Gardtec 370 Engineer
Gardtec 370 Engineer
Gardtec 370 Engineer
GARDINER TECHNOLOGY
Input: Nominal Temp Range:
Introduction
The Gardtec 370 Control Panel is a seven zone microprocessor based unit that has been designed to be suitable for domestic and small commercial installations. All zones are fully programmable by the engineer. Upon completion of the installation the engineer may, if required, re-program several factory set options so as to tailor the Control Panel to suit the requirements of the system. It should be noted that if a new four digit engineer code starts with a 9 it will be locked into the system and may only be changed by using the code again (default to factory settings will have no effect). We recommend that this engineer manual and the user manual are read and fully understood before any installation of the system is carried out.
AC230V +/-10% ~50Hz 200mA Max. 49W Max 0 - 50C Gardtec 370 Range Metal Versions For Indoor Use Only Gardtec 370 Range Plastic Versions For Indoor Use Only
This equipment is intended only for use as a Security Alarm Control Panel. Adequate ventilation away from heat and humidity must be provided. The unit must be fixed securely to a non-flammable surface using suitable fixings. All mains wiring must be to BS7671 (1992) IEEE wiring regulations (or appropriate international regulatory standards). See Mains Supply Connection section within this manual for more detailed instructions. All wiring must be protected from sharp or jagged edges. All Low voltage (alarm) wiring must be to the appropriate international regulatory standards and comply to good wiring practice. Replacement fuses should be of the same type and rating conforming to IEC 127.
A more detailed description is given in the programmable options description (page 12). Power Supply Rating It should be noted that the Gardtec 370 has 1 Amp available for the full system. Sounders, detectors and other auxiliary items should be included when calculating current drawn by the system. Any damage caused through overloading the Control Panel will not be covered by the warranty. AUX 12V Terminals This pair of terminals supply the + and - supply for the keypads and detectors. 1 Amp is available from these terminals (see power supply rating above). Strobe Terminals This pair of terminals are the output for the Strobe. The negative terminal is switched during an alarm period. A maximum of 1 Amp may be drawn from these terminals (see power supply rating above). Bell Terminals This pair of terminals are the output for the Bell or external sounder. The negative terminal is switched during an alarm period. A maximum of 1 Amp may be drawn from these terminals (see power supply rating above). Page 3
The maximum current draw from the unit for all output combinations must not exceed 1Amp. The unit is intended for use with a suitable re-chargeable lead acid battery permanently connected to the appropriate terminals. All documentation and manuals must be thoroughly read by suitably qualified installation personnel prior to installation. The unit has no user serviceable parts inside. Internal access should only be by suitably qualified personnel. Gardtec 370 Metal Versions The unit must be Earthed. It is the responsibility of the installation engineer to ensure that the earth connection to the unit lid is good on completion of the installation or after service. Gardtec 370 Plastic Versions Provision is provided for an earth connection within the mains input connector block, this connection is for protection of the wiring only and is not functional for the unit. Page 1 PR5032Rev1.0
The Panel should be fixed to the wall using appropriate wall plugs and No.8 screws at least 30mm long. Do not tighten the screws at this stage, wait until all your wiring is in place.
Page 2
Remote Keypads
Up to four remote keypads may be fitted to the GARDTEC 370 control panel. A four core connection will be required between the control panel data port and remote keypad(s), all keypads must be in a 'daisy chain' format as shown in Fig2. below. Note: All RKP models have an EOL jumper with the exception of the 370 model which is supplied with an EOL resistor. If only one RKP is used the jumper or resistor should be fitted in that RKP. If more than one RKP is used the jumper or resistor should only be fitted to the last RKP in the line. When using RKPs fitted with an Entry/Exit zone only one may be used irrespective of the number of RKPs fitted. This RKP zone will be Entry/Exit with Chime allocated and will be indicated on the display as r1.
Initial Power Up
When the Control Panel is powered up it will be either set or unset dependent on the state of the Control Panel when it was powered down. The factory default state will be unset.
As power is applied all segments of the twin seven segment display will be lit for approx six seconds. During this period press 4 6 YES NO to ensure that the Control Panel is at factory settings. The display will then show set or unset.
Note:
Note: ProDigi EOL jumper must be OFF ProDigi 580 SEL jumper must be ON ProDigi Communicator + AUX 12V
Novagard 1E
Gardtec 370
OUT IN DATA
D IN D OUT
N/C Devices
N/O Device
TAMP
RKP 1
TMP+ E/E-
The Control Panel is now back to factory defaults. Note: The two methods shown above will have no effect on the engineer code if it started with a '9'. If this is the case, only re-use of the programmed engineer code will allow it to be changed.
N/C Tamper
AZ1
SAB TAMP
AUX 12V
STROBE
12V 0V
AUX 12V
BELL HOLD-
E/E+
N/C Devices
N/O Device
OUT IN
DATA
D IN D OUT
AZ2
+ +
N/C Devices
N/O Device
+
AZ3
System Programming
The system may be programmed by the engineer by use of the engineer code (1234 factory default). Other Engineer/User functions are also available to the engineer, these are as follows. Set Chime Unset Remove Test Log
N/C Devices
N/O Device
+
AZ4
Note: If 370 RKP is used 680 ohm resistor should be fitted between 12v & D IN terminals on last RKP
+
AZ5
Note:
16 Ohm Min
Strobe Light
0V Tamp Ret
N/O Device
N/C Devices
Note: Details of the above functions are given in the User Manual. Program Engineer Code Programming of the Engineer Code is only possible via the Engineer Code (e.g 1234). See Engineer Programming Flow Chart (overleaf). Page 7
AZ6
+
AZ7
IMPORTANT:
Page 5
Page 6
MENU No 1
FUNCTION
OPTIONS AVAILABLE RIGHT DIGIT 0=Full Set 1=Part1 2=Part2 3=Part1&2 4=Full Set+Chime 5=Part1+Chime 6=Part2+Chime 7=Part 1&2+Chime
DEFAULT 14
System is Unset
Enter Engineer Code Press 0 (Quit) Press NO Press YES Press NO Press 0 (Quit)
Zone1 Attributes LEFT DIGIT 0=12Hr 1=E/E 2=Access 3=Panic 4=24Hr 5=Fire 6=Alert 7=Exit Term 8=Part E/E Zone 2 Attributes Zone 3 Attributes Zone 4 Attributes Zone 5 Attributes Zone 6 Attributes Zone 7 Attributes Sounder Level
MENU No 12
FUNCTION
OPTIONS AVAILABLE PROGRAMMABLE OUTPUT1 PGM1 RIGHT DIGIT 0=Pulse On 1=SW+ 2=Pulse Off 3=Bell 4=Strobe 5=Entry/Exit 6=Test 7=Int. Alarm
DEFAULT 31
Part Set Sounders PART & Output 1 Mode SOUNDERS LEFT DIGIT 0=All Parts silent 1=Part 2 silent 2=Parts1&3 silent 3=All Parts Audible
2 3
As Zone1 Options As Zone1 Options As Zone1 Options As Zone1 Options As Zone1 Options As Zone 1 Options CHIME LEFT DIGIT 0-9 ENTRY/EXIT RIGHT DIGIT 0-9
80 13 00 14 Entry Time 2 Keypad 00 - 99seconds ALERT KEYS 1&3 LEFT DIGIT 0=Off 1=Panic 2=Fire 3=Alert 10 10 RIGHT DIGIT Always 0 01 15 02 00 30 55 16 17 18 Bell Re-Arms Bell Ring Time Bell Delay Bell Mode Entry Time 1 00 - 99seconds 30
4 5
6 7
00 Re-Arms - 99 Re-Arms 00 minutes - 99 minutes 00 minutes - 99 minutes BELL TYPE LEFT DIGIT 0=SAB 1=SCB 00=Audible PA TAMPER RING RIGHT DIGIT 0=Off 1=On 10=Silent PA RESET MODE RIGHT DIGIT 0=Any Code 1=Master Code 2=Anti-Code 3=Engineer Code 99 = Off
99 20 00 00
9 Press NO 10
Full Set Exit Time Part Set Exit Time Setting Modes FULL SET LEFT DIGIT 0=Exit Term 1=E/E Door 2=Time 3=Time+E/E
00 - 99seconds 00 - 99seconds PART SET RIGHT DIGIT 0=Exit Term 1=E/E Door 2=Time 3=Time+E/E
11
00 01
Press YES Enter new Engineer Code Press YES Re-Enter Engineer Code Press YES Press 0 to return to Unset Page 8
22
Service Timer
99
Exit Terminator With Panel programmed to set with exit terminator the panel will only set when zone is activated during exit. Page 11
Bell Mode (Option No.19) The Bell Mode Function allows the mode of the Bell to be programmed from SAB to SCB. In SAB mode the current for the sounder is supplied from the Control Panel unless the cable to the Bell box is cut. In SCB mode the current for the sounder is supplied by the sounder battery under all circumstances. The Bell Tamper mode if programmed ON will always trigger the external sounder from the control panel in the event of a Bell Tamper. Reset Modes (Option No.21) The reset modes are programmed using this function. Service Timer (Option No.22) The service timer period is programmed using this function. When service time expires the system will lock the user out. Extra service may be gained using the Anti-Code software. If the timer is set to 99 weeks the timer function is Off.
Display Messages (Log) Apart from the System and Status displays the following messages may also appear whilst viewing the Log. 'S 'S ' ' System Full Set System Part 2 Set Unset User 1 Unset User 3 Unset User 5 Unset User 7 Unset User 9 Alarm has occurred 'S 'S ' ' System Part 1 Set System Part 3 Set Unset User 2 Unset User 4 Unset User 6 Unset User 8 Unset User 0 (Engineer) Watchdog reset
Other Accessories
A complete range of accessories are available to complement your Gardtec 370 security system. Some of this range is shown below:-
(01-087)
' o1 ' ' o3 ' ' o5 ' ' o7 ' ' o9 ' ' AL '
' o2 ' ' o4 ' ' o6 ' ' o8 ' ' o0 ' ' rE '
(02-064) (04-069)
Display Messages
The Following System messages are possible.
The Gardtec Speech Dialler offers communications between your security system and any telephone or selected pagers. One Common message along with three Information messages may be programmed to be sent to up to four telephone numbers. The unit offers a full range of programmable features to ensure your message gets across.
' 1 to 7 ' (flashing) '1 to 7' 't' 'E 'E ' ' ' ' ' ' Represent zones 1 to 7 Tamper zone System Part 1 Setting System Part 3 Setting System Fully Set System Part 2 Set An Alarm has occurred Fuse Fail or Battery Fault Bell box Tamper Control Box Tamper Phone Line or Digi Fault Engineer Reset required (or Service Timer activated). 'E 'CA' 'E Un' ' ' 'Ac' 'Ct' 'Pc' 'r1' ' ' ' ' System Full Setting Alert keys activated System Part 2 Setting System is Unset System Part 1 Set System Part 3 Set Anti-Code reset required RKP Tamper Mains Power Cut Keypad Zone Complies with Number of Zones Display Type User Code Default Engineer Code Default Event Log Size No. of User Codes No. of Part Sets
ProDigi Communicator ProDigi AV Communicator ProDigi AV Serial Communicator Additional RKPs Gardtec 370 LED RKP Gardtec 370/580 LED RKP Gardtec 370/580 Contour LED RKP Gardtec 370/580 Profile LED RKP ACE RX ACE TX (Key Fob) *Include RKP Zone
Up to four RKPs may be fitted to the Gardtec 370 Control Panel. ACE offers Setting, Unsetting, Part Setting & Resetting via high security Infra-Red keyfobs. ACE is available as compact stand alone units which are fully compatible with the Gardtec 370 Control Panel. Page 15
Page 12
Page 13