Fire Protection System Boq

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 94

PROJECT : IIIT DATE 15-Jun-23

LOCATION : HYDERABAD REVISION


DOCUMENT :FIRE PROTECTION SYSTEM SUMMARY STATUS TENDER
SUPPLY ERECTION
S.NO DESCRIPTION TOTAL
AMOUNT INR AMOUNT INR
1 SPRINKLER SYSTEM (ACADEMIC BLOCK) - - -
2 INTERNAL & EXTERNAL ( ACADEMIC BLOCK) - - -
3 INTERNAL & EXTERNAL ( SRIC BLOCK) - - -
4 PUMP ROOM - - -
5 LIAISING -
6 ADDRESSABLE FIRE ALARM SYSTEM BOQ (FA-NAB) - - -
7 PUBLIC ADDRESS SYSTEM BOQ(PA-NAB) - - -
8 SIGNAGE SYSTEM BOQ(NAB) - - -
9 FIRE EXTINGUISHER SYSTEM BOQ(FE-NAB) - - -
10 ADDRESSABLE FIRE ALARM SYSTEM BOQ(FA-SRIC) - - -
11 PUBLIC ADDRESS SYSTEM BOQ(PA-SRIC) - - -
12 SIGNAGE SYSTEM BOQ(SRIC) - - -
13 FIRE EXTINGUISHER SYSTEM BOQ(FE-SRIC) - - -
TOTAL WITHOUT TAX - - -
GST @18% -
GRAND TOTAL -
DOCUMENT TITLE : FIRE PROTECTION SYSTEM MAKE OF MATERIALS

Sl.No DESCRIPTION

A FIRE PROTECTION SYSTEM


1 PIPES
2 SOCKET OR THREADED FITTINGS
3 GROOVED FITTINGS
4 PAINT
5 SUPPORTS
6 SPRINKLER BULB
7 FLEXIBLE DROP
8 BALL VALVE
9 BUTTERFLY VALVE
10 FLOW SWITCH
11 FIRE SEALANT
12 PUMPS & MOTOR
13 SLUICE VALVE
14 NON RETURN VALVE
15 Y STRAINER
16 SINGLE HYDRANT VALVE
17 RRL HOSE
18 BRANCH PIPE NOZZLE
19 HOSE CABINET
20 HOSE REEL DRUM
21 FOUR & TWO WAY FIREBRIGADE INLET
22 SS EXPANSION BELLOWS
23 CABELS
24 CABLE TRAY
STEM MAKE OF MATERIALS

APPROVED MAKES

JINDAL STAR TATA


VIJAY CYCLE & STEEL INDUSTRIES(VS) B.M METERS PRIVATE LIMITED (B&M)
NEW NVR
ASIAN BERGER
HITECH RIPPLE
TYCO VIKING
TYCO VIKING
SANT NVR
SANT NVR
SYSTEM SENSOR HONEYWELL
3M HILTI
LUBI KIRLOSKAR
SANT NVR
SANT NVR
SANT NVR
NEWAGE MINIMAX
NEWAGE MINIMAX
NEWAGE MINIMAX
NEWAGE MINIMAX
NEWAGE MINIMAX
NEWAGE MINIMAX
EASYFLEX CORI
POLYCAB VARSHA
PROFAB TECHNOFAB
NEW
NATIONAL
NIPPON
HILTI
VICTUALIC
VICTUALIC
ZOLOTO
AUDCO
POTER

AUDCO
AUDCO
UNIVERSAL
SAFEGUARD
SAFEGUARD
SAFEGUARD
SAFEGUARD / FABRICATED
SAFEGUARD
SAFEGUARD
DUNLOP
KEI
PROJECT : IIIT
LOCATION : HYDERABAD
DOCUMENT : SPRINKLER SYSTEM- ACADAMIC BUILDING
SI.No Descriptions Unit

Note:
Vendor to visit the site & quote accordingly
All the paints used for piping, fittings, valves and accessories shall
have VOC level below 250 g/ltrs. VOC level for any sealants shall be
less than 250 g/ltrs and for rubber lining 850g/ltrs.

Supplying, installing,hydraulic testing and commissioning of Heavy


grade MS Pipes confirming to IS :1239 part - I with malleable specials
confirming to IS:1239 part - II, such as Tees, elbows, check nuts,
unions, flanges, nipples etc. Including cutting, fixing in / on walls / on
Floors, ceiling by using suitable supports such as MS
1 channels ,angles,flats,rods as required at site with anchor
fasteners,clamps,threaded rods,nuts,bolts,washers etc...complete.
Painting the exposed with one coat of metal zinc chromate primer
with two coats of synthetic enamel paint of approved colour / shade
etc., complete.The pipe fittings shall be Socket type up to 50 mm dia
and Weldable type for 65 mm dia & above.

a 25mm nominal dia Rmt


b 32mm nominal dia Rmt
c 40mm nominal dia Rmt
d 50mm nominal dia Rmt
e 65mm nominal dia Rmt
f 80mm nominal dia Rmt
g 100mm nominal dia Rmt
h 150mm nominal dia Rmt
i 150mm nominal dia - Sprinkler Riser Pipes Rmt
j 80mm nominal dia - Drain Riser Pipes Rmt

Supply testing and commissioning of 15 mm gunmetal/chrome


2 quartzoid bulb, standard response sprinkler heads suitable for 68 deg.
C, K 80
a) Pendent- 68deg C Nos
b) Upright - 68deg C Nos

Dial type pressure guage for (0-16 Kg/cm2) with necessary nipple &
3 other fittings, mounting arrangements and with a 15 mm ball valve Nos

Supply, Installation, Testing & Commissioning of 25mm Ball valve


4 with sight glass for Sprinkler test line Nos

Supply, Installation, Testing & Commissioning of 50mm Ball valve for


5 Sprinkler drain line Nos

Supply, Installation, Testing & Commissioning of Flow Switches with


6 two NO and two NC contacts with necessary nipple & other fittings, Nos
Flow switch shall be suitable for 150 dia

Providing and fixing C.I. butterfly valves to IS:13095 with operating


7 lever, bolts, nuts, washers and companion flanges complete. (PN-16)

a 50mm dia Nos


b 80mm dia Nos
c 100mm dia Nos
d 150mm dia Nos
Supply & fixing of approved type rosette plates ( Recessed type, in
8 two piece) for Sprinklers below false ceiling area.
The Rosette shall be fabricated by M.S. plate of 2mm thick and the
a finish shall be powder coated and color shall be as approved by Nos
architects / clients.

Stainless steel corrugated flexible pipe(hose) for dropping sprinklers


below false ceiling, pipe shall be UL Listed, 16 bar pressure rating and
9 1800 mm long 25 mm dia with union / reducer collar, clamps etc. as Nos
required. (BRAIDED)

Stainless steel corrugated flexible pipe(hose) for dropping sprinklers


below false ceiling, pipe shall be UL Listed, 16 bar pressure rating and
10 1500 mm long 25 mm dia with union / reducer collar, clamps etc. as Nos
required. (BRAIDED)

Stainless steel corrugated flexible pipe(hose) for dropping sprinklers


below false ceiling, pipe shall be UL Listed, 16 bar pressure rating and
11 1000 mm long 25 mm dia with union / reducer collar, clamps etc. as Nos
required.(BRAIDED)

Testing & commissioning of sprinkler system 24hr at 12 bar pressure


12 for both existing and new pipes Lot

Cutting , removing, rerouting / providing dummy of existing fire


fighting pipes, sizes from 25 to 150mm dia from various places or
reroute the existing pipes as per the site requirement ( IDF/SERVER
13 ROOM/UPS & BATTERY ROOM) Lot
Vendor to visit the site, analyse the quantum of works involved &
quote accordingly and also refer the layout

14 Supply ,installation, testing and commissioning of 25mm diameter Nos


FORGED BRASS AIR RELEASE VALVES PN-1.6 BODY - FORGED BRASS 25 mm

Supplying, installing, testing and commissioning of Gun metal chrome


15 finished 25mm dia Ball valves with fittings of screwed end type. Nos

TOTAL

AMC Cost
Charges for Comprehensive Annual Maintenance Charges for a
period of 5 years from the end of Guarantee period.
I year Lot
II year Lot
III year Lot
IV year Lot
V year Lot
PROJECT : IIIT
LOCATION : HYDERABAD
DOCUMENT :- CONTROLLED FOR INTERNAL HYDRANT SYSTEM - ACADAMIC BUILDING
EXTER
SL.No DESCRIPTION GF 1F 2F
.

Supplying, erecting and commissioning of Landing Hydrants comprising of the following in the Fire
duct;

Under Ground piping - Supply, erection, testing and commissioning of MS PIPES C CLASS pipes
conforming to IS 3589 for 200NB & above and IS 1239 for 150NB including cutting the pipes to correct
length, providing and welding flanges to pipe, etc as per specifications (rate including Anti-corrosive
Coating & Wrapping and heavy class forged fittings of IS standards) of the following diameters. brackets
testing to 13.5 Kg/Sq.cm hydraulic pressure after instalation,complete as per specification. Rates shall
1
be inclusive of 10% radiograph test complete as per specifications of the following diameters and all
necessary supports.
Note
Vendor to consider The pipe fittings shall be threaded up to 50 mm dia and Welded type for 65 mm dia
& above.

150mmdia - Existing System to Proposed Riser connection


Above Ground piping - Supplying, installing,hydroulic testing and commissioning of Heavy grade MS
Pipes confirming to IS :1239 part - I with malleable specials confirming to IS:1239 part - II, such as Tees,
elbows, check nuts, unions, flanges, nipples etc. Including cutting, Welding, fixing in / on walls / on
Floors, ceiling by using suitable supports such as MS channels ,angles,flats, threaded rods as required at
site with anchor fasteners,clamps,threaded rods,nuts,bolts,washers etc...complete. Painting the
exposed with one coat of metal zinc chromate primer with two coats of synthetic enamel paint of
approved colour / shade etc., complete.The pipe shall be socket weld type up to 50 mm dia and butt
weld type for 65 mm dia& above. hydro pressure testing to 13.8 Kg/Sq.cm hydraulic pressure after
instalation,complete as per specification. Rates shall be inclusive of 10% radiograph test complete as per
2 specifications of the following diameters and all necessary supports.
Note
Vendor to consider The pipe fittings shall be Socket up to 50 mm dia and Welded type for 65 mm dia &
above.

150mmdia - Riser 12 9 9
150mmdia (From Pump room to Risers) 580
100mmdia
80mmdia 18 156 156 156
25mmdia 4 4 4
Supply, installation, testing and commissioning of electrically driven pump set as per specification.
Motor TEFC type, 2900 RPM 415 V, 50 cycles, 3 phase, class ‘F’ insulation, IP 54 protection, 10 HP
starting on DOL. The Pump shall be horizontal end suction top discharge. The pump shall be weather
proof type. The pump shall have cast iron casing, Cast iron impeller, steel shaft with common base
3 frame capable of discharging 54 m3/hour at 45 meter head as per ISI Standard (rate is inclusive of
control panel, Cables, PS, PG and supports)

Supplying, Installing, testing and commissioning CAST IRON BUTTERFLY VALVE WAFER TYPE LEVER
4
OPERATED PN-1.6 WITH INTEGRALLY MOULDED LINER OF NITRLE OR EPDM, S.S. (CF-8) DISC, S.S STEM

150 NB 6
100 NB
Supplying and installation of CAST IRON NON RETURN VALVE FLANGED PN-1.6 S.S HING PIN, RUBBER
5
SEATED, DRILLING AS PER : IS-1538
150 NB
Supplying and installation of CAST IRON Y-TYPE STRAINERS (Flanged)PN-1.6 BODY,-C.I., SCREEN
6 STAINLESS STEEL
150 NB
Supplying, installing, testing and commissioning of Gun metal chrome finished 25mm dia Ball valves
7 4 4 4
with fittings of screwed end type.
Supply installation ,testing and commissioning of Single headed Hydrant valve confirming to IS 5290
8 with ISI mark of 63mm dia oblique type with instantaneous hose coupling adaptor etc complete as 8 4 4 4
required.
Supply, installation, testing and commissioning of 63 mm dia and 15m long RRL type with GM 63 mm
size male coupling at one end and female coupling at the other end etc complete. Hose shall comply to
9 IS:636 Type II and coupling to IS 903:1975 with IS certification. 16 8 8 8

Supply ,installation ,testing and commissioning of Short branch pipe with 63mm female instantaneous
10 inlet made of gun metal, male threaded outlet, complete with nozzle heavy quality conforming IS 903 8 4 4 4
etc.
Hose cabinet stand mounted type fabricated out of M.S. sheet of 16 swg. with glass fronted ( 4mm thick
glass with rubber beading) door and size of the cabinet shall be 600mm x 750 mm x 250 mm Quoted
rate shall be includes suitable stand for mounting for gnd lvl with supports, all fasteners etc, and cabinet
11 shall be powder coated of approved colour both inside and out side. 8 2 2 2

Supply ,installation, testing and commissioning of 25mm diameter FORGED BRASS AIR RELEASE
12 VALVES PN-1.6 BODY - FORGED BRASS 25 mm
Supply ,installation, testing and commissioning of Fire Hose Reel (as per ISI) wall mounted, swinging
type18 SWG MS sheet, fitted with 20 mm dia x 40 M long, high pressure hose with 5 mm outlet GM
13 nozzle with shut off valve (IS: 884) includes stop cock and chrome plated nozzle with all necessary fixing 4 4 4
materials complete.

Supply and fixing of Fire shaft door fabricated out of GI. sheet and frame, door shall be 900mm x
1500mm min with double leaf. & fixed with 4 mm thick Glass, suitable Rubber beeding and Locking
arrangement. Quoted rate shall be includes all fasteners etc, and complete shutter shall be powder
14 coated of approved colour both inside and out side. 2 2 2

Supply and installation of RCC hume pipes of 300 mm dia & NP 3 Class with collars for road / below
floor crossing of Fire water pipes. NP3 type hume pipe of the following diameter with necessary collars
conforming to IS 458 including cost and conveyance to site, laying to proper grade and alignment,
jointing etc. complete as per direction of the Engineer including cost and conveyance of all materials to
site, all labour, hire and fuel charges for all tools and plants employed and all other incidental charges
15 etc. complete as per specifications .The rate shall includes excavation, PCC ( 1:4:8 100 mm thick)bed and 24
ends shall be closed with Brick masonry work as directed by site engineer.

Supply & installation of Siamese inlet (Fire Brigade inlet) connection with provision for Four male
instantaneous coupling with MS cabinet fabricated. approved make heavy class GI pipe with non-return
valve,gate valve for fire fighting system including making connection by providing necessary piping &
fittings to the fire storage tank, fire fighting wet riser painting the same with 2 coats of enamel paint
16 over a coat of Zinc Chromate primer all complete as per drawings, specifications. Common for both 1
building Connection to yard line.

TOTAL - in Rs.
TOTAL INSTALLATI
3F 4F TER.F UNIT SUPPLY
QTY ON
UNIT RATE AMOUNT UNIT RATE AMOUNT

10 Rmt - -

9 9 48 Rmt - -
150 730 Rmt - -
10 Rmt - -
156 156 798 Rmt - -
4 4 20 Rmt - -

1 Nos - -

4 10 Nos - -
5 Nos - -

1 1 Nos - -
1 1 Nos - -
4 4 3 23 Nos - -

4 4 28 Nos - -

8 8 56 Nos - -

4 4 28 Nos - -

2 2 18 Nos - -

3 3 Nos - -

4 4 20 Nos - -

2 2 10 Nos - -

24 Rmt - -

1 Nos - -

- -
PROJECT : IIIT
LOCATION : HYDERABAD
DOCUMENT :- CONTROLLED FOR INTERNAL HYDRANT SYSTEM - SRIC BUILDING
SL.No DESCRIPTION EXT GF

Supplying, erecting and commissioning of Landing Hydrants comprising of the following in the Fire
duct;

Under Ground piping - Supply, erection, testing and commissioning of MS PIPES C CLASS pipes
conforming to IS 3589 for 200NB & above and IS 1239 for 150NB including cutting the pipes to correct
length, providing and welding flanges to pipe, etc as per specifications (rate including Anti-corrosive
Coating & Wrapping and heavy class forged fittings of IS standards) of the following diameters. brackets
testing to 13.5 Kg/Sq.cm hydraulic pressure after instalation,complete as per specification. Rates shall
1
be inclusive of 10% radiograph test complete as per specifications of the following diameters and all
necessary supports.
Note
Vendor to consider The pipe fittings shall be threaded up to 50 mm dia and Welded type for 65 mm dia
& above.

150mmdia - Existing System to Proposed Riser connection


Above Ground piping - Supplying, installing,hydroulic testing and commissioning of Heavy grade MS
Pipes confirming to IS :1239 part - I with malleable specials confirming to IS:1239 part - II, such as Tees,
elbows, check nuts, unions, flanges, nipples etc. Including cutting, Welding, fixing in / on walls / on
Floors, ceiling by using suitable supports such as MS channels ,angles,flats, threaded rods as required at
site with anchor fasteners,clamps,threaded rods,nuts,bolts,washers etc...complete. Painting the
exposed with one coat of metal zinc chromate primer with two coats of synthetic enamel paint of
approved colour / shade etc., complete.The pipe shall be socket weld type up to 50 mm dia and butt
weld type for 65 mm dia& above. hydro pressure testing to 13.8 Kg/Sq.cm hydraulic pressure after
instalation,complete as per specification. Rates shall be inclusive of 10% radiograph test complete as per
2 specifications of the following diameters and all necessary supports.
Note
Vendor to consider The pipe fittings shall be Socket up to 50 mm dia and Welded type for 65 mm dia &
above.

150mmdia - Riser 6
150mmdia (From Pump room to Risers) 492
150mmdia (From Accadamic Block shaft to Riser) 114
100mmdia
80mmdia 12 2
25mmdia 2
Supply, installation, testing and commissioning of electrically driven pump set as per specification.
Motor TEFC type, 2900 RPM 415 V, 50 cycles, 3 phase, class ‘F’ insulation, IP 54 protection, 10 HP
starting on DOL. The Pump shall be horizontal end suction top discharge. The pump shall be weather
proof type. The pump shall have cast iron casing, Cast iron impeller, steel shaft with common base
3 frame capable of discharging 27 m3/hour at 35 meter head as per ISI Standard (rate is inclusive of
control panel, Cables, PS, PG and supports)

Supplying, Installing, testing and commissioning CAST IRON BUTTERFLY VALVE WAFER TYPE LEVER
4
OPERATED PN-1.6 WITH INTEGRALLY MOULDED LINER OF NITRLE OR EPDM, S.S. (CF-8) DISC, S.S STEM

150 NB 3
100 NB
Supplying and installation of CAST IRON NON RETURN VALVE FLANGED PN-1.6 S.S HING PIN, RUBBER
5
SEATED, DRILLING AS PER : IS-1538
150 NB
Supplying and installation of CAST IRON Y-TYPE STRAINERS (Flanged)PN-1.6 BODY,-C.I., SCREEN
6 STAINLESS STEEL
150 NB
Supplying, installing, testing and commissioning of Gun metal chrome finished 25mm dia Ball valves
7 2
with fittings of screwed end type.
Supply installation ,testing and commissioning of Single headed Hydrant valve confirming to IS 5290
8 with ISI mark of 63mm dia oblique type with instantaneous hose coupling adaptor etc complete as 6 2
required.
Supply, installation, testing and commissioning of 63 mm dia and 15m long RRL type with GM 63 mm
size male coupling at one end and female coupling at the other end etc complete. Hose shall comply to
9 IS:636 Type II and coupling to IS 903:1975 with IS certification. 12 4

Supply ,installation ,testing and commissioning of Short branch pipe with 63mm female instantaneous
10 inlet made of gun metal, male threaded outlet, complete with nozzle heavy quality conforming IS 903 6 2
etc.
Hose cabinet stand mounted type fabricated out of M.S. sheet of 16 swg. with glass fronted ( 4mm thick
glass with rubber beading) door and size of the cabinet shall be 600mm x 750 mm x 250 mm Quoted
rate shall be includes suitable stand for mounting for gnd lvl with supports, all fasteners etc, and cabinet
11 shall be powder coated of approved colour both inside and out side. 6 2

Supply ,installation, testing and commissioning of 25mm diameter FORGED BRASS AIR RELEASE
12 VALVES PN-1.6 BODY - FORGED BRASS 25 mm
Supply ,installation, testing and commissioning of Fire Hose Reel (as per ISI) wall mounted, swinging
type18 SWG MS sheet, fitted with 20 mm dia x 40 M long, high pressure hose with 5 mm outlet GM
13 nozzle with shut off valve (IS: 884) includes stop cock and chrome plated nozzle with all necessary fixing 2
materials complete.

Supply and fixing of Fire shaft door fabricated out of GI. sheet and frame, door shall be 900mm x
1500mm min with double leaf. & fixed with 4 mm thick Glass, suitable Rubber beeding and Locking
arrangement. Quoted rate shall be includes all fasteners etc, and complete shutter shall be powder
14 coated of approved colour both inside and out side. (OPTIONAL)

Supply and installation of RCC hume pipes of 300 mm dia & NP 3 Class with collars for road / below
floor crossing of Fire water pipes. NP3 type hume pipe of the following diameter with necessary collars
conforming to IS 458 including cost and conveyance to site, laying to proper grade and alignment,
jointing etc. complete as per direction of the Engineer including cost and conveyance of all materials to
site, all labour, hire and fuel charges for all tools and plants employed and all other incidental charges
15 etc. complete as per specifications .The rate shall includes excavation, PCC ( 1:4:8 100 mm thick)bed and 24
ends shall be closed with Brick masonry work as directed by site engineer.

Supply & installation of Siamese inlet (Fire Brigade inlet) connection with provision for Four male
instantaneous coupling with MS cabinet fabricated. approved make heavy class GI pipe with non-return
valve,gate valve for fire fighting system including making connection by providing necessary piping &
fittings to the fire storage tank, fire fighting wet riser painting the same with 2 coats of enamel paint
16 over a coat of Zinc Chromate primer all complete as per drawings, specifications. Common for both 1
building Connection to yard line.

TOTAL - in Rs.
TOTAL INSTALLATI
MEZ.F 1F TER.F UNIT SUPPLY
QTY ON
UNIT RATE AMOUNT UNIT RATE AMOUNT

2 Rmt - -

6 6 18 Rmt - -
132 624 Rmt - -
114 Rmt - -
10 Rmt - -
2 2 18 Rmt - -
2 2 6 Rmt - -

1 Nos - -

3 6 Nos - -
5 Nos - -

1 1 Nos - -
1 1 Nos - -
2 2 1 7 Nos - -

2 2 12 Nos - -

4 4 24 Nos - -

2 2 12 Nos - -

2 2 12 Nos - -

1 1 Nos - -

2 2 6 Nos - -

1 Nos - -

24 Rmt - -

1 No - -

- -
PROJECT : IIIT
LOCATION : HYDERABAD
DOCUMENT :- CONTROLLED FOR FIRE PUMP ROOM
SL.NO DESCRIPTION QTY UNIT

FIRE PUMP ROOM


1 MAIN ELECTRICAL DRIVEN FIRE PUMPSET

Supply, installation, testing and commissioning of electrically Vertical Turbine driven pump set as per
specification. IEC / TEFC type, 2900 rpm, 415V, 50 cycle frequency 3 phase class ‘F’ insulation, I.P. 54 protection,
starting on Soft starter. The pump shall have cast iron casing, bronze impeller, steel shaft with common base
a. frame capable of discharging 137m3/hr at 120MWC-(Hydrant & Sprinkler Pumps). 2 Nos
Note : -
1.Rate shall inclusive of civil foundation for pump placement with accessories.
2.Pump Head has to be selected based on the hydraulic calculation done on the detailed engineering drawings

2 STANDBY DIESEL ENGINE PUMP


Supply, installation, testing and commissioning of diesel engine Vertical Turbine pump set as per
specification.The engine should have RPM between 1500 to 1800. Pump shall be directly coupled to diesel
engine as per system design condition. Engine shall be complete with flywheel, spider coupling, Air cleaners,
Water cooled, Heat Exchanger, Corrosion Resistor, Oil Sump with lube at pump. Governor, Fuel Filter, starting
motor battery charging alternator & instrument panel suitable for 24 volt DC including starting switches, Diesel
tank, lube oil temperature gauge, lube oil pressure & high water temperature including flexible exhaust
connection. The pump shall be capable to delivery 137m3/hr at 120MWC. Rate shall be inclusive of steel
fabricated tank fitted with level indicator with stand, the tank should in elevated level than the Engine so that
the fuel is drawn to the Engine due to gravity. Tank shall be designed to hold sufficient fuel oil for minimum four
hour operation. 1 Nos
Note : -
1.Rate shall inclusive of civil foundation for pump placement with accessories.
2.Pump Head has to be selected based on the hydraulic calculation done on the detailed engineering drawings

3 JOCKEY PUMPSET

Supply, installation, testing and commissioning of Vertical Turbine pump set as per specification. IEC /TEFC type,
2900 RPM 415 V, 50 cycles, 3 phase, class ‘F’ insulation, IP 54 protection, 20 HP starting on DOL starter. The
pump shall have cast iron casing, Cast iron impeller, steel shaft with common base frame capable of discharging
10.8m3/hour at 120MWC. (Hydrant & Sprinkler Pumps). 2 Nos
Note : -
1.Rate shall inclusive of civil foundation for pump placement with accessories.
2.Pump Head has to be selected based on the hydraulic calculation done on the detailed engineering drawings

4 Test Array Arrangement for pumpset with pressure switch valves pipes and fittings etc. 5 Set
5 Test Array Arrangement for pumpset with Dial type pressure gauge valves pipes and fittings etc. 2 Set

Supply, Erection, Testing and commissioning of CAST IRON SLUICE VALVE / GATE VALVE RISING STEM FLANGED
6
PN-1.6 S.S STEM, GUN METALWORKING PARTS, DRILLING AS PER : IS-1538
250 NB 1 Nos
200 NB 1 Nos
150 NB 1 Nos
100 NB 1 Nos
80 NB 1 Nos

Supplying, Installing, testing and commissioning CAST IRON BUTTERFLY VALVE WAFER TYPE LEVER OPERATED
7
PN-1.6 WITH INTEGRALLY MOULDED LINER OF NITRLE OR EPDM, S.S. (CF-8) DISC, S.S STEM

200 NB 1 Nos
150 NB 3 Nos
100 NB 1 Nos
65 NB. 2 Nos
Supply, installation, testing and commissioning of SS” stainless wired Expansion bellows (Flexible coupling) with
8
required flanges,nuts,bolts & accessories
200 NB 1 Nos
150 NB 3 Nos
80 NB 1 Nos
65 NB. 2 Nos
Supplying and installation of CAST IRON NON RETURN VALVE FLANGED PN-1.6 S.S HING PIN, RUBBER SEATED,
9
DRILLING AS PER : IS-1538
200 NB 1 Nos
150 NB 3 Nos
100 NB 1 Nos
65 NB. 2 Nos
Supplying and installation of CAST IRON Y-TYPE STRAINERS (Flanged)PN-1.6 BODY,-C.I., SCREEN STAINLESS
10 STEEL
250 NB 1 Nos
Supplying and installation of FORGED BRASS BALL VALVE PN- 2.5 BODY D.I. , FLAP S.S , SEATNITRILE OR EPDM
11
RUBBER
50 NB 5 Nos
25 NB 5 Nos
15 NB 1 Nos
Electronic level indicator with Tank level alarm control system, pressure transducer sensors ED display high /
12 1 Nos
low level / cabling to pump house with indicators etc.,
Exhaust pipe for Diesel engine of 150 mm dia M.S. Medium grade with mineral wool insulation with aluminum
13
sheet & residential muffler accessories.

a) 150mm dia M.S. Medium grade shall be laid above ground with aluminum gladding & structural steel supports. 18 Rmt

Supply,Installation, Testing & commissioning of Air vessel in pump room on M.S stand with necessary
14 arrangement and including the cut off, drain and air release and drain pipes to the channel in pump 1 Set
room,complete as per specification. Size 250mm dia

Above Ground piping - Supply, erection, testing and installation of MS PIPES C CLASS conforming to IS 3589 for
200NB & above and IS 1239 for 150NB & below with welded joints including cutting the pipes to correct length,
providing and welding flanges to pipe, etc as per specifications (including heavy class forged fittings of IS
standards) of the following diameters.Brackets testing to 13.5 Kg/Sq.cm hydraulic pressure after instalation.
Rate shall be inclusive of Zinc chromate primer over that 2 coats red enamel paint as per Fire authorities
15 requirement over all above ground pies and also inclusive of making hole in the wall, chasing, chipping, making
good with plastering after completion of work, pipe sleeve of suitable higher size, sealing the sleeves with glass
wool in between & fire sealant, etc. Cost of Steel supports for piping (like angles, channels, clamps, tie rods,
brackets, nuts and bolts as per details given in the drawings) shall also be included in the quoted rate.
VVendor to consider The pipe fittings shall be threaded up to 50 mm dia and Groveed / Welded type for 65 mm
dia & above. All necessary consumables like lubricant to be included in the quoted cost.

250 NB - Class C 10 Rmt


200 NB - Class C 12 Rmt
150 NB - Class C 36 Rmt
100 NB - Class C 5 Rmt
80 NB - Class C 5 Rmt
65 NB - Class C 12 Rmt
50 NB - Class C 24 Rmt
25 NB - Class C 54 Rmt

16 FIRE FIGHTING PANEL


Design, Supply, Installation, testing and commissioning of cubicle type floor mounting switch board comprising
1 Set
of the following, the board shall be fabricated as per the detailed specification enclosed.

The below mentioned ratings are indicative only however the contractor shall have to select the suitable rating
breakers, switches, starters and related all the accessories based on the selected motors

Incoming
630A, 35KA, 4P MOT MCCB with all connected accessories - 1 Nos. as incomer. Incomers & Buscoupler shall
have electrically interlocked with auto manual selector switch
Instrument Panel
Digital type MFM with RS485 port - 1 NOS
Outgoing

250A TP&N 25kA THERMAL MAGNETIC MCCB with SOFT starter suitable for Electrical Driven Pumps with
ON/OFF/TRIP indicating lamps, ON/OFF push buttons and all other required accessories - 2 Nos

63A TP&N THERMAL MAGNETIC MCCB 25kA suitable for Jockey pumps with ON/OFF/TRIP indicating lamps,
ON/OFF push buttons and all other required accessories - 2 Nos
With necessary Aluminium busbars, interconnections, earthing etc., with required accessories as per the
specifications.630 Amps TPN Aluminium busbars:- All the neutral busbars shall have the same capacity of phase
busbars.

17 DIESEL ENGINE AUTO START PANEL

Supply installation testing and commissioning of Autostart panel for the diesel engine complete with
auto/manual switch, relay, timers, contactors, rotary switches for AC ON / DC ON, indication lamps, protective
fuses with battery charger, suitable of working on 230 V, AC, single phase, enclosure being vermin & dust proof, 1 Set
necessary alarms, different selector switches, push buttons etc. Also potential free contacts shall be provided
for connecting to the IBMS.

Battery charger with transformer with rectifier resistance DC ammeter, DC voltmeter, Trickle / booster / off
selector switch - 2 Nos.
1 set of indicating lamps for the following :
1. phase indication
2. battery charger on
3. over load relay
4. DC supply on
5. control switch on
6. Engine fails to start
7. Pump on
8. Low oil pressure
9. High water temperature
10. Auto manual selector switch
d) 1 sets of push button stations for the following :
1. Engine Start
2. Engine Stop
3. Engine - hooter ACK
4. Engine - fault reset
e) Selector switches (Engine control, mode selector)-1 No.
f) Auxiliary relays / contactors / timer for sequence operating for starting and stopping of the engine - 1 set.
g) Hooter for audio alarm (Industrial type) - 1 No.
All the components shall be housed in a common cubical made of 16 swg. M.S. sheet with required stiffeners ( if
required). The panel shall be powder coated of approved colour both inside & out side. The panel shall have
both bottom & top cable entry provisions and panel shall be mounted on Pedestal of 300 mm height.

Design, supply, laying of following size PVC/XLPE insulated outer sheathed (1100 V grade) alu. armoured
conductor cable partly laid in cable tray and partly laid in wall/ ceiling with suitable clamps. The rate shall
18
inclusive of suitable double compression glands and crimping socket for the cables. Rate shall inclusive of cable
terminations. pls refer SLD
a 3.5 Core 300 Sq.mm XLPE Aluminium armoured Cable 5 Rmt
b 3.5 Core 240 Sq.mm XLPE Aluminium armoured Cable - FOR FIRE/HYD /SPK /PUMP 45 Rmt
c 4.0 Core 16 Sq.mm XLPE Aluminium armoured Cable - FOR JOCKEY PUMP 45 Rmt
d 3.0 Core 1.5 Sq.mm PVC insulated Cu Cable 100 Rmt
19 Design, supply and laying of 50 x 6 mm GI. flat run along the cable tray 100 Rmt

Design, supply and laying of 8 gauge bare copper wire for Gland earthing, loop earthing in the existing
20 100 Rmt
surface/recessed steel conduit, DB earthing and other equipment body earthing as required.

21 Supply and laying of suitable size electrical rubber mats tested to 11KV, with grooved ISI Mark. For pump room 1 Lot

Supply, erection of following sizes GI ladder type cable rack system made out of sheet steel folded to required
22
shape with adequate number of supports. The rate shall be inclusive of suitable hanging support

150mm x 75mm x 2.5mm 45 Rmt


300mm x 75mm x 2.5mm 45 Rmt
TOTAL - in Rs.
SUPPLY INSTALLATION
UNIT RATE AMOUNT UNIT RATE AMOUNT

- -

- -

- -

- -
- -

- -
- -
- -
- -
- -

- -
- -
- -
- -

- -
- -
- -
- -

- -
- -
- -
- -

- -

- -
- -
- -
- -

- -

- -

- -
- -
- -
- -
- -
- -
- -
- -
0.00 0.00

0.00 0.00
- -
- -
- -
- -
- -

- -

- -

- -
- -
- -
Table 1
PROJECT : IIIT
LOCATION : HYDERABAD
DOCUMENT :- Obtaining Fire Noc

QTY(Builtup Area) UNIT

A Scope and Check list


On behalf of IIIT Hyd filing the fire noc application and successfully obtaining
the preliminary NOC at shortest duration and final NOC post completion of fire
fighting works

Coordination with client,consultant, PM team,any other stake holder for


preparation of documents, drawings, filing of application and submitting the
file for provisional fire NOC from fire department of hyderabad region

Obtaining Provisional Fire Noc/ Revised Provisional Fire NOC for both NAB &
i
SRIC Buildings.

Providing a check list for submitting each approval along with a thorough
write-up letter and other write-ups, and if necessary, preparing/altering all
1
basic drawings mentioned mandatory in comprehensive list of documents
required for Provisional NOC

Help the client with all necessary paperwork, including the affidavit
2 submission, along with coordination with the client's architect and PM team
and any write-ups that may be necessary.
Reviewing and, if necessary, correcting documents that the client
4
representative has prepared.

Online application filing, submission, online uploading of documents(with all


5 required signatures) and follow-up with Fire Department to update the client
on the status of Provisional Fire NOC on agreed time lines.

Coordinating/arranging Inspection of Fire Committee officers, Coordinating for


Payment of fee online, Re-submission of drawings if required as per Fire
6 Department requirements and meeting the Fire Department concerned
persons along with the architect and client representatives on regular intervals
for obtaining Provisional NOC

Successfully Obtaining the Provisional Fire NOC from Fire department of


7 199348 SFT.
hyderabad
Submission of a Provisional fire NOC to the IIIT Hyderabad team from the fire
8
department
B Final Fire NOC ( Occupancy Noc) for both NAB & SRIC Buildings.

Providing a check list for submitting each approval along with a thorough
write-up letter and other write-ups, and if necessary, preparing/altering all
1
basic drawings mentioned mandatory in comprehensive list of documents
required for Final Fire NOC ( Occupancy Noc)
Help the client with all necessary paperwork, including the affidavit
2 submission, along with coordination with the client's architect and PM team
and any write-ups that may be necessary.
Reviewing and, if necessary, correcting documents that the client
4
representative has prepared.

Online application filing, submission, online uploading of documents(with all


5 required signatures) and follow-up with Fire Department to update the client
on the status of Final Fire NOC ( Occupancy NOC) on agreed time lines.

Coordinating/arranging Inspection of Fire Committee officers, Coordinating for


Payment of online fee, Re-submission of drawings if required as per Fire
6 Department requirements and meeting the Fire Department concerned
persons along with the architect and client representatives on regular intervals
for obtaining Final Fire NOC ( Occupancy NOC)

Successfully Obtaining the Final Fire NOC ( Occupancy NOC) from Fire
7
department of hyderabad
Submission of Final Fire NOC ( Occupancy NOC) to the IIIT Hyderabad team
8
from the fire department
TOTAL
RATE/SFT AMOUNT

0
0
PROJECT : IIIT ACADEMIC BUILDING
DOCUMENT : ADDRESSABLE FIRE ALARM SYSTEM BOQ
SI.No

6
7

10

11

12

13

14

15
16

17

18

19

20

21

22

23
PROJECT : IIIT ACADEMIC BUILDING
DOCUMENT : ADDRESSABLE FIRE ALARM SYSTEM BOQ
Descriptions

SITC OF ADDRESSABLE FIRE ALARM SYSTEM

Analogue Addressable Intelligent 8 loop Fire alarm control panel including loop card, provision to make
with a minimum capacity of 125 devices + 125 modules per loop, with battery back up for 48 Hrs during
normal operation and 15 minutes alarm operation, with minimum 600 Character LCD display, necessary
interface card to connect a repeater panel and all hardware & software as per specification. Panel &
Components shall be UL listed (latest edition)

SITC of Bacnet card for BMS integration for proposed FAS panels

Passive Repeater Panel with minimum 80 character display for monitoring other Panels on the network
loop with Power supply unit. Peer To Peer Networked with main panel, such that the status of the entire
system shall be available on individual Annunciator.

Graphics User Interface for Monitoring & Control of complete Fire,. The GUI based main network
software shall network with other panels on True Peer-to-Peer network. It shall be capable of graphically
representing each facility being monitored with floor plans and icons depicting the actual locations of the
various systems.. It shall have the facility to change the sensitivity of any detector. The software shall be
capable of monitoring 200 Nodes with 100 MB baud Transmission rate on Fibre Optics Network and 12
MB baud Transmission on cable and 2,50,000 network , GUI shall be capable of monitoring & controlling
and mapping the unlimited fire points. The Graphic workstation shall act as an independent node
communicating on the peer to peer network and shall not be dependant on the Fire Panel CPU for
operation. Failure of Fire Panel CPU shall not result in failure of GUI. Software shall be suitable for total
numbers of Fire alarm panels

PC for GUI software


Intel i8 or higher version 3 Ghz processor,
16 GB RAM,
NVIDIA Graphics card with 2GB,
1TB HDD,
24" Color flat panel HD LED Monitor,
1080P HD Resolution,
100/1000Mbps network card with original Microsoft Windows 8 Operating System, antivirus
softwares,MS softwares.

Supply Installation Testing & Commissioning of Multi sensor detector (photo+heat) with base,powder
coated back box and other accessories as required and Detectors shall be UL listed, - (ABOVE FALSE
CEILING & FALSE FLOOR). Detectors shall be UL listed 268 7th edition
Supply Installation Testing & Commissioning of Multi sensor detector (photo+heat) with base and other
accessories as required and Detectors shall be UL listed, - (BELOW FALSE CEILING). Detectors shall be UL
listed 268 7th edition

Supply Installation Testing & Commissioning of Analog Addressable Smoke Detector with programmable
for timed automatic sensitivity selection with Standard base, powder coated backbox and other
accessories as required and Detectors shall be UL Listed. (TRUE CEILING/ABOVE FALSE CEILING).
Detectors shall be UL listed 268 7th edition

Supply Installation Testing & Commissioning of Analog Addressable Smoke Detector with programmable
for timed automatic sensitivity selection with Standard base and other accessories as required and
Detectors shall be UL Listed. (BELOW FALSE CEILING). Detectors shall be UL listed 268 7th edition

Supply Installation Testing & Commissioning of heat detector with base, Junction box and other
accessories as required and Detectors shall be UL listed,Detectors shall be UL listed 268 7th edition

Supply, installation, fixing, testing and commissioning of Addressable four-wire 70mtr coverage Beam
smoke detector with Single-ended, reflective design, Six user selectable sensitivity levels, Optional integral
NFPA 72 sensitivity test feature, Digital display for easy alignment, suitable for operating in temperature
range of (-) 22°F to (+) 131°F (UL Listed).It should provided with necessary Power supply units, fixing
accessories.As per the specifications

SITC of Response indicator


Analogue Addressable Fault isolator module capable of monitoring shorted loop circuit and automatically
restore communications when shorted conditions are corrected. (FIM's are used for every 20
detectors/devices)

Supply, installation, fixing, testing and commissioning of Analogue Addressable Monitor module with
back box(1.6mm thick RED colour) operating at 24V DC, 2A, rated at 230V, provided with DPDT contact.
FLOW SWITCH
ASD#0,
WLD#
GRP#0
FIRE DOOR#10 with required fixing accessories

Supply, installation, fixing, testing and commissioning of Analogue Addressable Control module with
back box (1.6mm thick RED colour) operating at 24V DC, 2A, rated at 230V, provided with DPDT
contact,with required fixing accessories
Access Control #5
PA INTEGRATION#5
Hooter#25
Supply, installation, fixing, testing and commissioning of Analogue Addressable Control relay module
with back box(1.6mm thick RED colour) operating at 24V DC, 2A, rated at 230V, provided with DPDT
contact. with required fixing accessories, AC/AHU TRIPPING/ Pressurization fans/Lift

Addressable Electronic Hooter cum Strobe ceiling mounted. The hooters shall be made of ABS plastic, and
have a DB level of 65dbA and a multi tone facility. Addressable Control Module shall be fitted in a junction
box.

SITC of Addressable Manual call point having an integrally mounted addressable module that monitors
and reports contact status. (PULL TYPE) with back box(1.6mm thick RED colour) along with required fixing
accessories. The device shall have an LED which shall blink in normal state & get steady on activation to
monitor the heath status of the device.

2C x 1.5 mm2, Stranded Copper conductor,Type A ST1 PVC insulated,Armoured FRLS CU Cable 1100 V as
per IS 1554, with GI saddle spacers every 0.3 mtr with Single compression Cable Glands,ABS Junction
Boxes (wherever required), terminals,Ferruling complete.

Supplying, installing, testing and commissioning of approved make FRLS PVC conduits on ceiling / wall /
floor etc. complete with accessories like, Junction boxes, Collars, Bends, clamps, saddles etc. (for MCP)

25 mm dia.

Supply and laying of MS Powder coated Trunking 300 x 50 mm x 1.6mm with cover & fixing suppports
etc as required (Cable dressing for Fire & PA panel )

Supply and laying of GI enclosed raceway 300 x 50 mm x 1.6mm with cover & fixing suppports etc as
required (Cable dressing inside the shaft )

SITC of PSU for hooters & AHU tripping (inclusive of Battery ckt & battery)

TOTAL
AMC Cost
Charges for Comprehensive Annual Maintenance Charges for a period of 5 years from the end of
Guarantee period. Vendor to note that all important security upgrades to the software necesiated due to
isues in the software itself or due to upgrades made to OS shall be provided without any additional cost.

I year
II year
III year
IV year
V year
Unit GF 1F 2F 3F 4F Total Qty SUPPLY

RATE INR

Lot 1 1

Lot 1

Nos 1

Lot 1

Nos 1

Nos 4 2 2 2 18 28
Nos 1 1 1 18 21

Nos 125 100 90 95 85 495

Nos 25 45 20 20 25 135

Nos 2 2 2 2 8

Nos 5 5

Nos 25 45 20 25 45 160

Nos 9 8 7 7 8 39

Nos 2 2 2 2 2 10

Nos 7 7 7 6 7 34
Nos 10 10 8 8 8 44

Nos 25 25 25 20 25 120

Nos 13 11 8 8 10 50

Rmt 3150 2450 1850 1950 2450 11850

Rmt 39 33 24 24 30 150

Rmt 25 25

Rmt 5 5 5 5 20

Set 5 5 5 4 5 24

Lot 1
Lot 1
Lot 1
Lot 1
Lot 1
ERECTION

AMOUNT INR RATE INR AMOUNT INR

0 0

0 0

0 0

0 0

0 0

0 0
0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0
0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

- -
Makes

NOTIFIER /EDWARDS/SIMPLEX/SCHNEIDER/SIEMENS
CERBERUS PRO

NOTIFIER /EDWARDS/SIMPLEX/SCHNEIDER/SIEMENS
CERBERUS PRO

NOTIFIER /EDWARDS/SIMPLEX/SCHNEIDER/SIEMENS
CERBERUS PRO

NOTIFIER /EDWARDS/SIMPLEX/SCHNEIDER/SIEMENS
CERBERUS PRO

HP/ DELL

NOTIFIER /EDWARDS/SIMPLEX/SCHNEIDER/SIEMENS
CERBERUS
NOTIFIER /EDWARDS/SIMPLEX/SCHNEIDER/SIEMENS
CERBERUS

NOTIFIER /EDWARDS/SIMPLEX/SCHNEIDER/SIEMENS
CERBERUS

NOTIFIER /EDWARDS/SIMPLEX/SCHNEIDER/SIEMENS
CERBERUS

NOTIFIER /EDWARDS/SIMPLEX/SCHNEIDER/SIEMENS
CERBERUS

NOTIFIER /EDWARDS/SIMPLEX/SCHNEIDER/SIEMENS
CERBERUS

RAVEL/C SYSTEM/AGNI

NOTIFIER /EDWARDS/SIMPLEX/SCHNEIDER/SIEMENS
CERBERUS

NOTIFIER /EDWARDS/SIMPLEX/SCHNEIDER/SIEMENS
CERBERUS

NOTIFIER /EDWARDS/SIMPLEX/SCHNEIDER/SIEMENS
CERBERUS
NOTIFIER /EDWARDS/SIMPLEX/SCHNEIDER/SIEMENS
CERBERUS

NOTIFIER /EDWARDS/SIMPLEX/SCHNEIDER/SIEMENS
CERBERUS

NOTIFIER /EDWARDS/SIMPLEX/SCHNEIDER/SIEMENS
CERBERUS

POLYCAB / VARSHA/ DATA FLEX

VIP/ PRECISION/ASTRA/ANCHOR

REPUTED

REPUTED

Battery : Panasonic/Exide/Amaron
PSU : CTEC/CSYSTEM/INSYIN
PROJECT : IIIT ACADEMIC BUILDING
DOCUMENT : PUBLIC ADDRESS SYSTEM BOQ
SI.No Descriptions

SITC OF PUBLIC ADDRESS SYSTEM

SITC of 6W RMS False Ceiling Mount Speakers with inbuilt 100V Line Matching Transformer,
wide opening angle, optimized for music & speech applications with mounting clamps as per
1
specifications

SITC of 6W RMS True Ceiling Mount Speakers with inbuilt 100V Line Matching Transformer,
wide opening angle, optimized for music & speech applications with powder coated back box,
2 supports as per specifications
Speakers shall have the tappings at 1.5/3/6 watts

SITC of 6 W Wall Mounted box Speakers with line matching transformers as specified as per
3
specifications

SITC of 15W bidirectional wall mount wooden speaker with Frequency response of 200Hz to
4 15Khz with SPL sensitivity of 88db @ 1mtr and tapping of 15W/7.5W/3.75W as specified as
per specifications

SITC of System Controller 6 zone controller with 500w inbuilt amplifier complete with
5 Microprocessor based, Dual Tone Control for Speech & Music, with automatic
announcement incase of fire, etc.

6 SITC of 6 zone router with accessories


7 SITC of 6 zone call station with microphone with accessories
8 SITC of 6 zone call station keypad with accessories
9 SITC of Rack Mounted 120 W Power Amplifier
10 SITC of Rack Mounted 240 W Power Amplifier
11 SITC of Rack Mounted 480 W Power Amplifier

2C x 1.5 mm2, Stranded Copper conductor,Type A ST1 PVC insulated,Armoured FRLS Cable
12 1100 V as per IS 1554, with GI saddle spacers every 0.3 mtr with Single compression Cable
Glands,ABS Junction Boxes (wherever required), terminals,Ferruling complete.

13 SITC of Volume controller for one speaker (near call station)


14 Rack Mounted DVD Player as per specifications
SITC OF Suitable size rack as per following specification,
Conforms to DIN 41494 Or Equivalent EIA/ISO/EN/CEA Standard
Finish - Powder coated finish with Seven tank pretreatment process meeting ASTM standard
Color - Black/off white/grey
Fan module on top of the rack
15 Welded frame with vented top cover with fan , perforated Metal Door with lock & Key and
Back vented / Perforated metal door with lock & key and partially vented side panels, free
standing on floor with 4 No. casters wheels with 2 no with brakes & 2 No. without brakes,
cable oraginesers, Levelers with required 16A/5A power strips including accessories.
Number of racks shall be as per the design requirement. vendor to consider required number
of racks as per their requirement

TOTAL
AMC Cost

Charges for Comprehensive Annual Maintenance Charges for a period of 5 years from the end
of Guarantee period. Vendor to note that all important security upgrades to the software
necesiated due to isues in the software itself or due to upgrades made to OS shall be provided
without any additional cost.

I year
II year
III year
IV year
V year
Unit GF 1F 2F 3F 4F Total Qty SUPPLY

RATE INR

Nos 25 45 15 20 40 145

Nos 90 55 70 70 65 350

Nos 5 5 5 5 5 25

Nos 15 15

Nos 1 1

Nos 1 1
Nos 1
Nos 1
Nos 1
Nos 1 1 1 3
Nos 2 2 1 1 1 7

Rmt. 2100 1800 1500 1500 1800 8700

Nos 1 1
Nos 1 1
Lot 1 1

Lot
Lot
Lot
Lot
Lot
ERECTION

AMOUNT INR RATE INR AMOUNT INR

0 0

0 0

0 0

0 0

0 0

0 0
0 0
0 0
0 0
0 0
0 0

0 0

0 0
0 0
0 0

- -
Makes

BOSCH /HONEYWELL /TSG

BOSCH /HONEYWELL /TSG

BOSCH /HONEYWELL /TSG

BOSCH /HONEYWELL /TSG

BOSCH PLENA /HONEYWELL INTEVIO /TSG

BOSCH PLENA /HONEYWELL INTEVIO /TSG


BOSCH PLENA /HONEYWELL INTEVIO /TSG
BOSCH PLENA /HONEYWELL INTEVIO /TSG
BOSCH /HONEYWELL /TSG
BOSCH /HONEYWELL /TSG
BOSCH /HONEYWELL /TSG

POLYCAB / VARSHA/ DATA FLEX

BOSCH/HONEYWELL
Philips / Sony / LG / Samsung
VALL RACK / MASS RACK
PROJECT : IIIT ACADEMIC BUILDING
DOCUMENT : SIGNAGE SYSTEM BOQ
SI.No Descriptions Unit GF 1F

SITC OF SIGNAGE SYSTEM

SITC of LED Configured Emergency Exit SIGNAGE system


1. Recessed Mounting Type
2. LED 5 watts with Rechargeable battery backup of 90 minutes
3. Continously provides illumination through mains power supply
4. Suitable for different types of exit Facia (size 300 L * 150 Ht mm)
5. Refer Image on specification sheet
6. As per IS 9583-1981
7.Photoluminescent & maintained type
8.Suitable for 230v, 50Hz
9.Similar to Prolite PEL LED E/M/P (RM)

"FIRE EXIT " (BATTERY BACKED LED SIGNAGE) - size 150 x 300mm
1 Nos 7 4
SINGLE SIDE
" Emergency Exit Signages - (Autoglow type) size 150 x 300mm - double
2 Nos 45 45
side with suspension chains (SS)

" EXTINGUISHER Signages - Autoglow, with suspension chains (Autoglo


3 Nos 31 26
signages, size 150 x 300) - double side with suspension chains (SS)

" MCP Signages - Autoglow, with suspension chains (Autoglo signages,


4 Nos 13 11
size 150 x 300 - double side with suspension chains (SS)

" Hydrant - Autoglow, with suspension chains (Autoglo signages, size 150
5 Nos 2 2
x 300 - double side with suspension chains (SS)

Fire Evacuation Route Map as per following specification


Preparation of drawing and providing, Autoglow Fire escape route map
in clear acrylic glass and required glass studs supports etc. Indicating
direction, Key plan, contact numbers etc. (The sample of the same need
6 to be presented for approval before execution)…. (Maximum size of the Nos 6 6
board A2)
Evacuation plan shall be glow in dark.
A2 size with 5mm thick rear & 3mm thick front acrylic cover including
wall mount supports.

TOTAL
AMC Cost
Charges for Comprehensive Annual Maintenance Charges for a period of
5 years from the end of Guarantee period.
I year Lot
II year Lot
III year Lot
IV year Lot
V year Lot
2F 3F 4F Total Qty SUPPLY ERECTION
RATE INR AMOUNT INR RATE INR AMOUNT INR

2 2 2 17 0 0

50 50 50 240 0 0

23 23 28 131 0 0

8 8 10 50 0 0

2 2 2 10 0 0

4 4 4 24 0 0

- -
Makes

PROLITE/AUTOGLOW/Technoware

PROLITE/AUTOGLOW/Technoware

PROLITE/AUTOGLOW/Technoware

PROLITE/AUTOGLOW/Technoware

PROLITE/AUTOGLOW/Technoware

PROLITE/AUTOGLOW/Technoware
PROJECT : IIIT ACADEMIC BUILDING
DOCUMENT : FIRE EXTINGUISHER SYSTEM BOQ
SI.No Descriptions Unit

SITC OF FIRE EXTINGUISHER

CO2 type Fire Extinguisher ISI marked confirming to IS:15683 latest. Capacity 4.5 Kg.
Complete with delivery hose horn, squeeze grip release valve, locking
arrangement,operating temperature -30°C to +55°C, supplied with body bearing IS
1 7285 mark and approved by CCoE tested at 250 kgf/cm2., fitted with ISI marked & Nos
CCoE approved valve as per IS 3224. CO2 Gas as per IS: 15222. externally painted
with PO Red Shade No. 538 of IS 5, operation manual and floor stand or Wall Mount
Bracket including accessories as required as per site condition

Powder Fire Extinguisher (Stored Pressure type) (Powder pressurized with dry
nitrogen gas at 15 bar.) capacity: 4kg duly ISI marked conforming to IS:
15683:2006/latest, with IS 14609 ISI marked ABC powder complete with squeeze
2 grip release valve, discharge pipe, locking arrangement, pressure gauge, operation Nos
manual,Body Hydrotested at 35 bar, Operating temperature -30°C to +55°C, external
epoxy powder coating with PO Red Shade No. 538 of IS 5, and floor stand or Wall
Mount Bracket including accessories as required as per site condition

Clean Agent (Stored Pressure) Type Fire Extinguisher Complete with squeeze grip
release valve, locking arrangement, pressure gauge, operation manual, bracket with
3 Nos
two screw and sleeve filled with FE36/HFC- 236 FA . Complete in all respect, Capacity
4 Kg. with Floor mounting bracket with four leg or Wall Mount Bracket. ZERO ODC

FE36 Automatic ceiling Mounted Clean agent Extinguisher - 10 Kg with Ceiling


4 mount accessories including nozzle(57 deg), pressure guage. ISI approved - UPS, Nos
Battery,Server room & Hub room

FE36 Automatic ceiling Mounted Clean agent Extinguisher - 5 Kg with Ceiling mount
5 accessories including nozzle(57 deg), pressure guage. ISI approved - UPS, Nos
Battery,Server room & Hub room
Wet chemical stored pressure 6Ltr capacity including accessories, pressure guage
6 Nos
and floor mounting accessories (kitchen - preparation area)
Fire buckets round bottom type enamel painted, white inside & Red out side and
7 Nos
Letter "FIRE" in black out side and handle with mounting bracket.
Fire bucket stand fabricated by MS angles to install 4 Nos. of buckets including rain
8 Nos
top cover .
TOTAL
AMC Cost
Charges for Comprehensive Annual Maintenance Charges for a period of 5 years
from the end of Guarantee period.
I year Lot
II year Lot
III year Lot
IV year Lot
V year Lot
GF 1F 2F 3F 4F Total Qty SUPPLY
RATE INR AMOUNT INR

1 1 3 3 3 11 0

30 25 20 20 25 120 0

1 0

1 0

1 2 2 1 6 0

1 0

1 0

1 0

-
ERECTION
Makes
RATE INR AMOUNT INR

0 MINIMAX/KANEX

0 MINIMAX/KANEX

0 MINIMAX/KANEX

0 MINIMAX/KANEX

0 MINIMAX/KANEX

0 MINIMAX/KANEX

0 Fabricated

0 Fabricated

-
PROJECT : IIIT , SIRC Building
DOCUMENT : ADDRESSABLE FIRE ALARM SYSTEM BOQ
SI.No

7
8

10

11

12

13

14

15

16
17

18

19

20

21

22

23
PROJECT : IIIT , SIRC Building
DOCUMENT : ADDRESSABLE FIRE ALARM SYSTEM BOQ
Descriptions

SITC OF ADDRESSABLE FIRE ALARM SYSTEM

Analogue Addressable Intelligent 3 loop Fire alarm control panel including loop card, provision to make with a
minimum capacity of 125 devices + 125 modules per loop, with battery back up for 48 Hrs during normal operation
and 15 minutes alarm operation, with minimum 600 Character LCD display, necessary interface card to connect a
repeater panel and all hardware & software as per specification. Panel & Components shall be UL listed (latest
edition)

SITC of Bacnet card for BMS integration for proposed FAS panels

Passive Repeater Panel with minimum 80 character display for monitoring other Panels on the network loop with
Power supply unit. Peer To Peer Networked with main panel, such that the status of the entire system shall be
available on individual Annunciator.

Graphics User Interface for Monitoring & Control of complete Fire,. The GUI based main network software shall
network with other panels on True Peer-to-Peer network. It shall be capable of graphically representing each facility
being monitored with floor plans and icons depicting the actual locations of the various systems.. It shall have the
facility to change the sensitivity of any detector. The software shall be capable of monitoring 200 Nodes with 100
MB baud Transmission rate on Fibre Optics Network and 12 MB baud Transmission on cable and 2,50,000 network ,
GUI shall be capable of monitoring & controlling and mapping the unlimited fire points. The Graphic workstation
shall act as an independent node communicating on the peer to peer network and shall not be dependant on the
Fire Panel CPU for operation. Failure of Fire Panel CPU shall not result in failure of GUI.

PC for GUI software


Intel i8 or higher version 3 Ghz processor,
16 GB RAM,
NVIDIA Graphics card with 2GB,
1TB HDD,
24" Color flat panel HD LED Monitor,
1080P HD Resolution,
100/1000Mbps network card with original Microsoft Windows 8 Operating System, antivirus softwares,MS
softwares.

Supply Installation Testing & Commissioning of Multi sensor detector (photo+heat) with base,powder coated back
box and other accessories as required and Detectors shall be UL listed, - (ABOVE FALSE CEILING & FALSE FLOOR).
Detectors shall be UL listed 268 7th edition

Supply Installation Testing & Commissioning of Multi sensor detector (photo+heat) with base and other
accessories as required and Detectors shall be UL listed, - (BELOW FALSE CEILING). Detectors shall be UL listed 268
7th edition
Supply Installation Testing & Commissioning of Analog Addressable Smoke Detector with programmable for timed
automatic sensitivity selection with Standard base, powder coated backbox and other accessories as required and
Detectors shall be UL Listed. (TRUE CEILING/ABOVE FALSE CEILING). Detectors shall be UL listed 268 7th edition

Supply Installation Testing & Commissioning of Analog Addressable Smoke Detector with programmable for timed
automatic sensitivity selection with Standard base and other accessories as required and Detectors shall be UL
Listed. (BELOW FALSE CEILING). Detectors shall be UL listed 268 7th edition

Supply Installation Testing & Commissioning of heat detector with base, Junction box and other accessories as
required and Detectors shall be UL listed,Detectors shall be UL listed 268 7th edition

Supply, installation, fixing, testing and commissioning of Addressable four-wire 70mtr coverage Beam smoke
detector with Single-ended, reflective design, Six user selectable sensitivity levels, Optional integral NFPA 72
sensitivity test feature, Digital display for easy alignment, suitable for operating in temperature range of (-) 22°F to
(+) 131°F (UL Listed).It should provided with necessary Power supply units, fixing accessories.As per the
specifications

SITC of Response indicator

Analogue Addressable Fault isolator module capable of monitoring shorted loop circuit and automatically restore
communications when shorted conditions are corrected. (FIM's are used for every 20 detectors/devices)

Supply, installation, fixing, testing and commissioning of Analogue Addressable Monitor module with back
box(1.6mm thick RED colour) operating at 24V DC, 2A, rated at 230V, provided with DPDT contact.
FLOW SWITCH
ASD#0,
WLD#
GRP#0
FIRE DOOR#0 with required fixing accessories

Supply, installation, fixing, testing and commissioning of Analogue Addressable Control module with back box
(1.6mm thick RED colour) operating at 24V DC, 2A, rated at 230V, provided with DPDT contact,with required fixing
accessories
Access Control #3
PA INTEGRATION#3
Hooter#7

Supply, installation, fixing, testing and commissioning of Analogue Addressable Control relay module with back
box(1.6mm thick RED colour) operating at 24V DC, 2A, rated at 230V, provided with DPDT contact. with required
fixing accessories, AC/AHU TRIPPING/ Pressurization fans/Lift
Addressable Electronic Hooter cum Strobe ceiling mounted. The hooters shall be made of ABS plastic, and have a
DB level of 65dbA and a multi tone facility. Addressable Control Module shall be fitted in a junction box.

SITC of Addressable Manual call point having an integrally mounted addressable module that monitors and reports
contact status. (PULL TYPE) with back box(1.6mm thick RED colour) along with required fixing accessories. The
device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of
the device.

2C x 1.5 mm2, Stranded Copper conductor,Type A ST1 PVC insulated,Armoured FRLS CU Cable 1100 V as per IS
1554, with GI saddle spacers every 0.3 mtr with Single compression Cable Glands,ABS Junction Boxes (wherever
required), terminals,Ferruling complete.

Supplying, installing, testing and commissioning of approved make FRLS PVC conduits on ceiling / wall / floor etc.
complete with accessories like, Junction boxes, Collars, Bends, clamps, saddles etc. (for MCP)

25 mm dia.

Supply and laying of MS Powder coated Trunking 300 x 50 mm x 1.6mm with cover & fixing suppports etc as
required (Cable dressing for Fire & PA panel )

Supply and laying of GI enclosed raceway 300 x 50 mm x 1.6mm with cover & fixing suppports etc as required
(Cable dressing inside the shaft )

SITC of PSU for hooters & AHU tripping (inclusive of Battery ckt & battery)

TOTAL
AMC Cost
Charges for Comprehensive Annual Maintenance Charges for a period of 5 years from the end of Guarantee period.
Vendor to note that all important security upgrades to the software necesiated due to isues in the software itself or
due to upgrades made to OS shall be provided without any additional cost.

I year
II year
III year
IV year
V year
Unit GF MF 1F Total Qty SUPPLY ERECTION

RATE INR AMOUNT INR RATE INR

Lot 1 1 0

Lot 1 0

Nos 1 0

Lot 1 0

Nos 1 0

Nos 1 0

Nos 1 0
Nos 65 20 35 120 0

Nos 65 20 35 120 0

Nos 1 0

Nos 2 2 0

Nos 65 20 35 120 0

Nos 7 3 4 14 0

Nos 2 2 2 6 0

Nos 5 4 4 13 0

Nos 5 5 5 15 0
Nos 11 6 6 23 0

Nos 8 4 4 16 0

Rmt 1950 600 1150 3700 0

Rmt 24 12 12 48 0

Rmt 10 10 0

Rmt 5 5 10 0

Set 3 2 2 8 0

Lot
Lot
Lot
Lot
Lot
AMOUNT INR

0
0

0
0

-
Makes

NOTIFIER /EDWARDS/SIMPLEX/SCHNEIDER/SIEMENS CERBERUS PRO

NOTIFIER /EDWARDS/SIMPLEX/SCHNEIDER/SIEMENS CERBERUS PRO

NOTIFIER /EDWARDS/SIMPLEX/SCHNEIDER/SIEMENS CERBERUS PRO

NOTIFIER /EDWARDS/SIMPLEX/SCHNEIDER/SIEMENS CERBERUS PRO

HP/ DELL

NOTIFIER /EDWARDS/SIMPLEX/SCHNEIDER/SIEMENS CERBERUS

NOTIFIER /EDWARDS/SIMPLEX/SCHNEIDER/SIEMENS CERBERUS


NOTIFIER /EDWARDS/SIMPLEX/SCHNEIDER/SIEMENS CERBERUS

NOTIFIER /EDWARDS/SIMPLEX/SCHNEIDER/SIEMENS CERBERUS

NOTIFIER /EDWARDS/SIMPLEX/SCHNEIDER/SIEMENS CERBERUS

NOTIFIER /EDWARDS/SIMPLEX/SCHNEIDER/SIEMENS CERBERUS

RAVEL/C SYSTEM/AGNI

NOTIFIER /EDWARDS/SIMPLEX/SCHNEIDER/SIEMENS CERBERUS

NOTIFIER /EDWARDS/SIMPLEX/SCHNEIDER/SIEMENS CERBERUS

NOTIFIER /EDWARDS/SIMPLEX/SCHNEIDER/SIEMENS CERBERUS

NOTIFIER /EDWARDS/SIMPLEX/SCHNEIDER/SIEMENS CERBERUS


NOTIFIER /EDWARDS/SIMPLEX/SCHNEIDER/SIEMENS CERBERUS

NOTIFIER /EDWARDS/SIMPLEX/SCHNEIDER/SIEMENS CERBERUS

POLYCAB / VARSHA/ DATA FLEX

VIP/ PRECISION/ASTRA/ANCHOR

FABRICATED

FABRICATED

Battery : Panasonic/Exide/Amaron
PSU : CTEC/CSYSTEM/INSYIN
PROJECT : IIIT , SIRC Building
DOCUMENT : PUBLIC ADDRESS SYSTEM BOQ

SI.No Descriptions Unit

SITC OF PUBLIC ADDRESS SYSTEM

SITC of 6W RMS False Ceiling Mount Speakers with inbuilt 100V Line Matching
Transformer, wide opening angle, optimized for music & speech applications with
1 Nos
mounting clamps as per specifications

SITC of 6W RMS True Ceiling Mount Speakers with inbuilt 100V Line Matching
Transformer, wide opening angle, optimized for music & speech applications with
2 powder coated back box, supports as per specifications Nos
Speakers shall have the tappings at 1.5/3/6 watts

SITC of 6 W Wall Mounted box Speakers with line matching transformers as specified
3 Nos
as per specifications

SITC of 15W bidirectional wall mount wooden speaker with Frequency response of
4 200Hz to 15Khz with SPL sensitivity of 88db @ 1mtr and tapping of 15W/7.5W/3.75W Nos
as specified as per specifications

SITC of System Controller 6 zone controller with 500w inbuilt amplifier complete with
5 Microprocessor based, Dual Tone Control for Speech & Music, with automatic Nos
announcement incase of fire, etc.

6 SITC of 6 zone router with accessories Nos


7 SITC of 6 zone call station with microphone with accessories Nos
8 SITC of 6 zone call station keypad with accessories Nos
9 SITC of Rack Mounted 120 W Power Amplifier Nos
10 SITC of Rack Mounted 240 W Power Amplifier Nos
11 SITC of Rack Mounted 480 W Power Amplifier Nos

2C x 1.5 mm2, Stranded Copper conductor,Type A ST1 PVC insulated,Armoured FRLS


Cable 1100 V as per IS 1554, with GI saddle spacers every 0.3 mtr with Single
12 Rmt.
compression Cable Glands,ABS Junction Boxes (wherever required), terminals,Ferruling
complete.
13 SITC of Volume controller for one speaker (near call station) Nos
14 Rack Mounted DVD Player as per specifications Nos

SITC OF Suitable size rack as per following specification,


Conforms to DIN 41494 Or Equivalent EIA/ISO/EN/CEA Standard
Finish - Powder coated finish with Seven tank pretreatment process meeting ASTM
standard
Color - Black/off white/grey
Fan module on top of the rack
15 Welded frame with vented top cover with fan , perforated Metal Door with lock & Key Lot
and Back vented / Perforated metal door with lock & key and partially vented side
panels, free standing on floor with 4 No. casters wheels with 2 no with brakes & 2 No.
without brakes, cable oraginesers, Levelers with required 16A/5A power strips
including accessories.
Number of racks shall be as per the design requirement. vendor to consider required
number of racks as per their requirement

TOTAL
AMC Cost

Charges for Comprehensive Annual Maintenance Charges for a period of 5 years from
the end of Guarantee period. Vendor to note that all important security upgrades to
the software necesiated due to isues in the software itself or due to upgrades made to
OS shall be provided without any additional cost.

I year Lot
II year Lot
III year Lot
IV year Lot
V year Lot
GF MF 1F Total Qty SUPPLY ERECTION

RATE INR AMOUNT INR RATE INR

65 20 35 120 0

1 0

2 2 2 6 0

4 4 0

1 1 0

0 0
1 1 0
0 0
0 0
1 1 0
1 1 0

1450 450 850 2750 0


1 1 0
1 1 0

1 1 0

1.00
1.00
1.00
1.00
1.00
Makes
AMOUNT INR

0 BOSCH /HONEYWELL /TSG

0 BOSCH /HONEYWELL /TSG

0 BOSCH /HONEYWELL /TSG

0 BOSCH /HONEYWELL /TSG

0 BOSCH PLENA /HONEYWELL INTEVIO /TSG

0 BOSCH PLENA /HONEYWELL INTEVIO /TSG


0 BOSCH PLENA /HONEYWELL INTEVIO /TSG
0 BOSCH PLENA /HONEYWELL INTEVIO /TSG
0 BOSCH /HONEYWELL /TSG
0 BOSCH /HONEYWELL /TSG
0 BOSCH /HONEYWELL /TSG

0 POLYCAB / VARSHA/ DATA FLEX


0 BOSCH/HONEYWELL
0 Philips / Sony / LG / Samsung

0 VALL RACK / MASS RACK

-
PROJECT : IIIT , SIRC Building
DOCUMENT : SIGNAGE SYSTEM BOQ
SI.No Descriptions Unit GF MF

SITC OF SIGNAGE SYSTEM

SITC of LED Configured Emergency Exit SIGNAGE system


1. Recessed Mounting Type
2. LED 5 watts with Rechargeable battery backup of 90 minutes
3. Continously provides illumination through mains power supply
4. Suitable for different types of exit Facia (size 300 L * 150 Ht mm)
5. Refer Image on specification sheet
6. As per IS 9583-1981
7.Photoluminescent & maintained type
8.Suitable for 230v, 50Hz
9.Similar to Prolite PEL LED E/M/P (RM)

1 "FIRE EXIT " (BATTERY BACKED LED SIGNAGE) - SINGLE SIDE Nos 7 2
" Emergency Exit Signages - (Autoglow type) size 150 x 300mm - double
2 Nos 20 15
side with suspension chains (SS)

" EXTINGUISHER Signages - Autoglow, with suspension chains (Autoglo


3 Nos 15 4
signages, size 150 x 300) - double side with suspension chains (SS)

" MCP Signages - Autoglow, with suspension chains (Autoglo signages, size
4 Nos 8 4
150 x 300 - double side with suspension chains (SS)

" Hydrant - Autoglow, with suspension chains (Autoglo signages, size 150 x
5 Nos 2 2
300 - double side with suspension chains (SS)

Fire Evacuation Route Map as per following specification


Preparation of drawing and providing, Autoglow Fire escape route map in
clear acrylic glass and required glass studs supports etc. Indicating
direction, Key plan, contact numbers etc. (The sample of the same need to
6 be presented for approval before execution)…. (Maximum size of the Nos 3 2
board A3)
Evacuation plan shall be glow in dark.
A3 size with 5mm thick rear & 3mm thick front acrylic cover including wall
mount supports.

TOTAL
AMC Cost
Charges for Comprehensive Annual Maintenance Charges for a period of 5
years from the end of Guarantee period.
I year Lot
II year Lot
III year Lot
IV year Lot
V year Lot
1F Total Qty SUPPLY ERECTION
RATE INR AMOUNT INR RATE INR AMOUNT INR

2 11 0 0

20 55 0 0

7 26 0 0

4 16 0 0

2 6 0 0

2 7 0 0

- -
Makes

PROLITE/AUTOGLOW/Technoware

PROLITE/AUTOGLOW/Technoware

PROLITE/AUTOGLOW/Technoware

PROLITE/AUTOGLOW/Technoware

PROLITE/AUTOGLOW/Technoware

PROLITE/AUTOGLOW/Technoware
PROJECT : IIIT , SIRC Building
DOCUMENT : FIRE EXTINGUISHER SYSTEM BOQ
SI.No Descriptions

SITC OF FIRE EXTINGUISHER

CO2 type Fire Extinguisher ISI marked confirming to IS:15683 latest. Capacity 4.5 Kg.
Complete with delivery hose horn, squeeze grip release valve, locking
arrangement,operating temperature -30°C to +55°C, supplied with body bearing IS 7285
1 mark and approved by CCoE tested at 250 kgf/cm2., fitted with ISI marked & CCoE approved
valve as per IS 3224. CO2 Gas as per IS: 15222. externally painted with PO Red Shade No.
538 of IS 5, operation manual and floor stand or Wall Mount Bracket including accessories
as required as per site condition

Powder Fire Extinguisher (Stored Pressure type) (Powder pressurized with dry nitrogen gas
at 15 bar.) capacity: 4kg duly ISI marked conforming to IS: 15683:2006/latest, with IS 14609
ISI marked ABC powder complete with squeeze grip release valve, discharge pipe, locking
2 arrangement, pressure gauge, operation manual,Body Hydrotested at 35 bar, Operating
temperature -30°C to +55°C, external epoxy powder coating with PO Red Shade No. 538 of
IS 5, and floor stand or Wall Mount Bracket including accessories as required as per site
condition

Clean Agent (Stored Pressure) Type Fire Extinguisher Complete with squeeze grip release
valve, locking arrangement, pressure gauge, operation manual, bracket with two screw and
3
sleeve filled with FE36/HFC- 236 FA . Complete in all respect, Capacity 4 Kg. with Floor
mounting bracket with four leg or Wall Mount Bracket. ZERO ODC

FE36 Automatic ceiling Mounted Clean agent Extinguisher - 10 Kg with Ceiling mount
4 accessories including nozzle(57 deg), pressure guage. ISI approved - UPS, Battery,Server
room & Hub room

FE36 Automatic ceiling Mounted Clean agent Extinguisher - 5 Kg with Ceiling mount
5 accessories including nozzle(57 deg), pressure guage. ISI approved - UPS, Battery,Server
room & Hub room
Wet chemical stored pressure 6Ltr capacity including accessories, pressure guage and floor
6
mounting accessories (kitchen - preparation area)
Fire buckets round bottom type enamel painted, white inside & Red out side and Letter
7
"FIRE" in black out side and handle with mounting bracket.
Fire bucket stand fabricated by MS angles to install 4 Nos. of buckets including rain top
8
cover .
TOTAL
AMC Cost
Charges for Comprehensive Annual Maintenance Charges for a period of 5 years from the
end of Guarantee period.
I year
II year
III year
IV year
V year
Unit GF MF 1F Total Qty SUPPLY ERECTION
RATE INR AMOUNT INR RATE INR

Nos 2 2 2 6 0

Nos 15 4 7 26 0

Nos 1 1 2 0

Nos 1 1 2 0

Nos 1 1 2 0

Nos 1 1 2 0

Nos 1 1 2 0

Nos 1 1 2 0

Lot
Lot
Lot
Lot
Lot
ERECTION
Makes
AMOUNT INR

0 MINIMAX/KANEX

0 MINIMAX/KANEX

0 MINIMAX/KANEX

0 MINIMAX/KANEX

0 MINIMAX/KANEX

0 MINIMAX/KANEX

You might also like