prior to installation you must remove the chassis containing the 4010 SFI/O and power supply
Chassis from the back box. Use the following steps to remove the chassis.

1. Remove the door grounding wire from the back box. Remove the door from the hinges
and set it aside.

2. Remove the metal retainer by gently lifting and pulling the bottom of the retainer out from
the back box. Then, being careful not to drop the retainer, slide the top of the retainer out
from under the lip of the top of the back box.

3. Remove the AC wiring Quick-Disconnect connector from the chassis by firmly squeezing
the release tabs and pulling it free. The Quick-Disconnect connector is located directly
below the chassis. Dress the wires so that they do not interfere with back box installation.

4. Loosen or remove the four mounting screws holding the chassis to the back box.

5. Lift the chassis out of the back box and store in a clean, dry, safe area for re-installation
later.

Step 2. Cutting Conduit Determine the amount and proper location of conduit/service entrances. Make all appropriate
Entrances entrances into back box (see Figure 2-1).

Caution: Power-Limited and Non-Power-Limited wiring must enter through separate


conduit/service entrances. AC power entrance into back box is recommended at the bottom
right side of the back box.

If a Bus Bar is required to terminate wire shields, see Figure 2-1 for proper mounting location.
Entrances for shielded wire must be located within two inches of the bus bar. Maximum
intrusion into box for conduit is 1/2-inch.

Figure 2-1. Conduit and Bus Bar Mounting Locations

2-3
Mounting the Back Box

Surface Mounting the 1. Using the pre-cut holes in the back of the box as a guide, mark off where you want to
Back Box mount the back box (see the “Before You Begin” section of this chapter).

2. Using mounting hardware capable of supporting a fully loaded 4010 (approximately 50


lbs.), screw two screws into the wall where the top two teardrop holes of the back box are
to be located. Tighten the screws, leaving about a 1/8-inch gap from the seated position.

3. Carefully lift the back box and place the two teardrop holes over the mounting screws.

4. Screw two mounting screws into the two bottom back box holes. Then tighten all screws.

Semi-Flush Mounting the 1. Remove the mounting knockouts from both sides of the back box. See Figure 2-2 for their
Back Box location.

2. Make the appropriate opening in the wall or wall board to accommodate the back box.
Dimensions of the back box are 22" (55.8 cm) W x 18 (45.7 cm) H x 6 ¼ (15.8 cm) D.

3. Frame the opening to accommodate the back box. Fit the back box into the opening. Use
wall stud guides to ensure free movement of the door.

4. Using mounting hardware capable of supporting a fully loaded 4010, screw or nail back
box to the studs.

FRO NT O F STU D FO R
1 /2 " W A L L B O A R D
FRO NT O F STU D FO R
5 /8 " W A L L B O A R D
6 1 /4 "

5 3 /8 "
DOOR

W A L L S T U D G U ID E S
( 1 /2 " W A L L B D ) KNOCKOUT
S C R E W /N A IL H O L E S
(F O R S E M I
F L U S H M O U N T .)

W A L L S T U D G U ID E S
( 5 /8 " W A L L B D )

S ID E V IE W

Figure 2-2. Wall Stud Guides

Continued on next page

2-4
Re-Installing the Chassis

Use the following steps to re-install the 4010 chassis containing the SFI/O and power supply
into the back box.

1. Insert two mounting screws into the top two mounting holes for the chassis. Tighten the
screws leaving a 1/8-inch gap from the seated position.

Caution: When mounting the chassis, pay careful attention to any wiring inside the back box.
Do not crimp any wiring behind the chassis when mounting.

2. Carefully hang the chassis on the two top mounting screws using the top teardrop holes on
the chassis.

3. Insert two mounting screws into the bottom two teardrop chassis mounting holes and
tighten all screws.

4. Re-hang the door on the back box hinges and re-attach the door grounding wire to the
back box.

5. You can re-install the retainer now before wiring or later after wiring is complete.
Re-install the retainer by guiding the top lip of the retainer under the top lip of the back
box and carefully sliding the bottom of the retainer into place.

WARNING: Do not apply power to the 4010 at this time! DO NOT connect the quick-dis-
connect AC connector to the chassis. Refer to the “Power-Up and Checkout” section of this
publication for more information.

2-5
Door-Mounted Annunciator Setup

Introduction If the panel contains a door-mounted annunciator, use the information in the following section
to set its address, N2 baud, and LED color switches.

Location of Switches Switches SW1 and SW2 set the door-mounted annunciator’s N2 baud rate and address,
respectively. Switches SW4, SW5, and SW6 allow you to set the color of each LED to either
red or yellow. The location of switches SW1 and SW2 is shown in the Figure 2-3. The
location of switches SW4, SW5, and SW6 is shown in Figure 2-4. See the appropriate section
for a description of each switch’s function and how to set it.

SW1

SW2
Figure 2-3. Location of SW1 and SW2

Remove Metal PCB The switches are located on a printed circuit board (PCB) that is mounted on the rear side of
Cover the door. A metal cover protects the PCB. To remove this cover, open the door and loosen the
four nuts, located at the four corners of the metal cover, and slide the cover toward the top of
the door to remove it.

Set N2 Baud Rate Switch The N2 communication channel connects the door-mounted annunciator with the main 4010
(SW1) SFIO board. The door-mounted annunciator's N2 baud rate is set via switch SW-1, which is
located as shown in Figure 2-3.

Note: The N2 baud rate set on the door-mounted annunciator must match the baud rate
setting enabled on the main board. See Chapter 3 of publication 574-187for information on
setting the baud rate on the 4010.

Settings for SW-1 are listed in Table 2-1. Refer to Figure 2-3 for the location of Switch SW1.
ON indicates the switch is in the UP position. Switch 1-1 is on the left of the switch block.
Switch 1-2 is on the right.

Continued on next page

2-6
Door-Mounted Annunciator Setup, Continued

Set N2 Baud Rate Switch


(SW1) Table 2-1: N2 Baud Settings

Baud SW 1-1 SW 1-2


Offline ON ON
9600 OFF ON
19. 200 ON OFF

Setting Card Address The door-mounted annunciator's card address, enabled via switch SW2, must be set within the
(SW2) range 9 through 14. Set the dip switches located on switch block SW2 as indicated in
Table 2-2. Refer to Figure 2-3 for the location of Switch SW2. ON indicates the switch is in
the UP position. Switch 2-1 is on the left of the switch block. Switch 2-8 is on the right.

Note: The 4010 programmer automatically assigns the next available address between 9 and
14 to the 24 point I/O card that represents the door-mounted annunciator. Before setting the
switches, use the programmer to add a 24 point I/O card to the job. Record the address
assigned to the card and then set the annunciator’s switches to this address. (The door-
mounted annunciator does not have a unique card type and is represented in the programmer
by a 24 point I/O card.)

Table 2-2: Card Address Settings

2-1 2-2 2-3 2-4 2-5 2-6 2-7 2-8

9 ON OFF OFF ON OFF OFF OFF OFF

10 OFF ON OFF ON OFF OFF OFF OFF

12 OFF OFF ON ON OFF OFF OFF OFF

13 ON OFF ON ON OFF OFF OFF OFF

14 OFF ON ON ON OFF OFF OFF OFF

Setting LED Color The color of each LED is determined by the setting of a switch on the door-mounted
Switches (SW4, SW5, annunciator PCB. There are three switch blocks, each containing eight switches, and each
SW6) switch is labeled with a zone number (ZN1, for example). For each LED, move the
appropriate switch to the left to enable the LED color as Red, or move the switch to the right to
enable the LED color as Yellow.
SW6 SW5 SW4

Figure 2-4. Location LED Color Switches

Continued on next page

2-7
Door-Mounted Annunciator Setup, Continued

Setting LED Color Zone numbers correspond to the LEDs on the front of the door as shown in Figure 2-5.
Switches (SW4, SW5,
SW6)

Figure 2-5. Zone Number/LED Assignments

Important Note: When programming the operation of the LEDs, be aware that the zone
number corresponds to the second number in the door annunciator’s point name. For
example, if the door-mounted annunciator's card number is 9, the point name 9-1 corre-
sponds to the LED labeled ZN1.

For Canadian applications, LED colors must comply with Table 2-3.

Table 2-3: Color Codes for Visual Indicators (Canada)

Function Color
Alarm Inputs Red
Alarm Signal Red with unique identifier
Alert Signal Red with unique identifier
Page Select Green
Signal Circuit Fault Yellow
Ancillary Device “ON” Green
Ancillary Device “OFF” Yellow
Telephone Call-in Flashing Green
Telephone Select Green
Telephone Circuit Fault Yellow
Inhibit Yellow
Preannounce Yellow
Supervisory Inputs Yellow with unique identifier
Power - ON Green
Trouble Signal Yellow
Alarm Signal Silence Yellow
Automatic Alarm Signal Green
Activation Timer
Automatic Alarm Signal Activa- Yellow
tion Timer Cancelled (Ack’d)

Note: The door-mounted annunciator supports only red/yellow LED. Green LEDs are avail-
able via optional LED modules.

Continued on next page

2-8
Door-Mounted Annunciator Setup, Continued

Programming LEDs Refer to 574-187 for information on programming the 4010.

1. Add a 24 point I/O card to the job. The address of the card you add must match the
address set via dip switches.
2. Define the card’s device type as GRAPHOUT.
3. For each point, define the Point Type as a Lamp.
4. Assign each point a mode (i.e., what action triggers the LED to illuminate).
5. Click on the Ref Addr field and select the point whose state change will trigger the LED to
illuminate.

2-9
Chapter 3.
Wiring

Introduction This chapter contains instructions and guidelines for wiring the 4010 FACP.

Use the information in this chapter, as well as the 526-407 and 526-408 labels located on the
inside door of the FACP, and the 842-058 Field Wiring Diagram, to wire the base panel.

Refer to the publications listed in Chapter 1 to wire all optional modules.

In This Chapter This chapter discusses the following topics:

Topic See Page #

Overview 3-2

NAC Wiring 3-4

IDNet Wiring 3-5

AC Power and Battery Wiring 3-6

Auxiliary Relays 3-9

System Power-Up and Checkout 3-10

Periodic Testing and Maintenance 3-13

3-1
Overview

Power Limited Versus The 4010 system can be wired as either a power limited or non-power limited system. Adhere
Non-Power Limited to the following guidelines and consult the NEC for specifics.
Systems
• When installing the 4010 as a power limited system, you must observe the following
guidelines:

• Maintain ¼ inch of space between power limited wiring and AC power or battery
wiring.

• Run AC power wiring in a separate conduit that enters the back box in the upper or
lower right corner.

• Route AC power, battery wiring, city circuit connections, and non-power limited
relay wiring only through the shaded areas shown in Figure 3-1. Do not route power
limited wiring through the shaded areas shown in the figure.

• The 4010 FACP can be reclassified as a non-power limited system when installed in
accordance with the latest version of NEC 760. In this case, all references to power
limited must be removed from the panel's labels.
18"

DISCARD
AFTER
SHIPPING

22"
AC POWER
HARNESS

14.5"

BATTERY AREA
NO CONDUIT ENTRY OR AC TERMINAL
8 1/2" WIRING IN THIS AREA BLOCK

SHADED AREA
IS FOR NON-POWER
FRONT VIEW LIMITED WIRING ONLY

Figure 3-1. Location of Non-Power Limited Wiring Area

Continued on next page

3-2
Overview, Continued

Locations of Terminal Figure 3-2 shows the location of all terminal connections for the system components. Refer to
Connections the appropriate section later in this chapter for specific information on wiring a component.

Figure 3-2. Base Panel Wiring

3-3
NAC Wiring

Overview The 4010 provides four NACs for notification appliances such as horns and strobes. These
NACs are standard Class B (Style Y). Optional Class A (Style Z) operation can be achieved
using an adapter. Refer to the 4010-9806 Class A Module Installation Instructions (574-055)
for information on the Class A NAC adapter.

The NACs supervise for short or open circuit troubles. In the event of a short, the NAC does
not energize. Each NAC is rated at 2 A. Up to 4 A of NAC power is available from the base
unit. If more power is needed, NAC 3 and NAC 4 can be connected to an expansion power
supply.

An auxiliary (AUX) power connection (rated at ½ A, 24 VDC) is provided at TB5 located to


the left of the auxiliary (AUX) relay terminal blocks at the bottom center of the SFI/O. Current
drawn from TB5 must be deducted from the 4 A total NAC power.

Each NAC can be configured as “On until Silence” or “On until Reset” and can be coded or
non-coded (refer to “Chapter 6 - Configuring Points” for more information). The 4010 can
disconnect each NAC individually to aid in locating earth faults.

Terminal Connections The NAC's wiring connects to TB1 and TB2 as shown in Figure 3-3. These terminal blocks
are barrier strip type that can accommodate 12-18 AWG wires. TB1 and TB2 are located in the
upper left corner of the SFI/O. Refer to the 842-058 wiring diagram for alarm current,
wiring distance, and line resistance values.

TB1-1: NAC 1 + Alarm TB2-1: NAC 3 + Alarm

TB1-2: NAC 1 - Alarm TB2-2: NAC 3 - Alarm

TB1-3: NAC 2 + Alarm TB2-3: NAC 4 + Alarm

TB1-4: NAC 2 - Alarm TB2-4: NAC 4 - Alarm

NAC 1 NAC 2 NAC 3 NAC 4

Alm+ Alm- Alm+ Alm- Alm+ Alm- Alm+ Alm-

TB2
TB1

1 2 3 4 1 2 3 4

Figure 3-3. NAC Wiring

3-4
IDNet Wiring

Overview The 4010 uses addressable IDNet devices (smoke and heat detectors/sensors and pull stations,
4009 IDNet NAC Extender, etc.). The 4010 supports 250 devices on a single pair of wires on
a single channel.

The IDNet channel supports Style 4 and 6 as part of the base system. Refer to the 4010 Field
Wiring Diagram (842-058) for all wiring information.

IDNet communication also supports the detection of duplicate devices. IDNet detects if two
devices are set to the same address. This function is activated from the front panel (see IDNet
Diagnostics in the Diagnostic/Troubleshooting section of this publication).

Terminal Connections Use the following information to wire the IDNet communication lines (14-18 AWG) to TB4
located in the upper right corner of the SFI/O.

• To connect Class A wiring, wire the “B” terminals (TB4-1 and -2) to each device in
succession without T-taps (observe polarity). At the last device in the loop, return the B+
wire to the A+ terminal (TB4-4) and the B- wire to the A- terminal (TB4-5).

• To connect Class B wiring, jumper B+ to A+ and B- to A- using 14-18 AWG insulated


wire (T-taps are allowed). Connect B+ to all devices (positive connection) and connect B-
to all devices (negative connection).

IDNet Comms

A- A+ SHLD B- B+

Figure 3-4. IDNet Connections

3-5
AC Power and Battery Wiring

AC Power When the 4010 FACP is installed as a power-limited system, AC power lines must be run in a
separate conduit, and should enter the back box in the lower right corner. Use the shaded area
of Figure 3-5 only for routing of AC power wiring. All wiring must be neatly dressed within
the back box. Use the wiring guides inside the back box when possible.

• The FACP requires connection to a separate dedicated AC fire alarm circuit, which must
be labeled “Fire Alarm.”

• The AC power circuit must connect to the line side of the main power feed of the
protected premises.

• No other equipment can be powered from the fire alarm circuit.

• The AC power circuit wiring must run continuously, without any disconnect devices, from
the power source to the FACP.

• Over-current protection for this circuit must comply with Article 760 of the National
Electric Code as well as local codes.

• Use 12 AWG wire with 600-volt insulation for this circuit.

1 Match incoming Neutral and Hot


wires to their corresponding wires
leading from the terminal block
located in the lower right corner of
the back box to the Quick-
Disconnect harness and screw
WIRE
into place. GUIDES
2 The safety ground wire from the
AC source must be connected to
the ground stud located below the
terminal block. Do the following to AC POWER
HARNESS
connect the ground wire to the
stud:
a) Run the ground wire to the stud 14.5"

and cut it, leaving a little slack BATTERY AREA


for adjustment. NO CONDUIT ENTRY OR AC TERMINAL
WIRING IN THIS AREA BLOCK
b) Crimp a spade terminal (Part
No. 474-144 or -015) onto the
ground wire.
SHADED AREA
c) Place a lock washer on the IS FOR NON-POWER
LIMITED WIRING ONLY
stud, followed by the terminal
and then another lock washer.
d) Securely fashion a nut (Part Figure 3-5. AC Power Wiring
No. 322-128) onto the stud.

Continued on next page

3-6
AC Power and Battery Wiring, Continued

Installing and The base 4010 FACP accommodates (and charges) up to 25 Ah capacity batteries. The
Connecting Batteries following is a list of compatible batteries.

• ·2081-9272, 6.2 Ah

• ·2081-9274, 10 Ah

• ·2081-9275, 18 Ah

• ·2081-9288, 12.7 Ah

• ·2081-9287, 25 Ah

Install the batteries in the area shown on the label located in the bottom of the back box. Use
the 733-945 Battery Harness (733-903 for Canadian systems), to connect the batteries to TB8
located in the lower left corner of the SFI/O.

• Canadian systems should use Figure 3-7 (on the next page) as an installation guide.

• U.S. systems should use the following procedure and Figure 3-6.

1 Using the short white wire crimped at both ends, jumper one positive (+) terminal of one
battery to the negative (-) terminal of the other battery.

2 Take the non-crimped end of the red wire from the harness and connect this to the + side
of TB8.

3 Take the non-crimped end of the black wire from the harness and connect this to the - side
of TB8.

TB8

- BATTERY +

Figure 3-6. Battery Connections - U.S.

Continued on next page

3-7
AC Power and Battery Wiring, Continued

WARNING: Do not apply power to the 4010 at this time! DO NOT connect crimped ends
of the red and black wires to the battery. Refer to the “Power-Up and Checkout” section of this
publication for more information.

CANADIAN LOW BATTERY MODULE

P4

SF I/O BD
565-738 RED BLK

RELAY

6 5
4 3
2 1

BTRY
RED

TB8

BATTERY HARNESS
733-903

RED

BATTERY BATTERY

Figure 3-7. Canadian Battery Wiring

WARNING: Do not apply power to the 4010 at this time! DO NOT connect crimped ends
of the red and black wires to the battery. Refer to the “Power-Up and Checkout” section of
this publication for more information.

3-8
Auxiliary Relays

The 4010 provides two programmable auxiliary (AUX) relay circuit connections: one at TB6
and the other at TB7. Each circuit provides one form "C" contact (normally open or normally
closed) rated at 2 A (24 VDC), or 0.5 A (120 VAC) with the optional 120 Volt auxiliary relay
kit.

The default operation for AUX1 is an Alarm Relay and AUX2 is a Trouble Relay. The AUX
relay circuits can also be programmed for other desired operations using the front panel (see
“Chapter 6 - Configuring Points”).

Use Figure 3-8 to wire the AUX relay circuits. TB6 and TB7 are located at the bottom of the
SFI/O near the center.

When power for the AUX relay contacts is from TB5 (AUX Power), 4010-9813, or 4010-9814
expansion power supplies, the circuit is power-limited. When power for the AUX relay
contacts IS NOT from the sources listed above, use an in-line fuse (Part No. 208-165). If the
power source is non-power-limited, wiring must be routed through the non-power-limited
spaces shown in Figure 3-1, and “power-limited” markings must be obliterated.
TB6 TB7

NO C NC NO C NC

BOTTOM OF SFI/O
AUX1 AUX2

Figure 3-8. AUX Relay Connections

3-9
System Power-Up and Checkout

Connecting AC and Use the following steps to apply AC and battery power to the 4010 FACP.
Battery Power
1 Re-connect the AC power harness removed in previous steps.

2 Connect the crimped ends of the 733-945 battery harness (733-903 for Canadian systems)
to the batteries. Observe polarity (red to +, black to -) when connecting batteries.

WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and eyes,
and can destroy fabrics. Replace any leaking or damaged battery. If contact is made with
sulfuric acid, immediately flush skin or eyes with water for 15 minutes and seek immediate
medical attention.

Power-Up Caution: Notify fire, central station, and/or building personnel before testing the system.

Power-Up

After applying power to the system, use the following list to check the 4010 for proper
operation.

• Check that the green AC Power LED is ON.

• Check that all yellow and red LEDs are OFF.

• Use the Lamp Test procedure in “Chapter 11 - Operation” of this publication to verify that
all 4010 LEDs and LCD segments work properly.

On power-up, the 4010 performs the following:

• Displays revision of boot-loader software

• Self Test - CPU Hardware Checkout

• Linkscan - Checking for a Programmer Unit Connection

• Memory Scan - Checking for Incorrect Application

• Start up - 4010 FACP Startup

Figure 3-9. 4010 Startup Screen

Continued on next page

3-10
System Power-Up and Checkout, Continued

Power-Up If the 4010 passes its start up self-test, the FACP starts and the system is normal, the High-
Level Status screen shown in Figure 3-10 displays. If troubles exist in the system, Figure 3-11
displays after pressing <ACK>.

Note: The High-Level Status screen is the first screen shown on a 4010 whether in a normal or
a trouble/supervisory/fire alarm state before any keys are pressed.

SYST
SYSTEMEM
IS I
S NOR
NORMAL M
A
L
1
0
:0
9:3 3 am Tue 27-Nov-01
10:09:33am T ue 2 7-
N
ov
-1
0

Figure 3-10. System Normal (High Level Status) Screen

FIRE=0 SUPERVISORY=0 TROUBLE=3


CUSTOM LABEL
FIRST FLOOR EAST WING ROOM 12
Smoke Detector Trouble 1/3
POINT TYPE

DEVICE CONDITION FIRST OF 3 TROUBLES

Figure 3-11. System Trouble Screen

Note: If the self-test fails, the 4010 displays the error code and waits 45 seconds before
attempting a restart. Refer to Chapter 10 for a list of error codes.

Before Checkout Before proceeding with the acceptance test procedures, do the following:

• Notify the fire department and the central alarm receiving station if transmitting alarm
conditions.

• Notify building personnel of the test so that alarm sounding devices are disregarded
during the test session.

• When necessary, disable activation of alarm notification appliances and speakers to


prevent their sounding.

Continued on next page

3-11
System Power-Up and Checkout, Continued

Checkout (Acceptance When you are finished with the original installation and all modifications, conduct a complete
Testing) operational test on the entire installation to verify compliance with applicable NFPA standards.
Testing should be conducted by a Simplex-trained technical representative in the presence of a
representative of the Authority Having Jurisdiction, and the customer's representative. Follow
the procedures outlined in Chapter 7 “Inspection, Testing, and Maintenance” of NFPA
Standard 72 and the following steps.

1 Activate an initiating device (smoke, pull, etc.) and check that all active notification
appliances (strobes, horns, etc.) function. Reset the alarm initiating device, the FACP, and
any other associated equipment. Repeat this step for each initiating device.

2 Remove AC power, activate an initiating device, and check that active notification
appliances sound, and alarm indicators illuminate. Measure the battery voltage with
notification appliances active. Replace any battery with a voltage of less than 24VDC and
reapply AC power.

Note: Step 2 requires fully charged batteries. If batteries are new or discharged due to a
recent power outage, allow the batteries to charge for 48 hours before testing. Refer to
“Periodic Testing and Maintenance” section for more information on testing batteries.

3 Reapply AC power and check that all yellow and red LEDs are OFF and the green AC
Power LED is ON.

Caution: Notify fire, central station, and/or building personnel when you finish testing the
system.

3-12
Periodic Testing and Maintenance

Overview Periodic testing and maintenance of the FACP, all initiating and notification devices, and any
other associated equipment is essential to ensure proper and reliable operation. Test and
maintain the FACP according to the schedules and procedures outlined in the following
publications:

• NFPA Standard 72, Chapter 7, “Inspection, Testing, and Maintenance.”

• Installation Instructions for the peripheral devices installed in your system. Correct any
trouble condition or malfunction immediately.

Periodic testing and maintenance of the system batteries must be done to ensure proper and
reliable back-up operation. Test and maintain the system batteries using the following
information.

Battery Testing All sealed lead-acid batteries in fire alarm service should be tested annually. Replace all
Information sealed lead-acid batteries that have been in service for four or more years.

It is recommended that a battery tester made specifically for checking sealed lead-acid
batteries be used. Such a tester is available under Service Part No. 553-602.

If a battery tester is unavailable, the “voltage response test” described in the following
information can be used to detect batteries with very low capacity or shorted cells.

Caution: A defective battery charger circuit can cause battery failure. Check the condition of
the battery charger when either a battery tester or a voltage response test reveals weakened
batteries.

Voltage Response Test

1 Disconnect the battery from the system.

2 Connect a digital voltmeter across the battery.

3 Connect the appropriate sized resistor(s) (see Table 3-1) across the battery's terminals for
the listed test time.

Caution: Resistors will get hot during the test! Use 12 AWG wire for the battery-to-
resistor hookup.

4 Record the end voltage reading.

5 Treat the battery as described in Table 3-2.

Continued on next page

3-13
Periodic Testing and Maintenance, Continued

Battery Testing
Information

Table 3-1: Battery Testing

Resistor Part No. and


Voltage Amp Hr Watts Test Time
(Ohms) Description

12 6.2 6.0 50 380-031 2 Seconds

380-031 (adj
12 8 4.5 50 2 Seconds
to 4.5 Ohm)

380-031 (adj
12 10 4.0 50 2 Seconds
to 4 Ohm)

380-031
12 18 2.0 100 2 Seconds
(3 in parallel)

382-090
12 25 1.5 100 2 Seconds
(2 in parallel)

382-090
12 33 1.0 150 2 Seconds
(3 in parallel)

382-090
6* 50 1.0 150 4 Seconds
(3 in parallel)

382-090
12 110 1.0 150 4 Seconds
(3 in parallel)

*Test batteries in series for 12 V

Table 3-2: Battery Readings and Instructions

If end voltage reading of battery is: Instructions

11.8V or more Put in Service

11.7V to 11.0V Charge Battery*

10.9V or less Discard Battery

*Re-test battery after charging

Discard battery after four or more years of service. Dispose of according to manufacturer's
guidelines.

3-14
Chapter 4.
Quick CFIG

Introduction The Quick CFIG option provides you with the ability to quickly and automatically program the
components and features of the 4010. Quick CFIG is especially useful for programming basic
system components following a new installation, and for adding components to an existing
installation.

Quick CFIG functions include the following:

• Reconfigure All Hardware

• Autodetect all new hardware added since CFIG was last saved

• Restore the Factory CFIG

• Accept default settings for system options

• Edit settings of system options

In This Chapter This chapter discusses the following topics:

Topic See Page #

Cautions and Warnings 4-2

Reconfiguring All Hardware 4-3

Auto Detecting New Hardware 4-4

Restoring Factory CFIG 4-5

Accepting Default Settings for System Options 4-6

Editing Settings for System Options 4-7

Save CFIG Option 4-9

4-1
Cautions and Warnings

Be alert to the following when using Quick CFIG:

WARNING: The 4010 system will NOT continue to operate as a Fire Alarm System during
the programming of Quick CFIG operations.

• Quick CFIG performs an IDNet duplicate address search, and terminates if duplicate
addresses are found.

• Using the Quick CFIG options changes the 4010 configuration. When changing the
configuration, information could be lost.

• Quick CFIG is not allowed if a DACT or network card is installed. Use Quick CFIG first,
and then program the DACT or network card.

• Class A Adapters are not automatically detected by Quick CFIG. Refer to Chapter 6 for
information on programming a Class A NAC.

• TrueAlert Non-Addressable functions are not accessible through Quick CFIG. You must
manually program the appropriate NACs with the TrueAlert point type to enable
TrueAlert operation. Refer to Chapter 6 for information on manually programming a
NAC's point type.

• Quick CFIG automatically configures the hardware device type for a 4009 (4009A,
R4009A, 4009A8, R4009A8). All 4009 NACs are set for Class B operation and assigned
a point type of SSIGNAL.

4-2
Reconfiguring All Hardware

Overview This option starts the 4010 with a new configuration. If a configuration already exists and this
option is selected, it clears the current configuration and adds all currently connected devices
to the CFIG.

Procedure 1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [Quick CFIG] is displayed and then press
<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

Please Wait . . .
Fire Alarm Operation Suspended

3. Press <ENTER> to continue with the Quick-CFIG option.

4. Press <NEXT> or <PREVIOUS> until <RECONFIGURE ALL HARDWARE> is


displayed and then press <ENTER>. A warning appears, indicating that this will delete
the current configuration.

WARNING <Enter> to Continue WARNING


This will DELETE current configuration

5. Press <ENTER> to continue. Another warning appears, indicating that you need to press
<ENTER> to confirm the deletion.

WARNING <Enter> to Continue WARNING


Press <ENTER> to confirm deletion

A message appears indicating that Quick CFIG is reconfiguring the hardware. This message is
followed by another, which indicates that Quick CFIG is scanning for IDNET devices. The
Reconfigure ALL Hardware function is complete when a message similar to the following
appears.

** Automatic Hardware Detection Completed **


Total IDNet Devices Added: 128

Refer to "Save CFIG Option" at the end of this chapter for information on saving the CFIG
once you have reconfigured the hardware.

4-3
Auto Detecting New Hardware

Overview This option adds new hardware that is not currently in the CFIG. All existing hardware and
programming remains the same.

Procedure 1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [Quick CFIG] is displayed and then press
<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

Please Wait . . .
Fire Alarm Operation Suspended

3. Press <ENTER> to continue with the Quick-CFIG option.

4. Press <NEXT> or <PREVIOUS> until <AUTO DETECT NEW HARDWARE> is


displayed and then press <ENTER>. A warning appears, indicating that this will change
the current configuration.

WARNING <Enter> to Continue WARNING


This will CHANGE current configuration

5. Press <ENTER> to continue. Another warning appears, indicating that you need to press
<ENTER> to confirm the hardware detection operation.

WARNING <Enter> to Continue WARNING


Press <ENTER> to confirm Detect NEW

A message appears indicating that Quick CFIG is reconfiguring the hardware. This
message is followed by another, which indicates that Quick CFIG is scanning for IDNET
devices. The Auto Detect NEW Hardware function is complete when a message similar to
the following appears.

** Automatic Hardware Detection Completed **


Total IDNet Devices Added: 128

Refer to "Save CFIG Option" at the end of this chapter for information on saving the
CFIG once you have reconfigured the hardware.

Continued on next page

4-4
Restoring Factory CFIG

Overview This option restores the 4010 to its original (factory default) CFIG. All pseudo points (Analog
and Digital) are cleared, Custom Control is erased, etc.

Procedure 1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [Quick CFIG] is displayed and then press
<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

Please Wait . . .
Fire Alarm Operation Suspended

3. Press <ENTER> to continue with the Quick-CFIG option.

4. Press <NEXT> or <PREVIOUS> until <RESTORE FACTORY CONFIG.> is displayed


and then press <ENTER>. A warning appears, indicating that this will delete the current
configuration.

WARNING <Enter> to Continue WARNING


This will DELETE current configuration

5. Press <ENTER> to continue. The following message appears, indicating that the system
is restoring the factory default configuration.

** Restoring Factory Default Panel **

This message is followed by a series of internal test messages. The High-Level Status
screen appears when the operation is complete.

4-5
Accepting Default Settings for System Options

Overview This section describes how to set the panel to its default settings via Quick CFIG.

Procedure 1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [Quick CFIG] is displayed and then press
<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

Please Wait . . .
Fire Alarm Operation Suspended

3. Press <ENTER> to continue with the Quick-CFIG option.

4. Press <NEXT> or <PREVIOUS> until <ACCEPT DEFAULT OPTIONS> is displayed


and then press <ENTER>. A warning appears, indicating that this operation may change
current settings.

WARNING <Enter> to Continue WARNING


This may CHANGE current setting

5. Press <ENTER> to continue. The following message appears, indicating that the system
is restoring the default settings for system options.

** Default Settings Restored **

4-6
Editing Settings for System Options

Overview Once this action is selected from the Quick CFIG menu, you can set these options by scrolling
through the choices shown in Table 4-1 and selecting the appropriate settings for each. For
timer options, selecting "0"initiates the action immediately.

Procedure 1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [Quick CFIG] is displayed and then press
<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

Please Wait . . .
Fire Alarm Operation Suspended

3. Press <ENTER> to continue with the Quick-CFIG option.

4. Press <NEXT> or <PREVIOUS> until <EDIT SYSTEM OPTIONS> is displayed and


then press <ENTER>.

5. Use the <NEXT> and <PREVIOUS> keys to scroll through the system options. Edit each
of the system options as necessary, using the information in Table 4-1. Refer to Chapter 7
for specific information on system options.

Table 4-1: System Options and Available Settings

System Option Settings

Time/Date Format Choose 12- or 24-Hour Format

Active Status Reminder Choose:


ON or OFF (default = OFF)
Set Reminder Interval (1 - 12 hours; default = 8)
Signal Duration (0 - 60 seconds; 0 = ON until clear;
default = 5)

Alarm Silence/Reset Choose a timer range from 0 - 60 minutes (default = 0)


Inhibit

Alarm Cutout Timer Choose a timer range from 0 - 60 minutes (default = 0)

Door Drop on Alarm Choose a timer range from 0 - 60 minutes (default = 0)

Door Drop on AC Choose a timer range from 0 - 60 minutes (default = 0)


Power Loss

Audible NAC Operation Choose:


• Audible NACs: Steady
• Audible NACs: Slow March
• Audible NACs: Fast March
• Audible NACs: Temporal (default)

Continued on next page

4-7
Editing Settings for System Options, Continued

Procedure Table 4-1: System Options and Available Settings (continued)

System Option Settings

Visual NAC Operation Choose:


• Visual NACs: Steady
• Visual NACs: Slow March
• Visual NACs: Fast March
• Visual NACs: Temporal
• Visual NACs: Synchronous (default)

TrueAlert Choose:
Non-Addressable NAC • Temporal (default)
Horn Operation • Steady
• Slow March

Depleted Battery Cutout Choose ON or OFF; default = OFF. Note: Set Depleted
Battery Cutout to ON for suppression release systems.

Stagger Start AHU Choose a timer range from 0 - 60 seconds; default = 30

Enable City Circuit Choose ON or OFF; default = OFF

Expansion Power Choose ON or OFF; default = OFF

Suppression Release Choose:


(refer to Chapter 7 for ON or OFF (default = OFF)
more information) Dual Detector (default = OFF)
Detector Delay (default = 60)
Manual Delay (default = 30)

Edit Passcodes* Change Passcode Designations

Logical Zone Labels* Apply Zone Labels

*Available under Quick-CFICG System Options Menu Only.

4-8
Save CFIG Option

Depending on whether or not you will be doing additional programming (such as changing
hardware and point types, etc.), you may want to save the CFIG following the Quick CFIG
operation.

The Save CFIG option saves all information to the 4010 configuration after or during
programming. Choose this option if you wish to save all of the edits and modifications you
made during your programming session to the 4010 configuration. You can Save CFIG by
choosing the menu option or pressing Exit/Clear to back out of Programming mode and then
choosing the Save CFIG option from the 4010 prompts.

When exiting the programming mode, your 4010 re-boots and becomes operational as a fire
alarm system.

4-9
Chapter 5.
Configuring Cards

Introduction The 4010 allows you to manually configure each option card in the system. This chapter
describes how to add, delete, or modify optional cards in the 4010 FACP.

Note: The system must be powered down before cards are added to the system.

In This Chapter This chapter discusses the following topics:

Topic See Page #

Card Addresses 5-2

Adding, Deleting, or Modifying 4010 Cards 5-3

5-1
Card Addresses

All card addresses (whether hardware or logical cards) are shown in Table 5-1.

Table 5-1: 4010 Card Addresses

Card Address Reserved Cards

0 CPU Board

1 NAC/Relay circuits

2 Power Supply

3 IDNet Channel

4 Dual RS232 or Service Modem

5-7 Unused

8 4120 Network or DACT cards

9 - 14 N2 Slaves (24-Point I/O or LCD Annunciator)

15 - 16 Unused

17 4009 IDNet NAC Extender

18 System Digital Pseudo Points

19 User Digital Pseudo Points

20 System Analog Pseudo Points

21 User Analog Pseudo Points

22 System List Pseudo Points

23 User List Pseudo Points

5-2
Adding, Deleting, or Modifying 4010 Cards

Overview This section describes how to add, delete, or modify cards in a 4010FACP. Be aware of the
following configuration rules when adding, deleting, or modifying cards.

• Cards 1 through 3 and 17 through 23 cannot be deleted.

• Certain cards are mutually exclusive. For example:

• One 4120 Network Card or One DACT is allowed.

• One Dual RS232 Card or One RS232/Modem is allowed.

• The City Circuit card and Expansion Power Supply are enabled via the System Options
menu. Refer to Chapter 7 for information on doing this.

• The DACT and Network cards are programmed and added to the 4010PC Programming
tool.

Adding a Card Use the following steps to add a card to the 4010 FACP.

1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed and then press


<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

Please Wait . . .
Fire Alarm Operation Suspended

3. Press <ENTER> to continue.

4. Press <NEXT> or <PREVIOUS> until <CONFIGURE CARDS> is displayed and then


press <ENTER>.

5. Press <NEXT> or <PREVIOUS> until <ADD 4010 CARD> is displayed.

6. Press <NEXT> or <PREVIOUS> to scroll through the following choices.

• RS232 Card (Card Address 4)

• Modem Card (Card Address 4)

• 24IO Card (Card Address 9 through 14)

• LCD (Card Address 9 through 14)

7. Once the desired card is displayed, press Enter. The RS232 and Modem cards are
automatically set to card address 4. Follow the prompts to confirm this action.

Continued on next page

5-3
Adding, Deleting, or Modifying 4010 Cards, Continued

Adding a Card 8. When first adding a 24-Point I/O or LCD Annuciator card to the 4010, you must choose an
available address of 9 through 14. (The system automatically picks the next available
address.) When selecting 24IO or LCD and then pressing Enter, the following figure
appears.

Card = [09]
Card Type = LCD Card

9. Press <NEXT> or <PREVIOUS> to scroll through the available addresses, select the
appropriate address for your card, and then press Enter. Follow the prompts to confirm
this action.

Deleting a Card Use the following steps to delete a card from the 4010 FACP.

1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed and then press


<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

Please Wait . . .
Fire Alarm Operation Suspended

3. Press <ENTER> to continue.

4. Press <NEXT> or <PREVIOUS> until <CONFIGURE CARDS> is displayed and then


press <ENTER>.

Caution: Deleting 4010 Cards also deletes any modes and SMPL (Custom Control)
programming associated with that card.

5. After selecting Delete a 4010 Card as your option under the Configure Cards menu, press
<NEXT> or <PREVIOUS> to scroll through the cards configured in the 4010 FACP.

6. When the card you wish to delete is displayed, press Enter.

7. Follow the prompts to confirm this action.

Continued on next page

5-4
Adding, Deleting, or Modifying 4010 Cards, Continued

Modifying a Card Use the following steps to modify a card in the 4010 FACP. The only cards you can modify
from this menu are the Dual RS232, Modem/RS232, and LCD Annunciator cards.

1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed and then press


<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

Please Wait . . .
Fire Alarm Operation Suspended

3. Press <ENTER> to continue.

4. Press <NEXT> or <PREVIOUS> until <CONFIGURE CARDS> is displayed and then


press <ENTER>.

5. Press <NEXT> or <PREVIOUS> until <MODIFY A 4010 CARD> is displayed.

6. Press <NEXT> or <PREVIOUS> to scroll through the cards configured in the 4010
FACP.

7. When the card you wish to modify is displayed, press Enter. The available modifications
you can make per card are shown in Table 5-2. The 4010 prompts you on which keys to
press to execute different options.

Continued on next page

5-5
Adding, Deleting, or Modifying 4010 Cards, Continued

Modifying a Card

Table 5-2: Modification Options for 4010 Cards

4010 Card Modifications

RS-232 Card Device:


Port A and Port B PRT40U (unsupervised 40-Column printer)
PRT40S (supervised 40-Column printer)
PRT80U (unsupervised 80-Column printer)
PRT80S (supervised 80-Column printer)
UNUSED
COMMAND (For use with a CRT on Port B Only)
Baud Rates: 1200, 2400, 4800, 9600, 19200, 38400
Parity: NONE, EVEN, ODD
Note: To print reports, you must have an 80-column printer.

Modem Card Device:


Port A and Port B PRT40U (unsupervised 40-Column printer)
PRT40S (supervised 40-Column printer)
PRT80U (unsupervised 80-Column printer)
PRT80S (supervised 80-Column printer)
UNUSED
COMMAND (For use with a CRT on Port B Only)
Baud Rates: 1200, 2400, 4800, 9600, 19200, 38400
Parity: NONE, EVEN, ODD

LCD Card Enter selects ALL events to report to the LCD, Default Key
Operation, and Default Overrides.
Pressing Next allows you to choose Yes or No for the
following:
EVENTS: Fire, Supervisory, Trouble, Reset/Silence, Test,
CCE Print Events
KEY OPERATION: Fire Ack, Supv Ack, Trouble Ack,
System Reset, Alarm Silence
OVERRIDE ON ALARM: Fire Ack, Supv Ack, Trouble
Ack, System Reset, Alarm Silence

5-6
Chapter 6.
Configuring Points

Introduction The 4010 allows you to manually program each point in the system. This chapter describes
how to add, delete, edit, etc., points in the 4010 FACP. The following information assumes
you have all cards properly installed. If your cards are not installed properly or need
modification, refer to “Chapter 5 . Configuring Cards.”

In This Chapter This chapter discusses the following topics:

Topic See Page #

The Configure Points Menu 6-2

Configuring TrueAlarm Points 6-3

Configuring ZAM/IAM/RIAM Points 6-6

Configuring Programmable Relay and NAC Points 6-9

Configuring Digital and Analog Pseudo Points 6-11

Configuring 24-Point Programmable I/O Points 6-14

Configuring List Points 6-17

Configuring User-Defined Programmable Switches and LEDs 6-19

6-1
The Configure Points Menu

All options for configuring 4010 points are located in the Configure Points menu. Figure 6-1
shows the structure of this menu.
Programming Menus

Save Configure Configure


CFIG Points Cards

• TrueAlarm
• ZAMs/IAMs/RIAMs
• Relay
• NACs
• Digital Pseudos
• Analog Pseudos
• 24-I/O Outputs
• 24-I/O Inputs
• Lists
• User Defined SW/LED

Figure 6-1. Configure Points Menu

6-2
Configuring TrueAlarm Points

Overview This section describes how to add an IDNet point, edit a TrueAlarm point, and delete a
TrueAlarmTrueAlarm point.

Adding an IDNet Point Use the following steps to add an IDNet point to the 4010 FACP.

1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed and then press


<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

Please Wait . . .
Fire Alarm Operation Suspended

3. Press <ENTER> to continue.

4. Press <NEXT> or <PREVIOUS> until <CONFIGURE POINTS> is displayed and then


press <ENTER>.

5. Press <NEXT> or <PREVIOUS> to scroll through your choices until <TRUEALARM>


is displayed and then press <ENTER>.

6. Use <NEXT> or <PREVIOUS> to scroll through your choices until <Add IDNet Point>
is displayed and then press Enter.

7. The first unused point in the system (for example, M1-1) is displayed. Press <NEXT> or
<PREVIOUS> to scroll through your list of unused points until the desired point is
displayed and then press Enter.

8. Follow the prompts to confirm this action.

Note: If there are 250 devices present in the 4010 (maximum allowed), the system informs
you that the IDNet channel is full and does not allow you to add any more points.

Editing a TrueAlarm Use the following steps to edit a TrueAlarm point in the FACP.
Point
1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed and then press


<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

Please Wait . . .
Fire Alarm Operation Suspended

6-3
Configuring TrueAlarm Points, Continued

Editing a TrueAlarm 3. Press <ENTER> to continue.


Point
4. Press <NEXT> or <PREVIOUS> until <CONFIGURE POINTS> is displayed and then
press <ENTER>.

5. Press <NEXT> or <PREVIOUS> to scroll through your choices until <TRUEALARM>


is displayed and then press <ENTER>.

6. Use <NEXT> or <PREVIOUS> to scroll through your choices until <Edit IDNet Point> is
displayed and then press Enter.

7. Press <NEXT> or <PREVIOUS> to scroll through your list of TrueAlarm points until the
desired point is displayed and then press Enter.

8. Press <NEXT> or <PREVIOUS> to scroll through your list of choices until the desired
option is displayed and then press Enter. Your choices are shown in Table 6-1.

Table 6-1: TrueAlarm Point Editing Choices

Function Description

Edit Device Type


Changes the point’s Hardware Device Type
(See Note 1)

Edit Point Type


Changes the Software Point Type
(See Notes 1 and 2)

Edit Point Label


Changes the point’s 40-character label
(See Note 2)

Clear Point Label


Blanks the point’s 40-character label
(See Note 2)

Edit Mode
Changes the point’s Mode of Operation
(See Note 1)

Notes:

1. For a complete list of your choices for these edit functions, refer to "Appendix A. Device
and Point Types."

2. To complete these functions, refer to their appropriate section in this publication.

6-4
Configuring TrueAlarm Points, Continued

Deleting a Use the following steps to delete an IDNet point from the 4010 FACP.
TrueAlarm Point
1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed and then press


<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

Please Wait . . .
Fire Alarm Operation Suspended

3. Press <ENTER> to continue.

4. Press <NEXT> or <PREVIOUS> until <CONFIGURE POINTS> is displayed and then


press <ENTER>.

5. Press <NEXT> or <PREVIOUS> to scroll through your choices until <TRUEALARM>


is displayed and then press <ENTER>.

6. Use <NEXT> or <PREVIOUS> to scroll through your choices until <DELETE IDNet
POINT> is displayed and then press Enter.

7. Press <NEXT> or <PREVIOUS> to scroll through your list of IDNet points until the
desired point is displayed and then press Enter.

8. Follow the prompts to confirm this action.

Caution: Any Custom Control equations and LED/Switch Modes referencing the deleted
point are also deleted.

6-5
Configuring ZAM/IAM/RIAM Points

Overview This section describes how to Add, Edit, and Delete a ZAM/IAM/RIAM point.

Adding a ZAM/IAM/RIAM Use the following steps to add a ZAM/IAM/RIAM point to the 4010 FACP.
Point
1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed and then press


<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

Please Wait . . .
Fire Alarm Operation Suspended

3. Press <ENTER> to continue.

4. Press <NEXT> or <PREVIOUS> until <CONFIGURE POINTS> is displayed and then


press <ENTER>.

5. Press <NEXT> or <PREVIOUS> to scroll through your choices until <ZAMs/IAMs/


RIAMs> is displayed and then press <ENTER>.

6. Use <NEXT> or <PREVIOUS> to scroll through your choices until <Add IDNet Point>
is displayed and then press Enter.

7. The first unused point in the system (for example, M1-1) is displayed. Press <NEXT> or
<PREVIOUS> to scroll through your list of unused points until the desired point is
displayed and then press Enter.

8. Follow the prompts to confirm this action.

Note: If there are 250 devices present in the 4010 (maximum allowed), the system informs
you that the IDNet channel is full and does not allow you to add any more points.

Editing a ZAM/IAM/RIAM Use the following steps to edit a ZAM/IAM/RIAM point in the FACP.
Point
1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed and then press


<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

Please Wait . . .
Fire Alarm Operation Suspended

3. Press <ENTER> to continue.

6-6
Configuring ZAM/IAM/RIAM Points, Continued

Editing a ZAM/IAM/RIAM 4. Press <NEXT> or <PREVIOUS> until <CONFIGURE POINTS> is displayed and then
Point press <ENTER>.

5. Press <NEXT> or <PREVIOUS> to scroll through your choices until <ZAMs/IAMs/


RIAMs> is displayed and then press <ENTER>.

6. Use <NEXT> or <PREVIOUS> to scroll through your choices until <Edit IDNet Point> is
displayed and then press Enter.

7. Press <NEXT> or <PREVIOUS> to scroll through your list of ZAM/IAM/RIAM points


until the desired point is displayed and then press Enter.

8. Press <NEXT> or <PREVIOUS> to scroll through your list of choices until the desired
option is displayed and then press Enter. Your choices are shown in Table 6-2.

Table 6-2: ZAM/IAM/RIAM Configuration Choices

Function Description

Edit Device Type


Changes the point’s Hardware Device Type
(See Notes 2 and 3)

Edit Point Type


Changes the Software Point Type
(See Notes 2 and 3)

Edit Point Label


Changes the point’s 40-character label
(See Note 3)

Clear Point Label


Blanks the point’s 40-character label
(See Note 3)

Edit Mode (See Note 1) Changes the point’s Mode of Operation

Notes:

1. This function not allowed for ZAM/IAM/RIAM points.

2. For a complete list of your choices for these edit functions, refer to "Appendix A. Device
and Point Types."

3. To complete these functions, refer to their appropriate section in this publication.

6-7
Configuring ZAM/IAM/RIAM Points, Continued

Deleting a ZAM/IAM/ Use the following steps to delete a ZAM/IAM/RIAM point from the 4010 FACP.
RIAM Point
1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed and then press


<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

Please Wait . . .
Fire Alarm Operation Suspended

3. Press <ENTER> to continue.

4. Press <NEXT> or <PREVIOUS> until <CONFIGURE POINTS> is displayed and then


press <ENTER>.

5. Press <NEXT> or <PREVIOUS> to scroll through your choices until <ZAMs/IAMs/


RIAMs> is displayed and then press <ENTER>.

6. Use <NEXT> or <PREVIOUS> to scroll through your choices until <DELETE IDNet
POINT> is displayed and then press Enter.

7. Press <NEXT> or <PREVIOUS> to scroll through your list of IDNet points until the
desired point is displayed and then press Enter.

8. Follow the prompts to confirm this action.

Caution: Any Custom Control equations and LED/Switch Modes referencing the deleted
point are also deleted.

6-8
Configuring Programmable Relay and NAC Points

Overview This section describes how to configure a Programmable Relay, NAC, or User-Defined SW/
LED point. The following assumes that you have chosen Relay, NAC, or User-Defined SW/
LED as your option after entering the Configure Points menu.

Procedure Use the following steps to configure a Programmable Relay or NAC point in the 4010 FACP.

1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed and then press


<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

Please Wait . . .
Fire Alarm Operation Suspended

3. Press <ENTER> to continue.

4. Press <NEXT> or <PREVIOUS> until <CONFIGURE POINTS> is displayed and then


press <ENTER>.

5. Press <NEXT> or <PREVIOUS> to scroll through your choices until <RELAY> or


<NAC> is displayed and then press <ENTER>.

6. Use <NEXT> or <PREVIOUS> to scroll through your NAC or RELAY points until the
desired point is displayed and then press Enter.

7. Press <NEXT> or <PREVIOUS> to scroll through your list of choices until the desired
option is displayed and then press Enter. Your choices are shown in Table 6-3.

Continued on next page

6-9
Configuring Programmable Relay and NAC Points, Continued

Procedure

Table 6-3: Relay and NAC Point Configuration Choices

Function Description

Edit Device Type


Changes the point’s Hardware Device Type
(See Note 2)

Edit Point Type


Changes the Software Point Type
(See Notes 2 and 3)

Edit Point Label


Changes the point’s 40-character label
(See Note 3)

Clear Point Label


Blanks the point’s 40-character label
(See Note 3)

Edit Mode
Changes the point’s Mode of Operation
(See Notes 1 and 2)

Notes:

1. This function not allowed for NAC and Relay points.

2. For a complete list of your choices for these edit functions, refer to “Appendix A. Device
and Point Types.”

3. To complete these functions, refer to their appropriate section in this publication.

6-10
Configuring Digital and Analog Pseudo Points

Overview This section describes how to configure digital and analog pseudo points.

Configuring Digital This section describes how to configure digital pseudo points P76 through P150. P1 through
Pseudo Points P75 are system points and cannot be edited. Use the following information to configure digital
pseudo points in a 4010 FACP.

1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed and then press


<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

Please Wait . . .
Fire Alarm Operation Suspended

3. Press <ENTER> to continue.

4. Press <NEXT> or <PREVIOUS> until <CONFIGURE POINTS> is displayed and then


press <ENTER>.

5. Press <NEXT> or <PREVIOUS> to scroll through your choices until <DIGITAL


PSEUDOS> is displayed and then press <ENTER>.

6. Use <NEXT> or <PREVIOUS> to scroll through your points until the desired point (P76
through P150) is displayed and then press Enter.

7. Press <NEXT> or <PREVIOUS> to scroll through your list of choices until the desired
option is displayed and then press Enter. Your choices are shown in Table 6-4.

Continued on next page

6-11
Configuring Digital and Analog Pseudo Points, Continued

Configuring Digital
Pseudo Points
Table 6-4: Digital Pseudo Point Configuration Choices

Function Description

Edit Device Type


Changes the point’s Hardware Device Type
(See Note 1)

Edit Point Type Changes the Software Point Type. Choices are:
(See Note 2) • Utility Point
• Fire Point
• Trouble Point
• Supervisory

Edit Point Label


Changes the point’s 40-character label
(See Note 2)

Clear Point Label


Blanks the point’s 40-character label
(See Note 2)

Edit Mode
Changes the point’s Mode of Operation
(See Notes 1)

Notes:

1. This function not allowed for digital pseudo points.

2. To complete these functions, refer to their appropriate section in this publication.

Configuring Analog This section describes how to configure analog pseudo points A27 through A50. A1 through
Pseudo Points A26 are system points and cannot be edited. Use the following information to configure
analog pseudo points in a 4010 FACP.

1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed and then press


<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

Please Wait . . .
Fire Alarm Operation Suspended

3. Press <ENTER> to continue.

4. Press <NEXT> or <PREVIOUS> until <CONFIGURE POINTS> is displayed and then


press <ENTER>.

5. Press <NEXT> or <PREVIOUS> to scroll through your choices until <ANALOG


PSEUDOS> is displayed and then press <ENTER>.

Continued on next page

6-12
Configuring Digital and Analog Pseudo Points, Continued

Configuring Analog 6. Use <NEXT> or <PREVIOUS> to scroll through your points until the desired point (A27
Pseudo Points through A50) is displayed and then press Enter.

7. Press <NEXT> or <PREVIOUS> to scroll through your list of choices until the desired
option is displayed and then press Enter. Your choices are shown in Table 6-5.

Table 6-5: Analog Pseudo Point Configuration Choices

Function Description

Edit Device Type


Changes the point’s Hardware Device Type
(See Note 1)

Edit Point Type Changes the Software Point Type. Choices are:
(See Notes 2 and 3) • Analog
• Timer
• Counter

Edit Point Label


Changes the point’s 40-character label
(See Note 3)

Clear Point Label


Blanks the point’s 40-character label
(See Note 3)

Edit Mode
Changes the point’s Mode of Operation
(See Notes 1)

Notes:

1. This function not allowed for analog pseudo points.

2. For a complete list of your choices for these edit functions, refer to "Appendix B.
Hardware and Pseudo Points."

3. To complete these functions, refer to their appropriate section in this publication.

6-13
Configuring 24-Point Programmable I/O Points

Configuring 24-Point The 4010 allows you to use the 24-Point I/O card to monitor input points (switches) and
Input Points control output points (lamps, tone-alerts, and relays).

1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed and then press


<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

Please Wait . . .
Fire Alarm Operation Suspended

3. Press <ENTER> to continue.

4. Press <NEXT> or <PREVIOUS> until <CONFIGURE POINTS> is displayed and then


press <ENTER>.

5. Press <NEXT> or <PREVIOUS> to scroll through your choices until <24 IO INPUTS> is
displayed and then press <ENTER>.

6. Use <NEXT> or <PREVIOUS> to scroll through your points until the desired point is
displayed and then press Enter.

7. Press <NEXT> or <PREVIOUS> to scroll through your list of choices until the desired
option is displayed and then press Enter. Your choices are shown in Table 6-6.

Continued on next page

6-14
Configuring 24-Point Programmable I/O Points, Continued

Configuring 24-Point
Input Points
Table 6-6: 24 I/O Input Configuration Choices

Function Description

Edit Device Type Changes the point’s Hardware Device Type.


Choose Input or Output.

Edit Point Type Changes the Software Point Type. Choices are:
• USWITCH (2-position unsupervised switch)
• OSWITCH (2-position Open supervised switch)
• SSWITCH (2-position Open/Short supervised
switch)
• TSWITCH (3-position supervised switch)

Edit Point Label* Changes the point’s 40-character label

Clear Point Label* Blanks the point’s 40-character label

Edit Mode Changes the point’s Mode of Operation. Choices are:


• SMPL (SMPL controlled)
• Ack (Acknowledge)
• Fire Ack (Fire alarm acknowledge)
• Supv. Ack (Supervisory alarm acknowledge)
• Trouble Ack (Trouble acknowledge)
• Reset (System reset)
• LTEST (Lamp test)
• ONOFF (On/Off switch)
• TOF (Toggle On/Off switch)
• PBT (Push button track)
• PBH (Push button hold)
• DE (Disable/ enable)
• TDE (Toggle disable/enable)
*This function not allowed for 24-point input points.

Configuring 24-Point Use the following steps to configure output points on the 24-Point I/O card.
Output Points
1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed and then press


<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

Please Wait . . .
Fire Alarm Operation Suspended

3. Press <ENTER> to continue.

Continued on next page

6-15
Configuring 24-Point Programmable I/O Points, Continued

Configuring 24-Point 4. Press <NEXT> or <PREVIOUS> until <CONFIGURE POINTS> is displayed and then
Output Points press <ENTER>.

5. Press <NEXT> or <PREVIOUS> to scroll through your choices until <24 IO OUTPUTS>
is displayed and then press <ENTER>.

6. Use <NEXT> or <PREVIOUS> to scroll through your points until the desired point is
displayed and then press Enter.

7. Press <NEXT> or <PREVIOUS> to scroll through your list of choices until the desired
option is displayed and then press Enter. Your choices are shown in Table 6-7.

Table 6-7: 24 I/O Output Configuration Choices

Function Description

Edit Device Type Changes the point’s Hardware Device Type.


Choose Input or Output.

Edit Point Type Changes the Software Point Type. Choices are:
• LAMP (Lamp or LED output)
• PIEZO (Piezo output)
• RELAY (Generic relay)
• RRELAY (Relay on until reset)

Edit Point Label* Changes the point’s 40-character label

Clear Point Label* Blanks the point’s 40-character label

Edit Mode Changes the point’s Mode of Operation. Choices are:


• SMPL (SMPL controlled)
• Fire (Fire alarm LED)
• Supervisory (Supervisory LED)
• Trouble (Trouble LED)
• Disable (Disable LED)
• ON (ON LED)
• OFF (OFF LED)
• LF (Local fire acknowledge)
• LS (Local supervisory acknowledge)
• LT (Local trouble acknowledge)
*This function not allowed for 24-point output points.

6-16
Configuring List Points

Overview This section describes how to configure a List, and how to add to and delete points from a List.

Configure a List 1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed and then press


<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

Please Wait . . .
Fire Alarm Operation Suspended

3. Press <ENTER> to continue.

4. Press <NEXT> or <PREVIOUS> until <CONFIGURE POINTS> is displayed and then


press <ENTER>.

5. Press <NEXT> or <PREVIOUS> to scroll through your choices until <UST> is displayed
and then press <ENTER>.

6. Use <NEXT> or <PREVIOUS> to scroll through your points until the desired point is
displayed and then press Enter.

7. Press <NEXT> or <PREVIOUS> to scroll through your list of choices until the desired
option is displayed and then press Enter. Your choices are shown in Table 6-8.

Table 6-8: List Pseudo Point Configuration Choices

Function Description

Add Point (See Note 2) Allows you to add specific points to a List

Delete Point Allows you to delete specific points from a List

Delete ALL Points Allows you to delete ALL points from a List

Edit Point Label*


Allows you to change the List’s 40-character label
(See Notes 1 and 3)

Clear Point Label


Blanks the List’s 40-character label
(See Notes 1 and 3)

Edit Point Type


Changes the List’s Point Type
(See Notes 1, 2 and 3)

Notes:
1. This function not allowed for all Lists.

2. For a complete list of your choices for these edit functions, refer to "Appendix B.
Hardware and Pseudo Points."

3. To complete these functions, refer to their appropriate section in this publication.

6-17
Configuring List Points, Continued

Adding a Point to a List Use the following steps to add a point to a List on the 4010 FACP. A TrueAlarm point is used
as an example in the following steps.

1. After selecting Lists as your option under the Configure Points menu, use <NEXT> or
<PREVIOUS> to scroll through your lists until the desired list is displayed and then press
<FUNCTION>.

2. Press <NEXT> or <PREVIOUS> until Add Point is displayed and then press Enter.

IDNet Device: 3-1


[TrueAlarm] Add 1/130

3. Press <NEXT> or <PREVIOUS> to scroll through the device types shown in the focus
brackets ([ ]) until the desired device type is displayed (in this example, TrueAlarm).

4. Press the right arrow to move the focus brackets ([ ]) to the Add option.

5. Press <NEXT> or <PREVIOUS> to scroll through the points you wish to add to the list.

6. Once the correct point is displayed, press Enter to add that point to the list.

Repeat Steps 5 and 6 to add all desired points to your chosen List.

Deleting a Point from a Use the following steps to delete a point from a List on the 4010 FACP. A TrueAlarm point is
List used as an example in the following steps.

1. After selecting Lists as your option under the Configure Points menu, use <NEXT> or
<PREVIOUS> to scroll through your lists until the desired list is displayed and then press
Enter.

2. Press <NEXT> or <PREVIOUS> until the point you wish to delete is displayed and then
press Enter.

3. Press <NEXT> or <PREVIOUS> until Delete Point is displayed and then press Enter.

4. Follow the prompts to confirm this action.

Deleting All Points from Use the following steps to delete ALL points from a List on the FACP.
a List
1. After selecting Lists as your option under the Configure Points menu, use <NEXT> or
<PREVIOUS> to scroll through your lists until the desired list is displayed and then press
<FUNCTION>.

2. Press <NEXT> or <PREVIOUS> until Delete ALL Points is displayed and then press
Enter.

3. Follow the prompts to confirm this action.

6-18
Configuring User-Defined Programmable Switches and LEDs

Overview This section describes how to configure User-Defined Programmable Switches and LEDs.
The following assumes that you have chosen User Defined SW/LED as your option after
entering the Configure Points menu.

Configuring a User- Use the following steps to configure a User-Defined Switch or LED in the 4010 FACP.
Defined Switch or LED
1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed and then press


<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

Please Wait . . .
Fire Alarm Operation Suspended

3. Press <ENTER> to continue.

4. Press <NEXT> or <PREVIOUS> until <CONFIGURE POINTS> is displayed and then


press <ENTER>.

5. Press <NEXT> or <PREVIOUS> to scroll through your choices until <USER DEFINED
SW/LED> is displayed and then press <ENTER>.

6. Press <NEXT> or <PREVIOUS> to scroll through the following choices. Once your
choice is displayed, press Enter

• User LED 1

• User LED 2

• User LED 3

• User Defined Key 1

• User Defined Key 2

7. Press <NEXT> or <PREVIOUS> to scroll through your list of choices until the desired
option is displayed and then press Enter. Your choices are shown in Table 6-9.

Continued on next page

6-19
Configuring User-Defined Programmable Switches and LEDs, Continued

Configuring a User-
Defined Switch or LED
Table 6-9: User Defined Switch Configuration Choices

Function Description

Edit Device Type


Changes the point’s Hardware Device Type
(See Notes 1 and 2)

Edit Point Type


Changes the Software Point Type
(See Note 2)

Edit Point Label


Changes the point’s 40-character label
(See Note 1)

Clear Point Label


Blanks the point’s 40-character label
(See Note 1)

Edit Mode Changes the point’s Mode of Operation

Notes:

1. This function not allowed for User-Defined SW/LED.

2. Your Point Type choices for LEDs are Yellow LED or NON-Yellow LED. The switches
default to USWITCH point type and is not editable.

Edit a Mode of a User- This section describes how to edit the mode of a User-Defined SW/LED. Use the following
Defined SW/LED steps to edit the mode of a User-Defined Switch or LED in the 4010 FACP.

1. After selecting User Defined SW/LED as your option under the Configure Points menu,
press <NEXT> or <PREVIOUS> to scroll through the following choices. Once your
choice is displayed, press Enter.

• User LED 1

• User LED 2

• User LED 3

• User Defined Key 1

• User Defined Key 2

2. Press <NEXT> or <PREVIOUS> to scroll through your list of choices until Edit Mode is
displayed and then press Enter. Your modes for Switches and LEDs are shown in
Table 6-10.

Continued on next page

6-20
Configuring User-Defined Programmable Switches and LEDs, Continued

Edit a Mode of a User-


Defined SW/LED
Table 6-10: User-Defined SW/LED Modes

User-Defined SW/LED Modes

Switch Modes • SMPL


• Ack
• Fire Ack
• Supv Ack
• Trouble Ack
• Reset
• Silence
• LTEST
• ON-OFF
• TOF
• PBT
• PBH
• DE
• TDE

Led Modes • SMPL


• Fire
• Supervisory
• Trouble
• Disable
• On
• Off
• LF
• LS
• LT

3. Select the appropriate mode and then press Enter.

4. Follow the prompts to confirm this action.

6-21
Chapter 7.
System Options

Introduction This chapter describes how to set system options such as Time/Date Format, Active Status
Reminder, etc. These options are custom functions for the 4010. The System Options (shown
in Figure 7-1) can also be set from the Quick-CFIG menus.

In This Chapter This chapter discusses the following topics:

Topic See Page #

System Options Menu 7-2

Time/Date Format 7-3

Active Status Reminder 7-4

Silence/Reset Inhibit 7-5

Alarm Cut-Out Timer 7-6

Door Drop on Alarm 7-7

Door Drop on AC Loss 7-8

Audible and Visible NAC Operation 7-9

TrueAlert Non-Addressable Horn Operation 7-10

Depleted Battery Cut-Out 7-11

Stagger Starting AHUs 7-12

Enabling the City Circuit 7-13

Expansion Power 7-14

Single Station 7-15

Display 1st Alarm 7-15

Immediate AC Fail 7-15

7-1
System Options Menu

Introduction All 4010 system options are accessed via the System Options menu choice, which is located in
the Programming menu tree. Figure 7-1 shows the structure of the System Options menu.

Programming Menus

Configure System Custom


Cards Options Control

• Time/Date Format
• Active Status Reminder
• Silent/Reset Inhibit
• Alarm Cut-Out Timer
• Door Drop on Alarm
• Door Drop on AC Loss
• Audible NAC Operation
• Visual NAC Operation
• Depleted Batt. Cutout
• Stagger Start AHUs
• Enable City Circuit
• Expansion Power
• Single Station Override
• TrueAlert Horn Operation
• Display 1st Alarm
• Immediate AC Fail
• Suppression Release
• Wheelock
• Recurring Trouble Filter

Figure 7-1. System Options Menu

7-2
Time/Date Format

Overview When setting the Time/Date Format, you are only setting the Time format in 12 or 24-hour
format. That is, the time is displayed in 12-hour format with the AM (morning) or PM
(afternoon) indications or in 24-hour (military style) format. The date is always displayed in
the following format and cannot be changed:

Fri 7-Dec-01
Day of week, date, month, year

The Time format directly affects how time is displayed on the 4010 not only at the high-level
status screen but also in the Historical Logs.

Setting the Time Format Use the following steps to set the Time format on the 4010 FACP.

1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed and then press


<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

3. Press <ENTER> to continue.

4. Press <NEXT> or <PREVIOUS> until <SYSTEM OPTIONS> is displayed and then


press <ENTER>.

5. Press <NEXT> or <PREVIOUS> to scroll through your choices until <TIME/DATE


FORMAT> is displayed and then press <ENTER>.

6. Press <NEXT> or <PREVIOUS> to scroll through the options until 12 Hour or 24 Hour is
displayed, and then press Enter.

7. Follow the prompts to confirm this action.

7-3
Active Status Reminder

Overview The Active Status Reminder option allows you to set an interval and duration in which the
4010 reminds operators of the FACP that a FIRE, SUPV, or TBL condition still exists in the
panel. Your choices are as follows:

• ON/OFF Status (turn the option ON or OFF). A setting of ON activates the option with a
default Reminder Interval of 8 hours with a 5-second Acknowledge Option signal
duration.

• Reminder Interval (set a reminder interval from 1-12 hours).

• Acknowledge Option (set a signal duration of 1-60 seconds). A setting of 0 seconds has
the following effect:

• For a Trouble condition, the signal sounds until the condition is acknowledged at the
front panel.

• For an Alarm (FIRE) condition, the signal sounds until the alarm condition is cleared.

Setting the Active Status Use the following steps to set the Active Status Reminder on the 4010 FACP.
Reminder
1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed and then press


<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

3. Press <ENTER> to continue.

4. Press <NEXT> or <PREVIOUS> until <SYSTEM OPTIONS> is displayed and then


press <ENTER>.

5. Press <NEXT> or <PREVIOUS> to scroll through your choices until <ACTIVE STATUS
REMINDER> is displayed and then press <ENTER>.

6. Press <NEXT> or <PREVIOUS> to scroll through the options until On/Off Status is
displayed and then press Enter.

7. Press <NEXT> or <PREVIOUS> to select ON or OFF and then press Enter. Follow the
prompts to confirm this action.

8. Press <NEXT> or <PREVIOUS> to scroll through the options until Reminder Interval is
displayed and then press Enter.

9. Press <NEXT> or <PREVIOUS> to select an interval from 1-12 hours and then press
Enter. Follow the prompts to confirm this action.

10. Press <NEXT> or <PREVIOUS> to scroll through the options until Acknowledge Option
is displayed and then press Enter.

11. Press <NEXT> or <PREVIOUS> to select an signal duration from 0-60 seconds and then
press Enter. Follow the prompts to confirm this action.

7-4
Silence/Reset Inhibit

Overview You can inhibit the Alarm Silence/System Reset on a 4010 FACP for a set duration. The range
for the Silence/Reset Inhibit timer is 0-60 minutes with zero (No Inhibit) being the default
setting.

Setting the Silence/Reset Use the following steps to set the Silence/Reset Inhibit timer on the 4010 FACP.
Inhibit
1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed and then press


<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

3. Press <ENTER> to continue.

4. Press <NEXT> or <PREVIOUS> until <SYSTEM OPTIONS> is displayed and then


press <ENTER>.

5. Press <NEXT> or <PREVIOUS> to scroll through your choices until <SILENCE/RESET


INHIBIT> is displayed and then press <ENTER>.

6. Press <NEXT> or <PREVIOUS> to set the timer from 0-60 minutes and then press Enter.

7. Follow the prompts to confirm this action.

7-5
Alarm Cut-Out Timer

Overview The Alarm Signal Cut-Out Timer allows you to set a duration for how long signals sound after
an alarm. In other words, when an alarm condition exists, the signals sound until silenced.
With this option set at two minutes, building signals sound on alarm for two minutes and then
automatically stop sounding. However, the alarm condition does remain active in the panel.
The default setting for this option is No Cutout (meaning a manual Alarm Silence is required to
shut off signals).

Setting the Alarm Cut- Use the following steps to set the Alarm Signal Cut-Out timer on the 4010 FACP.
out Timer
1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed and then press


<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

3. Press <ENTER> to continue.

4. Press <NEXT> or <PREVIOUS> until <SYSTEM OPTIONS> is displayed and then


press <ENTER>.

5. Press <NEXT> or <PREVIOUS> to scroll through your choices until <ALARM CUT-
OUT TIMER> is displayed and then press <ENTER>.

6. Press <NEXT> or <PREVIOUS> to set the timer from 0-60 minutes and then press Enter.

7. Follow the prompts to confirm this action.

7-6
Door Drop on Alarm

Overview The Door Holder - Alarm Door Drop Timer allows the 4010 to hold doors open for a set
duration during an alarm condition. After that duration has expired, the 4010 shuts off the door
holder relays and the doors close. The range for the timer is 0-60 seconds with a default setting
of zero seconds. To have door holders drop the doors immediately, leave the timer set to zero
seconds.

Setting the Door Drop on Use the following steps to set the Door Holder Alarm Door Drop timer on the 4010 FACP.
Alarm Timer
1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed and then press


<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

3. Press <ENTER> to continue.

4. Press <NEXT> or <PREVIOUS> until <SYSTEM OPTIONS> is displayed and then


press <ENTER>.

5. Press <NEXT> or <PREVIOUS> to scroll through your choices until <DOOR DROP ON
ALARM > is displayed and then press <ENTER>.

6. Press <NEXT> or <PREVIOUS> to set the timer from 0-60 seconds and then press Enter.

7. Follow the prompts to confirm this action.

7-7
Door Drop on AC Loss

Overview The Door Holder - AC Fail Door Drop Timer allows the 4010 to hold doors open for a set
duration during an AC power loss condition. After that duration has expired, the 4010 shuts
off the door holder devices and the doors close. The range for the timer is 0-60 minutes, with a
default setting of 5 minutes. To have door holders drop the doors immediately upon AC power
loss, set the timer to zero minutes.

Setting the Door Drop on Use the following steps to set the Door Holder Alarm Door Drop timer on the 4010 FACP.
AC Loss Timer
1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed and then press


<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

3. Press <ENTER> to continue.

4. Press <NEXT> or <PREVIOUS> until <SYSTEM OPTIONS> is displayed and then


press <ENTER>.

5. Press <NEXT> or <PREVIOUS> to scroll through your choices until <DOOR DROP ON
AC LOSS > is displayed and then press <ENTER>.

6. Press <NEXT> or <PREVIOUS> to set the timer from 0-60 seconds and then press Enter.

7. Follow the prompts to confirm this action.

7-8
Audible and Visible NAC Operation

Overview The Audible and Visible ON 'til Silence Notification Appliance Circuits (NACs) can be set to
the choices shown in Table 7-1. The default setting for the Audible NACs is Temporal coding
and the default setting for the Visible NACs is Steady. Refer to "Appendix C - Glossary of
Terms" for more information on the types of coding.

Setting the Audible or Use the following steps to set the Audible and/or Visual NAC operation on the 4010 FACP.
Visual NAC Operation
1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed and then press


<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

3. Press <ENTER> to continue.

4. Press <NEXT> or <PREVIOUS> until <SYSTEM OPTIONS> is displayed and then


press <ENTER>.

5. Press <NEXT> or <PREVIOUS> to scroll through your choices until <AUDIBLE NAC
OPERATION> or <VISUAL NAC OPERATION> is displayed and then press <ENTER>.

6. Press <NEXT> or <PREVIOUS> to choose the settings shown in Table 7-1.

Table 7-1: Audible and Visible NAC Operation Settings

System Option Choices

Audible NAC Operation Choose:


Audible NACs: Temporal (default)
Audible NACs: Steady
Audible NACs: Slow March
Audible NACs: Fast March

Visible NAC Operation Choose:


Visual NACs: Steady (default)
Visual NACs: Slow March
Visual NACs: Fast March
Visual NACs: Temporal
Visual NACs: Synchronous

7. Follow the prompts to confirm this action.

7-9
TrueAlert Non-Addressable Horn Operation

Overview The TrueAlert Non-Addressable Horn Operation option defines the way in which TrueAlert
Horns function when activated. The default function is Temporal.

Setting the TrueAlert Use the following steps to set the TrueAlert Non-Addressable Horn system option.
Non-Addressable Horn
Option 1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed and then press


<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

3. Press <ENTER> to continue.

4. Press <NEXT> or <PREVIOUS> until <SYSTEM OPTIONS> is displayed and then


press <ENTER>.

5. Press <NEXT> or <PREVIOUS> to scroll through your choices until <QALERT HORN
OPERATION> is displayed and then press <ENTER>.

6. Press <NEXT> or <PREVIOUS> to choose the Temporal (default), Steady, or Slow


March option.

7. Follow the prompts to confirm this action.

7-10
Depleted Battery Cut-Out

Overview This option selects the mode of operation for the 4010 FACP if an alarm occurs during an AC
power loss while a Depleted Battery trouble exists. The specific operation of this option
differs slightly, depending on whether you have a domestic or Canadian system.

Domestic Operation. The default setting for the option is OFF and the threshold voltage is
19.4 VDC ± 5%. Operation of this option for a domestic system is as follows:

• If the system is in alarm and a depleted battery condition occurs, any NACs that are active
remain active.

• If the system in not in alarm and a depleted battery condition occurs, the NACs are
prevented from activating.

Canadian Operation. The default setting for the option is OFF and the threshold voltage is
19.4 VDC ± 5%. Operation of this option for a Canadian system is as follows:

• When a depleted battery condition occurs, power is turned off to the 4010. AC power
must be restored to re-activate the 4010.

Setting the Depleted Use the following steps to set the Depleted Battery Cut-Out on the 4010 FACP.
Battery Cut-Out
1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed and then press


<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

3. Press <ENTER> to continue.

4. Press <NEXT> or <PREVIOUS> until <SYSTEM OPTIONS> is displayed and then


press <ENTER>.

5. Press <NEXT> or <PREVIOUS> to scroll through your choices until <DEPLETED


BATT. CUTOUT> is displayed and then press <ENTER>.

6. Press <NEXT> or <PREVIOUS> to set the option to ON or OFF and then press Enter.

7. Follow the prompts to confirm this action.

7-11
Stagger Starting AHUs

Overview This option allows you to set the 4010 to stagger start any Air Handling Unit (AHU) control
points (point types AHUR, AHUO, and AHUF) in the 4010 FACP . This option protects
against power spikes that may cause the circuit breakers to trip when AHUs start
simultaneously. The range for stagger starting the AHUs is 0-60 seconds. The default setting
for this option is 30 seconds. A setting of zero allows the AHUs to start immediately.

The 4010 displays an AHU Stagger Start message when the sequence starts and an AHU
Stagger Start Complete message when the sequence ends.

Setting the Stagger Start Use the following steps to set the Stagger Start AHUs timer on the 4010 FACP.
AHU Delay Timer
1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed and then press


<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

3. Press <ENTER> to continue.

4. Press <NEXT> or <PREVIOUS> until <SYSTEM OPTIONS> is displayed and then


press <ENTER>.

5. Press <NEXT> or <PREVIOUS> to scroll through your choices until <STAGGER


START AHUS> is displayed and then press <ENTER>.

6. Press <NEXT> or <PREVIOUS> to set the timer from 0-60 seconds and then press Enter.

7. Follow the prompts to confirm this action.

7-12
Enabling the City Circuit

Overview You must enable the City Circuit via the 4010 System Options menu when installing the city
circuit card. The default setting for the city circuit is OFF.

Setting the Enable City Use the following steps to set the Enable City Circuit option on the 4010 FACP.
Circuit Option
1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed and then press


<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

3. Press <ENTER> to continue.

4. Press <NEXT> or <PREVIOUS> until <SYSTEM OPTIONS> is displayed and then


press <ENTER>.

5. Press <NEXT> or <PREVIOUS> to scroll through your choices until <ENABLE CITY
CIRCUIT > is displayed and then press <ENTER>.

6. Press <NEXT> or <PREVIOUS> to set the option to ON or OFF and then press Enter.

7. Follow the prompts to confirm this action.

7-13
Expansion Power

Overview You must enable the Expansion Power Supply via the 4010 System Options menu when
installing the expansion power supply. The default setting for the expansion power supply is
OFF.

Setting the Expansion Use the following steps to set the Expansion Power Supply option on the 4010 FACP.
Power Option
1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed and then press


<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

3. Press <ENTER> to continue.

4. Press <NEXT> or <PREVIOUS> until <SYSTEM OPTIONS> is displayed and then


press <ENTER>.

5. Press <NEXT> or <PREVIOUS> to scroll through your choices until <EXPANSION


POWER> is displayed and then press <ENTER>.

6. Press <NEXT> or <PREVIOUS> to set the option to ON or OFF and then press Enter.

7. Follow the prompts to confirm this action.

7-14
Single Station

Overview The Single Station option has the following effect.

• Sounder activates when the associated sensor is above its alarm threshold.

• Sounder silences when sensor is below its alarm threshold.

• Alarm remains at panel until reset is performed.

Setting the Single Station Use the following steps to set the Single-Station option on the 4010 FACP. The default setting
Option for this option is ON.

1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed and then press


<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

3. Press <ENTER> to continue.

4. Press <NEXT> or <PREVIOUS> until <SYSTEM OPTIONS> is displayed and then


press <ENTER>.

5. Press <NEXT> or <PREVIOUS> to scroll through your choices until <SINGLE


STATION OVERRIDE> is displayed and then press <ENTER>.

6. Press <NEXT> or <PREVIOUS> to set the option to ON or OFF and then press Enter.

7. Follow the prompts to confirm this action.

Display 1st Alarm

Overview When the Display 1st Alarm option is selected, the first alarm in the system is displayed
automatically on the LCD. This allows the first responder to identify the zone of origin without
having to open the door and use the keypad. If this option is turned off, the overall system tally
screen is displayed when non-normal events are in the panel.

Immediate AC Fail

Overview If this option is selected, an AC failure will activate the city trouble relay immediately. If the
option is turned off, the city trouble relay will delay 2 hours after an AC fail before activating.

7-15
Wheelock

Overview When this option is selected, any NAC that is programmed as point type SQALERT or
QALERT will generate Wheelock Sync Protocol when the NAC is in alarm. Any Simplex
TrueAlert non-addressable appliance connected to the panel will not work properly if this
option is selected. This option is ignored by any 4009 IDNet NAC extenders (4009A)
connected to the 4010. SW1-6 on the 4009A system board must be set to ON if Wheelock
Sync Protocol appliances are attached to the 4009A.

Recurring Trouble Filter

Overview This option will stop a recurring trouble event from continuously dialing the central station if
the programmed criteria are met (number of occurrences of that point in the trouble log within
the specified elapsed time frame). The trouble is not prevented from reporting at the panel.
Number of occurrences: The number of times the point is found in the trouble log
(0 = no filtering; default for pre-existing jobs upgraded to 4.02). Selectable from 0 and 2 to 10.

Elapsed Time: Number of minutes in which the troubles must be found. Selectable from 1 to
1440.
Chapter 8.
Custom Control

Introduction This chapter provides an overview of the Simplex Multi-functional Programming Language
(SMPL), which is also known as Custom Control (both terms are equivalents and are used
interchangeably throughout this publication).

In This Chapter This chapter discusses the following topics:

Topic See Page #

Overview 8-2

SMPL Opcodes and Operators 8-3

Custom Control Example 8-6

Custom Control Programming 8-7

Application-Specific Examples 8-24

8-1
Overview

Custom Control is used for custom functions such as selective signaling/control, cross zoning
pre-signal, and many other possible functions. Equations are written by the programmer to
describe the various operations of the 4010 FACP. SMPL programming can be used to
customize the operation of various points while the remaining points operate as general alarm
points. SMPL programming is programmed through the front panel interface or from the PC
Programmer tool.

The 4010 base panel is configured (and shipped) as a general alarm system. You must
program the Custom Control option when more sophisticated operations are required.

Custom Control equations are developed to define specified operations. Each equation
contains interrelated statements, which consists of the INPUT SIDE and OUTPUT SIDE.
Version 2.01 or later of the 4010 accepts up to 60 programming equations, each consisting of
up to six statements total from the front panel. Older versions of the panel accept 40 equations.

Custom Control is used to customize the operation of an output, while the rest of the system
continues to operate as a general alarm system. SMPL also allows the programmer to modify
the operation of points to be used in non-alarm functions. A point can be selected as a non-
alarm, tracking (non-latching) point.

The 4010 has resident editing capability. Once the programming mode is selected, the Custom
Control is programmed through a series of menu options.

Once all the equations are entered, you can scroll through the Custom Control programming to
review its contents. If errors are found, you can then insert new data or delete existing data.
When you are satisfied with the program, you must exit the Custom Control mode to save all
data to the 4010 CFIG chip.

Once programmed with Custom Control and back on line, the 4010 handles its inputs and
outputs differently. The 4010 checks to see what inputs and outputs have been changed by the
Custom Control programmed equations. Outputs not used in the Custom Control program
remain general alarm outputs. Outputs which have new defined operations operate as
specified in the Custom Control equations.

Caution: Once an output is used in a Custom Control equation, it no longer responds to the
general alarm monitor points.

8-2
SMPL Opcodes and Operators

Input Opcodes The following is a list of valid Input Opcodes, Input Operators, and Relational Operators for
the 4010 Custom Control option.
Table 8-1: Input Opcodes

Input Opcodes Description


FIRE DETECT Fire Detect State
FIRE Fire State
FIRE ACK Fire Acknowledge State (needs ACK)
SUPV Supervisory State
SUPV ACK Supervisory Acknowledge State
TBL Trouble State
TBL ACK Trouble Acknowledge State
PHY NORM Physically Normal State
PHY ABN Physically Abnormal State
PHY OPEN Physically Open State
PHY SHORT Physically Short State
ABN DET Abnormal Detect State
OPEN DET Open Detect State
SHORT DET Short Detect State
CTRL ON Control ON State
CTRL OFF Control OFF State
DISABLE Disable State
CLASS A TROUBLE Class A Trouble State
ON/CODE On coding State
OFF OFF State
COMP CNST Compare to a Constant Value
COMP VAR Compare to a Variable Value
EMPTY Empty state of a list
ANY Any number of elements in a list
ALL All elements in a list
SAVE Save the state of an equation
RECALL Recall the state of an equation
DELAY CNST Delay for a constant value
DELAY VAR Delay for a variable value
CYCLE CNST Cycle for a constant value
CYCLE VAR Cycle for a variable value
DIRTY Dirty detector state
SMOKE LEV A percentage smoke level

Continued on next page

8-3
SMPL Opcodes and Operators, Continued

Input and Relational Table 8-2 lists the Input and Relational Operators.
Operators
Table 8-2: Input and Relational Operators

OR
AND
NOT
Input Operators SAVE
RECALL
DELAY (Constant and Variable)
CYCLE (Constant and Variable)

EQ (Equal To)
NE (Not Equal To)
GT (Greater Than)
Relational Operators
GE (Greater Than or Equal To)
LT (Less Than)
LE (Less Than or Equal To)

Continued on next page

8-4
SMPL Opcodes and Operators, Continued

Output Opcodes Table 8-3 lists Output Opcodes for the 4010 Custom Control option.

Table 8-3: Output Opcodes


Output Opcodes Description
SET ON Set Point ON (refreshes continuously)
SET OFF Set Point OFF (refreshes continuously)
SET PRI Set Point's priority (refreshes continuously)
TRACK ON Track Point ON
TRACK OFF Track Point OFF
TRACK PRI Track Point's Priority
HOLD ON Hold Point ON
HOLD OFF Hold Point OFF
HOLD PRI Hold Point's Priority
ACK Acknowledge Point
DISABLE Disable Point
ENABLE Enable Point
RESET Reset
LOAD CNST Load Analog Pseudo Point w/Constant Value
LOAD VAR Load Analog Pseudo Point w/Variable Value
PULSE CNST Pulse Analog Pseudo Point w/Constant Value
PULSE VAR Pulse Analog Pseudo Point w/Variable Value
LED OFF Turn LED/Lamp OFF
LED ON Turn LED/Lamp ON
F FLASH Fast Flash Point (LED)
S FLASH Slow Flash Point (LED)
S MARCH Slow March Code the Point
F MARCH Fast March Code the Point
TEMPORAL Temporal Code the Point
CHAN CODE (IDNet) Set up IDNetIDNet Channel Code (ON\Temporal\March
Time)
DEV CODE (TrueAlarm
Device Code
sensor outputs)
ALARM THR Set Alarm Threshold (sensitivity)
ROR HEAT Rate-of-Rise Heat (set for sensitivity)

Continued on next page

8-5
Custom Control Example

Output Opcodes The following is an example of a valid Custom Control equation.

FIRE DET 03-01 Input Statement 1


Input Opcode (Fire Detect state of M1-1 : IDNet Device: M1-1)

OR FIRE DET 03-02 Input Statement 2


(or the Fire Detect state of M1-2 : IDNetIDNet Device: M1-2)
Input Operator
OR FIRE DET 03-03 Input Statement 3
(or the Fire Detect state of M1-3 : IDNetIDNet Device: M1-3)
Output Opcode
HOLD ON 01-01 Pri 9, 9 Output Statement
(Hold ON NAC Circuit: SIG 1 at a priority of 9, 9)

8-6
Custom Control Programming

To Start Custom Control You must log in at the appropriate level and use the following steps to begin a Custom Control
Programming session.

1. From the High-Level Status screen, press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [Programming] is displayed and then press


<ENTER>. The display warns you that the 4010 is no longer in the Fire Alarm Operation
mode.

3. A confirmation screen appears. Follow the prompts to enter programming. Press


<NEXT> or <PREVIOUS> to select [Custom Control] and then press <ENTER>.

Custom Control Menu Using <Next> and <Previous>, you can scroll through all the existing equations of the Custom
Navigation Control program.

Note: All insertions are done above the current location.

If you wish to create a new equation before the first equation in the program, press <Next> to
scroll to Equation 1 and then select Insert. When the new equation has been created and saved
it will become Equation 1 and all other equations are incremented by 1.

If you wish to add a new equation to the end of the program, press <Next> or <Previous> until
** End of Program ** is displayed on the screen. Select Insert from the menu to create a new
equation at the end of the current equation list with the number of the last equation plus 1.

Note: Selecting Insert does NOT change the current focus. That is, if you insert at the end of
program marker when the action is completed, the current focus is still at the ** End of
Program ** marker. This facilitates sequentially entering a program when none is present or
adding a sequence of equations within the existing program.

When you enter Custom Control programming you see one of the screens in Figure 8-1. (A) in
Figure 8-1 shows the active equation number and how many equations exist in the program.
(B) in Figure 8-1 is displayed if no equations exist in the database or when you have scrolled
past the last equation in the program.

Note: You are required to select the Insert option to create a new equation. If you attempt to
edit or delete the ** End of Program ** marker, an error message is displayed.

Equation 1 1/4
A [Edit] Insert Delete

**End of Program**
B [Edit] Insert Delete

Figure 8-1. Entering Custom Control Programming

Continued on next page

8-7
Custom Control Programming, Continued

Equation Level You enter the equation level by selecting an existing equation to edit or you elect to Insert a
new equation. When creating a new equation, you are shown an empty equation with the
active indicator (signified by a leading asterisk [*]) on the End of Input marker (remember all
inserts go above the current focus). An empty equation consists of the "Input Side" header, the
"End of Input" marker, and the "End of Output" marker (see A in Figure 8-2). If an equation
exists, you are shown the first input statement in the equation (see B in Figure 8-2).

*1: End of Input


A [Edit] Insert Delete Save Equation

*NOT Fire 3-01


B [Edit] Insert Delete Save Equation

Figure 8-2. Screens for New and Existing Equations

Press <Next> and <Previous> to scroll through the statements of the selected equation.

When the active statement (indicated by the *) to be modified is displayed, you may enter the
statement level by pressing <Enter> or by pressing the up and down buttons to move the focus
brackets ( [ ] ) to select another menu option and then press <Enter>.

The menu options are:

• Edit: To change the current statement.

• Insert: To create a new statement ABOVE the current statement.

• Delete: To remove the current statement from the equation.

• Save Equation: To update the program with the new equation and return to the program
level.

Custom Control Level After entering the statement level you can work on the individual parts of a Custom Control
statement. The display shows the current statement on the top line with the current "field" of
the statement marked with focus brackets ( [ ] ). The current option selection is shown in
focus brackets on the lower line of the display. Use the left and right arrow buttons to move
between the statement fields on the top line and <Next> and <Previous> to scroll through the
options for the current field (and display the new selection) on the lower line. Press <Enter> to
move the new option from the lower line to the selected field in the top line. This also moves
the field focus to the next field.

Continued on next page

8-8
Custom Control Programming, Continued

Equations Version 2.01 or later of the 4010 system supports up to 60 Custom Control equations. A
Custom Control equation consists of up to six statements. Each equation consists of two sides:
an INPUT SIDE and an OUTPUT SIDE. An equation can be better understood as an "IF/
THEN" command. "IF" the INPUT SIDE is true, "THEN" execute the OUTPUT SIDE.

Each equation is made up of one or more input statement and one or more output statement (for
a total of six statements). The equation in Figure 8-3 has four statements: two input
statements and two output statements.

Input Statement
Input Statement
Equation End of Inputs

Output Statement
Output Statement
End of Outputs

Figure 8-3. An Equation with Four Statements

Input Side (IF) Each input statement is made up of four fields.

Field 1 Field 2 Field 3 Field 4


FIRST
STATEMENT [ ] [NOT] [FIRE] [3-01]

Empty field Optional NOT Condition qualifier Point


starts a operator for Field 4
Custom Control
equation input

Figure 8-4. Input Statement Fields

Field 1 Field 1 is always empty in the first statement of any Custom Control equation. In subsequent
statements, Field 1 will contain one of the two Link operators:

• AND - which links the statement in "Series" with all previous statements

• OR - which links the statement in "Parallel" with all previous statements.

Continued on next page

8-9
Custom Control Programming, Continued

Field 1 AND

The AND Link operator links the current statement in Series with all previous statements in an
equation (see Figure 8-5).

Field 1 Field 2 Field 3 Field 4


FIRST
STATEMENT [ ] [ ] [FIRE] [3-01]

SECOND
STATEMENT [AND] [ ] [FIRE] [3-02]
Figure 8-5. The AND Operator

In Figure 8-5, IF the condition of 3-01 is Fire AND the condition of 3-02 is Fire, then the
INPUT SIDE is true. Another way to look at this equation is shown in Figure 8-6. In order to
cross from the INPUT SIDE of the equation to the OUTPUT SIDE, both of the statements
must be true.

3-01 3-02

INPUT SIDE OUTPUT


(Statements 1 & 2) SIDE

Points 3-01 and 3-02 are


in series. Both statements
must be true in order to go
from the input to the output.

Figure 8-6. Statements in Series

Continued on next page

8-10
Custom Control Programming, Continued

Field 1 OR

The OR Link operator links the current statement in Parallel with all previous statements in an
equation (see Figure 8-7).

Field 1 Field 2 Field 3 Field 4


FIRST
STATEMENT [ ] [ ] [FIRE] [3-01]
SECOND
STATEMENT [OR] [ ] [FIRE] [3-02]
Figure 8-7. The OR Operator

In Figure 8-7, IF the condition of 3-01 is Fire OR the condition of 3-02 is Fire, then the INPUT
SIDE is true. Another way to look at this equation is shown in Figure 8-8. In order to cross
from the INPUT SIDE of the equation to the OUTPUT SIDE, one of the statements (3-01 or
3-02) must be true.

3-01

INPUT SIDE OUTPUT


(Statements 1 & 2) SIDE

3-02 Points 3-01 and 3-02 are


in parallel. One statement
or the other must be true
for the output side to turn on.

Figure 8-8. Statements in Parallel

Continued on next page

8-11
Custom Control Programming, Continued

Field 1 AND (First) & OR (Second)

In Figure 8-9 the first and second statements are linked in series and the third statement is
linked in parallel with the first and second statements. Remember, a Link operator links that
statement with all previous statements, not just the statement before it.

Field 1 Field 2 Field 3 Field 4


FIRST
STATEMENT [ ] [ ] [FIRE] [3-01]
SECOND
STATEMENT [AND] [ ] [FIRE] [3-02]
THIRD
STATEMENT [OR] [ ] [FIRE] [3-03]
Figure 8-9. AND with OR Operator

In Figure 8-9, IF the condition of 3-01 is Fire AND the condition of 3-02 is Fire, OR the
condition of 3-03 is Fire, then the INPUT SIDE is true. Another way to look at this equation is
shown in Figure 8-10. In order to cross from the INPUT SIDE of the equation to the OUTPUT
SIDE, the first and second statements (together) or the third statement must be true.

18-
3-01 3-02
01

OUTPUT
INPUT SIDE
(Statements 1, 2 & 3) SIDE

Points 3-01 and 3-02 (in series)


3-03 are parallel with 3-03.
3-01 and 3-02 must be true
(together) or 3-03 must be true
in order to go from the INPUT
to the OUTPUT.

Figure 8-10. Series/Parallel Statement Combination

Continued on next page

8-12
Custom Control Programming, Continued

Field 1 OR (first) & AND (second)

In Figure 8-11 the first and second statements are linked in Parallel and the third statement is
linked in Series with the first and second statements. Remember, a Link operator links that
statement with all previous statements, not just the statement before it.

Field 1 Field 2 Field 3 Field 4


FIRST
STATEMENT [ ] [ ] [FIRE] [3-01]
SECOND
STATEMENT [OR] [ ] [FIRE] [3-02]
THIRD
STATEMENT [AND] [ ] [FIRE] [3-03]
Figure 8-11. OR with AND Operator

In Figure 8-11, IF the condition of 3-01 is Fire OR the condition of 3-02 is Fire, AND the
condition of 3-03 is Fire, then the INPUT SIDE is true. Another way to look at this equation is
shown in Figure 8-12. In order to cross from the INPUT SIDE of the equation to the OUTPUT
SIDE, the first or second statements and the third statement must be true.

3-01

3-03
OUTPUT
INPUT SIDE SIDE
(Statements 1, 2 & 3)
Points 3-01 and 3-02 (in parallel)
are in series with 3-03.
3-02 3-01 or 3-02 must be true and
3-03 must be true in order to
go from the INPUT to the OUTPUT.

Figure 8-12. Parallel/Series Statement Combination

Continued on next page

8-13
Custom Control Programming, Continued

Field 2 Field 2 can be empty or can contain the negative operator NOT. NOT is used in Figure 8-13 to
state IF point 3-01 is NOT in a FIRE condition, THEN that statement is true.

AND & NOT

The AND Link operator links the current statement in series with all previous statements in an
equation (see Figure 8-13).

Field 1 Field 2 Field 3 Field 4


FIRST
STATEMENT
[ ] [ ] [FIRE] [3-01]
SECOND
STATEMENT [AND] [NOT] [FIRE] [3-02]
Figure 8-13. AND with NOT Operator

In Figure 8-13, if the condition of 3-01 is Fire AND the condition of 3-02 is NOT Fire then the
INPUT SIDE is true. Another way to look at this equation is shown in Figure 8-14. In order to
cross from the INPUT SIDE of the equation to the OUTPUT SIDE, the first and second
statements must be true.

Note: The NOT gate is shown as a normally closed contact. This statement is true because
there is a path from the Input to the Output.

INPUT SIDE 3-01 3-02


(Statements 1 & 2)
OUTPUT
SIDE
This statement is true because
3-01 is in the FIRE condition
and 3-02 is NOT in the FIRE
condition.

Figure 8-14. NOT Operator Used in Series

Continued on next page

8-14
Custom Control Programming, Continued

Field 2 OR & NOT

The OR Link operator links the current statement in Parallel with all previous statements in an
equation (see Figure 8-15).

Field 1 Field 2 Field 3 Field 4


FIRST
STATEMENT [ ] [ ] [FIRE] [3-01]
SECOND
STATEMENT [OR] [NOT] [FIRE] [3-02]

Figure 8-15. OR with NOT Operator

In Figure 8-15, if the condition of 3-01 is Fire OR the condition of 3-02 is NOT Fire then the
INPUT SIDE is true.

Another way to look at this equation is shown in Figure 8-16. In order to cross from the
INPUT SIDE of the equation to the OUTPUT SIDE, the first or the second statement must be
true.

Note: The NOT gate is shown as a normally closed contact. This statement is true because
there is a path from the Input to the Output.

18-
3-01
01

OUTPUT
INPUT SIDE SIDE
(Statements 1 & 2)

3-02 This statement is true because


18- 3-01 is not in the FIRE condition
and 3-02 is not in the FIRE
condition.

Figure 8-16. NOT Operator Used in Parallel

Fields 3 and 4 Field 3 contains the condition qualifier for the point listed in Field 4 (refer to Table 8-1 for all
INPUT SIDE condition qualifiers). Field 4 options change per condition qualifier selected.

Continued on next page

8-15
Custom Control Programming, Continued

Fields 3 and 4 FIRE

When using the input condition qualifier FIRE, a statement is true when the point indicated in
Field 4 is in the FIRE state. Field 4 choices for the FIRE qualifier are:

• System Card Points

• Digital Pseudo Points

Note: The statement holds true until the system is no longer in the FIRE state.

When the condition of 3-01 is FIRE, the input is true, and the output is executed. If the system
is not reset, and the condition of 3-02 becomes FIRE after 3-01, the system outputs ignore
3-02. In other words, if the output executes from the FIRE condition of 3-01, the output will
not re-execute from the FIRE condition of 3-02.

Field 1 Field 2 Field 3 Field 4


FIRST
STATEMENT [ ] [ ] [FIRE] [3-01]
SECOND
STATEMENT [OR] [ ] [FIRE] [3-02]

Figure 8-17. The FIRE Condition Qualifier

Example: The condition of 3-01 is FIRE. The 4010 is reset from the Fire Alarm Control
Panel (FACP)Agent Release Control System. After the system is reset (and there are no
alarms) the condition of 3-02 is FIRE. The appropriate notification appliances now activate
for the FIRE condition of 3-02.

FIRE DET

When using the input condition qualifier FIRE DET (Fire Detect), a statement is true when the
point indicated in Field 4 is activated. Field 4 Choices for the FIRE DET qualifier are:

• IDNet Points

• Digital Pseudo Points

Note: When using the FIRE DET qualifier, the statement holds true for one 4010 polling cycle
(typically less than one second). This allows the output to re-execute after a signal silence.

When the condition of 3-01 is FIRE DET, the input is true for one 4010 polling cycle which
can vary depending upon your application, and the output is executed. If the condition of 3-02
becomes FIRE DET after 3-01, the system re-executes the output. In other words, if the output
executes from the FIRE DET condition of 3-01, the output will re-execute from the FIRE DET
condition of 3-02.

Continued on next page

8-16
Custom Control Programming, Continued

Fields 3 and 4
Field 1 Field 2 Field 3 Field 4
FIRST
STATEMENT [ ] [ ] [FIRE DET] [3-01]
SECOND
STATEMENT [OR] [ ] [FIRE DET] [3-02]

Figure 8-18. The FIRE DET Qualifier

Example: The condition of 3-01 is FIRE DET. The appropriate notification appliances are
silenced from the FACP. After the notification appliances are silenced the condition of 3-02 is
FIRE DET. The notification appliances now resound for the FIRE DET condition of 3-02.

FIRE ACK

When using the input condition qualifier FIRE ACK (Fire Acknowledge), a statement is true
when the point indicated in Field 4 is activated. Field 4 Choices for the FIRE ACK qualifier
are:

• IDNet Points

• Digital Pseudo Points

Note: The statement holds true until the point indicated in Field 4 is Acknowledged.
Field 1 Field 2 Field 3 Field 4
FIRST
STATEMENT
[ ] [ ] [FIRE ACK] [3-01]
SECOND
STATEMENT
[OR] [ ] [FIRE ACK] [3-02]
Figure 8-19. The FIRE ACK Qualifier

Example: The condition of 3-01 is FIRE ACK. The input of the equation remains true until
the point indicated in Field 4 is acknowledged. The same holds true for 3-02.

SUPV

When using the input condition qualifier SUPV (Supervisory), a statement is true when the
point indicated in Field 4 is activated. Field 4 choices for the SUPV qualifier are:

• System Card Points

• Digital Pseudo Points

Note: The statement holds true until the point indicated in Field 4 clears.

Continued on next page

8-17
Custom Control Programming, Continued

Fields 3 and 4
Field 1 Field 2 Field 3 Field 4
FIRST
STATEMENT [ ] [ ] [SUPV] [3-01]
Figure 8-20. The SUPV Qualifier

Example: The condition of 3-01 is SUPV. The input of the equation remains true until the
point indicated in Field 4 is cleared.

SUPV ACK

When using the input condition qualifier SUPV ACK (Supervisory Acknowledge), a statement
is true when the point indicated in Field 4 is activated. Field 4 choices for SUPV ACK are:

• System Card Points

• Digital Pseudo Points

Note:The statement holds true until the point indicated in Field 4 is Acknowledged.

Field 1 Field 2 Field 3 Field 4


FIRST
STATEMENT [ ] [ ] [SUPV ACK] [3-01]
Figure 8-21. The SUPV ACK Qualifier

Example: The condition of 3-01 is SUPV ACK. The input of the equation remains true until
the point indicated in Field 4 is acknowledged from the FACP.

TBL

When using the input condition qualifier TBL (Trouble), a statement is true when the point
indicated in Field 4 is in trouble. Field 4 choices for the TBL qualifier are:

·CPU Card Points

·System Card Points

·Power Supply Points

·Digital Pseudo Points

Note:The statement holds true until the point indicated in Field 4 not in trouble.

Field 1 Field 2 Field 3 Field 4


FIRST
STATEMENT [ ] [ ] [TBL] [3-01]
Figure 8-22. The TBL Qualifier

Continued on next page

8-18
Custom Control Programming, Continued

Fields 3 and 4 Example: The condition of 3-01 is SUPV ACK. The input of the equation remains true until
the point indicated in Field 4 is acknowledged from the FACP.

TBL ACK

When using the input condition qualifier TBL ACK (Trouble Acknowledge), a statement is
true when the point indicated in Field 4 is in trouble and requires an acknowledge. Field 4
choices for the TBL ACK qualifier are:

• CPU Card Points

• System Card Points

• Power Supply Points

• Digital Pseudo Points

Note: The statement holds true until the point indicated in Field 4 (in trouble) is
Acknowledged.

Field 1 Field 2 Field 3 Field 4


FIRST
STATEMENT [ ] [ ] [TBL ACK] [3-01]
Figure 8-23. The TBL ACK Qualifier

Example: The condition of 3-01 is TBL ACK. The input of the equation remains true until
the point indicated in Field 4 is acknowledged.

ON/CODE and OFF

When using the input condition qualifier ON/CODE (On Coding), a statement is true when the
point indicated in Field 4 is On or Coding. Field 4 choices for the ON/CODE qualifier are:

• CPU Card Points

• System Card Points

• Power Supply Points

• Digital Pseudo Points

• Analog Pseudo Points

Note: The statement holds true until the point indicated in Field 4 is OFF.

Continued on next page

8-19
Custom Control Programming, Continued

Fields 3 and 4
Field 1 Field 2 Field 3 Field 4
FIRST
STATEMENT [ ] [ ] [ON/CODE] [3-01]
Figure 8-24. The ON/CODE Qualifier

Example: The condition of 3-01 is ON/CODE. The input of the equation remains true until
the point indicated in Field 4 is OFF.

When using the input condition qualifier OFF, a statement is true when the point indicated in
Field 4 is OFF. Field 4 choices for the OFF qualifier are:

• CPU Card Points

• System Card Points

• Power Supply Points

• Digital Pseudo Points

• Analog Pseudo Points

Note: The statement holds true until the point indicated in Field 4 is ON or Coding.

Field 1 Field 2 Field 3 Field 4


FIRST
STATEMENT [ ] [ ] [OFF] [3-01]
Figure 8-25. The OFF Qualifier

Example: The condition of 3-01 is OFF. The input of the equation remains true until the point
indicated in Field 4 is ON or Coding.

COMP CNST, ANY, ALL, & DELAY CNST

The COMP CNST (Compare Constant) ANY, ALL, and DELAY CNST input condition
qualifiers are two-stage qualifiers. Additional programming is necessary in order for these
qualifiers to work correctly. When selecting these qualifiers, you must press Enter to program
the second stage. In this second stage there are four additional fields with the following
choices: Analog Points, numbers, relational qualifiers, and Lists. The choices for the different
fields are related directly to the qualifier selected.

Continued on next page

8-20
Custom Control Programming, Continued

Fields 3 and 4 COMP CNST

When using the input condition qualifier COMP CNST, a statement is true when the value of
the Analog Pseudo point in Field 2 is the proper relationship (Field 3 relational qualifier) to the
number in Field 4 (see Figure 8-27). The choices for Fields 2, 3, and 4 are as follows:

• Field 2 - Analog Pseudo points 21-01 through 21-25 (20-01 through 20-07 are system
Analog Pseudo points)

• Field 3 - Relational Qualifiers EQ (Equal), NE (Not Equal), GT (Greater Than), LT (Less


Than), GE (Greater Than or Equal), and LE (Less Than or Equal)

• Field 4 - Number Value (00000 to 65535)

Field 1 Field 2 Field 3 Field 4


SECOND STAGE
FIELDS [COMP CNST] [20-01] [EQ] [00001]
Two-Stage Input Analog Pseudo Relational Number
Condition Qualifier Point 20-01 Qualifier

Figure 8-26. The COMP CNST Qualifier

Example: When the value of the analog pseudo point equals 1, then execute the output.

ANY

When using the input condition qualifier ANY, a statement is true when the specified number
of points from Field 2 equals the number of points in the List identified in Field 4 that are in
the condition specified by Field 3. The choices for Fields 2, 3, and 4 are as follows:

• Field 2 - Point number value 001 to 255

• Field 3 - Conditions FIRE ACK, SUP ACK, TBL ACK, FIRE, SUP, TBL, ON IN, ON
CODE, PHY NRM, PHY ABN, PHY SHR, FIRE DET, DISABLE, MAN

• Field 4 - List Pseudo Points 23-01 through 23-25 are user points (List Points 22-01
through 22-12 are system List Pseudo Points)
Field 1 Field 2 Field 3 Field 4
SECOND STAGE
FIELDS [ANY] [001] [FIRE ACK] [23-01]
Two-Stage Input Point Number Condition List Point
Condition Qualifier Value

Figure 8-27. The ANY Qualifier

Example: When any one (1) point's condition in the List 23-01 is FIRE ACK, then execute
the output.

Continued on next page

8-21
Custom Control Programming, Continued

Fields 3 and 4 ALL

Note: When choosing the ALL condition qualifier, there are only three fields open for
programming.

When using the input condition qualifier ALL, a statement is true when all points specified in
Field 3 are in the condition specified in Field 2. The choices for Fields 2 and 3 are as follows:

• Field 2 - Conditions FIRE ACK, SUP ACK, TBL ACK, FIRE, SUP, TBL, ON IN, ON
CODE, PHY NRM, PHY ABN, PHY SHR, FIRE DET, DISABLE, MAN

• Field 3 - List Points 23-01 through 23-25


Field 1 Field 2 Field 3
SECOND STAGE
FIELDS [ALL] [FIRE ACK] [23-01]
Two-Stage Input Condition List Point
Condition Qualifier
Figure 8-28. The ALL Qualifier

Example: When all points in List 23-01 are in the condition of FIRE ACK, then execute the
output.

DELAY CNST

When using the input condition qualifier DELAY CNST, and the input statement is true, the
output action is delayed for a specified amount of time (in seconds).

Note: The input must be true for the entire delay time specified.

Field 1 Field 2 Field 3


SECOND STAGE
FIELDS [DELAY CNST] [21-05] [00020]
Two-Stage Input Point Specified Delay Time
Condition Qualifier

Figure 8-29. The DELAY CONST Qualifier

Output Side (THEN) Each output statement is made up of three fields.

Field 1 Field 2 Field 3


OUTPUT
STATEMENT [Hold On] [21-02] [9,9]
Action Specifier Point Priority
for Field 2
Figure 8-30. The Three Output Fields

Continued on next page

8-22
Custom Control Programming, Continued

Output Side (THEN) FIELD 1

Field 1 contains Action Operators, as listed in Table 8-3.

FIELD 2

When using any Action Operator, Field 2 choices are:

• CPU Card Points

• System Card Points

• Power Supply Points

• Digital Pseudo Points

• List Pseudo Points

FIELD 3

Field 3 contains the Set and Reset Priorities of control equipment (relays) and Pseudo points.
This eliminates confusion of when a point is under control of one statement and another
statement tries to take control (see Figure 8-31).
Field 1 Field 2 Field 3
OUTPUT
STATEMENT [Hold On] [23-02] [9,9]
Action Specifier Point
for Field 2 Set Priority Reset Priority
Figure 8-31. Field 3

In Figure 8-31, point 23-02 will HOLD ON (IF the input is true) at a Set Priority of 9. This
output statement will maintain control of this point until another output statement with an
equal (9) or greater Set Priority takes over. The possible ranges for a priority are from 1 to 15,
1 being the highest and 15 being the lowest priority. By default, the priority is 9. When
changing a priority, press Function and then press the right arrow button to place the cursor
under the Set Priority. Use <Next> and <Previous> to scroll through the priorities.

Press the right arrow button to place the cursor under the Reset priority. Use <Next> and <Pre-
vious> to scroll through the priorities and then press <Enter> to program the priorities selected.

8-23
Application-Specific Examples

Overview The following examples detail the use of the 4010's newer Custom Control features.

Day/Night Programming M1-1 is a TrueAlarm Photo sensor. Customer wants normal 2.5% sensitivity during working
Example hours (7am - 6pm) and higher sensitivity (1.0%) at night. (A11 is current hour analog pseudo
point.)

Equation 1:
IN:
A11 GREATER THAN 7(7 is 7am)
OUT:
SET THRESHOLD M1-1 LEVEL 5 (level 5 is 2.5% obscuration)
END:

Equation 2:
IN:
A11 GREATER THAN 18(18 is 6pm)
OUT:
SET THRESHOLD M1-1 LEVEL 2 (level 2 is 1.0% obscuration)
END:

TrueAlarm Heat Utility A customer wants a supervisory alert when an impending freeze is detected by a TrueAlarm
Monitoring Example heat sensor. M1-1 is a HEAT sensor programmed with the UTILITY point type. P75 is a user
defined digital point with the SUPERVISORY point type.

IN:
M1-1 LESS THAN 38(38 is degrees F)
OUT:
TRACK ON P75 PRI=9,9
END:

City Circuit Alarm-Output A customer only wants the city circuit's alarm output to activate when a waterflow alarm
Programming Example occurs. In this example, L25 is a user-created list of all Waterflow monitor points.

IN:
L25 ALARM
OUT:
TRACK ON P60 PRI=7,7 (Use priority greater than 9
to control this point)
END:

AHJ City Circuit Reset This example shows how to program the panel or AHJ City Reset operation.
Operation Example
IN:
A4 ON
OUT:
HOLD ON P16 PRI=9,9
END:

8-24
Chapter 9.
Saving a CFIG

Introduction The 4010 FACP provides the ability to continue making edits, save or discard changes that you
make to the panel's programming.

In This Chapter This chapter discusses the following topics:

Topic See Page #

Viewing CFIG Properties 9-2

Continue, Restore CFIG, and Save CFIG 9-3

9-1
Viewing CFIG Properties

Overview CFIG properties include information such as the System Revision, the job name and its
revision, and the system's current time and date.

Procedure The Software Revision menu allows access to the CFIG properties. It is located at the topmost
level of the 4010 menu structure.

Historical Software
Diagnostics
Logs Revision

1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> to scroll through the options until SOFTWARE


REVISION is displayed and then press <ENTER>.

3. Press <ENTER>. Information similar to the following appears. The exact revision
number and Job Rev. that you see depends on the revision level of the software installed
on your 4010.

Sys Rev 3.00.00 4010 System


JOB REV: 1 12:00:00 am Fri 7-Dec-01

Figure 9-1. CFIG Properties

9-2
Continue, Restore CFIG, and Save CFIG

Continue The Continue option allows you continue an edit session without saving or restoring the
information stored in the Edit Buffer to the CFIG. This option appears when you use the Exit/
Clear button to back out of programming mode.

Restore CFIG The Restore CFIG option restores all information to the 4010 configuration prior to any
programming modifications. Select this option if you do not wish to save any edits or
modifications you made during your programming session to the 4010 configuration.

You can restore a CFIG by choosing the menu option as described below or by pressing Exit/
Clear to back out of Programming mode and then choosing the Restore CFIG option from the
4010 prompts. In both cases, your 4010 re-boots and becomes operational as a fire alarm
system.

To access the Restore CFIG menu option, follow these steps:

1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed and then press


<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

3. Press <ENTER> to continue.

4. Press <NEXT> or <PREVIOUS> until <RESTORE CFIG> is displayed and then press
<ENTER>.

Save CFIG The Save CFIG option saves all information to the 4010 configuration after or during
programming. Choose this option if you wish to save all of your edits and modifications you
made during your programming session to the 4010 configuration.

You can save CFIG by choosing the menu option as described below or by pressing Exit/Clear
to back out of Programming mode and then choosing the Save CFIG option from the 4010
prompts. In both cases, your 4010 re-boots and becomes operational as a fire alarm system.

To access the Restore CFIG menu option, follow these steps:

1. Press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed and then press


<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

3. Press <ENTER> to continue.

4. Press <NEXT> or <PREVIOUS> until <SAVE CFIG> is displayed and then press
<ENTER>.

When exiting the programming mode, your 4010 re-boots and becomes operational as a fire
alarm system.

9-3
Chapter 10.
Diagnostics and Troubleshooting

Introduction This chapter describes the diagnostic tools provided with the 4010 FACP and describes some
simple techniques used to help you troubleshoot the 4010.

Before Calling Technical DID YOU…


Support
Verify all system wiring?

Test all power circuits (AC and Batteries) and fuses for opens?

Ensure that all IDNet devices are correctly addressed?

Verify that all hardware has been added to the system either individually or via the Quick CFIG
option?

Verify that all switches and adjustable potentiometers are correctly set, and End-of-Line
Devices are in place (refer to “Chapter 1 . 4010 FACP Overview” for correct settings)?

WHEN YOU CALL, HAVE THE FOLLOWING AT HAND…

Any error messages from the front panel.

History Logs for all Alarm, Trouble, and Supervisory information.

Revision Level of your system as well as any option cards.

Note: An accurate time and date are essential for the proper operation of the 4010 FACP.
Make sure to check the time and date at least once a month, and reset it if necessary. Changing
the time and date are described in Chapter 11 of this manual.

In This Chapter This chapter discusses the following topics:

Topic See Page #

Diagnostics 10-2

Walk Test 10-6

TrueTest 10-8

Crash Codes 10-10

10-1
Diagnostics

Overview The 4010 has the capability to run diagnostics on the N2 communication lines, the IDNet
channel, the Network communication lines, and to locate an Earth Fault between IDNet
devices. This section shows how to run the diagnostic utility on the 4010.

Running Diagnostics Running diagnostics is the easiest way to ensure proper communication between the FACP and
its various devices. To use the Diagnostics, you must be logged in at a Level 4. Follow Steps
1 through 3 to run diagnostics on the 4010.

1. From the High-Level Status screen, press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [Diagnostics] is displayed and then press


<ENTER>.

3. Press <NEXT> or <PREVIOUS> to select the desired diagnostic option and then press
<ENTER>.

The Diagnostic options are shown in Figure 10-1.


Top Level Menus

Software Set Time


Diagnostics
Revision and Date

• N2 Communications

• IDNet Earth Fault Search

• IDNet Diagnostics

• Network

Figure 10-1. Diagnostic Options

Continued on next page

10-2
Diagnostics, Continued

Diagnostic Options Once a diagnostic option is selected, you can set the options by pressing <NEXT> or
<PREVIOUS> to scroll through the choices shown in Table 10-1.

Table 10-1: Diagnostic Options

Diagnostic Option Settings

N2 Comm On or Off

IDNet Earth Fault Search On or Off

IDNet Diagnostics Choose:


• IDNet Weak Answer (On/Off)

• IDNet Duplicate Device (On/Off)

Network Choose
• Node Number (displays the current
4010 node number)

• Topology

• Attendance

N2 Comm Diagnostics Use the N2 Comms Diagnostics to check for noisy N2 comm lines and other N2 comm errors.
The screen in Figure 10-2 shows a typical N2 Communication Diagnostic screen. This screen
informs you of the amount of messages sent, the amount of message retries and the amount of
card failures. Note that these tallies are only kept while diagnostics are active.

4010 Card 1, 4010 NAC/Relay Card


Msgs Sent=0 Retries=0 Fails=0

Figure 10-2. N2 Communication Diagnostic Screen

Pressing <NEXT> or <PREVIOUS>scrolls through the available cards that are


communicating on the N2 lines and displays that card's N2 diagnostic information.

Pressing <ENTER> (while a particular card's information is displayed) prompts you to press
<ENTER> again to clear the message counts for that card.

IDNet Diagnostics Duplicate Devices

To detect devices set to the same address you can activate the IDNet Diagnostics - Duplicate
Device option. Once activated, there is a trouble in the panel indicating that you have activated
the option. The two devices set to the same address then come in as a duplicate device trouble
for that address. Acknowledge the trouble and view the point information to determine the
address that the devices are set to and correct the problem.

Continued on next page

10-3
Diagnostics, Continued

IDNet Diagnostics Weak Answer Devices

When receiving a Weak Answer Trouble you can determine which device is causing the
trouble by activating the IDNet Diagnostics - Weak Answer option. When activated there is a
trouble in the panel informing you that the option is active. Acknowledge the trouble and wait.
Any device which is weak will then report NO ANSWER when the Weak Answer Diagnostic
is run.

IDNet Earth Fault Search Use the IDNet Earth Fault Search Diagnostics to locate an "earth" between the panel and the
Diagnostics first IDNet isolator device or to another isolator device. Note that the 4010 FACP does not
function as a fire panel for the duration of an Earth Fault search.

If an "earth" cannot be isolated or there are no isolators configured on the system, the 4010
returns an "Unable to Isolate Earth Fault" message.

If the "earth" is isolated between the first isolator and the FACP, the 4010 returns an "Earth
Fault Between Panel and 1st Device" message.

If the "earth" is isolated to any other device, the 4010 returns an "Earth Fault Isolated to Device
M1-X" where X is the isolator address.

Network Diagnostics Once the 4010 is "networked" to other panels using the PC Programmer (see 4010 Fire Alarm
- PC Programming Instructions, Part No. 574-187) you can check the node number of the
4010, network topology, and network attendance.

Figure 10-3 shows a typical Network Topology screen. Topology information shows how the
network is physically wired and whether there are any breaks in the network loop.

M=Monitor Node
L=LEFT End Node
R=RIGHT End Node
(_)=This Node
a=Missing Node

Figure 10-3. Network Topology Screen

Attendance information shows if the network nodes are configured. Each position on the
4010's LCD represents a node's address for a maximum of 80 nodes (only 80 nodes can be
displayed because there are only 80 positions on the 2 by 40 character LCD). Each node can
only be represented by one character. Figure 10-4 is NOT a typical Attendance screen; it is
shown for reference only.

Continued on next page

10-4
Diagnostics, Continued

Network Diagnostics

1M.4L_7.RO...........2..................
..3...................................9.

Figure 10-4. Network Attendance Screen

Notes for Figure 10-4:

1 = Node number 1

M = Monitor node (node number 2)

. = No node configured at this address

4 = Node number 4

L = Node number 5 (fifth position on screen; it is the left end node)

_ = Missing node

7 = Node number 7

R = Node number 9 (ninth position on screen; it is the right end node)

2 = Node number 22 (twenty-second position on screen)

3 = Node number 43 (forty-third position on screen)

9 = Node number 79 (seventy-ninth position on screen)

10-5
Walk Test

Overview Walk Test allows one person to test the functionality of the 4010. Once the panel is placed into
Walk Test mode, any device can be tested in any order. For each device, you should simulate
both an alarm and trouble. If an audible or visible indication is used, wait for the indication
before moving on to the next device. Walk Test options are viewed by selecting the WalkTest
entry at the main menu. The Walk Test screens allow you to customize the Walk Test
operation. The signals (if enabled) annunciate device coding for Walk Test. Earth Faults are
signaled during Walk Test on both the front panel display/tone-alert and by activating audible
and visible notification circuits for 4 seconds. Suppression release outputs are NOT activated
by Walk Test.

Walk Test automatically aborts after eight hours and restores the panel to normal operation.

Using Walk Test To activate Walk Test, follow Steps 1 through 5.

1. From the High-Level Status screen, press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [WalkTest] is displayed and then press <ENTER>.

3. Press the right and left arrow buttons to move the focus brackets to the desired option.

4. Press <NEXT> or <PREVIOUS> to scroll through the following choices:

• On/Off - Walk Test mode.

• Log/No Log - allows events to be recorded to the Historical Logs.

• Signal/Silent - activate/deactivate Signals.

5. Press <ENTER> to activate Walk Test.

10-6
Walk Test, Continued

Using Walk Test Figure 10-5 shows an example of the Walk Test screen with the default values.

<ENTER> to Accept <ARROW KEYS> to Change


[Off] Log Silent

Figure 10-5. Walk Test Screen

10-7
TrueTest

Overview The TrueTest feature provides a simple method of testing the application specific software in
the FACP without the need to manually activate the initiating device circuits. In other words,
TrueTest provides an easy method of testing the Input/Output programming to verify that the
programming is written as the customer specified.

Once the panel is in TrueTest mode, you can modify a point's status by selecting the desired
point at the front panel and pressing <NEXT> or <PREVIOUS> until the TrueTest screen is
displayed. The point's custom label and device address are displayed along with an option
select box allowing you to select the desired TrueTest physical state.

The choices for the TrueTest state depend on the currently selected point's attributes. For
monitor hardware device type points, the options are NORMAL, ABNORMAL, OPEN, and
SHORT. For TrueAlarm sensors, the sensitivity threshold possibilities available for the
selected device are presented (see Appendix A for sensitivities and levels). Press <NEXT> or
<PREVIOUS> to scroll through the possible choices for that point type.

Once you have selected the desired state, pressing <ENTER> forces the state change as a
TrueTest simulated event. Pressing <EXIT/CLR> exits the TrueTest menu without making
any changes.

When a TrueTest simulated event occurs, the system responds as if that point had actually
entered the specified state up to the point of activating control outputs if NoCTRL is selected.
If CTRL is selected, selected outputs activate. Any control point activation, DACT reporting,
printing, and logging is selected in the TrueTest menu (refer to Table 10-2 for options). Any
LEDs programmed to track any point also operate (there is no way to disable this).

Table 10-2: TrueTest Options

TrueTest
Description
Option

On/Off Activates or deactivates TrueTest.

Log/NoLog Determines whether the TrueTest events are sent to the logs.

Print/NoPrint Determines whether the TrueTest events are sent to a printer.

DACT/NoDACT Determines whether any events occurring in TrueTest are


reported to the DACT.

NoCTRL/CTRL By default no control circuits of any kind are activated during


the test. If desired, all control points may be activated during
the test by selecting CTRL. This category includes all control
points (audibles, visibles, and any other control points).

Continued on next page

10-8
TrueTest, Continued

Using TrueTest Use Steps 1 through 5 and Figure 10-6 and Figure 10-7 to activate TrueTest.

1. From the High-Level Status screen, press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [TrueTest] is displayed and then press <ENTER>.

3. Press the right and left buttons to move the focus brackets to the desired option.

4. Press <NEXT> or <PREVIOUS> to enable the options listed in Table 10-2.

5. Once all options are set, press <ENTER> to activate TrueTest.

Top Level Menus

Walk Test TrueTest Quick CFIG

• On/Off

• Log/NoLog

• Print/NoPrint

• DACT/NoDACT

• NoCTRL/CTRL

Figure 10-6. TrueTest. Options

Figure 10-7 shows an example of the TrueTest screen with the default values.

<ENTER> to Accept <ARROW KEYS> to Change


[Off] Log Print NoDACT NoCTRL

Figure 10-7. WalkTest Screen

10-9
Crash Codes

Table 10-3: Crash Codes

Code Meaning Cause Corrective Action


0 Illegal Crash Code Erroneous call to crash handler. Code not supported
RAM memory failed pattern check or the newly
1 RAM Memory Fail Replace hardware
calculated checksum did not restore correctly.
2 Hardware Stack Fail Not used - erroneous call to crash handler. Code not supported
3 Bad Message Index Call to get message string with illegal value. Reload application
Default for switch when illegal value cannot be
4 Bad Switch Value Reload application
defaulted.
ROM memory failed its CRC check, either BOOT or Reload applicationReplace
5 ROM Memory Fail
Application. Hardware
The 4010 Application failed trying to define an OS Reload applicationReplace
6 OS Initialization Fail
object. Hardware
An interrupt vector was executed when that interrupt Reload applicationReplace
7 Unexpected Interrupt
was not enabled. Hardware
The 4010 application called a BOOT function that Reload applicationReplace
8 Unexpected Function
does not exist. Hardware
9 Internal RAM Fail The on-chip RAM failed integrity check during startup. Replace hardware
Check keypad connections /
A Keypad Missing The 4010 keypad is missing.
Replace hardware
Indicates a mismatch between the EXEC and Upgrade EXEC and
CFIG Format
B programmer software. For example, using a version 1 programmer software to
Mismatch
EXEC with a version 2 programmer. same revision.
Invalid SMPL The SMPL interpreter failed trying to execute a corrupt Reload job. Check versions
C
Opcode program. of tools and panel
A database routine failed trying to access an illegal Reload job. Check versions
D Invalid Card Address
card number. of tools and panel
A database routine failed trying to access an illegal Reload job. Check versions
E Invalid Point Number
point number. of tools and panel
F I/O Scan Time-Out Not used - erroneous call to crash handler. Code not supported.
The application tried to get a type of data that is not
associated with the data point it was intended for. This Reload job. Check versions
10 Invalid Get Status
can be caused by using the PC programmer to assign of tools and panel
a point type of "unavailable" to a NAC or 24 PT I/O
The application tried to save a type of data that is not Reload job. Check versions
11 Invalid Put Status
associated with the data point it was intended for. of tools and panel
12 Flash Erase Failure The Flash chip erase function returned an error. Replace hardware
13 Flash Write Failure The Flash chip write function returned an error. Replace hardware
The OS signaled a mail event but had no mail for the
14 Empty Mail Event Reload application
process.
The system was unable to allocate a required
15 No Comm. Memory Reduce cards/reload job
communication buffer.

10-10
Crash Codes, Continued

Table 10-3: Crash Codes (continued)

Code Meaning Cause Corrective Action


The state index for a card was invalid for the card's
16 Bad Card State Reload BIN File
type
Failed Restoring
17 Not Used. Erroneous call to the crash handler *
SMPL
Unable to Restore
18 The flash chip copy to RAM function returned an error Replace Hardware
CFIG
19 Task 1 Stopped Supervisor task watchdog timer has expired. *
Reload CFIG. Check
1A Task 2 Stopped Front panel task watchdog timer has expired.
versions of panel and tools.
Reload CFIG. Check
1B Task 3 Stopped System operation task watchdog timer has expired
versions of panel and tools.
Reload CFIG. Check
1C Task 4 Stopped Communication task watchdog timer has expired
versions of panel and tools.
Reload CFIG. Check
1D Task5 Stopped Serial port task watchdog timer has expired.
versions of panel and tools.
1E Task 6 Stopped Not used. Erroneous call to the crash handler. *
1F Task 7 Stopped Not used. Erroneous call to the crash handler. *
Execution across the common code area boundary
20 Common Overrun Reload BIN file.
was detected.
Execution across the code bank 0 area boundary was
21 Bank 0 Overrun Reload BIN file.
detected.
Execution across the code bank 1 area boundary was
22 Bank 1 Overrun Reload BIN file.
detected.
Execution across the code bank 2 area boundary was
23 Bank 2 Overrun Reload BIN file.
detected.
Execution across the code bank 3 area boundary was
24 Bank 3 Overrun Reload BIN file.
detected.
Execution across the code bank 4 area boundary was
25 Bank 4 Overrun Reload BIN file.
detected.
Execution across the code bank 5 area boundary was
26 Bank 5 Overrun Reload BIN file.
detected.
Execution across the code bank 6 area boundary was
27 Bank 6 Overrun Reload BIN file.
detected.
Execution across the code bank 7 area boundary was
28 Bank 7 Overrun Reload BIN file.
detected.
Execution across the code bank 8 area boundary was
29 Bank 8 Overrun Reload BIN file.
detected.
Execution across the code bank 9 area boundary was
2A Bank 9 Overrun Reload BIN file.
detected.
Execution across the code bank 10 area boundary was
2B Bank 10 Overrun Reload BIN file.
detected.

Continued on next page

10-11
Crash Codes, Continued

Table 10-3: Crash Codes (continued)

Code Meaning Cause Corrective Action


2C Bank 11 Overrun Not used. Erroneous call to the crash handler. *
2D Bank 12Overrun Not used. Erroneous call to the crash handler. *
2E Bank 13 Overrun Not used. Erroneous call to the crash handler. *
2F Bank 14 Overrun Not used. Erroneous call to the crash handler. *
30 Bank 15 Overrun Not used. Erroneous call to the crash handler. *
31 Bank 16 Overrun Not used. Erroneous call to the crash handler. *
Reload Job / Check versions
32 Network Buffer Error The network card local port buffer handler lost a buffer of tools and panel / reload
BIN File
Reload Job / Check versions
The mapnet card received a packet that failed its
33 Bad Mapnet Packet of tools and panel / reload
consistency check.
BIN File
Reload Job / Check versions
An LCD function was passed an illegal or impossible
34 Bad Parameter of tools and panel / reload
value.
BIN File
Reload Job / Check versions
The LCD processing failed to allocate a global memory
35 Out of Memory of tools and panel / reload
buffer
BIN File
Reload Job / Check versions
The RAM CFIG area failed its CRC calculation during
36 CFIG Consistency of tools and panel / reload
a background check.
BIN File
Reload Job / Check versions
The system called the string format function (sprintf)
37 Bad String Length of tools and panel / reload
with a format string greater than 59 characters.
BIN File
38 Illegal Crash Code Erroneous call to the crash handler. *

* denotes a code that should never appear.

10-12
Chapter 11.
Operation

Introduction This chapter describes common tasks that need to be performed following installation and
programming of the 4010 FACP.

An operator logged into the system at Level 1 can perform all tasks described in this chapter.

In This Chapter This chapter discusses the following topics:

Topic See Page #

Handling Abnormal Conditions 11-2

Viewing and Clearing Historical Logs 11-5

Viewing and Controlling Points 11-7

Editing Custom Labels 11-10

User Control Functions 11-12

Setting the Time and Date 11-13

11-1
Handling Abnormal Conditions

Normal Operation The 4010 shows the following under normal conditions:

• Green AC power LED ON (indicating that AC power is applied)

• All other panel indicator LEDs OFF

• System Information on the LCD (SYSTEM NORMAL with the current time and date)

Abnormal Conditions Abnormal conditions are indicated on the 4010 by flashing the alarm, supervisory, or trouble
LED and sounding the tone-alert. The display provides information as to the point status
(alarm, supervisory, and trouble), time, date, type of device (smoke detector, pull station, etc.),
number of abnormal conditions in the system, and a custom description of the abnormal
condition causing the alarm. Alarm, supervisory, and trouble conditions each have their
respective acknowledge key. Pressing the appropriate acknowledge key silences the tone-
alert. However, the LED indicator remains ON until all initiating devices are restored to
normal.

CUSTOM FIRE=0 SUPERVISORY=0 TROUBLE=3


LABEL
FIRST FLOOR EAST WING ROOM 12
POINT
TYPE Smoke Detector Trouble 1/3

FIRST OF
DEVICE CONDITION THREE TROUBLES

Figure 11-1. Example Abnormal Condition Screens

When the 4010 senses an Alarm Condition, the tone-alert sounds at a march time rate, and the
FIRE ALARM LED turns ON and flashes, indicating that an alarm condition is present. In
addition, the appropriate indications are shown on the display.

When the 4010 senses a Supervisory Condition, the tone-alert sounds steady, the SYSTEM
SUPERVISORY LED turns ON and flashes, and various programmed events occur.

When the 4010 senses a malfunction within the system (loss of power, hardware failure, etc.),
a Trouble Condition is announced by the system. The tone-alert sounds steady, the SYSTEM
TROUBLE LED flashes, and various programmed events occur.

The tone-alert may be programmed to sound at specified time intervals to serve as a reminder
that any active status condition still exists within the system (Active Status Reminder).

Continued on next page

11-2
Handling Abnormal Conditions, Continued

Acknowledging an The 4010 is a Global Acknowledge System, which means ONE (1) press of an <ACK> key
Alarm, Trouble, or globally acknowledges every abnormal point in the system in that category. When
Supervisory Condition acknowledged, an appropriate message is displayed.

When a point is acknowledged, the appropriate LED remains ON and the tone-alert is silenced.
The total number of alarm, trouble, and supervisory conditions is shown in an alternating
sequence on the display along with a prompt to the press <ACK> for point review. Pressing
<ACK> scrolls through the selected list in chronological order. Each list is different and
contains information concerning a particular abnormal condition. In some cases, additional
information is available on the condition by pressing <ENTER>.

Silencing Alarms When an alarm condition exists, various signals, auxiliary relays, the city connection, and the
tone-alert may activate, depending on the system configuration and the stage of the alarm
condition. Turning signals, tone alerts, etc. off is known as Alarm Silencing.

An important feature to be aware of when silencing alarms on the 4010 is its "re-sound"
capability. If, after silencing the signals, the 4010 detects another abnormal condition, the
zone with the abnormal condition is indicated on the panel display, the appropriate indicator
again flashes, and the signals sound again.

Caution: Pressing the Alarm Silence key causes fire alarm evacuation signals to turn OFF.
Follow local procedures to silence alarm evacuation signals.

To silence an alarm, press the <ALARM SILENCE> key. Two actions occur when you do
this:

• The <ALARM SILENCE> key, when pressed, turns OFF all circuits programmed to
follow the Alarm Silence key.

• The ALARM SILENCED LED turns ON and remains ON.

Note: If Waterflow/Sprinkler Devices are activated, notification appliances may or may not be
silenced (depending on local code requirements). Usually, a dedicated bell continues to sound
to indicate waterflow.

Continued on next page

11-3
Handling Abnormal Conditions, Continued

Resetting the System The <SYSTEM RESET> key is used to return the system to its normal state after an alarm
condition has been cleared. When the <SYSTEM RESET> key is pressed, it causes any
latched circuits to reset automatically. Also reset are initiating devices, relays (including the
city relay), notification appliances, and all LEDs and indicators which are programmed to reset
with the <SYSTEM RESET> key. The message, SYSTEM RESET IN PROGRESS, is
displayed when the key is pressed.

To reset the system, perform the following steps:

1. Restore/replace all affected devices in accordance with the instructions provided with each
device.

2. Press the <SYSTEM RESET> key.

If a device stays in alarm during the reset period, the system reset is aborted, and the system
remains in an alarm state. The display indicates the total number of alarms present in the
system along with a prompt to use the <ACK> key to review the points. These points do not
require acknowledgment. The alarm LED remains ON to indicate that a device is still in an
alarm condition.

If the system does not reset, and the display still shows an alarm, read the display to determine
the type of device and the address of the device still in alarm. Follow local procedures to
investigate the area of the building with the alarm. Look for devices still in alarm. Most
devices latch until they are reset, either by the system or manually.

11-4
Viewing and Clearing Historical Logs

Overview This section describes how to view and clear the Historical Logs on the 4010.

The 4010 has three logs; Alarm, Supervisory, and Trouble. The logs can be viewed separately,
or they can be viewed in chronological sequence as a single Combined log. Each log records
information about the event and the time the event occurred. Table 11-1 describes the
different logs and their stored events.

Table 11-1: Historical Logs and Events

Historical Log Stored Events

ALOG • Alarms
Alarm Log (up to 100 entries) • Alarm Ack (global only)
• Log cleared
• Alarm Silence
• System Reset

SLOG • Supervisory conditions


Supervisory Log (up to 50 • Supervisory Ack (global only)
entries) • Log cleared

TLOG • All card and system troubles


Trouble Log (up to 300 entries) • Login/Logout for Level 2 or higher
• Log cleared
• Walk Test events (abnormal and trouble)
• TrueAlarm peak values (if selected)

CLOG
• All Events in chronological order
Combined Log (all entries)

Figure 11-2 shows an example of an Alarm Log.

One of 34 alarm
log entries
ALOG: 1/34 10:09:01 am Fri 7-Dec-01
Fire Alarm

Figure 11-2. Sample Alarm Log Screen

Continued on next page

11-5
Viewing and Clearing Historical Logs, Continued

Using the Historical Logs To view the Historical Logs, follow Steps 1 through 4.

1. From the High-Level Status screen, press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [Historical Logs] is displayed and then press
<ENTER>.

3. Press <NEXT> or <PREVIOUS> to view the desired log and then press <ENTER>.

4. Press <NEXT> or <PREVIOUS> to scroll through the log entries.

To clear the log you are viewing, press <ENTER> and follow the prompts to confirm this
action.

The Historical Log options are shown in Figure 11-3.

Top Level Menus

Login/ Historical Software


Logout Logs Revision

• Alarm

• Supervisory

• Trouble

• Combined

Figure 11-3. Historical Log Options

11-6
Viewing and Controlling Points

Overview The 4010 allows you to view each configured point in the system and, depending on your
access level, control and disable/enable the point you are viewing. This section describes how
to view, control, and enable/disable points.

Controlling/Viewing Use steps 1 through 5 and Figure 11-4 to control/view points in a 4010. A TrueAlarm device
Points type and point are used as an example in this section.

1. From the High-Level Status screen, press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [Control/View Points] is displayed and then press
<ENTER>.

3. Press <NEXT> or <PREVIOUS> to scroll through the point types until the desired device
type is displayed [TrueAlarmTrueAlarm] and then press <ENTER>.

4. Press <NEXT> or <PREVIOUS> to scroll through the points until the point you wish to
view/control is displayed and then press <ENTER>.

5. Press <ENTER> to activate control of that point and to view additional information about
that point. Press <NEXT> or <PREVIOUS> to scroll through the allowable functions for
the point you are viewing.

Top Level Menus

Panel Control/ Login/


Restart View Points Logout

TrueAlarm

• View Additional Info

• Control Points

• Enable/Disable

Figure 11-4. Control/View Points Menu

Continued on next page

11-7
Viewing and Controlling Points, Continued

Controlling/Viewing The control functions for each point type are listed in Table 11-2.
Points
Table 11-2: Device Type and Control Functions

Device Type Control Functions View Functions

TrueAlarm Control: View:


• Clear Verification Tally • Address
• Force on Device LED • Device Type
• Change Sensitivity • Point Type
• Clear Peak Value • Sensitivity
• Change TrueTest State
• Manually Control Sounder,
Relay or Isolator

ZAMS/IAMs Control: View:


• Clear Verification Tally • Address
• Force on Device LED • Device Type
• Change TrueTest State • Point Type

Relay/RIAMs Control: Same as


ON/OFF/Auto/Change Priority ZAMS/IAMS

NACs Control: Same as


ON/OFF/Auto/Change Priority ZAMS/IAMS

Digital Pseudos Control: Same as


ON/OFF/Change Priority ZAMS/IAMS

Analog Pseudos SET analog value for the point Same as


(range: 0 to 65535) ZAMS/IAMS

Lists Control: ON/OFF/Auto Same as


View: ZAMS/IAMS
• List Counts
• List Contents

24-I/O Inputs Turn on Card LED Same as


ZAMS/IAMS

24-I/O Outputs Control:ON/OFF/Auto/Change Same as


Priority ZAMS/IAMS

System Points VIEW ONLY, NO CONTROL Same as


ALLOWED ZAMS/IAMS

Continued on next page

11-8
Viewing and Controlling Points, Continued

Disabling/Enabling Use steps 1 through 6 to disable/enable points in a 4010. A TrueAlarm device type and point
Points are used as an example in this section.

1. From the High-Level Status screen, press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [Control/View Points] is displayed and then press
<ENTER>.

3. Press <NEXT> or <PREVIOUS> to scroll through the point types until the desired device
type is displayed [TrueAlarmTrueAlarm] and then press <ENTER>.

4. Press <NEXT> or <PREVIOUS> to scroll through the points until the point you wish to
disable/enable is displayed and then press <Disable/Enable>.

5. Press <NEXT> or <PREVIOUS> to select [Enable] or [Disable] and then press


<ENTER>.

6. Press <ENTER> to disable/enable the viewed point.

A Disable Trouble sounds at the FACP when disabling points. NACs are isolated when
disabled. The 4010 preserves the disable state of a point on a warm start.

When a disabled monitor point is enabled, the 4010 displays a 30 second count down,
displaying the time until the point is enabled. When enabling a point that is still in an alarm
state, theFACP warns you that the point is in alarm. The FACPFACP gives you 30 seconds
that allows you to abort the enabling of that point.

Disabling Points in Alarm Use steps 1 through 3 to disable/enable points in alarm on a 4010. You must be logged in at
the appropriate level to disable/enable points.

1. From the High-Level Status screen, press <Alarm ACK>.

2. Continue to press <Alarm ACK> until the desired point is displayed and then press
<Disable/Enable>.

3. Press <ENTER> to confirm this action.

11-9
Editing Custom Labels

To edit a point's custom label, use steps 1 through 11. As an example, editing the label of a
TrueAlarm point is used in the following steps and in Figure 11-5. Once in the Programming
Mode, the 4010 is OFF-LINE.

1. Login to the 4010 at the appropriate level.

2. Press <MENU>.

3. Press <NEXT> or <PREVIOUS> to scroll through the menu until [Programming] is


displayed and then press <ENTER>.

4. Press <NEXT> or <PREVIOUS> to scroll through the menus until [Configure Points] is
displayed and then press <ENTER>.

5. Press <NEXT> or <PREVIOUS> to scroll through the menus until the type of point you
wish to configure is displayed [TrueAlarm] and then press <ENTER>.

6. Press <NEXT> or <PREVIOUS> to scroll through the menus until [Edit


TrueAlarmTrueAlarm Point] is displayed and then press <ENTER>.

7. Press <NEXT> or <PREVIOUS> to scroll through the TrueAlarmTrueAlarm points until


the point you wish to edit is displayed and then press <ENTER>.

8. Press <NEXT> or <PREVIOUS> to scroll through the menus until [Edit Point Label] is
displayed and then press <ENTER>.

Top Level Menus

Quick Upload/
CFIG Programming Download

Configure
Points

TrueAlarm

Edit
TrueAlarm
Point

Edit Point
Label

Figure 11-5. Menu Structure for Editing a Custom Label

11-10
Editing Custom Labels, Continued

An edit point label screen appears (Figure 11-6) with the first character of the existing label
underlined.

Figure 11-6. Edit Point Label Screen

9. Press <NEXT> or <PREVIOUS> to scroll through the character set. Use the right and left
arrow keys to move to the next character in the label. The <Disable/Enable> key
overwrites characters with a space.

Pick a label that best suits the location of the device. The 4010 provides up to 40
characters per line (including spaces). The available characters are as follows:

• Digits: 0-9

• Alpha: A-Z (only capital letters are available)

• Punctuation: comma space & ( ) * + - period / : ' # ! @ $


% ^ = ? ;

10. Press <ENTER> once the label reads correctly. Press <ENTER> again to confirm the
change to the label. For changes to take effect, press <EXIT/CLEAR> until a
confirmation screen appears.

11. Once you complete the editing, the 4010 prompts you to save the new information to the
CFIG. Press the right or left keys to select [Save CFIG] and press <ENTER> to save the
information.

11-11
User Control Functions

Overview User control functions, such as Manual Evac, City Disconnect, Control Point Bypass and
Elevator Recall Bypass, are available from the High Level Status screen by pressing
<FUNCTION>. Pressing <FUNCTION> also accesses operations including latching earth
faults, displaying the current time and date when the system is abnormal, and performing lamp
test.

In addition to the pre-defined functions listed above, the 4010 supports two "User-Defined"
function keys. The two user-defined key choices in the function menu are "User Defined 1"
and "User Defined 2." These user-defined keys may be programmed to perform often used
functions. A 40-character custom label may be assigned to these user-defined keys.

Using the Function Use steps 1 through 3 to access the Function Control menu.
Options
1. From the High-Level Status screen, press <Function>.

2. Press <NEXT> or <PREVIOUS> to scroll through the function options (see Table 11-3)
until the desired option is displayed and then press <ENTER>.

3. Press <NEXT> or <PREVIOUS> to select ON or OFF for that option and then press
<ENTER>.

Table 11-3 lists the function options and their descriptions.

Table 11-3: Function Menu Options and Descriptions

Function Option Description

Manual Evacuation Activates the Manual Evacuation operation (NACs


activate and Fire Alarm LED flashes until Ack'd).

City Circuit Disconnect* Disconnects the City Circuit.

Control Point Bypass* Bypasses the following Control Points:


• On until Silence signals
• Resettable signals
• AHU outputs

Elevator Bypass* Bypasses the Elevator Recall.

Doorholder Bypass* Bypasses Doorholder operation.

Lamp Test Illuminates all LEDs and all LCD segments on the
display.

Earth Fault Latch Latches intermittent Earth Fault Troubles into the
4010.

User Defined Key 1 One of two user-defined function keys.

User Defined Key 2 One of two user-defined function keys.

Display Current Time Displays current time during abnormal conditions.

*Activation of these options causes a trouble at the panel.

11-12
Setting the Time and Date

Use steps 1 through 5 and Figure 11-7 to set the time and date.

An accurate time and date setting is essential to the proper operation of the 4010 system. The
time and date should be checked at least once a month and reset, as described below, if
necessary.

1. From the High-Level Status screen, press <MENU>.

2. Press <NEXT> or <PREVIOUS> until [Set Time/Date] is displayed and then press
<ENTER>.

3. Press the right and left arrow keys to move the focus brackets to the desired field (hours,
minutes, date, month, year).

4. Press <NEXT> or <PREVIOUS> until the desired value is displayed.

5. Once all fields are set, press <ENTER> to set the time and date.

Top Level Menus

Set
Diagnostics Walk Test
Time/Date

• Hour

• Minute

• Day

• Month

• Year

Figure 11-7. Set Date/Time

11-13
Appendix A.
Device and Point Types

Introduction Each point in the 4010 has both a hardware device type and a software point type. The
hardware device type is determined by the hardware used. This is used to determine what
physical states exist for the point. The hardware device type also determines the valid software
point types that can be assigned to a point.

The software point type defines which "banner" and "status" is used in displaying a point when
it changes state on the display or is logged to the historical log. The software point type,
especially for output points, also defines the default application programming. For example a
NAC with a point type of SSIGNAL indicates that the signal circuit activates on alarm until
silence.

This chapter describes the Hardware Device and Software Point Types available with the
4010. For more information on Analog, Digital, List, and 24-Point I/O point types, refer to
"Appendix B. Hardware and Pseudo Points" in this publication.

In This Chapter This chapter discusses the following topics:

Topic See Page #

Hardware Device Types A-2

Software Point Types A-4

A-1
Hardware Device Types

Overview The 4010 supports IDNet devices as Fire Alarm input and output, as well as four hardwired
output points, and two auxiliary relay output points.

TrueAlarm Hardware Table A-1 lists the TrueAlarm Hardware Device Types available with the 4010 FACP.
Device Types
Table A-1: Hardware Device Types

Device Type Description

PHOTO TrueAlarm photoelectric sensor

SPHOTO TrueAlarm photoelectric sensor with sounder base

RPHOTO TrueAlarm photoelectric sensor with relay base

IPHOTO TrueAlarm photoelectric sensor with isolator base

XPHOTO TrueAlarm extra-sensitive photoelectric sensor

XSPHOTO TrueAlarm extra-sensitive photoelectric sensor with sounder base

XRPHOTO TrueAlarm extra-sensitive photoelectric sensor with relay base

XIPHOTO TrueAlarm extra-sensitive photoelectric sensor with isolator base

ION TrueAlarm ionization sensor

SION TrueAlarm ionization sensor with sounder base

TION TrueAlarm single station ionization sensor

RION TrueAlarm ionization sensor with relay base

IION TrueAlarm ionization sensor with isolator base

HEAT TrueAlarm fixed temperature heat sensor

SHEAT TrueAlarm fixed temperature heat sensor with sounder base

RHEAT TrueAlarm fixed temperature heat sensor with relay base

IHEAT TrueAlarm fixed temperature heat sensor with isolator base

OHEAT TrueAlarm fixed temperature and rate of rise heat sensor

SOHEAT TrueAlarm fixed temperature and rate of rise heat sensor with
sounder base

ROHEAT TrueAlarm fixed temperature and rate of rise heat sensor with
relay base

IOHEAT TrueAlarm fixed temperature and rate of rise heat sensor with
isolator base

Continued on next page

A-2
Hardware Device Types, Continued

TrueAlarm Levels and Sensitivities and corresponding levels are shown in Table A-2 for TrueAlarm types.
Sensitivities
Table A-2: TrueAlarm Levels and Sensitivities

Levels Sensitivities

PHOTOs XPHOTOs IONs HEATs

Level 1 0.5% 0.2% 0.5% 117°F (47°C)

Level 2 1.0% 0.5% 0.9% 135°F (57°C)

Level 3 1.5% 1.0% 1.3% 155°F (68°C)

Level 4 2.0% 1.5% 1.7% 155°F (68°C)

Level 5 2.5% 2.0% 1.7% 155°F (68°C)

Level 6 3.0% 2.5% 1.7% 155°F (68°C)

Level 7 3.7% 3.7% 1.7% 155°F (68°C)

Monitor Hardware Device Table A-3 lists the Monitor Hardware Device Types for the 4010.
Types
Table A-3: Monitor Hardware Device Types

Device Type Description

MAZAM Class A Monitor ZAM (T-sense)

MBZAM Class B Monitor ZAM (T-sense)

ADRPUL Addressable Pull Station

SIAM Supervised IAM (T-sense)

CANPUL Canadian 2-stage Pull Station

KACPUL International KAC Pull Station

4009A Hardware Device Table A-4 lists the 4009A hardware device types. (Note: Each 4009A is located at "virtual
Types card" address 17.)

Table A-4: 4009A Hardware Device Types

Device Type Description

4009A Standard 4009A

R4009A 4009A with repeater

4009A8 4009A with four-NAC option board

4009A with four-NAC option board


R4009A8
and repeater

A-3
Software Point Types

Monitor Point Types Table A-5 lists the monitor point types and their descriptions.

Table A-5: Monitor Point Types

Point Type Description


FIRE Fire alarm (generic)
WATER Waterflow switch
HEAT Heat detector
DUCT Duct detector
FLAME Flame detector
PULL Pull station - manual
SMOKE Smoke detector
VSMOKE Verified smoke zone
ABORT Abort Zone (pre-signal)
EMERG Emergency Alarm
SFIRE Combination Smoke/Fire zone
VSFIRE Verified Combination Smoke/Fire zone
SPULL Combination Smoke/Pull zone
VSPULL Verified Combination Smoke/Pull zone
GENMON Generator monitor
SGENMON Supervisory generator monitor
FPUMP Fire pump monitor
SFPUMP Supervisory fire pump monitor
S2STAGE 2-stage monitor (abn=pre-signal, short=alarm)
SO Sprinkler supervision (normally open)
WSO Waterflow/sprinkler supervision (normally open)
LATSUPV Latching supervisory
SDUCT Supervisory Duct Detector
SUPDET Suppression Release detector zone
SUPABRT Suppression Release abort zone
SUPDUMP Suppression Release manual dump
SUPPRES Suppression Release pressure monitor
SUPV Supervisory (generic)
UTIL Non-alarm utility
DAMPER Damper Monitor (open/closed)
TROUBLE Trouble monitor
STYLEC Current limit = fire alarm, short/open = trouble
GVMON Generic verified monitor

A-4
Software Point Types, Continued

Table A-5: Monitor Point Types (Continued)

Point Type Description


SSABORT Suppression Release Abort Zone
(current limit/short = supervisory)
SSDUMP Suppression Release Manual Dump
(current limit/short = fire)
LSDUCT Latching Supervisory Duct Detector
SSPRES Suppression Release Pressure Monitor
(current limit/short = fire)

Signal Point Types Every 4010 has four Notification Appliance (signal) points. The default configuration is SIG1
& SIG2 "on 'til silence" (point type = SSIGNAL) and SIG3 & SIG4 "on 'til reset" (point type =
RSIGNAL).
Table A-6 lists the signal point types and their descriptions.

Table A-6: Signal Point Types

Point Type Description

SIGNAL Generic signal (no default operation)

SSIGNAL Alarm signal - on 'til silence (temporal coded)

RSIGNAL Alarm signal - on 'til reset

SVISUAL Visual - on 'til silence

RVISUAL Visual - on 'til reset

SWATER Waterflow signal - on 'til silence

RWATER Waterflow signal - on 'til reset

SUPV Sprinkler supervisory signal - on 'til ack

SUPREL Suppression (agent discharge) release output

PRIMARY Elevator capture - primary

ALTERN Elevator capture - alternate

AHUR AHU on/off relay - single relay control

AHUO AHU on relay - dual relay control

AHUF AHU off relay - dual relay control

DHOLDER Doorholder control

TSIGNAL Trouble/supervisory signal - on 'til clear

BSIGNAL Trouble/supervisory "bell" signal - on 'til acknowledged

RELAY Generic Relay

A-5
Software Point Types, Continued

Table A-6: Signal Point Types (Continued)

Point Type Description

QALERT TrueAlert Non-Addressable (no default operation)

SQALERT TrueAlert Non-Addressable

RELISIG See Table D-1 Appendix D

RELVIS See Table D-1 Appendix D

RELWVIS See Table D-1 Appendix D

RELSIG See Table D-1 Appendix D

Relay Point Types The 4010 includes two AUX relay points configured as AUX1 and AUX2. The default point
type settings for AUX1 set as an Alarm relay on until reset (point type = RRELAY) and AUX2
set as a Trouble/Supervisory relay on until clear (point type = TRELAY).

Table A-7 lists the Relay point types and their descriptions.

Table A-7: Relay Point Types

Point Type Description

RELAY Generic relay

PRIMARY Elevator Capture - primary

ALTERN Elevator Capture - alternate

AHUR AHU on/off relay - single relay control

AHUO AHU on relay - dual relay control

AHUF AHU off relay - dual relay control

SRELAY Alarm Relay - on 'til silence

RRELAY Alarm relay - on 'til reset

TRELAY Trouble relay - on til clear

BRELAY Trouble relay - on til acknowledge

DHOLDER Door Holder

SWATER Waterflow relay - on 'til silence

RWATER Waterflow relay - on 'til reset

RSUPV Supervisory relay

SVISUAL Visual - on 'til silence

RVISUAL Visual - on 'til reset

SUPREL Suppression (agent discharge) release output

A-6
Software Point Types, Continued

Table A-7: Relay Point Types (Continued)

Point Type Description

SIGNAL Generic Signal (no default operation)

Continued on next page

A-7
Software Point Types, Continued

TrueAlert Non- TrueAlert Non-Addressable operation for a particular NAC is enabled by selecting the
Addressable Point Types QALERT software point types. Two types of points exist - one under system control and one
with no system mode, which allows you to use Custom Control to perform selective signaling.

Table A-8: TrueAlert Non-Addressable Point Types

Point Type Description

QALERT This point type has no automatic operation. All operations for
this point type must be programmed using Custom Control.

SQALERT When the SQALERT point type is selected, the system does
the following:
• Automatically turns ON the designated circuit on alarm
detect.
• Issues the Horn Silence command upon Alarm Silence.
• Turns OFF the circuit at the completion of System Reset.
Any point programmed with this point type will not be available
for Custom Control programming.

A-8
Appendix B.
Hardware and Pseudo Points

Introduction This appendix describes the points that may exist in all 4010 systems. The points are broken
up into two major groups: hardware points and pseudo points. Furthermore, each of these
groups is broken down by card.

In This Chapter This chapter discusses the following topics:

Topic See Page #

Hardware Points B-2

Pseudo Points B-13

B-1
Hardware Points

Overview There are many different types of hardware points that exist in the 4010 system. They include
system points that are read only to the user, points on the IDNet channel, points on optional
cards, public 4120 network points, and card status points. Many of these points may be
referenced in Custom Control in both the input and output sides of an equation, depending on
the Custom Control operation, and the type of point (refer to “Chapter 8. Custom Control” for
more information). The following sections will describe each hardware point for each card in
the system, both default and optional.

General Card Status This section describes attributes that apply to all card status points in the 4010. Card status
Point Information points are used to indicate card troubles in the system. Card status points may only be viewed
from the Active Trouble List, the Historical Logs, or on an RS232 port (if available). When
viewing a card status point, a banner will be displayed that will indicate that the trouble is a
card status trouble, and which card the point is associated with. A card status point label will
also be displayed to indicate the type of card status trouble it is.

Note: A card status point cannot be used in Custom Control or with LED mode programming.

Master Controller Card The Master Controller Card resides at Card Address 0 and contains 13 hardware points. The
Master Controller Card is required in all 4010 configurations.

Master Controller Card The Master Controller Card does not have any card status points associated with it.
Status Points

Master Controller Points The Master Controller Card has 13 hardware points associated with it. Of the 13 hardware
points, eight are system points which are not editable by the user. The other five master points
can be configured by the user. Table B-1 shows a list of the Master Controller points. The type
field denotes which class the point falls into (R=System point that is Read Only to user,
U=User Configurable Points).

Continued on next page

B-2
Hardware Points, Continued

Master Controller Points

Table B-1: Master Controller Points

Point Type Label Description

Indicates the status of the Piezo Sounder on


0-1 R Front Panel Piezo
the 4010 Master.

Indicates the status of the External N2


External N2 Disconnect Disconnect Relay. Turns on when no slaves
0-2 R
Relay are communicating; turns off on System
Reset.

0-3 R Fire LED Status of the front panel Alarm LED.

0-4 R Supervisory LED Status of the front panel Supervisory LED.

0-5 R Trouble LED Status of the front panel Trouble LED.

0-6 R Alarm Silence LED Status of the front panel Alarm Silence LED.

0-7 R AC Power LED Status of the front panel AC Power LED.

This point indicates the status and


0-8 U User LED 1 configuration of the first user programmable
LED on the front panel.

This point indicates the status and


0-9 U User LED 2 configuration of the second user
programmable LED on the front panel.

This point indicates the status and


0-10 U User LED 3 configuration of the third user programmable
LED on the front panel.

This point indicates the status and


0-11 U User Defined Key 1 configuration of the first user programmable
key (in the function menu).

This point indicates the status and


0-12 U User Defined Key 2 configuration of the second user
programmable key (in the function menu).

Indicates the status of the LCD backlight on


0-13 R LCD Backlight
the front panel.

NAC Card The NAC (Notification Appliance Circuit) Card is required for all 4010 configurations, and is
located at Card Address 1. There are seven hardware points and eight card status points
associated with the NAC card.

Continued on next page

B-3
Hardware Points, Continued

NAC Card Status Points The NAC Card has eight card status points associated with it. Table B-2 describes the card
status points for the NAC card.
Table B-2: NAC Card Status Points

Point Label Description

This trouble indicates that the NAC card is not communicating with the
1-CS 1 Missing Card
master.

This trouble indicates that the card returned a card type as something
1-CS2 Wrong Card
other than a NAC card type.

NAC 1 and 2 Class A card not inserted trouble. Only occurs if circuits
1-CS3 NACs 1 & 2 Class A
are configured with NACA device type.

NAC 3 and 4 Class A card not inserted trouble. Only occurs if circuits
1-CS4 NACs 3 & 4 Class A
are configured with NACA device type.

1-CS5 NAC 1 Signal Power Indicates a signal power trouble for NAC 1.

1-CS6 NAC 2 Signal Power Indicates a signal power trouble for NAC2.

1-CS7 NAC 3 Signal Power Indicates a signal power trouble for NAC3.

1-CS8 NAC 4 Signal Power Indicates a signal power trouble for NAC4.

NAC Card Points The NAC has seven hardware points associated with it. Of the seven hardware points, six are
points which may be programmed by the user. The other point is the City Circuit point which
is not available for programming or viewing by the user. The following table is a list of the
points on the NAC card. The type field denotes which class the point falls into (S=System
point that is not available to the user for viewing or programming, U=User Configurable
Points).
Table B-3: NAC Card System and User Points

Point Type Label (default) Description

1-1 U NAC Circuit: SIG 1 NAC card Signal 1 status and configuration.

1-2 U NAC Circuit: SIG 2 NAC card Signal 2 status and configuration.

1-3 U NAC Circuit: SIG 3 NAC card Signal 3 status and configuration.

1-4 U NAC Circuit: SIG 4 NAC card Signal 4 status and configuration.

1-5 U AUX Circuit: AUX 1 NAC card Relay 1 status and configuration.

1-6 U AUX Circuit: AUX 2 NAC card Relay 2 status and configuration.

1-7 S City Circuit Interface 4010 City Module.

Continued on next page

B-4
Hardware Points, Continued

Power Supply Card The power supply card is required for all 4010 configurations, and is located at Card Address
2. There are nine hardware points and two card status points associated with the Power Supply
card.

Power Supply Card The power supply card has two card status points associated with it. The following table
Status Points describes the card status points for the power supply card.

Table B-4: Power Supply Card Status Points

Point Label Description

This trouble indicates that the power supply card is


2-CS1 Missing Card
not communicating with the master.

This trouble indicates that the card returned a card


2-CS2 Wrong Card type as something other than a Power Supply card
type.

Power Supply Points The power supply card has nine hardware points associated with it. All of the power supply
points are system points that cannot be modified by the user. Table B-5 displays a list of the
points on the power supply card.
Table B-5: Points on the Power Supply Card

Point Label Description

This trouble point will indicate that the AC line voltage is too low for proper
2-1 AC Power
system operation.

Positive Earth This trouble point indicates that there is a fault condition between +24 V and
2-2
Ground Earth.

Negative Earth This trouble point indicates that there is a fault condition between 0 V and
2-3
Ground Earth.

Expansion Power This trouble point indicates Expansion Power Supply trouble. Only occurs if
2-4
Supply expansion supply is configured.

Expansion Power This trouble point indicates Expansion Power Supply AUX Battery Power
2-5
Supply Battery trouble. Only occurs if expansion supply is configured.

2-6 Battery Low This trouble point indicates that the battery has a voltage less than 22.8 V.

Battery Depleted
2-7 This trouble point indicates that the battery has a voltage less than 19.5 V.
or Disconnected

Battery Low This trouble point indicates that AC Power has been lost and the batteries
2-8
Cutout have reached a depleted state, the system shuts off.

2-9 Battery Charger This utility point indicates the status of the battery charger (on/off).

Continued on next page

B-5
Hardware Points, Continued

IDnet Card The IDNet card is required for all 4010 configurations, and is located at Card Address 3. The
IDNet card defaults to a configuration with no hardware points (devices). However, up to 250
devices may be programmed for the IDNet card. The IDNet card also includes eight card status
points.

IDNet Card Status Points The IDNet Card has eight card status points associated with it. Table B-6 describes the card
status points for the IDNet card.

Table B-6: IDNet Card Status Points

Point Label Description

This trouble indicates that the IDNet card is not communicating with the
3-CS1 Missing Card
master.

This trouble indicates that the card returned a card type as something
3-CS2 Wrong Card
other than a IDNetcard type.

This trouble indicates a channel failure on the IDNet line (no devices are
3-CS3 Channel Failure
communicating).

This trouble indicates that there is a device answering that is not included
3-CS4 Extra Device in the configuration (view the trouble log to determine the devices
address).

This trouble indicates a Class A trouble condition on the IDNet line. This
3-CS5 Class A Status
requires a System Reset to clear.

Power Supply
3-CS6 This point indicates a power supply trouble on the IDNet card.
Status

3-CS7 Short Status This trouble point indicates a short condition on the IDNet card.

Ground Fault
3-CS8 This trouble indicates that there is a ground fault in the IDNet line.
Status

Continued on next page

B-6
Hardware Points, Continued

IDNet Points The IDNet card can have up to 250 devices configured. All of the IDNet devices can be
modified by the user. How the point is configured (i.e. software point type) determines what
action is taken (trouble, alarm, etc.) when the point changes state. The following table is a list
of the points that may be included on the IDNet card. The labels indicated for the points are
the default labels assigned when the point is added from the front panel.

Table B-7: Points That May Appear on an IDNet Card

Point Label (default) Description

3-1 IDNet Device: M1-1 The point on the IDNetcard configured for address 1.

3-2 IDNet Device: M1-2 The point on the IDNet card configured for address 2.

3-3 IDNet Device: M1-3 The point on the IDNet card configured for address 3.

3-249 IDNet Device: M1-249 The point on the IDNet card configured for address
249.

3-250 IDNet Device: M1-250 The point on the IDNet card configured for address
250.

RS-232 or Modem Card Either an RS-232 card or modem card may be added to the 4010 system. Even though these
cards are optional, if an RS-232 or modem card is configured, it must reside at Card Address
4. There are two hardware points and eight card status points associated with both the RS-232
card and modem card.

Continued on next page

B-7
Hardware Points, Continued

RS-232/Modem Card Both the RS-232 card and the modem card have eight card status points associated with them.
Status Points The card status points described in this section apply to either card. The following table
describes the card status points for both the RS-232 and modem card.

Table B-8: RS-232 or Modem Card Status Points

Point Label Description

4-CS1 Missing Card This trouble indicates that the card is not communicating with the master.

This trouble indicates that the card returned a card type as something other
4-CS2 Wrong Card
than a RS232 or modem card type (respectively).

Port A If Port A is a supervised port, and disconnected, this point will indicate this
4-CS3
Disconnected with a trouble.

Port B If Port B is a supervised port, and disconnected, this point will indicate this
4-CS4
Disconnected with a trouble.

This point indicates a trouble in the Primary Telco line (not presently
4-CS5 Primary Telco
supported).

Secondary This point indicates a trouble in the Secondary Telco line (not presently
4-CS6
Telco supported).

Port A Ground This point indicates a ground fault trouble on Port A (not presently
4-CS7
Fault supported).

Port B Ground This point indicates a ground fault trouble on Port B (not presently
4-CS8
Fault supported).

RS-232/Modem Points The RS-232 and modem cards havehas two hardware points associated with them. Both of the
RS-232/modem points are user configurable. However, the points have no labels associated
with them, because they cannot be viewed on the front panel. Table B-9 is a list of the points
on the RS-232/modem cards.

Table B-9: RS-232 or Modem Card Hardware Points

Point Label Description

Port A point. Default to unsupervised 80 character


4-1 None
Printer port.

4-2 None Port B point. Default to command line port.

DACT Card The DACT card is an optional card that may be added to the 4010 system. The DACT card is
mutually exclusive with the network card, and if configured, must reside at Card Address 8.
There is one hardware point and seven card status points associated with the DACT card.

Continued on next page

B-8
Hardware Points, Continued

DACT Card Status Points The DACT card has seven card status points associated with it. The following table describes
the card status points for the DACT card.

Table B-10: SDACT Card Status Points

Point Label Description

8-CS1 Missing Card This trouble indicates that the card is not communicating with the master.

This trouble indicates that the card returned a card type as something other than
8-CS2 Wrong Card
a DACT card type.

Central This trouble indicates that communication was lost with the Central Station.
8-CS3
Station

8-CS4 Phone Line 1 This trouble indicates that Phone Line 1 has been disconnected.

8-CS5 Phone Line 2 This trouble indicates that Phone Line 2 has been disconnected.

Program This trouble indicates that the on board DACT card checksum test has failed.
8-CS6
Checksum

DB Version This trouble indicates that the configuration loaded on the DACT card differs from
8-CS7
Mismatch the configuration on the master.

SDACT Points The SDACT card has one hardware point associated with it. The point does not have a label,
because it cannot be viewed from the front panel. Table B-11 describes the point on the
SDACT card.

Table B-11: Point on the SDACT Card

Point Label Description

8-1 None SDACT Port

Network Card The network card is an optional card that may be added to the 4010 system. The network card
is mutually exclusive with the SDACT card, and if configured, must reside at Card Address 8.
The network card allows the 4010 to serve as a network node for a 4120 network. Points on the
4010 may be declared public to the 4120 network. These points are the Network Status points,
and will be described in this section. There are also seven card status points associated with
the network card.

Continued on next page

B-9
Hardware Points, Continued

Network Card The network card has seven card status points associated with it. The following table describes
Status Points the card status points for the network card.

Table B-12: Network Card Status Points

Point Label Description

8-CS1 Missing Card This trouble indicates that the card is not communicating with the master.

This trouble indicates that the card returned a card type as something other
8-CS2 Wrong Card
than a network card type.

Version This trouble indicates that the 4010's current configuration differs from versions
8-CS3
Mismatch on other nodes.

Net Comm This trouble indicates that communication was lost between the Network card
8-CS4
Failure and the 4120 network.

8-CS5 Ground Fault This trouble indicates that there is a ground fault in the network line.

Duplicate This trouble indicates that more than one node on the 4120 network is
8-CS6
Node answering for the same address (not presently supported).

Network This trouble indicates that the port-to-port network wiring is incorrect (i.e. left-
8-CS7
Miswire to-left or right-to-right).

Network Points The network card can have up to 511 network points configured. Table B-13 shows a list of the
points that may be configured on the network card. The Common Trouble Point is the only
default point for the network card.

Table B-13: Points That May Appear on a Network Card

Label
Point Description
(default)

NetPt1 None This is the Network Common Trouble point. This point is public on the network.

This point contains the Network Type, Class, Destination, and Reference for
NetPt2 None
the second network public point.

This point contains the Network Type, Class, Destination, and Reference for
NetPt3 None
the third network public point.

This point contains the Network Type, Class, Destination, and Reference for
NetPt510 None
the 510th network public point.

This point contains the Network Type, Class, Destination, and Reference for
NetPt511 None
the 511th network public point.

Continued on next page

B-10
Hardware Points, Continued

24 I/O Card The 4010 can have up to six annunciator cards added to the system. One of these cards is the
24 I/O card. The 24 I/O card can reside at addresses 9 through 14. There are 24 hardware
points and two card status points associated with the 24 I/O card.

24 I/O Status Points The 24 I/O Card has two card status points associated with it. The following table describes
the card status points for the 24 I/O card.

Table B-14: 24 I/O Card Status Points

Point Label Description

This trouble indicates that the card is not


Card-CS1* Missing Card
communicating with the master.

This trouble indicates that the card returned a card


Card-CS2 Wrong Card
type as something other than an 24 I/O card type.
*CS = Card status

24 I/O Points Each 24 I/O card has 24 hardware points associated with it. All hardware points on the 24 I/O
card can be programmed by the user. The functionality of the point depends on the device type
(Input or Output), the point type, and modes programmed against it. The labels for the points
on the 24 I/O card are default labels, and cannot be changed by the user. The following table
describes the organization of points on the 24 I/O card.

Table B-15: 24 I/O Card Point Organization

Point Label Description

Card-1 I/O Card #, Point 1 The 1st point on the 24 I/O card.

Card-2 I/O Card #, Point 2 The 2nd point on the 24 I/O card.

Card-3 I/O Card #, Point 3 The 3rd point on the 24 I/O card.

Card-23 I/O Card #, Point 23 The 23rd point on the 24 I/O card.

Card-24 I/O Card #, Point 24 The 24th point on the 24 I/O card.

LCD Card The 4010 can have up to six annunciator cards added to the system. One of these cards is the
LCD card. The LCD card can reside at addresses 9 through 14. There are five hardware points
and four card status points associated with the LCD card.

Continued on next page

B-11
Hardware Points, Continued

LCD Card Status Points The LCD card has four card status points associated with it. The following table describes the
card status points for the LCD card.

Table B-16: LCD Card Status Points

Point Label Description

Card-CS1* Missing Card This trouble indicates that the card is not communicating with the master.

This trouble indicates that the card returned a card type as something other
Card-CS2 Wrong Card
than an LCD card type.

LCD
Card-CS3 This trouble indicates that there is a problem with the keypad on the LCD card.
Membrane

Card-CS4 LCD Display This trouble indicates that there is a problem with the display on the LCD card.
*CS = card status

LCD Points The LCD card has five hardware points associated with it. Only the first three hardware points
(user LEDs) on the LCD card can be programmed by the user. The labels for the points on the
LCD card are default labels, and cannot be changed by the user. The following table describes
the points included on the LCD card.

Table B-17: LCD Card Points

Point Label Description

LCD Card #, The status of the First User LED on the LCD card. Programmable for color and
Card-1
Point 1 mode.

LCD Card #, The status of the Second User LED on the LCD card. Programmable for color
Card-2
Point 2 and mode.

LCD Card #, The status of the Third User LED on the LCD card. Programmable for color
Card-3
Point 3 and mode.

LCD Card #,
Card-4 The status of the Alarm Silence LED on the LCD card.
Point 4

LCD Card #,
Card-5 The status of the Piezo Sounder on the LCD card.
Point 5

B-12
Pseudo Points

Overview Like the 4100U and 4005, there are three types of pseudo points that exist in every system.
They include digital, analog, and list pseudos. Each of these types may be referenced in
Custom Control in both the input and output sides of an equation. Reserved system pseudo
points are used to indicate system trouble or alarm indications, control diagnostics or other
system functions, and to communicate information between the 4010 Master and SMPL.
Some pseudos are set by the system and are read only to the user. Other pseudos are either set
from SMPL or from the front panel as a cue for the system to perform some operation. Pseudo
cards contain no card status points.

Digital Pseudo Points Every 4010 system has two digital pseudo "cards" at addresses 18 and 19. The first card is
reserved for system pseudo points while the second is available to the user. Each contains 75
digital pseudo points which may be programmed as shown in Table B-18.

Table B-18: Programming Digital Pseudo Points

Type Description

UTILITY Utility point (ON/OFF - no acknowledge required).

ALARM Fire alarm point.

SUPV Supervisory point.

TROUBLE Trouble point.

Each system digital pseudo point falls into one of the following three categories shown in
Table B-19.

Table B-19: Categories for Digital Pseudo Points

Class Description

R Point is controlled by the 4010 master and is read only to the end user.

Point is controlled by the 4010 master but may also be controlled by the
RW
end user (front panel or SMPL).

Point is controlled by the end user and is read by the 4010 Master in
W
order to accomplish some function or operation.

Continued on next page

B-13
Pseudo Points, Continued

4010 System Digital The system digital pseudo card in the 4010 system is located at Card Address 18. It contains a
Pseudos total of 75 reserved system pseudo points that cannot be edited. The following table lists the
system pseudo points. The type field denotes which class (see above) the point falls into, and
what its type is (U =UTIL, F=FIRE, T=TROUBLE, S=SUPERVISORY).

Table B-20: System Pseudo Points

Point Type Label Description

D1 RU Unacked Fire in System On if unacked fire exists in system.

On if unacked supervisory exists in


D2 RU Unacked Supervisory in System
system.

D3 RU Unacked Trouble in System On if unacked trouble exists in system.

Turned on at panel startup if an


D4 RT Extra N2 Card unprogrammed N2 slave card is
detected. Only clears on panel restart.

Turns on when panel is no longer


D5 RT External N2 Trouble communicating with ALL slave cards.
Turns off on a System Reset.

On when User SMPL program is


D6 RW U User SMPL Program
active.

Indicates that panel has performed a


D7 RT Cold Start cold start. Turns off when
acknowledged.

Indicates that panel has performed a


D8 RT Warm Start / Check Time and Date warm start. Turns off when
acknowledged.

Turns on when Manual Evacuation is


D9 RW F Manual Evacuation
selected. Turns off on a System Reset.

Indicates that the time and date is


D10 RT System Time and Date incorrect. Turns off when time and date
is updated.

Indicates that the panel is in Service


D11 RT Simplex Service Mode
Mode. Turns off only on a panel restart.

D12 RW U Keypad Inactivity Timer Disable Disables Keypad Inactivity timer.

Turns on when the number of alarms,


supervisories, or troubles is greater
D13 RT Active List Overflow than the system active list size (100
fires, 50 supv, 300 troubles). Turns off
on a panel restart.

Continued on next page

B-14
Pseudo Points, Continued

4010 System Digital


Pseudos
Table B-20: System Pseudo Points (continued)

Point Type Label Description

D14 RW T City Disconnect On if city circuit is disconnected.

D15 RT City Circuit Trouble On if city circuit is in trouble.

D16 - AHJ City Reset Utility Point On if city circuit reset is enabled.

D17 RW T Control Point Bypass On if control points are bypassed.

On if elevator recall points are


D18 RW T Elevator Bypass
bypassed.

D19 RW T Doorholder Bypass On if doorholder points are bypassed.

On when any verified points tally limit


D20 RW T Verification Tally Limit Exceeded exceeds10. Off when all points tally
limit is below 10.

D21 RT Walk Test Active in System On when Walk Test is active.

On when Earth Fault Latch diagnostic


D22 RU Earth Fault Latch
is active.

D23 RT TrueTest Active in System On when TrueTestTrueTest is active.

On when Programming or QuickCFIG


Programming Mode ? System
D24 RT is entered. Panel is no longer
Disabled
operational.

D25 RW U System Reset Activated On when System Reset Starts.

D26 RW U Alarm Silence Activated On when Alarm Silence Starts.

D27-D30 - Reserved System Pseudo Point Unused.

D31 RU Network Running in Style 4 On if network is running in Style 4.

D32-D35 Reserved System Pseudo Point Unused.

On if no sethost session is active on


D36 RU No CRT Connected
network card.

D37-D44 - Reserved System Pseudo Point Unused.

When on (either through front panel or


Duplicate IDNet Device Detection SMPL) it enables the duplicate device
D45 RW T
Active detection diagnostic on the IDNetIDNet
card.

Continued on next page

B-15
Pseudo Points, Continued

4010 System Digital


Pseudos
Table B-20: System Pseudo Points (continued)

Point Type Label Description

When on (either through front panel or


SMPL) it detects devices beyond
D46 - Weak Answer
specifications by reducing sensitivity of
receiver.

On when the RS-232/LCD annunciator


event queue is overflowed and events
D47 RT Event Queue Overflow
have been missed. Panel restart clears
the trouble.

When on the panel tells all LCD


Annunciators to disable their local
D48 WT LCD Annunciator Sounder Disable sounder. Turning pseudo off will enable
the sounders. Controllable from front
panel only? not SMPL.

D49 WU IDNet Boost When on it boosts the IDNetlevels.

When active it forces IDNet almost


D50 WU Device Almost Dirty
dirty troubles to report.

When on any peak value change


D51 WU TrueAlarm Peak Log Enable recorded on IDNet devices is sent to
the Trouble Log.

On whenever nothing is connected to


D52 RU RS232 Port A Disconnected Port A on the RS-232 or RS-232/
modem card.

On whenever nothing is connected to


D53 RU RS232 Port B Disconnected Port B on the RS-232 or RS-232/
modem card.

D54-D57 - Reserved System Pseudo Point Unused.

D58 RU Network System Reset

D59 RU Network Signal Silence

D60 - Digital: P60 Unused.

D75 - Digital: P75 Unused.

Continued on next page

B-16
Pseudo Points, Continued

4010 User Digital The user digital pseudo card in the 4010 is at address 19. It has 75 points available for
Pseudos specialized applications programming. Any point may be programmed as one of the four types
of digital pseudos (i.e. UTILITY, FIRE, etc.), and each may be assigned a 40 character custom
label.

Note that any user pseudo points defined as FIRE type are not auto-generated in the General
Alarm List (L1), and SUPERVISORY points are not generated into the Supervisory Monitor
List (L8).

Analog Pseudo Points Analog pseudo points exist as counters or timers in the 4010 system. SMPL delay and cycle
equations may be written referencing the user Analog pseudo points on the output side (for
delay/cycle operations). Each analog point may contain a value from 0-65,535 and the point is
considered ON when the value is non-zero. For delay and cycle purposes, the maximum
allowable value gives a real-time range of just over 18 hours. There are two analog pseudo
cards in the 4010 system - one reserved for system analogs, and one reserved for user points.

Continued on next page

B-17
Pseudo Points, Continued

4010 System Analog The 4010 system has one analog pseudo card reserved for system use at Card Address 20. It
Pseudos contains a total of 25 points. At present, only the first twelve are used but the remainder are
reserved for future expansion.

Table B-21: System Analog Pseudos

Point Label Description

A1 Fire Count Number of fire alarms active in system.

A2 Supervisory Number of supervisory alarms active in system.


Count

A3 Trouble Number of troubles active in system.


Count

A4 System Pulsed for one poll cycle during system startup.


Startup

A5 Almost Dirty Total number of devices that have an almost dirty status
Device Count (not necessarily a trouble).

A6 Dirty Device Total number of devices that are in Dirty Trouble.


Count

A7 Excessively Total number of devices that are in Excessively Dirty


Dirty Device Trouble.
Count

A8 Current Year

A9 Current
Month

A10 Current Day


of Month

A11 Current Hour

A12 Current
Minute

4010 User Analog The user analog pseudo card in the 4010 is at Card Address 21. It has 25 points available for
Pseudos specialized applications programming. The analog user pseudos can have custom labels
assigned to them.

Continued on next page

B-18
Pseudo Points, Continued

List Pseudo Points List pseudo points provide a convenient way to group points in any manner the user desires.
The 4010 contains two list pseudo cards - one reserved for the system and one for the user.
The status of the list is determined by counts which are maintained for the following states:

• Fire Count • Trouble Count

• Supervisory Count • Normal

• Open • Short

• Fire Ack • Limited

• Supervisory Ack • Trouble Ack

• On/Input • Disable

• Manual Control • On/Coding

The 4010 restricts the total number of points in any one list to 255. It also restricts the total
number of points available on any one list card to 500 (the total number of points in all lists on
one list card cannot exceed 500).

4010 System Lists The 4010 system reserves one list card at address 22 for system use. Currently, 12 of the 25
system lists are used by the 4010 application. All of these lists control application specific
operation of the 4010 panel. Some are auto-generated by the system as points are added and
may not be edited, while the remainder are filled by the user to activate pre-defined
applications. The system lists are shown in Table B-22.

Continued on next page

B-19
Pseudo Points, Continued

4010 System Lists

Table B-22: 4010 System List

Auto-generated by the panel and not editable. Contains all fire-alarm


General Alarm Monitor
L1 monitor points in the system plus the Manual Evac pseudo. User FIRE
Points
digital pseudos are not auto generated here.

Waterflow Alarm Monitor Auto-generated by the panel and not editable. Contains all waterflow-
L2
Zones type monitor points (WSO).

Sprinkler Supervisory Auto-generated by the panel and not editable. Contains all sprinkler-
L3
Monitor Zones type monitor points (SO).

Primary Elevator Recall Filled by the user. When in fire state, will activate the primary elevator
L4
Monitors recall function.

Alternate Elevator Recall Filled by the user. When in fire state, will activate the alternate elevator
L5
Monitors recall function.

Control Points, Off With Filled by the user. Output points turn on when L1 is in FIRE detect and
L6
Silence turn off with alarm silence.

Control Points, Off With Filled by the user. Output points turn on when L1 is in FIRE detect and
L7
Reset turn off with completed system reset.

Supervisory Monitor Auto-generated by the system - may be edited. Contains all


L8
Points Supervisory type monitor points.

Automatic Suppression Filled by the user. When in fire state, causes L12 to activate after
L9
Release Points automatic release delay timer expires.

Suppression Manual Filled by the user. When in the fire state, causes L 12 to activate after
L10
Release Points manual release delay timer expires.

Suppression Release Filled by the user. When in the supervisory state, causes the
L11
Abort Points suppression release sequence to abort.

Suppression Release Filled by the user. Activated by the panel when the suppression release
L12
Output Points algorithm completes.

4010 User Lists The user list pseudo card in the 4010 is at Card Address 23. It has 25 points available that may
be filled by the user for specialized applications. The user lists may have custom labels
assigned to them.

B-20
Appendix C.
Glossary

Introduction This appendix contains a glossary of common terms used throughout the manual.

Glossary Alarm - A warning of fire danger.

Alarm Signal - A signal indicating an emergency requiring immediate action, such as a signal
indicative of fire.

Alarm Verification - A feature to reduce unwanted alarms wherein smoke detectors must report
alarm conditions for a minimum period of time, or confirm alarm conditions within a given
time period, after being reset to be accepted as a valid alarm initiation signal.

Annunciator - A unit containing two or more indicating lamps, alpha-numeric displays, or


other equivalent means in which each indication provides status information about a circuit,
condition or location.

Authority Having Jurisdiction (AHJ) - The "authority having jurisdiction" is the organization,
office or individual responsible for approving equipment, an installation or a procedure.

Class A - A four wire method of connecting IDC or NAC that guarantees operation with a
single open conductor. See Style D (IDC) and Style Z (NAC).

Class B - A two wire method of connecting IDC or NAC that will cause a trouble indication
with an open circuit. See Style B (IDC) and Style Y (NAC).

Current Limited IDC State - A "current limited" state exists when an initiating device shunts a
resistor across the IDC.

Device Type - See Hardware Device Type.

Digital Alarm Communicator Transmitter (DACT) - A system component at the protected


premises to which initiating devices or groups of devices are connected. The DACT will seize
the connected telephone line, dial a preselected number to connect to a DACR, and transmit
signals indicating a status change of the initiating device.

Display - The visual representation of output data other than printed copy.

Evacuation - The withdrawal of occupants from a building.

Evacuation Signal - A distinctive signal intended to be recognized by the occupants as


requiring evacuation of the building.

FACP - Fire Alarm Control Panel. A system component that receives input from automatic and
manual fire alarm devices and may supply power to detection devices and transponders or off-
premises transmitters. The control panel may also provide transfer of power to the notification
appliances and transfer of conditions to relays or devices connected to the control panel. The
FACP can be a local fire alarm control panel or a master control panel.

Continued on next page

C-1
Glossary Fire/Supervisory - An IDC point type that is zone selectable. This point type will initiate a
"Supervisory Abnormal" condition at the FACP if a current limited state is detected.

Form C Contacts - A relay or switch configuration that provides access to both normally open
and normally closed dry contacts.

Hardware Device Type - The Hardware Device Type is assigned to each point in the 4010
system. The Hardware Device was formerly known as Device Type. Valid Hardware Device
Types include the Addressable Detector Base, Line Powered IAM, TrueAlarm Photoelectric
Detector and other types of hardware that are assigned as points in the system. Each hardware
device type is assigned a software point type (formerly point type) that defines system
operation regarding that point. There are specific software point types that can be assigned to
each hardware device type in the system.

Heat Detector - A device that detects abnormally high temperature or rate of temperature rise.

Initiating Device - A system component that originates transmission of a change of state


condition, such as a smoke detector, manual fire alarm box, supervisory switch etc.

Initiating Device Circuit (IDC) - A circuit to which automatic or manual initiating devices are
connected where the signal received does not identify the individual device operated.

Labeled - Equipment or materials to which has been attached a label, symbol or other
identifying mark of an organization acceptable to the "authority having jurisdiction" and
concerned with product evaluation, that maintains periodic inspection of production of labeled
equipment or materials and by whose labeling the manufacturer indicates compliance with
appropriate standards or performance in a specified manner.

Listed - Equipment or materials included in a list published by an organization acceptable to


the "authority having jurisdiction" and concerned with product evaluation, that maintains
periodic inspection of production of listed equipment or materials and whose listing states
either that the equipment or material meets appropriate standards or has been tested and found
suitable for use in a specified manner.

Logical State - The state of a point seen by the end user that is determined by point type and
physical state (alarm, trouble, etc.).

March Time Code - A notification code that consists of a 50% duty cycle pulse train. The
march time rate is specified in beats per minute (BPM). A 20 BPM March Time code consists
of 20 on/off cycles in one minute.

Municipal Master Box - An initiating device intended to send an alarm condition to the public
fire service communications center.

N2 COMMS - The communications protocol used by the 4010 to communicate from the CPU
to "slaves" in the system.

Notification Appliance - A fire alarm system component such as a bell, horn, strobe, etc.,
which provides an audible or visible output, or both.

Continued on next page

C-2
Glossary Notification Appliance Circuit (NAC) - A circuit or path directly connected to one or more
notification appliances.

Open Circuit State (IDC) - An open circuit is defined as the absence of the end of line resistor,
with or without a detector load.

Physical State - The control panels representation of the electrical state of a circuit or device
(open, short, etc.).

Point Type - See Software Point Type.

Protected Premises - The physical location protected by a fire alarm system.

Remote Master Box - An initiating device intended to send alarm, supervisory and trouble
signals to a remote location at which appropriate action is taken.

Smoke Detector - A device that detects visible or invisible particles of combustion.

Software Point Type - The software point type assigned to each hardware device in the system
defines the software operation associated with that hardware device. This was formerly
referred to as "point type." The software point type assigned to each hardware device defines
status reporting, including the default point banner that is displayed, printed or logged upon
point status changes. The hardware device type defines allowable software point types.
Examples of software point types include Smoke Detector, Verified Smoke Detector and Heat
Detector. The system will respond differently to certain status changes depending on the
software point type assigned.

Style B - A method of connection for IDC that will provide a trouble indication in the event of
an open circuit on the wiring loop. Also known as Class B.

Style C/Style E - An IDC point type. A trouble indication is provided if a short (+ to -) or


open circuit condition exists on the wiring loop. An alarm is initiated if a "current limited"
state exists. Style C is two wire, Style E is 4 wire.

Style D - A method of connecting initiating devices on IDCs that provides multiple signal
paths so that circuit operation is maintained with a single open circuit connection. A trouble
indication is provided in the event of an open circuit on the wiring loop. Also known as Class
A.

Style Y - A method of connecting notification appliances on NACs that provides a trouble


indication in the event of an open circuit on the wiring loop. Also known as Class B.

Style Z - A method of connecting notification appliances on NACs that provides multiple


signal paths so that circuit operation is maintained with a single open circuit connection. A
trouble indication is provided in the event of an open circuit on the wiring loop. Also known
as Class A.

Supervisory Signal - A signal indicating the need of action in connection with the fire
suppression system or equipment or with the maintenance features of related systems. (See
Fire/Supervisory point type.)

Continued on next page

C-3
Glossary Temporal Code - A three pulse coding pattern adopted by NFPA as a standard evacuation
pattern for audible notification. The pattern consists of three 1/2-second pulses, each pulse
separated by 1/2-second silence. Each group of three pulses is separated by 1.5 seconds of
silence.

VSMOKE - A point type that is selectable for an IDC. This point type will initiate an
immediate alarm from a contact closure Pull Station or Heat Detector, but will initiate the
Alarm Verification sequence (see definition above) for a current limited alarm. A point
configured as VSMOKE must NOT have any devices other than smoke detectors that initiate a
current limited alarm.

Zone - A defined area within the protected premises. A zone may define an area from which a
signal can be received, an area to which a signal can be sent, or an area in which a form of
control can be executed.

C-4
Appendix D.
Suppression Release

Introduction This appendix describes programming the 4010 panel as a suppression release panel. It con-
tains guidelines for suppression release, as well as wiring and programming instructions.

In this Chapter Refer to the page number listed in this table for information on a specific topic.

Topic See Page

Overview D-2

Wiring Suppression Devices D-6

Programming Device and Point Types for Suppression Devices D-7

Programming Suppression Release Options D-10

D-1
Overview

General Capabilities The 4010 is capable of controlling either a preaction/deluge sprinkler system or an agent
release extinguishing system. The functionality described in this section requires the 4010
panel be at revision level 3.01 or higher. The SFIO firmware must also be at revision level
3.01 or higher.
• The 4010 is capable of monitoring up to 10 hazards (each hazard is defined as a separate
area containing its own 4090-4005 releasing peripheral and solenoid).

• Each hazard area requires four to five Notification Appliance Circuits (NACs).
• One NAC controls Notification Appliance visuals. This circuit is ON when the
releasing output activates and OFF on system reset.
• One NAC controls Notification Appliance audibles. This circuit provides an audible
indication of the release sequence.
• One NAC provides a "warning circuit." This circuit may be wired to a bell or strobe
in the hazard area. It activates during the first stage of a releasing sequence and can
be used to alert system operators when the initial alarm occurs.
• One NAC provides power to the 4090-4005 releasing peripheral for the hazard area.
• One NAC provides power for "NYC Abort Investigation Apppliances." Note that this
NAC is only used when NYC Abort operation is selected. This NAC allows bells and
strobes to be tied to the same circuit. These devices activate when the NYC investi-
gation timer activates and turn off when the investigation timer reaches zero.

• The releasing peripheral activates its output (which attaches to the solenoid) only when
the designated IDNet initiating device(s) and the NAC connected to the release peripheral
are active at the same time. This prevents a malfunctioning input (either the IDNet input
or the NAC input) from triggering a release.
• When the 4010 is used to monitor two or more hazards, a 4009-9201 (120VAC) or 4009-
9301 (220/240 VAC) IDNet NAC Extender must be used to provide additional NACs.
When equipped with a 4009-9807 NAC Option Card, each 4009 IDNet can provide a
maximum of 8 additional NACs. Up to five 4009 IDNet NAC extenders can be connected
to a 4010 FACP, providing a maximum of 40 additional NACs.

• Releasing signaling patterns are as follows:


• Dual Detector Application. Temporal on first alarm (can also be configured as 20
beats per minute). Signal changes to 120 BPM on second alarm. When the releasing
appliances activate, the tone changes to Steady.
• Single Detector Application. When an initiating device in the hazard area activates,
the system does one of two things: If a delay timer is used, the NACs play a 120
BPM signal as the timer counts down. This changes to a Steady pattern when release
occurs. If no delay timer is used, the releasing appliances activate as soon as a single
detector enters an alarm state. In this case, the NACS sound a Steady tone pattern and
no distinct pre-discharge tone pattern plays.
• Alarm Triggered by Activation of Manual Release Switch. If a delay timer is used,
the system plays a 120 BPM signal on the NACs as the timer counts down. When the
releasing outputs activate, the signal changes to a steady tone.

Alarm Triggerd by Activation of Pressure Switch. The system will activate “steady-on” all
release NACs.

D-2
Overview, Continued

Hazard 2
Two NACs required for Hazard's
F
I
F
I
R
notification appliances, one for
R E
E
visuals (RELVIS) and one for
audibles (RELSIG)

Warning NAC
F
I
F
I
with RELWVIS
R
R
E E
Point Type NAC for Releasing
Peripheral (SUPREL)

IDNet Releasing
CAUTI O N
DISCONNECT

POWER
BEFORE
FIRE ALARM
Peripheral
PULL DOWN
SERVICING

(SUPREL)
- I DNET IN +
+IDNET IN -

4009 IDNet NAC EXTENDER


TM

Coil
SYSTEM ABOR T
Supervision
4009A IDNet NAC Module
Extender -- Provides
up to 8 additional NACs Solenoid
Abort
Switch with
Supervised
IAM

Hazard 1
IDNet Solenoid
FIRE ALARM

PULL DOWN
- I DN ET I N
+
+IDNET IN
-

Coil
Supervision
SYSTEM ABORT

Module
IDNet

F
Two NACs for
F
I
R
I
R
Hazard's Releasing
E E
Abort Switch with
notification Peripheral
Supervised IAM
appliances, one (SUPREL)
for visuals
(RELVIS) and
one for audibles
F
I
F
I
(RELSIG)
R R
E
E
Warning NAC
12:02:15pm
FIRE
**SYSTEM ISNORM AL**
M on 9-Feb-98
SYSTEM SYSTEM ALARM AC
TROUBLE SILENCED POWER
ALARM SUPERVISORY
FIREA LARM
CONTROL
with RELWVIS
Point Type
ALARM SUPV TROUBLE ALARM SYSTEM
ACK ACK ACK SILENCE RESET
CAUTION

DISCONNECT
POWER BEFORE
SERVICIN G

NAC for Releasing


4010 Fire Alarm Peripheral (SUPREL)
Control Panel

Figure D-1. 4010 Suppression Release

Applying Suppression The 4010 ships with a self-adhesive label that must be applied to the front door of the unit
Label to Front Cover when it is used as a suppression release system. This label (526-200 domestic/526-262 Cana-
dian) is used to indicate that the 4010 has been programmed to work as a releasing panel and
all releasing circuits must be disabled prior to servicing. This label can be applied to any area
of the front door

D-3
Overview, Continued

Flow Charts The following two figures illustrate the sequence of events which must occur prior to activat-
ing the 4010 releasing outputs.

Detect Manual
Alarm

Start Manual
Delay Tim er

Process NACs
RELW VIS = Steady
RELSIG = 120bpm

Delay
Y
Tim eout?

N Process NACs
RELVIS = Steady
RELSIG = Steady
Release = ON
Decrem ent Tim er

Done

Figure D-2. Manual Alarm Sequence

Continued on next page

D-4
Overview, Continued

Flow Charts

Autom atic Alarm

Alarm >=
N Trip Count? Y

RELSIG = 120bpm
RELW VIS = Steady
Start Autom atic
Delay Tim er
RELSIG = Tem poral
RELW VIS = Steady

Y N
Abort?
Y

Y N
Abort Switch Autom atic
Pressed? Tim e Out?

RELSIG = Steady
Load RELW VIS = Steady Decrem ent Tim er
Abort Release = ON
Tim eout

Abort switch N Done


Abort Tim eout?
pressed? Y

Decrem ent Tim er

Figure D-3. Automatic Alarm Sequence

D-5
Wiring Suppression Devices

Wiring Initiating Devices The 4010 uses Simplex IDNet initiating devices to detect the presence of an alarm condition in
a suppression release hazard area. Non-IDNet devices may also be used, but require the use of
a Simplex Zone Adapter Module (ZAM) or Individual Addressable Module (IAM) to connect
the non-IDNet device to the IDNet channel. Refer to 842-058 Field Wiring Diagram for addi-
tional information.

All IDNet initiating devices wire to the 4010's IDNet channel in the same manner. Refer to
"IDNet Wiring" in Chapter 3 of this manual and Field Wiring Diagram 842-058 for informa-
tion on wiring IDNet devices to the panel. Refer to the individual instruction sheets accompa-
nying the device.

Wiring Notification Each suppression release hazard area protected by the 4010 requires four NACs (audible,
Appliances visual, warning, and power for suppression peripheral).

The 4010 includes four NACs. Information on wiring 4010 NACs is contained in Chapter 3 of
this manual and Field Wiring Diagram 842-058.

4009 IDNet NAC extenders can be used to supply additional NACs (up to 40 total) for use
with suppression applications. Information on wiring notification appliances to the 4009
IDNet NAC extenders is contained in Simplex document 574-181.

Note: The signaling patterns used by the audible NACs are not user selectable, with the excep-
tion of the first stage NAC

Wiring Manual Release Manual release switches and abort switches are not IDNet devices and cannot be wired directly
and Abort Switches to the IDNet channel. Use either a Zone Adapter Module (ZAM) or Individual Addressable
Module (IAM) to wire these switches to the IDNet channel. All manual release and abort
switches must be UL and ULC listed and their function must be marked accordingly.

Refer to Field Wiring Diagram 842-058 for specific information on wiring these devices.

Wiring Releasing Each hazard area requires a 4090-4005 IDNet releasing peripheral. This peripheral controls
Peripheral the operation of the solenoid that is connected to the releasing agent storage tanks or sprinkler
control valve. It contains three sets of terminal connections - one control connection from the
IDNet, a power input from either a 4009 IDNet4009 or 4010 NAC, and an output to the coil
supervision module and solenoid.
Complete setup, mounting, and wiring instructions for the 4090-4005 releasing peripheral are
located in Simplex Document 574-385. Also refer to Field Wiring Diagram 842-058.

D-6
Programming Device and Point Types for Suppression Devices

Overview Programming suppression points is typically a two-part process.


• Part One involves using the Quick CFIG programming utility to automatically add the
devices to the job. Quick CFIG scans the IDNet channel identifies new devices, associ-
ates them with an IDNet identifier (M1-1, for example), and assigns the appropriate
device type (SMOKE, HEAT, etc.) to the device.
Refer to Chapter 4 of this manual for information on running the Quick CFIG utility.

• Part Two involves using the front panel interface to assign the appropriate point type and
hazard area to the device. The point type defines the specific operation of the point. Table
D-1 shows the point types that must be assigned to the devices.
Refer to Chapter 6 of this manual for information on defining point types. Refer to the
next section of this appendix for information on assigning points to a hazard area.

Table D-1Suppression Device and Point Types

Allowed Device Required Point


Device Operation
Types Type

Initiating Devices HEAT, ION, Short/Abnormal = Fire


for Suppression PHOTO,
SUPDET Open = Trouble
Release Detec- MAZAM,
tors MBZAM, IAM Points go in Hazard's automatic release point list.

RELVIS is on when releasing output activates; off


on reset.
RELVIS RELSIG is 20 BPM on first alarm, 120 BPM on
RELSIG second alarm (delay timers must be active, not 0),
NAC Appliances SIGA, SIGB RELWVIS steady on release, and off on silence.
RELISIG RELWVIS is on when an alarm occurs in hazard
area, off on reset.
RELISIG. See description of NYC Abort later in
this manual.

Suppression
Release
RELEASE SUPREL On-steady for release
Peripheral
(IDNet)

MAZAM, Abnormal = Fire


Manual Release
MBZAM, SUPDUMP Short/Open = Trouble
Switches
ADRPUL, IAM Points go in Hazard's manual release point list.

MAZAM, Short/Abnormal = Fire


Manual Release
MBZAM, SSDUMP Open = Trouble
Switches
ADRPUL, IAM Points go in Hazard's manual release point list.

Continued on next page

D-7
Programming Device and Point Types for Suppression Devices, Continued

Table D- 1. Suppression Device and Point Types (continued)

Allowed Device Required Point


Device Operation
Types Type

Abnormal = Supervisory
MAZAM, Short/Open = Trouble
Abort Switches SUPABRT
MBZAM, IAM Points go in specified hazard area's list of abort
points.

Short/Abnormal = Supervisory
MAZAM, Open = Trouble
Abort Switches SSABORT
MBZAM, IAM Points go in specified hazard area’s list of abort
points.

Short/Open = Trouble
Abnormal = Fire
SUPPRES
Points go in specified hazard area’s list of
Pressure MAZAM, pressure monitor points.
Switches MBZAM, IAM Short/Abnormal = Fire
Open = Trouble
SSPRES
Points go in specified hazard area’s list of
pressure monitor points.

Assigning a Point's Each point's hazard area is initially set to 0. Points associated with a hazard area of 0 will not
Hazard Area function properly. You must assign a hazard area to the point in order to assure function as a
suppression release zone. Follow these steps to assign a specific hazard area to each suppres-
sion point.

1. Login at Access Level 4.

2. Press <MENU> and then press <NEXT> until <PROGRAMMING> appears. Press
<ENTER>. Press <ENTER> again to confirm that you want to enter programming mode.
3. Press <NEXT> until <CONFIGURE POINTS> appears and then press <ENTER>.
4. Do one of the following, depending on whether you are programming an IDNet device, a
ZAM or IAM, or a NAC.
IDNet Point. Suppression release systems can have two types of IDNet points - IDNet
initiating devices (smoke and heat detectors, for example) and the 4090-4005 IDNet sup-
pression release peripheral. Follow these instructions to edit the hazard area for these
devices.
a. Press <NEXT> until <TRUEALARM> is displayed and then press ENTER.
b. Press <NEXT> until <EDIT TRUEALARM POINT> is displayed and then press
ENTER.
c. Press <NEXT> or PREV until the name of the appropriate point is displayed. Press
ENTER.

Continued on next page

D-8
Programming Device and Point Types for Suppression Devices, Continued

Assigning a Point's d. Press <NEXT> until <SELECT HAZARD AREA> is defined and then press
Hazard Area ENTER.
e. Press <NEXT> until the appropriate hazard area is displayed and then press ENTER.
f. Press ENTER to confirm that the assigned hazard area is correct.
g. Press EXIT/CLEAR to back out of the menus if necessary.

ZAM/IAM. If the point you are programming is a conventional detector, manual release
station, or abort switch, you need to program the ZAM or IAM to which the point is wired.
Follow these steps.

a. Press <NEXT> until <ZAMS/IAMS/RIAMS> is displayed and then press ENTER.


b. Press <NEXT> until <EDIT IDNET POINT> is displayed and then press ENTER.
c. Press <NEXT> or PREV until the name of the appropriate point is displayed. Press
ENTER.
d. Press <NEXT> until <SELECT HAZARD AREA> is defined and then press
ENTER.
e. Press <NEXT> until the appropriate hazard area is displayed and then press ENTER.
f. Press ENTER to confirm that the assigned hazard area is correct.
g. Press EXIT/CLEAR to back out of the menus if necessary.
Notification Appliances. Follow these steps:

a. Press <NEXT> until <NACS> is displayed and then press ENTER.

b. Press <NEXT> or <PREV> until the circuit whose hazard area you want to assign is
displayed. Press ENTER.

c. Press <NEXT> until <SELECT HAZARD AREA> is defined and then press
ENTER.

d. Press <NEXT> until the appropriate hazard area is displayed and then press ENTER.

e. Press ENTER to confirm that the assigned hazard area is correct.

f. Press EXIT/CLEAR to back out of the menus if necessary.

D-9
Programming Suppression Release Options

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISIDICTION, AND


OTHER INVOLVED PARTIES

This product incorporates field programmable software. In order for the product to comply with
the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems,
UL 864, certain programming features or options must be limited to specific values or not
used at all as indicated below.

Program feature Permitted in UL 864? Possible settings Settings permitted in UL 864


or option (Y/N)

Abort Operation Yes Greater, IRI, Greater, Immediate,


Reload, 10 seconds
Immediate, 10
seconds, NYC

Step 1. Enable Use the following steps to enable the suppression release system options.
Suppression Release
System Options 1. Press <MENU>.
2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed. Press
<ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm
Operation mode.

Please Wait...
Fire Alarm Operation Suspended

3. Press <ENTER> to confirm that you want to enter Programming Mode.

4. Press <NEXT> or <PREVIOUS> until <SYSTEM OPTIONS> is displayed and then


press <ENTER>.
5. Press <NEXT> or <PREVIOUS> until <SUPPRESSION RELEASE> is displayed and
then press <ENTER>. A display similar to the following appears.

<ENTER> to Accept <NEXT/PREV to Scroll


Suppression Release: [ON/OFF] Status

6. Press <ENTER> to continue. A prompt similar to the following appears. By default, sup-
pression release is set to OFF.

Suppression Release:
New: [ON] Current: [OFF]

7. Press <NEXT> to toggle the status from OFF to ON. Press <ENTER> to continue. A
confirmation prompt appears. Press <ENTER> again to confirm the ON selection.

D-10
Programming Suppression Release Options, Continued

Step 2. Set Audible The next prompt is for the Audible Output Option, which allows you to determine the pattern
Output Option of tones that play when a first stage alarm occurs.
1. Press <NEXT> to see the next prompt. A display similar to the following appears.

<ENTER> to Accept <NEXT/PREV to Scroll


Suppression Release: [Audible Output]

Press <ENTER> to continue. Use the <NEXT> and <PREV> keys to scroll through the avail-
able options (TEMPORAL, STEADY, SLOW MARCH, FAST MARCH). Press <ENTER> to
continue when the appropriate choice is selected. A confirmation prompt appears. Press
<ENTER> again to confirm the new choice.

Step 3. Set Options for The next prompt allows you to set various options for each specific hazard area.
Hazard Area
1. Press <NEXT> to see the next prompt. A display similar to the following appears.

<ENTER> to Accept <NEXT/PREV> to Scroll


Suppression Release: [Hazard Area 1]

2. Press <NEXT> or <PREV> to scroll to the hazard area whose options you want to pro-
gram and then press <ENTER>.
The first prompt, shown below, asks whether the area will use dual detectors to determine
whether an alarm condition exists in the hazard area. If you select NO, a single activated
detector in the hazard area triggers agent release. If you select YES, two activated detec-
tors are required to trigger release.

<ENTER> to Accept <NEXT/PREV to Scroll


Suppression Release: [Dual Detector]

3. Press ENTER to continue. The prompt shows the currently selected state (On or OFF) for
the option. Press NEXT to toggle between these states. Press Enter when the appropriate
choice is selected. Press ENTER again to confirm the selection.

Step 4. Set Detector 1 Press <NEXT> to see the next option for the selected hazard area. A display similar to the
Delay following appears.

<ENTER> to Accept <NEXT/PREV to Scroll


Suppression Release: [Detector Delay]

2. Press ENTER to continue. The next prompt asks you to specify the value of the detector
delay. This is the number of seconds of delay that occurs between activation of the detec-
tor(s) and release of the agent.

Set Detector Delay for 0-60 Secs


New: [30] Current: 30 Secs

D-11
Programming Suppression Release Options, Continued

3. Press NEXT or PREV to scroll the timer value. Press ENTER when the appropriate value
is displayed. Press ENTER again to confirm the selection.

Step 5. Set Manual Delay 1 Press <NEXT> to see the next option for the selected hazard area. A display similar to the
following appears.

<ENTER> to Accept <NEXT/PREV> to Scroll


Hazard Area 1: [Manual Delay]

2. Press ENTER to continue. The next prompt asks you to specify the manual delay. This is
the amount of delay that occurs between activation of a manual release station and release
of the agent.

Set Manual Delay for 0-30 Secs


New: [10] Current: 10 Secs

3. Press NEXT or PREV to scroll the timer value. Press ENTER when the appropriate value
is displayed. Press ENTER again to confirm the selection.

Step 6. Set Cutout Timer 1 Press <NEXT> to see the next option for the selected hazard area. A display similar to the
following appears.

<ENTER> to Accept <NEXT/PREV> to Scroll


Hazard Area 1: [Cutout Timer]

2. Press ENTER to continue. The next prompt asks you to specify the cutout timer. The cut-
out timer allows you to specify the amount of time that the releasing peripheral provides
power to the solenoid. When the timer expires, the releasing peripheral "cuts out," which
stops the water flow or release of the extinguishing agent. This option is typically used
with deluge systems and does not work with all releasing systems or releasing devices.
(Some devices discharge their entire supply of agent when fired so this option would have
no effect on operation.) A selection of 0 for this option means the releasing peripheral
does not cut out and remains on until the system is reset.

Set Cutout Timer for 0-2400 Secs


New: [00] Current: 00 Secs

3. Press NEXT or PREV to scroll the cutout timer value. Press ENTER when the appropri-
ate value is displayed. Press ENTER again to confirm the selection.
Continued on next page

D-12
Programming Suppression Release Options, Continued

Step 7. Set Release 1 Press <NEXT> to see the next option for the selected hazard area. A display similar to the
Abort Operation following appears.

<ENTER> to Accept <NEXT/PREV> to Scroll


Hazard Area 1: [Abort Operation]

2. Press ENTER to continue. The next prompt asks you to specify the abort operation.
3. Press NEXT or PREV to scroll through the following set of options.
• Greater. Releasing outputs do not activate as long as the abort switch is pressed.
When the abort switch is released, the delay used is whichever of the following is
greater - the remaining time left on the Automatic Release Delay timer or 10 seconds.
• IRI. Releasing outputs do not activate as long as the abort switch is pressed and one
automatic alarm is present. If a second alarm occurs while the abort switch is pressed,
the Automatic Release Timer begins counting down from its programmed value, stop-
ping with 10 seconds remaining. When the abort switch is released, the panel contin-
ues the Automatic Release Timer countdown from its remaining value and activates
the release outputs when the timer reaches zero. If the abort switch is pressed after
the second alarm occurs, it has no effect. This option does not comply with UL 864.
• Reload. Releasing outputs do not activate as long as the abort switch is pressed.
Releasing the abort switch resets the Automatic Release Timer to the original value.
This option does not comply with UL 864.
• Immediate. Releasing outputs do not activate as long as the abort switch is pressed.
If a confirmed alarm exists, the releasing peripheral activates the solenoid immedi-
ately upon release of the abort switch.
• 10 Seconds. Releasing outputs do not activate as long as the abort switch is
pressed. When the abort switch is released, the panel starts a 10 second timer and
activates the releasing outputs when the timer expires.
• NYC. Releasing outputs do not activate as long as the abort switch is pressed.
Releasing the abort switch causes the following to occur:
• Warning visual notification appliances associated with the hazard turn off
• Audible notification appliances associated with the hazard turn off.
• NAC wired to NAC circuit with RELISIG point type "NYC Investigative
NACs" turns on to indicate that the investigation phase is occurring.
• 90 second investigative timer starts.
When the investigative timer reaches zero, the following occurs:

• Warning visual notification appliances associated with the hazard turn on


• Audible notification appliances associated with the hazard turn off.
• NAC wired to NAC with RELISIG point type “NYC Investigative NAC” turns
off to indicate that the investigation phase has ended.

Continued on next page

D-13
Programming Suppression Release Options, Continued

Subsequently pressing and releasing the abort switch repeats the process described above, until
the Automatic Release Timer reaches zero and the releasing outputs activate. Pressing and
releasing the abort switch while the investigation timer is counting down has no effect. This
option does not comply with UL 864.

Step 7. Set Release 4. Press ENTER when the appropriate value is displayed. Press ENTER again to confirm the
Abort Operation selection. To program the options for another hazard area, press the EXIT key and then
press the NEXT or PREV keys to select another hazard area.

D-14
re-installing 2-5
removing 2-3
24 I/O card points B-11
checkout 3-12
24-Point I/O Card 1-7
City Circuit 7-13
24-Point I/O points 6-14
City Circuit Card 1-5
COMP CNST qualifier 8-20
A
conduit entrances 2-3
abnormal conditions 11-2 Configure Points menu 6-2
AC power 3-6 configuring analog pseudo points 6-12–6-13
Accept Default Options 4-6 configuring digital pseudo points 6-11
Acceptance Testing 3-12 configuring NAC points 6-9
access levels 1-11 configuring relay points 6-9
acknowledging conditions 11-3 Control/View Points menu 11-7
Active Status Reminder 7-4 crash codes 10-10
adding cards 5-3–5-4 Custom Control 8-2
adding IDNet points 6-3 ALL qualifier 8-20
adding TrueAlarm points 6-3–6-4 AND operator 8-10
adding ZAM/IAM/RIAM points 6-6 ANY qualifier 8-20
Alarm Acknowledge 1-9 COMP CNST qualifier 8-20
Alarm Cut-Out Timer 7-6 DELAY CNST qualifier 8-20
Alarm Silence 1-9 equations 8-9
ALL qualifier 8-20 examples 8-24
analog pseudo points B-17 FIRE ACK qualifier 8-17
AND operator 8-10 FIRE qualifier 8-16
ANY qualifier 8-20 input opcodes 8-3
arrow keys 1-10 input operators 8-4
Auto Detect New Hardware 4-4 menus 8-7
auxiliary relays 3-9 NOT operator 8-14
OFF qualifier 8-19
B ON/CODE qualifier 8-19
back box mounting OR operator 8-11
semi-flush 2-4 output opcodes 8-5
surface 2-4 relational operators 8-4
Battery Meter Module 1-6 starting 8-7
battery wiring 3-7 SUPV ACK qualifier 8-18
SUPV qualifier 8-17
C TBL ACK qualifier 8-19
TBL qualifier 8-18
card addresses 5-2 Custom Labels 11-10
cards
adding 5-3–5-4 D
addresses 5-2
deleting 5-4 DACT Cards 1-6
modifying 5-5 DELAY CNST qualifier 8-20
CFIG deleting cards 5-4
properties 9-2 deleting TrueAlarm points 6-5
restore 9-3 deleting ZAM/IAM/RIAM points 6-8
saving 9-3 Depleted Battery Cut-Out 7-11
CFIG properties 9-2 device types
chassis monitor A-3

I-1
TrueAlarm A-2 LCD Remote Annunciator 1-7
diagnostics 10-2 LEDs 6-19
comm 10-3 lists 6-17
IDNet 10-3–10-4 adding to 6-18
IDNet Earth Fault Search 10-4 deleting from 6-18
network 10-4–10-5 logging in and out 1-12
digital pseudo points B-13
Disable/Enable button 1-10 M
disabling points 11-9 maintenance 3-13
Display 1st Alarm 7-15 Master Controller points B-3
Door Drop on AC Loss 7-8 Menu button 1-10
Door Drop on Alarm 7-7 menu structure 1-13
Dual RS-232 Card 1-6 Modem card points B-8
modifying cards 5-5
E Monitor device types A-3
Edit System Options 4-7 Monitor point types A-4
editing ZAM/IAM/RIAM points 6-6–6-7 mounting
enabling points 11-9 back boxes 2-4
Enter key 1-10 semi-flush 2-4
environmental specifications 1-4
Exit/Clear key 1-10 N
Expansion Power 7-14 NAC card points B-4
NAC points
F configuring 6-9
FIRE ACK qualifier 8-17 NACs
FIRE qualifier 8-16 operation 7-9
Function button 1-10 wiring 3-4
Function Control menu 11-12 Network card points B-10
Network Cards 1-7
G Next key 1-10
Non-Power Limited wiring 3-2
guidelines for installation 2-2
NOT operator 8-14
H
O
hardware points B-2
OFF qualifier 8-19
Historical Logs 11-5
ON/CODE qualifier 8-19
OR operator 8-11
I
Overview 1-1
IDNet card points B-6
IDNet NAC Extender 1-7 P
IDNet points
point types
adding 6-3
Monitor A-4
IDNet wiring 3-5
Relay A-6
Immediate AC Fail 7-15
Signal A-5
installation guidelines 2-2
TrueAlert Non-Addressable A-8
points
L
24 I/O card B-11
LCD card points B-12 24-Point I/O 6-14

I-2
adding to lists 6-18 SFI/O board 1-3
controlling 11-7 Signal point types A-5
deleting from lists 6-18 Silence/Reset Inhibit 7-5
disabling 11-9 silencing alarms 11-3
enabling 11-9 Single Station option 7-15
IDNet 6-3 Software Revision menu 9-2
IDNet card B-6 Stagger Start AHUs 7-12
LCD card B-12 standards and codes 2-2
master controller B-3 Supervisory Acknowledge 1-9
Modem card B-8 SUPV 8-17
NAC 6-9 SUPV ACK qualifier 8-18
NAC card B-4 SUPV qualifier 8-17
Network card B-10 surface mounting back boxes 2-4
Power Supply card B-5 System Options menu 7-2
relay 6-9 System Reset 1-9
RS-232 card B-8 system reset 11-4
SDACT B-9
TrueAlarm 6-3–6-5 T
viewing 11-7 TBL ACK qualifier 8-19
ZAM/IAM/RIAM 6-6 TBL qualifier 8-18
Power Limited wiring 3-2 technical support 10-1
power supply 1-4 Time/Date Format 7-3
Power Supply card points B-5 time/date setting 11-13
power-up 3-10 Trouble Acknowledge 1-9
Previous key 1-10 TrueAlarm device types A-2
pseudo points TrueAlarm points
analog 6-12–6-13, B-17 adding 6-3–6-4
digital 6-11, B-13 deleting 6-5
TrueAlert Non-Addressable Horn operation 7-10
Q TrueAlert Non-Addressable point types A-8
Quick CFIG TrueTest 10-8
cautions and warnings 4-2
U
R user interface 1-9
Reconfigure All Hardware 4-3 User-Defined Switches 6-19
Recurring Trouble Filter 7-16
Relay point types A-6 V
relay points Voice Control Panel 1-7
configuring 6-9
Restore CFIG 9-3 W
Restore Factory CFIG 4-5
RS-232 card points B-8 Walk Test 10-6
RS-232/Service Modem Card 1-6 Wheelock 7-16
wiring
S AC power 3-6
auxiliary relays 3-9
Save CFIG 4-9, 9-3 batteries 3-7
SDACT card points B-9 IDNet 3-5
semi-flush mounting back boxes 2-4 Non-Power Limited 3-2
Set Time/Date 11-13

I-3
Power Limited 3-2
wiring NACs 3-4

Z
ZAM/IAM/RIAM points
adding 6-6
deleting 6-8
editing 6-6–6-7

I-4
574-052
Rev. S

© 2006-2010 SimplexGrinnell LP. Specifications and other information were current as of publication and are subject to change without notice.

You might also like