METSO DNA HARDWARE

- ACN CS AND DIGITAL MODULES


ACN I/O units M120 series

I/O Power Supply I/O Bus Controller I/O Units


IPSP IBC

Connector with cables to terminal


blocks
ACN I/O UNITS M120 SERIES
ACN I/O UNITS M120 SERIES
ACN I/O UNITS M120 SERIES
Analog units, 1500 VAC Digital units Other units , 1500 VAC
isolation between channels DII8P24, DII8P48 isolation between channels
-8 digital input channels
- Self-powered short-circuit
AII8C protected,opto-isolated,
- 8 analog input channels FII4V
PNP input (24 or 48 VDC)
- voltage supply to transmitters - 4 channel frequency inputs
- I/O channels have common ground
- 0/4 - 20 mA - 0 - 400 kHz
DII4U120, DII4U240 - 24V P-type pulse inputs
AII8CN -4 digital input channels
- 8 analog input channels TII4W3, TII4W4
- Potential free full wave rectified digital inputs
- no voltage supply to transmitters - 4 channel temperature input unit for RTD
for 120 or 240 VAC inputs
- 0/4 - 20 mA (PT-10, PT-100,PT-1000)
- 2200 VAC isolation between channels
- 3 wire or 4 wire connection
AII8V DII8U120, DII8U240
- 8 analog input channels -8 digital input channels TCI8
- 0/1 - 5 V - Potential free full wave rectified digital inputs - 8 channel temperature input unit for
for 120 or 240 VAC inputs thermocouples
AII4H - 1500 VAC isolation between the unit and the - 2 wire connection
- 4 analog input channels system -Thermocouples supported : J, K, T, E, S, R,
- 0/4 - 20 mA HART B, N, G, C, D, Platinel II and EMF
DII4U125
AOI4C -4 digital input channels
- 4 analog output channels - Potential free/polarity free digital inputs for
- 0/4 - 20 mA 125 VDC inputs
- 2200 VAC isolation between channels
AOI4H
- 4 analog output channels DOI4RO
- 0/4 - 20 mA HART - 4 digital output channels
-Single pole, closing contact,polarity free
3.0-5.0 A//120-240 VAC or 0.3-5 A/ 24-125 VDC
- 2200 VAC isolation between channels
ACN SR1, Small Rail
DOI8RO
mounted controller
- 8 digital output channels - Application compatible to other
-Single pole, closing contact,polarity free
1.0 A//120-240 VAC or 0.3-3.0 A/ 24-125 VDC
ACN
- 1500 VAC isolation between the unit and the - max. 2 I/O groups / SR1 controller
system

IBC, I/O Bus Controller IPSP, I/O Power Supply


-Connects I/O group to ACN -Power supply for I/O group
-max. 32 I/O units / IBC controller -max. 32 I/O units / IPSP
ED69235DO51A (DOI4RO)

 Digital Output Unit with 4


channels.
 Potential free electromechanical
relay output.
 Normally open contacts.

Field Interfaces:
• Load voltage 120 VAC 240 VAC 24 VDC 48 VDC 125 VDC
• Load current, resistive <5,0 A <5,0 A <5,0 A <0,7 A <0,3 A
• Output update interval 1.0 ms
• Isolation to system 1500 VAC / 60 s
• Isolation between channels 2200 VAC / 60 s
ED69235DO51A (DOI4RO)

Structure / Digital Units


• CPU (AT89C51RB2) and Interfaces
– RS485
– LED driver
– Watchdog
– Card address
– Product ID
– Digital Interface
• Backplane Connectors
– X1: MBI8 Logic
– X2: MBI8 Power
• Frontplane Connector and LEDs
– X3: I/O Connector
– 4 yellow leds
ED69235DO51A (DOI4RO)

DOI4RO output circuit

DOI4RO signal lights


• Yellow led for every channel
• Continuous yellow: output is in state ‘1’
• When all signal lights change their status temporarily at a
frequency of approximately 1 Hz, the unit's communication
connection to the process control server is broken.
ED69235DO51A (DOI4RO)
Front Panel
Digital units have yellow
LEDs to indicate channel
logic state (LED on = ‘1’)

I/O CONNECTOR
DOI4RO

Pin Signal

1 NO0
2 COM0
3 NO1
4 COM1
5 NO2
6 COM2
7 NO3
8 COM3
ED69235DO51A (DOI4RO)

DOI4RO ISOLATION
ED69235DO52A (DOI8RO)
 Digital Output Unit with 8
channels.
 Electromechanical relay output.

 Normally open contacts.


ED69235DO52A (DOI8RO)
 Digital Output Unit with 8
channels.
 Electromechanical relay output.

 Normally open contacts.

Technical Specification
Output voltage 0..125 VDC, 0…240 VAC
Load voltage 120 240 +24 +48 +125
VAC VAC VDC VDC VDC
Load current resistive < 1,0 A < 1,0 A < 1,0 A < 0,7 A < 0,3 A
Number of channels 8
Isolation between channels ---
Isolation between channels 1500 VAC/60 s
and system
Update interval 1.0 ms
ED69235DO52A (DOI8RO)
Front Panel
I/O
CONNECT
OR
Digital units have DOI8
yellow LEDs to R
indicate channel O

logic state (LED Pin Signal

on = ‘1’) 1 NO0
2 NO1
3 NO2
4 NO3
5 NO4
6 NO5
7 NO6
8 NO7
9 COM
10 COM
ED69235DO52A (DOI8RO)
Isolation
ED69235DO52A (DOI8RO)
CHANNEL DESCRIPTION
ED69235DI51A (DII8P24) , ED69235DI52A (DII8P48)

 Digital Input Unit with 8


channels.
 DII8P24 includes a channel
specific +24V DC current-
limited(40mA)voltage supply.
 DII8P48 includes a channel
specific +48V DC current-
limited(40mA)voltage supply.
ED69235DI51A (DII8P24) , ED69235DI52A (DII8P48)

• 8 channel digital input, type 1


• Input impedance 3,5 k (24), 7,0 k (48)
• Channel specific current limit 40 mA
• Field voltage supply [VS] 18…32 VDC (24), 40…58 VDC (48)
• Measuring interval 1,0 ms
• Isolation to system 1500 VAC / 60 s
• Isolation between channels ---
ED69235DI51A (DII8P24) , ED69235DI52A (DII8P48)

DII8P24/48 ISOLATION
ED69235DI51A (DII8P24) , ED69235DI52A (DII8P48)
input circuit

DII8P24/48 signal lights


• Yellow led for every channel
• Continuous yellow: input is in state ‘1’
• When all signal lights change their status temporarily at a frequency
of approximately 1 Hz, the unit's communication connection to the
process control server is broken.
ED69235DI51A (DII8P24) , ED69235DI52A (DII8P48)

Power Supplies

• MBI8 +5 V powers the CPU and related logic

• DII8P uses field power from MBI8 (FP_i) for supplying


the field connection and channel electronics.
ED69235DI54A DII4U125, ED69235DI53A DII4U120,
ED69235DI55A DII4U240

 Digital Input Unit with 4


galvanically isolated channels.
channels.
 DII4U120 : 120VAC full-wave
rectified input channel.
 DII4U240 : 240VAC full-wave
rectified input channel.
 DII4U125 : 125VDC polarity free
input channel.
ED69235DI54A DII4U125, ED69235DI53A DII4U120,
ED69235DI55A DII4U240

ISOLATION
ED69235DI54A DII4U125, ED69235DI53A DII4U120,
ED69235DI55A DII4U240
Input circuit

DII4U125/120/240 signal lights


• Yellow led for every channel
• Continuous yellow: input is in state ‘1’
• When all signal lights change their status temporarily at a
frequency of approximately 1 Hz, the unit's communication
connection to the process control server is broken.
ED69235DI56A DII8U120, ED69235DI57A DII8U240

o DII8U120 from the M120 series


of the ACN I/O product family is
a digital input unit with eight
galvanically isolated 120VAC
full-wave rectified input
channels
o DII8U240 unit has eight
galvanically isolated 240 VAC
full-wave rectified input
channels.
ED69235DI56A DII8U120, ED69235DI57A DII8U240
ISOLATION
ED69235DI56A DII8U120, ED69235DI57A DII8U240
ED69235DI56A DII8U120, ED69235DI57A DII8U240
ED69235FI51A FII4
 Has 4 channel frequency and
pulse input unit.
 Channels have +24V voltage
supplies.
ED69235FI51A FII4

FII4 ISOLATION
ED69235FI51A FII4
FII4 signal lights
• 6 Red, 8 yellow and 2 red/yellow leds
• Yellow leds S0…S3 lights for 200 ms when channel
in questions has received rising pulse edge

• Red leds TF0…TF3 alerts


- in pulse mode when channel receives no more
pulses

•Red leds LF0/1…LF2/3 lights if there is overloading

•Red/yellow DI/DO
-Doesn’t light: state is ‘0’
-Yellow: state is ‘1’
-Red: overloading

•When all signal lights change their status temporarily


at a frequency of approximately 1 Hz, the unit's
communication connection to the process control
server is broken.
ACN CS – EMBEDDED INDUSTRIAL
CONTROLLER
 ACN CS is a high performance multifunction
controller.
 Fast control cycles as low as 20ms

 No moving parts(no fan nor hard disk)

 IP20 enclosure protection.

 One to one redundancy capability.

 Removable Compact Flash


ACN CS
ACN CS- INTERFACES
3 Ethernet ports on CPU
Redundant Metso DNA Ethernet network
Interface with Metso DNA I/O field buses

Two PCI card slots


Profibus DP Interface
Serial Interfaces
Ethernet Interfaces
ACN CS – TECHNICAL SPECIFICATION
 Compact Rack or wall-mounted frame.
 Fanless construction, cooling by heat pipes and a
massive heat sink
 Dimensions:210x87x296mm

 Weight: 4.5kg

 Protection: IP20
ACN CS – TECHNICAL SPECIFICATION
 Main Board: PCI riser 2xPCI
 Memory : 1GB DDR2 667 MHz

 Processor : Intel Celeron M440

 512MB Compact Flash

 Expansion: 2 x PCI

 Operating Temperature : 0°C…+50°C


 Storage Temperature : -20°C ….+60°C

 Operating System : Real Time Operating System


ACN CS - CONNECTORS
 ACN CS ‘s connectors:
 1 x Compact Flash Slot
 2 x PCI card slot
 2 x USB port
 1 x serial Interface port (RS-232)
 Input Voltage 18 to 36VDC.
 1 x alarm input
 1 x PS/2 port for keyboard and mouse
 1 x VGA
 3 x Ethernet port (PB1, PB2, FB1)
ACN CS – LED INDICATIONS
 ACN CS displays its status and fault
information on 2 identical LED cards.
 LED cards are on the front panel and on
frame cover.
 LEDs in use:
 Pwr (Green): LED is ON and steady when
power is switched ON
 Run (Green) : Operating Status indicator.
 PB1 – 2 ( Yellow) : Process Bus Staus.
 FB1 – 3 (Yellow): Field Bus status.

You might also like