Introduction
CDROM includes system program installation program to update or to recover your Programmable
Terminal (PT).
Please follow the instruction below just in case when System Program Ver.8.9 is corrupted or
the System Program in the PT is Ver.4.x, Ver.5.x, Ver.6.x, Ver.7.x or Ver.8.x.
This program can be used for the all models listed below. Therefore, the following operations are also
common to the all models.
-NS15-V2, NS12-V1/V2, NS10- V1/V2, NS8- V1/V2 and NS5- V1/V2
-NSJ12, NSJ10, NSJ8 and NSJ5
-NSH5
In this manual PT indicates the models of NS-series listed above unless otherwise noted.
NOTE
Do NOT use this program for NS12/10/7, which does not have –V1 or
Contents
Introduction...............................................................................................................................................1
1. Preparations Before Updating or Recovering .......................................................................................2
2. Process for Updating or Recovering the System Program ...................................................................5
3. Confirmation after Updating or Recovering ........................................................................................ 11
4. Troubleshooting ..................................................................................................................................13
5. About Memory Cards ..........................................................................................................................14
6. Using Old Version of Recover/Update Program .................................................................................15
-1-
1. Preparations Before Updating or Recovering
A Memory Card (50MB or over) is required to perform this program. Please prepare the Memory
Card beforehand. Please note that operation will not be properly performed with a Memory Card that
was formatted using Windows. Refer to the Section 5 for details on using a Memory Card.
Note: If the touch screen has no input within 20 seconds, it proceeds the program regarding as the
Overwrite Installation has been selected.
A Clean Install will automatically run without showing an Install Instruction Selection Screen. When
the version of the project data in the NS Hardware are higher than the system version you are going
to install with the Update/Recover program.
Example:
A Clean Install will automatically run under such a combination as below.
Update/ Recover program Ver.5.0
Project in the NS Hardware Ver.6.0
-2-
Execute RecoverUpdate_[]_[][].exe.
Double click the exe module and extract the compressed data. Folder will be newly created. The following
figure shows in the case you decompressed on C:\NSV8.
Copy all those modules under the root of the Memory Card. The following figure shows in the case the
Memory Card is assigned to E:drive.
Preparation completed. Safely remove your Memory Card from your personal computer.
1.2 Step2: How to place the Memory Card in the PT and execute the program.
1. Pull out all communications cable connected to the PT.
2. Place the Memory Card in the PT.
3. Turn ON the power to the PT. (If the power is already turned ON, turn OFF the power once, and
turn On again.)
4. The program will be started approx. 10 seconds later.
- Installation program will not start in case the PT does not recognize the Memory Card. Check whether
the Memory Card is placed in the connector. Refer to the Section 5 for more details.
-3-
1.3 Step 3: Select installation method.
Select Clean Installation or Overwrite Installation according to the followings.
-4-
Press Start button at the right of each explanation.
If the touch screen has no input within 20 seconds, it proceeds the program regarding as the
Overwrite Installation has been selected.
-5-
The following shows # which indicates Japanese fonts.
----------------------------------------------------------
System Update/Recover Program Ver.8.9
----------------------------------------------------------
Now Checking Screen Data Area
########################
Now Formatting Screen Data Area
Flashes ########################
Now Checking System Program Area
###########################
Now Formatting System Program Area
#############################
Check & Format Phase : END
######################
----------------------------------------------------------
System Update/Recover Program Ver.8.9
----------------------------------------------------------
Now Checking Screen Data Area
#########################
Now Formatting Screen Data Area
Flashes #########################
Now Checking System Program Area
###########################
Now Formatting System Program Area
#############################
Check & Format Phase : END
######################
-6-
2.1.3 Updating the Operating System
Update the operating system.
When updating the operating system is completed, “OS Update Phase: END” is displayed as shown
below.
----------------------------------------------------------
System Update/Recover Program Ver.8.9
----------------------------------------------------------
Now Checking Screen Data Area
########################
Now Formatting Screen Data Area
Flashes ########################
Now Checking System Program Area
###########################
Now Formatting System Program Area
#############################
Check & Format Phase : END
######################
Flashes
-7-
2.1.4 Initializing Log Data and Program Termination
Initializing log data is immediately completed and “Log Data Clear Phase: END” is displayed as
shown below.
Message “Please switch OFF “ appears after all processes are completed normally. Then, the
indicator flashes green.
Turn OFF the power of the PT and safely remove the Memory Card.
----------------------------------------------------------
System Update/Recover Program Ver.8.9
----------------------------------------------------------
Now Making Backup Copy of Setting Files
##########################
Flashes Now Checking System Program Area
###########################
Now Formatting System Program Area
#############################
Check & Format Phase : END
######################
-8-
2.2.2 Downloading the System Program
Download the system program.
When downloading the system program is completed, “System Program Download Phase: END” is
displayed as shown below.
----------------------------------------------------------
System Update/Recover Program Ver.8.9
----------------------------------------------------------
Now Making Backup Copy of Setting Files
######################
Flashes
Now Checking System Program Area
###########################
Now Formatting System Program Area
#############################
Check & Format Phase : END
#####################
----------------------------------------------------------
System Update/Recover Program Ver.8.9
----------------------------------------------------------
Now Making Backup Copy of Setting Files
######################
Flashes Now Checking System Program Area
###########################
Now Formatting System Program Area
##############################
Check & Format Phase : END
######################
-9-
OS Update Phase : END
################################
Flashes
- 10 -
3. Confirmation after Updating or Recovering
REMOVE the memory card and turn ON the power to the PT after terminating the program.
Please check the points as shown below.
3.1 The Version of Operating System
Welcome to NS Series!
Version:3.19
Hardware Devices : OK
As the image above shows, the version of system program is displayed in the second line after
turning ON the power. Confirm that the version is changed to 3.19 (See note.).
Note: In the case of NS5-[]Q0[]-V2, NSJ5-[]Q0[], NSH5-SQ[]0[]-V2, V1 Series, confirm that the
version is changed to 3.14.
- 11 -
3.2 The Version of System Program
Go to the system menu and select System Version in the Special Screen tab. Check whether it
shows Version 8.98.
<NS15/12/10/8/5, NSH5>.
System Version
Back
<NSJ12/10/8/5>.
System Version
NSJ5_SQ01_G5D
Controller
Unit Version 3.0
Display
System Version 8.98
Project Data Version [].[]
Back
- 12 -
4. Troubleshooting
The possible error symptoms while executing the program and countermeasures are described.
Symptom Cause Countermeasure
The indicator lights Model type information Contact your nearest OMRON
red and the program registered in the PT cannot be representative.
does not start. read.
The indicator flashes Backlight has malfunctioned. Contact your nearest OMRON
green and the buzzer representative.
sounds.
Message “Touch The touch panel is not detected.
Panel Error” is
displayed.
The indicator flashes Failed to download the system Check whether the Memory Card is
red/”ERROR” is program or upload the operating corrupted with a computer and
displayed system. perform update/recovery again.
The indicator flashes The system becomes unstable. Check weather the conditions such as
orange for long time power supply, noise, or temperature
and does not change. are appropriate.
Execute all over again after checking
whether the memory card is corrupted
on a computer.
Started up the upgrading Pull out all the communications cable
program while communicating from the PT and execute all over
with PLC. again.
The indicator turns to The memory card is not Copy the program to another memory
orange but nothing is recognized. card and execute the program.
started. Refer to the Section 5 About Memory
cards for details.
The indicator lights An attempt was made to A program in the Memory Card must
green and the recover/update a system be patched when you recover/update
WARNING No.24 is program earlier than version 8.0 a system program earlier than version
displayed. in the following NS series. 8.0 in the NS-series PTs in the left
NS5-SQ1[]-V2, column.
NS5-TQ1[]-V2, For details on how to patch the
NS5-MQ1[]-V2, program, refer to Chapter 6.
NSJ5-SQ1[],
NSJ5-TQ1[],
NSH5-SQ[]1[]-V2
- 13 -
5. About Memory Cards
This symptom is caused by changing specification of operation system on the computer to support
large capacity hard disk.
- 14 -
6. Using Old Version of Recover/Update Program
If your computer does not have a memory card slot, you can use a USB memory card adapter.
- 15 -
2) Execute the Patch Program “CFPATCH”
To patch, use the CFPATCH.EXE. When you need CFPATCH.EXE, contact our sales office.
Execute CFPATCH.EXE. The patch program will start and the following dialog will be displayed.
Select any of the following patch methods and click Patch Button.
1. Patching the program in the Memory Card (default).
A Recover/Update Program in the Memory Card will be directly patched.
Specify the drive for the Memory Card that you set in the step 1).
2. Patching the Recover/Update Program in the personal computer.
A folder list of the Recover/Update Program will be displayed in the center of the window. Select a
Recover/Update Program you want to patch.
3. Directory specifying a folder in which the Recover/Update Program is stored.
A Recover/Update Program, not stored in the standard installation folder, will be patched. Click Patch
Button. The Browse for Folder will be displayed. Select an appropriate folder.
- 16 -
6.4 Patch Program Dialog Boxes and Countermeasures
The system program version in the PT is earlier than 4.0 (PT model number without –V or –V suffix.).
Patch is not necessary.
- 17 -
Cannot patch because the specified drive or folder is write-protected. Check the property.
Cannot patch because the capacity of the specified drive or folder is insufficient, or the drive or folder is
write-protected. Check the capacity of the file or folder, and the property.
When Recover Update Program Folder option is selected, the Patch Button is clicked without any
folder being selected.
Select a folder for patch (Select a checkbox).
- 18 -